Block Wall Systems to Meet BCA Deemed- To-Satisfy Energy Efficiency Provisions
BCA 2010
2 adbri masonry
The energy efficiency wall systems shown in this brochure only cover Adbri Masonry walls utilising added insulating products to achieve the requirements of the 2010 Building Code of Australia (BCA) Volumes 1 and 2. It should be noted the BCA details many other alternative Deemed-To-Satisfy options to achieve the required energy efficiency including walls with a surface density of not less than 220kg/m2. Note many Adbri Masonry products achieve a 220kg/m2 surface density. Please contact your Adbri Masonry representative for details.
Adbri Masonry acknowledges the Concrete Masonry Association of Australia’s (CMAA) ‘Design of Concrete Masonry Building’s Manual’ in the development of some of the wall systems.
Adbri Masonry also acknowledges CSR Gyprock®, CSR Bradford® and Rmax for providing technical information on their respective products.
As of May 2010, the BCA has amended legislation regarding energy efficiency of new buildings in Australia. This brochure is intended as a guide for the design of walls to achieve BCA Deemed-to-satisfy compliance in energy efficiency using Adbri Masonry products.
The wall systems in this brochure are specific to Adbri Masonry products and do not apply to products of other manufacturers
2 adbri masonry
Preface
Introduction
adbri masonry 33adbri masonry
Preface 2
Introduction 2
1.0 BCA Requirements 4
2.0 Design of Adbri Masonry block walls for energy efficiency
2.1 Step 1: Establish requirements 5
2.2 Step 2: Selecting your Adbri Masonry wall system 5
3.0 General design/construction considerations 5
Glossary 12-13
Appendix 1 – Australian Climate Zones 14-15
List of Tables
Table 1 - External Wall Minimum Total ‘R’ Values Required 4 Table 2 - Adbri Masonry Wall Systems (Specifications) 6-7 Table 3 - Detailed Specifications for T1 and T2 8-9 Table 4 - Detailed Specifications for T3 and T4 10-11
Contents
4 adbri masonry
All wall systems are based on the Deemed-To-Satisfy (DTS) provisions of the Building Code of Australia (BCA) Volume 1 Part J and Volume 2 Part 3.12. These walls are considered to be acceptable forms of construction.
The DTS walls consider the individual thermal resistances of the wall components, which in total must meet the BCA requirement.
The BCA requirements for external walls are summarised in Table 1. Reference should be made to the BCA 2010 for detailed information about different options available to achieve required energy efficiency for each climate zone and concessions including walls with surface density of not less than 220kg/m2.
To determine the relevant climate zone, use the map provided in Appendix 1.
Notes Volume One
1. A sole occupancy unit of a Class 2 building or a Class 4 part of a building must achieve 6 star minimum rating.
2. For Class 2 buildings in Queensland BCA 2009 Volume One still applies.
3. For all Building Classes in Tasmania BCA 2009 Volume One still applies.
4. For Class 2 and Class 4 Buildings in New South Wales subject to BASIX energy provisions of BCA 2009 as varied by the New South Wales appendix in the BCA apply.
Table 1 - External Wall Minimum Total ‘R’ Values Required
1.0 BCA Energy Efficiency Requirements for Walls
2.0 Design of Adbri Masonry block walls for Deemed-to-satisfy energy efficiency
Climate Zone BCA 2010 Volume One Building Classes 24 to 9 Climate Zone BCA Volume Two Building Classes 1 to 10
Total mimimum ‘R’ Value1,2 Options Total mimimum ‘R’ Value1,2 Options
1,2,3
(i) 3.3 (A) BCA Table 3.12.1, 3(a) Options
(ii) 2.8 if wall density is not less than 220kg/m2 1,2,3,4,5 (i) 2.8
(iii) 1.4 in QLD only 2 (ii) 2.4 if wall shaded with 15° projection (refer BCA Fig 3.12.1.2)
4,5,6
(i) 2.8 6,7 (i) 2.8
(ii) 2.3 if wall surface density is not less than 220kg/m2 8 (i) 3.8
(iii) 1.4 or achieve surface density not less than 220kg/m2 in QLD only 2 OR
7(i) 2.8
(B) BCA Table 3.12.1, 3(b) options for external walls with a surface density not less than 220kg/m2
(ii) 1.9 or 220kg/m2 + R1.0 TAS only
1,2,3,4,5,6,7,8
Please refer to table 3.12.1, 3(b) options. These options are too detailed to include in this brochure and include options for masonry internal walls, shading, concrete stat-in-ground glazing, etc.8
(i) 3.8
(ii) 2.8 TAS only 3
These wall systems are generally used in external wall applications in residential, commercial, industrial, institutional, domestic and high-rise domestic construction or in the renovation of older buildings. Walls systems incorporate single leaf concrete masonry, and where required CSR Bradford® insulation products and CSR Gyprock® Products, or Rmax ExinTEX® polystyrene products.
adbri masonry 5
3.0 General design/construction considerations
2.1 Step 1: Establish requirements
2.1.1 Determine applicable climate zone from the BCA climate zone map detailed in Appendix 1.
2.1.2 Using table 1 and the relevant climate zone, select the minimum total R-value required for the relevant climate zone and building class. Note: Walls detailed in this brochure only meet BCA Option (a) for each climate zone. Refer to the BCA for other option details including the 220kg/m2 surface density and slab on ground options.
2.2 Step 2: Selecting your Adbri Masonry wall system
2.2.1 Using the required minimum total R-value from the relevant climate zone from table 1, select a suitable Adbri Masonry wall system from table 2. This table categorises the requirements of the BCA and details Adbri Masonry wall systems which meet these requirements. Note: There are several Adbri Masonry wall systems available to meet each individual BCA minimum total R-value requirement, listed as wall type T1, T2, T3 or T4. More than one wall system can be selected to allow for direct comparison between wall systems. Choose a system that is most appropriate to your application.
2.2.2 The following information is shown in Table 2 for each wall type
- Typical layout of the wall system - BCA Requirement being met - Building class - Applicable climate zones - Adbri Masonry Block type/series - Basic wall details - Overall wall thickness - Further information (if applicable)
NOTE: For all wall types i.e. T1, T2, T3, and T4, further information is required to determine the actual wall specifications. These systems include various CSR Bradford® insulation products, CSR Gyprock® products and Rmax exinTEX® polystyrene products as detailed in Step 2.2.3.
2.2.3 For wall types T1 or T2, Table 3 must be used. For wall types T3 or T4, Table 4 must be used.
These tables give the following details of the wall system specifications.
- Building class - Applicable climate zone - External wall lining - Block series - Sarking - Insulation and frame - Internal wall lining - Total R-value of wall - Minimum wall thickness - Additional wall thickness (for thicker block series)
• Gyprock® may be directly applied to the masonry substrate, screw fixed to metal furring channels that are fixed to the masonry, or alternatively fixed to a separate stud frame.
• Refer to manufacturer for all related loading bearing and non-load bearing stud design information.
• Rmax ExinTEX® polystyrene can be fixed direct to the external masonry face.
• All block wall elements are to be designed in accordance with AS3700 Masonry Structures.
• Some walling systems incorporate an insulated cavity to provide improved thermal performance. The provision of a cavity also allows the inclusion of services such as water pipes.
• No allowance is made for thermal bridging of cavity ties or furring channels.
• For fire and sound properties refer to the Adbri Masonry Fire and Sound Insulation of Concrete Besser block masonry brochure.
6 adbri masonry
Wall Type T1 T2 T3 T4
Typical Layout
BCA Requirement being met Total R-Value 1.9/2.8/3.8 Total R-Value 1.9 Total R-Value 2.8/3.8 Total R-Value 2.5/3.5
Building Class Applicable Climate Zones Applicable Climate Zones Applicable Climate Zones Applicable Climate Zones
BCA 2010 Volume One Class 1 to 9 buildings, refer to notes 1, 2, 3 below
All, but will depend on which Adbri Masonry wall version is used, e.g. V1, V2 or V3. Refer to Table 3
1, 2, 3, 5, 6 QLD only for class 2 buildings only2
7 Tas only 3All, but will depend on which Adbri Masonry wall version is used, e.g. V1 or V2. Refer to Table 4
All, except in climate zone B in NSW and VIC and which Adbri Masonry wall version is used eg V1 or V2 refer to Table 4
BCA 2010 Volume TwoClass 1 and 10 Buildingsrefer to notes 4, 5, 6 below
All, but will depend on which Adbri Masonry wall version is used, e.g. V1, V2 or V3. Refer to Table 3 2,5 NSW only4 All, but will depend on which Adbri Masonry wall version is used, e.g. V1 or V2.
Refer to Table 4All, but will depend on which Adbri Masonry wall version is used, e.g. V1 or V2. Refer to Table 4
Adbri Masonry Block Type/Series 150 series200 series
150 series200 series
150 series200 series
QuickbrickTwinbrick100 series120 series
Basic Wall DetailsRmax Exintex polystyrene insulation direct fixed to the external face, Gyprock® direct fixed to the internal face
Stud one side direct fixed, Gyprock® lined internal side, with Glasswool / Rockwool / Polystyrene insulation in cavity
Stud one side 20mm off masonry, Gyprock® lined internal side, Glasswool / Rockwool insulation in cavity
Stud one side 20mm off masonry. Gyprock® lined internal side, Glasswool / Rockwool insulation in cavity
Overall Wall Thickness Varies 228mm - 308mm depending on block series 234mm Varies 247mm - 273mm depending on block series Varies 197mm - 223mm depending on block series
Further Information Table 3 Table 3 Table 4 Table 4
Table 2 - Adbri Masonry Wall System Specifications
Notes Volume One
1. For sole occupancy unit of a Class 2 building or a Class 4 part of a building must achieve 6 stars minimum rating. 2. For Class 2 building in Queensland energy provisions of BCA 2009 Volume One still apply. Note also some 220kg/m2 surface density options
apply, refer to BCA 2010.3. For Tasmania BCA 2009 Volume One energy provisions still applies to all building classes. Note also some 220kg/m2 surface density options
apply, refer to BCA 2010.
adbri masonry 7
Wall Type T1 T2 T3 T4
Typical Layout
BCA Requirement being met Total R-Value 1.9/2.8/3.8 Total R-Value 1.9 Total R-Value 2.8/3.8 Total R-Value 2.5/3.5
Building Class Applicable Climate Zones Applicable Climate Zones Applicable Climate Zones Applicable Climate Zones
BCA 2010 Volume One Class 1 to 9 buildings, refer to notes 1, 2, 3 below
All, but will depend on which Adbri Masonry wall version is used, e.g. V1, V2 or V3. Refer to Table 3
1, 2, 3, 5, 6 QLD only for class 2 buildings only2
7 Tas only 3All, but will depend on which Adbri Masonry wall version is used, e.g. V1 or V2. Refer to Table 4
All, except in climate zone B in NSW and VIC and which Adbri Masonry wall version is used eg V1 or V2 refer to Table 4
BCA 2010 Volume TwoClass 1 and 10 Buildingsrefer to notes 4, 5, 6 below
All, but will depend on which Adbri Masonry wall version is used, e.g. V1, V2 or V3. Refer to Table 3 2,5 NSW only4 All, but will depend on which Adbri Masonry wall version is used, e.g. V1 or V2.
Refer to Table 4All, but will depend on which Adbri Masonry wall version is used, e.g. V1 or V2. Refer to Table 4
Adbri Masonry Block Type/Series 150 series200 series
150 series200 series
150 series200 series
QuickbrickTwinbrick100 series120 series
Basic Wall DetailsRmax Exintex polystyrene insulation direct fixed to the external face, Gyprock® direct fixed to the internal face
Stud one side direct fixed, Gyprock® lined internal side, with Glasswool / Rockwool / Polystyrene insulation in cavity
Stud one side 20mm off masonry, Gyprock® lined internal side, Glasswool / Rockwool insulation in cavity
Stud one side 20mm off masonry. Gyprock® lined internal side, Glasswool / Rockwool insulation in cavity
Overall Wall Thickness Varies 228mm - 308mm depending on block series 234mm Varies 247mm - 273mm depending on block series Varies 197mm - 223mm depending on block series
Further Information Table 3 Table 3 Table 4 Table 4
Notes Volume Two
4. For New South Wales Class 1 and 10 building subject to BASIX, BCA 2009 energy provisions apply. 5. For Tasmania BCA 2009 Volume Two energy provisions still apply to Class 1 and 10 buildings. 6. For Victoria BCA 2009 Volume Two energy provisions still apply to CLass 1 and 10 buildings ie Zone 4 R2.2. 7. Refer to BCA 2010 Table 3.12.1.3b for options for each part of an external wall with a surface density of not less than 220kg/m3.
20mm minimum cavity to stud
20mm minimum cavity to stud
8 adbri masonry
Climate Zone Notes1. All zones but will depend on which Adbri Masonry wall version is used e.g. V1, V2 or V3. Refer Table 2.
2. Zones 1, 2, 3, 5 and 6 QLD only for Class 2 buildings only. Also Zone 7 TAS only. Refer Table 2.
3. Zones 2 and 5 NSW only. Refer to Table 2.
Table 3 - Detailed Specifications for T1 & T2
Typical Layout
Wal
l Typ
e
Building Class Applicable Climate Zones
Wall ComponentsTotal R-Value1 of
wall (m2K/W)Min. Wall
Thickness2 (mm)Additional
Thickness (mm)1External Wall Lining3
2Block
3Sarking
4 and 5Insulation and Frame
6Internal Wall Lining
Vers
ion
1
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2Volume Two Building Class 1 and 10, refer to notes bottom of Table 2
See Note 1 below
See Note 1 below
Render, Texturecoat orEquivalent
Render, Texturecoat orEquivalent
150mm series or200mm series
150mm series or200mm series
None
None
Rmax Exintex Polystryene 60mm thick
Rmax Exintex Polystryene 60mm thick
Min. 10mm Gyprock®
Min. 10mm Gyprock®
1.9
1.9
228
228
+ 50mm for 200mm series if not using 150mm series
+ 50mm for 200mm series if not using 150mm series
Vers
ion
2
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2Volume Two Building Class 1 and 10, refer to notes bottom of Table 2
See Note 1 below
See Note 1 below
Render, Texturecoat orEquivalent
Render, Texturecoat orEquivalent
150mm series or 200mm series
150mm series or 200mm series
None
None
Rmax Exintex Polystryene 94mm thick
Rmax Exintex Polystryene 94mm thick
Min. 10mm Gyprock®
Min. 10mm Gyprock®
2.8
2.8
262
262
+ 50mm for 200mm series if not using 150mm series
+ 50mm for 200mm series if not using 150mm series
Vers
ion
3
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2Volume Two Building Class 1 and 10, refer to notes bottom of Table 2
See Note 1 below
See Note 1 below
Render, Texturecoat orEquivalent
Render, Texturecoat orEquivalent
150mm series or 200mm series
150mm series or 200mm series
None
None
Rmax Exintex Polystryene 132mm thick
Rmax Exintex Polystryene 132mm thick
Min. 10mm Gyprock®
Min. 10mm Gyprock®
3.8
3.8
300
300
+ 50mm for 200mm series if not using 150mm series
+ 50mm for 200mm series if not using 150mm series
Vers
ion
1
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2
Volume Two Building Class 1 and 10, refer to notes bottom of Table 2
See Note 2 below
See Note 3 below
Render, Texturecoat orEquivalent
Render, Texturecoat orEquivalent
150mm series or200mm series
150mm series or200mm series
None
None
For Steel Studs 51mm min. use• CSR Bradford Glasswool Partition Batts
75mm (R1.5) or• CSR R1.6 Bradford Rockwool Soundscreen
Partition Batts 64mmFor Timber Studs 51mm min. use• CSR R1.5 Bradford Glasswool Wall Batts
75mm or• CSR R1.6 Bradford Rockwool Soundscreen
Wall Batts 64mm
For Steel Studs 51mm min. use• CSR Bradford Glasswool Partition Batts
75mm (R1.5) or• CSR R1.6 Bradford Rockwool Soundscreen
Partition Batts 64mmFor Timber Studs 51mm min. use• CSR R1.5 Bradford Glasswool Wall Batts
75mm or• CSR R1.6 Bradford Rockwool Soundscreen
Wall Batts 64mm
Min. 10mm Gyprock®
Min. 10mm Gyprock®
1.9
1.9
234
234
+ 50mm for 200mm series if not using 150mm series
+ 50mm for 200mm series if not using 150mm series
T1
T2
Additional notes• 150 and 200 series block only• Exterior wall linings applied strictly in accordance
with manufactures guidelines• Polystyrene attached with adhesive supplied
by Sika or equivalent in accordance with manufacturer guidelines
• Single leaf masonry wall• Min. 10mm Gyprock® direct fixed to masonry using
‘CSR Gyprock Masonry Adhesive’
Additional notes• 150 and 200 series block only• Exterior wall linings applied strictly in accordance
with manufactures guidelines• Single leaf masonry wall• Min. 51mm steel/timber stud, 20mm min. off masonry
fixed with ties• Insulation in furring channel cavity, as per table• Min. 10mm Gyprock® fixed to studs
adbri masonry 9
General Notes1. All listed Total R-values are inclusive of 0.15m2K/W to account for thermal effect of inside and outside airfilms.
2. The minimum wall thickness is based on using the thinnest available block.
3. External wall linings are based on a 13mm thickness.
Typical Layout
Wal
l Typ
e
Building Class Applicable Climate Zones
Wall ComponentsTotal R-Value1 of
wall (m2K/W)Min. Wall
Thickness2 (mm)Additional
Thickness (mm)1External Wall Lining3
2Block
3Sarking
4 and 5Insulation and Frame
6Internal Wall Lining
Vers
ion
1
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2Volume Two Building Class 1 and 10, refer to notes bottom of Table 2
See Note 1 below
See Note 1 below
Render, Texturecoat orEquivalent
Render, Texturecoat orEquivalent
150mm series or200mm series
150mm series or200mm series
None
None
Rmax Exintex Polystryene 60mm thick
Rmax Exintex Polystryene 60mm thick
Min. 10mm Gyprock®
Min. 10mm Gyprock®
1.9
1.9
228
228
+ 50mm for 200mm series if not using 150mm series
+ 50mm for 200mm series if not using 150mm series
Vers
ion
2
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2Volume Two Building Class 1 and 10, refer to notes bottom of Table 2
See Note 1 below
See Note 1 below
Render, Texturecoat orEquivalent
Render, Texturecoat orEquivalent
150mm series or 200mm series
150mm series or 200mm series
None
None
Rmax Exintex Polystryene 94mm thick
Rmax Exintex Polystryene 94mm thick
Min. 10mm Gyprock®
Min. 10mm Gyprock®
2.8
2.8
262
262
+ 50mm for 200mm series if not using 150mm series
+ 50mm for 200mm series if not using 150mm series
Vers
ion
3
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2Volume Two Building Class 1 and 10, refer to notes bottom of Table 2
See Note 1 below
See Note 1 below
Render, Texturecoat orEquivalent
Render, Texturecoat orEquivalent
150mm series or 200mm series
150mm series or 200mm series
None
None
Rmax Exintex Polystryene 132mm thick
Rmax Exintex Polystryene 132mm thick
Min. 10mm Gyprock®
Min. 10mm Gyprock®
3.8
3.8
300
300
+ 50mm for 200mm series if not using 150mm series
+ 50mm for 200mm series if not using 150mm series
Vers
ion
1
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2
Volume Two Building Class 1 and 10, refer to notes bottom of Table 2
See Note 2 below
See Note 3 below
Render, Texturecoat orEquivalent
Render, Texturecoat orEquivalent
150mm series or200mm series
150mm series or200mm series
None
None
For Steel Studs 51mm min. use• CSR Bradford Glasswool Partition Batts
75mm (R1.5) or• CSR R1.6 Bradford Rockwool Soundscreen
Partition Batts 64mmFor Timber Studs 51mm min. use• CSR R1.5 Bradford Glasswool Wall Batts
75mm or• CSR R1.6 Bradford Rockwool Soundscreen
Wall Batts 64mm
For Steel Studs 51mm min. use• CSR Bradford Glasswool Partition Batts
75mm (R1.5) or• CSR R1.6 Bradford Rockwool Soundscreen
Partition Batts 64mmFor Timber Studs 51mm min. use• CSR R1.5 Bradford Glasswool Wall Batts
75mm or• CSR R1.6 Bradford Rockwool Soundscreen
Wall Batts 64mm
Min. 10mm Gyprock®
Min. 10mm Gyprock®
1.9
1.9
234
234
+ 50mm for 200mm series if not using 150mm series
+ 50mm for 200mm series if not using 150mm series
10 adbri masonry
Climate Zone notes1. All zones, but will depend on which Adbri Masonry wall version is used e.g. V1 or V2. Refer to Table 2.
2. All zones, except in zone 8 in NSW and VIC and which Adbri Masonry wall version is used e.g. V1 or V2. Refer to Table 2.
3. All zones, but will depend on which Adbri Masonry wall version is used e.g. V1 or V2. Refer to Table 4.
Typical Layout
Wal
l Typ
e
Building Class Applicable Climate Zones
Wall ComponentsTotal R-Value1
of wall (m2K/W)
Min. Wall Thickness2
(mm)
Additional Thickness (mm)1
External Wall Lining32
Block3
Sarking4 and 5
Insulation and Frame6
Internal Wall Lining
Vers
ion
1
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2
Volume Two Building Class 1 and 10, refer to notes 4, 5, 6 bottom of Table 2
See note 1 below
See note 1 below
Render, Texturecoat or Equivalent
Render, Texturecoat or Equivalent
150mm series or200mm series
150mm series or200mm series
CSR Enviroseal Wall Wrap, airspace >20mm
CSR Enviroseal Wall Wrap, airspace >20mm
For Steel Studs 51mm min. use• CSR Bradford Glasswool Partition Batts
75mm (R1.5) or• CSR R1.6 Bradford Rockwool Soundscreen
Partition Batts 64mm
For Timber Studs 51mm min. use• CSR R1.5 Bradford Glasswool Wall Batts
75mm or• CSR R1.6 Bradford Rockwool Soundscreen
Wall Batts 64mm
Min. 10mm Gyprock®
Min. 10mm Gyprock®
2.8
2.8
247
247
+ 50mm for 200mm series if not using 150mm series
+ 50mm for 200mm series if not using 150mm series
Vers
ion
2
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2
Volume Two Building Class 1 and 10, refer to notes bottom of Table 2
See note 1 below
See note 1 below
Render, Texturecoat or Equivalent
Render, Texturecoat or Equivalent
150mm series or 200mm series
150mm series or 200mm series
CSR Enviroseal Wall Wrap, airspace >20mm
CSR Enviroseal Wall Wrap, airspace >20mm
Timber Studs only 90mm min. use CSR R2.5 Bradford Rockwool Soundscreen Wall Batt 88mm
Timber Studs only 90mm min. use CSR R2.5 Bradford Rockwool Soundscreen Wall Batt 88mm
Min. 10mm Gyprock®
Min. 10mm Gyprock®
3.8
3.8
273
273
+ 50mm for 200mm series if not using 150mm series
+ 50mm for 200mm series if not using 150mm series
Vers
ion
1
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2
Volume Two Building Class 1 and 10, refer to notes bottom of Table 2
See note 2 below
See note 2 below
Render, Texturecoat or Equivalent
Render, Texturecoat or Equivalent
Quickbrick, Twinbrick, 100mm series or 120mm series
Quickbrick, Twinbrick, 100mm series or 120mm series
CSR Enviroseal Wall Wrap, airspace >20mm
CSR Enviroseal Wall Wrap, airspace >20mm
For Steel Studs 51mm min. use• CSR Bradford Glasswool Partition Batts
75mm (R1.5) or• CSR R1.6 Bradford Rockwool Soundscreen
Partition Batts 64mm
For Timber Studs 51mm min. use• CSR R1.5 Bradford Glasswool Wall Batts
75mm or• CSR R1.6 Bradford Rockwool Soundscreen
Wall Batts 64mm
Min. 10mm Gyprock®
Min. 10mm Gyprock®
2.5
2.5
197
197
+ 20mm for Quickbrick, Twinbrick or 120mm series if not using 120mm series
+ 20mm for Quickbrick, Twinbrick or 120mm series if not using 120mm series
Vers
ion
2
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2
Volume Two Building Class 1 and 10, refer to notes bottom of Table 2
See note 3 below
See note 3 below
Render, Texturecoat or Equivalent
Render, Texturecoat or Equivalent
Quickbrick, Twinbrick, 100mm series or 120mm series
Quickbrick, Twinbrick, 100mm series or 120mm series
CSR Enviroseal Wall Wrap, airspace >20mm
CSR Enviroseal Wall Wrap, airspace >20mm
Timber Studs only 90mm min. use CSR R2.5 Bradford Rockwool Soundscreen Wall Batt 88mm
Timber Studs only 90mm min. use CSR R2.5 Bradford Rockwool Soundscreen Wall Batt 88mm
Min. 10mm Gyprock®
Min. 10mm Gyprock®
3.5
3.5
223
223
+ 20mm for Quickbrick, Twinbrick or 120mm series if not using 120mm series
+ 20mm for Quickbrick, Twinbrick or 120mm series if not using 120mm series
Table 4 - Detailed Specifications for T3 & T4
T3 20mm minimum cavity to stud
T4 20mm minimum cavity to stud
Additional notes:• 100, 120, Quickbrick, Twinbrick series block only• Exterior wall linings applied strictly in accordance
with manufactures guidelines• Concrete masonry veneer• Min. 64mm steel/timber stud framing at 600mm max.
centres, 20mm min. cavity between stud and wall• Insulation in stud cavity, as per table• Min. 10mm Gyprock® fixed to studs
Additional notes:• 150 and 200 series block only• Exterior wall linings applied strictly in accordance
with manufactures guidelines• Single leaf masonry wall• Min. 64mm steel/timber stud framing at 600mm max.
centres, 20mm min. cavity between stud and wall• Insulation in stud cavity, as per table• Min. 10mm Gyprock® fixed to studs
adbri masonry 11
General notes1. All listed Total R-values are inclusive of 0.15m2K/W to account for thermal effect of inside and outside airfilms.
2. The minimum wall thickness is based on using the thinnest available block.
3. External wall linings are based on a 13mm thickness.
Typical Layout
Wal
l Typ
e
Building Class Applicable Climate Zones
Wall ComponentsTotal R-Value1
of wall (m2K/W)
Min. Wall Thickness2
(mm)
Additional Thickness (mm)1
External Wall Lining32
Block3
Sarking4 and 5
Insulation and Frame6
Internal Wall Lining
Vers
ion
1
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2
Volume Two Building Class 1 and 10, refer to notes 4, 5, 6 bottom of Table 2
See note 1 below
See note 1 below
Render, Texturecoat or Equivalent
Render, Texturecoat or Equivalent
150mm series or200mm series
150mm series or200mm series
CSR Enviroseal Wall Wrap, airspace >20mm
CSR Enviroseal Wall Wrap, airspace >20mm
For Steel Studs 51mm min. use• CSR Bradford Glasswool Partition Batts
75mm (R1.5) or• CSR R1.6 Bradford Rockwool Soundscreen
Partition Batts 64mm
For Timber Studs 51mm min. use• CSR R1.5 Bradford Glasswool Wall Batts
75mm or• CSR R1.6 Bradford Rockwool Soundscreen
Wall Batts 64mm
Min. 10mm Gyprock®
Min. 10mm Gyprock®
2.8
2.8
247
247
+ 50mm for 200mm series if not using 150mm series
+ 50mm for 200mm series if not using 150mm series
Vers
ion
2
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2
Volume Two Building Class 1 and 10, refer to notes bottom of Table 2
See note 1 below
See note 1 below
Render, Texturecoat or Equivalent
Render, Texturecoat or Equivalent
150mm series or 200mm series
150mm series or 200mm series
CSR Enviroseal Wall Wrap, airspace >20mm
CSR Enviroseal Wall Wrap, airspace >20mm
Timber Studs only 90mm min. use CSR R2.5 Bradford Rockwool Soundscreen Wall Batt 88mm
Timber Studs only 90mm min. use CSR R2.5 Bradford Rockwool Soundscreen Wall Batt 88mm
Min. 10mm Gyprock®
Min. 10mm Gyprock®
3.8
3.8
273
273
+ 50mm for 200mm series if not using 150mm series
+ 50mm for 200mm series if not using 150mm series
Vers
ion
1
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2
Volume Two Building Class 1 and 10, refer to notes bottom of Table 2
See note 2 below
See note 2 below
Render, Texturecoat or Equivalent
Render, Texturecoat or Equivalent
Quickbrick, Twinbrick, 100mm series or 120mm series
Quickbrick, Twinbrick, 100mm series or 120mm series
CSR Enviroseal Wall Wrap, airspace >20mm
CSR Enviroseal Wall Wrap, airspace >20mm
For Steel Studs 51mm min. use• CSR Bradford Glasswool Partition Batts
75mm (R1.5) or• CSR R1.6 Bradford Rockwool Soundscreen
Partition Batts 64mm
For Timber Studs 51mm min. use• CSR R1.5 Bradford Glasswool Wall Batts
75mm or• CSR R1.6 Bradford Rockwool Soundscreen
Wall Batts 64mm
Min. 10mm Gyprock®
Min. 10mm Gyprock®
2.5
2.5
197
197
+ 20mm for Quickbrick, Twinbrick or 120mm series if not using 120mm series
+ 20mm for Quickbrick, Twinbrick or 120mm series if not using 120mm series
Vers
ion
2
Volume One Building Class 2 to 9, for Class 2 refer to notes bottom of Table 2
Volume Two Building Class 1 and 10, refer to notes bottom of Table 2
See note 3 below
See note 3 below
Render, Texturecoat or Equivalent
Render, Texturecoat or Equivalent
Quickbrick, Twinbrick, 100mm series or 120mm series
Quickbrick, Twinbrick, 100mm series or 120mm series
CSR Enviroseal Wall Wrap, airspace >20mm
CSR Enviroseal Wall Wrap, airspace >20mm
Timber Studs only 90mm min. use CSR R2.5 Bradford Rockwool Soundscreen Wall Batt 88mm
Timber Studs only 90mm min. use CSR R2.5 Bradford Rockwool Soundscreen Wall Batt 88mm
Min. 10mm Gyprock®
Min. 10mm Gyprock®
3.5
3.5
223
223
+ 20mm for Quickbrick, Twinbrick or 120mm series if not using 120mm series
+ 20mm for Quickbrick, Twinbrick or 120mm series if not using 120mm series
12 adbri masonry
Building Classes
Class 1
One or more buildings which in association constitute
(a) Class 1a - single dwelling house
(i) a detached house; or
(ii) one or more attached dwellings, each
being a building, separated by a fire-
resisting wall, including a row house,
terrace house, town house or villa unit; or
(b) Class 1b - boarding house, guest house, hostel
or the like with a total floor area not exceeding 300 m2 and in which not more than 12 persons
would ordinarily be resident, which is not located
above or below another dwelling or another Class
of building other than a private garage.
Class 2
A building containing 2 or more sole-occupancy units each being a separate dwelling.
Class 3
A residential building, other than a building of Class 1 or 2 which is a common place of long term or transient living for a number of unrelated persons, including
(a) a boarding house, guest house, hostel, lodging-
house or backpackers accommodation; or
(b) a residential part of an hotel or motel; or
(c) a residential part of a school; or
(d) accommodation for the aged, disabled or
children; or
(e) a residential part of a health-care building
which accommodates members of staff.
(f) a residential part of a Detention Centre for the
accommodation of the inmates of the centre.
Class 4
A dwelling in a building that is Class 5, 6, 7, 8 or 9 if it is the only dwelling in the building.
Class 5
An office building used for professional or commercial purposes, excluding buildings of Class 6, 7, 8, or 9.
Class 6
A shop or other building for the sale of goods by retail or the supply of services direct to the public, including -
(a) an eating room, cafe, restaurant, milk or soft-
drink bar; or,
(b) a dining room, bar, shop or kiosk part of a hotel
or motel; or
(c) a hairdresser’s or barber’s shop, public laundry,
or ‘undertaker’s establishment; or
(d) market or sale room, showroom, or service
station.
Class 7
A building which is -
(a) a public carpark; or
(b) for storage, or display of goods or produce for
sale by wholesale.
Class 8
A laboratory, or a building in which a handicraft or process for the production, assembling, altering, repairing, packing, finishing, or cleaning of goods or produce is carried on for trade, sale or gain.
Class 9
A building of a public nature -
(a) Class 9a - a health-care building; including
those parts of the building set aside as a
laboratory; or
(b) Class 9b - an assembly building, including
a trade workshop, laboratory or the like in
a primary or secondary school, but excluding
any other parts of the building that are of
another Class.
(c) Class 9c - an aged care building
Glossary
adbri masonry 13
Class 10
A non-habitable building or structure -
(a) Class 10a - a non-habitable building being a
private garage, carport, shed, or the like; or
(b) Class 10b - a structure being a fence, mast,
antenna, retaining or free-standing wall, swimming
pool, or the like.
Climate Zone means an area defined in Appendix 1 for specific loca-tions, having energy efficiency provisions based on a range of similar climatic characteristics.
Conditioned Space means a space within a building that is heated or cooled by the building’s domestic services, excluding a inhabitable room in which a heater with a capacity of not more than 1.2 K/W installed.
Deemed to Satisfy Provisions means provisions which are deemed to satisfy the Performance Requirements
Envelope means the parts of a building’s fabric that separate a conditioned space or habitable room from
(a) the exterior of the building, or
(b) a non-conditioned space (other than a space through which conditioned air is being exhausted such as a cleaner’s room, chemical storage room or exhaust riser) including-
(i) The floor of a rooftop plant room, lift
machine room of the like; and
(ii) The floor above a carpark or
warehouse; and
(iii) The common wall with a carpark,
warehouse or the like
External Wall means an outer wall of a building which is not a common wall.
R-Value means the thermal resistance (m2 K/W) of a component calculated by dividing its thickness by its thermal conductivity.
Reflective insulation means a building membrane with a reflective surface such as a reflective foil laminate, reflective barrier, foil batt or the like capable of reducing radiant heat flow.
Sarking-type material means a material such as a reflective foil or other flexible membrane of a type normally used for a purpose such as water proofing, vapor proofing or thermal reflectance.
Total R-Value means the sum of the R-values of the individual component layers in a composite element including any air spaces and associated surface resistances.
14 adbri masonry
Note: This map is provided by the ABCB and may be revised on an annual basis. The latest version is available from www.abcb.gov.au
Appendix 1: Australian Climate Zones
adbri masonry 15
State / Territory Location Climate Zones Location Climate Zones Location Climate zones Location Climate Zones
ACT Canberra 7
NSW Albury 4 Cobar 4 Lord Howe Island 2 Tamworth 4
Armidale 7 Coffs Harbour 2 Moree 4 Thredbo 8
Batemans Bay 6 Dubbo 4 Newcastle 5 Wagga Wagga 4
Bathurst 6 Goulburn 7 Nowra 6 Williamtown 5
Bega 6 Grafton 2 Orange 7 Wollongong 5
Bourke 4 Griffith 4 Port Maquarie 5 Yass 6
Broken Hill 4 Ivanhoe 4 Sydney East 5
Byron Bay 2 Lismore 2 Sydney West 6
NT Alice Springs 3 Elliot 3 Renner Springs 3
Darwin 1 Katherine 1 Tennant Creek 3
QLD Birdsville 3 Cunnamulla 3 Maryborough 2 Toowoomba 5
Brisbane 2 Longreach 3 Mount Isa 3 Torens Creek 3
Bundaberg 2 Gladstone 2 Normanton 1 Townsville 1
Cairns 1 Labrador 2 Rockhampton 2 Warwick 5
Cooktown 1 Mackay 2 Roma 3 Weipa 1
SA Adelaide 5 Kingscote 6 Marree 4 Port Lincoln 5
Bordertown 6 Leigh Creek 4 Mount Gambier 6 Renmark 5
Ceduna 5 Lobethal 5 Murray Bridge 6 Tarcoola 4
Cook 4 Loxton 5 Oodnadatta 4 Victor Harbour 6
Elliston 5 Naracoorte 6 Port Augusta 4 Whyalla 4
TAS Burnie 7 Flinders Island 7 Launceston 7 Rossarden 7
Bicheno 7 Hobart 7 New Norfolk 7 Smithton 7
Deloraine 7 Huonville 7 Oatlands 7 St Marys 7
Devonport 7 Kind Island 7 Orford 7 Zeehan 7
VIC Anglesea 6 Bright 7 Horsham 6 Swan Hill 4
Ararat 7 Colac 6 Melbourne 6 Traralgon 6
Bairnsdale 6 Dnadengong 6 Mildura 4 Wangaratta 4
Ballarat 7 Echuca 4 Portland 6 Warrnambool 6
Bendigo 6 Hamiliton 7 Shepparton 4
WA Albany 6 Cocos Island 1 Kalgoorlie-Boulder 4 Port Hedland 1
Balladonia 4 Derby 1 Karratha 1 Wagin 4
Broome 1 Esperance 5 Meekatharra 4 Wyndham 1
Bunbury 5 Exmouth 1 Northam 4
Carnarvon 3 Geraldton 5 Pemberton 6
Christmas Island 1 Halls Creek 3 Perth 5
Climate Zones for Various Locations
Adbri Masonry Pty Ltd
ABN: 31 009 687 521
Vers
ion
1 - 1
1500
- 11
/11/
2010
- AB
M 1
096
11/1
1