67
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวัฒนา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected] For directly ignited burners of unlimited capacity in intermittent operation or in continuous operation pursuant to EN 746-2 Plug-in function unit for mounting in 19" module subracks Flame control by UV, ionization or a further option of using the furnace chamber temperature Display of the program status, unit parameters and flame signal; Manual mode for burner adjustment and for diagnostic purposes Visualization and adaptation to the specific application via the PC programming and diagnostic software BCSoft to simplify logistics management Air valve control relieves the furnace control Connection to PROFIBUS-DP via field bus interface PFA Certified for systems up to SIL 3 and compliant with PL e Burner control unit PFU 760 Technical Information ·GB 6.2.1.4 Edition 05.11

Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

• For directly ignited burners of unlimited capacity in intermittent operation or in continuous operation pursuant to EN 746-2

• Plug-in function unit for mounting in 19" module subracks

• Flame control by UV, ionization or a further option of using the furnace chamber temperature

• Display of the program status, unit parameters and flame signal; Manual mode for burner adjustment and for diagnostic purposes

• Visualization and adaptation to the specific application via the PC programming and diagnostic software BCSoft to simplify logistics management

• Air valve control relieves the furnace control

• Connection to PROFIBUS-DP via field bus interface PFA

• Certified for systems up to SIL 3 and compliant with PL e

Burner control unit PFU 760

Technical Information · GB

6.2.1.4 Edition 05.11

Page 2: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

2

PFU 760 · Edition 05.11 = To be continued t

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

Contents Burner control unit PFU 760 . . . . . . . . . . . . . . . . . . . . . . . . . 1 Contents . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.1 Examples of application .................................................... 6

1.1.1 Staged On/Off burner control ................................................. 6 1.1.2 Staged High/Low burner control .............................................7 1.1.3 Two-stage-controlled burner .................................................. 8 1.1.4 Modulating-controlled burner ................................................ 9 1.1.6 PFU for PROFIBUS-DP with PFA 700 .................................... 10 1.1.5 PFU 760..D: High temperature equipment.......................... 10

2 Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

3 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 3.1 Connection diagram ....................................................... 12

3.1.1 PFU 760 ............................................................................... 12 3.1.2 PFU 760..K1 ......................................................................... 13 3.1.3 PFU 760..K2 ......................................................................... 14

3.2 PFU 760 program sequence .......................................... 15 3.3 Program status and fault messages .............................. 17

4 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 4.1 Scanning the parameters ............................................... 19 4.2 Flame control ................................................................. 20

4.2.1 Burner flame signal .............................................................. 20 4.2.2 Program status when the most recent fault occurred. . . 20 4.2.3 Switch-off threshold of the flame amplifier ....................... 20 4.2.4 High temperature operation with PFU..D ........................... 21 4.2.5 UVS check ......................................................................... 24

4.3 Behaviour in start-up position/standby ........................ 25 4.3.1 Flame simulation check in start-up position/standby . . . 25 4.3.2 Minimum burner pause time tBP ................................................... 26

4.4 Behaviour during start-up ............................................. 27 4.4.1 Safety time on start-up tSA ................................................................. 27 4.4.2 Flame proving period tFS .................................................................... 27 4.4.3 Minimum combustion time tB ......................................................... 27 4.4.4 Burner start-up attempts .................................................... 28

4.5 Behaviour during operation ........................................... 29

4.5.1

Page 3: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

3

PFU 760 · Edition 05.11 = To be continued t

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

Safety time during operation tSB for V1 and V2 ................... 29 4.5.2 Fault lock-out or restart ...................................................... 29

4.6 Switchable gas valve V2 on PFU..L 31

4.7 Air valve control PFU..L .................................................. 32 4.7.1 Purge ................................................................................. 32 4.7.2 Cooling in start-up position/standby .................................. 32 4.7.3 Burner start ......................................................................... 32 4.7.4 Air valve opens in the case of external activation (not during start-up) 33 4.7.5 Air valve opens in the case of external activation (even during start-up) 34 4.7.6 Air valve opens with valve V1 ............................................. 35 4.7.7 Air valve opens with valve V2 ............................................. 36 4.7.8 Low fire over run time tKN after a controlled shut-down . .37 4.7.9 Behaviour of the air valve in the event of a fault lock-out 38

4.8 Manual operation ......................................................... 39 4.8.1 Manual mode limited to 5 minutes .................................... 39

4.9 Password ................................................................... 39 4.10 Multi-flame control ...................................................... 40

5 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 5.1 Safety time

41 5.1.1 Calculating the safety time tSA

.................................................................................................................................. 4

1

5.2 Selection table ............................................................... 42 5.3 Type code................................................................... 42

6 Project planning information . . . . . . . . . . . . . . . . . . . . . 43

6.1 Cable selection ............................................................... 43 6.1.1 Ignition cable ........................................................................ 43 6.1.2 Ionization cable ................................................................... 43 6.1.3 UV cable ............................................................................ 43

6.2 Ignition electrode .......................................................... 43

6.2.1 Electrode gap..................................................................... 43 6.2.2 Star electrodes ....................................................................43

6.3 Minimum combustion time .......................................... 44 6.4 Safety interlocks (Limits) ............................................... 44 6.5 Emergency stop ............................................................ 44

Page 4: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

4

PFU 760 · Edition 05.11 = To be continued t

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

6.5.1 In the event of fire or electric shock ................................... 44 6.5.2 Via the safety interlocks (limits) ......................................... 44

6.6 Reset .............................................................................. 45 6.6.1 Parallel reset ........................................................................ 45 6.6.2 Permanent remote reset .................................................... 45 6.6.3 Automatic remote reset (PLC) ............................................ 45 6.6.4 Burner start ......................................................................... 45 6.6.5 Restart and start-up attempts ............................................ 45

6.7 Fault signalling ............................................................... 46 6.8 Protecting the burner from overload ............................ 46 6.9 Installation ..................................................................... 46 6.10 Wiring ........................................................................... 46

6.10.1 UVS sensor wiring ........................................................... 46

6.11 PFU switched off ........................................................... 46 6.12 Furnace control ............................................................ 47 6.13 Note on EC type-examination ...................................... 47 6.14 Mains switch ................................................................ 47 6.15 Changing parameters ................................................ 47

7 Flame control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 7.1 With ionization sensor .................................................... 48 7.2 With UV sensor .......................................................... 48 7.3 Via the temperature in high temperature equipment 48

8 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

8.1 High-voltage cable .............................................................. 49

8.2 BCSoft ............................................................................ 49 8.3 Stickers for labelling ...................................................... 49 8.4 “Changed parameters” stickers ..................................... 49 8.5 Radio interference suppressed electrode adapters . 50 8.6 Socket connectors .......................................................... 50

8.7 Module subracks ....................................................... 50 8.8 Power supply PFP 700 ................................................... 51 8.9 Relay module PFR 704 ................................................... 52 8.10 Flame detector PFF 704 ............................................... 53

8.11 Field bus interface PFA 700 .......................................... 54

8.12

Page 5: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

5

PFU 760 · Edition 05.11 = To be continued t

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

Impulse system MPT 700 ............................................. 55

9 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 9.1 Safety-specific characteristic values ............................... 58 9.2 Operating controls ......................................................... 59

10 Maintenance cycles . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

11 Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

12 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

12.1 Waiting time tW ....................................................................... 62 12.2 Safety time on start-up tSA ........................................... 62 12.3 Ignition time tZ .............................................................. 62

12.4 Flame simulation/Flame simulation delay time tLV . 62 12.5 Safety time during operation tSB .................................. 62 12.6 Flame signal .............................................................. 63 12.7 Fault lock-out ................................................................ 63 12.8 Safety interlocks (Limits) .............................................. 63 12.9 Pilot gas valve V1 .......................................................... 63 12.10 Main gas valve V2 ................................................... 63 12.11 Continuous operation .................................................. 63 12.12 Air valve ...................................................................... 63 12.13 Diagnostic coverage DC .......................................... 64 12.14 Mode of operation ...................................................... 64 12.15 Safe failure fraction SFF .............................................. 64 12.16 Probability of dangerous failure PFHD ........................ 64 12.17 Mean time to dangerous failure MTTFd ..................... 64

Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

Page 6: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

6

PFU 760 · Edition 05.11

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

1 Application The burner control units PFU 760 control, ignite and moni- tor gas burners for intermittent or continuous operation. As a result of their fully electronic design they react quickly to various process requirements and are therefore also suitable for frequent cycling operation.

The PFU 760 can be used for directly ignited industrial burners. The burners may be modulating or stage-controlled.

On industrial furnaces, the PFU 760 reduces the load on the central furnace control by taking over tasks that only relate to the burner, for example it ensures that the burner always ignites in a safe condition after it has been restarted.

The burner control unit is used for burners with mechanical combustion air supply where the fan is controlled by a separate logic and for atmospheric burners.

Module subrack BGT for instance serves to accom- modate several function units. It is provided with a backplane with screw terminals for simple, reliable wiring.

The air valve control on the burner control unit PFU 760L assists the furnace control for cooling, purging and output control tasks.

The program status, the unit parameters and the level of the flame signal can be read directly from the unit. The burner can be controlled manually for commissioning and diagnostic purposes.

If the local requirements on the burner control unit change, the PC software BCSoft can be adjusted to the unit parameters of the application by using the optical interface.

The service personnel is supported by a convenient visualiza- tion system of the input and output signals and the error history.

To reduce the installation and wiring costs, Elster Kromschröder offers the field bus interface PFA 700 to transfer the control signals and feedbacks via PROFIBUS-DP.

Page 7: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

5

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

Bogie hearth forging furnace in the metallurgical industry

Intermittent shuttle kiln in the ceramics industry

Walking beam furnace with overhead firing

Page 8: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

6

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

1 .1 Examples of application

1 .1 .1 Staged On/Off burner control The burner can be started with reduced capacity.

A UV sensor monitors the flame signal from the burner. UV sensor UVD 1 is used for continuous operation, UV sensor UVS for intermittent operation.

SPS PLC API

L1, N, PE DI P

P 1

PFU 760L

DI

22a 10c 26e

A

30e 10a 10e 2e 4e

µC

2c 4c

22e 16c 28c 26a

TZI

VAG

VR..R

Page 9: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

7

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

1 .1 .2 Staged High/Low burner control The burner starts at low-fire rate. When the operating state is reached, the PFU 760L advises the control unit. The PLC can now pulse the air valve in order to control the burner output. SPS

PLC API

L1, N, PE DI P

DI

22a 10c 26e

P A 1

PFU 760L 30e 10a 10e 2e 4e

µC

2c 4c

22e 16c 28c 26a

TZI

GIK..B

VAS..N

VR..R

Page 10: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

8

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

1 .1 .3 Two-stage-controlled burner Control: ON/OFF with ignition via bypass

The burner starts at low-fire rate. When the operating state is reached, the PFU 760L issues the Enable signal for the maximum burner output.

L1, N, PE DI P

DI P A

22a 10c 26e PFU 760L 30e

1

10a 10e 2e 4e

µC 2c 4c

22e 18e 16c 28c 26a

TZI

VBY

VAG

BVA + IC 40

SPS PLC API

4

7 M

Page 11: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

9

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

1 .1 .4 Modulating-controlled burner Control: continuous

The external control system moves the butterfly valve for air BVA to ignition position. The burner starts at low-fire rate, and a controller in the PLC controls the burner output via the butterfly valve for air BVA after the operating state has been signalled.

L1, N, PE

DI

mA

P SPS PLC API

PFU 760

DI

22a 10c 26e

1

10e

µC

2e 4e

2c 4c

16c 28c 26a

TZI BIO BIC

VAG

M

BVA+IC 20

Page 12: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

10

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

1 .1 .6 PFU for PROFIBUS-DP with PFA 700 The bus system transfers the control sig- nals for starting, resetting and for con- trolling the air valve from the control sys- tem (PLC) to the PFU 760 via the PFA 700. In the opposite direction it sends infor- mation on the operating status. Control signals that are relevant for safety, such as the safety interlocks and digital input, are transferred independently of the bus communication by separate cables.

1 .1 .5 PFU 760 . .D: High temperature equipment Indirect flame control using the tempera- ture. During the start-up process, as long as the wall temperature is below auto ignition temperature the flame must be controlled by conventional methods. When the working temperature has exceeded 750°C, the safety tempera- ture monitor (STW) takes over the indirect flame control.

STW >750 °C

PFU 760..D L1

PFU 760..D

µC µC

18a 18a

22a

DI

22a

DI

PROFIBUS-DP

L1, N, PE DI P

SPS PLC API

BUS

BUS

BU

S

PFA

/PFP

PFU

76

0

PFU

76

0

PFU

76

0

PFU

76

0

PFU

76

0

PFU

76

0

PFU

76

0

PFU

76

0

PFU

76

0

PFA

/PFP

PFU

76

0

PFU

76

0

PFU

76

0

PFU

76

0

PFU

76

0

PFU

76

0

PFU

76

0

PFU

76

0

PFU

76

0

Page 13: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

11

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

2 Certification Certified pursuant to SIL

AGA approved

Australian Gas Association, Approval No.: 5597 www.aga.asn.au/product_directory

For systems up to SIL 3 pursuant to EN 61508

Pursuant to EN ISO 13849-1:2006, Table 4, the PFU can be used up to PL e.

EC type-tested and certified

pursuant to

– Gas Appliances Directive (2009/142/EC) in conjunction with EN 298:2004-01,

Meets the requirements of the – Low Voltage Directive (2006/95/EC),

– EMC Directive (2004/108/EC).

PFU . .T is FM approved

Factory Mutual Research Class: 1997.

Suitable for applications pursuant to NFPA 86. www.fmglobal.com Products and Services Product Cer- tification Approval Guide

AGA

Page 14: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

12

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

3 Function

3 .1 Connection diagram For cable selection and wiring, see page 43 (Project planning information).

3 .1 .1 PFU 760 For the explanation of symbols, see page 61 (Legend).

( PFU 760L)

L1 (L1) 30e PFU 760

22e N

F1 sk1 16c

V1 26e

DI 22a

V2

30a N (L2)

32c 24c

20c a 2a 4a

230 V

28c s 4e 2e

N Z I

26a m

2c 4c

PFF 704

24 V 8a 8c

8a

8c

8e µC

0 V 8e

A

S

SK

24 V

0 V

1 10e

12e

10a

12a

10c

12c

1 UVS 2

26a 20c

3 24c

N 28c

26a

N

28c

P

A

18e

ma

x. 1

A, 2

4 V

Page 15: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

13

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

3 .1 .2 PFU 760 . .K1 As a replacement unit for burner control unit PFS/PFD 778.

For the explanation of symbols, see page 61 (Legend).

( PFU 760L..K1)

PFU 760..K1

L1 (L1) 30e N

F2

F1

22e

sk1

V1 26e

DI 22a

V2

30a N (L2)

32c 24c

20c a 2a 4a

230 V

28c s 4e 2e

N Z I

26a m

2c 4c

PFF 704

24 V 8a 8c

8a

8c

8e µC

0 V 8e

24 V

0 V

A

S

SK 1

10e

12e

10a

12a

10c

12c

26a UVS 2 20c

1

3 24c

N

28c

26a

N

28c

P

A

16c

18e

ma

x. 1

A, 2

4 V

Page 16: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

14

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

3 .1 .3 PFU 760 . .K2 As a replacement unit for burner control unit PFU 778.

For the explanation of symbols, see page 61 (Legend).

( PFU 760L..K2)

L1 (L1) 30e PFU 760..K2

22e N

F1 sk1 16c

V1 26e

DI 22a

V2

30a N (L2)

32c 24c

20c a 2a 4a

230 V

28c s 4e 2e

N Z I

26a m

2c 4c

PFF 704

24 V 8a 8c

8a

8c

8e µC

0 V 8e

24 V

0 V

A

S

SK 1

10e

12e

10a

12a

10c

12c

UVS 2 20c 1 26a

3 24c

N 28c

26a

N

28c

P

A

18e

ma

x. 1

A, 2

4 V

Page 17: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

Wait until has elapsed (P21)

Function

00

01

Start-up position/standby

Start-up with signal

PFU 760L with air valve control features the following additional functions.

In start-up position, the air valve can be opened for cooling A .

Using parameter 31, it can be determined whether the air valve can be activated externally during start-up.

15

3 .2 PFU 760 program sequence

Normal start-up If an “old” fault is still being signalled after switching on, it will be necessary to reset this first.

When the safety interlocks are closed, the PFU reverts to start-up position and conducts a self-test. If it does not deter- mine a malfunction of the internal elec- tronic circuitry or of the flame sensor, the burner can be started.

The flame simulation check is conducted during start-up position or after applying the start-up signal (), depending on parameter 15.

After the min. burner pause time tBP has elapsed, the PFU opens valve V1 and ignites the burner. The ignition time tZ is constant.

If a flame is detected during the safety time tSA, the flame proving period tFS

0

Safety time tSA running (P22),

ignition in process, V1 opens and

min. combustion time tB starts to elapse (P20)

If no flame detected: next start-up attempt (P10)

or fault lock-out

The air valve can be set to open together with V1 (display A ) via parameter 30.

starts after this safety time has elapsed. Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes. This completes start- up. An adjustable min. combustion time tB ensures that the burner burns for a defined period even if the start-up signal

() is switched off beforehand.

t

min. burner pause time tBP

Switch on PFU 760

In the event of fault signal: Reset

Safety interlocks (Limits)

If parameter P15 = 1: Flame simulation check

If parameter P15 = 0: Flame simulation check

Page 18: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

16

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

If min. combustion time tB

min. burner pause time tBP

running (P23)

0

04

04

00

Operation signalling

contact closes and V2 opens

In the event of flame failure:

restart or fault lock-out

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30.

The burner can also be started manually with the aid of the button on the PFU. Voltage must be applied continuously to terminals 10e, 26e and 30a in order for this to occur.

The PFU can also be operated in Manual mode for start-up.

Start-up without flame signal If no flame is detected during the safety time tSA, either a fault lock-out occurs or up to three further start-up attempts occur. The required functions and, if applicable, the number of start-up attempts must be specified when or- dering. (Parameter 10, “Burner start-up attempts”).

Behaviour in the event of flame failure during operation If the flame fails during operation, either an immediate fault lock-out occurs or a restart occurs. This procedure can be set via the optical interface (parameter 12, “Burner restart”).

starts to elapse (P21)

Controlled shut-down via signal

In the event of flame failure: fault lock-out

Flame proving period tFS

has elapsed: Operation signalling

contact opens, V1 and V2 close,

Page 19: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

17

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

3 .3 Program status and fault messages During operation, the 7-segment display shows the program status. In the event of a fault, the PFU halts the program run, the display blinks and it then displays the cause of the fault. The burner control unit can be reset using the Reset button or the remote reset.

Program status I LAY Fault message (blinking*)

Start-up position/standby 00

Cooling A0

Waiting time/Pause time 1 Flame simulation, pilot burner

Burner safety time on start-up Burner start-up without flame signal

Burner flame proving period Flame failure during burner flame proving period

Burner operation 4 Flame failure during operation, pilot burner

Purge 0

Air valve A

High temperature operation** . .

10 Faulty remote reset

Supply voltage too low

Faulty parameterization

Short-circuit on a valve output

6 Short-circuit on ignition or valve output

1 Safety interlock failure

Permanent reset

Time between two start-ups is too short

* In Manual mode, two dots will blink on the display in program status 01 – 04. ** Optionally available.

Page 20: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

18

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

4 Parameters

Description Parameter Value range Factory default

setting Adjustable*

Burner flame signal 01 0 – 30 μA

Program status when the most recent fault occurred 03 x0 – x8

Burner switch-off threshold 04 1 – 20 µA 1 µA

Burner start-up attempts 10 1 – 4 1

Burner restart 12 0; 1 0

Safety time during operation for V1 and V2 tSB 14 1; 2 s 1 s

Flame simulation check in start-up position/standby 15 0; 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 – 250 s 0 s

Burner safety time on start-up tSA 22 3; 5; 10 s

Burner flame proving period tFS 23 0 – 25 s 0 s

Switchable gas valve V2 (only on PFU..L) 26 0; 1 0

Air valve control 30 0; 1; 2 0

Air valve can be activated externally on start-up 31 0; 1 0

Air valve closed/can be activated in the event of malfunction 32 0; 1 1

High temperature operation** 33 2; 3

t

Page 21: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

19

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

Description Parameter Value range Factory default

setting Adjustable*

Manual mode limited to 5 minutes 34 0; 1 1

UVS check (1 x in 24 hours) 35 0; 1 0

Low fire over run time 36 0; 3; 5; 10; 15;

25; 60 s 0 s

Purge 42 0; 1 1

Multi-flame control 45 0; 1 0

Password 50 0000 – 9999 1234

* Adjustable using BCSoft software and a PC opto-adapter. ** Please quote in your order. 0 = Function inactive, 1 = Function active.

On parameterization, ensure that the program sequence matches the application. Select the parameters so that the burner can be operated as intended in all operating phases.

4 .1 Scanning the parameters During operation, the 7-segment display shows the program status.

The flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the Reset/Information button (for 2 s).

In the event of a fault, the PFU halts the program run, the display blinks and it then displays the cause of the fault in coded form.

Page 22: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

20

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

01

4 .2 Flame control

4 .2 .1 Burner flame signal Parameter 01

Flame signal of the burner, display in µA, measuring range: 0 – 30 µA.

4 .2 .2 Program status when the most recent fault occurred Parameter 03

This indicates the program status in which the last burner fault occurred (e.g. the unit indicates that a flame simulation has been detected with a blinking 01.

In parameter 03, it is now shown which program position the

4 .2 .3 Switch-off threshold of the flame amplifier Parameter 04, burner switch-off threshold

The sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 µA.

Example: In the case of UV control with the UV sensor UVS, the signal of the burner to be monitored is influenced by other burners.

The set value can be incremented in parameter 04 so that only the flame of the system’s “own” burner is detected.

The measured flame signal of the system’s “own” burner should be at least 3 µA (empirical value) higher than the set switch- off threshold.

unit was in when the fault was detected (waiting time or standby 00 ).

Result: A flame simulation was detected during the waiting time or standby.

Page 23: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

21

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

4 .2 .4 High temperature operation with PFU . .D Parameter 33

Operation of firing systems at temperatures above 750°C. The PFU features a safety-relevant DI input (Digital Input). This input supports the “High temperature operation” function. If firing systems are operated above 750°C, the system is considered to be a high temperature equipment (see EN 746-2). Flame control must be in operation until the furnace wall temperature has exceeded 750°C. Note the requirements of the Standards!

Flame control can be dispensed with during high temperature operation to improve the system availability. This means that no incorrect flame signals, e.g. signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation, may lead to faults.

When the DI input is activated, the burner control unit reverts to High temperature mode. This means: the PFU operates without evaluation of the flame signal. The safety function of the device-internal flame control system is placed out of operation.

In High temperature mode, the gas valves are opened without flame control.

The precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature. For this purpose, we recommend a safety temperature monitor with twin thermocouple (DIN 3440). Sensor discontinuity, sensor short-circuit, failure of a component or mains failure must set the installation to a safe state.

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750°C. The PFU starts the burner as usual, without monitoring the presence of the flame.

If the temperature in the furnace chamber drops below 750°C, the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system.

t

4 88 30a 26e 10e 28c 22a DI

16c V1 26a 2c–4c 18e V2 2e–4e

t

tSA

tZ tFS

Page 24: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

22

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

The PFU then responds, depending on setting: Parameter 33 = 1 (PFU 760..K2 only)

Parameter 33 = 2

If the flame fails during high temperature operation, the ready contact opens for the duration of the flame failure (FA).

When High temperature mode is ended, the PFU switches off the burner and restarts with flame simulation check (recom- mended in the case of UV control with UVS).

When High temperature mode is ended, the PFU switches off the burner and restarts with flame simulation check (recom- mended in the case of UV control with UVS).

On programming parameter 33, ensure that the program sequence matches the application. Select the parameters so that the burner can be operated as intended in all operating phases.

t

FA

4 1 4 88 30a 26e 10e 28c 22a DI

16c V1 26a 2c–4c 18e V2 2e–4e 2a–4a

t

tW

tZ

tSA

tFS

4 1 4 88 30a 26e 10e

tW

tZ

tSA

tFS

28c 22a DI

16c V1 26a 2c–4c 18e V2 2e–4e 2a–4a

t

Page 25: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

23

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

Parameter 33 = 3 Parameter 33 = 4 (PFU 760..K2 only)

When High temperature mode is ended, the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD).

If no flame signal is present when High temperature mode is ended, the burner control unit performs a fault lock-out, regardless of parameter 33.

If the flame fails during high temperature operation, the ready contact is opened for the duration of the flame failure.

When High temperature mode is ended, the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD).

4 4 88 30a 26e 10e

28c 22a DI

16c V1 26a 2c–4c 18e V2 2e–4e

t

4 4 88 30a 26e 10e

28c 22a DI

16c V1 26a 2c–4c 18e V2 2e–4e

t

FA

4 4 88 30a 26e 10e 28c 22a DI

16c V1 26a 2c–4c 18e V2 2e–4e 2a–4a

t

Page 26: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

24

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

4 .2 .5 UVS check Parameter 35

An automatic restart of the burner control unit can be activated every 24 hours via this parameter. The time starts each time the start-up signal ( ) is applied.

Parameter 35 = 0: Unlimited burner operation.

Parameter 35 = 1: An automatic restart is activated once every 24 hours.

It must be ensured in this case that the program sequence started matches the application. This parameter may be set in this way only if the burner can restart as intended in all operating phases.

Page 27: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

25

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

01

4 .3 Behaviour in start-up position/standby

4 .3 .1 Flame simulation check in start-up position/standby Parameter 15

This defines the instant for the flame simulation check.

What is an extraneous signal?

Parameter 15 = 0: The flame simulation check is conducted after applying the start-up signal () during the waiting time tW.

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence. If the PFU 760 notices such an extraneous signal during the flame simulation check, it starts the flame simulation delay time tLV. If the extraneous signal is discontinued during this period, the burner can start up. Otherwise, a fault lock-out occurs. blinks on the display.

Parameter 15 = 1: The flame simulation check is conducted provided no start-up signal () is applied (during the so-called start-up position/standby). This allows fast start-up of the burner since there is no waiting time tW.

The burner must have been switched off for at least 4 s be- fore start-up in order for the flame simulation check to be conducted correctly.

The flame simulation check of the burner is active until valve V1 is enabled.

tW

1 . . . 88

V1

t

. . . 88

V1

t

1 88 30a 26e 10e

tLV

28c 26a 16c V1 18e V2 2c–4c 2e–4e

t

Page 28: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

26

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

tBP

4 .3 .2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s.

An immediate restart of the main burner after a controlled shut-down, a start-up attempt, restart, cooling or purging is prevented by the pause time. The pause time starts when the air valve is switched off. If a start-up signal ( ) is applied before expiry of this time, the start-up is delayed until the end of the pause time.

After the pause time, the burner is started if the start-up signal ( ) is applied.

The minimum burner pause time tBP serves to adapt the pro- gram sequence to the requirements of the application.

The time should be set such that the system can be moved to ignition position, i.e. butterfly valves can be closed and, pos- sibly, gas can be flared off, before a restart occurs.

See examples of application Staged On/Off burner control, Staged High/Low burner control oder Two-stage-controlled burner.

4 1 4 88 1 5 4 7

9 12 V1 14 V2 16-17 18-19

tZ tFS t

tSA

Page 29: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

tSA

tFS

Parameters

4 .4 Behaviour during start-up

4 .4 .1 Safety time on start-up tSA Parameter 22

27

4 .4 .3 Minimum combustion time tB Parameter 20

Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operation.

In the case of brief activation of the start-up signal input () (e.g. with a pulse), the combustion time tB is started, and the burner remains in operation for at least this period.

Safety time on start-up tSA for the burner.

4 .4 .2 Flame proving period tFS Parameter 23

Programmable time between 0 and 25 s.

This time elapses before the PFU starts the next program step so as to give the flame time to stabilize.

4 88 30a 26e 10e 28c

tZ

16c V1 18e V2 2c–4c 2e–4e

t

26a

tSA

88 30a 26e 10e

tZ tFS

28c 26a 16c V1 18e V2 2c–4c 2e–4e

t

4

Page 30: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

Parameters > Behaviour during start-up

4 .4 .4 Burner start-up attempts Parameter 10

This indicates the number of possible start-up attempts of the burner.

In accordance with EN 746-2, three start-ups are permitted in specific cases in the event of flame failure during start-up, if the safety of the installation is not impaired. Note the require- ments of the Standards!

If no flame is detected during start-up, either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occur.

Pursuant to NFPA 86, only one start-up attempt is permitted in the event of flame failure during start-up. For units approved by FM Approval (see type label), it is only possible to select one start-up attempt.

1 start-up attempt Parameter 10 = 1

28

2 or 3 start-up attempts Parameter 10 = 2, 3

If several start-up attempts are set and if the PFU detects a flame failure during start-up, it closes valve V1 after the safety time tSA has expired and attempts to start up again. After the last programmed start-up attempt has been completed, the burner control unit conducts a fault lock-out. The display blinks and shows the cause of the fault.

If no flame forms during start-up, a fault lock-out is performed after expiry of time tSA. The display blinks and shows the cause of the fault.

88 30a 26e 10e 1 28c 26a 16c V1 18e V2 2c–4c 2e–4e

tZ t

tSA

88 30a 26e 10e

tZ tZ

28c 26a 16c V1 18e V2 2c–4c 2e–4e

t

tSA tSA

Page 31: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

Parameters

4 .5 Behaviour during operation

4 .5 .1 Safety time during operation tSB for V1 and V2 Parameter 14

This indicates the safety time during operation tSB for valves V1 and V2. The default in accordance with EN 298 is 1 s. The PFU has also the available option of a safety time during operation tSB of 2 s. Prolonging the time increases the installation avail- ability in the case of brief-duration signal fades (e.g. fades of the flame signal). In accordance with EN 746-2, the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards).

29

4 .5 .2 Fault lock-out or restart Parameter 12

This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information).

Immediate fault lock-out following flame failure Parameter 12 = 0:

After a fault lock-out, the burner control unit can be reset, either with the button on the front panel or using an external button. Several burner control units can be reset in parallel using the external button.

The PFU cannot be reset by mains failure. The fault signalling contact does, however, open as soon as the mains voltage fails.

See also parameter 32, Behaviour of the air valve in the event of a fault lock-out.

t

4 4

tSB

88 30a 26e 10e 28c 26a 16c V1 18e V2 2c–4c 2e–4e

t

Page 32: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

tSB

Parameters > Behaviour during operation > Fault lock-out or restart 30

Restart following flame failure Parameter 12 = 1: Restart following flame failure.

If the PFU detects a flame failure after a minimum operating time of 2 s, the valves are closed and the operation signalling contact is opened within time tSB.

The burner control unit now attempts to restart the burner once. If the burner does not function, a fault lock-out occurs. The display blinks and shows the cause of the fault.

In accordance with EN 746-2, a restart may be conducted only if the safety of the installation is not impaired. Restart is recommended for burners which occasionally display unstable behaviour during operation.

The precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases). In this case, it must be ensured that the program sequence started by the PFU matches the application.

1x

4 1 4 88 30a 26e 10e

>2 s

tZ tFS

28c 26a 16c V1 2c–4c 2e–4e

t

tW tSA

Page 33: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

31

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

4 .6 Switchable gas valve V2 on PFU . .L Parameter 26

Parameter 26 = 0: Gas valve V2 opens with the operating signal.

Parameter 26 = 1: Gas valve V2 opens with the air valve during operation

A switchable gas solenoid valve V2 can be activated with the PFU..L. If Parameter 26 is set to 1, gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a/12a).

L1, N, PE

DI P

SPS PLC API

DI P A 1

PFU 760L 22a 10c 26e 30e 10a 10e 2e 4e

µC 2c 4c

22e 18e 16c 28c 26a

TZI

VBY

VAG

4

7 M

BVA + IC 40

Page 34: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

32

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

4 .7 Air valve control PFU . .L Parameter 30, Behaviour of the air valve during operation

Parameter 31, Behaviour of the air valve during start-up

Parameter 32, Behaviour of the air valve in the event of a fault lock-out

The PFU..L features an adjustable air valve control. The display shows that purging is currently being carried out with 0 . A indicates that the air valve is being activated for cooling or heating.

The PFU..L supports the following functions:

– Purge

– Cooling in start-up position/standby

– Switching of the burner between low and high burner output during operation via the air valve

– To start up the burner as intended, external activation of the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system).

– Controlling the air valve so that it

– opens with valve V1

– opens with valve V2

– Low fire over run time tKN after a controlled shut-down

4 .7 .1 Purge Parameter 42 = 0: The air valve is closed when voltage is applied to terminal 30e.

Parameter 42 = 1: The air valve is opened when voltage is applied to terminal 30e.

In the case of multiple burner applications, burners with mechanical combustion air supply are used. The air for com- bustion and pre-purge is supplied by a central fan controlled by a separate logic. This logic determines the purging time.

The PFU..L supports centrally-controlled pre-purge or post- purge. The PFU..L is informed that purging is currently being performed by input 30e. It then opens the air valve, regard- less of the status of the other inputs (purging has priority). The

display indicates 0 .

4 .7 .2 Cooling in start-up position/standby The air valve can be activated externally via input 10a for cool- ing in the start-up position. During activation of the air valve

the display shows A0 , indicating that cooling is currently being carried out.

4 .7 .3 Burner start Parameters 30 and 31 determine the behaviour of the air valve during burner start.

Page 35: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

33

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

4 .7 .4 Air valve opens in the case of external activation (not during start-up)

Parameter 30 = 0: The air valve opens if it is activated exter- nally by input 10a.

Parameter 31 = 0: The air valve remains closed during start-up even if it is activated externally.

These settings are required on burners on which the gas/air ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire, e.g. on two-stage- controlled burners. In this case, activation of the air valve during burner start via input 10a must be prevented.

External control allows switchover between low fire and high fire during operation.

The air valve can be activated externally via input 10a for cool- ing the burner in the start-up position/standby.

4 88 30a 26e 10e

10a

28c 26a 16c V1 18e V2

A

tZ

tSA

tFS

22e 2c–4c 2e–4e

t

L1 PFU 760L

A

P

SPS PLC API

TZI

GIK..B

VAS..N

VR..R

Page 36: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

34

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

4 .7 .5 Air valve opens in the case of external activation (even during start-up)

Parameter 30 = 0: The air valve opens if it is activated exter- nally via input 10a.

Parameter 31 = 1: The air valve can be activated even during start-up.

These settings may be selected only if the burner can start with full air capacity.

The air valve can be activated externally via input 10a for cool- ing the burner in the start-up position/standby.

4 88 30a 26e 10e 1 28c 26a 16c V1 18e V2

22e 2c–4c 2e–4e

10a A

tZ

tSA

tFS t

L1 PFU 760L

A

P

SPS PLC API

TZI

VG..L EKO

GEH

BICR VR..R

LEH EKO

Page 37: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

35

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

4 .7 .6 Air valve opens with valve V1 Parameter 30 = 1:

The air valve opens simultaneously with valve V1.

Application: Single-stage-controlled burner is switched ON/OFF via the input.

The air valve can be activated externally via input 10a for cool- ing the burner in the start-up position/standby.

4 88 30a 26e 10e 1 28c 26a 16c V1 18e V2

22e 2c–4c 2e–4e

10a A

tZ

tSA

tFS t

L1 PFU 760L

A

P

SPS PLC API

TZI

VG..L EKO

GEH

BICR VR..R

LEH EKO

Page 38: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

36

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

4 .7 .7 Air valve opens with valve V2 Parameter 30 = 2:

The air valve opens simultaneously with valve V2.

Application: Two-stage-controlled burner is switched ON/OFF via the input.

The air valve can be activated externally via input 10a for cool- ing the burner in the start-up position/standby.

A

4 88 30a 26e 10e 28c

16c V1 18e V2 10a 22e

26a

2e–4e 2c–4c

tZ

tSA

tFS t

L1 PFU 760L

A

P

SPS PLC API

TZI

VAG

VR..R

Page 39: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

37

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

4 .7 .8 Low fire over run time tKN after a controlled shut-down Parameter 36

Settings: 0; 3; 5; 10; 15; 25 or 60 (low fire over run time in seconds)

This parameter is applicable to systems with a pneumatic ratio control system and On/Off control.

Parameter 36 = 0 (low fire over run time tKN = 0 s): Without low fire over run, the gas side is closed immediately owing to the quick-closing gas valve in the case of On/Off control. The air side closes more slowly. The air flowing in during the closing time increases the O2 content in the combustion chamber.

Parameter 36 = 3; 5; 10; 15; 25 or 60 (low fire over run time tKN = 3, 5, 10, 15, 25 or 60 s): The air valve closes slowly after the activation signal has been switched off. The gas valve remains open for tKN. This means that the burner, after deactivation of the start-up signal ( ), is initially adjusted down to low fire and then switched off completely.

Using the low fire over run function reduces the O2 content in the furnace atmosphere.

Flame control is still operational. Can be used only in the case of a pneumatic air/gas ratio control system and On/Off control. Its must be ensured that no excess gas occurs.

4 88 30a 26e

tKN

28c 16c V1 26a 2c–4c 18e V2 22e 2e–4e

t

10e

L1 PFU 760L

A

P

SPS PLC API

TZI

VAG

VR..R

Page 40: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

38

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

4 .7 .9 Behaviour of the air valve in the event of a fault lock-out Parameter 32

This determines whether the air valve can be activated in the case of a fault lock-out.

Parameter 32 = 0:

The air valve is closed in the event of a fault. It cannot be activated externally via terminal 10a.

Parameter 32 = 1:

The air valve can be activated externally via input 10a even during a fault, e.g. for cooling.

Page 41: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

39

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

4 .8 Manual operation For convenient setting of the burner or analyzing faults.

The parameter display is not available in Manual mode. Manual mode can be accessed only if the unit was not in Fault state before switching off. The following times/functions are not active in Manual mode: start-up attempts, restart, minimum combustion time and cycle lock.

If the Reset/Information button is pressed for 2 s during switch- on, the PFU reverts to Manual mode. Two dots blink on the display.

In this operating mode, the burner control unit operates inde- pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks. These are of higher priority and will be processed first).

Each time after the button is pressed again, the PFU moves to the next section of the program sequence and stops there. After approx. 3 s, the flame signal will be displayed instead of the program parameter. Briefly pressing the Reset/Informa- tion button (< 1 s) displays the relevant Manual mode step. If there is flame simulation during the start-up, the flame signal is displayed immediately.

On units with air valve control, the air valve can be opened and closed repeatedly by pressing the button during operation.

Manual mode can be terminated by switching off the PFU (On/Off button).

4 .8 .1 Manual mode limited to 5 minutes Parameter 34

Parameter 34 determines when Manual mode is terminated.

Parameter 34 = 0: Manual mode is not limited in time. If this function has been selected, operation of the furnace may be continued manually in the event of failure of the central control system.

Parameter 34 = 1: Manual mode ends automatically five minutes after the last time the button was pressed. The PFU then moves abruptly back to start-up position/standby.

4 .9 Password Parameter 50

(Four-digit) password saved to protect parameter settings. To prevent unauthorized changes to parameter settings, a password is stored in parameter 50. Changes to parameter settings can only be made once this number has been entered. The password can be changed using BCSoft.

Note the effect of parameter settings on the safe functioning of your system.

The password set at the factory can be found in the delivery note supplied.

Page 42: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

40

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

4 .10 Multi-flame control Parameter 45

Parameter 45 = 0: Multi-flame control is switched off.

Parameter 45 = 1: Multi-flame control is switched on. The parameter must be set to 1 to ensure that the flames are monitored.

( PFU 760L)

L1

N

2e

30e 3 2a 2 UVS

1

30a

32c

30e

2a

230V

2e

L1 (L1) 30e PFU 760

22e N

26a UVS 2 20c

1 F1 sk1

6a 3 24c

16c

18e V1

Z Z I

N N

L1

4c

4e

6e

26e

22a V2

N

28c

N (L2) 30a

L1

8e

30e 3 8a 2 UVS

1 8a

230V

8e

12a 32c 24c

20c a 2a 4a

10c 230 V

28c s 2e 4e

Z Z I

N N

10e

12e

N Z I

L1 L1 26a

m 2c 4c

18e 18a

230V

18e

22a

30e 3 18a 2 UVS

1

Z Z I

N N

L1 L1

20c

20e

22e

24e

0 V

24 V

0 V

30e 3

24a

230V

24e

28a 24a 2 UVS

1

Z Z I

N N

L1 L1

26c

26e

28e

PFF 704 24 V

8a

8c

8e

10e

12e

10a

12a

10c

12c

µC

A

S

SK

P

DI

1

A

ma

x. 1

A, 2

4 V

Page 43: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

41

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

5 Selection

5 .1 Safety time Please quote the safety time tSA when ordering.

tSA = 3 s, 5 s or 10 s

PN = Rated heat output

PZ = Ignition capacity

The safety time of the burner control unit depends on the burner type, the burner output and the respective application.

EN 746-2

PN

≤ 70 kW

> 70 kW*

tSA

5 s

3 s

≤ 350 kW 10 s

> 350 kW** 5 s

0 ³ ∞* 10 s

* PZ 0,1 x PN, P Zmax = 350 kW

** PZ 0,33 x PN, P Zmax = 350 kW

5 .1 .1 Calculating the safety time tSA

Burner with mechanical combustion air supply Natural draught burner with direct ignition

Natural draught burner with pilot burner

Burner output 1.00kW Safety time

on start-up tSA 3s

Ignition burner input rating at a level of 10 % of nominal heat input with a maximum of 350 kW.

Page 44: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

42

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

5 .2 Selection table

Type L* T N D* U* K1* K2* PFU 760

* If “none”, this specification is omitted.

= standard, = available

Order example PFU 760LT

5 .3 Type code

Mains voltage

T 220 – 240 V AC, -15/+10%, 50/60 Hz

N 110 – 120 V AC, -15/+10%, 50/60 Hz

D* Digital input to interrupt flame control

U* Preparation for UV sensor for continuous operation UVD 1

K1* Compatible with PFS/PFD

K2* PFU 778

* If “none”, this specification is omitted.

Code Description

L* Air valve control

Page 45: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

43

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

6 Project planning information

6 .1 Cable selection Use mains cable suitable for the type of operation and com- plying with local regulations. Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields.

6 .1 .1 Ignition cable Use unscreened high-voltage cable see page 49 (Accessories). Cable length: max. 5 m, recommended < 1 m. Screw the igni- tion cable securely into the ignition transformer and run to the burner by the shortest possible route.

The longer the ignition cable, the lower the ignition capacity. Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces- sories). Do not lay UV/ionization cable and ignition cables together and lay them as far apart as possible.

6 .1 .2 Ionization cable Use unscreened high-voltage cable see page 49 (Accessories). Cable length: max. 100 m. Avoid external electrical interfer- ence. Install as far as possible from mains and ignition cables and interference from electro-magnetic sources. If possible, do not lay in a metal conduit. Several ionization cables can be routed together.

6 .1 .3 UV cable Cable length: max. 100 m. Avoid external electrical interference. Install as far as possible from mains and ignition cables and interference from electro-magnetic sources. If possible, do not lay in a metal conduit. Several UV cables can be routed together.

6 .2 Ignition electrode

6 .2 .1 Electrode gap Gap between electrode and burner ground: 2 mm ± 0.5 mm.

6 .2 .2 Star electrodes We recommend using 7.5 kV ignition transformers on burners with star electrodes.

Page 46: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

44

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

1

6 .3 Minimum combustion time Even if the start-up signal () is applied only briefly, the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a fault.

The minimum combustion time tB can be extended beyond the safety time tSA to max. 25 s.

6 .4 Safety interlocks (Limits) The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application, e.g. safety temperature limiter, minimum and maximum gas pressure, tightness control) must isolate ter- minal 26e from the voltage supply. If the safety interlock is interrupted, this is indicated by a blinking on the display.

If the safety interlocks fail, an immediate program abort with switch-off of all outputs occurs (even during the safety time). If the safety interlocks are operational again or the unit is switched back on, the program run is restarted in standby.

6 .5 Emergency stop

6 .5 .1 In the event of fire or electric shock If there is a risk of fire, electric shock or similar, inputs L1, N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply – this should be reflected in the wiring on site.

6 .5 .2 Via the safety interlocks (limits) The safety interlock turns off the power to input 26e, such as in the event of air deficiency or similar.

Page 47: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

45

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

10

6 .6 Reset

6 .6 .1 Parallel reset Several burner control units can be reset in parallel using the external button. The PFU cannot be reset by mains failure.

6 .6 .2 Permanent remote reset Permanent remote reset gives rise to a malfunction. If a remote reset signal is permanently applied to terminals 10c/12c, flashes on the display to indicate a fault.

Reset with a pulse < 1 s.

6 .6 .3 Automatic remote reset (PLC) In the case of automatic remote reset (PLC), the reset pulse duration should not exceed 1 second. Check compliance with standards.

If a fault is acknowledged by remote reset too often, error (Too many remote resets) is displayed. The error can only be acknowledged with the Reset/Information button on the unit.

The burner malfunction must be remedied. The malfunction can not be remedied by changing the method of activation.

6 .6 .4 Burner start A furnace start may only be initiated, if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustion/processing chamber, in the con- nected areas or in the exhaust gas system (heat exchanger, dust collector). This can be achieved by pre-purge, which occurs immediately before ignition or within the period speci- fied in the operating instructions.

In the case of multiple burner applications, pre-purge is not necessary after a controlled burner shut-down.

Note the requirements of the Standards. For exceptions, see Standards.

6 .6 .5 Restart and start-up attempts The precondition for a restart/start-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases). In this case, it must be ensured that the program sequence started by the PFU matches the application.

Note the requirements of the Standards. For exceptions, see Standards.

Page 48: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

46

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

6 .7 Fault signalling The fault signalling contact opens, as soon as the mains volt- age fails.

6 .8 Protecting the burner from overload To protect the unit against overload by frequent cycling, the maximum number of start-ups per minute is limited for the PFU. Excessive cycling triggers a fault message (blinking ). The max. number of start-ups per minute depends on the safety time tSA:

tSA [s] Ignition transformer TZI Max. start-ups/min.

3 5-15/100 6

5 5-15/100 5

10 5-15/100 4

6 .9 Installation Installation position: any.

Installation in 19" module subracks only, see page 50 (Module subracks).

Install in clean environment ensuring enclosure IP 54 or higher, whereby no condensation is permitted.

Cable length between PFU and burner: max. 100 m.

6 .10 Wiring The PFU is suitable for hard wiring only. Do not reverse phase and neutral conductor. Different phases of a three-phase current system must not be installed at the PFU. No voltage may be connected to the valve and ignition outputs.

6 .10 .1 UVS sensor wiring Connect the UVS sensor directly to the PFU. Operating the sensor with incorrect polarity or voltage can lead to destruc- tion of the sensor.

6 .11 PFU switched off The PFU cannot be activated when no mains voltage is applied or when it is switched off. The fault signalling contact is only closed when the unit is supplied with voltage and switched on.

If the unit is switched off, an immediate program abort with switch-off of all outputs occurs (even during the safety time). When the unit is switched on, the program run is restarted in standby.

Page 49: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

47

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

6 .12 Furnace control Switch on the system to start up the furnace, then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended. To shut down the furnace, first disconnect the burner control unit from the temperature control (burner ON signal), then disconnect the safety interlocks and finally switch off the system.

6 .13 Note on EC type-examination Since EN 298 (1993) does not describe all functions of the PFU, the operator is responsible for ensuring that all parameters and functions are matched to the respective application.

6 .14 Mains switch The mains switch in the unit isolates the PFU on two poles from the mains. It does not meet the requirements of EN 50156- 1:2004 (5.2.2 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply. Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156, it does allow the burner to be isolated functionally from the central control system. This function is required for manual operation and, in the case of PROFIBUS units, to switch off the unit without causing BUS errors. Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only, in accordance with Standard EN 50156.

6 .15 Changing parameters In certain cases, it may be necessary to change the default settings. Using a separate software package and a PC opto- adapter, it is possible to modify certain parameters on the PFU, such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failure.

The software package with PC opto-adapter, as well as “Changed parameters” stickers, are available as accesso- ries – see section entitled “Accessories”.

The unit parameters set at the factory are specified in the delivery note.

Document changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentation.

If a replacement is ordered for a PFU with changed parameters, refer to the protocol for details.

Page 50: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

48

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

7 Flame control

7 .1 With ionization sensor The PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground. The flame rectifies this voltage. Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signal.

A flame cannot be simulated. Ignition and monitoring with a single electrode is possible.

7 .2 With UV sensor A UV tube inside the UV sensor detects the ultraviolet light of a flame. It does not respond to sunlight, incandescent bulb light or infrared radiation emitted by hot workpieces or red- hot furnace walls.

In the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage. As with ionization control, the burner control unit only detects this DC signal.

When using UV sensors of Type UVS, the burner control unit may be used for intermittent operation only. This means that operation must be interrupted at least once every 24 hours. This can be programmed using parameter 35.

For further information, see brochure UVS.

The burner control unit PFU..U is prepared for UV sensor UVD 1. This enables continuous operation. For further information, see Technical Information Bulletin UVD.

7 .3 Via the temperature in high temperature equipment High temperature equipment is defined as a thermoprocessing installation, in which the wall temperature of the combustion chamber and/or the processing chamber exceeds 750°C. Burner control unit PFU..D features a special “High temperature operation” function. During heating up, standard monitoring methods (ionization or UV) must be used for flame control. When the working temperature has exceeded 750°C, indirect flame control can be taken over by a central monitoring device. When the DI input (terminal 22a) is activated, the burner control unit reverts to this operating mode.

Important: In “High temperature operation”, i.e. with the DI input being activated, burner control unit PFU..D does not evaluate the flame signal. The safety function of the burner control unit’s flame control is deactivated during this operat- ing phase.

Page 51: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

49

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

8 Accessories

8 .1 High-voltage cable FZLSi 1/7 up to 180°C,

Order No.: 04250410.

FZLK 1/7 up to 80°C, Order No.: 04250409.

8 .2 BCSoft

8 .3 Stickers for labelling

For printing with laser print- ers, plotters or engraving machines, 27 × 18 mm or 28 × 17.5 mm.

Colour: silver

8 .4“Changed parameters” stickers Affix on the connection diagram of the PFU following changes to unit parameters set at the factory.

100 pcs, Order No.: 74921492.

Opto-adapter including BCSoft CD-ROM, Order No.: 74960437.

The current software can be downloaded from our Internet site at www.docuthek.com. To do so, you need to register in the DOCUTHEK.

D-49018 Osnabrück, Germany

Achtung, geänderte Parameter! Die Angaben auf dem Typenschild gelten nicht mehr in vollem Umfang. Aktuelle Parameter direkt auslesen.

Important, changed parameters! The details on the type label are no longer completely accurate. Read the current parameters direct from the unit.

Attention, paramètres modifiés ! Les informations figurant sur la plaque signalétique ne sont plus valables dans leur intégralité. Veuillez vous référer directement aux paramètres actualisés.

Page 52: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

50

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

8 .5 Radio interference suppressed electrode adapters Plug cap, 4 mm, interference-suppressed, Order No. 04115308.

Straight adapter, 6 mm, interference-suppressed, Order No. 04115306.

8 .6 Socket connectors

Type Order No.

Socket connector E, 48-pin solder tag connection 04120148

Socket connector E, 48-pin wire-wrap connection 04120158

8 .7 Module subracks

Module subracks BGT S-9U/1 for PFP 700, PFU 760 comprising: module subrack, printed-circuit board with rear terminal strip, function-tested, standard documentation, guide rails, without partial front plates, screw terminals at the rear.

Slots 1–9 for PFU 760, slot 10 for PFP 700

Order No. 84402281.

Module subrack BGT SM-8/1/1 for MPT 700, PFU 760 comprising: module subrack, printed-circuit board with rear terminal strip, function-tested, standard documentation, guide rails, without partial front plates, screw terminals at the rear, single-zone operation for MPT 700 operating modes 1-4, two- zone operation for MPT 700 operating modes 1-4, but max. 4 burners per zone.

Slot 1 for MPT 700, slots 2–9 for PFU 760, slot 10 for PFP 700

Order No. 84402282 (no illustration provided).

Module subrack BGT SA-9U/1DP for PFA 700, PFU 760 comprising: module subrack, printed-circuit board with rear terminal strip, function-tested, standard documentation, guide rails, without partial front plates, screw terminals at the rear, relays and screw terminals for four free inputs and four free outputs.

Slot 1 for PFA 700, slots 2–10 for PFU 778 without digital input, connection to PROFIBUS-DP with D-Sub socket.

Order No. 84402283 (no illustration provided).

Page 53: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

51

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

8 .8 Power supply PFP 700 For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704. Operating status display on the front plate. PFP switches off in the event of an output overload.

Output voltage 24 V, output rating 14 VA.

PFP 700

S0

S1

L1 30a F1 O

I

230 V

115 V

8ace

N 32c

24 V= 600 mA

12ace 0 V

U I

Page 54: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

52

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

8 .9 Relay module PFR 704 For contact multiplication, e.g. if several air valves are activated via one control signal for pre-purge, or for heating/cooling switchover when using an MPT. Switching status display on the front plate.

Input voltage: 110/120 V AC, -15/+10%, 50/60 Hz, 220/240 V AC, -15/+10%, 50/60 Hz, 24 V AC/DC, ± 10%.

Current per relay: 25 mA.

Contact rating of floating outputs: max. 2 A, 264 V (not fused internally).

PFR 704 230 V~ 2e 115 V~ 2a 24 V=/~ 2c

1

0 V 4e

230 V~ 10e 115 V~ 10a 24 V=/~ 10c

2

0 V 12e

230 V~ 18e 115 V~ 18a 24 V=/~ 18c

3

0 V 20e

230 V~ 26e 115 V~ 26a 24 V=/~ 26c

4

0 V 28e

6a 6e

8a 8e

8c

6c

16a 16e

14a 14e

14c

16c

24a 24e

22a 22e

22c

24c

32a 32e

30a 30e

30c

32c

ma

x. 2

A, 2

64

V

ma

x. 2

A, 2

64

V m

ax.

2 A

, 26

4 V

m

ax.

2 A

, 26

4 V

Page 55: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

53

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

8 .10 Flame detector PFF 704 For flame detection or multi-flame control in conjunction with PFU, with 4 independent flame detectors. For intermittent op- eration with ionization or UV control.

Power consumption: 10 VA.

Ionization voltage: 230 V AC.

Max. flame signal cable length: 100 m.

Cut-off sensitivity of the flame amplifiers: adjustable between 1 µA and 10 µA (factory default setting: 1 µA).

Contact rating: max. 2 A.

Mains voltage: 110 – 240 V AC, 15/10%, 50/60 Hz.

Further information can be found in brochure PF 19”.

PFF 7x4 S0 O

L1

N

2 3

30a

32c

30e

2a

230V

2e

I S1 230 V

115 V

2e 2a 30e

1 UVS - +

Z Z I

N N F1

L1

1

L1 P1 F2

8e 8a 30e

2 UVS 1

3

8a

230V

8e

- +

Z Z I F3 N

N 2 P2

L1 L1 F4

18e 18a 30e

2 UVS 1

3

18a

230V

18e

- +

6a

6c

4a

4c

4e

6e

12a

12c

10a

10c

10e

12e

22a

22c

20a

20c Z Z I

N N

3 P3 L1 L1

F6

24e 24a 30e

2 UVS 1

3

24a

230V

24e

- +

F5 20e

22e

28a

28c

26a

26c Z Z I

N N

4

F7

L1 P4

L1 F8

26e

28e P1–P4: PFF 704

ma

x.

2 A

, 2

64

V

ma

x.

2 A

, 2

64

V

ma

x.

2 A

, 2

64

V

ma

x.

2 A

, 2

64

V

Page 56: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

54

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

8 .11 Field bus interface PFA 700 For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP, in order to transfer measuring, control and regulation signals as a bundle.

4 digital inputs: 24 V DC, ± 10%, < 10 mA, 4 digital outputs: relay contact, max. 1 A, 264 V (not fused internally).

Mains voltage: 110 – 240 V AC, -15/+10%, 50/60 Hz.

Further information can be found in brochure PFA.

PFA 700 L1 32b

N 30a

15b 24 V=

16b 0 V

C

VP 8b

RxD/TxD-P 11b

RxD/TxD-N 12b

2

24 V 18b 1

24 V 21b

0 V 22b 4

1c

9c

10c

18c

1a

9a

10a

18a

19a

23a

20c

23c

19c

17b

24 V

30c

1. PFU

9. PFU

1. PFU

9. PFU

DGND 14b 1. PFU

9. PFU

1. PFU

9. PFU

I/O

24 V 23b 1

24 V 26b 4

1. PFU

5. PFU

6. PFU

9. PFU

PFU

1

L1 30e

26e PFU

PR

OF

IBU

S D

P

… …

Page 57: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

55

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

8 .12 Impulse system MPT 700 With 11 outputs for activation of burner control units PFU 780. The furnace atmosphere is circulated thanks to intermittent operation, and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensured.

Mains voltage: 95 – 240 V AC, ± 10%, 50/60 Hz.

Power consumption: 10 VA.

Additional auxiliary voltage: 12 – 24 V DC, ± 10%, max. 1.1 A.

Controller inputs: 2 x 0(4) – 20 mA with common ground, float- ing, load impedance approx. 225 Ω.

Three-point step input: floating, 12 – 24 V DC, load impedance approx. 2.7 kΩ.

Digital inputs E1 – E3: with common ground, floating, 12 – 24 V DC, load impedance approx. 2.7 kΩ.

Further information can be found in brochure MPT.

L1

MPT 700 30z

F1

N

PE

30b

30d

28z

28b

28d

32z

32b

32d

2b

4b

10b

12b

12–24 V

0 V

8888

mA 1

mA 2

GND

20z

20b

20d

88

0 – 100%

GND

100% – 0

18z

18b

18d

2z

2d

4z

4d

6z

6d

8z

8d

A1

A2

A3

A4

A5

A6

A7

A8

12–24 V E1

14z

E2

10z

10d

/ 1

/ 2 14d

E3 µC 12z

0 V

16z

14b

16b

6b

8b COM

Page 58: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

56

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

9 Technical data Mains voltage: 220/240 V AC, -15/+10%, 50/60 Hz or 110/120 V AC, -15/+10%, 50/60 Hz, for grounded and ungrounded mains.

Power consumption: < 8 VA.

Control inputs: Input voltage/current: Burner, air valve, multi-flame control and remote reset: 24 V DC, ± 10%, < 7 mA per input.

Input voltage for safety interlocks, digital input DI and purge = mains voltage.

Input voltage of signal inputs:

Rated value 110/120 V AC 220/240 V AC

Signal “1” 80 – 132 V 160 – 264 V

Signal “0” 0 – 20 V 0 – 40 V

Frequency 50/60 Hz 50/60 Hz

Rated value 24 V DC

Signal “1” 24 V, ±10%

Signal “0” < 1 V

Inherent current:

Output voltage for voltage-related outputs = mains voltage

Contact rating

Gas valve V1, V2 Max. 1 A resistive Max. 1 A cos 0.3

Air valve Max. 1 A resistive Max. 1 A cos 0.3

Ignition Max. 1 A resistive Max. 1 A cos 0.3

Number of oper- ating cycles

Max. 1,000,000, typically 400,000

Max. 250,000, typically 100,000

Output current: max. 2 A per output, but total current for valves and ignition transformer max. 2.5 A.

Number of operating cycles: Mains switch: 1000, Reset/Information button: 1000.

typ. 5 mA Signal “1”

t

Page 59: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

57

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

Signalling contacts: max. 24 V, 1 A.

Flame control: Sensor voltage: approx. 230 V AC. Sensor current: > 1 μA, Length of sensor cable: max. 100 m.

Fuse in unit:

F1: 3.15 A, slow-acting, H pursuant to IEC 127-2/5, F2: 3.15 A, slow-acting, H pursuant to IEC 127-2/5.

Ambient temperature:

-20 to +60°C (-4 to +140°F), Climate: no condensation permitted.

Enclosure: IP 00 pursuant to IEC 529,

after installing in a 19" module subrack according to the in- structions, e.g. type BGT, the front corresponds to IP 20.

Input/Output safety circuit:

All the inputs and outputs marked “ ” (see connection dia- grams) may be used for safety tasks.

Weight: approx. 650 g (23 oz)

Page 60: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

58

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

9 .1 Safety-specific characteristic values

In the case of ionization control, suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 97.9%

Type of subsystem Type B to EN 61508-2, 7.4.3.1.4

Mode of operation High demand mode pursu- ant to EN 61508-4, 3.5.12

Mean probability of dan- gerous failure PFHD

1.34 x 10-8 l/h

Mean time to dangerous failure MTTFd

Safe failure fraction SFF 99.2%

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic).

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SIL

a –

b 1

c 1

d 2

e 3

Pursuant to EN ISO 13849-1:2006, Table 4, the PFU can be used up to PL e.

Max. service life under operating conditions:

20 years after date of production, plus max. 1/2 year in stor- age prior to first use.

For a glossary of terms, see page 62 (Glossary).

Page 61: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

59

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

9 .2 Operating controls A: 2-digit 7-segment display

B: Reset/Information button to reset the system after a fault or to scan parameters on the display.

C: Mains switch

D: Optical interface

E: Type label

A

B C

D

E

Page 62: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

60

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

10 Maintenance cycles Burner control unit PFU requires little servicing.

Page 63: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

61

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

1

11 Legend

88 Display

88 Blinking display

Ready

Safety interlocks (Limits)

Burner start-up signal

DI Digital input

Ignition transformer

Gas valve

Air valve

P Purge A Ext. air valve control

Flame signal

Burner operating signal

Fault signal

Reset

Input signal

Output signal

Flame simulation check

tW Waiting time 2 s

tSA Safety time on start-up 3 s, 5 s or 10 s

tSB Safety time during operation < 1 s or < 2 s

tZ Ignition time 2 s, 3 s or 6 s

tLV Flame simulation delay time 25 s

tFS Flame proving period 0 – 25 s

tB Minimum combustion time tSA up to max. 25 s

tBP Minimum burner pause time 0 – 250 s

tKN Low fire over run time 0 s, 5 s, 15 s or 25 s

Input/Output safety circuit

Page 64: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

62

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

12 Glossary

12 .1 Waiting time tW

12 .4 Flame simulation/Flame simulation delay time tLV

Once the start-up signal has been applied, the waiting time tW starts to elapse. During this time, a self-test is conducted to detect errors in internal and external circuit components. If no malfunction is detected, the burner will start up.

12 .2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve, when no flame signal is detected. The safety time on start-up tSA (3, 5 or 10 s) is the minimum operating time of the burner and burner control unit.

12 .3 Ignition time tZ If no malfunction is detected during the waiting time tW, the

An extraneous signal (flame simulation) is a flame signal that is detected, although there should be no flame according to the program sequence. If such an extraneous signal is detected, the flame simulation delay time tLV starts to elapse. If the flame simulation is discontinued during the flame simu- lation delay time tLV, start-up can be initiated or operation continued. Otherwise, a fault lock-out occurs.

12 .5 Safety time during operation tSB

ignition time tZ then starts to elapse. Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited. The duration of the ignition time is either 2, 3 or 7 seconds (depending on safety time tSA selected).

If the flame fails during operation, the valve outputs are dis- connected within the safety time tSB.

t

01 0

30e 10e 28c 16c 26a 18e

2c–4c 2e–4e

88 L1

V1

V2

tW tZ

tSA

t

01 01 30e 10e 28c 16c 26a 18e

2c–4c 2e–4e

88 L1

V1

V2

tW t

tLV

04 04 30e 10e 28c 16c 26a 18e

2c–4c 2e–4e

88 L1

V1

V2

tSB t

Page 65: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

63

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

The default safety time during operation tSB in accordance with EN 298 is 1 second. In accordance with EN 746-2, the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see “Project plan- ning information”). Note the requirements of the Standards!

12 .6 Flame signal If a flame is detected, the flame detector will supply a flame signal.

12 .7 Fault lock-out In the event of a fault lock-out, all valves and the ignition trans- former are disconnected from the electrical power supply, and a fault is signalled. Resetting must take place manually following a fault lock-out.

12 .8 Safety interlocks (Limits) The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application, e.g. safety temperature limiter, minimum/maxi- mum gas pressure) must isolate input from the voltage supply.

12 .9 Pilot gas valve V1 The start fuel flow rate for the burner is released by pilot gas valve V1. It opens when the safety time on start-up tSA starts to elapse. It remains open until the burner is switched off again by a normal shut-down or fault lock-out.

12 .10 Main gas valve V2 Once the safety time on start-up tSA has elapsed, the main gas valve V2 is opened. It remains open until the burner is switched off or a fault is signalled.

12 .11 Continuous operation The gas burner runs continuously for more than 24 hours.

12 .12 Air valve The air valve can be used

– for cooling,

– for purging,

– to control the burner output in ON/OFF mode and in High/ Low mode when using a pneumatic air/gas ratio control system.

( PFU 760L)

L1 (L1) 30e PFU 760

22e N

F1 sk1 16c

26e 18e V1

DI

22a V2

30a N (L2)

32c 24c

a 2a

4a

P

Page 66: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

64

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

12 .13 Diagnostic coverage DC Measure of the effectiveness of diagnostics, which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failures

NOTE: Diagnostic coverage can exist for the whole or parts of a safety-related system. For example, diagnostic cover- age could exist for sensors and/or logic system and/or final elements. Unit: %.

from EN ISO 13849-1:2008

12 .14 Mode of operation High demand mode or continuous mode

Operating mode, where the frequency of demands for opera- tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequency

from EN 61508-4:2001

12 .15 Safe failure fraction SFF Fraction of safe failures related to all failures, which are as- sumed to appear

from EN 13611/A2:2011

12 .16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode. Unit: 1/h

from EN 13611/A2:2011

12 .17 Mean time to dangerous failure MTTFd

Expectation of the mean time to dangerous failure

from EN ISO 13849-1:2008

Page 67: Burner control unit PFU 760 - add-furnace.com · 2021. 3. 4. · Safety time during operation t SB for V1 and V2.....29 4.5.2 Fault ... 49 8.1 High-voltage ... 12.5 Safety time during

PFU 760 · Edition 05.11

65

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: [email protected]

บริษัท: บริษัท เอดีดี เฟอร์เนส จ ำกัด Add Furnace Co.,Ltd.

ท่ีอยู่:(bangkok) 44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒันา กทม. 10170.

website: https://www.add-furnace.com/

e-mail: [email protected] [email protected]

โทร.(ออกแบบ): 08-08-170-170, 088-300-1122

โทร: 02-888-3472

Online Support: Line ID: @add11 Wechat ID: add0883001122

แฟกซ์: 02-888-3258

line ID: @add11