6
Scientific Bulletin of the Electrical Engineering Faculty – Year 11 No. 3 (17) ISSN 1843-6188 20 BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION MACHINES BY MOTOR CURRENT SIGNATURE ANALYSIS METHOD C. HARLIŞCA 1 , R.P. HANGIU 1 , L. SZABÓ 1 , H. SILAGHI 2 1 Department of Electrical Machines and Drives, Technical University of Cluj-Napoca 400114, Cluj-Napoca, 28 Memorandumului str., Romania 2 Department of Control Systems Engineering and Management, University of Oradea Oradea, 1 University str., Romania E-mail: [email protected] Abstract Condition monitoring is an important issue in the maintenance of electrical machines. In the last years several methods for fault diagnosis of the squirrel-cage induction motors were cited in the literature. Among these methods the Motor Current Signature Analysis (MCSA) is considered the most effective non-invasive fault detection method, because it can easily detect all the common electrical machine's faults. The method in discussion uses the harmonic content of the line current of the induction machine to detect diverse faults of the analyzed electrical machine. In the paper experimental results on detecting broken rotor bars in squirrel cage induction motors by using MCSA are given. Keywords: induction machine, rotor faults, fault diagnosis, condition monitoring, Motor Current Signature Analysis. 1. INTRODUCTION Due to their robustness, low cost, and easy maintenance the squirrel cage induction machines are widely used in modern industry applications. Many of its basic components are susceptible to failure. About 40% of the faults that occur in induction machines are in the bearings, 30 to 40% in the stator, 10% in the rotor and the remaining ones in the auxiliary devices of the machine [1]. An interruption of a manufacturing process due to a mechanical or electrical problem induces a significant financial loss. In order to avoid such problems these faults has to be detected, so they not to lead to major failures of the machine [2]. Numerous fault detection methods have been proposed in the literature. The most frequent used detection methods are [2]: Motor current signature analysis (MCSA), acoustic noise measurements, artificial intelligence and neural network based techniques, noise and vibration monitoring, electromagnetic field monitoring using search coils, temperature measurements, infrared recognition, radio frequency (RF), emissions monitoring, chemical analysis, etc. Most of the diagnostic methods require expensive sensors or specialized tools. The current monitoring methods have an advantage over the methods mentioned above: they require only (in most cases already existing) simple and cheap current sensors. The current monitoring based techniques can be used to detect almost all of the faults of a squirrel cage induction machine: bearing faults, rotor bar faults, air-gap eccentricity faults, shorted winding fault, load faults, etc. These methods are non-intrusive and can be applied both on-line and in a remotely controlled way. The condition monitoring of induction machines is a vital component of preventative and predictive maintenance programs that seek to reduce cost and avoid unplanned downtime of industrial processes. Condition monitoring systems include both measurement hardware and software that acquire and process signals generated by the machine being monitored [3], [4]. 2. THE MOTOR CURRENT SIGNATURE ANALYSIS METHOD (MCSA) The MCSA is a reliable method for fault detection that provides a precise analysis based on the detection of specific current sideband harmonics by means of Fast Fourier Transform (FFT), with frequencies that are characteristic to each type of fault [5]. In a working electrical machine fault indicators can be chosen from a wide range of parameters that influence the condition of the machine, like: flux, stator current, stator line voltage, impedance, power, electromagnetic torque, etc. Among these the easiest to analyze is the stator current, as it is very easy to measure [6], [7]. In an induction machine, depending of the type of fault, the detected sideband harmonic components of the line current may differ. To determine the existence of a certain fault the measured data has to be analyzed in the

BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION ... - harlisca-broken.pdf · BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION ... In an induction machine, depending of

Embed Size (px)

Citation preview

Page 1: BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION ... - harlisca-broken.pdf · BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION ... In an induction machine, depending of

Scientific Bulletin of the Electrical Engineering Faculty – Year 11 No. 3 (17) ISSN 1843-6188

20

BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION

MACHINES BY MOTOR CURRENT SIGNATURE ANALYSIS METHOD

C. HARLIŞCA1, R.P. HANGIU1, L. SZABÓ1, H. SILAGHI2

1 Department of Electrical Machines and Drives, Technical University of Cluj-Napoca 400114, Cluj-Napoca, 28 Memorandumului str., Romania

2 Department of Control Systems Engineering and Management, University of Oradea Oradea, 1 University str., Romania

E-mail: [email protected]

Abstract Condition monitoring is an important issue in the

maintenance of electrical machines. In the last years

several methods for fault diagnosis of the squirrel-cage

induction motors were cited in the literature. Among these

methods the Motor Current Signature Analysis (MCSA) is

considered the most effective non-invasive fault detection

method, because it can easily detect all the common

electrical machine's faults. The method in discussion uses

the harmonic content of the line current of the induction

machine to detect diverse faults of the analyzed electrical

machine. In the paper experimental results on detecting

broken rotor bars in squirrel cage induction motors by

using MCSA are given.

Keywords: induction machine, rotor faults, fault diagnosis,

condition monitoring, Motor Current Signature Analysis.

1. INTRODUCTION

Due to their robustness, low cost, and easy maintenance the squirrel cage induction machines are widely used in modern industry applications. Many of its basic components are susceptible to failure. About 40% of the faults that occur in induction machines are in the bearings, 30 to 40% in the stator, 10% in the rotor and the remaining ones in the auxiliary devices of the machine [1]. An interruption of a manufacturing process due to a mechanical or electrical problem induces a significant financial loss. In order to avoid such problems these faults has to be detected, so they not to lead to major failures of the machine [2]. Numerous fault detection methods have been proposed in the literature. The most frequent used detection methods are [2]: • Motor current signature analysis (MCSA), • acoustic noise measurements, • artificial intelligence and neural network based

techniques, • noise and vibration monitoring, • electromagnetic field monitoring using search coils, • temperature measurements, • infrared recognition, • radio frequency (RF), • emissions monitoring, chemical analysis, etc.

Most of the diagnostic methods require expensive sensors or specialized tools. The current monitoring methods have an advantage over the methods mentioned above: they require only (in most cases already existing) simple and cheap current sensors. The current monitoring based techniques can be used to detect almost all of the faults of a squirrel cage induction machine: • bearing faults, • rotor bar faults, • air-gap eccentricity faults, • shorted winding fault, • load faults, etc. These methods are non-intrusive and can be applied both on-line and in a remotely controlled way. The condition monitoring of induction machines is a vital component of preventative and predictive maintenance programs that seek to reduce cost and avoid unplanned downtime of industrial processes. Condition monitoring systems include both measurement hardware and software that acquire and process signals generated by the machine being monitored [3], [4]. 2. THE MOTOR CURRENT SIGNATURE

ANALYSIS METHOD (MCSA)

The MCSA is a reliable method for fault detection that provides a precise analysis based on the detection of specific current sideband harmonics by means of Fast Fourier Transform (FFT), with frequencies that are characteristic to each type of fault [5]. In a working electrical machine fault indicators can be chosen from a wide range of parameters that influence the condition of the machine, like: flux, stator current, stator line voltage, impedance, power, electromagnetic torque, etc. Among these the easiest to analyze is the stator current, as it is very easy to measure [6], [7]. In an induction machine, depending of the type of fault, the detected sideband harmonic components of the line current may differ. To determine the existence of a certain fault the measured data has to be analyzed in the

Page 2: BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION ... - harlisca-broken.pdf · BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION ... In an induction machine, depending of

ISSN 1843-6188 Scientific Bulletin of the Electrical Engineering Faculty – Year 11 No. 3 (17)

21

frequency domain. This is done by verifying and comparing certain parts of the analyzed signal's harmonic content with those of the signal measured for a healthy machine [8], [9]. Although the broken rotor bars of a squirrel-cage induction machine do not initially cause the motor to fail, they can have serious secondary effects. The breakings or cracks of a rotor bar can easily extend to the neighboring bars. This type of fault progresses slowly in time and can be easily detected by using MCSA technique [10]. When a rotor bar fault occurs, it induces in the current spectrum two frequency sidebands that appear at ±2sf1 around the supply frequency [11]:

1)21( fsfb ±= (1)

The lower sideband is induced due to broken bar, and the upper sideband is due to consequent speed oscillation. Several authors have shown that broken rotor bars create additional sideband components in the current spectrum at frequencies given by [11]:

1)21( fksfb ±= , k = 2, 3, 4... (2)

An idealized current spectrum is shown in Figure 1.

Figure 1. The idealized current spectrum

The two slip frequency sidebands due to broken rotor bars near the main harmonic can be clearly observed in the figure [12]. The amplitude of these sideband harmonics dependents of three factors [13]:

• Motor's load inertia • Motor's load torque (current in the rotor bars) • Severity of the rotor fault

3. LABORATORY SETUP FOR FAULT

DETECTION

In order to perform the required measurements for the detection of broken rotor bars a test bench was set up (see Figure 2).

Figure 2. The laboratory setup

The laboratory test bench consists of two coupled electrical machines: the squirrel cage induction machine to be tested and a disc rotor type dc machine for braking and loading purposes. The rated data of the tested three-phase squirrel cage induction machine is: • Rated power: 1.5 kW • Rated voltage: 220/380 V (∆/Y) • Rated current: 6.18/3.56 A (∆/Y) • Rated speed: 1500 1/min. The measurement part of the test bench uses voltage and current sensors. The measured data is acquired by a PC having a National Instruments PCI-MIO-16E-4 12-Bit Multifunction DAQ type data acquisition board. For the data acquisition several virtual instruments (VIs) were built up in LabVIEW. Besides data acquisition the VIs can also perform the real time graphical processing of the tested induction machine's measured currents and voltages. These VIs can be easily transformed and used also for the data processing if it should be required [16], [17]. The VI developed for the data acquisition and the analyzing of the acquired data is given in Figure 3.

Figure 3. The data acquisition

virtual instrument’s block diagram

The sample frequency for data acquisition was set to a high value (216=65.536 samples/seconds). One second long measurements were performed, which means that on each channel 65.536 values were saved.

Page 3: BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION ... - harlisca-broken.pdf · BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION ... In an induction machine, depending of

Scientific Bulletin of the Electrical Engineering Faculty – Year 11 No. 3 (17) ISSN 1843-6188

22

4. RESULTS OF THE MEASUREMENTS

The tests were carried out for four different loads for two conditions of the motor in study: healthy and having 3 broken rotor bars. Two similar rotors were used during the tests. In one of the rotors 3 bars were interrupted by drilling holes into the rotor near the end rings, as shown in Figure 4.

Figure 4. The rotor with 3 broken bars

During the measurements the three line currents and three line voltages were acquired.

The measured data was processed using the National Instruments DIAdem software. DIAdem is software specifically designed to help engineers and scientists quickly locate, inspect, analyze, and report on measurement data using a single easy-to-use comprehensive software tool. By using this program it is very easy to perform FFT based spectral analysis of the data acquired by means of NI's advanced data acquisition boards [19], [20]. NI DIAdem is a software tool that is used to quickly locate, load, visualize, analyze, and report measurement data collected during data acquisition and/or generated during simulations. The acquired data also can be stored in simple ASCII-type text files in order to be easy imported in any other programming environment. The measured line currents for the healthy and faulty rotors of the induction machine at no-load and full load are given in the Figures 5 and 6.

a) no-load b) full load

Figure 5. The line current for a healthy motor

a) no-load b) full load

Figure 6. The line current for 3 broken rotor bars

As it can be seen in Figures 5 and 6 the amplitude of the currents is intensifying with the increase of the load. Also a pronounced fluctuation of the line currents can

also be observed in the case of the induction motor having rotor faults. Several measurements were performed by using the above mentioned test bench and the virtual instruments developed.

Page 4: BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION ... - harlisca-broken.pdf · BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION ... In an induction machine, depending of

ISSN 1843-6188 Scientific Bulletin of the Electrical Engineering Faculty – Year 11 No. 3 (17)

23

The obtained results of the measurements were compared. The sideband components' frequencies due to the broken rotor bars given by equations (1) or (2) were searched in the spectrum of the measured line currents. Due to the limited space in the paper only the most significant results will be presented and discussed in details. The main results of the line current's spectral analysis performed by using the DIAdem software tool for the healthy condition and for 3 broken rotor bars of the squirrel cage induction machine in study are given in the next figures. In Figure 7 the spectrums of the line current for the healthy condition and for the case of the rotor having 3 broken bars are given at the rated (full) loading of the tested induction machine.

Figure 7. The line current's spectrum at full load

For a better view of the harmonic content of the line currents a zoom taken on the previous picture is given in Figure 8.

Figure 8. A zoomed view of the

line current's spectrum at full load

In the figure, the above mentioned sideband components can be very clearly distinguished in the case of the induction machine having broken rotor bars. The existence of these harmonic components is the clear evidence of the existence of broken rotor bars in the machine.

The qualitative analysis of the sideband harmonics should be joined with a more precise quantitative study. As the speed of the machine was measured during all the laboratory tests performed for all the cases taken into study the frequencies of the sideband components can be easily computed by using equations (1) and (2). The sideband frequencies of the main interest, computed for k = 1 and k = 2 for different loads of the squirrel cage induction machine in study having 3 broken rotor bars are given in Table 1.

Table 1. The analytically computed frequencies of

the sideband harmonics for the induction

machine having 3 broken rotor bars

speed [1/rot] slip frequency [Hz]

40.13 45.06 54.93

full load

1426l 0.049

59.86 43.33 46.66 53.33

75 %

of

load

1450 0.033

56.66 46.80 48.40 51.60

50 %

of

load

1476 0.016

53.20 48.40 49.20 50.60

25 %

of

load

1488 0.08

51.60 Next it should be checked if the sideband components from Table 1 can be identified in the spectrums of the measured line current. In Figure 9 the main sideband components of the line current in the case of the induction motor having 3 broken rotor bars at full load are given.

Figure 9. The main sideband components of the

line current in the case of the induction motor

having 3 broken rotor bars at full load

Page 5: BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION ... - harlisca-broken.pdf · BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION ... In an induction machine, depending of

Scientific Bulletin of the Electrical Engineering Faculty – Year 11 No. 3 (17) ISSN 1843-6188

24

In the figure the sideband harmonic components indicating the existence of rotor bar faults are marked with circles. The four sideband harmonic components corresponding to the given condition and load of the induction machine from Table 1 (40.13 Hz, 45.06 Hz, 54.93 Hz and 59.86 Hz) are clearly observable in Figure 9. All these emphasize both the effectiveness of the selected fault detection method and the correctness of the measurements and of the following data processing (spectral analysis). As the load of the machine is greater also the magnitude of the typical, fault type dependent sideband harmonic components are higher, as it can be seen in Figure 10, where the spectral contents of the line currents for the faulty machine at different loads are plotted.

Figure 10. The line current's spectrum

at different loads in the case of the

induction machine having 3 broken bars

As it can be seen in the figure at no load the typical sideband components are not evidenced although the induction machine's rotor is faulty. At the half of the rated load these components already can be seen, but they are clearly detectable only in the case of the full load of the machine. This is the main drawback of the motor current signature analysis: the sideband harmonic components indicating diverse machine faults can be hardly observed at lower loads of the monitored electrical machines. But in industrial environment in most of the cases the electrical machines are working mainly near they rated load, hence the fault diagnosis methods studied in this paper can be widely applied 5. CONCLUSIONS

The motor current signature analysis fault detection method provides a highly sensitive, selective, and cost-effective means for non-invasive and on-line monitoring of a wide variety of electric machinery. This technique can be used also combined with other methods, such as motor circuit analysis, as part of motor

diagnostics program in order to give a complete view of motor system health. A way forward is for the technology and intelligent diagnosis to be integrated into a technologically advanced hand-held instrument that is applicable to a diverse range of induction motor derives. All the given results show that the method in study is a suitable fault diagnosis method in the field of fault detection of electrical machines. The LabVIEW and DIAdem software used for data acquisition and processing purposes can be successfully used also in fault detection of electrical machines in industrial environment. 6. ACKNOWLEDGMENT

This paper was supported by the project "Improvement of the doctoral studies quality in engineering science for development of the knowledge based society-QDOC" contract number POSDRU/107/1.5/S/78534, project co-funded by the European Social Fund through the Sectorial Operational Program Human Resources 2007-2013. 7. REFERENCES [1] Benbouzid, M.E.H. A Review of Induction Motors

Signature Analysis as a Medium for Faults Detection, IEEE Transactions on Industrial Electronics, vol. 47, no. 5 (October 2000), pp. 984-993.

[2] Motor Reliability Working Group. Report of large motor reliability survey of industrial and commercial installations Part I, and II, IEEE Transactions on Industry Applications, vol. IA21, no. 4 (July 1985), pp. 853-872.

[3] Sin, M.L., Soong, W.L., Ertugrul, N. Induction machine on-line condition monitoring and fault diagnosis - A survey, Australasian Universities Power Engineering Conference (AUPEC '03), Christchurch (New Zeeland), 2003.

[4] Negrea, M.D. Electromagnetic flux monitoring for Detecting faults in electrical machines, Ph.D. Dissertation, Department of Electrical and Communications Engineering, Helsinki University of Technology, Espoo (Finland), 2006.

[5] Jung, J.H., Lee, J.J., Kwon, B.H. On-line Diagnosis of Induction Motors Using MCSA, IEEE Transaction on Industrial Electronics, vol. 53, no. 6, pp. 1842-1852, 2006.

[6] Thomson, W.T. On-Line Motor Current Signature Analysis Prevents Premature Failure of large Induction Motor Drives, Maintenance & Asset Management, vol. 24, no. 3, pp. 30-35, 2009.

[7] Blodt, M., Chabert, M., Regnier, J., Faucher, J. Mechanical Load Fault Detection in Induction Motors by Stator Current Time-Frequency Analysis, IEEE Transaction on Industry Applications, vol. 42, no. 6, pp. 1454-1463, 2006.

[8] Fenger, M., Susnik, M., Laderoute, P., Thomson, W.T. Development of a tool to detect faults in induction motors via current signature analysis, Proceedings of the Cement Industry Technical Conference, pp. 37-46, 2003.

[9] Thomson, W.T., and Gilmore, R.J. Motor Current Signature Analysis to Detect Faults in Induction Motor Drives, Fundamentals, Data Interpretation, and Industrial

Page 6: BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION ... - harlisca-broken.pdf · BROKEN ROTOR BARS DETECTION IN SQUIRREL-CAGE INDUCTION ... In an induction machine, depending of

ISSN 1843-6188 Scientific Bulletin of the Electrical Engineering Faculty – Year 11 No. 3 (17)

25

Case Histories, Proceedings of 32nd Turbomachinery Symposium, Texas A&M University, USA, 2003.

[10] Szabó, L., Tóth, F., Kovács, E., Fekete, G. An Overview on Induction Machine's Diagnosis Methods, Journal of Computer Science and Control Systems, Oradea (Romania), pp. 229-234, 2008.

[11] Szabó, L., Dobai, J.B., Biró, K.Á. Rotor faults detection in squirrel-cage induction motors by current signature analysis, Proceedings of 2004 IEEE-TTTC International Conference on Automation, Quality and Testing, Robotics, Cluj (Romania), pp. 353-358, 2004.

[12] Szabó, L., Bíró, K.Á., Fodor, D., Kovács, E. Improved Condition Monitoring System for Induction Machines Using a Model-Based Fault Detection Approach, Oradea University Annals, Electrotechnical Fascicle, Computer Science and Control Systems Session, pp. 126-131, 2006.

[13] Mehala, N., Dahiya, R. An Approach of Condition Monitoring of Induction Motors using MCSA, International Journal of System Applications, Engineering & Development, vol. 1, no. 1, pp. 13-17, 2007.

[14] Mehala, N., Dahiya, R. Motor Current Signature Analysis and its Applications in Induction Motor Fault Diagnosis, International Journal of System Applications, Engineering& Development, vol. 2, no. 1, pp. 29-35, 2008.

[15] Milimonfared, J. et al. A Novel Approach for Broken Rotor Bar Detection in Cage Induction Motors, IEEE Transactions on Industry Applications, vol. 35, no. 5, pp. 1000-1006, 1999.

[16] Szabó, L., Bíró, K.Á., Dobai, J.B. On the Rotor Bar Faults Detection in Induction Machines, Proceedings of the International Scientific Conference MicroCAD '2003, Miskolc (Hungary), Section J (Electrotehnics and Electronics), pp. 81-86, 2003.

[17] Szabó, L., Dobai, J.B., Bíró, K.Á. Virtual Instruments for Detecting Rotor Faults in Induction Motors, Advances in Electrical and Electronic Engineering (Slovakia), no. 2, vol. 3, pp. 119-122, 2004.

[18] Szabó, L., Kovács, E., Bíró K.Á., Dobai J.B., Blága Cs. Advanced data acquisition systems used in the condition monitoring and diagnosis devices of electrical machines (in Hungarian), International Conference on Power Systems and Electrical Engineering ENELKO '2006, Cluj (Romania), pp. 117-121, 2006.

[19] Travis, J., Kring, J., LabVIEW for Everyone: Graphical Programming Made Easy and Fun (National Instruments Virtual Instrumentation Series), Prentice Hall PTR, Upper Sadle (USA), 2006.

[20] FFT Use in NI DIAdem™, National Instruments Inc. Ireland Resources Limited, Dublin (Ireland), URL: http://www.diadem-forum.de/attachment.php?aid=281.