21
Biogas Treatment and Combined Heat and Power (CHP) Combined Heat and Power (CHP) John L. Willis, P.E., BCEE, Brown AND Caldwell

Biogas Treatment and Combined Heat and Power (CHP)

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Biogas Treatment and Combined Heat and Power (CHP)Combined Heat and Power (CHP)John L. Willis, P.E., BCEE, Brown AND Caldwell

Overview

• CHP Overview

• CHP Technologies

• Tools and Future Resources

CHP O i

Biogas Treatment and Combined Heat and Power (CHP)

CHP Overview

Methane from Sewage Taps Significant Potential Energy

• Much digester gas is currently flared (wasted)

B t f t t bl • Best source of wastewater renewable power production is:

COD > CH > CO + gCOD -> CH4 -> CO2 + energy

• Integral element to self-sufficient POTWs:• Strass - Austria• Point Loma - San Diego, CA• Carson JWPCP – LA County, CA

EBMUD O kl d CA• EBMUD – Oakland, CA

Payback is Improved with

• Higher power costs

Bigg l t• Bigger plants

• More gas – enhanced digestion/supplements

• Higher efficiency CHP options

• Higher GHG – REC value

Most Important:

An Enhancement with a Payback

Common, Wrong Way to Look at Biogas

The Better, CHP Way to Look at Biogas

CHP T h l i

Biogas Treatment and Combined Heat and Power (CHP)

CHP Technologies

Flow Sheet for Combustion Turbines

Joint Water Pollution Control Plant

• LACSD - Carson, CA

300 MGD• 300 MGD

• Combustion TurbineSolar Mars 90 (Three)• Solar Mars 90 (Three)

• 9 MW• 18 MW total output

• Combined Cycle• Additional 7 MW

Flow Sheet for Internal Combustion Engine

Point Loma WWTP

• San Diego, CA

160 MGD• 160 MGD

• Internal Combustion EngineEngine• Caterpillar 3612 (Two)• 2.3 MW• 4.6 MW total output

• Excess Digester Gas is Fl dFlared

Flow Sheet for Microturbine

Lancaster WRP

• LACSD - Lancaster, CA

15 MGD• 15 MGD

• MicroturbineIngersoll Rand (One)• Ingersoll-Rand (One)

• 250 kW• 190 kW total output

• Steam Boilers• Fueled by digester gas• Digester heating

Flow Sheet for Fuel Cell

Riverside WQCP

• Riverside, CA

40 MGD• 40 MGD

• Fuel CellFuelCell Energy• FuelCell Energy

• DFC 1500 MA• 300 kW/stack• 1000 kW total output

• $4.5 Million SGIP

T l d F t R

Biogas Treatment and Combined Heat and Power (CHP)

Tools and Future Resources

WERF’s LCAMER Tool

Brown and Caldwell | October 2, 2010

CHP-SET Tool Overview

Prime Mover

Efficiency Efficiency at

Various LoadsLoads

System Overview

EmissionsOverview

Ancillary Loads are Subtracted from

System Efficiency

WERF Barriers to Biogas Utilization for Renewable Energy• Future/Ongoing effort

• 4 Focus Groups:p• WEF Nutrient – Miami (Jan)• NYWEA – New York City (Feb)• WEF Biosolids – Sacramento (May)• WEF Water/Energy – Chicago (Aug)

• Participate in WERF’s “Barriers” discussion if you:• Do not have digesters but are considering themg g• Have digesters and no gas use• Have digesters and have recently implemented/

are implementing CHPare implementing CHP• Are just curious…

John L. Willis, P.E., BCEE, ,(770) 361-6431

[email protected]