36
Operating instructions 1987765448/09.2014, Replaces: 02.2006, EN Bus coupler CMS, M-Design DeviceNet English

Bus coupler CMS, M-Design, DeviceNet

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Bus coupler CMS, M-Design, DeviceNet

Operating instructions

1987765448/09.2014, Replaces: 02.2006, EN

Bus coupler CMS, M-Design

DeviceNet

Engl

ish

Page 2: Bus coupler CMS, M-Design, DeviceNet
Page 3: Bus coupler CMS, M-Design, DeviceNet

Contents

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 3

Engl

ish

Contents

1 About This Document .................................................... 5

1.1 Documentation validity ............................................................5

1.2 Required and supplementary documentation ..................5

1.3 Presentation of information ...................................................5

1.3.1 Safety instructions .................................................................. 6

1.3.2 Symbols ...................................................................................... 7

1.4 Abbreviations used ...................................................................7

2 For your safety .............................................................. 7

2.1 About this chapter .....................................................................7

2.2 Intended use................................................................................8

2.3 Improper use ..............................................................................8

2.4 Personnel qualifications..........................................................9

2.5 General instructions .................................................................9

2.6 Safety instructions related to the product

and technology ........................................................................ 10

3 System architecture ................................................... 11

3.1 Construction and design....................................................... 13

3.2 Function..................................................................................... 13

4 Configuration ............................................................... 14

4.1 Presettings ............................................................................... 14

4.1.1 Setting the baud rate ........................................................... 15

4.1.2 Setting the bus coupler participant's address ............ 15

4.1.3 Setting the operating mode of the 32 I/O box .............. 16

4.2 Valve system configuration ................................................. 17

4.2.1 Electronic Data Sheet (EDS) .............................................. 17

4.2.2 Configuration using the DeviceNet manager

(from Allen-Bradley) ............................................................ 17

5 Assembly ..................................................................... 25

5.1 Labeling the module .............................................................. 25

5.2 Connecting the bus coupler electrically .......................... 25

5.2.1 Field bus connection ............................................................ 25

5.2.2 Connecting the bus coupler logic .................................... 29

5.2.3 and load supply ..................................................................... 29

6 Bus coupler diagnostics display ................................ 31

Page 4: Bus coupler CMS, M-Design, DeviceNet

Contents

4 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

7 Disassembly/exchange .............................................. 32

7.1 Exchanging the bus coupler ................................................ 32

7.2 Replacing fuses....................................................................... 33

8 Technical Data ............................................................. 35

8.1 Characteristics ........................................................................ 35

9 Service parts and accessories .................................. 35

Page 5: Bus coupler CMS, M-Design, DeviceNet

About This Document

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 5

Engl

ish

1 About This Document

1.1 Documentation validity

These instructions contain important information on the safe

and appropriate assembly, operation, and maintenance of the

bus coupler and how to remedy simple malfunctions yourself.

O Read these instructions completely, especially chapter 2

“For your safety”, before working with the bus coupler.

1.2 Required and supplementary documentation

O Only commission the product once you have obtained the

following documentation and understood and complied with

its contents.

Further information on the components can be found in the

online catalog at www.aventics.com/pneumatics-catalog.

1.3 Presentation of information

To allow you to begin working with the product quickly and

safely, uniform safety instructions, symbols, terms, and

abbreviations are used in this documentation. For better

understanding, these are explained in the following sections.

Table 1: Required and supplementary documentation

Title Document number Document type

Documentation for the valve system HF02/HF03

1987765472 Instructions

System documentation

Page 6: Bus coupler CMS, M-Design, DeviceNet

About This Document

6 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

1.3.1 Safety instructions

This documentation contains safety instructions before any steps

that involve a risk of personal injury or damage to property. The

measures described to avoid these hazards must be observed.

Safety instructions are set out as follows:

W Safety sign: draws attention to the hazard

W Signal word: identifies the degree of hazard

W Hazard type and source: identifies the hazard type and source

W Consequences: describes what occurs when the safety

instructions are not complied with

W Precautions: states how the hazard can be avoided

SIGNAL WORDHazard type and source

Consequences

O Precautions

Table 2: Hazard classes according to ANSI Z 535.6-2006

Safety sign, signal word Meaning

DANGER

Indicates a hazardous situation which, if not avoided, will certainly result in death or serious injury.

WARNING

Indicates a hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION

Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

NOTICEIndicates that damage may be inflicted on the product or the environment.

Page 7: Bus coupler CMS, M-Design, DeviceNet

For your safety

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 7

Engl

ish

1.3.2 Symbols

The following symbols indicate information that is not relevant

for safety but that assists in comprehending the documentation.

1.4 Abbreviations used

2 For your safety

2.1 About this chapter

The product has been manufactured according to the accepted

rules of safety and current technology. There is, however, still a

danger of personal injury or damage to equipment if the

following general safety instructions and the warnings before

the steps contained in these instructions are not complied with.

O Read these instructions completely before working with the

product.

Table 3: Meaning of the symbols

Symbol Meaning

If this information is disregarded, the product cannot be used or operated optimally.

O Individual, independent action

1.

2.

3.

Numbered steps:

The numbers indicate sequential steps.

Abbreviation Meaning

BDC Bus Direct Control

DDL Drive & Diagnostics Link

CMS Central Mounted System

VS Valve system

GSD General Station Description

EP end plate End plate with electrical and pneumatic connections

P end plate End plate with pneumatic connections

PLC Programmable Logic Controller

PGND Protective Ground

Page 8: Bus coupler CMS, M-Design, DeviceNet

For your safety

8 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

O Keep these instructions in a location where they are

accessible to all users at all times.

O Always include the bus coupler operating instructions when

you pass the product on to third parties.

2.2 Intended use

The product is an electropneumatic system component.

The product may be used as follows:W only for industrial applications

W only within the performance range provided in the technical

data

The product is intended for professional use only.Intended use includes having read and understood this

documentation, especially the chapter “For your safety”.

2.3 Improper use

Any use other than that described under Intended use is

improper and is not permitted.

The installation or use of unsuitable products in safety-relevant

applications can result in unanticipated operating states in the

application that can lead to personal injury or damage to

equipment. Therefore, only use a product in safety-relevant

applications if such use is specifically stated and permitted in

the product documentation. For example, in areas with

explosion protection or in safety-related components of control

systems (functional safety).

AVENTICS GmbH is not liable for any damages resulting from

improper use. The user alone bears the risks of improper use of

the product.

Improper use of the product includes:

W changing or conversion of the product,

W use for any application not stated in these instructions, or

W use under operating conditions that deviate from those

described in these instructions.

Page 9: Bus coupler CMS, M-Design, DeviceNet

For your safety

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 9

Engl

ish

2.4 Personnel qualifications

Assembly, disassembly, commissioning and operation require

basic electrical and pneumatic knowledge, as well as knowledge

of the applicable technical terminology. Assembly, disassembly,

commissioning, and operation may therefore only be carried out

by qualified electrical or pneumatic personnel or an instructed

person under the direction and supervision of qualified personnel.

Qualified personnel are those who can recognize possible

hazards and institute the appropriate safety measures, due to

their professional training, knowledge, and experience, as well

as their understanding of the relevant conditions pertaining to

the work to be done. Qualified personnel must observe the rules

relevant to the subject area.

2.5 General instructions

W Observe the regulations for accident prevention and

environmental protection.

W Observe the safety instructions and regulations of the

country in which the product is used or operated.

W Only use AVENTICS products that are in perfect working order.

W Follow all the instructions on the product.

W Persons who assemble, operate, disassemble, or maintain

AVENTICS products must not consume any alcohol, drugs,

or pharmaceuticals that may affect their ability to respond.

W To avoid injuries due to unsuitable spare parts, only use

accessories and spare parts approved by the manufacturer.

W Comply with the technical data and ambient conditions

listed in the product documentation.

W If unsuitable products are installed or used in safetyrelevant

applications, this may result in unintended system

operating states that may lead to injuries and/or equipment

damage. Therefore, only use a product in safety-relevant

applications if such use is specifically stated and permitted

in the product documentation.

Page 10: Bus coupler CMS, M-Design, DeviceNet

For your safety

10 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

W You may only commission the product if you have determined

that the end product (such as a machine or system) in which

the AVENTICS products are installed meets the country-

specific provisions, safety regulations, and standards for the

specific application. A 24 V power pack supplies all

components with electricity. The power pack must be fitted

with a safe isolation in accordance with EN 60742, VDE 0551

classification. The corresponding electrical circuits are thus

SELV/PELV circuits in accordance with DIN EN 60204-1.

2.6 Safety instructions related to the product

and technology

W Do not place any mechanical loads on the device under

circumstances. Do not place any objects on it.

W Ensure that the power supply is within the stipulated

tolerance for the modules.

W Observe the safety notes found in your valve system's

operating instructions.

W A 24 V power pack supplies all components with electricity.

The power pack must be fitted with a safe isolation in

accordance with DIN EN 60742, VDE 0551 classification.

This ensures that the electric circuits comply with SELV/

PELV electric circuits in accordance with IEC 60364-4-41.

W Switch off the operating voltage before connecting or

disconnecting plugs.

During assembly W The warranty only applies to the delivered configuration. The

warranty will not apply if the product is incorrectly assembled.

W Make sure the relevant system component is not under

pressure or voltage before assembly or disassembly.

Ensure that the system is prevented from power restoration

during assembly work.

W Ground the modules and valve system. Observe the

following standards when installing the system:

– DIN EN 50178, classification VDE 0160

– VDE 0100

Page 11: Bus coupler CMS, M-Design, DeviceNet

System architecture

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 11

Engl

ish

During commissioning W Installation may only be performed in a voltage-free and

pressure-free state and only by a qualified technician. In

order to avoid accidents caused by dangerous movements

of the actuators, electrical commissioning may only be

carried out in a pressure-free state.

W Do not put the system into operation before it is completely

assembled as well as correctly wired and configured, and

after it has been tested.

W The device is subject to the restrictions of the IP 65

protection class. Before commissioning, make sure that all

the connection seals and plugs are leaktight to prevent

fluids and foreign bodies from penetrating the device.

During operation W Make sure that there is a sufficient exchange of air or

enough cooling if your valve system has any of the following:

– Full equipment status

– Continuously loaded solenoid coils

During cleaning W Never use solvents or strong detergents. Only clean the

device using a slightly damp cloth. Only use water and, if

necessary, a mild detergent.

3 System architecture

The versatility and flexibility of this valve system enables

AVENTICS to support your automation tasks. The valves are

completely assembled and tested according to your

requirements; the electrical connection is made via bus

couplers. The valve system in the local and external pilot control

versions is then ready for use. Its modular construction allows

existing systems to be expanded or converted at any time.

The valve system's operating instructions are composed

of individual components.

Page 12: Bus coupler CMS, M-Design, DeviceNet

System architecture

12 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

Fig. 1: System architecture

Valve systems with

a multiple plug

connector:

W Series HF03/

HF02

W I/O modules

(passive)

Valve systems with a multiple

plug connector:

W Series HF03/HF02

W Bus coupler series BDC

type V-Design:

– PROFIBUS-DP,

– INTERBUS

– DeviceNet,

CANopen type

A-Design:

– AS-Interface

W Modules series

DDL type

V-Design:

– DDL/DDL-E

Valve systems with bus coupler

W Series HF03/HF02

W Bus coupler series CMS type

M-Design: PROFIBUS-DP, INTERBUS,

DeviceNet, CANopen

W I/O modules

W Power module

W AS-Interface Master

Page 13: Bus coupler CMS, M-Design, DeviceNet

System architecture

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 13

Engl

ish

3.1 Construction and design

BUS X71 and BUS X72

2 sockets

Connections for the field bus DeviceNet, for control of valves and

I/O modules.

POWER X10 plug Electrical connection for

W valve solenoids and outputs,

W logic and

W inputs.

Control elements Two 8-position DIL switches for setting the node address, baud rate

and various modes of operation using the PG screw cap S1/S2.

3.2 Function

This field bus connects simple sensors, frequency converters,

barcode readers, pneumatic blocks, etc. to a superordinate

system such as a PLC, PC or similar system.

DeviceNet is based on the CAN bus system and represents layer 7

in the ISO/OSI layer model. It is a linear bus system that uses a

twisted, shielded pair of wires as a field cable. The bus length can

be up to 500 m (without a repeater), depending on the transfer

rate. The bus coupler can be operated at a speed of 500 kBaud.

The baud rate is set via DIL switch S1 on the bus coupler. The node

address setting can be made via DIL switch S2. The logic supply is

protected by means of a diode against reverse polarisation. The

valve supply is protected against short circuits by a fuse.

The supply voltage is monitored before and after the fuse. If the

value falls below the set threshold, an error signal is generated

and the diagnostic information is reported via LEDs.

Diagnostic display Table 4: LED display on bus coupler

LED Color Meaning

UI Green Sensor supply

UL Green Logic supply

DIA Red Diagnosis

RUN Green System state

MSN Green/red Module/net state

Page 14: Bus coupler CMS, M-Design, DeviceNet

Configuration

14 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

4 Configuration

4.1 Presettings

See figure 2 DIL switches S1 and S2 can be accessed after the DR/NA S1/S2

screw cap on the bus coupler is opened.

The baud rate, diagnostic mode and participant address

settings for DIL switches S1 and S2 are read after the L24V

power supply has been turned on (bus coupler power

turned on). The power must be turned on again for the

changes to take effect.

When delivered, all DIL switches are set to the OFF position.

DIL switch S1 is essentially for setting the baud rate.

DIL switch S1

See section 4.1.1

DIL switch S2

See section 4.1.2

The node address is set on DIL switch S2.

Fig. 2: Bus coupler address switch S1

Table 5: S1 address switch assignment

S1 Designation Meaning

1 B0 Baud rate

2 B1

3 B2

4 B3 Reserved

5 B4 Diagnostic status in the assembly object (input)

6 B5 Compressed assembly object (output)

7 B6 Reserved

8 B7 Reserved (bus power)

S2S1

12

34

56

78

12

34

56

78

NO

FF

O

NO

FF

O

Page 15: Bus coupler CMS, M-Design, DeviceNet

Configuration

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 15

Engl

ish

4.1.1 Setting the baud rate

The desired baud rate can be set using switches S1/1 to S1/3

Baud rate switch S1

(DIL switches S1/1

to S1/3)

See figure 2

4.1.2 Setting the bus coupler participant's address

An address (node) from 0 and 63 can be assigned. Double

assignments are not permitted within DeviceNet. A DIL switch is

active if it is at "ON". The individual switches S2/1 to S2/6 are

combined to form the node address. The bus coupler is

delivered with the bus address set at "0".

The set address is read by the bus coupler’s software after

the L24V supply voltage has been turned on. The bus coupler

supply voltage must therefore be turned off and then on

again in case of address changes.

Please note the order and position of the ON positions for

each individual switch. The switches are all at OFF at delivery.

Node address switch S2

(DIL switches

S2/1 to S2/6)

See figure 2

Table 6: Baud rate assignment

Baud rate DIL switch S1 Max. cable length Comment

3

B2

2

B1

1

B0

1 Mbit/sec on on on Reserved

- on on off Reserved

500 kbit/sec on off on

250 kbit/sec on off off 100 m

125 kbit/sec off on on 250 m

50 kbit/sec off on off 500 m Reserved

20 kbit/sec off off on Reserved

10 kbit/sec off off off Reserved

Table 7: S2 adresse switch assignment

DIL switch 8 7 6 5 4 3 2 1

Designation A7 A6 A5 A4 A3 A2 A1 A0

Address (ON) - - 32 16 8 4 2 1

Page 16: Bus coupler CMS, M-Design, DeviceNet

Configuration

16 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

4.1.3 Setting the operating mode of the 32 I/O box

The maximum number of assigned input and output bits is

determined by the operating mode. The settings are made via

the bus. The rotary switch must be in operating mode 0 (setting

at delivery, operating mode 0).

32 I/O

box operating mode

NOTICEUndefined switching states

Connecting a mixture of actuators and sensors on one byte

(X1/X2 or X3/X4 or X5/X6 or X7/X8) is not permissible since it

could lead to undefined switching states. This applies

independent of the operating mode set.

O Leave or set the standard operating mode 0 when

operating the 32 I/O box on the DeviceNet.

Table 8: I/O box modes of operation

Mode Number Plug

(On delivery

= 0)Inputs Outputs

X1/X2 X3/X4 X5/X6 X7/X8

As input and/or output

0 32 1)

1) The outputs can be read via the corresponding inputs. That means that the outputs can be queried via the inputs over the bus.

I/O I/O I/O I/O

1 32 0 I I I I

2 0 32 O O O O

3 16 16 I I O O

4 24 1) I/O I/O I/O

5 24 0 I I I

6 0 24 O O O

7 16 1) I/O I/O

8 16 0 I I

9 0 16 O O

A 8 8 I O

B 8 1) I/O

C 8 0 I

D 0 8 O

Page 17: Bus coupler CMS, M-Design, DeviceNet

Configuration

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 17

Engl

ish

Configuration In the interest of completeness, all possible settings are shown.

The 32 I/O box has 14 operating modes.

If operating mode 0 is selected, the number of input/output bits

or bytes actually required by the PLC can be set by assigning the

PLC addresses.

The standard configuration (32 input bits and 32 output bits,

outputs readable via inputs) always occupies 4 input bytes and

4 output bytes with respect to the PLC.

4.2 Valve system configuration

4.2.1 Electronic Data Sheet (EDS)

The Electronic Data Sheet EDS is an ASCII file specified by the

ODVA where DeviceNet's subjects/performance characteristics

are described. The file for the HF 03 valve system with the bus

coupler (corresponds to type RM65M-DN on the nameplate) is

called RM65MDN.EDS.

The diskette with the EDS file contains the files for all of the

valve system's components. The EDS file must be integrated in

the configuration tools to plan the valve system.

After that, this is done using the DeviceNet manager (from Allen-

Bradley). This makes a comfortable project solution available.

4.2.2 Configuration using the DeviceNet manager

(from Allen-Bradley)

Every valve system is fitted with valves and possibly input/

output modules, according to the contract, and must be

configured. In the following example this is done with help from

the "DeviceNet Manager" program. See the manual for more

details on dealing with this program.

Page 18: Bus coupler CMS, M-Design, DeviceNet

Configuration

18 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

O Start the DeviceNet Manager. It runs on a PC which is

connected to the DeviceNet via a serial interface with a

switching module. The serial interface must be configured

on the one hand and the switching module's node address

on the other hand in order for communication with the bus

to work.

Fig. 3: “Driver Configuration” menu

O Then the participants connected to the bus are searched for

using the Who menu item. The following participants are

connected in the example described here:

Table 9: Bus participant, example

Type Participant address

Bus master (e.g. PLC) Node_0

PC connection module (DeviceNet Manager) Node_62

RM65M-DN (Bosch valve system) Node_7

Digital I/O module made by Allen-Bradley Node_11

Page 19: Bus coupler CMS, M-Design, DeviceNet

Configuration

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 19

Engl

ish

Fig. 4: “Network Who” menu

O Click participant RM65M-DN with node address 7. This bus

participant's status is shown in the Device Configuration

window by using the Config. Device menu item. In the

example, there are 2 input bytes and 6 output bytes

available to the valve system. Close the window again.

Fig. 5: “Device Configuration” menu

O Then select the bus master by double-clicking it. Click the

Edit Scan List button in the open Module Configuration

window.

Page 20: Bus coupler CMS, M-Design, DeviceNet

Configuration

20 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

Fig. 6: “Module Configuration” menu

O The participants to be configured can now be inserted into

the Scan List Editor window. Then close the window.

Fig. 7: “Scan List Editor” menu

Now the individual participants are moved onto the bus

master in the Add Devices to Scan List... window. These are

then marked in red. Now exit this menu window using the OK

button.

Page 21: Bus coupler CMS, M-Design, DeviceNet

Configuration

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 21

Engl

ish

Fig. 8: “Add Device to Scan List” menu

O Participant 11 in the example was already known by the

master. The participant with address 7 still has to be

configured. Go to the next menu by clicking line 07.

Fig. 9: “Scan List Editor” menu

O Enter the number of bytes that are needed for the participant

in the Edit Device I/O parameters window in order to configure

the valve system as a slave in DeviceNet. 2 bytes should be

Page 22: Bus coupler CMS, M-Design, DeviceNet

Configuration

22 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

read and 6 bytes written in the example chosen here.

Under Polled Size the following must be entered:

The input is acknowledged with OK.

Fig. 10: “Edit Device I/O Parameters” menu

Fig. 11: “Scan List Editor” menu

O Then the input and output bytes must be assigned individual

addresses in the PLC. This is done via mapping and can be

executed automatically by pushing the Auto Map button.

for 'Rx' 2 (= 2 bytes for outputs)for 'Tx' 6 (= 6 bytes for inputs)

Page 23: Bus coupler CMS, M-Design, DeviceNet

Configuration

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 23

Engl

ish

Fig. 12: “Auto Map Options” menu

After successfully assigning them to the PLC, the

configuration must be saved in the master.

The PLC must be first switched to programming mode!

Fig. 13: “Scan List Editor'” menu

O Complete the configuration in the 1747-SDN Module

Configuration: [DEFAULTS] window by clicking the

SDN button in the Save To field.

Page 24: Bus coupler CMS, M-Design, DeviceNet

Configuration

24 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

Fig. 14: “Scan List Editor: DEFAULTS” menu

O This is done in the Scan List Editor: ... window by clicking the

SDN button in the Save To field. Confirm that participant

7's configuration is to be loaded into the master by clicking

the OK button in the Scan List Editor - Download window.

Fig. 15: “Scan List Editor - Download” menu

Page 25: Bus coupler CMS, M-Design, DeviceNet

Assembly

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 25

Engl

ish

5 Assembly

5.1 Labeling the module

The address provided/used for the bus coupler is inscribed on

the bus coupler in the bus participant's field.

Fig. 16: Labels on the bus coupler

5.2 Connecting the bus coupler electrically

5.2.1 Field bus connection

Sockets BUS X71 and BUS X72 for connecting the field bus cable

with the coupling plugs are located on the bus coupler.

If a continuing bus connection is needed, the “arriving” field bus

cable can be connected to BUS X71 and the “departing” one to

BUS X72 for example.

Since BUS X71 and BUS X72 are internally connected in parallel,

a T-junction is not required.

Fig. 17: Field bus connection

Page 26: Bus coupler CMS, M-Design, DeviceNet

Assembly

26 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

If the bus coupler is the last station in the field bus connection,

meaning that no continuing connection is required, the remote

bus is connected to one socket and the others are provided with

a bus terminator resistor.

Bus terminator resistor

BUS X71 and BUS X72

socket assignment

Fig. 18: Field bus connection as the last station

NOTICEFaulty wiring

Faulty wiring can lead to malfunctions as well as damage to

the bus system.

O Only a cable that meets the field bus specifications

should be used. In order to assure both the degree of

protection IP 65 and the required strain relief, the cable

and plug assembly should be performed specifically

according to the assembly instructions

Table 10: BUS X71 and BUS X72 socket assignment

Pin BUS X71 BUS X72 Assignment

1 SHIELD SHIELD Shield

2 CAN_L CAN_L (dominant low)Data line A (green)

3

4 V+ V+ 24 V power supply

5 V- V-

6 V- V-

7 CAN-H CAN-H (dominant high)Data line B (red)

8

9 V+ V+ 24 V power supply

Page 27: Bus coupler CMS, M-Design, DeviceNet

Assembly

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 27

Engl

ish

Assembly of the bus

connection plugs

1. Detach the coupling socket with 22 and 24 mm open-ended

wrenches. On the cable, string together the cable part of the

socket (4), the sealing ring (3), the sealing and strain relief

element (2), and the metal disc (1).

2. Remove approx. 80 mm of the cable sheathing.

3. Spread out the wire braid. Wrap ground sleeve (5) over foil

or cotton braid and insert under wire braid with a turning

motion until wire braid and ground sleeve lie flat against

cable sheathing. Cut off wire braid flush with the outside of

the ring of the ground sleeve. Cut off foil, filler, and internal

cable insulation so that the wires lie free. Remove about

3 mm insulation from the wires, twist together, and apply

solder to each wire.

4. Run the wires through the corner piece (6) until the ground

sleeve lies against the corner piece.

5. Solder the cable wires to the pins on the contact body (7) (for

assignment see Table 5). Wrap the spacer sleeve (8) around

the wires. Insert the contact body and spacer sleeve into the

front piece (9) of the cable socket. When doing this, mate the

coded groove of the contact body (7) with the coded ridge.

Insert the whole unit (7), (8) and (9) into the corner piece so

that the cable exists in a satisfactory direction. In doing this,

the front piece can be mounted in the corner piece in any of

8 positions, spaced 45° apart.

Secure with nut (9a).

Push the metal disk (1) and sealing ring (3) with the sealing

and strain relief element (2) into the corner piece and secure

the cable part (4) of the coupling socket.

Page 28: Bus coupler CMS, M-Design, DeviceNet

Assembly

28 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

Fig. 19: Assembly of the plug for connecting the bus

80 mm

3 mm

8 x 45°

(1) (2) (3) (4)

1.

2.

3.

4.

5.

(5)

(6)

(7)

(8)

(9)

(9a)

Page 29: Bus coupler CMS, M-Design, DeviceNet

Assembly

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 29

Engl

ish

5.2.2 Connecting the bus coupler logic

5.2.3 and load supply

POWER X10 The following are powered via the plug POWER X10 (bus coupler):

– the valves,

– the bus coupler,

– all input modules and the output modules that are aligned

on the bus coupler,

– but not the 32 I/O box.

See section 9 The bus coupler operating voltages must be connected via the

coupling socket (Accessories) in accordance with Table 12.

See section 8 The operating voltages given in the electrical data

characteristics must be adhered to.

Fig. 20: POWER X10 on the bus coupler

P24VNPGNDP24V

FEL24V

24 V

24 V LGNDACAC

Page 30: Bus coupler CMS, M-Design, DeviceNet

Assembly

30 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

The following current levels must be provided. The cable cross-

sections must be selected according to the cable length and the

operating current:

POWER X10

power consumption

(bus coupler)

CAUTIONThere is an internal connection between the PGND pin on the

X10 and the PGND pin on the bus coupler's X10 if a power

module is present. That means: if a power supply unit without

safe isolation is used and the power supply is only connected

to one of the two X10 plugs, voltage can form on the PGND pin

which is dangerous when touched.

O This measure is therefore absolutely required:

The 24 V power supply must stem from a power supply

unit which is electrically isolated according to

DIN EN 60742, classification VDE 0551.

Table 11: POWER X10 plug pin assignments on the bus coupler

Pin POWER X10 Assignment

1 FE Functional earth (protruding contact)

2 P24VN1)

(24 V via emer.off)

1) Voltage can be obtained from a common power supply.

Supply voltageValves and outputs

3 PGND Ground for P24 and P24VN

4 L24V1) Supply voltageBus coupler logic

5 LGND Ground for L24V

6 P24V1) Supply voltageInputs

Table 12: POWER X10 power consumption (bus coupler)

Signal Assignment Total current

L24V Logic supply 0.6 A

P24V Inputs max. 2.0 A

P24VN Valves and outputs max. 8.3 A

Page 31: Bus coupler CMS, M-Design, DeviceNet

Bus coupler diagnostics display

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 31

Engl

ish

6 Bus coupler diagnostics display

The LEDs on the front panel of the bus coupler show the

messages of the following table.

Replacing fuses see section 7.2.

Table 13: Bus coupler diagnostics display

LED Signal Error

UI green P24V sensor supply present or no input module present.

blink1)

1) Blinking frequency 1: 0.8 sec. on, 0.2 sec. off

Bus coupler P24V sensor supply fuse faulty.

blink2)

2) Blinking frequency 2: 0.125 sec. on, 0.125 sec. off

System error.

off Input module is present, but P24V sensor supply is not connected.

UL green L24V logic supply present and RESET not active.

off No logic supply present or RESET active.

DIA off No diagnosis or emergency off.

red Diagnostics display and diagnostics message to the master.W Low voltage P24V sensor supply.W Low voltage P24VN load supply.W No P24V load supply or emergency off.W P24V sensor supply fuse in the bus coupler faulty.W Valve supply fuse in the bus coupler faulty.

blink1) P24VN load supply fuse in the bus coupler faulty.

blink2) System error.

RUN green State of the RM65M-DN system. 24 V supply present via the bus,

module operational.

blink2) 24 V supply via bus is missing.

MNS green Module/Net status. Module online on bus, communication connections

have been established.

green blink3)

3) Blinking frequency 2: 0.5 sec. on, 0.5 sec. off

Module online on bus, communication connections have not yet been established, error can be resolved.

red blink3) Module online on bus, communication connections have not yet been established, critical error.

off Module is stuck in the "Initializing" mode after the power was turned off.Possible cause: supply via bus is missing (see RUN LED).

Page 32: Bus coupler CMS, M-Design, DeviceNet

Disassembly/exchange

32 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

7 Disassembly/exchange

7.1 Exchanging the bus coupler

1. Remove the electrical connections from the bus coupler.

2. Remove the left side cover from the valve system's bus

coupler (3 hexagon socket-head screws DIN 912 M4,

wrench width 3).

3. Unscrew the bus coupler (3 hexagon socket-head screws

DIN 912 M4, wrench width 3).

4. Insert the new bus coupler.

5. Screw on the new bus coupler (3 hexagon sockethead

screws DIN 912 M4, wrench width 3).

Tightening torque: 2,5...3 Nm.

6. Screw the left side cover back on (3 hexagon sockethead

screws DIN 912 M4, wrench width 3).

Tightening torque: 2,5...3 Nm.

See section 4.1 7. Set the address and baud rate on the new bus coupler.

8. Reestablish connections.

CAUTIONApplied electric voltage and high pressure

Danger of injury from electric shock and sudden pressure drops.

O Make sure that the system is not under voltage or pressure.

Page 33: Bus coupler CMS, M-Design, DeviceNet

Disassembly/exchange

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 33

Engl

ish

Fig. 21: Exchanging the bus coupler

7.2 Replacing fuses

Before changing a fuse(s), please observe the following:

O Remove the front panel of the bus coupler (6 Torx T10 screws).

Separating the front panel is hampered by the plug-in

connections.

CAUTIONApplied electric voltage and high pressure

Danger of injury from electric shock and sudden pressure drops.

O Make sure that the system is not under voltage or pressure.

O Observe the stipulated precautionary measures when

working with ESD-sensitive assemblies.

Page 34: Bus coupler CMS, M-Design, DeviceNet

Disassembly/exchange

34 AVENTICS | DeviceNet | 1987765448–BDL–001–AB

See figure 22 The fuse for the I/O module outputs is located on the back of the

bus coupler's front panel:

O Replace the heat-coil fuse: (5x20) super fast-acting

See figure 23 Two more fuses are located on boards in the bus coupler:

W The left heat-coil fuse for the I/O module inputs,

fast-acting 4 A, F4A.

W The right heat-coil fuse for the valves, fast-acting 4 A, F4A.

W Re-attach the front panel of the bus coupler

(6 Torx T10 screws).

Tightening torque: 2.5 to 3.0 Nm.

To assure the IP 65 protection level, make sure the gasket is

correctly seated.

Fig. 22: Position of the fuse on the back of the bus coupler's front panel

Fig. 23: Position of the fuse on the bus coupler's two boards

Page 35: Bus coupler CMS, M-Design, DeviceNet

Technical Data

AVENTICS | DeviceNet | 1987765448–BDL–001–AB 35

Engl

ish

8 Technical Data

8.1 Characteristics

9 Service parts and accessories

General

Installation position any

Degree of protection according to EN 60529/IEC 529 IP 65 when assembled

Ambient temperature U +5 °C to +50 °C

Electrical

Rated voltage logics Un 24 V DC (-15 %/+20 %)

Rated voltage outputs Un 24 V DC (-15 %/+20 %)

Electromagnetic compatibility

Interference immunity EN 61131-2

Interference signal EN 50081-2

Order code Order number

Bus coupler with DeviceNet1)

1) Delivery includes 3 fastening screws and 1 gasket

RMMDE/I 1827030150

Accessories

Plug connection for voltage supply, 6-pin socket 1824484053

Plug connection for bus connection, 6-pin socket 1824484056

Protective cap for bus connection 1823345008

Electronic Data Sheet (EDS)2)

2) Available on mediadirectory (www.aventics.com/mediadirectory)

1070075547

Page 36: Bus coupler CMS, M-Design, DeviceNet

AVENTICS GmbH

Ulmer Straße 430880 LaatzenPhone +49 (0) 511-21 36-0Fax: +49 (0) 511-21 36-2 [email protected]

Further addresses:www.aventics.com/contact

The data specified above only serve to describe the product. No statements concerning a certain condition or suitability for a certain application can be derived from our information. The given information does not release the user from the obligation of own judgement and verification. It must be remembered that our products are subject to a natural process of wear and aging.

An example configuration is depicted on the title page. The delivered product may thus vary from that in the illustration.

Translation of the original operating instructions. The original operating instructions were created in the German language.

1987765448–BDL–001–AB/09.2014Subject to modifications. © All rights reserved by AVENTICS GmbH, even and especially in cases of proprietary rights applications. It may not be reproduced or given to third parties without its consent.