RVM/UA-2 Module ATEX Flow Monitor Operation instructions Flow monitor for use in explosion-hazard zones Series RVM/UA-2 Type RVM/UA-2/02 thru RVM/ UA-2/30 with switch contact SG-15EX*********** Read this manual prior to performing any task!

Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

RVM/UA-2 Module ATEXFlow Monitor

Operation instructions

Flow monitor for usein explosion-hazard zones

Series RVM/UA-2Type RVM/UA-2/02 thru RVM/UA-2/30with switch contactSG-15EX*********** Read this manual prior to performing any task!

Page 2: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

RVM/UA-2 Modul ATEX, 2, en_US

© Meister Strömungstechnik GmbH 2019

Meister Strömungstechnik GmbH

Im Gewerbegebiet 2

63831 Wiesen

Germany

Telephone: +49 6096 9720 - 0

Fax: +49 6096 9720 - 30

E-mail: [email protected]

Internet: www.meister-flow.com

Diese Anleitung wurde erstellt von:

Meister Strömungstechnik GmbH

Technische Änderungen vorbehalten

04.05.2020RVM/UA-2 Module ATEX Flow Monitor2

Page 3: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

These instructions facilitate the safeand efficient handling of a flow monitor(referred to as "device" in the fol-lowing). The instructions are an inte-gral part of the device and must bekept within easy reach for the per-sonnel in the immediate vicinity of thedevice at all times. Personnel mustcarefully read and understand theseinstructions before commencing allwork. The basic requirement for safework is adherence to all safety andhandling instructions stipulated inthese instructions. The local accident-prevention regulations and generalsafety standards and regulations forthe field of application of the devicealso apply. Illustrations in theseinstructions are provided to aid generalunderstanding and might deviate fromthe actual model. No claims can bederived from any such differences.

Limitations of liability

All details and instructions in thismanual have been compiled underconsideration of the valid standardsand regulations, the current state-of-technology and our many years ofknowledge and experience. The manu-facturer does not accept any liabilityarising from:

n non-observance of any details inthese instructions

n improper use of the device, or usethat is not in accordance withthese instructions

n use of non-trained personnel

n unauthorized retrofitting or tech-nical changes that have not beenauthorized by the manufacturer

n use of non-approved replacementparts

The duties and obligations agreedupon in the delivery contract apply infull, as well as the general terms andconditions, the terms of delivery by themanufacturer and the valid legal regu-lations applicable at the conclusion ofthe contract.

Copyright

These operating instructions are pro-tected by copyright.

Except for internal purposes, transferof these instructions to third-parties,copying them in any way– even in part – as well as dissemina-tion and/or communication of their con-tent is forbidden without prior writtenauthorization from Meister Strömung-stechnik ("manufacturer"). Violationsare subject to claims for indemnifica-tion. The manufacturer reserves theright to assert additional claims.

Copyright is the property of the manu-facturer.

© Meister Strömungstechnik GmbH

Im Gewerbegebiet 2

63831 Wiesen

Germany

Supplemental directives

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 3

Page 4: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

Table of contents1 Overview..................................................................................................... 6

1.1 Short description.................................................................................. 61.2 Warranty and guarantee provisions..................................................... 61.3 Customer service................................................................................. 6

2 Safety.......................................................................................................... 72.1 Explanation of symbols........................................................................ 72.2 Correct use in explosion-hazard zones............................................... 82.3 Special precautions for use in explosion-hazard zones.................... 102.3.1 Precautions for use in explosion-hazard zones.............................. 112.4 Personnel requirements.................................................................... 122.5 Personal safety equipment................................................................ 132.6 Protective systems............................................................................ 13

3 Areas of employment............................................................................... 143.1 Mechanical component (flow meter without limiting contacts and

electrical accessories)....................................................................... 143.1.1 Exterior of the device...................................................................... 143.1.2 Interior of the device....................................................................... 143.1.3 General safety information for the mechanical component of the

device............................................................................................. 153.1.4 Categorization of the mechanical component of the flow monitor.. 163.1.5 List of media................................................................................... 183.1.6 Applicable documents.................................................................... 203.2 Electrical component of the device (limiting contacts)....................... 233.2.1 Applicable documents.................................................................... 23

4 Operating data.......................................................................................... 324.1 Operating data for the mechanical component of the device............ 324.2 Switch contact operating data........................................................... 324.3 Labeling of the switch contacts.......................................................... 34

5 Transport, packaging and storage......................................................... 35

6 Installation and initial startup................................................................. 366.1 Safety................................................................................................ 36

Table of contents

04.05.2020RVM/UA-2 Module ATEX Flow Monitor4

Page 5: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

6.2 Tools.................................................................................................. 366.3 Protection of the flow monitor............................................................ 366.4 Electrical connection.......................................................................... 366.5 Grounding the device........................................................................ 366.6 Contact protection measures............................................................. 36

7 Operation.................................................................................................. 38

8 Troubleshooting....................................................................................... 39

9 Maintenance............................................................................................. 409.1 Return Materials................................................................................ 409.1.1 Return Materials Authorization....................................................... 40

10 Disassembly and disposal...................................................................... 41

11 Technical data.......................................................................................... 4211.1 Dimension sheet.............................................................................. 4211.2 General specifications...................................................................... 4311.3 Replacement parts........................................................................... 45

12 Annex........................................................................................................ 48

13 Index.......................................................................................................... 49

Table of contents

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 5

Page 6: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

1 Overview1.1 Short description

Fig. 1: RVM/UA-2 flow monitor

1 Switch point adjustment scale2 Explosion-proof switch contact

SG-15EX***********3 Mechanical display with indicator

scale and pointer

The flow monitor RVM/UA-1 monitorsthe continuous flow of liquids. It isdesigned for installation into pipe sys-tems.

A float inside the device is moved bythe medium flowing through it. Thedesired switch point can be set on theswitch point adjustment scale,whereby the arrow on the switch con-tact is aligned to the desired volumeflow value on the adjustment scale.

Electrical monitoring is accomplishedby explosion-proof limit switch contactSG-15EX***********. The electrical con-nection is via the cast on power cableor various other connectors.

1.2 Warranty and guar-antee provisions

Warranty and guarantee provisions arecontained in the general terms andconditions of the manufacturer.

1.3 Customer serviceFor technical information, please con-tact our customer service department(for contact details, see Page 2).

Furthermore, our staff is always inter-ested in receiving new information andexperiences gained from application ofthe device, which might be useful inimproving our products.

Overview

Customer service

04.05.2020RVM/UA-2 Module ATEX Flow Monitor6

Page 7: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

2 SafetyThis Chapter provides an overview ofimportant safety aspects required foroptimum protection of personnel aswell as for safe installation and safeoperation of the device.

Non-observance of the handling andsafety instructions listed in this manualmay result in hazardous/dangerous sit-uations and in damage to property.

2.1 Explanation of sym-bols

Safety instructions

Safety instructions in this manual aremarked by symbols. The safetyinstructions are preceded by signalwords that indicate the level of danger/hazard.

To prevent accidents or injuries to per-sons as well as damage to property,always observe the safety instructionsand proceed carefully.

DANGER!

This combination of symbol andsignal word indicates an imme-diate, dangerous situation thatresults in death or serious injuryif it is not avoided.

WARNING!

This combination of symbol andsignal word indicates a possiblydangerous situation that mightresult in death or serious inju-ries if it is not avoided.

Safety

Explanation of symbols

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 7

Page 8: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

CAUTION!

This combination of symbol andsignal word indicates a possiblydangerous situation that mightresult in minor or slight injuriesif it is not avoided.

NOTICE!

This combination of symbol andsignal word indicates a possiblydangerous situation that mightresult in damage to propertyand to the environment if it isnot avoided.

Tips and recommendations

This symbol emphasizes usefultips and recommendations aswell as information for efficientand failure-free operation.

Signs used in these instructions

The following symbols and highlightingare used in these instructions to iden-tify handling instructions, the descrip-tion of results, lists/enumerations, ref-erences and other elements:

Designates step-by-step han-dling instructions.

ð Designates a state or anautomatic sequence as aresult of a specific operatingstep.

n Designates randomly ordered enu-merations and list entries

Ä “Signs used in these instructions”on page 8, designates references tochapters in these instructions.

2.2 Correct use inexplosion-hazardzones

The device is designed and con-structed exclusively for the correct usein accordance with these instructions.

The flow monitor serves exclusively formonitoring the continuous flow of liq-uids.

The areas of application are specifiedin Chapter 3 of these instructions.

The admissible operating conditionsare specified in Chapter 4 of theseinstructions.

Safety

Correct use in explosion-hazard zones

04.05.2020RVM/UA-2 Module ATEX Flow Monitor8

Page 9: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

Correct use of the device includes theobservance of all specifications in theOperating Instructions for "RVM/UA-2Module BASICS" and "RVM/UA-2Module ATEX".

Any addition or different application,above and beyond the correct use inaccordance with these instructions, isdeemed as incorrect use.

WARNING!

Danger due to incorrect use!– Use the flow monitor only

within the stipulated per-formance limits

– Do not subject the flowmonitor to severe tempera-ture fluctuations

– Do not use the flow monitorwith quick-acting valves

– Do not use the flow monitorwith solenoid valves

– Do not subject the flowmonitor to vibrations

– Do not subject the flowmonitor to pressure surges

– Do not use the flow monitorwith media containingsolids or abrasives

– Only use the flow monitorwith media previouslyapproved by the manufac-turer

– Do not use the flow monitoras the sole monitoringdevice to prevent dan-gerous conditions

– Do not install the flow mon-itor as a load bearing partwithin a pipeline system

– The flow monitor must beinstalled so, as to precludedamage by outside force. Ifnecessary, install an appro-priate impact protectiondevice

Safety

Correct use in explosion-hazard zones

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 9

Page 10: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

– The flow monitor may onlybe installed in explosion-hazard zones if:– the labeling on the flow

monitor,– the labeling on the

switch unit installed onthe flow monitor,

– and the informationcontained in theaccompanying docu-mentation (OperatingInstructions "RVM/UA-2 Module BASICS"and Operating Instruc-tions "RVM/UA-2Module ATEX"),authorize such installa-tion and operation.

– Planning and design ofequipment, protective sys-tems and components isthe responsibility of thefacility operator

– The potential impact, incase of an explosion, mustbe taken into account bythe facility operator.

– The facility operator isresponsible for the substi-tution, or the reduction ofthe quantity of substances,which may cause an explo-sive atmosphere

All claims for damages due to incorrectuse are excluded.

Incorrect use of the flow monitor mayresult in dangerous conditions.

2.3 Special precautionsfor use in explosion-hazard zones

The following chapter lists residualrisks that might arise from the device.

To reduce health risks and preventdangerous conditions, observe thesafety instructions listed here, thesafety instructions listed in other chap-ters of these Operating Instructions, aswell as all safety instructions listed inthe Operating Instructions for "RVM/UA-2 Module BASICS".

These Operating Instructionscannot cover all conceivabledangers because many dan-gers arise, not from the deviceitself, but from the respectivemedia flowing through it.Always observe the instructionson the appropriate safety datasheets when using hazardousmedia!

Safety

Special precautions for use in explosion-hazard zones

04.05.2020RVM/UA-2 Module ATEX Flow Monitor10

Page 11: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

2.3.1 Precautions for usein explosion-hazardzones

DANGER!

Danger to life from explo-sions– Potentially explosive dust-

air mixtures and hybrid mix-tures are not permittedinside the flow meter/flowmonitor and must beexcluded by the operator!

– Dust accumulations are notpermitted, neither insidethe flow meter/flow monitor,nor on the outside surfaceand must be excluded bythe operator! Whencleaning, do not use drycloths!

– To avoid electrostaticcharges capable ofresulting in dangerous sit-uations, the followingrequirements must be met:– All conductive parts,

capable of electrostaticcharging, must be con-nected and grounded.

– Dangerous electro-static charging of non-conductive parts andmaterials, includingsolids, fluids and dust,must be avoided.

– Ignitable dischargesmust be excluded.

– Chemical reactions, pyrol-ysis or biological processesinside the flow meter/flowmonitor are not permittedand must be excluded bythe operator.

– Intrusion of foreign mate-rials which can generatesparks, is not permitted andmust be excluded by theoperator.

– Friction, which may causelocal heat build-up andsparking, is not permittedand must be excluded bythe operator!

– Impact processes, involvingmaterials such as rust orlight alloys (e.g. aluminumor magnesium) are not per-mitted and must beexcluded by the operator.

– High voltage and currentsthat may cause sparkingare not permitted and mustbe excluded by the oper-ator.

– Electromagnetic waves in afrequency range between104 to 3×1012 Hz, as maybe found in the vicinity ofradio broadcasting stationsor high-frequency genera-tors, are not permitted andmust be excluded by theoperator.

Safety

Special precautions for use in explosion-hazard zones > Precautions for use in explosion-hazard zones

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 11

Page 12: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

– Electromagnetic waves in afrequency range between3×1011 to 3×1015 Hz, whichcan occur as radiation fromprotective systems or com-ponents (e.g. lamps, arclamps, lasers), are not per-mitted and must beexcluded by the operator.

– Devices that can focusradiation, and that can pro-vide an ignition source forparticles and surfaces, arenot permitted and must beexcluded by the operator.

– Ionizing radiation, thatexceeds the minimum igni-tion temperature of the sur-rounding combustibleatmosphere, is not per-mitted and must beexcluded by the operator.

– Ultrasound sources, thatcan ignite the sonicatedmaterial, are not permittedand must be excluded bythe operator.

– Adiabatic compression andshock waves are not per-mitted and must beexcluded by the operator.

– Exothermic reactions,including auto-ignition ofdust, is not permitted andmust be excluded by theoperator.

2.4 Personnel require-ments

WARNING!

Risk of injury due to insuffi-ciently trained and qualifiedpersonnel!If unqualified personnel work onthe device or are located withinits hazard zone, dangers arisewhich may result in serious inju-ries and considerable damageto property.

– All work must be performedby qualified personnel only

– Keep unqualified personnelaway from hazard zones.

The personnel requirements, as formu-lated in the Operating Instructions for"RVM/UA-2 Module BASICS" Chapter2.4, are valid. For employment withinexplosion-hazard zones, only trainedand qualified personnel may be used.Responsibility for the choice of per-sonnel and their qualification rests withthe facility operator. The requirementsfor standards DIN EN 60079-14 andDIN EN 60079-17 must be taken intoconsideration.

Refer also to the Operating Instruc-tions "RVM/UA-2 Module BASICS",Chapter 2.9 "Responsibility of theowner".

Authorized personnel is to berestricted to those persons who can beexpected to carry out their work reli-ably. Persons whose ability to respondis influenced, e.g. by drugs, alcohol ormedication, are not authorized.

Safety

Personnel requirements

04.05.2020RVM/UA-2 Module ATEX Flow Monitor12

Page 13: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

Observe the age and occupational reg-ulations at the site when choosing per-sonnel.

2.5 Personal safetyequipment

Personal safety equipment is used toprotect personnel from hazards/dangers that might impair their safetyor health during work.

When performing the various tasks at,and with the device, personnel mustwear personal safety equipment. Spe-cial reference to this equipment ismade in the Operating Instructions for"RVM/UA-2 Module BASICS". Thefacility operator must ensure that theprotective clothing used in explosion-hazard zone is suitable and approved.

2.6 Protective systemsThe design of the safety features isdescribed in the Operating Instructions"RVM/UA-2 Module BASICS". Theoperator must ensure that all appli-cable regulations which apply to oper-ation in an explosion-hazard zone aremet.

Safety

Protective systems

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 13

Page 14: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

3 Areas of employment3.1 Mechanical compo-

nent (flow meterwithout limiting con-tacts and electricalaccessories)

3.1.1 Exterior of thedevice

n Devices of the RVM/UA-1 typemay be employed in areas inwhich an explosive atmosphere,composed of a gas/air- or dust/air-mixture, may occasionally occur.The exterior of the device maytherefore be suitably located inexplosion hazard zone 1, zone 2,zone 21, or zone 22

n Dust accumulations are not per-mitted; neither internally, nor onthe outside surface of the flowmeter/flow monitor and must beexcluded by the operator.

3.1.2 Interior of the devicen Inside the device, only those flow

media may be used, to which thefollowing applies:

n the media is listed on the medialist (Chapter 3.1.5) and

n the medium is not aggressive tothe wetted parts of the device, and

n the device is approved b the man-ufacturer for use with the medium.

n It is permissible to occasionallyhave an explosive gas/air mixtureinside the device (explosionhazard zone 1). At no time maygasses of explosion hazard groupIIC (e.g. hydrogen or acetylene)be present inside device.

n Explosive dust-air mixtures andhybrid mixtures are not permittedinside the flow meter/flow monitorand must be excluded by the oper-ator.

n Chemical reactions, pyrolysis orbiological processes inside theflow meter/flow monitor are notpermitted and must be excludedby the operator.

n The entry of foreign materials thatmay produce sparks is not per-mitted and must be excluded b theoperator.

Areas of employment

Mechanical component (flow meter without limiting contacts and electrical accessories) > Interior of the device

04.05.2020RVM/UA-2 Module ATEX Flow Monitor14

Page 15: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

3.1.3 General safety infor-mation for themechanical compo-nent of the device

n Dust accumulation are not per-mitted; neither internally, nor onthe outside surface of the flowmeter/flow monitor and must beexcluded by the operator. Whencleaning, do not use dry cloths!

n In case of hazard through staticelectricity, the following require-ments must be met:– All conductive parts capable

of charging themselves elec-trostatically must be con-nected and grounded.

– Dangerous electrostaticcharging of non-conductiveparts and materials, includingsolids, fluids and dust, mustbe avoided.

– Ignitable discharges must beexcluded

n Friction, which may cause localheat build-up and sparking, is notpermitted and must be excludedby the operator.

n Impact processes involving mate-rials such as rust or light alloys(e.g. aluminum or magnesium) arenot permitted and must beexcluded by the operator.

n High voltage and currents thatmay cause sparking are not per-mitted and must be excluded bythe operator.

n Electromagnetic waves in a fre-quency range between 104 to3×1012 Hz, as may be found in thevicinity of radio broadcasting sta-tions, or high-frequency genera-tors, are not permitted and mustbe excluded by the operator.

n Electromagnetic waves in a fre-quency range between 3×1011 to3×1015 Hz, which can occur asradiation from protective systemsor components (e.g. lamps, arclamps, lasers), are not permittedand must be excluded by the oper-ator.

n Devices which can focus radiation,and which can provide an ignitionsource for particles and surfaces,are not permitted and must beexcluded by the operator.

n Ionizing radiation, which exceedsthe minimum ignition temperatureof the surrounding combustibleatmosphere, is not permitted andmust be excluded b the operator.

n Ultrasound sources, which canignite the sonicated material, arenot permitted and must beexcluded by the operator.

n Adiabatic compression and shockwaves are not permitted and mustbe excluded by the operator.

Areas of employment

Mechanical component (flow meter without limiting contacts and electrical accessories) > General safety information for the mechanical component

of the device

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 15

Page 16: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

n Exothermic reactions, includingauto-ignition of dust, are not per-mitted and must be excluded bythe operator.

n The device must be installed insuch a way as to precludedamage by outside force. It is theresponsibility of the operator toinstall appropriate protectivedevices.

3.1.4 Categorization ofthe mechanical com-ponent of the flowmonitor

n Equipment groupinternal: IIexternal: II

n Equipment categoryinternal: 2external: 2

n Atmosphereinternal: Gas (G)external: Gas (G), Dust (D)

n Type of protection: h (Construc-tional Safety "c")

n Gas groupinternal: IIBexternal: IIC, IIIC

n Temperature classificationinternal: T5, T6external: T5, T6external: T100 °C, T80 °COperating temperatures for devicewithout limit switch contactsThe maximum media tempera-ture for a device without limitswitch contacts must be lessthan:– the ignition temperature of the

medium and– the ignition temperature of the

atmosphere surrounding thedevice and

– less than or equal to 100 °C

It is the responsibility of the oper-ator to ensure that these require-ments are met concurrently.

Areas of employment

Mechanical component (flow meter without limiting contacts and electrical accessories) > Categorization of the mechanical component of the flow

monitor

04.05.2020RVM/UA-2 Module ATEX Flow Monitor16

Page 17: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

The minimum media tempera-ture for a device without limitswitch contacts must be higherthan or equal to - 20 °C.It must be ensured that themedium does not freeze.The maximum ambient tempera-ture for a device without limitswitch contacts must be lessthan:– the ignition temperature of the

medium and– the ignition temperature of the

atmosphere surrounding thedevice

– and less than or equal to100 °C

It is the responsibility of the oper-ator to ensure that these require-ments are met concurrentlyThe minimum ambient tempera-ture for a device without limitswitch contacts must be higherthan or equal to - 20 °C.Operating temperatures for adevice with the following limitswitch contacts:Explosion proof switch contacts,Series SG-15EX*********** withdesign examination:EPS 13 ATEX 1 596 UThe maximum media tempera-ture for a device with these limitswitch contacts must be lessthan:– the ignition temperature of the

medium and– the ignition temperature of the

atmosphere surrounding thedevice and

– less than 45 °C

It is the responsibility of the oper-ator to ensure that these require-ments are met concurrentlyThe minimum media tempera-ture for a device with these limitswitch contacts must be higherthan - 5 °C .It must be ensured that themedium does not freeze.The maximum ambient tempera-ture for a device with these limitswitch contacts must be lessthan:– the ignition temperature of the

medium and– the ignition temperature of the

atmosphere surrounding thedevice and

– less than 45 °C

It is the responsibility of the oper-ator to ensure that these require-ments are met concurrentlyThe minimum ambient tempera-ture for a device with these limitswitch contacts must be higherthan - 5 °C.

n EPL (Equipment Protection Level):Gb (Gas), Db (Dust)

n Labeling of the mechanical com-ponent of the flow meter/monitor:internal: II 2G Ex h IIB T5, T6Gbexternal: II 2G Ex h IIC T5, T6Gbexternal: II 2D Ex h IIIC T100°C, T80 °C Db

Areas of employment

Mechanical component (flow meter without limiting contacts and electrical accessories) > Categorization of the mechanical component of the flow

monitor

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 17

Page 18: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

3.1.5 List of mediaMedia used Ignition temp. Explosion limit

[%]

Lower Upper

Argon Inert gas

Cargon gaseous mixtureArgon+CO2

CO2 Inert gas

CO2liquid

Diesel 255 (ASTME659-78) 0,6 6,5

Biodiesel SME Soya seed oilmethyl ester

285 (ASTME659-78)

Biodiesel RME Rape seed oilmethyl ester

283 (ASTME659-78)

EDC (1,2-Dichlorethane) 440 6,2 16

Natural gas 575 - 640 4 17

Ethanol 400 3,1

City gas 560

Gaseous mix-ture 90 %Argon + 10 %CO2

Gaseous mix-ture 96 %Argon + 4 %O2

Helium none none none

Air

Methane 595 4,4 16,5

Areas of employment

Mechanical component (flow meter without limiting contacts and electrical accessories) > List of media

04.05.2020RVM/UA-2 Module ATEX Flow Monitor18

Page 19: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

Media used Ignition temp. Explosion limit[%]

Lower Upper

Methanol 455 6,1 44

N2 none none none

N2O none none none

NaOH Natrium-hydroxide-NaOH ("causticsoda")

none none none

NaOH 50% none none none

Caustic sodaNaOH 25%

none none none

NH3 anhydrousammonia

630 15 28

n-Heptan(highly puri-fied)

215 1 6,7

O2 none none none

Oil

organic Saltsolution den-sity 1,35 kg/l20 °C

Peroxide none none none

RAF2 Raffinate 2 385 1,6 10

Spirits ofAmmonia(25%)

630 15 28

SO2 Sulphur dioxide none none none

Areas of employment

Mechanical component (flow meter without limiting contacts and electrical accessories) > List of media

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 19

Page 20: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

Media used Ignition temp. Explosion limit[%]

Lower Upper

Solvana 2000(Universalcleaningagent)

236 0,4 7

Petroleumether

>200 0,6 7

Water none none none

Water / Nitrite-solution

Hydrogenper-oxyde 50%(ultra pure)

none none none

Hydrogenper-oxyde 50weight.-%, dis-solved inWater

none none none

Propane 470 2,2 9,5

n-Butane 365 1,4 8,5

3.1.6 Applicable docu-ments

Areas of employment

Mechanical component (flow meter without limiting contacts and electrical accessories) > Applicable documents

04.05.2020RVM/UA-2 Module ATEX Flow Monitor20

Page 21: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

Areas of employment

Mechanical component (flow meter without limiting contacts and electrical accessories) > Applicable documents

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 21

Page 22: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

.

Areas of employment

Mechanical component (flow meter without limiting contacts and electrical accessories) > Applicable documents

04.05.2020RVM/UA-2 Module ATEX Flow Monitor22

Page 23: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

3.2 Electrical compo-nent of the device(limiting contacts)

The electrical limit switch contacts,Series SG-15EX*********** , were sub-jected to design examination: EPS 13ATEX 1 596 U

This component type and acceptablevariations thereto is specified in thesupplement to this certificate.

The electrical limiting contacts mayonly be employed in combination withRVM/UA-2 type devices in areas inwhich an explosive atmosphere, com-posed of a gas/air- or dust/air- mixture,may occasionally occur. The limitingcontacts of the device may thereforebe suitably located in explosion hazardzone 1, zone 2, zone 21, or zone 22.Dust accumulations are not permittedon the limiting contacts and must beexcluded by the operator.

3.2.1 Applicable docu-ments

The electrical limit switch contactswere subjected to a design examina-tion

EPS 13 ATEX 1 596 U

The following documents must beobserved:

Manufacturer's declaration for theemployment of explosion-proof switchunits within a safety concept

n Design examination certificate withattachment

n Conformity declaration (MeisterStrömungstechnik GmbH)

n IECEX CoC+ ExTrIECEX EPS 13.0026U

Areas of employment

Electrical component of the device (limiting contacts) > Applicable documents

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 23

Page 24: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

.

Areas of employment

Electrical component of the device (limiting contacts) > Applicable documents

04.05.2020RVM/UA-2 Module ATEX Flow Monitor24

Page 25: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

.

Areas of employment

Electrical component of the device (limiting contacts) > Applicable documents

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 25

Page 26: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

.

Areas of employment

Electrical component of the device (limiting contacts) > Applicable documents

04.05.2020RVM/UA-2 Module ATEX Flow Monitor26

Page 27: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

.

Areas of employment

Electrical component of the device (limiting contacts) > Applicable documents

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 27

Page 28: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

.

Areas of employment

Electrical component of the device (limiting contacts) > Applicable documents

04.05.2020RVM/UA-2 Module ATEX Flow Monitor28

Page 29: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

.

Areas of employment

Electrical component of the device (limiting contacts) > Applicable documents

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 29

Page 30: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

.

Areas of employment

Electrical component of the device (limiting contacts) > Applicable documents

04.05.2020RVM/UA-2 Module ATEX Flow Monitor30

Page 31: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

.

Areas of employment

Electrical component of the device (limiting contacts) > Applicable documents

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 31

Page 32: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

4 Operating dataOperating data for employment inexplosion-hazard zones.

4.1 Operating data forthe mechanicalcomponent of thedevice

The maximum operating pressure isspecified in Chapter 10.7 of the Oper-ating Instructions for "RVM/UA-2Module BASICS".

The maximum media and ambienttemperatures for the mechanical com-ponent depends on various factors. Itis the responsibility of the operator tospecify the maximum temperatureswithin the framework set by the guide-lines in Chapter Ä Chapter 3.1.4 “Cat-egorization of the mechanical compo-nent of the flow monitor” on page 16and ensure adherence thereto.

4.2 Switch contactoperating data

Operating data for the explosion-proofswitch units, series SG-15EX***********with design examination.

Certificate number: EPS 13 ATEX 1596 U

This component and any acceptablevariation thereto are specified in theschedule to this certificate and thedocuments therein referred to.

The sign "U" placed behind the certifi-cate number indicates that this certifi-cate should not be confounded withcertificates issued for equipment orprotective systems. This componentcertificate only serves as a basis forthe issuing of certificates for equip-ment or protective systems.

Installation of the switch contact is setin the type certificate for the respectiveelectrical equipment

The operating temperature limits of- 5 °C< TService <+ 45 °C must not beexceeded.

The following intrinsically safe limitvalues must not be exceeded, noteven for brief periods:

Table 1: Electrical data - Gas

Ui li Pi

< 12,1 V 1,0 A 3,0 W

< 20 V 0,309 A 1,55 W

< 25 V 0,158 A 0,99 W

< 30 V 0,101 A 0,76 W

Li = 0

Ci = 0

Operating data

Switch contact operating data

04.05.2020RVM/UA-2 Module ATEX Flow Monitor32

Page 33: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

Table 2: Electrical data - Dust

Ui li Pi

< 12,1 V 0,250 A 0,75 W

< 20 V 0,250 A 0,75 W

< 25 V 0,250 A 0,75 W

< 30 V 0,250 A 0,75 W

Li = 0

Ci = 0

Operating data

Switch contact operating data

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 33

Page 34: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

4.3 Labeling of the switch contactsThe labeling of the components must contain the following information:

II 2G Ex ib IIC

II 2D Ex ib IIIC

Examples of the switch contact labels:

Fig. 2: Switch contact with connector DIN 43650 (Form C)

Fig. 3: Switch contact with cable

Operating data

Labeling of the switch contacts

04.05.2020RVM/UA-2 Module ATEX Flow Monitor34

Page 35: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

5 Transport, packaging and storageTransport, packaging and storage innon-explosion-hazard zones aredescribed in Chapter 4, "RVM/UA-2Module BASICS".

In explosion-hazard zones, in additionto the requirements described in theabove reference, all valid provisionsfor safety, accident prevention andenvironmental protection must be com-plied with.

Packaging procedures (wrapping/unwrapping) may only be conductedoutside the explosion-hazard zone.

DANGER!

Danger to life if packagingprocedures are conducted inexplosion-hazard zones.

n Packaging procedures may onlybe conducted outside the explo-sion-hazard zone.

Transport, packaging and storage

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 35

Page 36: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

6 Installation and initial startupInstallation and initial startup in non-explosion-hazard zones are describedin Chapter 5, "RVM/UA-2 ModuleBASICS". In addition, for installationand initial startup in explosion-hazardzones, the following sections must beobserved:

6.1 SafetyAll relevant safety-, accident preven-tion- and environmental protection reg-ulations must be followed for employ-ment in an explosion hazard zone.

6.2 ToolsTools, which may cause sparks, arenot to be employed. These tools mayonly be used when there is no poten-tially explosive atmosphere present.

The use of steel tools, of any kind, isprohibited in hazard zone 1, if there isrisk of explosion due to substances inexplosion hazard group IIC (in accord-ance with IEC/TR3 60079-20), (forexample, acetylene, hydrogen).

6.3 Protection of theflow monitor

The flow monitor must be installed insuch a way as to preclude damage byoutside force.

The facility operator is responsible forthe installation of an appropriateimpact protection shield.

6.4 Electrical connec-tion

Electrical connection is accomplishedthrough the connection cable leadingfrom the switch housing. All safetyadvisories contained in the OperatingInstructions for "RVM/UA-2 ModuleBASICS", Chapter 5, must beobserved. Additionally, for operation inexplosion-hazard zones, all valid provi-sions for safety, accident preventionand environmental protection must becomplied with.

6.5 Grounding thedevice

When installing the device in a pipesystem, ensure that the device isgrounded to the pipe system to avoid adangerous electrical potential differ-ence.

6.6 Contact protectionmeasures

Recommendations for contact protec-tion measures, when the device isemployed in a non-explosion-hazardzone, are described in chapter 5.9"Contact protection measures" of theOperating Instructions for "RVM/UA-2Module BASICS". When the device isemployed in an explosion-hazardzone, only those contact protectionmeasures may be taken, which are

Installation and initial startup

Contact protection measures

04.05.2020RVM/UA-2 Module ATEX Flow Monitor36

Page 37: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

consistent with all valid safety andaccident prevention measures forexplosion-hazard zones and the speci-fications contained in these OperatingInstructions.

Installation and initial startup

Contact protection measures

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 37

Page 38: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

7 OperationOperation is described in Chapter 6,"RVM/UA-2 Module BASICS". Allsafety- and hazard warnings containedin Chapter 6, "RVM/UA-2 ModuleBASICS", must be followed. For opera-tion in explosion-hazard zones, allvalid provisions for safety, accidentprevention and environmental protec-tion must be complied with.

Operation

04.05.2020RVM/UA-2 Module ATEX Flow Monitor38

Page 39: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

8 TroubleshootingThe procedures in case of malfunctionare described in Chapter 7, "RVM/UA-2 Module BASICS". All safety- andhazard warnings, contained in Chapter7, "RVM/UA-2 Module BASICS", mustbe followed. Additionally, for operationin explosion-hazard zones, all validprovisions for safety, accident preven-tion and environmental protection mustbe complied with.

Troubleshooting

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 39

Page 40: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

9 MaintenanceMaintenance procedures aredescribed in Chapter 8, "RVM/UA-2Module BASICS". All safety- andhazard warnings, contained in Chapter8, "RVM/UA-2 Module BASICS", mustbe followed. For operation in explo-sion-hazard zones, all valid provisionsfor safety, accident prevention andenvironmental protection must be com-plied with. Maintenance proceduresmay only be performed outside theexplosion-hazard zone.

DANGER!

Danger to life if maintenanceprocedures are performed inthe explosion-hazard zone– Maintenance procedures

may only be performed out-side the explosion-hazardzone

9.1 Return Materials9.1.1 Return Materials

AuthorizationFor products being returned, regard-less of the reason, the currently validprovisions of the returns policy set byMEISTER will apply. Return shipmentswhich do not comply with the returnspolicy may be refused by MEISTER atthe expense of the consignor.

Maintenance

Return Materials > Return Materials Authorization

04.05.2020RVM/UA-2 Module ATEX Flow Monitor40

Page 41: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

10 Disassembly and disposalDisassembly and disposal proceduresare described in Chapter 9, "RVM/UA-2 Module BASICS". All safety- andhazard warnings, contained in Chapter9, "RVM/UA-2 Module BASICS", mustbe followed. For operation in explo-sion-hazard zones, all valid provisionsfor safety, accident prevention andenvironmental protection must be com-plied with. Disassembly of the devicemay only be performed outside theexplosion-hazard zone.

DANGER!

Danger to life if disassemblyprocedures are performed inthe explosion- hazard zone– Disassembly may only be

performed outside theexplosion hazard zone

– Disassembly in an explo-sion hazard zone may onlybe performed if there is norisk from an explosiveatmosphere

Disassembly and disposal

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 41

Page 42: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

11 Technical data11.1 Dimension sheet

Technical data

Dimension sheet

04.05.2020RVM/UA-2 Module ATEX Flow Monitor42

Page 43: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

11.2 General specificationsType Overall dimensions (mm)

G DN SW L1 L2 T

RVM/UA-2/02

1/4" 8 24 90 98 15

3/8" 10 24 90 119 12,5

1/2" 15 - 90 - 15

RVM/UA-2/06

1/4" 8 24 90 98 15

3/8" 10 24 90 119 12,5

1/2" 15 - 90 - 15

RVM/UA-2/1

1/4" 8 24 90 98 15

3/8" 10 24 90 119 12,5

1/2" 15 - 90 - 15

RVM/UA-2/3

1/4" 8 24 90 98 15

3/8" 10 24 90 119 12,5

1/2" 15 - 90 - 15

RVM/UA-2/7

1/4" 8 24 90 98 15

3/8" 10 24 90 119 12,5

1/2" 15 - 90 - 15

RVM/UA-2/13

1/4" 8 24 90 98 15

3/8" 10 24 90 119 12,5

1/2" 15 - 90 - 15

RVM/UA-2/20

1/2" 15 - 90 - 15

RVM/UA-2/30

1/2" 15 - 90 - 15

Technical data

General specifications

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 43

Page 44: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

Type Overall dimensions (mm)

G D1 D2 A1 A2 A3 A4 Weight(g)

RVM/UA-2/02

1/4" 27,5 30 47 33 66 ca. 70 620

3/8" 27,5 30 47 33 66 ca. 70 670

1/2" - 30 47 33 66 ca. 70 570

RVM/UA-2/06

1/4" 27,5 30 47 33 66 ca. 70 620

3/8" 27,5 30 47 33 66 ca. 70 670

1/2" - 30 47 33 66 ca. 70 570

RVM/UA-2/1

1/4" 27,5 30 47 33 66 ca. 70 620

3/8" 27,5 30 47 33 66 ca. 70 670

1/2" - 30 47 33 66 ca. 70 570

RVM/UA-2/3

1/4" 27,5 30 47 33 66 ca. 70 620

3/8" 27,5 30 47 33 66 ca. 70 670

1/2" - 30 47 33 66 ca. 70 570

RVM/UA-2/7

1/4" 27,5 30 47 33 66 ca. 70 620

3/8" 27,5 30 47 33 66 ca. 70 670

1/2" - 30 47 33 66 ca. 70 570

RVM/UA-2/13

1/4" 27,5 30 47 33 66 ca. 70 620

3/8" 27,5 30 47 33 66 ca. 70 670

1/2" - 30 47 33 66 ca. 70 570

RVM/UA-2/20

1/2" - 30 47 33 66 ca. 70 570

RVM/UA-2/30

1/2" - 30 47 33 66 ca. 70 570

Technical data

General specifications

04.05.2020RVM/UA-2 Module ATEX Flow Monitor44

Page 45: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

Type Overall dimensions (mm)

G D1 D2 A1 A2 A3 A4 Weight(g)

* NPT thread on request

** Connecting cable weight, 2m approx. 80g

11.3 Replacementparts

Technical data

Replacement parts

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 45

Page 46: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

The following replacement parts drawing provides an example of the constructionof a RVM/UA-2 ATEX type flow monitor. The actual configuration may varydepending on the model.

Item Qty Description

1 1 Process connection (inlet)

2 2 O-ring (seal)

3 1 Device body

4 1 Float

5 3 Magnet

6 1 Spring

7 1 Threaded ring (outlet)

8 1 Process connection (outlet)

9 1 Cylinder pin (switch contact)

Technical data

Replacement parts

04.05.2020RVM/UA-2 Module ATEX Flow Monitor46

Page 47: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

Item Qty Description

10 1 Switch contact (ATEX) with male connector

11 1 Female socket (ATEX) and gasket

12 1 Fixing screw (female socket)

13 1 Mechanical display

14 1 Set screw (switch contact)

Technical data

Replacement parts

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 47

Page 48: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

12 AnnexThe required tools are specified inChapter 11.3 "Tools" of the OperatingInstructions for "RVM/UA-2 ModuleBASICS".

In explosion-hazard zones, tools whichmay cause sparks, are not to beemployed. These tools may only beemployed when there is no potentiallyexplosive atmosphere present.

The use of steel tools, of any kind, isprohibited in hazard zone 1, if there isa risk of explosion due to substancesin explosion hazard group IIC (inaccordance with IEC/TR3 60079-20),(for example, acetylene, hydrogen).

Annex

04.05.2020RVM/UA-2 Module ATEX Flow Monitor48

Page 49: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

13 IndexAApplicable documents . . . . . . . . . 23

CCategorization

mechanical component . . . . . . 16

Contact . . . . . . . . . . . . . . . . . . . . 6Contact protection measures . . . . 36Copyright . . . . . . . . . . . . . . . . . . . 3Correct use . . . . . . . . . . . . . . . . . 8Customer service . . . . . . . . . . . . . 6

DDevice

electrical component . . . . . . . . 23

exterior . . . . . . . . . . . . . . . . . 14

interior . . . . . . . . . . . . . . . . . 14

Disassembly . . . . . . . . . . . . . . . . 41disposal . . . . . . . . . . . . . . . . . . . 41

EElectrical connection . . . . . . . . . . 36employment . . . . . . . . . . . . . . . . . 8Environmental protection regula-tions . . . . . . . . . . . . . . . . . . . . . 36

FFlow monitor

protection . . . . . . . . . . . . . . . 36

GGeneral

safety . . . . . . . . . . . . . . . . . . . 7

Grounding . . . . . . . . . . . . . . . . . 36

IInitial start-up . . . . . . . . . . . . . . . 36Installation . . . . . . . . . . . . . . . . . 36

LLabeling

switch contacts . . . . . . . . . . . . 34

Limitation of liability . . . . . . . . . . . . 3Limiting contacts . . . . . . . . . . . . . 23List of media . . . . . . . . . . . . . . . . 18

MMaintenance . . . . . . . . . . . . . . . . 40

OOperating data

mechanical component . . . . . . 32

switch unit . . . . . . . . . . . . . . . 32

Operation . . . . . . . . . . . . . . . . . . 38

PPackaging . . . . . . . . . . . . . . . . . 35Personnel requirements . . . . . . . . 12Precautions

explosion . . . . . . . . . . . . . . . . 11

general . . . . . . . . . . . . . . . . . 10

Index

04.05.2020 RVM/UA-2 Module ATEX Flow Monitor 49

Page 50: Betriebsanleitung RVM/UA-2 Schaltkontakt Modul ATEX, 2, en US · 1 Overview. 1.1 Short description. Fig. 1: RVM/UA-2 flow monitor 1 Switch point adjustment scale 2 Explosion-proof

Protective systems . . . . . . . . . . . 13

RReplacement parts . . . . . . . . . . . 45Return Materials Authorization . . . 40

SSafety equipment . . . . . . . . . . . . 13Safety information

mechanical component . . . . . . 15

Safety regulations . . . . . . . . . . . . 36Service . . . . . . . . . . . . . . . . . . . . 6Storage . . . . . . . . . . . . . . . . . . . 35Symbols used

in the instructions . . . . . . . . . . . 7

TTechnical data

Dimension sheet . . . . . . . . . . 42

General specifications . . . . . . . 43

Temperature class, internal: TX,external: TX . . . . . . . . . . . . . . . . 17Tools . . . . . . . . . . . . . . . . . . 36, 48Transport . . . . . . . . . . . . . . . . . . 35Troubleshooting . . . . . . . . . . . . . 39

WWarranty and guarantee provisions 6

Index

04.05.2020RVM/UA-2 Module ATEX Flow Monitor50