VICINITY MAP
JEFF WELLS
DON BURNETTE
Know what's
R
MECHANICAL PLANS
ELECTRICAL PLANS
BARKER DROTTAR ASSOCIATES
4425 POLARIS AVE
LAS VEGAS, NV 89103
702-310-8000
DEPARTMENT OF
REAL PROPERTY MANAGEMENT
LEWIS PROFESSIONAL BUILDING
BOILER REHAB & MECHANICAL UPGRADES
330 S. THIRD STREET, LAS VEGAS, NEVADA 89101
RANDY TARR
(1/100 PER IBC TABLE 1004.1.1)
EXITS REQUIRED:
PARKING REQUIREMENTS:
(PER IBC TABLE 1015.4)
YES
TWO PER FLOOR - UNCHANGED
OCCUPANCY LOAD:
TYPE OF
CONSTRUCTION:
OCCUPANCY GROUP:
TYPE II-A (SECTION 603 IBC)
MIXED B / S-2 PARKING GARAGE
IBC 509.2
UNCHANGED
2012 INTERNATIONAL BUILDING CODE
EXISTING FLOOR AREAS:10,370 S.F. EACH FLOOR
PARCEL NO.
GENERAL COMMERCIAL DISTRICT C-2
JURISDICTION: LAS VEGAS
SPRINKLERS:
ZONING:
139-34-210-058
CODE:
EXITS PROVIDED:
PARKING PROVIDED: EXISTING UNCHANGED
TWO PER FLOOR - UNCHANGED
RP.D0915036
ACQUISITION DESIGN & CONSTRUCTION DIVISION
JERRY STUEVE, DIRECTOR, LISA KREMER, ASSISTANT DIRECTOR
CHUCK JAMES MANAGER OF DESIGN & CONSTRUCTION
ROBERT WOLF ARCHITECT
1364 VIA SAVONA DRIVE
HENDERSON, NV 89052
702-614-5369
REHAB EXISTING CENTRAL PLANT EQUIPMENT. REPLACE EXISTING BOILER, CLOSED CIRCUIT FLUID COOLER, PUMPS, AND APPURTENANCES. PROVIDE NEW CLOSED CIRCUIT COOLING TOWER STRUCTURAL SUPPORT. PROVIDE T10 ENAMEL PAINT FOR STRUCTURAL SUPPORTS TO RETARD CORROSION. PROVIDE NEW CENTRAL PLANT CONTROLS AND COMMISSIONING. PROVIDE WATER TREATMENT FOR HYDRONIC SYSTEMS FOR ONE YEAR. PROVIDE NEW JOHNSON CONTROLS ENERGY MANAGEMENT SYSTEM
FOR CENTRAL PLANT. PROVIDE ELECTRICAL POWER CONNECTIONS TO NEW EQUIPMENT. PATCH AND REPAIR EXISTING ROOF AS
REQUIRED BY RENOVATION WORK. PROVIDE TEMPORARY COOLING FOR INFORMATION TECHNOLOGY EQUIPMENT (SERVER ER & TR)
ROOMS WHEN HEAT PUMP HYDRONIC LOOP IS NOT IN SERVICE DUE TO CONSTRUCTION ACTIVITY. PROVIDE DEMOLITION OF
ELECTRICAL WIRING FOR EXISTING COOLING TOWER FANS, PUMPS, BOILERS AND PUMPS AND CONTROLS. PROVIDE NEW POWER
FOR NEW COOLING TOWER FANS, PUMPS, BOILERS, CONTROLS AND APPURTENANCES. PROVIDE 120v POWER FOR TEMPERATURE
CONTROLS. PROVIDE CONDUIT AND WIRING FOR COOLING TOWER VIBRATION SWITCHES AND HEATER.
ADDITIVIE ALTERNATE #1: PROVIDE EXTENSION OF 5" HYDRONIC MAINS FROM THE 5TH LEVEL TO THE FIRST LEVEL. PROVIDE VALVES AND BLIND FLANGES TO PERMIT CONNECTION OF TEMPORARY COOLING TOWER IF COOLING TOWER ON ROOF FAILS. REFER TO DRAWINGS FOR ADDITIONAL INFORMATION.
CHRIS GIUNCHIGLIANI
SUSAN BRAGER
LAWRENCE WEEKLY
LARRY BROWN - VICE CHAIR
MARILYN KIRKPATRICK
STEVE SISOLAK - CHAIR
MARY BETH SCOW
STRUCTURAL PLANS
2011 NEC
(702) 455-6731
Las V
egas, N
evada
500 S
. G
RA
ND
C
EN
TR
AL P
AR
KW
AY
DE
PA
RT
ME
NT
O
F R
EA
L P
RO
PE
RT
Y M
AN
AG
EM
EN
T
CLA
RK
C
OU
NT
Y
AC
QU
IS
IT
IO
N, D
ES
IG
N, &
C
ON
ST
RU
CT
IO
N D
IV
IS
IO
N
TH
E LE
WIS
P
RO
FE
SS
IO
NA
L B
LD
G.
DA
TE
: N
OV
EM
BE
R 1
9, 2
01
5
ME
CH
AN
IC
AL U
PG
RA
DE
330 S
. 3R
D S
TR
EE
T, LA
S V
EG
AS
, N
V 89101
1502
0
M0-0
A. FURNISH WITH DISCONNECT SWITCH, 5% INPUT REACTOR, RFI/EMI FILTERS, N2 BUS INTERFACE COMPATIBLE WITH EMCS.
B. PUMP MANUFACTURER MAY FURNISH PUMP MOUNTED VFD, AT MANUFACTURER'S OPTION.
ITEM
REMARKS
ELECTRICAL
HP
REMARKSLOCATION
VARIABLE FREQUENCY DRIVE SCHEDULE
V-PH
SERVES
A. FLANGE INLET AND OUTLET.
B. EQUALS BY BELL AND GOSSETT, ARMSTRONG, PACO-GRUNDFOS, TACO.
ITEM
REMARKS
RPM
REMARKSSERVICE
VERTICAL IN LINE PUMP SCHEDULE
MODEL NO IMPELLERTYPE
FEET
HEAD
EFF
HP
WEIGHT
LBS
BOILER WATER 17502070-5 5.0VERTICAL IN-LINE 20 64% 1 230PHP-1
MANUFACTURER
LOCATION
A
CLOSED CIRCUIT COOLING TOWER SCHEDULE
FXV-1212C-160-L
ITEM BAC
MODEL NO
REMARKS
A-(M2-2)
LOCATION
27,070
WEIGHT
LBS
OPER
8'-6"x12'-0"x16'-8"TALL
DIMENSIONS
SUMMER PEAK CONDITIONS
EWT
°FLWT
°FEWB
°FGPM
94 85 74 7502@4"
COIL
CONN
5.0
A. FURNISH WITH STAINLESS STEEL CONSTRUCTION, 150 PSI ASME GALVANIZED STEEL COIL, VIBRATION CUTOUT SWITCH W/ ALARM CONTACT, EXTENDED BEARING LUBE LINES, INTERNAL
WALKWAY AND LADDER.
B. FURNISH WITH 7.5 KW 460V 3PH BASIN HEATER PACKAGE WITH LOW WATER CUT OFF, CONTACTOR AND DISCONNECT WITH NEMA 4 ENCLOSURE.
C. FURNISH WITH SCH. 40 PVC BASIN SWEEPER PIPING ASSEMBLY WITH 3' SIDE SUCTION AND 2" SUPPLY HEADERS.
D. PRE-APPROVED EQUALS BY MARLEY OR EVAPCO.
REMARKS
WPD
PSI
COIL
CFM
60,500
HP
15 460-3
V-PH
ELECTRICAL
FAN
A, B, CCCCT-1
15 460-3VFD-1 CCCT-1 FAN A
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSER WATER RETURN
HOT WATER SUPPLY
DRAIN
INDUSTRIAL COLD WATER
UNION
CONTROL VALVE - 2 WAY
CONTROL VALVE - 3 WAY
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
MOTORIZED VALVE
PLUG VALVE
RELIEF VALVE
STRAINER
FLEXIBLE PIPE CONNECTION
REDUCER
HOT WATER RETURN
CONDENSER WATER SUPPLY
COOLING TOWER SUPPLY
COOLING TOWER RETURN
WP WORKING PRESSURE
EMCS ENERGY MANAGEMENT CONTROL SYSTEM
TYP TYPICAL
MAX MAXIMUM
NO NUMBER
MIN MINIMUM
LBS POUNDS
OPERATINGOPER
HP HORSE POWER
V-PH VOLTAGE-PHASE
VFD VARIABLE FREQUENCY DRIVE
REVOLUTIONS PER MINUTERPM
GPM GALLONS PER MINUTE
EFFICIENCYEFF
MECHANICAL LEGEND
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
CHS
CHR
CTS
CTR
HS
HR
CR
CS
D
ICW
SHEET INDEX
SYMBOL
SHEET DESCRIPTIONSHEET NO
09-23-15 IS
SU
E
LEGEND, INDEX, NOTES, SCHEDULES, CONTROLSM0-0
OVERALL FLOOR PLANSM1-0
PARTIAL DEMO ROOF PLANM2-1
PARTIAL ROOF PLANM2-2
FLOW DIAGRAMM3-0
1. DO NOT SCALE DRAWINGS. VERIFY FIT OF PUMP SKID AND PIPING PRIOR TO FABRICATION.
2. CONTRACTOR SHALL COORDINATE WORK INDICATED HEREON WITH PLUMBING AND ELECTRICAL SECTIONS. SUBMIT 1/4" SCALE
SHOP DRAWINGS FOR DUCT SYSTEMS, DIMENSIONED TO INCORPORATE THE WORK OF OTHER TRADES. REFER TO EQUIPMENT
DRAWINGS, SPECIFICATIONS, AND SHOP DRAWINGS FOR CONNECTIONS TO EQUIPMENT.
3. PROVIDE EQUIPMENT SCHEDULED OR INDICATED ON THE DRAWINGS BUT NOT INCLUDED WITHIN THE SPECIFICATIONS.
INSTALLATION SHALL CONFORM TO MANUFACTURER'S RECOMMENDATIONS AND APPLICABLE CODES. PROVIDE SUBMITTALS.
4. ELECTRICAL POWER REQUIREMENTS FOR MECHANICAL EQUIPMENT SHALL BE VERIFIED WITH ELECTRICAL DRAWINGS PRIOR
TO EQUIPMENT ORDER RELEASE. CONTRACTOR SHALL CONFIRM THAT VOLTAGE AND AMPERAGE REQUIRED BY MECHANICAL
EQUIPMENT IS COMPATIBLE WITH ELECTRICAL SYSTEM WITH NO CHANGES TO ELECTRICAL SYSTEM. ADDITIONAL ELECTRICAL
WORK RESULTING FROM EQUIPMENT SUBSTITUTION IS THE RESPONSIBILITY OF THE CONTRACTOR.
5. CONFIRM ACTUAL DESIRED TAGS/NAMES WITH OWNER PRIOR TO FINAL EMCS PROGRAMMING.
6. PIPING LOCATED BELOW 7'-6" IN MECHANICAL ROOMS SHALL BE EQUIPPED WITH PADDING MATERIAL ON ALL CORNERS, EDGES
AND OTHER SURFACES WHICH MAY BE HAZARDOUS.
7. DRAIN PIPING FROM HVAC EQUIPMENT SHALL BE ROUTED SO AS NOT TO CREATE A TRIPPING HAZARD. COORDINATE ACTUAL
DRAIN CONNECTIONS WITH PLUMBING SECTION. COORDINATE FLOOR SINK LOCATIONS ACCORDINGLY.
GENERAL NOTES
A-(M2-2)
PACO/GRUNDFOS A-(M2-2)
ITEM REMARKS
PUMP SKID SCHEDULE
TOTAL
GPM
750
INLET
PRESSURE
15 PSI
OUTLET
PRESSURE
50 PSI
PUMP #1
MODEL
NUMBER
GPM
750
PUMP #2
REMARKS
A. FACTORY BUILT, PRETESTED, SKID MOUNTED PACKAGE SUITABLE FOR INSTALLATION THROUGH EXISTING DOOR OPENING. FURNISH 6" SUCTION AND DISCHARGE HEADERS, VFD FOR EACH PUMP,
SUCTION AND DISCHARGE ISOLATION VALVES AND DISCHARGE CHECK VALVE FOR EACH PUMP, AIR DIRT SEPARATOR, (SEE SCHEDULE), 1" MAKE UP WATER CONNECTION, PRESSURE REDUCING VALVE
SET FOR 12 PSI, PRESSURE RELIEF VALVE, 5 GALLON BYPASS FILTER FEEDER,.
B. CONTROL PANEL WITH DISCONNECT SWITCHES, RUN LIGHTS, SINGLE POINT POWER CONNECTION, PREWIRED AND TESTED AT FACTORY.
C. FURNISH WITH ARMSTRONG A-200-L EXPANSION TANK, AS SCHEDULED FILTER FEEDER.
D. APPROVED EQUALS BY BELL AND GOSSETT, PACO GRUNDFOS AND SYSTECON.
PS-1 A, B, C
HP
7.5
PUMP
GPM
80
V-PH
460-3
ELECTRICAL
MANUFACTURER
ARMSTRONG
LOCATION
A-(M2-2)
HP
20
V-PH
460-3
RPM
1750
MODEL
NUMBER
GPM
750
HP
20
V-PH
460-3
RPM
1750
1 NETWORK CONTROL ENGINE
H
N
G
G
OA TEMP
CCCT SUMP TEMP
HYDRONIC SUPPLY TEMP
HYDRONIC RETURN TEMP
BOILER RETURN TEMP
BOILER SUPPLY TEMP
SYSTEM DP SENSOR
CCCT-1 LWT
MUW WATER METER
BOILER PUMP RUN
CCCT PUMP RUN
BOILER ALARM
BOILER S/S
BOILER RAMP
CCCT PUMP START STOP
SS-1 START STOP
TO VFD'S
JOHNSON
CONTROLS
NCE 251X
UN
IV
ER
SA
L O
UT
PU
TS
BIN
AR
Y O
UT
PU
TS
UN
IV
ER
SA
L IN
PU
TS
BIN
AR
Y IN
PU
TS
SA
B
US
N2 B
US
ET
HE
RN
ET
SUMP HEATER ENABLE
LAN MS/TP BUS
460V-3PH
2 VFD DRIVEN PUMPS & FANS
MOTOR
ROOM TEMP SENSOR AI ANALOG INPUT
DIRECT DIGITAL CONTROL SYSTEM LEGEND
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
DDC SYSTEM GENERAL REQUIREMENTS
1. DDC CONTROLS SHALL BE INSTALLED BY JOHNSON CONTROLS.
2. ALL WIRING SHALL BE IN CONDUIT OR MC CABLE. LOW VOLTAGE WIRING MAY BE IN PLENUM PLATED CABLE.
3. DDC CONTROL WORK INCLUDES LOW VOLTAGE CONDUIT & WIRING AND POWER CONDUIT & WIRING NOT SHOWN ON
ELECTRICAL DRAWINGS, BUT REQUIRED FOR THE SEQUENCE OF CONTROL.
4. REFER TO ELECTRICAL DRAWINGS FOR POWER WIRING, STARTERS, DISCONNECTS, CONTRACTORS, RELAYS &
APPURTENANCES INCLUDED WITH THE ELECTRICAL WORK.
5. DDC CONDUIT & WIRING SHALL CONFORM TO ELECTRICAL SPECIFICATIONS & GENERAL REQUIREMENTS.
6. PROVIDE BOILER ROOM EMERGENCY STOP PUSH BUTTON WITH GUARD TO SHUT DOWN BOILERS P-1,P-2, AND P-3. IN
ACCORDANCE WITH THE REQUIREMENTS OF NRS 455C. THE MECHANICAL SECTION OF THE NEVADA DIVISION OF
OCCUPATIONAL SAFETY AND HEALTH.
AO ANALOG OUTPUT
AUTO AUTOMATIC
AVE AVERGING
CO CARBON DIOXIDE
2
DI DIGITAL INPUT
DO DIGITAL OUTPUT
DDC DIRECT DIGITAL CONTROLS
DISC DISCONNECT
EMCS ENERGY MANAGEMENT
EA EXHAUST AIR
FA FIRE ALARM
G GROUND
H HOT
LAN ETHERNET LOCAL AREA NETWORK
N NEUTRAL
NC NORMALLY CLOSED
NO NORMALLY OPEN
OA OUTDOOR AIR
PH PHASE
REF REFERENCE
RA RETURN AIR
S/S START/STOP
SA SUPPLY AIR
TEMP TEMPERATURE
TSTAT THERMOSTAT
TYP TYPICAL
V VOLT
TEMP SENSOR - PENCIL PROBE
TEMP SENSOR - AVE ELEMENT
FREEZE PROTECTION THERMOSTAT
TEMP SENSOR WITH SUNSHIELD
TEMP SENSOR WITH WELL
AUTO DAMPER & OPERATOR
SPACE CARBON DIOXIDE SENSOR
AIR VELOCITY SENSOR
COMB TEMP / HUMIDITY SENSOR
FLOW SWITCH
DUCT SMOKE DETECTOR
CONDUCTIVITY PROBE
2 - WAY CONTROL VALVE
3 - WAY CONTROL VALVE
AIR FLOW INLET
CURRENT STATUS SWITCH
CIRCUIT BREAKER (POWER)
DISC SWITCH (POWER)
3 - PHASE DISC SWITCH (POWER)
STARTER OR CONTACTOR (POWER)
STARTER / DISC SWITCH (POWER)
VARIABLE FREQUENCY DRIVE (POWER)
POWER CONDUIT & WIRING
LOW VOLTAGE CONDUIT & WIRING
ELECTRICAL CONNECTION
FUSED CONTROL POWER TRANSFORMER
RELAY NO CONTACTS
RELAY NC CONTACTS
PROGRAMMABLE THERMOSTAT
AIR FLOW OUTLET
T
T
T
C
V
T H
FS
DD
CP
T
T
T
T
F
CS
F
V
D
BUS 78K BAUD TWISTED PAIR MSTP
R HYDRONIC RETURN
S HYDRONIC SUPPLY
150
PSIG
WP
ASME
8"
A. AIR-DIRT SEPARATOR WITH BOTTOM BLOW DOWN BALL VALVE, AUTOMATIC AIR VENT.
B. FURNISH WITH FLANGED CONNECTIONS.
C. APPROVED EQUALS BY THRUSH.
ITEM
REMARKS
REMARKSLOCATION
1-(M3.0)
AIR-DIRT SEPARATOR SCHEDULE
AS-1
SERVES
HYDRONIC LOOPSPIROTHERM
GPM
750
SIZE
95
WEIGHT
LBS
OPER
A, B
MODEL NOMFR
VDT-800
20 460-3VFD-2 P-1 A, BA-(M2-2)
20 460-3VFD-3 P-2 A, BA-(M2-2)
SOLIDS SEPARATOR SCHEDULE
CSS-201-HHA-(M2-2)
LOCATION
GRISWOLD
MODEL NO
420
WEIGHT
LBS
REMARKS
110
GPM
50
TDH
FT
OPER
460-3
V-PH
5.0
HP
A. FURNISH WITH 3500 RPM PUMP WITH INLET STRAINER, CAST IRON VOLUTE AND BRONZE IMPELLER; CARBON STEEL POWDER
COATED CYCLONIC SEPARATOR; CAST IRON INLET STRAINER WITH STAINLESS STEEL BASKET; 1" 115V MOTORIZED BALL TYPE
BLOW DOWN VALVE' NEMA 4 POWDER COATED, WATERTIGHT, UL LISTED CONTROL PANEL WITH 115V TRANSFORMER, PUMP RUN
LIGHT, CONTACTOR, LOCKABLE DOOR DISCONNECT, PURGE TIMER, H-O-A SWITCH, REMOTE STOP START CONTROL.
B. SKID MOUNTED.
REMARKS
ITEM
SS-1 A, B
4300-0610-020 4300-0610-020
ITEM
REMARKS
REMARKS
BOILER SCHEDULE
ELECTRICAL
V-PH
LOCATION
MBH
GAS
INPUT
MBH
OUTPUT
AMPS
AFUE
FLUE
DIA
OPER
WEIGHT
LBS
A. FURNISH WITH 50# ASME RELIEF VALVE, STAINLESS STEEL HEAT EXCHANGER, CONDENSATE TRAP, CONDENSATE
NEUTRALIZATION KIT, FLOW SWITCH, LOW WATER CUT OFF AND MANUAL RESET, PUMP ON- OFF CONTROL, ALARM ON ANY
FAILURE CONTACTS, RUNTIME OUTPUT CONTACTS; REMOTE ENABLE/DISABLE ,SUPPLY WATER TEMPERATURE SET POINT
ADJUSTMENT FROM ENERGY MANAGEMENT SYSTEM, AND ZERO CLEARANCE TO COMBUSTIBLE MATERIAL.
B. APPROVED EQUALS BY RAYPAK, LAARS, RBI, PATTERSON KELLY, AERCO AND THERMAL SOLUTIONS.
115-1B-1 A-(M2-2) 1500 1443 15 95.4% 6"Ø 926 ASYNC SBN 1500
MODEL NO
LOCHINVAR
VFD 3 S/S
VFD 2 RAMP
VFD 2 S/S
VFD 1 RAMP
VFD-1 S/S
VFD 3 RAMP
CHEMICAL TRT. ALARM
SS-1 PURGE VALVE OPEN
CCCT VIBRATION SWITCH
PARTIAL FLOOR PLANSM2-0
FILTER FEEDER SCHEDULE
FHC-DB-5HD
ITEM
WINGERT
MODEL NO
LBS
HYDRONIC LOOP
SERVICE
5
SIZE
GALLON
3/4
CONNECTION
SIZE
INCHES
25
FILTER
EFFICIENCY
MICRON
PUMP-SKID
LOCATION
50
WEIGHT
FF-1
MS/TP BUS
S/S
RAMP
P:\
2015_Jo
bs\
15020 L
ewis
Buil
din
g C
ooli
ng T
ow
er a
nd B
oil
er R
epla
cem
ent\
DW
G_B
LD
G D
EP
T\1
5020 M
0-0
.dw
g, 12/1
/2015 8
:59:4
9 A
M, A
lec
Dil
lard
4
3.6
3.4
1.6
1.4
1
2.5
1
2
3
4
2
3
UP
REFER TO A-(M2-1) FOR DEMO WORK
REFER TO A-(M2-2) FOR NEW WORK
4
3.6
3.4
1.6
1.4
1
2.5
1
2
3
4
2
3
BASEMENT LEVEL GARAGE
ELECTRICAL/
MECHANICAL
ROOM
103
TELE/DATA
ROOM
104
MEN
105
WOMEN
107
CL
106
CAFE
OPEN RESTAURANT SEATING
113
OFFICE
109
CAFE
115
ELEVATOR LOBBY
102
FIRST FLOOR LOBBY
100
MAIN BUILDING
ENTRANCE
CAFE
ENTRANCE
116
SERVER
STATION
114
KITCHEN
111
DRY
STORAGE
110
ELEVATOR ELEVATOR
PARKING
ENTRY
EXISTING MECHANICAL
ROOM
120
SID
EW
ALK
EXISTING 3 HR.
WALLS
TYPICAL
SUITE 100
108
CAFE
112
ADDITIVE
ALTERNATE #1
(702)
455-6731
Las V
egas, N
evada
500 S
. G
RA
ND
C
EN
TR
AL P
AR
KW
AY
DE
PA
RT
ME
NT
O
F R
EA
L P
RO
PE
RT
Y M
AN
AG
EM
EN
T
CLA
RK
C
OU
NT
Y
AC
QU
IS
IT
IO
N, D
ES
IG
N, &
C
ON
ST
RU
CT
IO
N D
IV
IS
IO
N
TH
E LE
WIS
P
RO
FE
SS
IO
NA
L B
LD
G.
DA
TE
: N
OV
EM
BE
R 1
9, 2
01
5
ME
CH
AN
IC
AL U
PG
RA
DE
330 S
. 3R
D S
TR
EE
T, LA
S V
EG
AS
, N
V 89101
1502
0
B ROOF PLAN M1-0
NO
RT
H
A FIRST FLOOR PLAN
NO
RT
H
POINT OF CONNECTION TO EXISTING. VERIFY EXACT SIZE
AND LOCATION IF FIELD PRIOR TO START OF WORK.
EXSITING WORK TO REMAIN SHOWN LIGHT. EXISTING WORK
TO BE REMOVED SHOWN DARK AND DASHED. NEW WORK
SHOWN DARK.
KEY NOTES
1. LOCATION OF EXISTING SYSTEM DRAIN VALVES.
2. EXTEND NEW 5" S/R FROM RISERS UP TO LOCATION SHOWN. PROVIDE BUTTERFLY VALVES WITH BLIND FLANGES FOR FUTURE EMERGENCY COOLING CONNECTION. (ADD ALTERNATE #1)
3. EXISTING LEVEL 1 ZONE ISOLATION VALVES.
4. INSTALL AS HIGH AS POSSIBLE.
NOTICE
P:\
20
15
_Jo
bs\
15
02
0 L
ewis
Bu
ild
ing
Co
oli
ng
To
wer
an
d B
oil
er R
epla
cem
ent\
DW
G_
BL
DG
DE
PT
\15
02
0 M
1-0
.dw
g,
12
/1/2
01
5 8
:59
:51
AM
, A
lec
Dil
lard
ELECTRICAL/
MECHANICAL
ROOM
103
TELE/DATA
ROOM
104
MEN
105
WOMEN
107
CL
106
OPEN RESTAURANT SEATING
OFFICE
109
ELEVATOR LOBBY
102
FIRST FLOOR LOBBY
100
KITCHEN
111
DRY
STORAGE
110
ELEVATOR ELEVATOR
PARKING
ENTRY
EXISTING 3 HR.
WALLS
TYPICAL
SUITE 100
108
CAFE
112
SECOND LEVEL GARAGE
MECH.
ROOM
201
ELEVATOR LOBBY
200
ELEVATOR ELEVATOR
SUITE 200
ELEVATOR ELEVATOR
ELEVATOR
LOBBY
600
W M
OFFICE OFFICE STORAGE OFFICE
RECEPTION
STORAGE
BREAK
ROOM
TRAINING
ROOM
OFFICEOFFICE
OPEN OFFICE
RECEPTION
MECH.
ROOM
RECEPTION
OFFICE
SUITE 600
ELEVATOR ELEVATOR
SERVER
ROOM
814
OFFICE
817
OFFICE
816
OFFICE
815
OFFICE
813
OFFICE
828
OFFICE
829
OFFICE
830
OPEN
AREA
869
OFFICE
870
ELEVATOR
LOBBY
884
MECH.
ROOM
883
OPEN
AREA
803
RECEPTION
AREA
802
WAITING
AREA
801
BREAK
ROOM
868
W
881
M
882
SUITE 800
CORRIDOR
826
CORRIDOR
880
ELEVATOR ELEVATOR
SUITE 900
SUITE 990ROOM
901
ROOM
903
ROOM
920
ROOM
921
ROOM
930
ROOM
931
CORRIDOR
940
SUITE 920SUITE 930
ROOM
998
ROOM
999
ELEVATOR
LOBBY
900
(702)
455-6731
Las V
egas, N
evada
500 S
. G
RA
ND
C
EN
TR
AL P
AR
KW
AY
DE
PA
RT
ME
NT
O
F R
EA
L P
RO
PE
RT
Y M
AN
AG
EM
EN
T
CLA
RK
C
OU
NT
Y
AC
QU
IS
IT
IO
N, D
ES
IG
N, &
C
ON
ST
RU
CT
IO
N D
IV
IS
IO
N
TH
E LE
WIS
P
RO
FE
SS
IO
NA
L B
LD
G.
DA
TE
: N
OV
EM
BE
R 1
9, 2
01
5
ME
CH
AN
IC
AL U
PG
RA
DE
330 S
. 3R
D S
TR
EE
T, LA
S V
EG
AS
, N
V 89101
1502
0
M2-0
NO
RT
H
B PARTIAL PLAN - LEVELS 2, 3 & 4
TEMPORARY COOLING
WHEN HVAC SYSTEM HYDRONIC FLOW IS SHUT DOWN
FOR CONSTRUCTION. CONTRACTOR SHALL PROVIDE
"SPOT COOLERS" OR EQUAL OFFICE PRO 18, 24 OR 36
COOLERS, SIZED TO MATCH THE EXISTING HEAT PUMP
SERVING THE SPACE, FOR THE FOLLOWING ROOMS:
1. ROOF ELEVATOR MACHINERY ROOM
2. LEVEL 10 IT ROOM
3. LEVEL 9 IT ROOM
4. LEVEL 8 IT ROOM
5. LEVEL 6 IT ROOM
6. LEVEL 5 IT ROOM
7. LEVEL 1 IT ROOM
8. LEVEL 1 FIRE CONTROL ROOM
C PARTIAL FIFTH FLOOR PLAN D PARTIAL SIXTH FLOOR PLAN
E PARTIAL SEVENTH FLOOR PLAN F PARTIAL EIGHTH FLOOR PLAN G PARTIAL NINTH FLOOR PLAN H PARTIAL TENTH FLOOR PLAN
A PARTIAL FIRST FLOOR PLAN
POINT OF CONNECTION TO EXISTING. VERIFY EXACT SIZE
AND LOCATION IF FIELD PRIOR TO START OF WORK.
EXSITING WORK TO REMAIN SHOWN LIGHT. EXISTING WORK
TO BE REMOVED SHOWN DARK AND DASHED. NEW WORK
SHOWN DARK.
NOTICE
KEY NOTES
1. REMOVE EXISTING 2-1/2" S/R PIPING UP & DOWN. IN CHASE, REPLACE WITH 5" S/R PIPING UP & DOWN.
(ADD ALTERNATE #1)
2. EXTEND NEW 5" S/R FROM RISERS UP TO LOCATION SHOWN. PROVIDE BUTTERFLY VALVES WITH BLIND FLANGES FOR FUTURE EMERGENCY COOLING CONNECTION. (ADD ALTERNATE #1)
3. CONNECT EXISTING PIPING SERVING THE FLOOR TO NEW 5" S/R PIPING.(ADD ALTERNATE #1)
4. CONNECT 5" S/R PIPING TO EXISTING 6" S/R PIPING IN CHASE. PROVIDE NEW 6" BUTTERFLY VALVES IN VERTICAL RISERS TO ISOLATE PIPING BELOW. (ADD ALTERNATE #1)
5. EXISTING ISOLATION VALVES TO FLOOR UNITS. CLOSE VALVES PRIOR TO DRAINING MAINS. MARK EXISTING BALANCE LOCATIONS.
6. EXISTING LEVEL 1 ZONE ISOLATION VALVES.
P:\
20
15
_Jo
bs\
15
02
0 L
ewis
Bu
ild
ing
Co
oli
ng
To
wer
an
d B
oil
er R
epla
cem
ent\
DW
G_
BL
DG
DE
PT
\15
02
0 M
2-0
.dw
g,
12
/1/2
01
5 8
:59
:54
AM
, A
lec
Dil
lard
UP
PHASE III DEMOLITION INCLUDES
CLOSED CIRCUIT FLUID COOLER
AND PIPING TO ISOLATION VALVES
(702) 455-6731
Las V
egas, N
evada
500 S
. G
RA
ND
C
EN
TR
AL P
AR
KW
AY
DE
PA
RT
ME
NT
O
F R
EA
L P
RO
PE
RT
Y M
AN
AG
EM
EN
T
CLA
RK
C
OU
NT
Y
AC
QU
IS
IT
IO
N, D
ES
IG
N, &
C
ON
ST
RU
CT
IO
N D
IV
IS
IO
N
TH
E LE
WIS
P
RO
FE
SS
IO
NA
L B
LD
G.
DA
TE
: N
OV
EM
BE
R 1
9, 2
01
5
ME
CH
AN
IC
AL U
PG
RA
DE
330 S
. 3R
D S
TR
EE
T, LA
S V
EG
AS
, N
V 89101
1502
0
A DEMO ROOF FLOOR PLAN - HVAC M2-1
GENERAL DEMOLITION
1. PHASE I. SHUT SYSTEM DOWN. CLOSE ISOLATION VALVES
TO EACH FLOOR. DRAIN MAINS FROM BOILER ROOM TO
LEVEL 1. PROVIDE NEW BUTTERFLY VALVES WHERE 6" S &
R ENTER & LEAVE BOILER ROOM. ISOLATION BUTTERFLY
VALVES TO PERMIT REMOVAL OF BOILER & PHASE I
PIPING. INSTALL ISOLATION VALVES ON RISER - REFER TO
PARTIAL SIXTH FLOOR PLAN REFILL SYSTEM. REMOVE AIR,
OPEN ISOLATION VALVES.
2. PHASE II. DEMOLITION PIPING REMOVE EXIST. BOILER
FLUE UP TO ROOF. EXIST PIPE THRU ROOF TO REMAIN.
3. REMOVE EXISTING EQUIPMENT AND ASSOCIATED PIPING.
4. REWORK EXISTING HOUSEKEEPING PADS AS REQUIRED
FOR NEW EQUIPMENT. PROVIDE SHOP DRAWING OF NEW
PAD LAYOUTS, TO INCLUDE REINFORCEMENTS AND
PROPOSED ATTACHMENT METHOD TO EXISTING
CONCRETE SLAB FOR REVIEW.
5. EXISTING WATER HEATER, FLUE, HOT WATER
CIRCULATING PUMP & FIRE SPRINKLERS SHALL REMAIN.
6. EXISTING COMBUSTION AIR LOOVERS SHALL REMAIN.
7. REMOVE EXISTING FLUE UP & FLUE PIPING FROM 12"
ABOVE THE ROOF UP.
8. EXISTING ATMOSPHERIC DRAFT 2000 MBH INPUT BOILER.
NO
RT
H
REQUIREMENTS
POINT OF DISCONNECTION TO EXISTING. VERIFY EXACT
SIZE AND LOCATION IF FIELD PRIOR TO START OF WORK.
EXSITING WORK TO REMAIN SHOWN LIGHT. EXISTING WORK
TO BE REMOVED SHOWN DARK AND DASHED. NEW WORK
SHOWN DARK.
NOTICE
P:\
2015_Jo
bs\
15020 L
ewis
Buil
din
g C
ooli
ng T
ow
er a
nd B
oil
er R
epla
cem
ent\
DW
G_B
LD
G D
EP
T\1
5020 M
2-1
.dw
g, 12/1
/2015 8
:59:5
7 A
M, A
lec
Dil
lard
UP
BOILER ROOM AREA=240 SF ONE EXIT REQ'D
(702) 455-6731
Las V
egas, N
evada
500 S
. G
RA
ND
C
EN
TR
AL P
AR
KW
AY
DE
PA
RT
ME
NT
O
F R
EA
L P
RO
PE
RT
Y M
AN
AG
EM
EN
T
CLA
RK
C
OU
NT
Y
AC
QU
IS
IT
IO
N, D
ES
IG
N, &
C
ON
ST
RU
CT
IO
N D
IV
IS
IO
N
TH
E LE
WIS
P
RO
FE
SS
IO
NA
L B
LD
G.
DA
TE
: N
OV
EM
BE
R 1
9, 2
01
5
ME
CH
AN
IC
AL U
PG
RA
DE
330 S
. 3R
D S
TR
EE
T, LA
S V
EG
AS
, N
V 89101
1502
0
A PARTIAL ROOF/MECHANICAL ROOM PLAN - HVAC M2-2
KEY NOTES
1. MOUNT ON 4" CONCRETE HOUSE KEEPING PAD.
2. BOILER CIRCULATOR PUMP.
3. EMERGENCY SHUT DOWN SWITCH.
4. CONNECT 6" SUPPLY & RETURN PIPING TO EXISTING MAINS.
5. EXISTING WATER HEATER & CIRC PUMP TO REMAIN.
6. NEW EMCS PANEL.
7. SERVES COOLING TOWER FAN.
8. 6" TYPE IV BOILER FLUE UP THRU ROOF THRU EXIST. SLEEVE. PROVIDE NEW CAP AND SEAL WATER TIGHT.
9. MOUNT ON NEW BASE. REFER TO DETAIL 1-(M3-0).
10. INSTALL ON STRUCTURAL SUPPORT. REFER TO STRUCTURAL DRAWINGS.
11. 8"Ø COMBUSTION AIR INTAKE PER BOILER MFR REQUIREMENTS.
12. CAP OFF UNUSED PORTION OF OSA LOUVER WITH SHEET METAL AND 2" RIGID INSULATION.
13. COMBUSTION AIR INTAKE FITTING PER MANUFACTURER'S RECOMMENDATIONS.
NO
RT
H
B BOILER ROOM VENTILATION PLAN
NOTICE
POINT OF CONNECTION TO EXISTING. VERIFY EXACT SIZE AND LOCATION IF FIELD PRIOR TO START OF WORK.
EXISTING WORK TO REMAIN SHOWN LIGHT. EXISTING WORK TO BE REMOVED SHOWN DARK AND DASHED.
NEW WORK SHOWN DARK.
VERIFY 'FIT' OF PUMP SKID AND REQUIREMENTS FOR ENTRY OF NEW EQUIPMENT PRIOR TO BEGINNING
WORK.
P:\
2015_Jo
bs\
15020 L
ewis
Buil
din
g C
ooli
ng T
ow
er a
nd B
oil
er R
epla
cem
ent\
DW
G_B
LD
G D
EP
T\1
5020 M
2-2
.dw
g, 12/1
/2015 8
:59:5
9 A
M, A
lec
Dil
lard
(702) 455-6731
Las V
egas, N
evada
500 S
. G
RA
ND
C
EN
TR
AL P
AR
KW
AY
DE
PA
RT
ME
NT
O
F R
EA
L P
RO
PE
RT
Y M
AN
AG
EM
EN
T
CLA
RK
C
OU
NT
Y
AC
QU
IS
IT
IO
N, D
ES
IG
N, &
C
ON
ST
RU
CT
IO
N D
IV
IS
IO
N
TH
E LE
WIS
P
RO
FE
SS
IO
NA
L B
LD
G.
DA
TE
: N
OV
EM
BE
R 1
9, 2
01
5
ME
CH
AN
IC
AL U
PG
RA
DE
330 S
. 3R
D S
TR
EE
T, LA
S V
EG
AS
, N
V 89101
1502
0
A FLOW DIAGRAM
CLOSED CIRCUITCOOLING TOWER
BYPASSFILTER-FEEDEREXPANSION
TANKBOILER
KEY NOTES
1. 3/4" BALL VALVE WITH HOSE THREADS & CAP FOR AIR VENT
2. CORROSION COUPON RACK.
3. CONCENTRIC INCREASER.
4. THERMOMETER.
5. SUCTION DIFFUSER.
6. COMBINATION PRESSURE/TEMPERATURE GAUGE.
7. ROUTE DRAIN TO OVER NEAREST FLOOR SINK.
8. CONDUCTIVITY CONTROL CONNECTED TO EXISTING
POWER SUPPLY.
9. SOLENOID DRAIN VALVE.
10. STEEL BASE FRAME. OVER CONCRETE HOUSE KEEPING
PAD.
11. TEST WELL (PETE'S PLUG).
12. EMCS TEMPERATURE SENSOR.
13. COOLING TOWER SUPPORT BEAMS PER MANUFACTURER'S
RECOMMENDATION. ALSO REFER TO STRUCTURAL
DRAWINGS.
14. RELIEF VALVE.
15. 3/4" BLOWDOWN VALVE WITH MALE HOSE THREADS.
16. CONNECT TO MAKE UP WATER CONNECTION.
17. MAKE UP WATER SHUTOFF VALVE. (CLOSE WHEN DRAINING
TOWER).
18. PVC PIPING WITH 1" INSULATION AND 0.016" ALUM JACKET.
19. FLOW SWITCH.
20. PRESSURE GAUGE 30" HG VAC TO +60 PSI.
21. ECCENTRIC REDUCER.
22. REDUCED PRESSURE BACKFLOW PREVENTER ASSEMBLY.
23. CONNECT TO EXISTING CW SUPPLY.
24. CONNECT TO TOWER BASIN EDUCTOR NOZZLES AND
DISTRIBUTION PIPING.
25. EXTEND FULL SIZE OVERFLOW TO TERMINATE OVER FLOOR
SINK.
26. EXTEND FULL SIZE DRAIN TO OVER FLOOR SINK.
27. BUTTERFLY VALVE.
28. MANUAL BYPASS (NORMALLY CLOSED).
29. EXTEND CONDENSATE DRAINS FROM BOILER AND FLUE
SYSTEM THRU CONDENSATE ACID NEUTRALIZATION TRAP
AND TERMINATE ABOVE FLOOR SINK.
30. INSTALL ON EQUIPMENT PLATFORM. REFER TO DETAIL
1-(M3.0)
NOTICE
UNIT WITH ELECT CONNECTION
SUPPLY CFM
OSA CFM
UNIT WITHOUT ELECT CONNECTION
SUPPLY CFM
POINT OF CONNECTION TO EXISTING. VERIFY EXACT SIZE
AND LOCATION IF FIELD PRIOR TO START OF WORK.
EXSITING WORK TO REMAIN SHOWN LIGHT. NEW WORK
SHOWN DARK.
CHEMICAL TREATMENTSYSTEM
(EXISTING - RELOCATED)
M3-0
SOLIDSSEPARATOR
PUMPPUMPPRIMARY
AIR/DIRTSEPARATOR
PUMP
PUMP SKID
1 EQUIPMENT PLATFORM DETAIL 2 ROOF TOP PIPE SUPPORT DETAIL
NOTE: ITEMS WITHIN DASHED OUTLINED AREA BELOW ARE TO BE INCLUDED IN THE PUMP SKID PACKAGE
PIPE/CONDUIT
CAULKING/ADHESIVE
(MIRO INDUSTRIES, OR APPROVED EQUAL)
(NOT ADHERED)
LAYER OF SINGLE PLY MEMBRANE
(TO SECURE PIPE STAND TO MEMBRANE)
PIPE STAND
3 FIRE STOPPING DETAIL
NOTES: PROVIDE ROOF PRODUCTS, INC. MODEL RPPF-3 PLATFORM CURB, 48"x48". PROVIDE
UNI-STRUT OR EQUAL STAND FOR DISCONNECT SWITCH AND POWER RECEPTACLE AS SHOWN.
CHEMICAL TREATMENT
CONTRACT INCLUDES ONE YEAR CLOSED HYDRONIC LOOP
CHEMICAL TREATMENT AND ONE YEAR OPEN COOLING
TOWER CHEMICAL TREATMENT BY NALCO. CONTACT
NALCO OFFICE AT (702) 373-8232. NO SUBSTITUTIONS.
P:\
2015_Jo
bs\
15020 L
ewis
Buil
din
g C
ooli
ng T
ow
er a
nd B
oil
er R
epla
cem
ent\
DW
G_B
LD
G D
EP
T\1
5020 M
3-0
.dw
g, 12/1
/2015 9
:00:0
2 A
M, A
lec
Dil
lard
(702) 455-6731
Las V
egas, N
evada
500 S
. G
RA
ND
C
EN
TR
AL P
AR
KW
AY
DE
PA
RT
ME
NT
O
F R
EA
L P
RO
PE
RT
Y M
AN
AG
EM
EN
T
CLA
RK
C
OU
NT
Y
AC
QU
IS
IT
IO
N, D
ES
IG
N, &
C
ON
ST
RU
CT
IO
N D
IV
IS
IO
N
TH
E LE
WIS
P
RO
FE
SS
IO
NA
L B
LD
G.
DA
TE
: N
OV
EM
BE
R 1
9, 2
01
5
ME
CH
AN
IC
AL U
PG
RA
DE
330 S
. 3R
D S
TR
EE
T, LA
S V
EG
AS
, N
V 89101
1502
0
E0-0
SURFACE MOUNTED FIXTURE
WALL SCONCE
HIGH BAY FIXTURE
FOUR-WAY SWITCH, 20A, 120/277V
THREE-WAY SWITCH, 20A, 120/277V
TWO POLE SWITCH, 20A
SUSPENDED LINEAR FLUORESCENT FIXTURE
LINEAR FLUORESCENT FIXTURE
3
M
F
J
COMBINATION CONTROLLER/DISCONNECT SWITCH
"30/3/15/1" DENOTES AMPERES/POLES/FUSE(OR
BREAKER)/NEMA STARTER SIZE.
VENDOR FURNISHED COMBINATION
CONTROLLER/DISCONNECT SWITCH
JUNCTION BOX
FLUSH MOUNT FLOOR JUNCTION BOX
NON-FUSED DISCONNECT SWITCH
VENDOR FURNISHED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
MOTOR CONTROLLER OR STARTER
WALL MOUNT
CEILING DUPLEX RECEPTACLE
CLOCK OUTLET w/ RECESSED COVER PLATE AT +9O"
SPECIAL PURPOSE OUTLET (TYPE AS NOTED)
GFCI RECEPTACLE
DUPLEX RECEPTACLE MOUNTED ABOVE
COUNTER - VERIFY MOUNTING HEIGHT
DUPLEX RECEPTACLE / HALF-SWITCHED
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, 20A, 125V
DUPLEX RECEPTACLE, NEMA 5-20R, 20A, 125V
SINGLE RECEPTACLE, NEMA 5-20R, 20A, 125V
C
J
J
TRANSFORMER
SERVICE PEDESTAL
SWITCHBOARD OR DISTRIBUTION BOARD
PANELBOARD - RECESSED AT +72" TO TOP
PANELBOARD - SURFACE AT +72" TO TOP
TELEPHONE BACKBOARD
TELEPHONE TERMINAL CABINET AT +72" TO TOP
T
SMOKE DETECTOR
WALL MOUNTED SENSOR
FIRE/SMOKE DAMPER
CARBON MONOXIDE DETECTOR (SPECIFIED BY
MECHANICAL ENGINEER)
THERMOSTAT OUTLET AT +54"
RELAY
TIME SWITCH
CONTACTOR
PHOTOCELL
FIRE ALARM HORN/STROBE
LIGHTING CONTACTOR
F-1
FD
CO
S
H
CR
LC
PC
S
C
XX
CIRCUIT BREAKER IN DEDICATED ENCLOSURE
FIXTURE
DEMOLITION/DEMOLISH
ELECTRICAL
NEVADA POWER COMPANY
NORMALLY OPEN
NOT TO SCALE
NEUTRAL
ABOVE FINISHED FLOOR
NIC
REQ'D
RECEP
PWR
EQUIP
FBO
FIXT
GFCI
ARCH'L.
DWG
AIC
AS
AL
CO, EC
C
A
ELECT.
DEMO
POLEP
(E), EXIST EXISTING
NORMALLY CLOSEDNC
SWGRSWITCH GEAR
SYSSYSTEM
TEMPTEMPORARY
BARE COPPER
NON-FUSIBLENF
GROUND FAULT ALARMGFA
INTERNATIONAL BUILDING CODEIBC
STANDARD ABBREVIATIONS ELECTRICAL LEGEND
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
LINEAR FLUORESCENT FIXTURE
PUSH BUTTON CONTROL STATION
PENDANT FIXTURE
"F" INSIDE INDICATES FLUORESCENT
A
RECESSED FIXTURE
OCCUPANCY SENSOR (DUAL-TECHNOLOGY TYPE UNO)
PILOT LIGHT
WARNING LIGHT
OCCUPANCY SENSOR SWITCH
DENOTES DUAL LEVEL SWITCHING
KEY SWITCH, 20A, 120/277V
LOWER CASE LETTER DENOTES FIXTURES TO BE
CONTROLLED
HP RATED MOTOR SWITCH WITH THERMAL OVERLOAD
PROTECTION
DIMMER SWITCH, MIN. 2000W, 120/277V
SINGLE POLE SWITCH, 20A, 120/277V
FIXTURE w/ EMERGENCY BATTERY BALLAST
EMERGENCY FIXTURE
EXIT SIGN
LETTER REFERS TO FIXTURE SCHEDULE
WALL WASHER
WALL MOUNTED FIXTURE
LIGHT FIXTURE
LINEAR FLUORESCENT STRIP FIXTURE
FLUORESCENT WALL MOUNT FIXTURE
4
2
D
M
a
K
OS
F
PULLBOX - EXTERIORPB
SMOKE DETECTOR (SUBSCRIPT "D" INDICATES DUCT
MOUNTED)
HEAT DETECTOR
W
FLUSH FLOOR BOX WITH COMBINATION
TELE/COMPUTER OUTLET
COMBINATION TELE/COMPUTER OUTLET AT +18"
COMPUTER OUTLET AT +18"
WALL TELEPHONE OUTLET AT +54"
CARD READER
TIME CLOCK
FLOW SWITCH
TAMPER SWITCH
SPEAKER, CEILING OR WALL MOUNTED
DOOR HOLD OPEN
T
FS
TS
SD
S
DH
TC
TS
R
S
REVISION SYMBOL
SCHEDULED EQUIPMENT
KEYNOTE SYMBOL
EQUIPMENT TAG
DIAGRAM TAG
PUSH BUTTON
POWER METER
CIRCUIT BREAKER
SURGE SUPPRESSOR
CONTACT NORMALLY OPEN
MOTOR
CONTACT NORMALLY CLOSED
TIME SWITCH
SWITCH
CURRENT TRANSFORMER
POTENTIAL TRANDFORMER
GROUNDING ELECTRODE
FUSE
FUSE DISCONNECT SWITCH
CABLE TERMINATION
SWITCH
AUTOMATIC TRANSFER SWITCH
SHUNT TRIP
GROUND FAULT INTERRUPT
TRANSFER
SWITCH
GENERATOR
CONDUIT ROUTED UNDER FLOOR / UNDERGROUND
RACEWAY WITH #12 UNO
RACEWAY TURNED UP
RACEWAY TURNED DOWN
HOMERUN TO PANELBOARD 1/2"C
WITH 3 #12 CONDUCTORS UNO
CIRCUIT BREAKER IN DEDICATED ENCLOSURE
HOMERUN
CONDUIT ONLY
ARCHITECTURAL
CIRCUIT BREAKER
COMMUNICATION
CABINET
AMPERE
NOT IN CONTRACT
MOUNTED
MINIMUM
MECHANICAL
MAIN CIRCUIT BREAKER
FEET OR FOOT
HORSEPOWER
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
HEATING, VENTILATING & AIR CONDITIONING
DISCONNECT
DRAWING
ELEVATOR
GROUND FAULT CIRCUIT INTERRUPTER
PANEL
POWER
RECEPTACLE
REQUIRED
SECTION
QUANTITY
SCHEDULE
OVERCURRENT PROTECTION
NATIONAL ELECTRICAL CONTRACTOR'S ASSOCIATION
NATIONAL FIRE CODE
MAIN LUGS ONLY
INTERMEDIATE METAL CONDUIT
AMERICAN WIRE GAUGE
ABOVE FINISHED GRADE
CATALOG/CATEGORY
ALUMINUM
FURNISHED BY OTHERS
AMPERE INTERRUPTING CAPACITY
ARC FAULT, AMP FUSE
NEMA
NEUT
NFC
NL
PH
NPCO
SPEC
RSC
SP
SN
OCP
SECT
SCHED
PNL
NTS
QTY
NO
EMT
EM
FF
HP
GND
FT
IMC
HVAC
MIN.
MLO
NEC
NECA
MCB
MECH.
MTD
NIGHT LIGHT
SINGLE POLE
SPECIFICATION
SOLID NEUTRAL
PHASE
RIGID STEEL CONDUIT
EQUIPMENT
EMERGENCY
ELECTRICAL METALLIC TUBING
GROUND
FINISHED FLOOR
NATIONAL ELECTRICAL CODE
AFF
C/B
COMM
CAB
AF
CAT
CKT
CLG
CU
AFG
AWG
EA
DISC
ELEV
CIRCUIT
COPPER
CEILING
CONDUIT
EACH
BLDG BUILDING
FLEXIBLE METALLIC CONDUIT (STEEL)FLEX
FLUORESCENTFLUOR
DOWNDN
SWSWITCH
SWBDSWITCHBOARD
TELETELEPHONE
T-STAT THERMOSTAT
UBC UNIFORM BUILDING CODE
TYP. TYPICAL
BC
POLYVINYL CHLORIDEPVC
TTB TELEPHONE TERMINAL BACKBOARD
TTC TELEPHONE TERMINAL CABINET
PV PHOTOVOLTAICPV
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
AMP SWITCH
THE FOLLOWING SCOPE OF WORK ITEMS REPRESENT A GENERAL DESCRIPTION OF THE WORK AND IS NOTINTENDED AS A COMPLETE DESCRIPTION. CONTRACTOR SHALL REFER TO THE PROJECT SPECIFICATIONS ANDDRAWINGS FOR A COMPLETE DESCRIPTION OF THE WORK REQUIRED.
1. PROVIDE DEMOLITION OF ALL ELECTRICAL WIRING FOR COOLING TOWER FANS, PUMPS AND ASSOCIATEDEQUIPMENT COMPLETE.
2. PROVIDE POWER FOR NEW COOLING TOWER FANS, PUMPS AND ASSOCIATED EQUIPMENT.
3. PROVIDE 120V POWER FOR ALL CONTROLS. VERIFY REQUIREMENTS WITH CONTROL CONTRACTOR.
4. PROVIDE CONDUIT AND WIRING FOR TOWER VIBRATION SWITCHES HEATER AND CONTROLS AS NEEDED.
SHEET INDEX
SYMBOL
SHEET DESCRIPTIONSHEET NO
08-11-15 P
ER
MIT
IS
SU
E
LEGEND, INDEX, NOTES, SCHEDULES, CONTROLSE0-0
OVERALL FLOOR PLANSE1-0
PARTIAL DEMO ROOF PLANE2-1
PARTIAL ROOF PLANE2-2
FLOW DIAGRAME3-0
C
1. CONTRACTOR SHALL VISIT THE BUILDING SITE, TAKE HIS OWN MEASUREMENTS AND OBTAIN SUCH OTHERINFORMATION AS MAY BE NECESSARY FOR HIS WORK. NO ALLOWANCES WILL SUBSEQUENTLY BE MADE FORANY ERROR OR OMISSION ON THE PART OF THE CONTRACTOR IN THIS REGARD.
2. FURNISH ALL MATERIALS AND TEMPORARY LIGHTS AND WIRING REQUIRED DURING CONSTRUCTION OF THEPROHECT FOR ALL TRADES THAT REQUIRE POWER. COMPLY WITH OSHA AND NEC REQUIREMENTS.
3. DO NOT SCALE DRAWINGS. FIELD VERIFY EXACT EQUIPMENT LOCATIONS PRIOR TO BEGINNING WORK.
4. IN THE EVENT OF CONFLICTS BETWEEN THE DRAWINGS AND THE SPECIFICATIONS, CONTRACTOR SHALL BIDTHE BETTER QUALITY OR GREATER QUANTITY.
5. CONTRACTOR SHALL REFER TO THE PROJECT MANUAL, ARCHITECTURAL, MECHANICAL AND STRUCTURALDRAWINGS FOR ADDITIONAL INFORMATION AND REQUIREMENTS FOR THE PROJECT.
6. FINAL CONNECTIONS TO ALL EQUIPMENT SHALL BE PER MANUFACTURER'S APPROVED WIRING DIAGRAMS,DETAILS AND INSTRUCTIONS. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO VERIFY REQUIREMENTS ANDPROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH THE ACTUAL EQUIPMENT SUPPLIED.
ELECTRICAL SCOPE OF WORK
ELECTRICAL GENERAL NOTES
P:\
2015_Jo
bs\
15020 L
ewis
Buil
din
g C
ooli
ng T
ow
er a
nd B
oil
er R
epla
cem
ent\
DW
G_B
LD
G D
EP
T\1
5020 E
0-0
.dw
g, 12/1
/2015 9
:00:0
5 A
M, A
lec
Dil
lard
FEDCBA
4
3.6
3.4
1.6
1.4
1
2.5
1
2
3
4
2
3
UP
(702) 455-6731
Las V
egas, N
evada
500 S
. G
RA
ND
C
EN
TR
AL P
AR
KW
AY
DE
PA
RT
ME
NT
O
F R
EA
L P
RO
PE
RT
Y M
AN
AG
EM
EN
T
CLA
RK
C
OU
NT
Y
AC
QU
IS
IT
IO
N, D
ES
IG
N, &
C
ON
ST
RU
CT
IO
N D
IV
IS
IO
N
TH
E LE
WIS
P
RO
FE
SS
IO
NA
L B
LD
G.
DA
TE
: N
OV
EM
BE
R 1
9, 2
01
5
ME
CH
AN
IC
AL U
PG
RA
DE
330 S
. 3R
D S
TR
EE
T, LA
S V
EG
AS
, N
V 89101
1502
0
A ROOF PLAN E1-0
NO
RT
H
KEY NOTES
1. FOR DEMOLITION PLAN - REFER TO A - (E2.1).
2. FOR NEW PLAN - REFER TO A - (E2.2).
P:\
2015_Jo
bs\
15020 L
ewis
Buil
din
g C
ooli
ng T
ow
er a
nd B
oil
er R
epla
cem
ent\
DW
G_B
LD
G D
EP
T\1
5020 E
1-0
.dw
g, 12/1
/2015 9
:00:0
7 A
M, A
lec
Dil
lard
(702) 455-6731
Las V
egas, N
evada
500 S
. G
RA
ND
C
EN
TR
AL P
AR
KW
AY
DE
PA
RT
ME
NT
O
F R
EA
L P
RO
PE
RT
Y M
AN
AG
EM
EN
T
CLA
RK
C
OU
NT
Y
AC
QU
IS
IT
IO
N, D
ES
IG
N, &
C
ON
ST
RU
CT
IO
N D
IV
IS
IO
N
TH
E LE
WIS
P
RO
FE
SS
IO
NA
L B
LD
G.
DA
TE
: N
OV
EM
BE
R 1
9, 2
01
5
ME
CH
AN
IC
AL U
PG
RA
DE
330 S
. 3R
D S
TR
EE
T, LA
S V
EG
AS
, N
V 89101
1502
0
A DEMO ROOF FLOOR PLAN - ELECTRICAL E2-1
NO
RT
H
GENERAL NOTES
1. REFER TO MECHANICAL PLANS FOR EXTENT OF
DEMOLITION REQUIRED. REMOVE ALL WIRING CONDUIT,
CONDUIT AND EQUIPMENT SUPPORTS, PULL BOXES,
DISCONNECT SWITCHES, CONTROLLERS, ETC. AS NEEDED
AND PREPARE FOR INSTALLATION OF NEW WIRING FOR
NEW EQUIPMENT.
KEY NOTES
1. REMOVE EXISTING BOILER. REUSE AND EXTEND EXISTING
CIRCUIT TO NEW BOILER LOCATION SHOWN ON E2-2.
2. REMOVE EXISTING PUMP AND ASSOCIATED VFD. EXTEND
EXISTING CIRCUIT TO NEW PUMP SKID LOCATION SHOWN
ON E2-2.
3. REMOVE EXISTING PUMP. EXTEND EXISTING CIRCUIT TO
NEW PUMP LOCATION SHOWN ON E2-2.
4. REMOVE EXISTING CLOSED CIRCUIT COOLING TOWER, VFD
AND PUMP. RECONNECT CIRCUITS TO NEW CCCT, VFD AND
PUMP SHOWN ON E2-2.
5. REMOVE EXISTING 'EMCS' PANEL AND EXTEND EXISTING
CIRCUIT L11A-29 TO NEW 'EMCS' PANEL LOCATION ON E2-2.
6. REMOVE EXISTING SUMP HEATER CONNECTION.
RECONNECTION TO NEW SHOWN ON E2-2.
UP
P:\
2015_Jo
bs\
15020 L
ewis
Buil
din
g C
ooli
ng T
ow
er a
nd B
oil
er R
epla
cem
ent\
DW
G_B
LD
G D
EP
T\1
5020 E
2-1
.dw
g, 12/1
/2015 9
:00:0
9 A
M, A
lec
Dil
lard
(702) 455-6731
Las V
egas, N
evada
500 S
. G
RA
ND
C
EN
TR
AL P
AR
KW
AY
DE
PA
RT
ME
NT
O
F R
EA
L P
RO
PE
RT
Y M
AN
AG
EM
EN
T
CLA
RK
C
OU
NT
Y
AC
QU
IS
IT
IO
N, D
ES
IG
N, &
C
ON
ST
RU
CT
IO
N D
IV
IS
IO
N
TH
E LE
WIS
P
RO
FE
SS
IO
NA
L B
LD
G.
DA
TE
: N
OV
EM
BE
R 1
9, 2
01
5
ME
CH
AN
IC
AL U
PG
RA
DE
330 S
. 3R
D S
TR
EE
T, LA
S V
EG
AS
, N
V 89101
1502
0
1 EXISTING SINGLE LINE DIAGRAM
KEY NOTES
GENERAL NOTES
E3-0
1. DISCONNECT AND REMOVE EXISTING VFD. PROVIDE
CONNECTION TO NEW VFD'S ON SKID. PROVIDE NEW
CONDUIT/WIRE TO NEW LOCATION.
2. DISCONNECT AND REMOVE EXISTING VFD. PROVIDE
RECONNECTION TO NEW VFD. PROVIDE NEW
CONDUIT/WIRE TO NEW CCCT-1 LOCATION. PROVIDE NEW
NEMA 3R DISCONNECT.
3. RELOCATE EXISTING PUMP CONNECTION. EXTEND
CONDUIT/WIRE. PROVIDE NEW DISCONNECT.
4. MODIFY EXISTING BUS TO ACCEPT NEW FUSED
DISCONNECT.
1. ALL EQUIPMENT REPLACED WITH SAME HP. NO LOAD
CHANGES.
2. ALL EQUIPMENT THAT IS EXISTING IS SHOWN LIGHT.
P:\
2015_Jo
bs\
15020 L
ewis
Buil
din
g C
ooli
ng T
ow
er a
nd B
oil
er R
epla
cem
ent\
DW
G_B
LD
G D
EP
T\1
5020 E
3-0
.dw
g, 12/1
/2015 9
:00:1
0 A
M, A
lec
Dil
lard