Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
• For directly ignited burners of unlimited capacity in intermittent operation or in continuous operation pursuant to EN 746-2
• Plug-in function unit for mounting in 19" module subracks
• Flame control by UV, ionization or a further option of using the furnace chamber temperature
• Display of the program status, unit parameters and flame signal; Manual mode for burner adjustment and for diagnostic purposes
• Visualization and adaptation to the specific application via the PC programming and diagnostic software BCSoft to simplify logistics management
• Air valve control relieves the furnace control
• Connection to PROFIBUS-DP via field bus interface PFA
• Certified for systems up to SIL 3 and compliant with PL e
Burner control unit PFU 760
Technical Information · GB
6.2.1.4 Edition 05.11
2
PFU 760 · Edition 05.11 = To be continued t
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
Contents Burner control unit PFU 760 . . . . . . . . . . . . . . . . . . . . . . . . . 1 Contents . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.1 Examples of application .................................................... 6
1.1.1 Staged On/Off burner control ................................................. 6 1.1.2 Staged High/Low burner control .............................................7 1.1.3 Two-stage-controlled burner .................................................. 8 1.1.4 Modulating-controlled burner ................................................ 9 1.1.6 PFU for PROFIBUS-DP with PFA 700 .................................... 10 1.1.5 PFU 760..D: High temperature equipment.......................... 10
2 Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
3 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 3.1 Connection diagram ....................................................... 12
3.1.1 PFU 760 ............................................................................... 12 3.1.2 PFU 760..K1 ......................................................................... 13 3.1.3 PFU 760..K2 ......................................................................... 14
3.2 PFU 760 program sequence .......................................... 15 3.3 Program status and fault messages .............................. 17
4 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 4.1 Scanning the parameters ............................................... 19 4.2 Flame control ................................................................. 20
4.2.1 Burner flame signal .............................................................. 20 4.2.2 Program status when the most recent fault occurred. . . 20 4.2.3 Switch-off threshold of the flame amplifier ....................... 20 4.2.4 High temperature operation with PFU..D ........................... 21 4.2.5 UVS check ......................................................................... 24
4.3 Behaviour in start-up position/standby ........................ 25 4.3.1 Flame simulation check in start-up position/standby . . . 25 4.3.2 Minimum burner pause time tBP ................................................... 26
4.4 Behaviour during start-up ............................................. 27 4.4.1 Safety time on start-up tSA ................................................................. 27 4.4.2 Flame proving period tFS .................................................................... 27 4.4.3 Minimum combustion time tB ......................................................... 27 4.4.4 Burner start-up attempts .................................................... 28
4.5 Behaviour during operation ........................................... 29
4.5.1
3
PFU 760 · Edition 05.11 = To be continued t
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
Safety time during operation tSB for V1 and V2 ................... 29 4.5.2 Fault lock-out or restart ...................................................... 29
4.6 Switchable gas valve V2 on PFU..L 31
4.7 Air valve control PFU..L .................................................. 32 4.7.1 Purge ................................................................................. 32 4.7.2 Cooling in start-up position/standby .................................. 32 4.7.3 Burner start ......................................................................... 32 4.7.4 Air valve opens in the case of external activation (not during start-up) 33 4.7.5 Air valve opens in the case of external activation (even during start-up) 34 4.7.6 Air valve opens with valve V1 ............................................. 35 4.7.7 Air valve opens with valve V2 ............................................. 36 4.7.8 Low fire over run time tKN after a controlled shut-down . .37 4.7.9 Behaviour of the air valve in the event of a fault lock-out 38
4.8 Manual operation ......................................................... 39 4.8.1 Manual mode limited to 5 minutes .................................... 39
4.9 Password ................................................................... 39 4.10 Multi-flame control ...................................................... 40
5 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 5.1 Safety time
41 5.1.1 Calculating the safety time tSA
.................................................................................................................................. 4
1
5.2 Selection table ............................................................... 42 5.3 Type code................................................................... 42
6 Project planning information . . . . . . . . . . . . . . . . . . . . . 43
6.1 Cable selection ............................................................... 43 6.1.1 Ignition cable ........................................................................ 43 6.1.2 Ionization cable ................................................................... 43 6.1.3 UV cable ............................................................................ 43
6.2 Ignition electrode .......................................................... 43
6.2.1 Electrode gap..................................................................... 43 6.2.2 Star electrodes ....................................................................43
6.3 Minimum combustion time .......................................... 44 6.4 Safety interlocks (Limits) ............................................... 44 6.5 Emergency stop ............................................................ 44
4
PFU 760 · Edition 05.11 = To be continued t
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
6.5.1 In the event of fire or electric shock ................................... 44 6.5.2 Via the safety interlocks (limits) ......................................... 44
6.6 Reset .............................................................................. 45 6.6.1 Parallel reset ........................................................................ 45 6.6.2 Permanent remote reset .................................................... 45 6.6.3 Automatic remote reset (PLC) ............................................ 45 6.6.4 Burner start ......................................................................... 45 6.6.5 Restart and start-up attempts ............................................ 45
6.7 Fault signalling ............................................................... 46 6.8 Protecting the burner from overload ............................ 46 6.9 Installation ..................................................................... 46 6.10 Wiring ........................................................................... 46
6.10.1 UVS sensor wiring ........................................................... 46
6.11 PFU switched off ........................................................... 46 6.12 Furnace control ............................................................ 47 6.13 Note on EC type-examination ...................................... 47 6.14 Mains switch ................................................................ 47 6.15 Changing parameters ................................................ 47
7 Flame control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 7.1 With ionization sensor .................................................... 48 7.2 With UV sensor .......................................................... 48 7.3 Via the temperature in high temperature equipment 48
8 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
8.1 High-voltage cable .............................................................. 49
8.2 BCSoft ............................................................................ 49 8.3 Stickers for labelling ...................................................... 49 8.4 “Changed parameters” stickers ..................................... 49 8.5 Radio interference suppressed electrode adapters . 50 8.6 Socket connectors .......................................................... 50
8.7 Module subracks ....................................................... 50 8.8 Power supply PFP 700 ................................................... 51 8.9 Relay module PFR 704 ................................................... 52 8.10 Flame detector PFF 704 ............................................... 53
8.11 Field bus interface PFA 700 .......................................... 54
8.12
5
PFU 760 · Edition 05.11 = To be continued t
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
Impulse system MPT 700 ............................................. 55
9 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 9.1 Safety-specific characteristic values ............................... 58 9.2 Operating controls ......................................................... 59
10 Maintenance cycles . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
11 Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
12 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
12.1 Waiting time tW ....................................................................... 62 12.2 Safety time on start-up tSA ........................................... 62 12.3 Ignition time tZ .............................................................. 62
12.4 Flame simulation/Flame simulation delay time tLV . 62 12.5 Safety time during operation tSB .................................. 62 12.6 Flame signal .............................................................. 63 12.7 Fault lock-out ................................................................ 63 12.8 Safety interlocks (Limits) .............................................. 63 12.9 Pilot gas valve V1 .......................................................... 63 12.10 Main gas valve V2 ................................................... 63 12.11 Continuous operation .................................................. 63 12.12 Air valve ...................................................................... 63 12.13 Diagnostic coverage DC .......................................... 64 12.14 Mode of operation ...................................................... 64 12.15 Safe failure fraction SFF .............................................. 64 12.16 Probability of dangerous failure PFHD ........................ 64 12.17 Mean time to dangerous failure MTTFd ..................... 64
Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
6
PFU 760 · Edition 05.11
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
1 Application The burner control units PFU 760 control, ignite and moni- tor gas burners for intermittent or continuous operation. As a result of their fully electronic design they react quickly to various process requirements and are therefore also suitable for frequent cycling operation.
The PFU 760 can be used for directly ignited industrial burners. The burners may be modulating or stage-controlled.
On industrial furnaces, the PFU 760 reduces the load on the central furnace control by taking over tasks that only relate to the burner, for example it ensures that the burner always ignites in a safe condition after it has been restarted.
The burner control unit is used for burners with mechanical combustion air supply where the fan is controlled by a separate logic and for atmospheric burners.
Module subrack BGT for instance serves to accom- modate several function units. It is provided with a backplane with screw terminals for simple, reliable wiring.
The air valve control on the burner control unit PFU 760L assists the furnace control for cooling, purging and output control tasks.
The program status, the unit parameters and the level of the flame signal can be read directly from the unit. The burner can be controlled manually for commissioning and diagnostic purposes.
If the local requirements on the burner control unit change, the PC software BCSoft can be adjusted to the unit parameters of the application by using the optical interface.
The service personnel is supported by a convenient visualiza- tion system of the input and output signals and the error history.
To reduce the installation and wiring costs, Elster Kromschröder offers the field bus interface PFA 700 to transfer the control signals and feedbacks via PROFIBUS-DP.
PFU 760 · Edition 05.11
5
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
Bogie hearth forging furnace in the metallurgical industry
Intermittent shuttle kiln in the ceramics industry
Walking beam furnace with overhead firing
PFU 760 · Edition 05.11
6
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
1 .1 Examples of application
1 .1 .1 Staged On/Off burner control The burner can be started with reduced capacity.
A UV sensor monitors the flame signal from the burner. UV sensor UVD 1 is used for continuous operation, UV sensor UVS for intermittent operation.
SPS PLC API
L1, N, PE DI P
P 1
PFU 760L
DI
22a 10c 26e
A
30e 10a 10e 2e 4e
µC
2c 4c
22e 16c 28c 26a
TZI
VAG
VR..R
PFU 760 · Edition 05.11
7
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
1 .1 .2 Staged High/Low burner control The burner starts at low-fire rate. When the operating state is reached, the PFU 760L advises the control unit. The PLC can now pulse the air valve in order to control the burner output. SPS
PLC API
L1, N, PE DI P
DI
22a 10c 26e
P A 1
PFU 760L 30e 10a 10e 2e 4e
µC
2c 4c
22e 16c 28c 26a
TZI
GIK..B
VAS..N
VR..R
PFU 760 · Edition 05.11
8
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
1 .1 .3 Two-stage-controlled burner Control: ON/OFF with ignition via bypass
The burner starts at low-fire rate. When the operating state is reached, the PFU 760L issues the Enable signal for the maximum burner output.
L1, N, PE DI P
DI P A
22a 10c 26e PFU 760L 30e
1
10a 10e 2e 4e
µC 2c 4c
22e 18e 16c 28c 26a
TZI
VBY
VAG
BVA + IC 40
SPS PLC API
4
7 M
PFU 760 · Edition 05.11
9
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
1 .1 .4 Modulating-controlled burner Control: continuous
The external control system moves the butterfly valve for air BVA to ignition position. The burner starts at low-fire rate, and a controller in the PLC controls the burner output via the butterfly valve for air BVA after the operating state has been signalled.
L1, N, PE
DI
mA
P SPS PLC API
PFU 760
DI
22a 10c 26e
1
10e
µC
2e 4e
2c 4c
16c 28c 26a
TZI BIO BIC
VAG
M
BVA+IC 20
PFU 760 · Edition 05.11
10
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
1 .1 .6 PFU for PROFIBUS-DP with PFA 700 The bus system transfers the control sig- nals for starting, resetting and for con- trolling the air valve from the control sys- tem (PLC) to the PFU 760 via the PFA 700. In the opposite direction it sends infor- mation on the operating status. Control signals that are relevant for safety, such as the safety interlocks and digital input, are transferred independently of the bus communication by separate cables.
1 .1 .5 PFU 760 . .D: High temperature equipment Indirect flame control using the tempera- ture. During the start-up process, as long as the wall temperature is below auto ignition temperature the flame must be controlled by conventional methods. When the working temperature has exceeded 750°C, the safety tempera- ture monitor (STW) takes over the indirect flame control.
STW >750 °C
PFU 760..D L1
PFU 760..D
µC µC
18a 18a
22a
DI
22a
DI
PROFIBUS-DP
L1, N, PE DI P
SPS PLC API
BUS
…
BUS
…
BU
S
PFA
/PFP
PFU
76
0
PFU
76
0
PFU
76
0
PFU
76
0
PFU
76
0
PFU
76
0
PFU
76
0
PFU
76
0
PFU
76
0
PFA
/PFP
PFU
76
0
PFU
76
0
PFU
76
0
PFU
76
0
PFU
76
0
PFU
76
0
PFU
76
0
PFU
76
0
PFU
76
0
PFU 760 · Edition 05.11
11
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
2 Certification Certified pursuant to SIL
AGA approved
Australian Gas Association, Approval No.: 5597 www.aga.asn.au/product_directory
For systems up to SIL 3 pursuant to EN 61508
Pursuant to EN ISO 13849-1:2006, Table 4, the PFU can be used up to PL e.
EC type-tested and certified
pursuant to
– Gas Appliances Directive (2009/142/EC) in conjunction with EN 298:2004-01,
Meets the requirements of the – Low Voltage Directive (2006/95/EC),
– EMC Directive (2004/108/EC).
PFU . .T is FM approved
Factory Mutual Research Class: 1997.
Suitable for applications pursuant to NFPA 86. www.fmglobal.com Products and Services Product Cer- tification Approval Guide
AGA
PFU 760 · Edition 05.11
12
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
3 Function
3 .1 Connection diagram For cable selection and wiring, see page 43 (Project planning information).
3 .1 .1 PFU 760 For the explanation of symbols, see page 61 (Legend).
( PFU 760L)
L1 (L1) 30e PFU 760
22e N
F1 sk1 16c
V1 26e
DI 22a
V2
30a N (L2)
32c 24c
20c a 2a 4a
230 V
28c s 4e 2e
N Z I
26a m
2c 4c
PFF 704
24 V 8a 8c
8a
8c
8e µC
0 V 8e
A
S
SK
24 V
0 V
1 10e
12e
10a
12a
10c
12c
1 UVS 2
26a 20c
3 24c
N 28c
26a
N
28c
P
A
18e
ma
x. 1
A, 2
4 V
PFU 760 · Edition 05.11
13
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
3 .1 .2 PFU 760 . .K1 As a replacement unit for burner control unit PFS/PFD 778.
For the explanation of symbols, see page 61 (Legend).
( PFU 760L..K1)
PFU 760..K1
L1 (L1) 30e N
F2
F1
22e
sk1
V1 26e
DI 22a
V2
30a N (L2)
32c 24c
20c a 2a 4a
230 V
28c s 4e 2e
N Z I
26a m
2c 4c
PFF 704
24 V 8a 8c
8a
8c
8e µC
0 V 8e
24 V
0 V
A
S
SK 1
10e
12e
10a
12a
10c
12c
26a UVS 2 20c
1
3 24c
N
28c
26a
N
28c
P
A
16c
18e
ma
x. 1
A, 2
4 V
PFU 760 · Edition 05.11
14
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
3 .1 .3 PFU 760 . .K2 As a replacement unit for burner control unit PFU 778.
For the explanation of symbols, see page 61 (Legend).
( PFU 760L..K2)
L1 (L1) 30e PFU 760..K2
22e N
F1 sk1 16c
V1 26e
DI 22a
V2
30a N (L2)
32c 24c
20c a 2a 4a
230 V
28c s 4e 2e
N Z I
26a m
2c 4c
PFF 704
24 V 8a 8c
8a
8c
8e µC
0 V 8e
24 V
0 V
A
S
SK 1
10e
12e
10a
12a
10c
12c
UVS 2 20c 1 26a
3 24c
N 28c
26a
N
28c
P
A
18e
ma
x. 1
A, 2
4 V
PFU 760 · Edition 05.11
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
Wait until has elapsed (P21)
Function
00
01
Start-up position/standby
Start-up with signal
PFU 760L with air valve control features the following additional functions.
In start-up position, the air valve can be opened for cooling A .
Using parameter 31, it can be determined whether the air valve can be activated externally during start-up.
15
3 .2 PFU 760 program sequence
Normal start-up If an “old” fault is still being signalled after switching on, it will be necessary to reset this first.
When the safety interlocks are closed, the PFU reverts to start-up position and conducts a self-test. If it does not deter- mine a malfunction of the internal elec- tronic circuitry or of the flame sensor, the burner can be started.
The flame simulation check is conducted during start-up position or after applying the start-up signal (), depending on parameter 15.
After the min. burner pause time tBP has elapsed, the PFU opens valve V1 and ignites the burner. The ignition time tZ is constant.
If a flame is detected during the safety time tSA, the flame proving period tFS
0
Safety time tSA running (P22),
ignition in process, V1 opens and
min. combustion time tB starts to elapse (P20)
If no flame detected: next start-up attempt (P10)
or fault lock-out
The air valve can be set to open together with V1 (display A ) via parameter 30.
starts after this safety time has elapsed. Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes. This completes start- up. An adjustable min. combustion time tB ensures that the burner burns for a defined period even if the start-up signal
() is switched off beforehand.
t
min. burner pause time tBP
Switch on PFU 760
In the event of fault signal: Reset
Safety interlocks (Limits)
If parameter P15 = 1: Flame simulation check
If parameter P15 = 0: Flame simulation check
PFU 760 · Edition 05.11
16
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
If min. combustion time tB
min. burner pause time tBP
running (P23)
0
04
04
00
Operation signalling
contact closes and V2 opens
In the event of flame failure:
restart or fault lock-out
The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30.
The burner can also be started manually with the aid of the button on the PFU. Voltage must be applied continuously to terminals 10e, 26e and 30a in order for this to occur.
The PFU can also be operated in Manual mode for start-up.
Start-up without flame signal If no flame is detected during the safety time tSA, either a fault lock-out occurs or up to three further start-up attempts occur. The required functions and, if applicable, the number of start-up attempts must be specified when or- dering. (Parameter 10, “Burner start-up attempts”).
Behaviour in the event of flame failure during operation If the flame fails during operation, either an immediate fault lock-out occurs or a restart occurs. This procedure can be set via the optical interface (parameter 12, “Burner restart”).
starts to elapse (P21)
Controlled shut-down via signal
In the event of flame failure: fault lock-out
Flame proving period tFS
has elapsed: Operation signalling
contact opens, V1 and V2 close,
PFU 760 · Edition 05.11
17
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
3 .3 Program status and fault messages During operation, the 7-segment display shows the program status. In the event of a fault, the PFU halts the program run, the display blinks and it then displays the cause of the fault. The burner control unit can be reset using the Reset button or the remote reset.
Program status I LAY Fault message (blinking*)
Start-up position/standby 00
Cooling A0
Waiting time/Pause time 1 Flame simulation, pilot burner
Burner safety time on start-up Burner start-up without flame signal
Burner flame proving period Flame failure during burner flame proving period
Burner operation 4 Flame failure during operation, pilot burner
Purge 0
Air valve A
High temperature operation** . .
10 Faulty remote reset
Supply voltage too low
Faulty parameterization
Short-circuit on a valve output
6 Short-circuit on ignition or valve output
1 Safety interlock failure
Permanent reset
Time between two start-ups is too short
* In Manual mode, two dots will blink on the display in program status 01 – 04. ** Optionally available.
PFU 760 · Edition 05.11
18
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
4 Parameters
Description Parameter Value range Factory default
setting Adjustable*
Burner flame signal 01 0 – 30 μA
Program status when the most recent fault occurred 03 x0 – x8
Burner switch-off threshold 04 1 – 20 µA 1 µA
Burner start-up attempts 10 1 – 4 1
Burner restart 12 0; 1 0
Safety time during operation for V1 and V2 tSB 14 1; 2 s 1 s
Flame simulation check in start-up position/standby 15 0; 1 1
Minimum combustion time tB 20 25 s tSA
Minimum burner pause time tBP 21 0 – 250 s 0 s
Burner safety time on start-up tSA 22 3; 5; 10 s
Burner flame proving period tFS 23 0 – 25 s 0 s
Switchable gas valve V2 (only on PFU..L) 26 0; 1 0
Air valve control 30 0; 1; 2 0
Air valve can be activated externally on start-up 31 0; 1 0
Air valve closed/can be activated in the event of malfunction 32 0; 1 1
High temperature operation** 33 2; 3
t
PFU 760 · Edition 05.11
19
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
Description Parameter Value range Factory default
setting Adjustable*
Manual mode limited to 5 minutes 34 0; 1 1
UVS check (1 x in 24 hours) 35 0; 1 0
Low fire over run time 36 0; 3; 5; 10; 15;
25; 60 s 0 s
Purge 42 0; 1 1
Multi-flame control 45 0; 1 0
Password 50 0000 – 9999 1234
* Adjustable using BCSoft software and a PC opto-adapter. ** Please quote in your order. 0 = Function inactive, 1 = Function active.
On parameterization, ensure that the program sequence matches the application. Select the parameters so that the burner can be operated as intended in all operating phases.
4 .1 Scanning the parameters During operation, the 7-segment display shows the program status.
The flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the Reset/Information button (for 2 s).
In the event of a fault, the PFU halts the program run, the display blinks and it then displays the cause of the fault in coded form.
PFU 760 · Edition 05.11
20
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
01
4 .2 Flame control
4 .2 .1 Burner flame signal Parameter 01
Flame signal of the burner, display in µA, measuring range: 0 – 30 µA.
4 .2 .2 Program status when the most recent fault occurred Parameter 03
This indicates the program status in which the last burner fault occurred (e.g. the unit indicates that a flame simulation has been detected with a blinking 01.
In parameter 03, it is now shown which program position the
4 .2 .3 Switch-off threshold of the flame amplifier Parameter 04, burner switch-off threshold
The sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 µA.
Example: In the case of UV control with the UV sensor UVS, the signal of the burner to be monitored is influenced by other burners.
The set value can be incremented in parameter 04 so that only the flame of the system’s “own” burner is detected.
The measured flame signal of the system’s “own” burner should be at least 3 µA (empirical value) higher than the set switch- off threshold.
unit was in when the fault was detected (waiting time or standby 00 ).
Result: A flame simulation was detected during the waiting time or standby.
PFU 760 · Edition 05.11
21
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
4 .2 .4 High temperature operation with PFU . .D Parameter 33
Operation of firing systems at temperatures above 750°C. The PFU features a safety-relevant DI input (Digital Input). This input supports the “High temperature operation” function. If firing systems are operated above 750°C, the system is considered to be a high temperature equipment (see EN 746-2). Flame control must be in operation until the furnace wall temperature has exceeded 750°C. Note the requirements of the Standards!
Flame control can be dispensed with during high temperature operation to improve the system availability. This means that no incorrect flame signals, e.g. signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation, may lead to faults.
When the DI input is activated, the burner control unit reverts to High temperature mode. This means: the PFU operates without evaluation of the flame signal. The safety function of the device-internal flame control system is placed out of operation.
In High temperature mode, the gas valves are opened without flame control.
The precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature. For this purpose, we recommend a safety temperature monitor with twin thermocouple (DIN 3440). Sensor discontinuity, sensor short-circuit, failure of a component or mains failure must set the installation to a safe state.
The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750°C. The PFU starts the burner as usual, without monitoring the presence of the flame.
If the temperature in the furnace chamber drops below 750°C, the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system.
t
4 88 30a 26e 10e 28c 22a DI
16c V1 26a 2c–4c 18e V2 2e–4e
t
tSA
tZ tFS
PFU 760 · Edition 05.11
22
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
The PFU then responds, depending on setting: Parameter 33 = 1 (PFU 760..K2 only)
Parameter 33 = 2
If the flame fails during high temperature operation, the ready contact opens for the duration of the flame failure (FA).
When High temperature mode is ended, the PFU switches off the burner and restarts with flame simulation check (recom- mended in the case of UV control with UVS).
When High temperature mode is ended, the PFU switches off the burner and restarts with flame simulation check (recom- mended in the case of UV control with UVS).
On programming parameter 33, ensure that the program sequence matches the application. Select the parameters so that the burner can be operated as intended in all operating phases.
t
FA
4 1 4 88 30a 26e 10e 28c 22a DI
16c V1 26a 2c–4c 18e V2 2e–4e 2a–4a
t
tW
tZ
tSA
tFS
4 1 4 88 30a 26e 10e
tW
tZ
tSA
tFS
28c 22a DI
16c V1 26a 2c–4c 18e V2 2e–4e 2a–4a
t
PFU 760 · Edition 05.11
23
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
Parameter 33 = 3 Parameter 33 = 4 (PFU 760..K2 only)
When High temperature mode is ended, the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD).
If no flame signal is present when High temperature mode is ended, the burner control unit performs a fault lock-out, regardless of parameter 33.
If the flame fails during high temperature operation, the ready contact is opened for the duration of the flame failure.
When High temperature mode is ended, the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD).
4 4 88 30a 26e 10e
28c 22a DI
16c V1 26a 2c–4c 18e V2 2e–4e
t
4 4 88 30a 26e 10e
28c 22a DI
16c V1 26a 2c–4c 18e V2 2e–4e
t
FA
4 4 88 30a 26e 10e 28c 22a DI
16c V1 26a 2c–4c 18e V2 2e–4e 2a–4a
t
PFU 760 · Edition 05.11
24
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
4 .2 .5 UVS check Parameter 35
An automatic restart of the burner control unit can be activated every 24 hours via this parameter. The time starts each time the start-up signal ( ) is applied.
Parameter 35 = 0: Unlimited burner operation.
Parameter 35 = 1: An automatic restart is activated once every 24 hours.
It must be ensured in this case that the program sequence started matches the application. This parameter may be set in this way only if the burner can restart as intended in all operating phases.
PFU 760 · Edition 05.11
25
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
01
4 .3 Behaviour in start-up position/standby
4 .3 .1 Flame simulation check in start-up position/standby Parameter 15
This defines the instant for the flame simulation check.
What is an extraneous signal?
Parameter 15 = 0: The flame simulation check is conducted after applying the start-up signal () during the waiting time tW.
An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence. If the PFU 760 notices such an extraneous signal during the flame simulation check, it starts the flame simulation delay time tLV. If the extraneous signal is discontinued during this period, the burner can start up. Otherwise, a fault lock-out occurs. blinks on the display.
Parameter 15 = 1: The flame simulation check is conducted provided no start-up signal () is applied (during the so-called start-up position/standby). This allows fast start-up of the burner since there is no waiting time tW.
The burner must have been switched off for at least 4 s be- fore start-up in order for the flame simulation check to be conducted correctly.
The flame simulation check of the burner is active until valve V1 is enabled.
tW
1 . . . 88
V1
t
. . . 88
V1
t
1 88 30a 26e 10e
tLV
28c 26a 16c V1 18e V2 2c–4c 2e–4e
t
PFU 760 · Edition 05.11
26
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
tBP
4 .3 .2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s.
An immediate restart of the main burner after a controlled shut-down, a start-up attempt, restart, cooling or purging is prevented by the pause time. The pause time starts when the air valve is switched off. If a start-up signal ( ) is applied before expiry of this time, the start-up is delayed until the end of the pause time.
After the pause time, the burner is started if the start-up signal ( ) is applied.
The minimum burner pause time tBP serves to adapt the pro- gram sequence to the requirements of the application.
The time should be set such that the system can be moved to ignition position, i.e. butterfly valves can be closed and, pos- sibly, gas can be flared off, before a restart occurs.
See examples of application Staged On/Off burner control, Staged High/Low burner control oder Two-stage-controlled burner.
4 1 4 88 1 5 4 7
9 12 V1 14 V2 16-17 18-19
tZ tFS t
tSA
PFU 760 · Edition 05.11
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
tSA
tFS
Parameters
4 .4 Behaviour during start-up
4 .4 .1 Safety time on start-up tSA Parameter 22
27
4 .4 .3 Minimum combustion time tB Parameter 20
Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operation.
In the case of brief activation of the start-up signal input () (e.g. with a pulse), the combustion time tB is started, and the burner remains in operation for at least this period.
Safety time on start-up tSA for the burner.
4 .4 .2 Flame proving period tFS Parameter 23
Programmable time between 0 and 25 s.
This time elapses before the PFU starts the next program step so as to give the flame time to stabilize.
4 88 30a 26e 10e 28c
tZ
16c V1 18e V2 2c–4c 2e–4e
t
26a
tSA
88 30a 26e 10e
tZ tFS
28c 26a 16c V1 18e V2 2c–4c 2e–4e
t
4
PFU 760 · Edition 05.11
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
Parameters > Behaviour during start-up
4 .4 .4 Burner start-up attempts Parameter 10
This indicates the number of possible start-up attempts of the burner.
In accordance with EN 746-2, three start-ups are permitted in specific cases in the event of flame failure during start-up, if the safety of the installation is not impaired. Note the require- ments of the Standards!
If no flame is detected during start-up, either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occur.
Pursuant to NFPA 86, only one start-up attempt is permitted in the event of flame failure during start-up. For units approved by FM Approval (see type label), it is only possible to select one start-up attempt.
1 start-up attempt Parameter 10 = 1
28
2 or 3 start-up attempts Parameter 10 = 2, 3
If several start-up attempts are set and if the PFU detects a flame failure during start-up, it closes valve V1 after the safety time tSA has expired and attempts to start up again. After the last programmed start-up attempt has been completed, the burner control unit conducts a fault lock-out. The display blinks and shows the cause of the fault.
If no flame forms during start-up, a fault lock-out is performed after expiry of time tSA. The display blinks and shows the cause of the fault.
88 30a 26e 10e 1 28c 26a 16c V1 18e V2 2c–4c 2e–4e
tZ t
tSA
88 30a 26e 10e
tZ tZ
28c 26a 16c V1 18e V2 2c–4c 2e–4e
t
tSA tSA
PFU 760 · Edition 05.11
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
Parameters
4 .5 Behaviour during operation
4 .5 .1 Safety time during operation tSB for V1 and V2 Parameter 14
This indicates the safety time during operation tSB for valves V1 and V2. The default in accordance with EN 298 is 1 s. The PFU has also the available option of a safety time during operation tSB of 2 s. Prolonging the time increases the installation avail- ability in the case of brief-duration signal fades (e.g. fades of the flame signal). In accordance with EN 746-2, the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards).
29
4 .5 .2 Fault lock-out or restart Parameter 12
This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information).
Immediate fault lock-out following flame failure Parameter 12 = 0:
After a fault lock-out, the burner control unit can be reset, either with the button on the front panel or using an external button. Several burner control units can be reset in parallel using the external button.
The PFU cannot be reset by mains failure. The fault signalling contact does, however, open as soon as the mains voltage fails.
See also parameter 32, Behaviour of the air valve in the event of a fault lock-out.
t
4 4
tSB
88 30a 26e 10e 28c 26a 16c V1 18e V2 2c–4c 2e–4e
t
PFU 760 · Edition 05.11
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
tSB
Parameters > Behaviour during operation > Fault lock-out or restart 30
Restart following flame failure Parameter 12 = 1: Restart following flame failure.
If the PFU detects a flame failure after a minimum operating time of 2 s, the valves are closed and the operation signalling contact is opened within time tSB.
The burner control unit now attempts to restart the burner once. If the burner does not function, a fault lock-out occurs. The display blinks and shows the cause of the fault.
In accordance with EN 746-2, a restart may be conducted only if the safety of the installation is not impaired. Restart is recommended for burners which occasionally display unstable behaviour during operation.
The precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases). In this case, it must be ensured that the program sequence started by the PFU matches the application.
1x
4 1 4 88 30a 26e 10e
>2 s
tZ tFS
28c 26a 16c V1 2c–4c 2e–4e
t
tW tSA
PFU 760 · Edition 05.11
31
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
4 .6 Switchable gas valve V2 on PFU . .L Parameter 26
Parameter 26 = 0: Gas valve V2 opens with the operating signal.
Parameter 26 = 1: Gas valve V2 opens with the air valve during operation
A switchable gas solenoid valve V2 can be activated with the PFU..L. If Parameter 26 is set to 1, gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a/12a).
L1, N, PE
DI P
SPS PLC API
DI P A 1
PFU 760L 22a 10c 26e 30e 10a 10e 2e 4e
µC 2c 4c
22e 18e 16c 28c 26a
TZI
VBY
VAG
4
7 M
BVA + IC 40
PFU 760 · Edition 05.11
32
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
4 .7 Air valve control PFU . .L Parameter 30, Behaviour of the air valve during operation
Parameter 31, Behaviour of the air valve during start-up
Parameter 32, Behaviour of the air valve in the event of a fault lock-out
The PFU..L features an adjustable air valve control. The display shows that purging is currently being carried out with 0 . A indicates that the air valve is being activated for cooling or heating.
The PFU..L supports the following functions:
– Purge
– Cooling in start-up position/standby
– Switching of the burner between low and high burner output during operation via the air valve
– To start up the burner as intended, external activation of the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system).
– Controlling the air valve so that it
– opens with valve V1
– opens with valve V2
– Low fire over run time tKN after a controlled shut-down
4 .7 .1 Purge Parameter 42 = 0: The air valve is closed when voltage is applied to terminal 30e.
Parameter 42 = 1: The air valve is opened when voltage is applied to terminal 30e.
In the case of multiple burner applications, burners with mechanical combustion air supply are used. The air for com- bustion and pre-purge is supplied by a central fan controlled by a separate logic. This logic determines the purging time.
The PFU..L supports centrally-controlled pre-purge or post- purge. The PFU..L is informed that purging is currently being performed by input 30e. It then opens the air valve, regard- less of the status of the other inputs (purging has priority). The
display indicates 0 .
4 .7 .2 Cooling in start-up position/standby The air valve can be activated externally via input 10a for cool- ing in the start-up position. During activation of the air valve
the display shows A0 , indicating that cooling is currently being carried out.
4 .7 .3 Burner start Parameters 30 and 31 determine the behaviour of the air valve during burner start.
PFU 760 · Edition 05.11
33
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
4 .7 .4 Air valve opens in the case of external activation (not during start-up)
Parameter 30 = 0: The air valve opens if it is activated exter- nally by input 10a.
Parameter 31 = 0: The air valve remains closed during start-up even if it is activated externally.
These settings are required on burners on which the gas/air ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire, e.g. on two-stage- controlled burners. In this case, activation of the air valve during burner start via input 10a must be prevented.
External control allows switchover between low fire and high fire during operation.
The air valve can be activated externally via input 10a for cool- ing the burner in the start-up position/standby.
4 88 30a 26e 10e
10a
28c 26a 16c V1 18e V2
A
tZ
tSA
tFS
22e 2c–4c 2e–4e
t
L1 PFU 760L
A
P
SPS PLC API
TZI
GIK..B
VAS..N
VR..R
PFU 760 · Edition 05.11
34
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
4 .7 .5 Air valve opens in the case of external activation (even during start-up)
Parameter 30 = 0: The air valve opens if it is activated exter- nally via input 10a.
Parameter 31 = 1: The air valve can be activated even during start-up.
These settings may be selected only if the burner can start with full air capacity.
The air valve can be activated externally via input 10a for cool- ing the burner in the start-up position/standby.
4 88 30a 26e 10e 1 28c 26a 16c V1 18e V2
22e 2c–4c 2e–4e
10a A
tZ
tSA
tFS t
L1 PFU 760L
A
P
SPS PLC API
TZI
VG..L EKO
GEH
BICR VR..R
LEH EKO
PFU 760 · Edition 05.11
35
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
4 .7 .6 Air valve opens with valve V1 Parameter 30 = 1:
The air valve opens simultaneously with valve V1.
Application: Single-stage-controlled burner is switched ON/OFF via the input.
The air valve can be activated externally via input 10a for cool- ing the burner in the start-up position/standby.
4 88 30a 26e 10e 1 28c 26a 16c V1 18e V2
22e 2c–4c 2e–4e
10a A
tZ
tSA
tFS t
L1 PFU 760L
A
P
SPS PLC API
TZI
VG..L EKO
GEH
BICR VR..R
LEH EKO
PFU 760 · Edition 05.11
36
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
4 .7 .7 Air valve opens with valve V2 Parameter 30 = 2:
The air valve opens simultaneously with valve V2.
Application: Two-stage-controlled burner is switched ON/OFF via the input.
The air valve can be activated externally via input 10a for cool- ing the burner in the start-up position/standby.
A
4 88 30a 26e 10e 28c
16c V1 18e V2 10a 22e
26a
2e–4e 2c–4c
tZ
tSA
tFS t
L1 PFU 760L
A
P
SPS PLC API
TZI
VAG
VR..R
PFU 760 · Edition 05.11
37
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
4 .7 .8 Low fire over run time tKN after a controlled shut-down Parameter 36
Settings: 0; 3; 5; 10; 15; 25 or 60 (low fire over run time in seconds)
This parameter is applicable to systems with a pneumatic ratio control system and On/Off control.
Parameter 36 = 0 (low fire over run time tKN = 0 s): Without low fire over run, the gas side is closed immediately owing to the quick-closing gas valve in the case of On/Off control. The air side closes more slowly. The air flowing in during the closing time increases the O2 content in the combustion chamber.
Parameter 36 = 3; 5; 10; 15; 25 or 60 (low fire over run time tKN = 3, 5, 10, 15, 25 or 60 s): The air valve closes slowly after the activation signal has been switched off. The gas valve remains open for tKN. This means that the burner, after deactivation of the start-up signal ( ), is initially adjusted down to low fire and then switched off completely.
Using the low fire over run function reduces the O2 content in the furnace atmosphere.
Flame control is still operational. Can be used only in the case of a pneumatic air/gas ratio control system and On/Off control. Its must be ensured that no excess gas occurs.
4 88 30a 26e
tKN
28c 16c V1 26a 2c–4c 18e V2 22e 2e–4e
t
10e
L1 PFU 760L
A
P
SPS PLC API
TZI
VAG
VR..R
PFU 760 · Edition 05.11
38
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
4 .7 .9 Behaviour of the air valve in the event of a fault lock-out Parameter 32
This determines whether the air valve can be activated in the case of a fault lock-out.
Parameter 32 = 0:
The air valve is closed in the event of a fault. It cannot be activated externally via terminal 10a.
Parameter 32 = 1:
The air valve can be activated externally via input 10a even during a fault, e.g. for cooling.
PFU 760 · Edition 05.11
39
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
4 .8 Manual operation For convenient setting of the burner or analyzing faults.
The parameter display is not available in Manual mode. Manual mode can be accessed only if the unit was not in Fault state before switching off. The following times/functions are not active in Manual mode: start-up attempts, restart, minimum combustion time and cycle lock.
If the Reset/Information button is pressed for 2 s during switch- on, the PFU reverts to Manual mode. Two dots blink on the display.
In this operating mode, the burner control unit operates inde- pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks. These are of higher priority and will be processed first).
Each time after the button is pressed again, the PFU moves to the next section of the program sequence and stops there. After approx. 3 s, the flame signal will be displayed instead of the program parameter. Briefly pressing the Reset/Informa- tion button (< 1 s) displays the relevant Manual mode step. If there is flame simulation during the start-up, the flame signal is displayed immediately.
On units with air valve control, the air valve can be opened and closed repeatedly by pressing the button during operation.
Manual mode can be terminated by switching off the PFU (On/Off button).
4 .8 .1 Manual mode limited to 5 minutes Parameter 34
Parameter 34 determines when Manual mode is terminated.
Parameter 34 = 0: Manual mode is not limited in time. If this function has been selected, operation of the furnace may be continued manually in the event of failure of the central control system.
Parameter 34 = 1: Manual mode ends automatically five minutes after the last time the button was pressed. The PFU then moves abruptly back to start-up position/standby.
4 .9 Password Parameter 50
(Four-digit) password saved to protect parameter settings. To prevent unauthorized changes to parameter settings, a password is stored in parameter 50. Changes to parameter settings can only be made once this number has been entered. The password can be changed using BCSoft.
Note the effect of parameter settings on the safe functioning of your system.
The password set at the factory can be found in the delivery note supplied.
PFU 760 · Edition 05.11
40
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
4 .10 Multi-flame control Parameter 45
Parameter 45 = 0: Multi-flame control is switched off.
Parameter 45 = 1: Multi-flame control is switched on. The parameter must be set to 1 to ensure that the flames are monitored.
( PFU 760L)
L1
N
2e
30e 3 2a 2 UVS
1
30a
32c
30e
2a
230V
2e
L1 (L1) 30e PFU 760
22e N
26a UVS 2 20c
1 F1 sk1
6a 3 24c
16c
18e V1
Z Z I
N N
L1
4c
4e
6e
26e
22a V2
N
28c
N (L2) 30a
L1
8e
30e 3 8a 2 UVS
1 8a
230V
8e
12a 32c 24c
20c a 2a 4a
10c 230 V
28c s 2e 4e
Z Z I
N N
10e
12e
N Z I
L1 L1 26a
m 2c 4c
18e 18a
230V
18e
22a
30e 3 18a 2 UVS
1
Z Z I
N N
L1 L1
20c
20e
22e
24e
0 V
24 V
0 V
30e 3
24a
230V
24e
28a 24a 2 UVS
1
Z Z I
N N
L1 L1
26c
26e
28e
PFF 704 24 V
8a
8c
8e
10e
12e
10a
12a
10c
12c
µC
A
S
SK
P
DI
1
A
ma
x. 1
A, 2
4 V
PFU 760 · Edition 05.11
41
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
5 Selection
5 .1 Safety time Please quote the safety time tSA when ordering.
tSA = 3 s, 5 s or 10 s
PN = Rated heat output
PZ = Ignition capacity
The safety time of the burner control unit depends on the burner type, the burner output and the respective application.
EN 746-2
PN
≤ 70 kW
> 70 kW*
tSA
5 s
3 s
≤ 350 kW 10 s
> 350 kW** 5 s
0 ³ ∞* 10 s
* PZ 0,1 x PN, P Zmax = 350 kW
** PZ 0,33 x PN, P Zmax = 350 kW
5 .1 .1 Calculating the safety time tSA
Burner with mechanical combustion air supply Natural draught burner with direct ignition
Natural draught burner with pilot burner
Burner output 1.00kW Safety time
on start-up tSA 3s
Ignition burner input rating at a level of 10 % of nominal heat input with a maximum of 350 kW.
PFU 760 · Edition 05.11
42
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
5 .2 Selection table
Type L* T N D* U* K1* K2* PFU 760
* If “none”, this specification is omitted.
= standard, = available
Order example PFU 760LT
5 .3 Type code
Mains voltage
T 220 – 240 V AC, -15/+10%, 50/60 Hz
N 110 – 120 V AC, -15/+10%, 50/60 Hz
D* Digital input to interrupt flame control
U* Preparation for UV sensor for continuous operation UVD 1
K1* Compatible with PFS/PFD
K2* PFU 778
* If “none”, this specification is omitted.
Code Description
L* Air valve control
PFU 760 · Edition 05.11
43
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
6 Project planning information
6 .1 Cable selection Use mains cable suitable for the type of operation and com- plying with local regulations. Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields.
6 .1 .1 Ignition cable Use unscreened high-voltage cable see page 49 (Accessories). Cable length: max. 5 m, recommended < 1 m. Screw the igni- tion cable securely into the ignition transformer and run to the burner by the shortest possible route.
The longer the ignition cable, the lower the ignition capacity. Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces- sories). Do not lay UV/ionization cable and ignition cables together and lay them as far apart as possible.
6 .1 .2 Ionization cable Use unscreened high-voltage cable see page 49 (Accessories). Cable length: max. 100 m. Avoid external electrical interfer- ence. Install as far as possible from mains and ignition cables and interference from electro-magnetic sources. If possible, do not lay in a metal conduit. Several ionization cables can be routed together.
6 .1 .3 UV cable Cable length: max. 100 m. Avoid external electrical interference. Install as far as possible from mains and ignition cables and interference from electro-magnetic sources. If possible, do not lay in a metal conduit. Several UV cables can be routed together.
6 .2 Ignition electrode
6 .2 .1 Electrode gap Gap between electrode and burner ground: 2 mm ± 0.5 mm.
6 .2 .2 Star electrodes We recommend using 7.5 kV ignition transformers on burners with star electrodes.
PFU 760 · Edition 05.11
44
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
1
6 .3 Minimum combustion time Even if the start-up signal () is applied only briefly, the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a fault.
The minimum combustion time tB can be extended beyond the safety time tSA to max. 25 s.
6 .4 Safety interlocks (Limits) The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application, e.g. safety temperature limiter, minimum and maximum gas pressure, tightness control) must isolate ter- minal 26e from the voltage supply. If the safety interlock is interrupted, this is indicated by a blinking on the display.
If the safety interlocks fail, an immediate program abort with switch-off of all outputs occurs (even during the safety time). If the safety interlocks are operational again or the unit is switched back on, the program run is restarted in standby.
6 .5 Emergency stop
6 .5 .1 In the event of fire or electric shock If there is a risk of fire, electric shock or similar, inputs L1, N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply – this should be reflected in the wiring on site.
6 .5 .2 Via the safety interlocks (limits) The safety interlock turns off the power to input 26e, such as in the event of air deficiency or similar.
PFU 760 · Edition 05.11
45
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
10
6 .6 Reset
6 .6 .1 Parallel reset Several burner control units can be reset in parallel using the external button. The PFU cannot be reset by mains failure.
6 .6 .2 Permanent remote reset Permanent remote reset gives rise to a malfunction. If a remote reset signal is permanently applied to terminals 10c/12c, flashes on the display to indicate a fault.
Reset with a pulse < 1 s.
6 .6 .3 Automatic remote reset (PLC) In the case of automatic remote reset (PLC), the reset pulse duration should not exceed 1 second. Check compliance with standards.
If a fault is acknowledged by remote reset too often, error (Too many remote resets) is displayed. The error can only be acknowledged with the Reset/Information button on the unit.
The burner malfunction must be remedied. The malfunction can not be remedied by changing the method of activation.
6 .6 .4 Burner start A furnace start may only be initiated, if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustion/processing chamber, in the con- nected areas or in the exhaust gas system (heat exchanger, dust collector). This can be achieved by pre-purge, which occurs immediately before ignition or within the period speci- fied in the operating instructions.
In the case of multiple burner applications, pre-purge is not necessary after a controlled burner shut-down.
Note the requirements of the Standards. For exceptions, see Standards.
6 .6 .5 Restart and start-up attempts The precondition for a restart/start-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases). In this case, it must be ensured that the program sequence started by the PFU matches the application.
Note the requirements of the Standards. For exceptions, see Standards.
PFU 760 · Edition 05.11
46
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
6 .7 Fault signalling The fault signalling contact opens, as soon as the mains volt- age fails.
6 .8 Protecting the burner from overload To protect the unit against overload by frequent cycling, the maximum number of start-ups per minute is limited for the PFU. Excessive cycling triggers a fault message (blinking ). The max. number of start-ups per minute depends on the safety time tSA:
tSA [s] Ignition transformer TZI Max. start-ups/min.
3 5-15/100 6
5 5-15/100 5
10 5-15/100 4
6 .9 Installation Installation position: any.
Installation in 19" module subracks only, see page 50 (Module subracks).
Install in clean environment ensuring enclosure IP 54 or higher, whereby no condensation is permitted.
Cable length between PFU and burner: max. 100 m.
6 .10 Wiring The PFU is suitable for hard wiring only. Do not reverse phase and neutral conductor. Different phases of a three-phase current system must not be installed at the PFU. No voltage may be connected to the valve and ignition outputs.
6 .10 .1 UVS sensor wiring Connect the UVS sensor directly to the PFU. Operating the sensor with incorrect polarity or voltage can lead to destruc- tion of the sensor.
6 .11 PFU switched off The PFU cannot be activated when no mains voltage is applied or when it is switched off. The fault signalling contact is only closed when the unit is supplied with voltage and switched on.
If the unit is switched off, an immediate program abort with switch-off of all outputs occurs (even during the safety time). When the unit is switched on, the program run is restarted in standby.
PFU 760 · Edition 05.11
47
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
6 .12 Furnace control Switch on the system to start up the furnace, then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended. To shut down the furnace, first disconnect the burner control unit from the temperature control (burner ON signal), then disconnect the safety interlocks and finally switch off the system.
6 .13 Note on EC type-examination Since EN 298 (1993) does not describe all functions of the PFU, the operator is responsible for ensuring that all parameters and functions are matched to the respective application.
6 .14 Mains switch The mains switch in the unit isolates the PFU on two poles from the mains. It does not meet the requirements of EN 50156- 1:2004 (5.2.2 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply. Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156, it does allow the burner to be isolated functionally from the central control system. This function is required for manual operation and, in the case of PROFIBUS units, to switch off the unit without causing BUS errors. Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only, in accordance with Standard EN 50156.
6 .15 Changing parameters In certain cases, it may be necessary to change the default settings. Using a separate software package and a PC opto- adapter, it is possible to modify certain parameters on the PFU, such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failure.
The software package with PC opto-adapter, as well as “Changed parameters” stickers, are available as accesso- ries – see section entitled “Accessories”.
The unit parameters set at the factory are specified in the delivery note.
Document changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentation.
If a replacement is ordered for a PFU with changed parameters, refer to the protocol for details.
PFU 760 · Edition 05.11
48
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
7 Flame control
7 .1 With ionization sensor The PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground. The flame rectifies this voltage. Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signal.
A flame cannot be simulated. Ignition and monitoring with a single electrode is possible.
7 .2 With UV sensor A UV tube inside the UV sensor detects the ultraviolet light of a flame. It does not respond to sunlight, incandescent bulb light or infrared radiation emitted by hot workpieces or red- hot furnace walls.
In the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage. As with ionization control, the burner control unit only detects this DC signal.
When using UV sensors of Type UVS, the burner control unit may be used for intermittent operation only. This means that operation must be interrupted at least once every 24 hours. This can be programmed using parameter 35.
For further information, see brochure UVS.
The burner control unit PFU..U is prepared for UV sensor UVD 1. This enables continuous operation. For further information, see Technical Information Bulletin UVD.
7 .3 Via the temperature in high temperature equipment High temperature equipment is defined as a thermoprocessing installation, in which the wall temperature of the combustion chamber and/or the processing chamber exceeds 750°C. Burner control unit PFU..D features a special “High temperature operation” function. During heating up, standard monitoring methods (ionization or UV) must be used for flame control. When the working temperature has exceeded 750°C, indirect flame control can be taken over by a central monitoring device. When the DI input (terminal 22a) is activated, the burner control unit reverts to this operating mode.
Important: In “High temperature operation”, i.e. with the DI input being activated, burner control unit PFU..D does not evaluate the flame signal. The safety function of the burner control unit’s flame control is deactivated during this operat- ing phase.
PFU 760 · Edition 05.11
49
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
8 Accessories
8 .1 High-voltage cable FZLSi 1/7 up to 180°C,
Order No.: 04250410.
FZLK 1/7 up to 80°C, Order No.: 04250409.
8 .2 BCSoft
8 .3 Stickers for labelling
For printing with laser print- ers, plotters or engraving machines, 27 × 18 mm or 28 × 17.5 mm.
Colour: silver
8 .4“Changed parameters” stickers Affix on the connection diagram of the PFU following changes to unit parameters set at the factory.
100 pcs, Order No.: 74921492.
Opto-adapter including BCSoft CD-ROM, Order No.: 74960437.
The current software can be downloaded from our Internet site at www.docuthek.com. To do so, you need to register in the DOCUTHEK.
D-49018 Osnabrück, Germany
Achtung, geänderte Parameter! Die Angaben auf dem Typenschild gelten nicht mehr in vollem Umfang. Aktuelle Parameter direkt auslesen.
Important, changed parameters! The details on the type label are no longer completely accurate. Read the current parameters direct from the unit.
Attention, paramètres modifiés ! Les informations figurant sur la plaque signalétique ne sont plus valables dans leur intégralité. Veuillez vous référer directement aux paramètres actualisés.
PFU 760 · Edition 05.11
50
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
8 .5 Radio interference suppressed electrode adapters Plug cap, 4 mm, interference-suppressed, Order No. 04115308.
Straight adapter, 6 mm, interference-suppressed, Order No. 04115306.
8 .6 Socket connectors
Type Order No.
Socket connector E, 48-pin solder tag connection 04120148
Socket connector E, 48-pin wire-wrap connection 04120158
8 .7 Module subracks
Module subracks BGT S-9U/1 for PFP 700, PFU 760 comprising: module subrack, printed-circuit board with rear terminal strip, function-tested, standard documentation, guide rails, without partial front plates, screw terminals at the rear.
Slots 1–9 for PFU 760, slot 10 for PFP 700
Order No. 84402281.
Module subrack BGT SM-8/1/1 for MPT 700, PFU 760 comprising: module subrack, printed-circuit board with rear terminal strip, function-tested, standard documentation, guide rails, without partial front plates, screw terminals at the rear, single-zone operation for MPT 700 operating modes 1-4, two- zone operation for MPT 700 operating modes 1-4, but max. 4 burners per zone.
Slot 1 for MPT 700, slots 2–9 for PFU 760, slot 10 for PFP 700
Order No. 84402282 (no illustration provided).
Module subrack BGT SA-9U/1DP for PFA 700, PFU 760 comprising: module subrack, printed-circuit board with rear terminal strip, function-tested, standard documentation, guide rails, without partial front plates, screw terminals at the rear, relays and screw terminals for four free inputs and four free outputs.
Slot 1 for PFA 700, slots 2–10 for PFU 778 without digital input, connection to PROFIBUS-DP with D-Sub socket.
Order No. 84402283 (no illustration provided).
PFU 760 · Edition 05.11
51
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
8 .8 Power supply PFP 700 For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704. Operating status display on the front plate. PFP switches off in the event of an output overload.
Output voltage 24 V, output rating 14 VA.
PFP 700
S0
S1
L1 30a F1 O
I
230 V
115 V
8ace
N 32c
24 V= 600 mA
12ace 0 V
U I
PFU 760 · Edition 05.11
52
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
8 .9 Relay module PFR 704 For contact multiplication, e.g. if several air valves are activated via one control signal for pre-purge, or for heating/cooling switchover when using an MPT. Switching status display on the front plate.
Input voltage: 110/120 V AC, -15/+10%, 50/60 Hz, 220/240 V AC, -15/+10%, 50/60 Hz, 24 V AC/DC, ± 10%.
Current per relay: 25 mA.
Contact rating of floating outputs: max. 2 A, 264 V (not fused internally).
PFR 704 230 V~ 2e 115 V~ 2a 24 V=/~ 2c
1
0 V 4e
230 V~ 10e 115 V~ 10a 24 V=/~ 10c
2
0 V 12e
230 V~ 18e 115 V~ 18a 24 V=/~ 18c
3
0 V 20e
230 V~ 26e 115 V~ 26a 24 V=/~ 26c
4
0 V 28e
6a 6e
8a 8e
8c
6c
16a 16e
14a 14e
14c
16c
24a 24e
22a 22e
22c
24c
32a 32e
30a 30e
30c
32c
ma
x. 2
A, 2
64
V
ma
x. 2
A, 2
64
V m
ax.
2 A
, 26
4 V
m
ax.
2 A
, 26
4 V
PFU 760 · Edition 05.11
53
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
8 .10 Flame detector PFF 704 For flame detection or multi-flame control in conjunction with PFU, with 4 independent flame detectors. For intermittent op- eration with ionization or UV control.
Power consumption: 10 VA.
Ionization voltage: 230 V AC.
Max. flame signal cable length: 100 m.
Cut-off sensitivity of the flame amplifiers: adjustable between 1 µA and 10 µA (factory default setting: 1 µA).
Contact rating: max. 2 A.
Mains voltage: 110 – 240 V AC, 15/10%, 50/60 Hz.
Further information can be found in brochure PF 19”.
PFF 7x4 S0 O
L1
N
2 3
30a
32c
30e
2a
230V
2e
I S1 230 V
115 V
2e 2a 30e
1 UVS - +
Z Z I
N N F1
L1
1
L1 P1 F2
8e 8a 30e
2 UVS 1
3
8a
230V
8e
- +
Z Z I F3 N
N 2 P2
L1 L1 F4
18e 18a 30e
2 UVS 1
3
18a
230V
18e
- +
6a
6c
4a
4c
4e
6e
12a
12c
10a
10c
10e
12e
22a
22c
20a
20c Z Z I
N N
3 P3 L1 L1
F6
24e 24a 30e
2 UVS 1
3
24a
230V
24e
- +
F5 20e
22e
28a
28c
26a
26c Z Z I
N N
4
F7
L1 P4
L1 F8
26e
28e P1–P4: PFF 704
ma
x.
2 A
, 2
64
V
ma
x.
2 A
, 2
64
V
ma
x.
2 A
, 2
64
V
ma
x.
2 A
, 2
64
V
PFU 760 · Edition 05.11
54
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
8 .11 Field bus interface PFA 700 For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP, in order to transfer measuring, control and regulation signals as a bundle.
4 digital inputs: 24 V DC, ± 10%, < 10 mA, 4 digital outputs: relay contact, max. 1 A, 264 V (not fused internally).
Mains voltage: 110 – 240 V AC, -15/+10%, 50/60 Hz.
Further information can be found in brochure PFA.
PFA 700 L1 32b
N 30a
15b 24 V=
16b 0 V
C
VP 8b
RxD/TxD-P 11b
RxD/TxD-N 12b
2
24 V 18b 1
24 V 21b
0 V 22b 4
1c
9c
10c
18c
1a
9a
10a
18a
19a
23a
20c
23c
19c
17b
24 V
30c
1. PFU
9. PFU
1. PFU
9. PFU
DGND 14b 1. PFU
9. PFU
1. PFU
9. PFU
I/O
24 V 23b 1
24 V 26b 4
1. PFU
5. PFU
6. PFU
9. PFU
PFU
1
L1 30e
26e PFU
…
…
…
…
PR
OF
IBU
S D
P
…
…
…
… …
…
PFU 760 · Edition 05.11
55
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
8 .12 Impulse system MPT 700 With 11 outputs for activation of burner control units PFU 780. The furnace atmosphere is circulated thanks to intermittent operation, and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensured.
Mains voltage: 95 – 240 V AC, ± 10%, 50/60 Hz.
Power consumption: 10 VA.
Additional auxiliary voltage: 12 – 24 V DC, ± 10%, max. 1.1 A.
Controller inputs: 2 x 0(4) – 20 mA with common ground, float- ing, load impedance approx. 225 Ω.
Three-point step input: floating, 12 – 24 V DC, load impedance approx. 2.7 kΩ.
Digital inputs E1 – E3: with common ground, floating, 12 – 24 V DC, load impedance approx. 2.7 kΩ.
Further information can be found in brochure MPT.
L1
MPT 700 30z
F1
N
PE
30b
30d
28z
28b
28d
32z
32b
32d
2b
4b
10b
12b
12–24 V
0 V
8888
mA 1
mA 2
GND
20z
20b
20d
88
0 – 100%
GND
100% – 0
18z
18b
18d
2z
2d
4z
4d
6z
6d
8z
8d
A1
A2
A3
A4
A5
A6
A7
A8
12–24 V E1
14z
E2
10z
10d
/ 1
/ 2 14d
E3 µC 12z
0 V
16z
14b
16b
6b
8b COM
PFU 760 · Edition 05.11
56
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
9 Technical data Mains voltage: 220/240 V AC, -15/+10%, 50/60 Hz or 110/120 V AC, -15/+10%, 50/60 Hz, for grounded and ungrounded mains.
Power consumption: < 8 VA.
Control inputs: Input voltage/current: Burner, air valve, multi-flame control and remote reset: 24 V DC, ± 10%, < 7 mA per input.
Input voltage for safety interlocks, digital input DI and purge = mains voltage.
Input voltage of signal inputs:
Rated value 110/120 V AC 220/240 V AC
Signal “1” 80 – 132 V 160 – 264 V
Signal “0” 0 – 20 V 0 – 40 V
Frequency 50/60 Hz 50/60 Hz
Rated value 24 V DC
Signal “1” 24 V, ±10%
Signal “0” < 1 V
Inherent current:
Output voltage for voltage-related outputs = mains voltage
Contact rating
Gas valve V1, V2 Max. 1 A resistive Max. 1 A cos 0.3
Air valve Max. 1 A resistive Max. 1 A cos 0.3
Ignition Max. 1 A resistive Max. 1 A cos 0.3
Number of oper- ating cycles
Max. 1,000,000, typically 400,000
Max. 250,000, typically 100,000
Output current: max. 2 A per output, but total current for valves and ignition transformer max. 2.5 A.
Number of operating cycles: Mains switch: 1000, Reset/Information button: 1000.
typ. 5 mA Signal “1”
t
PFU 760 · Edition 05.11
57
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
Signalling contacts: max. 24 V, 1 A.
Flame control: Sensor voltage: approx. 230 V AC. Sensor current: > 1 μA, Length of sensor cable: max. 100 m.
Fuse in unit:
F1: 3.15 A, slow-acting, H pursuant to IEC 127-2/5, F2: 3.15 A, slow-acting, H pursuant to IEC 127-2/5.
Ambient temperature:
-20 to +60°C (-4 to +140°F), Climate: no condensation permitted.
Enclosure: IP 00 pursuant to IEC 529,
after installing in a 19" module subrack according to the in- structions, e.g. type BGT, the front corresponds to IP 20.
Input/Output safety circuit:
All the inputs and outputs marked “ ” (see connection dia- grams) may be used for safety tasks.
Weight: approx. 650 g (23 oz)
PFU 760 · Edition 05.11
58
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
9 .1 Safety-specific characteristic values
In the case of ionization control, suitable for Safety Integrity Level
SIL 3
Diagnostic coverage DC 97.9%
Type of subsystem Type B to EN 61508-2, 7.4.3.1.4
Mode of operation High demand mode pursu- ant to EN 61508-4, 3.5.12
Mean probability of dan- gerous failure PFHD
1.34 x 10-8 l/h
Mean time to dangerous failure MTTFd
Safe failure fraction SFF 99.2%
The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic).
Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)
PL SIL
a –
b 1
c 1
d 2
e 3
Pursuant to EN ISO 13849-1:2006, Table 4, the PFU can be used up to PL e.
Max. service life under operating conditions:
20 years after date of production, plus max. 1/2 year in stor- age prior to first use.
For a glossary of terms, see page 62 (Glossary).
PFU 760 · Edition 05.11
59
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
9 .2 Operating controls A: 2-digit 7-segment display
B: Reset/Information button to reset the system after a fault or to scan parameters on the display.
C: Mains switch
D: Optical interface
E: Type label
A
B C
D
E
PFU 760 · Edition 05.11
60
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
10 Maintenance cycles Burner control unit PFU requires little servicing.
PFU 760 · Edition 05.11
61
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
1
11 Legend
88 Display
88 Blinking display
Ready
Safety interlocks (Limits)
Burner start-up signal
DI Digital input
Ignition transformer
Gas valve
Air valve
P Purge A Ext. air valve control
Flame signal
Burner operating signal
Fault signal
Reset
Input signal
Output signal
Flame simulation check
tW Waiting time 2 s
tSA Safety time on start-up 3 s, 5 s or 10 s
tSB Safety time during operation < 1 s or < 2 s
tZ Ignition time 2 s, 3 s or 6 s
tLV Flame simulation delay time 25 s
tFS Flame proving period 0 – 25 s
tB Minimum combustion time tSA up to max. 25 s
tBP Minimum burner pause time 0 – 250 s
tKN Low fire over run time 0 s, 5 s, 15 s or 25 s
Input/Output safety circuit
PFU 760 · Edition 05.11
62
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
12 Glossary
12 .1 Waiting time tW
12 .4 Flame simulation/Flame simulation delay time tLV
Once the start-up signal has been applied, the waiting time tW starts to elapse. During this time, a self-test is conducted to detect errors in internal and external circuit components. If no malfunction is detected, the burner will start up.
12 .2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve, when no flame signal is detected. The safety time on start-up tSA (3, 5 or 10 s) is the minimum operating time of the burner and burner control unit.
12 .3 Ignition time tZ If no malfunction is detected during the waiting time tW, the
An extraneous signal (flame simulation) is a flame signal that is detected, although there should be no flame according to the program sequence. If such an extraneous signal is detected, the flame simulation delay time tLV starts to elapse. If the flame simulation is discontinued during the flame simu- lation delay time tLV, start-up can be initiated or operation continued. Otherwise, a fault lock-out occurs.
12 .5 Safety time during operation tSB
ignition time tZ then starts to elapse. Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited. The duration of the ignition time is either 2, 3 or 7 seconds (depending on safety time tSA selected).
If the flame fails during operation, the valve outputs are dis- connected within the safety time tSB.
t
01 0
30e 10e 28c 16c 26a 18e
2c–4c 2e–4e
88 L1
V1
V2
tW tZ
tSA
t
01 01 30e 10e 28c 16c 26a 18e
2c–4c 2e–4e
88 L1
V1
V2
tW t
tLV
04 04 30e 10e 28c 16c 26a 18e
2c–4c 2e–4e
88 L1
V1
V2
tSB t
PFU 760 · Edition 05.11
63
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
The default safety time during operation tSB in accordance with EN 298 is 1 second. In accordance with EN 746-2, the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see “Project plan- ning information”). Note the requirements of the Standards!
12 .6 Flame signal If a flame is detected, the flame detector will supply a flame signal.
12 .7 Fault lock-out In the event of a fault lock-out, all valves and the ignition trans- former are disconnected from the electrical power supply, and a fault is signalled. Resetting must take place manually following a fault lock-out.
12 .8 Safety interlocks (Limits) The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application, e.g. safety temperature limiter, minimum/maxi- mum gas pressure) must isolate input from the voltage supply.
12 .9 Pilot gas valve V1 The start fuel flow rate for the burner is released by pilot gas valve V1. It opens when the safety time on start-up tSA starts to elapse. It remains open until the burner is switched off again by a normal shut-down or fault lock-out.
12 .10 Main gas valve V2 Once the safety time on start-up tSA has elapsed, the main gas valve V2 is opened. It remains open until the burner is switched off or a fault is signalled.
12 .11 Continuous operation The gas burner runs continuously for more than 24 hours.
12 .12 Air valve The air valve can be used
– for cooling,
– for purging,
– to control the burner output in ON/OFF mode and in High/ Low mode when using a pneumatic air/gas ratio control system.
( PFU 760L)
L1 (L1) 30e PFU 760
22e N
F1 sk1 16c
26e 18e V1
DI
22a V2
30a N (L2)
32c 24c
a 2a
4a
P
PFU 760 · Edition 05.11
64
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
12 .13 Diagnostic coverage DC Measure of the effectiveness of diagnostics, which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failures
NOTE: Diagnostic coverage can exist for the whole or parts of a safety-related system. For example, diagnostic cover- age could exist for sensors and/or logic system and/or final elements. Unit: %.
from EN ISO 13849-1:2008
12 .14 Mode of operation High demand mode or continuous mode
Operating mode, where the frequency of demands for opera- tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequency
from EN 61508-4:2001
12 .15 Safe failure fraction SFF Fraction of safe failures related to all failures, which are as- sumed to appear
from EN 13611/A2:2011
12 .16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode. Unit: 1/h
from EN 13611/A2:2011
12 .17 Mean time to dangerous failure MTTFd
Expectation of the mean time to dangerous failure
from EN ISO 13849-1:2008
PFU 760 · Edition 05.11
65
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]
บริษัท: บริษัท เอดีดี เฟอร์เนส จ ำกัด Add Furnace Co.,Ltd.
ท่ีอยู่:(bangkok) 44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170.
website: https://www.add-furnace.com/
e-mail: [email protected] [email protected]
โทร.(ออกแบบ): 08-08-170-170, 088-300-1122
โทร: 02-888-3472
Online Support: Line ID: @add11 Wechat ID: add0883001122
แฟกซ์: 02-888-3258
line ID: @add11