Buckling Length REPORT

Embed Size (px)

Citation preview

  • 8/18/2019 Buckling Length REPORT

    1/128

    Aalborg University

    Structural and Civil Engineering, 9th Semester

    Department of Civil Engineering

    Sohngårdsholmsvej 57

    www.bsn.aau.dk

    Title:   Determination of buckling lengthof columns in multi storey plane

    steel frames

    Project period:   B9K - Trainee, Au-

    tumn 2010

    By: Sugunenthiran Markandu

    Supervisors:Lars Pedersen

    Print runs: 4

    Number of pages: 76

    Appendix: 42 Appendix report and 1

    Appendix CD.

    Completed: 6 January 2011

    Synopsis:

    Buckling length of columns in a load-bearing

    multi storey steel frame structure, used

    as case study, are determined following

    approaches given by AISC and DIN 18800.

    Additionally the numerical tool Robot is

    applied for this issue.

    Initially frame design in practice, the differentmethods given by EC 3 are explained where

    design based on equivalent column method

    is chosen. Hence the concept of effective

    buckling length is explained by considering

    the fundamental column cases where the in-

    fluence of support conditions on the buckling

    length of column (K-factor) is elaborated.

    Several other buckling analysis are performed

    on frames with variance restraint conditions

    in Robot in order to determine factors that

    influence on K-factor of columns in framed

    structure.

    K-factor determination charts given by AISC

    and DIN 18800 are presented where the

    use and limitations of them are explained.

    Furthermore theoretical deviation of AISC

    charts are elaborated.

    Two load cases are considered due to obtain K-

    factor of columns in the case study structure

    by application of AISC and DIN 18800

    approaches. Buckling analyses in Robot areperformed for this issue. The determined

    results by employing different approaches are

    compared and discussed. Furthermore the

    influence of the K-factor on the final result is

    examined by performing code check in Robot.

    Finally the conclusion is made upon which

    method is most suitable for practical use.

    The report’s content is freely available, but the publication (with source indications) may only happen by agreement

    with the authors.

  • 8/18/2019 Buckling Length REPORT

    2/128

  • 8/18/2019 Buckling Length REPORT

    3/128

    Preface

    This report is a product of project work made by the author at the   3rd semester of 

    the candidate program of Structural and Civil Engineering at the Department of Civil

    Engineering at Aalborg University.

    The project is made during an internship at Rambøll Aalborg, where the author also

    participated in other projects and activities. These projects and activities are shortlydescribed in appendix F. The project is completed within the period of 6th of September

    to the 07th of January 2011.

    The project covers the investigation of different methods to determine the effective

    buckling length of columns in a load-bearing multi storey steel frame structure. The

    case study used for the current project is a plan steel frame structure part from a project

    called "Z-house".

    The project report consists of four parts: Pre-analysis of frame design, Case study,

    Conclusion and Appendix. The appendix is divided into A, B, C etc., which are found at

    the end of the report.

    The project report uses the Harvard method of bibliography with the name of the source

    author and year of publication inserted in brackets after the text, for example:  [Bonnerup

    and Jensen, 2007]. The lists of all the sources of reference are found at Bibliography list

    in the end of the report.

    A resume of this report including important conclusive matters gathered by different

    analysis and studies, with the aim to provide a quick overview of this project for staff at

    Rambøll and furthermore be a guidance to determine the K-factor in framed structure of 

    steel in practice, is given in appendix E.

    Acknowledgements

    I would like to acknowledge the employees at the Building department at Rambøll Aalborg

    for daily guidance and for being good colleagues during the internship. I was very pleasant

    with my stay at Rambøll Aalborg where I found both the working environment and the

    social life in general very much attractive.

    iii

  • 8/18/2019 Buckling Length REPORT

    4/128

  • 8/18/2019 Buckling Length REPORT

    5/128

     Table of contents

    Chapter 1 Introduction   1

    1.1 Problem statement   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    1.2 Problem definition   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    1.3 Methods of analysis   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    1.4 Layout of the report   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    I Pre-analysis of frame design   7

    Chapter 2 Frame design in practice   9

    2.1 Frame classification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    2.2 EC 3 - formulation   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    2.2.1 1. and 2. order response   . . . . . . . . . . . . . . . . . . . . . . . . . 11

    2.2.2 Accounting for P  −∆  and  P  − δ  effect in EC 3   . . . . . . . . . . . . 13

    2.3 Design approach preferred at Rambøll   . . . . . . . . . . . . . . . . . . . . . 14

    Chapter 3 Elastic buckling of columns   17

    3.1 Euler buckling load  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    3.2 Critical buckling load   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    3.2.1 Effective length factor (K-factor)   . . . . . . . . . . . . . . . . . . . . 23

    3.3 Critical buckling load of columns in framed structure  . . . . . . . . . . . . . 25

    Chapter 4 K-factor determination in practice   27

    4.1 AISC - formulation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    4.1.1 Non-sway frame   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    v

  • 8/18/2019 Buckling Length REPORT

    6/128

    Trainee report - Rambøll - Autumn 2010 Table of contents  

    4.1.2 Sway frame   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

    4.1.3 Assumptions made in AISC specification . . . . . . . . . . . . . . . . 36

    4.2 DIN 18800 procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

    4.2.1 Non-sway frame   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

    4.2.2 Sway frame   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

    4.3 Frame base effects on K-factor   . . . . . . . . . . . . . . . . . . . . . . . . . 43

    II Case study   45

    Chapter 5 Case study structure   47

    5.1 Load and load cases   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

    5.2 Global analysis in Robot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    Chapter 6 K - factor determination   53

    6.1 AISC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    6.2 DIN 18800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

    6.3 ROBOT   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

    6.4 Results compairison   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

    6.5 Code check using Robot   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

    6.5.1 Results and sensitivity analysis   . . . . . . . . . . . . . . . . . . . . . 67

    III Conclusion   71

    Chapter 7 Conclusion   73

    Chapter 8 Putting into perspective   75

    IV Appendix   77

    Appendix A Buckling analysis in Robot   1

    A.1 Buckling analysis in Robot   . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

    A.2 Convergence test   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    vi

  • 8/18/2019 Buckling Length REPORT

    7/128

    Table of contents 9th semester  

    Appendix B Factors that influence the K-factor   7

    B.1 Bracing effect of bays   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    B.2 Bracing effect of storeys   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    Appendix C Frame Base Effects on K-factor   13

    Appendix D K-factor determination using Robot   17

    D.1 Global buckling analysis in Robot . . . . . . . . . . . . . . . . . . . . . . . . 17

    D.2 Application of Robot to local storey buckling load determination   . . . . . . 20

    Appendix E Resume of the report   27

    Appendix F Overview of other participated project and activities at

    Rambøll   35

    Appendix G Guide to Appendix CD   39

    G.1 K-factor determination in sway frame   . . . . . . . . . . . . . . . . . . . . . 39

    G.2 Course - Buckling analysis in Robot   . . . . . . . . . . . . . . . . . . . . . . 39

    Bibliography   41

    vii

  • 8/18/2019 Buckling Length REPORT

    8/128

  • 8/18/2019 Buckling Length REPORT

    9/128

    Introduction1In this chapter the motivation for this project will be described followed by a 

     presentation of the problems to be handled. This leads to the problem definition

    for the project, which will be answered in the report. Furthermore the objectives 

    of the project in order to handle the problem are described.

    Design of tall buildings using steel frames is a very common method in the modern

    industry. Utilising steel frames as the primary load bearing structure allow a long spanning

    multiple-storey construction, where the benefit is that steel elements don’t take up a lot

    of space. Tall buildings made of steel frames have a lower self weight in comparison with

    for instance a solution of reinforced concrete elements. This means that the foundation

    cost of the building is lower than else. Furthermore steel elements are easier to handle at

    the construction site. These aspects make a construction solution of steel frames simple

    and economical, [Thomsen, 1968]. An example on such a construction is shown in figure

    1.1.

    Figure 1.1.  The exclusive project: "Z-house" near Aarhus harbour

    1

  • 8/18/2019 Buckling Length REPORT

    10/128

    Trainee report - Rambøll - Autumn 2010    1. Introduction 

    The construction sketch shown in figure 1.1 is the exclusive project named "Z-house". The

    house is intended to be build at a location near Aarhus harbour. The building is planned

    to consist of  11000 m2 housing area and  14000 m2 for commercial lease. The construction

    work is suspended at the moment caused by the economic crisis. But Rambøll Aalborg

    has until the date of suspension been the advisor regarding the engineering field related

    to the project. The construction engineers involved in the project at Rambøll Aalborg

    have chosen the primary load bearing principle of the house to be based on steel frames.

    These frames, with different levels in height, are joined in extension to each other in order

    to meet the special requirements of the geometry for the Z-house. [Dalsgaard, 2008]

    The static model shown to the left in figure  1.2,  represents a simplified frame from the

    project of Z-house. This static model is used for the case study in the current project. It

    is an unbraced, pinned, 10-storey frame consisting of 2 bays. Each storey is with a height

    of  3.6  m  and a bay span of  8   m. The connections between the columns and beams are

    regarded to be rigid, see the illustration to right in figure  1.2.  HE400B profiles are used

    for the columns in all the storeys. The beams in all the storeys are designed asymmetrichaving a wide lower flange in order to support the concrete floor, the dimensions are shown

    in figure 1.2.

    Figure 1.2.   Two-bay and ten-storey plane frame construction to be used for the case study

    2

  • 8/18/2019 Buckling Length REPORT

    11/128

    1.1. Problem statement 9th semester  

    The local coordinate system of the elements is illustrated on a column and beam element

    but is valid for all the other respective members in the structure. The frames are intended

    to be placed with an individual distance of  6  m  in longitudinal direction (parallel with the

    z-axis). It shall be mentioned that the stability in the z-axis direction is assumed to stable;

    hence only in plane situation is required by Rambøll to be considered. In accordance to

    the illustrated local coordinate system for the elements, the geometric and mechanical

    parameters of the members are presented in table  1.1.

    Profil Length   [mm]   E [M P a]   I z

    mm4

      f yk [M P a]

    Asymmetric beam   8000 210 · 103 776453 · 103 350

    HE400B column   3600 210 · 103 576805 · 103 350

    Table 1.1.  Geometrical and mechanical parameters of members involved in the frame used as

    case study, see figure 1.2 for illustration of the case study structure.

    Determination of the effective buckling length of the columns in the case study structure

    shown in figure 1.2,  by employing different analytical and numerical methods is the aim

    of this project. The motivation and furthermore why construction engineers at Rambøll

    Aalborg are interested on this study is described in the following.

    1.1 Problem statement

    The stability analysis of a frame shall be performed following the code of practice. Hence

    the stability of steel frame structure shall be insured by following the instruction given inEurocode 3. In general the code introduces three different methods in order to analyse

    and document the stability of the frame. But basically the design procedure is required

    to be based on either 1. or 2. order theory or by a combination of these. A more detailed

    description of this is given in chapter 2.   [EC3, 2007]

    The construction engineers at Rambøll Aalborg prefer to apply the equivalent column

    method (based on the 1. order theory) for the stability analyses of frames. This is due to

    the fact that the equivalent column method is the traditional way which the engineers are

    familiar with. Therefore they find it to be the most secure way of insuring the stability of 

    the frames as they are able to follow the calculation steps. A more detailed description of 

    why they prefer the equivalent column method is given in chapter  2.

    Applying the equivalent column method requires the designer to determine the effective

    buckling length value of the columns based on a global buckling mode of the frame

    accounting for the stiffness behaviour of the members and joint and the distribution of 

    the compressive forces. This means that the objective get complex. Eurocode 3 nor

    Danish National Annex suggest any procedure to determine the effective buckling length

    value of the columns but refer to some other relevant literature for this objective. It is

    hence essential to find and employ a method which gives reliable results and the use of 

    numerical tools can be relevant. There are hence a number of methods; therefore the

    accuracy, usability and limitations may be studied in order to point out one or moresuitable methods in the practical engineering work. [EC3, 2007]

    3

  • 8/18/2019 Buckling Length REPORT

    12/128

    Trainee report - Rambøll - Autumn 2010    1. Introduction 

    The description of the problem and requirements from the construction engineers at

    Rambøll lead to the following problems which seeks to be investigated and answered

    through the project:

     Point out, one or more methods whereby a quick and reliable estimate of effectivebuckling length of columns in framed steel structure can be determined.

    This project focuses on determination of the effective buckling length of columns in frames

    applying different methods. Hence the following problem formulation is the main issue of 

    this project:

    Determination of the effective buckling length of columns in steel framed 

    structures by employing different analytical and numerical methods

    1.2 Problem definition

    In order to handle the described problem, the following objectives for the project are

    made:

    •  Understand the design requirements and methods for steel frames given in Eurocode

    3 and what is meant by 1. and 2. order analysis.

    •  Understand the concept of the effective buckling length in general.

    •  Classify whether a given frame is of sway or non-sway type.•   Perform analyses in order to determine the parameters that influence buckling length

    of columns in a frame.

    •   Apply different approaches to determine the effective buckling length of columns

    and study theirs assumption, usability and limitations.

    •  Perform analyses in order to verify the reliability of the commercial program Robot

    with respect to buckling analysis and examine in what extend it can be applied due

    to determine the buckling length of columns in framed structures.

    •  Determine the effective buckling length of columns in the structure presented as case

    study using different analytical and numerical methods.

    •  Perform code check and sensitivity analysis due to examine the influence of effectivebuckling length value for the final design.

    Due to the lack of time available for this project, limitations on the treatment of some

    of the described objectives are made. These limitations are described in the respective

    chapters. Furthermore the instability problem, lateral torsional buckling of the members

    is not included this study.

    4

  • 8/18/2019 Buckling Length REPORT

    13/128

    1.3. Methods of analysis 9th semester  

    1.3 Methods of analysis

    Analytical approach

    Alignment charts given by AISC, American institute of steel construction, and charts

    published by the German code DIN 18800 are employed in order to determine theeffective buckling length of columns. Furthermore the theoretical background of the AISC

    alignment charts is developed analytically.

    Eurocode 3, mentioned EC 3 in the following, is studied in order to understand the

    design requirement in practice. The theoretical background is granted by study of several

    scientific notes and books on analysis of steel frame structures, references are made

    throughout the report.

    Numerical approach

    The finite element program: "AutoDesk Robot Structural Analysis Professional 2011",mentioned as Robot in the following, is applied in order to model and perform buckling

    analysis. Furthermore calculations programs available at Rambøll as Excel and MathCAD

    are used in order to set up small programs and MatLab is employed to plot graphs.

    The use of the program Robot is enabled by 1 week of training at Rambøll, following

    the manuals offered by AutoDesk. Understanding of the methods Robot calculations are

    based on, are gathered by studying the Robot manuals.

    1.4 Layout of the report

    This report is divided into 4 parts exclusive the introduction. Each chapter of this report

    starts with an overview of the contents in the actual chapter. The current report consists

    of following chapters and appendix:

    •  Chapter 1: Introduction

    Part I - Pre-analysis of frame design

    •  Chapter 2: Frame design in practice

    •  Chapter 3: Elastic buckling of columns

    •  Chapter 4: K-factor determination in practice

    Part II - Case study

    •  Chapter 5: Case study structure

    •   Chapter 6: K-factor determination

    5

  • 8/18/2019 Buckling Length REPORT

    14/128

  • 8/18/2019 Buckling Length REPORT

    15/128

    Part I

    Pre-analysis of frame design

    7

  • 8/18/2019 Buckling Length REPORT

    16/128

  • 8/18/2019 Buckling Length REPORT

    17/128

    Frame design in practice2In this chapter the frame design in practice following EC 3 is presented. Initially 

    the discussion and definition on classification of the frame type is given. This is 

    followed by a description of EC 3 formulation of theory and methods to be applied 

    in practice design of frames. Finally the design method preferred by Rambøll is 

    described whereby the cause for the current study of this project is elaborated.

    It shall initially be mentioned that buckling analysis in Robot is widely used in this project.

    Hence a description on the method Robot uses and input parameters it requires due to

    perform buckling analysis and furthermore a convergence test is made, see appendix   A.

    The reader is strongly suggested to read this document due to get the theoretical background 

    of buckling analysis in Robot.

    The main goal of this chapter is to clarify what is stated in EC 3 regarding the practical

    design of frames. Eurocode is in general made to cover a large number of construction

    types why it often contains a wide description of the design methods. Therefore it becomes

    hard to get an overview of the design requirement for a given construction. Hence this

    chapter is made due to enable a brief overview of the requirements in EC 3 that is valid

    for frames of the kind presented as case study in chapter  1.  But before this objective, the

    current chapter is initiated by a classification study on frame types introducing definitions

    and terms that are widely used in the stability study of frames and not least in this

    chapter.

    2.1 Frame classification

    When dealing with stability of columns or stability of frames, codes and design books

    commonly use the following terms, which is dependence on the deformation fashion that

    occurs when the frame is subjected to loading: [University of Ljubljana - Slovenia, 2010a]

     Sway / unbraced frame, shown to right in figure 2.1.•  Non-sway / braced frame, shown to left in figure  2.1.

    9

  • 8/18/2019 Buckling Length REPORT

    18/128

    Trainee report - Rambøll - Autumn 2010    2. Frame design in practice 

    Figure 2.1.  Non-sway/braced frame to left and sway/unbraced frame to right.   [University of 

    Ljubljana - Slovenia, 2010a]

    Sway frame is defined as a frame which is not restrained from deflecting laterally and

    non-sway is hence a frame which is restrained from deflecting laterally. But this doesn’t

    means that the structure example shown in figure 2.1  to right and left always is classified

    as sway and non-sway frame, respectively. If the restraint or the bracing of the braced

    structure is very flexible, then the frame may be classified as sway frame. Likewise if thestiffness of the elements in the unbraced structure is sufficiently large, then the frame may

    be classified as non-sway frame. [University of Ljubljana - Slovenia, 2010a]

    In fact the definition given above of non-sway frame has no real significance and is only

    valid in an "engineering" sense. Because there is no structure, whether it is braced

    or unbraced that doesn’t displace laterally. But it is a question on how small the

    displacements are thus to be considered equal zero in an engineering sense. But eventually

    the reason for defining whether the frame is a sway or non-sway type is due to argue for

    adopting conventional analysis on non-sway frames or if the 2. order analysis (on sway

    frames) shall be performed. Further description on this matter is given in this chapter

    2.2.   [University of Ljubljana - Slovenia, 2010a]

    A more precise definition of a non-sway frame is hence a structure which, from the points of 

    view of stability, can be considered to have small inter-storey displacements. Therefore the

    local column buckling is independent from the global frame buckling, why the instability

    problem can be uncoupled,  [University of Ljubljana - Slovenia,  2010a]. EC 3 indirectly

    provides the following criterion in order to define whether the frame can be considered as

    sway or non-sway type. A frame may be classified as non-sway if  αcr   factor for a given

    load case satisfies the criterion given in equation  2.1.   [EC3, 2007]

    10

  • 8/18/2019 Buckling Length REPORT

    19/128

    2.2. EC 3 - formulation 9th semester  

    αcr  =  F crF Ed

    ≥ 10   (2.1)

    αcr   Critical buckling factor, by which the design loading have to be increasedto cause elastic instability in the global mode

    F Ed   The vertical design load on the structure

    F cr   Elastic critical buckling load for global instability mode based on initial elastic

    stiffness

    It is hence seen that the definition of a frame as sway or non-sway type depends on the

    magnitude of vertical loads; which is understandable since even a very flexible structure

    doesn’t have any 2. order effects if the vertical loads are equal to zero. Therefore the

    classification of sway or non-sway type is not general for a given frame, but is just validfor a specific vertical load case. If equation  2.1  is satisfied, the global buckling can be

    neglected when carrying out the check against column buckling, further description on

    this matter is given in the following. [University of Ljubljana - Slovenia, 2010a]

    2.2 EC 3 - formulation

    In stability analysis of frames, flexure is the primary means for unbraced rigid frames by

    which they resist the applied load. Therefore it may be essential to account for so called

    2. order effects. The effect of deformed geometry (2. order analysis) of a structure shallbe included if they significantly increase the action effects. Therefore influence of 2. order

    effects shall be specified and evaluated. In the following the formulation given in EC 3 on

    this matter is described. Initially what is meant by 1. and 2. order response is illustrated.

    [EC3, 2007]

    2.2.1 1. and 2. order response

    EC 3 suggests design procedure of frames based on either 1. or 2. order analysis. Before

    going onto further details with the design regulations, a description on what is assumedand accounted for in 1. and 2. order analysis is given in the following. [University of 

    Ljubljana - Slovenia, 2010b]

    •   1. order analysis

    –   Assumes small deflection behaviour.–  Resulting forces and moments do not account for the additional effect due to

    the deformation of the structure under loading.

    11

  • 8/18/2019 Buckling Length REPORT

    20/128

    Trainee report - Rambøll - Autumn 2010    2. Frame design in practice 

    •   2. order analysis

    – Large displacement theory :

    ∗   Resulting forces and moments take full account of the effects due to the

    deformed shape of both the structure and its members.

    – Stress stiffening :

    ∗  Effect of element axial loads on structure stiffness: Tensile loads stiffening

    an element and compressive loads softening an element.

    In the following two cases, symmetric and asymmetric loading on an unbraced in-plane

    frame is considered in order to illustrate what is meant by the 2. order effect. Figure

    2.2 to left shows an undeformed frame with uniformly distributed load. For this case the

    primary deflection due to load  P < P cr  will be symmetrical until the bifurcation point is

    reached, illustrated in the middle in figure 2.2.  A detailed description on the critical load

    P cr  and the bifurcation point is given in chapter 3. When the critical load is reached thedeflection pattern changes to fail by side-sway buckling, shown on the illustration to right

    in figure 2.2. This behaviour is sketched in a load - lateral deflection curve, see figure 2.4,

    where elastic behaviour is assumed.   [Galambos and Surovek, 2008]

    Figure 2.2.  Symmetric deflection of the frame due to symmetric loading until bifurcation point

    is reached, hereafter deflection pattern changes to fail by side-sway buckling

    Consider the frame in figure   2.3,   which is in addition to the previous case, subjected to

    a lateral load   H . This frame doesn’t have any bifurcation point where the deflection

    pattern changes, but it deflects laterally from the start of loading. The  P  −∆  behaviour

    of this case can be described based on either 1. or 2. order deflection, see figure  2.4.

    In 1. order analysis, the load - deflection response is based on the undeformed structure

    where equilibrium is formulated on the deformed structure; hence it results in a linear load

    deflection curve. In the 2. order analysis, a load increment gives a incremental deflection,

    which is a little more than in the previous load increment. Hence slope of the 2. order

    curve decreases as the load increases, why it results in a non linear curve in figure  2.4.

    [Galambos and Surovek, 2008]

    12

  • 8/18/2019 Buckling Length REPORT

    21/128

    2.2. EC 3 - formulation 9th semester  

    Figure 2.3.  Unsymmetrical deflection (side-sway buckling) of the frame due to lateral loading

    H .

    Figure 2.4.   Load - lateral deflection curve   P  − ∆   for symmetric and unsymmetrical loadingincluding 1. and 2. order analysis.   [Galambos and Surovek, 2008]

    Figure 2.3 also shows the element deflection  δ , due to the axial loading. Hence to provide

    a complete stability analysis of frame both the  P  −∆ and  P  − δ  effects may be included.

    Such an analysis is called 2. order  P  − ∆− δ  analysis.  [S.L Chan & C.K. Lu, 2006]

    2.2.2 Accounting for   P  −∆  and   P  − δ  effect in EC 3

    EC 3 states the criterion given in equation   2.1  for the safety factor   αcr; if (αcr  ≥   10),

    the 2. order effect is assumed to be neglectable and the calculations can be performed

    using 1. order elastic analysis. For critical value lower than three,  αcr  ≤  3, a precise 2.

    order analysis shall be performed. For intermediate values,  3 ≤  αcr  <  10, EC 3 suggests

    to multiply the horizontal loads due to wind and imperfections by an amplification factor

    given by the equation 2.2.   [EC3, 2007]

    Afactor  =  1

    1−

      1

    αcr

    (2.2)

    13

  • 8/18/2019 Buckling Length REPORT

    22/128

    Trainee report - Rambøll - Autumn 2010    2. Frame design in practice 

    The global critical value αcr for the structure is directly obtainable by performing buckling

    analysis in Robot. Hence it can be verified if 2. order effect shall be included. Anyhow EC

    3 suggests three approaches in order to account for  P  − ∆− δ . Without going to details,

    it can briefly be said that EC 3 differentiate between three kind of analysis in order to

    demonstrate the structural stability of frames:   [EC3, 2007]

    1.   Complete P −∆−δ  analysis method: Analysis where 2. order effects in individual

    members (P  − δ  effect) and relevant member and global imperfections are totally

    accounted for in the global analysis (P  − ∆ effect) of the structure.

    •  No individual stability check for the members is necessary.

    2.   Partly   P  − ∆  −  δ   and partly equivalent column method: Analysis where

    2. order effects in individual members (P  − δ  effect) or certain individual member

    imperfections are not fully accounted for in the global analysis (P −∆ effect) but 2.

    order effect of global imperfections are included.

    •  Individual stability check for the members following the instruction given in EC

    3, section 6.3: "Buckling resistance of members" is necessary, where buckling

    length equals to the system length is used.

    3.   Equivalent column method: Analysis where only 1. order analysis, without

    considering imperfections, is accounted for in the global analysis.

    •  Stability of the frame is accessed by a check with the equivalent column method

    according to the instruction given in EC 3, section 6.3. The buckling length

    values should be based on a global buckling mode of the frame accounting for

    the stiffness behavior of the members and joints, the presence of plastic hingesand the distribution of compressive forces under the design load.

    As the different design approaches stated in EC 3 are explained, the approach that the

    construction engineers at Rambøll prefer to use and the reason for it is described in the

    following.

    2.3 Design approach preferred at Rambøll

    The construction engineers at Rambøll Aalborg prefer to use the design approach based on

    the equivalent column method. This is due to the fact that the equivalent column method

    is the conventional method they are familiar with, as described in the introduction, chapter

    1.

    On the other hand the numerical tool Robot, available at Rambøll, is able to perform

    a complete   P  − ∆ − δ  analysis, and hence no individual element check is required, why

    this approach obviously seems to be a quick method. But the problem connected to

    this method the engineers call attention to, is that the global-frame and local-element

    imperfections of the structure shall be included when performing the analysis.

    14

  • 8/18/2019 Buckling Length REPORT

    23/128

    2.3. Design approach preferred at Rambøll 9th semester  

    This means that the imperfections shall be calculated, which is maybe not the main time

    consuming process, but implementing them in Robot is a very time consuming process.

    This practically means that the geometry shall be adjusted including the imperfections,

    by offsetting the element nodes. The other problem is to place the imperfections thus

    it reflects the most unfavorable situation for a given load case. This objective gets very

    complicated, as in practice a large number of load combinations shall be checked and it is

    hard to point out which one is more critical in forehand, even for an experienced engineer.

    All these complications committed to the  P −∆−δ  analysis method, makes the engineers

    in practice to prefer the well known equivalent column method following EC 3, which is

    also available in Robot. The other design approach, where partly  P  − ∆ − δ  and partly

    equivalent column method is applied, also consist of complications as described before,

    why this method neither is preferred.

    Using the equivalent column method, requires to determine the effective buckling length

    of the columns based on a global buckling mode of the frame accounting for the stiffness

    behavior of the members and joints, the presence of plastic hinges and the distribution

    of compressive forces under the design load. No suggestion is given in EC 3 or Danish

    National Annex, in terms of how to determine the buckling length of columns in frames.

    The Danish National Annex refers to some other relevant literature for this objective.

    This leads to the reason for the scope of this project as described in chapter 1. It shall be

    mentioned that presence of plastic hinges are not included this study as only the elastic

    behaviour of the structure is considered.

    15

  • 8/18/2019 Buckling Length REPORT

    24/128

  • 8/18/2019 Buckling Length REPORT

    25/128

    Elastic buckling of 

    columns3

    In this chapter the concept of effective buckling length is explained based ona study of elastic buckling of planar columns. The expression of Euler load 

    is derived for the basic case, pin-ended column. Critical buckling load and 

    thereby the effective buckling length factor (K-factor) is determined for some 

    other fundamental cases.

    The basic and essential question in a study of the stability of a given structure goes on

    whether it is stable or instable. The definition of a stable elastic structure is that "a small

    increase in load causes small increase in displacement" where the instability is defined as"a small increase in load causes large displacement". The condition of stability refers to

    the state of equilibrium of the system which can be illustrated as: [Galambos and Surovek,

    2008]

    Figure 3.1.   Illustrations indicating the state of equilibrium of a system.  [Aalborg University, -]

    The illustration (a) in figure  3.1 indicates a stable equilibrium where the "element" can

    be disturbed but will return to the initial position. Contrary to this, the illustration

    (b) indicates an unstable equilibrium where the "element" will fail if it is disturbed.

    Illustration (c) represents the neutral equilibrium, where the element will find a new

    position of equilibrium if it get disturbed. These illustrations on state of equilibrium are

    the basic for understanding the stability condition of a structure.  [Galambos and Surovek,

    2008]

    17

  • 8/18/2019 Buckling Length REPORT

    26/128

    Trainee report - Rambøll - Autumn 2010    3. Elastic buckling of columns 

    Structural engineers are familiar with so called Euler load P E , of an axial loaded column.

    This is the critical buckling load   P cr, of a pin-ended column, referred as the basic case

    in the buckling analysis. More explanation on this matter will be given later in this

    chapter. Considering figure 3.1, the state of stability at the level of critical buckling load

    is recognised as the upper limit of the condition shown at the illustration (a), meaning

    that further increase in load will lead to instability of the column where unstable state

    shown at the illustration (b) occurs. Illustration (c) represents the "loading path" from

    no load on the column till the critical buckling load where the column keeps on finding

    new positions that establish equilibrium of the system as the load increases.

    3.1 Euler buckling load

    Having illustrated the state of equilibrium of the system, the next step is to determine the

    critical buckling load of a compression member with a given support conditions. In the

    stability study of compression elements, the Euler load is used as the reference which is

    determined from the Euler buckling equation. It is of the greatest important to understand

    the derivation of the Euler buckling equation where for instance the influence of the

    boundary conditions on the critical load can be demonstrated. Thereby it becomes easier

    to understand the behaviour of a column and perform analysis of frames where the columns

    are connected to beams that act as supports. Hence derivation of the Euler buckling

    equation based on the basic case, a pin-ended column, is performed in the following.

    Bernoulli-Euler beam theory is applied in the following, where the internal forces are

    assumed to act in accordance to the undeformed plane, in other words plane cross

    section remains plane. Hence a perfectly straight, pin-ended, Bernoulli-Euler bar withthe buckling stiffness   E   ·  I , subjected to a point load   P   is considered, see figure   3.2.

    [Galambos and Surovek, 2008]

    Figure 3.2.  Pin-ended column with buckling stiffness E ·I , suspected to point load P .  [Bonnerup

    and Jensen, 2007]

    18

  • 8/18/2019 Buckling Length REPORT

    27/128

  • 8/18/2019 Buckling Length REPORT

    28/128

  • 8/18/2019 Buckling Length REPORT

    29/128

  • 8/18/2019 Buckling Length REPORT

    30/128

    Trainee report - Rambøll - Autumn 2010    3. Elastic buckling of columns 

    First derivative of  v(z)   is the slope of the deflection  v

    (z)  and is given in equation  3.14.

    The second derivative   v

    (z), given in equation  3.15,   is the curvature   κ, used to define

    the moment which fulfils the constitutive condition, see equation  3.2.   Third derivative

    v

    (z)   is the derivative of the curvature, see equation  3.16, which is utilized to define the

    shear force by differentiating the moment - curvature relation given in equation 3.2. Using

    these derivatives, the boundary conditions for various support conditions is formulated.

    [Galambos and Surovek, 2008]

    v

    = B  + C  · k · cos(k · z) − D · k · sin(k · z)   (3.14)

    v

    = −C  · k2 · sin(k · z) − D · k2 · cos(k · z)   (3.15)

    v

    = −C  · k3 · cos(k · z) + D · k3 · sin(k · z)   (3.16)

    An example of a fundamental case is a cantilever column shown in figure  3.4, where it’s

    base end is fixed and the top end is free. The critical buckling load for this case will bedetermined in the following.

    Figure 3.4.   Cantilever column subjected to axial load

    The boundary conditions for the present case are:

    •   Zero moment at  z  = 0  :   v

    (0) = 0

    •  Zero shear at  z  = 0  :   v

    (0) + k2 · v

    (0) = 0

      Zero deflection at  z  =  L  :   v(L) = 0•  Zero slope at  z  =  L  :   v

    (L) = 0

    By applaying these boundary conditions to equation 3.13 and it’s derivates, the following

    four simultaneous equations are obtained:

    v

    (0) = 0 =A(0) + B(0) + C (0) + D(−k2)

    v

    (0) + k2 · v

    (0) = 0 =A(0) + B(k2) + C (0) + D(0)

    v(L) = 0 =A(1) + B(L) + C (sin(k · L)) + C (cos(k · L))

    v

    (L) = 0 =A(0) + B(1) + C (k · cos(k · L)) −D(k · cos(k · L))

    22

  • 8/18/2019 Buckling Length REPORT

    31/128

    3.2. Critical buckling load 9th semester  

    These equation can be presented in the following matrix form:

    0 0 0   −k2

    0   k2 0 0

    1   L sin(k · L)   cos(k · L)

    0 1   k · cos(k · L)   −k · cos(k · L)

    A

    B

    D

    =   0   (3.17)

    The coefficients  A, B,C   and D  define the deflection of the buckled bar, why one or more

    of them have value other than zero. Thus, the determinant of the coefficient must be equal

    to zero, in order to obtain nontrivial solution to the eigenvalue problem. [Galambos and

    Surovek, 2008]

    0 0 0   −k

    2

    0   k2 0 0

    1   L sin(k · L)   cos(k · L)

    0 1   k · cos(k · L)   −k · cos(k · L)

    =   0   (3.18)

    Solution to the problem given in equation  3.18, or in other words solution to the critical

    buckling load  P cr   for the case shown in figure  3.4 is hence found to be contained in the

    following eigenfunction.

    cos(k · L) = 0   (3.19)

    The eigenfunction in equation 3.19 has infinite number of roots or eigenvalues as  n  goes

    from one to infinity. But as described earlier only the first defection mode   n   = 1   is of 

    interest. Hence the lowest critical buckling load is determined:

    k · L =

       P 

    E · I   · L =  n ·

     π

    2 ⇒ P cr  =

     π2 · E · I 

    4 · L2  (3.20)

    The critical buckling load for the present case is thus reduced by   25 %   in comparison

    with the Euler buckling load for pin-ended column case, see equation   3.11. Therebythe influence of the support conditions on the critical buckling load is demonstrated.

    This is done by employing the general governing differential equation, applying boundary

    conditions and solving the eigenvalue problem.

    3.2.1 Effective length factor (K-factor)

    Having determined the Euler buckling load   P E , for pin-ended column, representing the

    basic case and critical buckling load  P cr, of a cantilever column presented in figure   3.4,

    the next step is to define the relation between these given by the effective length factorK , see equation 3.21.   [Galambos and Surovek, 2008]

    23

  • 8/18/2019 Buckling Length REPORT

    32/128

    Trainee report - Rambøll - Autumn 2010    3. Elastic buckling of columns 

    K 2 =  P E P cr

    =π·E ·I L2

    π·E ·I 4·L2

    = 4   (3.21)

    Hence the effective length factor, denoted as "K-factor" in the following, is found to be:K  = 2, for a cantilever column. K-factor is the ratio between the buckling length and the

    actual column length, see figure 3.5.

    Figure 3.5.   Effectiv buckling length of a pin-ended (left) and cantilever (right) column.   [DelftUniversity of Technology, -]

    Figure 3.5 shows the buckling length of a pin-ended and cantilever case where the buckling

    length is defined as the horizontal length between the points of inflection of the deformed

    shape of the column. Point of inflection is the point at which the secound derivative of 

    the buckled shape changes sign.

    Multiplication of K-factor by the actual column length L, the equivalent or effective column

    length is determined, which is replaced in the Euler buckling equation instead of  L. Thismatter is analysed in Robot by determining the critical buckling load of a cantilever

    column of length  5  m/2 = 2.5  m, see figure 3.6.

    Figure 3.6.   Cantilever column of length  2.5 m  modelled in Robot in order to perform buckling

    analysis.

    The critical buckling load is expected to have the same magnitude as found earlier for the

    pin-ended column of   5   meter length, given the same stiffness parameters, see table  3.1.

    24

  • 8/18/2019 Buckling Length REPORT

    33/128

    3.3. Critical buckling load of columns in framed structure 9th semester 

    Thereby it can be evaluated if buckling analysis in Robot provides results in accordance

    with the theory. Hence the critical buckling load for the case shown in figure   3.6   is

    determined to P cr  = 47819.8  kN  in Robot, which is in accordance with the theory.

    Some other fundamental cases than already studied and the point of inflection of the

    deformed shape are shown in figure 3.7.  The K-factor for the cases are:

    •  Fixed-ended: Both ends are fixed -  K  = 0.5

    •  Fixed-pinned: One end is pinned, the other end is fixed -  K  = 0.7

    Figure 3.7.   Effective buckling length of a fixed-ended (left) and fixed-pinned (right) column.

    [Delft University of Technology, -]

    3.3 Critical buckling load of columns in framed structure

    In what was done, the definition of K-factor is given and explained. It was demonstrated

    that K-factor is just a method of mathematically reducing the problem of evaluating

    the critical buckling load for columns in structures to that of equivalent pin-ended braced

    columns. Determination of the K-factor of the columns in complex frame buckling problem

    is the scope of this project.

    As the bases in buckling analysis of columns are clarified, some more complex models are

    studied aiming towards the scope of this project. Hence the parameters that influence on

    the K-factor of columns in framed structures are studied in more detail, see appendix  B,

    where two analyses are made:

    •   Bracing effect of bays:   Determine chances in degree of bracing of the exterior

    column by the other members of the storey as the number of its bays increases

    stepwise from 1 to 8.

    •   Bracing effect of storeys:  Determine chance in degree of bracing on the interior

    column in a two-bay frame as the number of storeys increases stepwise from 1 to 4.

    25

  • 8/18/2019 Buckling Length REPORT

    34/128

    Trainee report - Rambøll - Autumn 2010    3. Elastic buckling of columns 

    Hence the important conclusive matters from the analyses are included here, but detail

    description and results need to be found in appendix  B:

    Bracing effect of bays

    Scientists have made research of steel framed construction on this matter and have

    concluded the following statement which is also what was verified in the study made

    in appendix B  and is hence also the conclusion of the performed analysis:

    "In general, the critical buckling load which produces failure by side-sway can be distributed 

    among the columns in a storey in any manner. Failure by side-sway will not occur until 

    the total frame load on a storey reaches the sum of the potential individual critical column 

    loads for the unbraced frame. There is one limitation, the maximum load an individual 

    column can carry is limited to the load permitted on that column for the braced case,

    K  = 1. Side-sway is a total storey characteristic, not an individual column phenomenon." 

    [Joseph A. Yura, 2003]

    Bracing effect of storeys

    Analyses made in terms to determine the bracing effect of storeys on a considered storey

    showed that only the adjoining storeys of a considered storey have remarkably effect on its

    columns K-factor. Thereby it is evaluated to be sufficient to consider only the adjoining

    storeys when determination of K - factor of columns in a given storey.

    26

  • 8/18/2019 Buckling Length REPORT

    35/128

    K-factor determination in

    practice4

    In this chapter the AISC alignment charts in order to determine K-factor of columns in sway and non-sway frames and the theoretical background in

    derivation of them are presented. Furthermore the approach given in DIN 18800 

    for K-factor determination is presented.

    Design of framed structures can among others be dealt by the concept of effective length

    or K-factor. Definition of K-factor is given in chapter  3.   Figure 4.1 illustrates the physical

    of effective buckling length of a column in a rigid connected frame.

    Figure 4.1.   Illustration on physical of effective buckling length of a column in a rigid sway frame.

    [G.Johnston, 1976]

    Studies made in chapter   3, clarify the influence of support conditions on the K-factor,

    which are illustrated for the fundamental cases. Those analyses were based on idealised

    support conditions. This assumption will not be the case for the columns in framed

    structure, as they interact with other members.

    27

  • 8/18/2019 Buckling Length REPORT

    36/128

    Trainee report - Rambøll - Autumn 2010    4. K-factor determination in practice 

    This interaction makes it necessary to consider the connecting members when designing

    columns of frames. EC 3 and Danish National Annex refer to other specific literature for

    K-factor determination. This chapter presents the approaches given in the following two

    codes of practice:

    •   AISC: American Institute of Steel Structure

    •   DIN18800: German code for the design of structural steel

    Descriptions on the use of the charts provided by the mentioned codes are given in

    subsequent sections of this chapter. The background of the AISC approach is elaborated

    due to get the theoretical understanding of the charts. The aim is to apply these procedures

    to determine K-factor of columns in the case study structure, which is done in chapter  6.

    4.1 AISC - formulation

    AISC provides so-called alignment chart for sway and non-sway frames whereby the K-

    factor of a column is determined based on the joint stiffness of the column ends. In

    the following the background of the charts and the applied model and assumptions are

    elaborated.

    4.1.1 Non-sway frame

    A general case of column subjected to compression and restrained by elastic springs attheir ends is considered. This situation reflects a column restrained by beams of finite

    stiffness. For non-sway frame case, it is assumed that the column ends do not translate

    with respect to each other. The static model of the actual case is shown in figure 4.2.

    [Galambos and Surovek, 2008]

    Figure 4.2.  Static model applied for non-sway frame - column with rotational spring. [ Galambos

    and Surovek, 2008]

    28

  • 8/18/2019 Buckling Length REPORT

    37/128

    4.1. AISC - formulation 9th semester  

    Consider the rigid connection at the columns top; the column and adjoining beam are

    perpendicular to each other, meaning there is no deflection. Hence the slope of the column

    and beam, denoted  θT , are equal.

    The total spring constant from restraint in top and bottom of the column is denoted  αT 

    and   αB, respectively. Hence the moment from elastic restrained beam at the top canbe expressed as   M   =   αT   · θT . Further explanation on the spring constant quantity is

    given later, but only the symbol is used now. This expression for moment is rewritten

    to   M   =   αT   · v

    (0), where   v(z)   is the lateral deformation as a function of   z. Moment

    at the columns top, emerged from the change in column slope can be expressed as

    M   =   −E   · I C   · v

    (0), where   I C   is the moment of inertia of the column. Hence from

    the equilibrium condition the following relation is established:

    αT   · v

    (0) − E · I C  · v

    (0) = 0   (4.1)

    The above given condition is also valid for point B, at the distance   LC   (length of the

    column). But in point B, the sign for moment from elastic restrained beam is negative,

    hence the relation becomes:   [Galambos and Surovek, 2008]

    −αB · v

    (LC )− E · I C  · v

    (LC ) = 0   (4.2)

    These are 2 of the 4 boundary conditions needed in order to solve the differential equation

    for the system. The remaining 2 boundary conditions are governed by requiring no lateral

    displacement at the top and bottom, given by:

    v(0) = 0

    v(LC ) = 0

    The 4 boundary conditions are applied the general solution for the governing differential

    equation, given in equation 3.13, chapter 3.  Thus the determinant of the coefficient A,B,C

    and D becomes as given in equation 4.3, where the variable k  is earlier defined in equation

    3.5, chapter 3.  [Galambos and Surovek, 2008]

    0   =

    1 0 0 1

    1   LC    sin(k · LC )   cos(k · LC )

    1   αT    αT   · k E · I C  · k2

    0   −αB   a43   a44

    (4.3)

    a43  = −αB · k · cos(k · LC ) + E · I C  · k2 · sin(k · LC )

    a44  =  αB · k · sin(k · LC ) + E · I C  · k2 · cos(k · LC )

    The eigenfunction of the model is determined by solving the determinant in equation  4.3.

    29

  • 8/18/2019 Buckling Length REPORT

    38/128

  • 8/18/2019 Buckling Length REPORT

    39/128

    4.1. AISC - formulation 9th semester  

    (  πK 

    )2 · GT   · GB

    4  − 1 +

     GT  + GB2

      ·

    1 −

    πK 

    tan(  πK 

    )

    +

     2 · tan

      π2·K 

    πK 

    = 0   (4.7)

    Figure 4.3.  Subassembly rigid frame for non-sway case, where single curvature bending of the

    beam, with the slope θ  at both ends is assumed.   [Galambos and Surovek, 2008]

    In equation 4.7, the K-factor  K   =   πk·L

     is adapted and the flexibility parameters  GT   and

    GB   are introduced, which are determined by equation 4.8.   [G.Johnston, 1976]

    GT   =

      I C LC 

      I BT LBT 

    (4.8)

    GB  =

      I C LC    I BBLBB

      Summation of all members rigidly connected to the joint and laying in the plane

    in which buckling of the column is being considered.

    I C , LC    I C  is the moment of inertia and  LC   the corresponding unbraced length of 

    the column of consideration.

    I BT , LBT    I BT  is the moment of inertia and  LBT   the corresponding unbraced length of 

    the beam at columns top.

    I BB , LBB   I BB  is the moment of inertia and  LBB   the corresponding unbraced length of the beam at columns end.

    Having determined  GT   and  GB, the AISC Alignment chart for non-sway frame given in

    figure  4.4   is used to determine the K-factor of the columns. Otherwise equation   4.7   is

    used in a numerical solver, where K-factor is determined by iteration.

    31

  • 8/18/2019 Buckling Length REPORT

    40/128

  • 8/18/2019 Buckling Length REPORT

    41/128

  • 8/18/2019 Buckling Length REPORT

    42/128

    Trainee report - Rambøll - Autumn 2010    4. K-factor determination in practice 

    The variables   T T    and   T B   in equation   4.9, account for the translation stiffness where:

    [Galambos and Surovek, 2008]

    T T   =

     β T   · L3

    E · I 

    T B  = β B · L

    3

    E  · I 

    The AISC Specification, assumes that a sway frame consists of subassembly type of frames

    where the top of the column is able to translate with respect to the bottom, see figure  4.6.

    Furthermore it is assumed that the bottom column cannot translate where translational

    restraint is infinite large  T B  = ∞, and the top column is free to translate  T T   = 0. These

    are hence applied the equation 4.9 by substituting  T T   = 0  into the first row and dividing

    the third row by  T B  and then equating  T B   to  ∞, which yields: [Galambos and Surovek,

    2008]

    0   =

    0   k · L2 0 0

    0   RT    RT   · k · L   (k · L)2

    1 1   sin(k · L)   cos(k · L)

    0   RB   a43   a44

    (4.10)

    a43 =  RB · k · L · cos(k · L) − (k · L)2 · sin(k · L)

    a44 = −RB · k · L · sin(k · L)− (k · L)2 · cos(k · L)

    Figure 4.6.  Subassembly rigid frame for sway case, where reverse curve bending of the beam,

    with the slope θ  at both ends is assumed. [Galambos and Surovek, 2008]

    The rotational stiffness for this case is found by assuming equal rotation in magnitude

    and direction at near and far ends of the restraining beam but producing reverse curve

    bending, see figure   4.6.   This means   αT   = 6 ·  E ·I BT 

    LBT and   αB   = 6 ·

      E ·I BBLBB

    [Shanmugam

    and Choo,  1995]. Substituting these values into equation  4.10,  and after some algebraic

    manipulation, the eigenfunction given in equation 4.11 is derived. [Galambos and Surovek,

    2008]

    34

  • 8/18/2019 Buckling Length REPORT

    43/128

    4.1. AISC - formulation 9th semester  

    πK 

    tan

    πK 

     −

    πK 

    2· GT   ·GB − 36

    6 · (GT  + GB)  = 0   (4.11)

    This equation is the basic for the sway alignment chart shown in figure   4.7,that relatesthe flexibility parameters  GT   and  GB   with the K-factor.

    Figure 4.7.   AISC - Alignment chart for K-factor determination in a rigid sway frame. [Galambos

    and Surovek, 2008]

    Figure 4.8 shows the members involved in K-factor determination of the column marked

    with red, for both the sway and non-sway frames.

    35

  • 8/18/2019 Buckling Length REPORT

    44/128

    Trainee report - Rambøll - Autumn 2010    4. K-factor determination in practice 

    Figure 4.8.  The members enclosed by the dashed lines are involved in K-factor determination

    of the column marked with red. [Galambos and Surovek, 2008]

    For a column base connected to footing by a frictionless hinge,  GB   is theoretically infinite

    but 10 is suggested to be used in design practice. If the column base is rigidly attached,GB   approaches the theoretical value of zero, but should not be taken lower than 1,

    [G.Johnston, 1976]. Having introduced the theoretical background in AISC Specifications

    for K-factor determination, the inherent assumptions are summarized and discussed in

    the following.

    4.1.3 Assumptions made in AISC specification

    Mathematical solution to a practice problem is found by putting up a model and make

    a number of assumptions, otherwise it is impossible to determine a solution. Hence theobtained results would not be the exact, but the better the mathematical model describes

    the practical problem, the better the final results becomes. Hence the mathematical model

    and assumptions adopted in the AISC Specifications due to determine the K-factor are

    discussed in the following. The alignment charts are based on the following assumptions:

    1. Behaviour is purely elastic.

    2. All members have constant cross section.

    3. All joints are rigid.

    4. For the non-sway frame case, rotations at the far ends of restraint beams are equal

    in magnitude but opposite in sense to the joint rotations at the far ends (singlecurvature bending).

    5. For the sway frame case, rotations at the far ends of the restraint beams are equal in

    magnitude and in the same sense as the joint rotations at the column ends (reverse

    curvature bending).

    6. All columns in the frame buckle simultaneously.

    7. Only the members shown at figure 4.8   is accounted in K-factor determination.

    36

  • 8/18/2019 Buckling Length REPORT

    45/128

    4.1. AISC - formulation 9th semester  

    Purely elastic behaviour

    The assumption that the behaviour is purely elastic is not valid when the load increases

    thus yielding of the column occurs. This means  E C  reduces and the beams provide more

    relative restraint to the columns. Hence it causes a lower  G  - factor and consequently a

    lower K-factor, see the charts in figure   4.4  and 4.7.   Thus the alignment charts provideconservative values regarding this matter.  [Galambos and Surovek, 2008]

    Constant cross section

    The assumption that all members have constant cross section is not valid around a joint

    where for instant the column dimension changes. This is often seen in tall buildings that

    the dimension of the columns in the upper storeys is smaller than in the lower storeys.

    [Galambos and Surovek, 2008]

    Rigid joints

    AISC assumes rigid joins, which require perpendicular shape between beam and columnis maintained under deformation. The joints shall be able to transfer moment. This

    assumption put requirement for the performance of the joints in practice. An example of 

    rigid and pinned connections are given to the left and right in the figure 4.9, respectively.

    Pinned connections are theoretically only able to transfer axial and shear forces. It is

    hence important to establish the joints in practice as assumed.   [University of Ljubljana -

    Slovenia, 2010b]

    Figure 4.9.  Examples of rigid (left) and pinned (right) connections.   [University of Ljubljana -

    Slovenia, 2010b]

    Single/reverse curvature bending

    Single curvature bending for the non-sway and reverse curvature bending for sway frame

    is assumed. These assumptions are only fully valid for a perfectly symmetric deformation

    which requires symmetric geometry and loading conditions. The restraint of the columns

    by beams is affected by the far-end rotation of the beams. Hence the following modification

    of the beam length   L

    B   is suggested in order to account for the variation from the

    assumptions: [G.Johnston, 1976]

    37

  • 8/18/2019 Buckling Length REPORT

    46/128

  • 8/18/2019 Buckling Length REPORT

    47/128

    4.2. DIN 18800 procedure 9th semester  

    It is hence obtained that only the adjoining storeys of the considered storey are found

    to influence the K-factor. Therefore it is evaluated to be acceptable, only to include the

    adjoining storeys in K-factor determination of the case study structure, as suggested in

    AISC Specifications. It shall be mentioned that this evaluation is based on the analysed

    case (limited storeys); therefore this is not necessary valid in general for frames with

    various number of storeys.

    As the AISC specifications including the deviation of the charts and its assumptions are

    presented and discussed, another method for determining K-factor, provided by German

    code DIN18800 is presented in the following.

    4.2 DIN 18800 procedure

    The procedure presented in DIN 18800 is given in the following, where only the practical

    use of it is explained. DIN 18800 also suggests two charts; one for non-sway and one forsway frames. The original text by DIN 18800 in German is translated to English by the

    author. It should be mentioned that K-factor is denoted as (β ) in the following due to

    keep the same denotation given by DIN 18800. [DIN-Standards and Regulations, 1989]

    Common for both the non-sway and sway frames, are the two parameters  C O  and  C U   that

    is determined by using the equation 4.13, and the indices are illustrated at figure  4.10.

    C O  =  1

    1 +(α·K O)K S+K S,O

    (4.13)

    C U   =  1

    1 +

    (α·K U )K S+K S,U 

    The  K   parameters given with indices in equation 4.13, are illustrated in figure  4.10. The

    respective K  value is in general determined by K  = I /L, where I  and  L are the moment of 

    inertia and length of the member. The  α  values, known as the rotational stiffness factor,

    shall be applied as: [DIN-Standards and Regulations, 1989]

      α = 4  for the case where beams far end is fixed•   α = 1  for case where beams far end is pinned

    Furthermore for the pinned-base and fixed-base case the prescribed value   C U   = 1   and

    C U   = 0   are suggested, respectively. Parameters   C O   and   C U   are comparable with the

    flexibility parameters  GT   and  GB   given in the AISC formulation. But the difference in

    DIN 18800 from AISC formulation is the number of elements that is included for the K-

    factor determination. DIN 18800, consider the elements shown in figure 4.10, to contribute

    to restraint the storey marked with red.

    39

  • 8/18/2019 Buckling Length REPORT

    48/128

    Trainee report - Rambøll - Autumn 2010    4. K-factor determination in practice 

    The representative K-factor (β ) is determined using the charts; Thereafter the K-factor

    β  j   for each of the columns are found corresponding to the normal force and stiffness

    distribution of the columns in the storey, see equation   4.14.   [DIN-Standards and

    Regulations, 1989]

    Figure 4.10.   Elements included in K-factor determination of the storey marked with red,

    suggested by DIN 18800.

    β  j  =

      N  · K  jN  j · K S 

    · β    for  j  = 1, 2  .. n   (4.14)

    N  =

    N  j   for  j  = 1, 2  .. n

    K  =  I /LK  j  = I  j/L j   for  j  = 1, 2  .. n

    K S  =

    K  j   for  j  = 1, 2  .. n

    β    Representative K-factor of the storey

    β  j   K-factor of the individual columns in the storey

    n   Number of columns in the storey

    N  j   Normal force distribution factor, indicating the factor the column in question is

    loaded in comparison to the other columns in the storey

    N    Sum of the normal force distribution factors of the columns in the storey

    K S    Sum of stiffness factors for the individual columns K  jI  j , L j   Moment of inertia and length of the individual columns in the storey

    This idea is also what is concluded in appendix   B, that the side-sway is a total storey

    characteristic and not an individual column phenomenon; hence all the columns and beams

    in a storey contribute to the total restraints of the storey.

    40

  • 8/18/2019 Buckling Length REPORT

    49/128

  • 8/18/2019 Buckling Length REPORT

    50/128

    Trainee report - Rambøll - Autumn 2010    4. K-factor determination in practice 

    4.2.2 Sway frame

    In the same manner the representative K-factor  β , of a storey in a sway frame is found

    by reading the chart in figure  4.12.   Thereafter β  j , K-factor of the individual columns are

    determined by applying equation 4.14.

    Figure 4.12.   K-factor  β , represent for given storey, determination chart for a sway frame given

    by DIN 18800.   [DIN-Standards and Regulations, 1989]

    A calculation seat with illustrations and explanations is made in MathCAD and enclosed

    the Appendix CD, G.1.

    42

  • 8/18/2019 Buckling Length REPORT

    51/128

  • 8/18/2019 Buckling Length REPORT

    52/128

  • 8/18/2019 Buckling Length REPORT

    53/128

    Part II

    Case study

    45

  • 8/18/2019 Buckling Length REPORT

    54/128

  • 8/18/2019 Buckling Length REPORT

    55/128

    Case study structure5

    In this chapter, the geometric and mechanical parameters of the members,

    required to determine the K-factor of the columns in the frame presented as 

    case study structure in the introduction are given. Two different vertical load 

    cases are considered in order to determine whether the case study structure is 

    sway or non-sway type by buckling analysis in Robot.

    The frame to be used in this chapter and the following chapter is the one presented as case

    study structure in the introduction, see figure 1.2 in chapter 1.  The geometric parameters

    of this structure are summarized in figure   5.1. It consists of two bay and ten storeys,

    with rigidly connected members and pinned supported base. The local coordinate system

    applied for the each of the column and beam elements of the structure is illustrated, where

    z-axis is shown to be out-of-plane. It shall be mentioned that the stability in longitudinal

    direction, z-axis, is assumed to be stable, hence only in-plane situation is considered.

    The frame to be used in this chapter and the following chapter is the one presented as

    the case study structure in the introduction, see figure  1.2  in chapter 1. The geometric

    parameters of this structure are summarized in figure 5.1. It consists of two bay and ten

    storeys, with rigidly connected members and pinned supported base. The local coordinate

    system applied for the each of the column and beam elements of the structure is illustrated

    in the figure mentioned above, where z-axis is shown to be out-of-plane. It is assumed that

    the stability in longitudinal direction, z-axis, to be stable; hence only in-plane situation isrequired to be considered by Rambøll.

    47

  • 8/18/2019 Buckling Length REPORT

    56/128

    Trainee report - Rambøll - Autumn 2010    5. Case study structure 

    Figure 5.1.  The case study structure consisting 10 storeys in total

    The frames have an individual distance of 6 meters between each other in the longitudinal

    (z-axis) direction, (not included in the figure   5.1). The geometric and mechanical

    parameters of the members are presented in table 5.1 in accordance to the local coordinate

    system shown in the figure.

    Profil Length  [mm]   E [M P a]   I z

    mm4

      f yk [M P a]

    Asymmetric beam   8000 210 · 103 776453 · 103 350

    HE400B column   3600 210 · 103 576805 · 103 350

    Table 5.1.  Geometrical and mechanical parameters of members involved in the frame used as

    case study, see figure fig:framedetailcasestud for illustration of the frame.

    5.1 Load and load cases

    Global buckling analysis of the frame is performed in order to determine whether it is a

    sway or non-sway type. Hence only the vertical loads are considered. The vertical loads

    are limited to account for permanent and imposed loads on the construction.

    Permanent load

    The permanent load of a floor including the installations and partition walls, is determined

    to be  6.2  kN/m2. This load is set to act uniformly distributed on the beams, calculated

    as  G1  = 6.2  kN/m2 · 6  m = 37.2  kN/m. For simplification, the same load is assumed to

    act on the upper beams to account for load from the roof-floor.

    48

  • 8/18/2019 Buckling Length REPORT

    57/128

    5.1. Load and load cases 9th semester  

    The facade of Z-house is of glass and weighs   1   kN/m2. This load is assumed to

    act as centric point load on the exterior columns at each storey, calculated as   G2   =

    1  kN/m2 · 6  m · 3.6  m  = 21.6  kN .

    Imposed load

    The primary use of construction is assumed to be office related, which falls into category

    B in Eurocode definitions for the use of the construction. Hence the characteristic value

    of imposed load is taken as  2.5 kN/m2. Thus the uniformly distributed load on the beams

    is  N  = 2.5  kN/m2 · 6  m  = 15  kN/m. This load is also set to act at the top beams of the

    frame to account for platform roof.

    In accordance with the Danish National Annex for EC 1, the total imposed loads from

    several storeys may be multiplied by the reduction factor  αn  given in equation 5.1, where

    n   is number of storeys and   ψ0

      is a factor, that depends on the category, that is 0.6 for

    office areas.

    αn = 1 + (n − 1) · ψ0

    n  = α10  =

     1 + (10 − 1) · 0.6

    10  = 0.64   (5.1)

    Load cases

    Z-house is categorised as high consequence class, CC3. Two load combinations consisting

    permanent and imposed loads are considered for the current analysis:

    •   LC 1  :   1.1 · 1.0 ·G + 1.1 · 1.5 · αn ·N 

    •   LC 2  :   0.9 ·G + 1.1 · 1.5 · αn · N 

    Load combination LC 1, consists of loads that are to be applied symmetrically around

    the interior columns of the frame, see to the left in figure 5.2. Load combination LC 2,

    consists of loads that are to be applied asymmetrically around the interior columns of the

    frame, see to the right in figure 5.2  where the imposed load is only applied on the bays

    to the right. The choices of the two combinations are based on the advice by Rambøll, to

    establish two situations where the normal force in the columns varies the most compared

    to each other.

    49

  • 8/18/2019 Buckling Length REPORT

    58/128

    Trainee report - Rambøll - Autumn 2010    5. Case study structure 

    Figure 5.2.  Loads corresponding to LL 1 (left) and LL 2 (right)

    5.2 Global analysis in Robot

    Robot offers the feature to perform global buckling analysis of a frame. In appendix A

    the theoretical background in Robot calculations and the required input parameters are

    described. A global analysis on the frame is performed, subjecting the frame to each of 

    the load cases presented in figure  5.2.   Hence the critical global buckling load  P cr  and thecritical global load factor  αcr  of the frame can be determined to define whether the frame

    is sway or non-sway type based on the definition given in equation  2.1, chapter 2.

    Results

    The base columns of the frame are pinned and loaded the most; hence the base storey

    causes the global failure of the frame, but in general the global failure mode shall be

    considered due to point out the storey that causes the global failure of the frame. In

    appendix   D   more description on the global analysis in Robot and interpretation of theresults are given. Results from the current buckling analyses in Robot, determined for the

    base storey, are presented in table 5.2  and  5.3  for LL 1 and LL 2, respectively.

    50

  • 8/18/2019 Buckling Length REPORT

    59/128

    5.2. Global analysis in Robot 9th semester  

    Robot performs the buckling analysis by an iterative process, where it factorises the

    applied load and requires equilibrium. If the equilibrium state is found, it continuously

    increase the factor until the equilibrium is no longer obtainable. Hence the iterative

    process results in a critical load factor  αcr, which is directly multipliable by the internal

    normal forces in the column, whereby the critical buckling load is determined. This fact

    is notable by considering for instant the results in table  5.2.

    LC 1   Left base column Interior base column Right base column

    Normal force  [kN ] 2584 4555 2584

    Critical coefficient   4.826 4.826 4.826

    Critical force   [kN ] 12471 21982 12471

    Table 5.2.   Buckling analysis results determined in Robot for the load case: LC 1

    LC 2   Left base column Interior base column Right base columnNormal force  [kN ] 1586 3303 2180

    Critical coefficient   6.637 6.637 6.637

    Critical force   [kN ] 10528 21926 14470

    Table 5.3.   Buckling analysis results determined in Robot for the load case: LC 2

    The critical load factor   αcr   = 4.826   is found to be lowest for the considered load cases.

    But both load cases indicate the actual frame as sway frame type, as the critical load

    factor is lower than 10. Hence the charts for sway frame suggested by AISC and DIN

    18800 along with analysis in Robot are used to determine the K-factor of the columns in

    the following chapter.

    51

  • 8/18/2019 Buckling Length REPORT

    60/128

  • 8/18/2019 Buckling Length REPORT

    61/128

    K - factor determination6

    In this chapter, K-factor determination of columns in the case study structure 

    is performed following the approaches given in AISC and DIN 18800. The 

    results from buckling analysis of subassembly models in Robot, representing base,

    intermediate and top storey cases, are also used for the determination of K-factor.

    The results from AISC and DIN 18800 approaches are compared to the results 

    from Robot and discussed. Finally, code check according to EC 3 by employing 

    Robot is performed, where a sensitivity analysis of the K-factor influence for the 

    final result is made.

    The case study structure is classified as a sway frame type in chapter   5,   which means

    the effective buckling length of the columns become larger than the system length,

    K >  1.Practical methods according to AISC and DIN 18800 to determine the K-factors

    are presented in chapter4 and are applied to the case study structure. In addition, Robot

    is also employed for this objective. In appendix D, it is shown that buckling analysis in

    Robot is only applicable for global analysis of the structure, resulting in the global critical

    parameters. But it is further demonstrated that subassembly models can be used in Robot

    to represent the local storey, whereby the critical buckling load of the storey is obtainable

    and is used to determine the respective K-factor of the columns, see appendix D.

    6.1 AISC

    In order to apply the AISC Alignment chart for sway frame, the flexibility parameters

    shall be calculated. This is done for 6 different column restraint types, numbered 1 to 6

    in figure 6.1. These are representative for the other columns that have identical restraint

    conditions at theirs ends.

    53

  • 8/18/2019 Buckling Length REPORT

    62/128

    Trainee report - Rambøll - Autumn 2010    6. K - factor determination 

    Figure 6.1.  Case study frame, divided into 6 different representative column restraint types.

    In equation   6.1, calculation example of the flexibility parameters is shown for column

    number 4, where equation   4.8  given in chapter   4  is used and the input parameters are

    given in table   5.1, chapter  5. In equation  6.1,   L

    B   = 1.5 · LB, is applied to account for

    beams connection at the far end, which is fixed for the actual case. For the example shown

    in equation 6.1, the same value of the flexibility parameters for both the top and bottom

    connections are obtained due to the identical restraint conditions.

    GT   =   I C LC    I BT 

    LBT =

      2 ·   576805·103 mm4

    3600  mm

    2 ·   776453·103 mm4

    1.5·8000  mm= 2.476   (6.1)

    GB  =

      I C LC    I BBLBB

    =  2 ·   576805·10

    3 mm4

    3600  mm

    2 ·   776453·103 mm4

    1.5·8000  mm

    = 2.476

    Thus the flexibility parameters are determined for the different column types as illustrated

    in figure 6.1.  Hence the respective K-factors are determined by using the equation  4.11

    given in chapter 4. The results are given in table  6.1.

    Column : Type 1 Type 2 Type 3 Type 4 Type 5 Type 6

    GT    4.952 2.476 4.952 2.476 2.476 1.238GB   10 10 4.952 2.476 4.952 2.476

    K - factor   2.552 2.192 2.219 1.706 1.954 1.497

    Table 6.1.  Flexibility parameters and K-factors for different column types as illustrated in figure

    6.1, determined in accordance to AISC formulation.

    54

  • 8/18/2019 Buckling Length REPORT

    63/128

  • 8/18/2019 Buckling Length REPORT

    64/128

    Trainee report - Rambøll - Autumn 2010    6. K - factor determination 

    There are large number of load cases in practice, but in order to stick to the scope of this

    project, only the load cases presented in figure  5.2, chapter 5  are employed, but modified

    by including the wind load  V , hence:

      LC 3  :   1.1 · 1.0 ·G + 1.1 · 1.5 · αn · N  + 1.1 · ψ0 · 1.5 · V •   LC 4  :   0.9 · G + 1.1 · 1.5 · αn ·N  + 1.1 · 1.5 · V 

    The wind pressure q max = 0.8 kN/m2 is assumed, which results in the following uniformly

    distributed load values:

    •   V   = 0.8  kN/m2 · 6 m · 0.7 = 3.36  kN/m  for  cf   = 0.7

    •   V   = 0.8  kN/m2 · 6 m · 0.3 = 1.44  kN/m  for  cf   = 0.3

    The loads included in load cases LC 3 and LC 4 are applied to the structure as shown infigure 6.2.  These load distributions are suggested by Rambøll in order to get two situations

    where distribution of the compressive forces in columns varies the most.

    Figure 6.2.  Load distribution, suggested by Rambøll to be applied for load cases LC 3 and LC

    4

    By applying these load cases and performing static analysis in Robot, the distribution of the compressive forces and hence the  αLoad   factors are determined. Results are given in

    table  6.3 and table  6.4  for LC 3 and LC 4 load cases, respectively. Columns numbered

    1 − 3,  4 − 27  and  27 − 30   in the table, belongs to the base, intermediate and top storey

    case, respectively.

    56

  • 8/18/2019 Buckling Length REPORT

    65/128

    6.2. DIN 18800 9th semester  

    Having obtained the load factors for the different columns in each storeys, the next step is

    to determine the respective K-factor for the columns by applying the equation 4.14 given

    in chapter 4. An example hereupon is provided in equation 6.3 for columns: 4, 5 and 6,

    in load case LC 3. These columns belongs to the category for an intermediate storey, for

    which kind the representative K-factor  β storey  = 1.7, is determined, see table 6.2.

    β column  =

     N  j · K  j

    N  j · K S · β storey    for  j  = 1, 2  and  3   (6.3)

    β col nr 4  =

     4.06 ·   576805·103 mm43600  mm1 · 3 ·   576805·10

    3 mm4

    3600  mm

    · 1.7 = 1.977

    β col nr 4  =

     

    4.06 ·   576805·103 mm4

    3600  mm

    1.88 · 3 ·   576805·103 mm4

    3600  mm

    · 1.7 = 1.440

    β col nr 4  =

      4.06 ·   576805·103 mm43600  mm1.17 · 3 ·   576805·10

    3 mm4

    3600  mm

    · 1.7 = 1.826

    Similarly the K-factors for the other columns are determined. 

    N  j   and  N  j   value to be

    inserted in equation 6.3 and the determined K-factors are given in table 6.3 and 6.4 for

    LC 3 and LC 4, respectively.

    57

  • 8/18/2019 Buckling Length REPORT

    66/128

    Trainee report - Rambøll - Autumn 2010    6. K - factor determination 

    Load case   Normal Load Total load   β storey   β columnLC 3   force   [kN ]   factor  N  j   factor

     N  j   K-factor

    Col nr 1 2334 1.00 3.299

    Col nr 2 4554 1.95 4.17 2.8 2.362

    Col nr 3 2834 1.21 2.994

    Col nr 4 2155 1.00 1.977

    Col nr 5 4062 1.88 4.06 1.7 1.440

    Col nr 6 2526 1.17 1.826

    Col nr 7 1946 1.00 1.960

    Col nr 8 3588 1.84 3.99 1.7 1.444

    Col nr 9 2230 1.15 1.831

    Col nr 10 1725 1.00 1.947

    Col nr 11 3121 1.81 3.93 1.7 1.447

    Col nr 12 1939 1.12 1.836

    Col nr 13 1495 1.00 1.934

    Col nr 14 2661 1.78 3.88 1.7 1.450

    Col nr 15 1649 1.10 1.842

    Col nr 16 1257 1.00 1.923

    Col nr 17 2208 1.76 3.84 1.7 1.451

    Col nr 18 1360 1.08 1.849

    Col nr 19 1011 1.00 1.914

    Col nr 20 1760 1.74 3.80 1.7 1.451

    Col nr 21 1075 1.06 1.856

    Col nr 22 758 1.00 1.909Col nr 23 1317 1.74 3.78 1.7 1.448

    Col nr 24 792 1.04 1.867

    Col nr 25 499 1.00 1.909

    Col nr 26 875 1.7