1. INTERIOR BATHROOMS SHALL BE MECHANICALLY VENTILATED TO PROVIDE
FOUR (4) CHANGES OR AIR PER HOUR, KITCHENETTE AREAS SHALL BE
MECHANICALLY VENTILATED TO PROVIDE SIX (6) CHANGES OR AIR PER HOUR.
2. ALL ASPECTS OF MECHANICAL VENTILATION SYSTEMS SHALL COMPLY WITH
SECTION 37 OF THE M.D.L. AND ALL OTHER APPLICABLE SECTIONS.
3. A STATEMENT SHALL BE FILED BY THE OWNER THAT STATES THE
MECHANICALLY VENTILATION SYSTEMS WILL BE OPERATED CONTINUOSLY AT AL
TIMES DURING THE NORMAL OCCUPANCY OF THE STRUCTURE AS PROVIDED IN
THE APPLICABLE SECTION OF THE CODE.
4. BATHROOM DUCTS SHALL BE A MINIMUM OF 20gr. GALVANIZED METAL
KITCHENETTE DUCTS SHALL BE A MINIMUM OF 18gr. GALVANIZED METAL, ALL
DUCTS SHALL BE A MINIMUM OF 5" dia. AND BOXED IN AS REQUIRED PER FIRE
RETARDING EXPLAINED BELOW.
5. DUCTS SHALL BE SUPPORTED AT EVERY FLOOR AND PER RS 13-1 AND 13-2.
ALL JOINTS AND ELBOWS SHALL BE TIGHT FITTING AND SCREWED.
6. FIRE RETIED ALL DUCWORK HAVING A CROSS SECTIONAL ARE OF UNDER
2SQFT WITH CONSTRUCTION HAVING A FIRE RESISTANCE RATING OF 1 HR
PLACED AS CLOSE AS POSSIBLE
7. EXACT LOCATION OF THE DUCT RUNS SHALL BE COORDINATED WITH THE
ARCHITECT IN THE FIELD.
8. EACH BATHROOM EXHAUST FAN SHALL BE INDIVIDUALLY WIRED TO OPERATE
WITH THE BATHROOM LIGHT SWITCH. EACH KITCHENETTE EXHAUST FAN SHALL
BE WIRED AND SWITCHED INDEPENDENTLY.
MECHANICAL VENTILATION NOTES:
1. CONTACTOR SHALL CHECK AND VERIFY ALL CONDITIONS AND DIMENTIONS
AND SHALL REPORT AND DISCREPANCES TO THE ARCHITECT PROR TO
COMMENCEMENT OF WORK.
2. CONTRACTORS SHALL OBTAIN ALL REQUIRED AND NECESSARY PERMITS
FROMM ALL MUNICIPAL AGENCIES HAVING JURISDICTION. NO WORK SHALL
PROCEED UNLEES PERMIT IS OBTAINED AND DISPLAYED AT OBVIOUS LOCATION
AT FRONT OF PREMISES.
3. UPON COMPLETION OF WORK, CONTRACTORS WILL BE RESPONSIBILE FOR
CALLING FOR INSPECTIONS AND OBTAINING SIGN-OFFS FOR CONSTRUCTION,
PLUMBING AND ELECTRIC WORK.
4. CONTRATOR SHALL CARRY WORKMAN'S COMPESATION INSURANCE AND
DISABILITY BENEFITS AND ALL OTHER INSURANCE PAPERS REQUIRED.
5. CONTRACTOR SHALL COMPLY WITH ALL REQUIREMENTS OF THE NEW YORK
CITY BUILDING CODE AND ALL OTHER RULES AND REGULATIONS OF THE COUNT
AND STATE AS THEY APPLY TO THIS ALTERATION.
6. DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL FIELD CONDITIONS
AND THE WORK OF OTHER TRADES PERMIT, ANY PIPING WIRING OR OTHER
MATERIALS NOT SPECIFICALLY SHOWN OR SPECIFIED BUT NEEDED TO
COMPLETE THE WORK SHALL BE DEEMED TO BE PART OF THESE
SPECIFICATIONS AND SHALL BE FURNISHED AND INSTALLED BY THE
CONTRACTOR.
GENERAL NOTES:
1. BUILDING SHALL COMPLY WITH SECTION D.26.03 H.M.C. DRAINAGE OF ROOFS
AND COURT YARDS.
2. BUILDING SHALL COMPLY WITH SECTION D.26 -17.01 H.M.C. CENTRAL HEAT.
3. BUILDING SHALL COMPLY WITH SECTION D.26 - 17.07 H.M.C. SUPPLY HOT
WATER.
4. BUILDING SHALL COMPLY WITH SECTION D.26 - 17.09 H.M.C. GAS - FUELED OR
ELECTRIC HEATERS WHERE PERMITED.
5. BUILDING SHALL COMPLY WITH SECTION D.26 - 19.01 H.M.C. ELECTRIC
LIGHTING EQUIPMENT IN DWELLINGS.
6. BUILDING SHALL COMPLY WITH SECTION D.26 - 19.03 H.M.C. ELECTRIC
LIGHTING IN PUBLIC AREAS.
7. BUILDING SHALL COMPLY WITH SECTION D.26 - 20.05 H.M.C. LOCKS IN DOORS.
8. BUILDING SHALL COMPLY WITH SECTION D.26 - 21.05 H.M.C. STREET
NUMBERS.
9. BUILDING SHALL COMPLY WITH SECTION D.26 - 30.11 H.M.C. LIGHTING AND
VENTILATION.
10. BUILDING SHALL COMPLY WITH SECTION D.26 - 31.13 H.M.C. SANITARY
FACILITIES.
HOUSING MAINTENANCE NOTES:
1. THE ELECTRIC INSTALLATION AND REPAIRS SHALL BE IN STRICT ACCORDANCE
WITH THE NEW YORK CITY CODE AND OTHER CODES OR AGENCIES HAVING
JURIDICTION.
2. CONTRACTOR SHALL PROCURE RECUIRED PERMITS FOR HIS WORK.
3. EACH DWELLING UNIT SHALL BE PROVIDED WITH A SEPARATE METER.
4. ALL EXPOSED WIRING, UNLESS OTHERWISE NOTED SHALL BE INSTALLED IN
EMT CONDUIT. ALL CONCEALED WIRING MAY BE FLEXIBLE METALIC CONDUIT.
5. SMOKE DETECTORS SHALL BE INSTALLED IN WIRING BEFORE ELECTRICAL
SWITCHES ARE WIRED INTO LINE.
ELECTRICAL NOTES:
1. MECHANICAL AND PLUMBING WORK SHALL BE FILED AS REQUIRED WITH THE
APPROPRIATE CITY AGENCIES, UPOM COMPLETION WORK, CONTRACTOR SHALL
ARRANCE FOR AND OBTAIN RELEVANT SIGN-OFF.
2. ALL MECHANICALL AND PLUMBING WORK SHALL CONFORM TO THE NYC CODE
AND ALL LOCAL LAWS.
MECHANICAL & PLUMBING NOTES:
1. EACH DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE DETECTING DEVICES
RECEIVING THEIR PRIMARY POWER FROM THE BUILDING WIRING AND THERE
SHALL BE NO SWITCHES IN THE CIRCUIT OTHER THAN THE OVER CURRENT
DEVICE PROTECTING THE BRANCH.
2. NO DEVICE SHALL BE DEEMED TO BE IN COMPLIANCE WITH BUILDING
DEPARTMENT REQUIREMENTS UNLESS IT IS OF WITHER THE IONIZATION
CHAMBER OR PHOTOELECTRIC TYPE, SUCH DEVICE SHALL BE IN COMPLIANCE
WITH THE REQUIREMENTS OF REFERENCE STANDARD RS 17-1.
3. SMOKE DETECTOR SHALL BE LOCATED WITHIN 15'0' OF BEDROOM DOORS.
BUILDING DEPARTMENT NOTES:1. ALL NEW CONSTRUCTION SHALL ADHERE TO THE NEW YORK STATE ENERGY
CONSERVATION GUIDELINES.
2. ALL CONSTRUCTION WORK SHALL BE CONFINED TO THE AREAS SHOWN ON
PLANS AND SHALL NOT BLOCK ANY MEANS OF EGRESS.
3. CONSTRUCTION WORK SHALL TAKE PLACE BETWEEN TO THE HOURS OF 8:00
A.M. AND 5:00 P.M.
SMOKE DETECTION NOTES:
Table 3-4 CONCTRUCTION CLASS IID
EXTERIOR WALL BETWEEN 3' OR
LESS - BEARING 2HR
-NON BEARING 2HR
BETWEEN 3' AND 15'-BEARING 1HR
-NON BEARING 1HR
BETWEEN 15' AND 30' 1HR
-NON BEARING 1HR
30' OR MORE'-BEARING 1 HR
-NON BEARING 0 HR
INTERIOR BEARING PARTITION 1 HR
ENCLOSURE OF VERTICAL EXITS 2 HR
FLOOR CONSTRUCTION 1HR
ROOF CONSTRUCTION
3
4
HR
FIRE STOPPING1. CONCEALED SPACES (EXCEPT SHAFTS & SPRINKLER SPACES), WITHIN PARTITIONS, WALLS, FLOORS, ROOFS, STAIRS, FURRING &
PIPE SPACES, THAT WOULD PERMIT THE PASSAGE OF FLAME, SMOKE, FUMES, OR HOT GASES FROM ONE FLOOR TO ANOTHER OR
TO ROOF SPACES, OR FROM ONE CONCEALED AREA TO ANOTHER, SHALL BE FIRE STOPPED, TO FORM AND EFFECTIVE DRAFT
BARRIER OR SHALL BE FILLED WITH NON-COMBUSTABLE MATERIAL AS PER C26-504.7.
2. EXTERIOR CORNERS AND EAVES SHALL BE FIRE STOPPED AT THE ENDS OF PARTY WALLS.
3. ALL SPACES BETWEEN CHIMNEYS AND WOOD JOISTS, BEAMS OR HEADERS SHALL BE FIRE STOPPED AS PER ARTICLE 5.
ASPHALT ROOF SHINGLESALL SLOPED ROOF SHINGLES SHALL BE CLASS-A ASPHALT ROOF SHINGLES OR APPROVED EQUAL. SHINGLES SHALL BE APPLIED
OVER 15# ASPHALT FELT WITH GAF-WEATHER-WATCH ICE AND WATER BARRIER APPLIED AT EAVES, VALLEYS AND FLASHINGS.
ROOFER TO PROVIDE ALL FLASHING NECESSARY FOR A WATERTIGHT, WEATHERPROOF JOB. ROOFING IS TO BE APPLIED IN STRICT
ACCORDANCE WITH THE MANUFACTURERS SPECIFICATIONS. CONTRACTOR SHALL SUPPLY COLOR SAMPLES OF THE SHINGLES FOR
ARCHITECT'S AND/OR OWNER'S APPROVAL, PRIOR TO INSTALLATION.
GYPSUM WALLBOARDGYPSUM WALLBOARD APPLICATION SHALL BE TAPE JOINT SYSTEM. ALL GYPSUM BOARD TO BE 5/8" ON WALLS AND 1/2" ON
CEILING UNLESS OTHERWISE INDICATED. FINISH JOINTS, J-BEADS, NAIL DIMPLES, CORNERS AND EDGES SHALL BE TAPED AND
RECEIVE THREE COATS OF JOINT COMPOUND. ALLOW 24 HOURS TO DRY BETWEEN COATS. FINAL COAT TO BE SANDED SMOOTH.
METAL CORNER BEADS TO BE USED ON ALL OUTSIDE CORNERS AND AROUND ALL OPENINGS. ALL WALLS AND CEILINGS OF ALL
GARAGES AND MECHANICAL ROOMS TO BE SHEATHED WITH 5/8" TYPE-X FIRECODE SHEETROCK. SHOWER AND TUB ENCLOSURES
TO BE LINED WITH 5/8" WONDERBOARD. ALL OTHER BATHROOMS AND LAUNDRY ROOMS TO HAVE 5/8" WATER RESISTANT
SHEETROCK.
"HARDWIRED CARBON MONOXIDE DETECTORS COMPLYING WITH RS 17-13 AND
INSTALLED IN ACCORDANCE WITH 17-14 SHALL BE PROVIDED IN EVERY DWELLING
UNITWITHIN 15 FEET OF THE PRIMARY ENTRANCE TO EACH BEDROOM."
TR3 & TR2 EXEMPTIONS
The work meets the exemption criteria of Buildings Bulletin
2009-026, item IV, and i herby elect to waive the requirement
of concrete testing and of the TR2 form and/or TR3 form.
* The total structural concrete specified for the project is
less than 50 cubic yards (43 m³);
* The structural design of the concrete is based on a
specified compressive strength, fc, no greater than
2,500 pounds per square inch (psi) (17.2 MPa) ,
regardless of the compressive strength specified in the
construction documents or used in the construction; and
* The concrete to be placed is specified to have a
compressive strength of at least 4,000 psi (28 MPa)
NOTE:
LEGEND
DENOTES FLOOR DRAIN
DENOTES 2 HR RATED PARTITION
CONSTRUCTED OF 2X4 WOOD STUD
@ 16" O.C. WITH 2 LAYERS
5
8
" TYPE "X"
G.W.B. EACH SIDE-TWO HR. RATED
(B.S.A. NO. 171-52-SM).
C.M.& S.D.
DENOTES APPROVED TYPE
SMOKE DETECTOR & CARBON MONOXIDE
DENOTES NON-RATED NON BEARING
PARTITION CONSTRUCTED OF 2"x4" WOOD
STUDS @ 16" O.C. WITH 1 LAYER 5/8" G.W.B
EACH SIDE. IN WET AREAS (BATH, KITCHEN
AND LAUNDRY) USE M.R. G.W.B.
(B.S.A. No. 171-52-SM)
S.D.
DENOTES APPROVED TYPE SMOKE DETECTOR
EXISTING PARTITION TO BE REMOVED
DENOTES 100 CMF EXHAUST FAN
DUCTED TO OUTSIDE.
PROVIDE FUSIBLE-LINK FIRE DAMPER
WHERE EXHAUST DUCTS
PASS THRU RATED CONSTRUCTION
EXISTING PARTITION TO REMAIN
NOTE:TO THE BEST OF MY KNOWLEDGE , BELIEF AND PROFESSIONAL JUDGMENT,THESE PLANS AND
SPECIFICATIONS ARE IN COMPLIANCE WITH THE ENERGY CONSERVATION CONSTRUCTION
CODE OF NEW YORK STATE, USING CHAPTER - CHAPTER IV
EXISTING: ONE FLOOR & CELLAR
PROPOSED DEVELOPMENT:
CONVERT TO COMMUNITY FACILITY-CHURCH
- REPAIR WALLS & PARTITIONS
- INSTALLATION NEW BOILER & 1 HOT WATER HEATER.
- INSTALLATION OF NEW PLUMBING AND FIXTURES
- INSTALLATION NEW DOORS & WINDOWS
SCOPE OF WORK
CONTRACTOR SHALL PROVIDE CONTROLLED INSPECTIONS IN ACCORDANCE
WITH APPLICABLE NYC BUILDING CODE PROVISIONS. WORK SUBJECT TO
CONTROLLED INSPECTIONS SHALL INCLUDE THE FOLLOWING:
SPECIAL INSPECTION
ENERGY CODE PROGRESS INSPECTION
TAB. REFERENCE 1RCNY
PROGRESS INSPECTIONSN
PROTECTION OF FOUNDATION INSULATION (IA1), (IIA1)
INSULATION PLACEMENT AND R VALUES(IA2), (IIA2)
FENESTRATION THERMAL VALUES AND RATINGS (IA3), (IIA3)
FENESTRATION RATINGS FOR AIR LEAKAGE (IA4), (IIA4)
FENESTRATION AREAS (IA5), (IIA5)
AIR SEALING AND INSULATION - VISUAL (IA6), (IIA6)
AIR SEALING AND INSULATION - TESTING (IA7)
PROJECTION FACTORS (IIA7)
LOADING DECK WEATHER SEALS (IIA8)
VESTIBULES (IIA9)
FIREPLACES (IB1), (IIB1)
DAMPERS INTEGRAL TO BUILDING ENVELOPE (IB2), (IIB2)
HVAC AND SERVICE WATER HEATING EQUIPMENT (IB3), (IIB3)
HVAC AND SERVICE WATER HEATING SYSTEM CONTROLS (IB4), (IIB4)
DUCT PLENUM AND PIPING INSULATION AND SEALING (IB5), (IIB5)
DUCT LEAKAGE TESTING (IB6), (IIB6)
ELECTRICAL METERING (IC1), (IIC1)
LIGHTING IN DWELLING UNITS (IC2), (IIC2)
INTERIOR LIGHTING POWER (IIC3)
EXTERIOR LIGHTING POWER (IIC4)
LIGHTING CONTROLS (IIC5)
EXIT SIGNS (IIC6)
TANDEM WIRING (IIC7)
ELECTRICAL MOTORS (IIC8)
TENANCE INFORMATION
PERMANENT CERTIFICATE
(ID1), (IID1)
(ID2)
SPECIAL INSPECTION CODE / SECTION
SOILS - SITE PREPARATION
BC 1704.7.1
SOILS - INVESTIGATIONS (BORINGS/TEST PITS)
TR4 BC 1704.7.4
PILE FOUNDATIONS & DRILLED
PIER INSTALLATION
TR5 BC 1704.8
MECHANICAL SYSTEMSBC 1704.15
STRUCTURAL SAFETY - STRUCTURAL STABILITY
BC 1704.19
SOIL PERCOLATION TEST - DRYWELL
BC 1704.20.1
SITE STORM DRAINAGE DISPOSAL
AND DETENTION SYSTEM INSTALLATION
BC 1704.20
HEATING SYSTEMS
BC 1704.23
FIRESTOP, DRAFTSTOP, AND FIREBLOCK SYSTEMS
BC 1704.25
PROGRESS INSPECTION ITEMS CODE / SECTION
FRAME INSPECTION
ENERGY CODE COMPLIANCE INSPECTIONS
BC 109.3.2BC 109.3.3
BC 109.3.5
FIRE-RESISTANCE RATED CONSTRUCTION
BC 109.3.4
X
X
X
X
X
X
CONCRETE - CAST-IN-PLACE BC 1704.4
SMOKE CONTROL SYSTEMSBC 1704.14X
X
X
X
AREA OF WORKSCALE N.T.S.
X
X
X
ZONING: R5MAP #: 31aBLOCK #: 15805LOT #: 25
100.00'
OPEN PORCH
down
BEACH 30th STREET
SCALE 1/16"=1'0"1
SITE PLAN
TAX LOT 25
SE
AG
IR
T A
VE
NU
E
# 202 BEACH 30th STREETBLOCK: 15805
LOT:25ZONE R5
MAP: 31A
95.0
0'
LINE
PARALL
EL W
ITH S
EAG
IRT
BLV
D.
EXISTING
RESIDENTIAL MULTI FAMILY
42' W
IDE
UPT
O F
INAL)
74.9'
32
.9'
15.00'
RAISED
CONC.
OPEN PORCH OPEN PORCH
(HUDSON AVE.) (50' WIDE)
RAMP UP
56.9'
cell steps
5.O8E
BRICKFENCE
90°
90°
chai
n lin
k fe
nce
FINAL
MAP
LINE
- C
ITY
OF
NEW
YO
RK
chai
n lin
k fe
nce
PROPOSEDCOMMUNITY FACILITY - PLACE OF WORSHIP.
C.LK.FC. ±0.1N
74.9'
LOCATION: # 202 B 30 STREET
ZONING DISTRICT: R5
MAP #: 31 A
BLOCK: 15805
LOT: 25
EXISTING 1 BUILDING, 4 UNITS, 1 FLOOR AND CELLAR.
PROPOSED DEVELOPMENT:
CONVERSION TO COMMUNITY FACILITY - (PLACE OF WORSHIP)
NO CHANGE IN BULK OF BUILDING.
-LOT AREA: 100'X95= 9,500 SF , CORNER LOT.
ZR 24-11 -F.A.R.: 2.0
-FLOOR AREA ALLOWED: 9,500X2.0 = 19,000 SF
-EXISTING FLOOR AREA :
-EXISTING CELLAR: (597.12 + 839.88 ) = 1,437.00 SF (NOT INCLUDED)
-EXISTING/PROPOSED FIRST FLOOR.: = 2,464.21 S.F.
2,464.21 S.F. < 19,000 SF O.K.
ZR 24-11 - MAX. LOT COVERAGE: 60% (CORNER LOT)
- REQUIRED L.C. = 60% x 9,500 = 5,700SF
- PROPOSED L.C. = 2,464.21 SF OR
2464.21/9,500 x 100 = 25.93% O.K
ZR 24-34 - FRONT YARDS
- REQUIRED 15' DEPTH.
-EXISTING: 5' & 15' DEPTH. O.K.
ZR 24-36 - REAR YARD
- REQUIRED NONE'
- EXISTING 10.16'
ZR 24-521 - HEIGHT & SETBACK
- REQUIRED : MAX. HEIGHT ABOVE FRONT YARD LINE: 35'
- HEIGHT ABOVE FRONT YARD LINE: 21'
ZR 25-31 - PARKING REQUIREMENT:
REQD. 1 PER 15 PERSONS
NEW/EXIST. AREA OF LARGEST PLACE OF ASSEMBLY: 47' x 31.75'= 1,492.25 SF
RATED CAPACITY: 10 SF / PERSON (BC TABLE 6-2)
1492.21 SF / 10 = 149 PERSONS
REQD. PARKING: 149 / 15 =10 SPACES ( ZR 25-31)
10 SPACES WAIVED
NO PARKING REQD.
NONE PROVIDED.
10.16'
RAISED
CONC.
1
2
3
4
RAMP UP
X
X
74.9'
32
.9' EXISTING 1ST FLOOR
EXISTING: 32.9' x 74.9' = 2,464.21 S.F.
EXIST/PROPOSED FIRST FLOOR:
PROPOSED: =2,464.21 S.F.TOTAL: =2,464.21 S.F.
Two (2) lamp, emergency light battery pack powered, NYC
approved.
12.0'1'-9"
6'-6
"
8'-10"
95.0
0'
THE ARCHITECT SHALL NOT HAVE CONTROL OR CHARGE OF AND
SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS,
DEVIATIONS, TECHNIQUES, SEQUENCES, OR PROCEDURES, OR FOR
SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE
WORK, FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR,
SUBCONTRACTORS OR ANY OTHER PERSONS PERFORMING ANY OF THE
WORK, OR FOR THE FAILURE OF ANY OF THEM TO CARRY OUT THE
WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. ALWAYS USE
DIMENSIONS AS SHOWN. DRAWINGS ARE NOT TO BE SCALED.
PROJECT
SEAL & SIGNATURE DATE:
PROJECT No:
DRAWING BY:
CHK BY:
T. AJAYI
B. AWOSIKA
DWG No:
CADO FILE No:
A R C H I T E C T S
C O N S U L T AN T SP L A N N E R S
BANJI AWOSIKA ARCHITECT P.C.
140-23 Queens Blvd.Jamaica, NY 11435Tel. 1(718) 657 5004Fax. 1(718) 657 2447
B
OF 6
No.
REVISION DATE
SHORING AREA & EXCAVATION DETAIL 03.22.101
D.O.B. No:
9/30/2014
202 BEACH 30 STREETFARROCKAWAY
QUEENS NY
SITE PLAN, NOTES
PR0POSED 1
EXIST. LIVING ROOM
EXIST KITCHEN
EXIST. LIVING ROOM
EXIST KITCHEN
CL.
CL.
CL.
EXIST. BEDROOM
EXIST. BEDROOM
EXIST. BATH EXIST. BATH
EXIST. BEDROOM
EXIST. BEDROOM
EXIST. LIVING ROOM
EXIST KITCHEN
EXIST. LIVING ROOM
EXIST KITCHEN
CL.
CL.
CL.
EXIST. BEDROOM
EXIST. BEDROOM
EXIST. BATHEXIST. BATH
EXIST. BEDROOM
EXIST. BEDROOM
SCALE 1/4"=1'0"
EXIST. CELLAR PLAN
SCALE 1/4"=1'0"
EXIST. FIRST FLOOR PLAN
CL.
CL.CL. CL.
CL
EXIST. MECH. ROOM
EXISTING STORAGE AREA EXISTING OPEN CELLAR
up
EXIST. CHIMNEY
FAV
CLOSET CLOSET
EXIST. (4)
ELECT
METER
EXIST. (1) GAS METER
W
UNEXCAVATED
EXIST. RAISED
PLATFORMEXIST
PRO
PERTY
LIN
EPR
OPE
RTY
LI
NE
PRO
PERT
LINE
EXISTING 9" THICK FOUNDATION WALL
EXIST. (1) WATER METER
100.00'
190.0
0'
6' HIGH
down
REMOVE EXISTING
PARTITIONS, DOOR,
TOILET, LAVATORY &
SHOWER .TOILET FIXT.
CAP CONNECTION
BELOW FLOOR,
PATCH-UP FLOOR
TO MATCH EXIST.
REMOVE EXISTING
PARTITIONS, DOOR,
TOILET, LAVATORY &
SHOWER .TOILET FIXT.
CAP CONNECTION
BELOW FLOOR,
PATCH-UP FLOOR
TO MATCH EXIST.
REMOVE EXISTING
PARTITIONS, DOOR,
TOILET, LAVATORY &
SHOWER .TOILET FIXT.
CAP CONNECTION
BELOW FLOOR,
PATCH-UP FLOOR
TO MATCH EXIST.
CL
REMOVE
EXIST KITCHEN
APPLIANCES
& SINK
REMOVE EXISTING
PARTITIONS, DOOR,
TOILET, LAVATORY &
SHOWER .TOILET FIXT.
CAP CONNECTION
BELOW FLOOR,
PATCH-UP FLOOR
TO MATCH EXIST.
EXISTING EXTERIOR WALLS
FIRST FLOOR: (74'-10'' X 2) + (32'-11" X 2) += 215.5 LF
WALLS REMOVED= 0 LF
TOTAL EXISTING EXTERIOR WALLS = 215.5 SF
TOTAL WALLS REMOVED = 0 L.F.
PERCENTAGE OF WALLS REMOVED
= 0 < 50.0% OK
I HEREBY CERTIFY THAT LESS THAN 50%
OF EXTERIOR WALLS ARE BEING DEMOLISHED
DEMO OF EXTERIOR WALLS
up
LANDING
up
R=6"
4 Risers @ 8"
3 [email protected]"3 [email protected]"
4 Risers @ 8"
up up
4 Risers @ 8"
4 Risers @ 8"
EXISTING
PARTITIONS & DOORS
TO BE REMOVED
(BY USING HAND TOOLS)
2
2
2
2
REMOVE
EXIST WINDOW AND SEAL WITH
BLOCKS
REMOVE
EXIST WINDOW AND SEAL WITH
BLOCKS
DEMOLITION FLOOR PLAN, NOTES
THE ARCHITECT SHALL NOT HAVE CONTROL OR CHARGE OF AND
SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS,
DEVIATIONS, TECHNIQUES, SEQUENCES, OR PROCEDURES, OR FOR
SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE
WORK, FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR,
SUBCONTRACTORS OR ANY OTHER PERSONS PERFORMING ANY OF THE
WORK, OR FOR THE FAILURE OF ANY OF THEM TO CARRY OUT THE
WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. ALWAYS USE
DIMENSIONS AS SHOWN. DRAWINGS ARE NOT TO BE SCALED.
PROJECT
SEAL & SIGNATURE DATE:
PROJECT No:
DRAWING BY:
CHK BY:
T. AJAYI
B. AWOSIKA
DWG No:
CADO FILE No:
A R C H I T E C T S
C O N S U L T AN T SP L A N N E R S
BANJI AWOSIKA ARCHITECT P.C.
140-23 Queens Blvd.Jamaica, NY 11435Tel. 1(718) 657 5004Fax. 1(718) 657 2447
B
OF 6
No.
REVISION DATE
SHORING AREA & EXCAVATION DETAIL 03.22.101
D.O.B. No:
202 BEACH 30TH STREET FAR ROCKAWAY
QUEENS NY
EXISTING STORAGE AREA
up
EXISTING OPEN CELLAR
NEW MECH. ROOM
up
up
EXIST. CHIMNEY
PRO
PERT
LINE
EXISTING 9" THICK FOUNDATION WALL
dn
EXIST. (4)
ELECT
METER
EXIST. (1) GAS METER
W
UNEXCAVATED
PRO
PERTY
LIN
EPR
OPE
RTY
LI
NE
PRO
PERT
LINE
CONTROLROOM H.C.
TOILETH.C.TOILET
RECEPTION
CHILDREN AREA
OFFICE
OFFICE
4 Risers @ 8"
3 Treads @11.5"
3 Treads @11.5"
4 Risers @ 8"up up
4 Risers @ 8"
3 Treads @11.5" 3 Treads @11.5"
4 Risers @ 8"
ACESSORY USE
NOT TO BE USED FOR LIVING,
SLEEPING,COOKING PURPOSES.
Room Area= 170 SF
Req'd Light(10%)= 17.0 SF
Req'd VA (5%)=7.3 SF
Room Area= 92.30 SF
Req'd Light(10%)= 9.23 SF
Req'd VA (5%)=4.6 SF
Room Area= 92.30 SF
Req'd Light(10%)= 9.23 SF
Req'd VA (5%)=4.6 SF
Room Area= 338.92 SF
Req'd Light(10%)= 33.89 SF
Req'd VA (5%)=16.94 SF
C.M.&S.D.
M.Vent
80 cfm
M.Vent
80 cfm
4
SCALE 1/4"=1'0"
EXIST. AND PROPOSED CELLAR FLOOR PLAN
SCALE 1/4"=1'0"
EXIST. AND PROPOSED FIRST FLOOR PLAN
OCCUPANCY BY MORE THAN 250 PERSONS IS DANGEROUS AND UNLAWFUL
Public Assembly License N0__________ Commissioner,
(where applicable) Dept. of Buildings, City of New
4 W
HE
AL
C
HE
IR
S
PA
CE
S
PROGRESS INSPECTIONS:PUBLIC ASSEMBLY EMERGENCY LIGHTING CODE/SECTION 28-116.2.2
4
wc
wc
1
SANCTUARY
12
34
56
1
2
3
4
5
6
116 PERSONSMOVEABLE SEATS
STA
GE
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
8 R
X 6
P
=
4
8 P
ER
SO
NS
up
4 Risers @ 8"
3 Treads 1.8'
RAISEDCONC.+6"
RAISEDCONC.+6"
EXIST. OPEN PORCH. EXIST. OPEN PORCH.EXIST. OPEN PORCH.
4
slope 1:12
In lieu of providing emergency lighting with battery packs, an emergency generator has
been provided as an additional source of power in the event of an emergency as per
Section 27-542 of the NYC Building Code.
No Place of Assembly shall be located within 250 feet of any occupancy containing
explosive contents.
For all Class 3 Exits, not more than forty percent (40%) of the Exit capacity shall be
discharged into those specifically designated exits as per the NYC Building Code,
Section c27-533(d)
Artificial lighting by eletrical means is provided and will be avaiable at all times.
GENERAL NOTES
4 WHEAL CHAIRS SPACES = 4 PERSONS
1 GENERAL AUDIENCE = 102 PERSONS
0 SEAT ON STAGE = 0 PERSONS
10 MISCELLANEOUS SEATING = 10 PERSONS
TOTAL 116 PERSONS
POSTED CAPACITY:- SIZE 12"W X 16"H (MIN.)
- LETTERING - RED ON WHITE BACKGROUND, ONE INCH HIGH.
- NUMERALS - ONE AND A QUARTER INCH HIGH.
concrete ram with guard rail@ 42" min. HT. A.F.F. Typ.
slope 1:12
2
BRICKFENCE
CHORISTERS
BAND
9 R
X 6
P
=
5
4 P
ER
SO
NS
1 1 1
DO
OR
E
XIT
C
AP
AC
IT
Y
54
P
ER
SO
NS
PR
IM
AR
Y
DIS
CH
AR
GE
S
DOOR EXIT CAPACITY
91 PERSONS
SECONDARY
DISCHARGES
DOOR EXIT CAPACITY
91 PERSONS
SECONDARY
DISCHARGES
C.M.&S.D.
C.M.&S.D.
C.M.&S.D.
C.M.&S.D.
C.M.&S.D.C.M.&S.D.
C.M.&S.D.
2
2
1
2 2 2 2 2 2
1
4
4
5
1
3
2
4
4
5
5
6
6
6
FLOOR PLAN, NOTES, DETAILS
THE ARCHITECT SHALL NOT HAVE CONTROL OR CHARGE OF AND
SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS,
DEVIATIONS, TECHNIQUES, SEQUENCES, OR PROCEDURES, OR FOR
SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE
WORK, FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR,
SUBCONTRACTORS OR ANY OTHER PERSONS PERFORMING ANY OF THE
WORK, OR FOR THE FAILURE OF ANY OF THEM TO CARRY OUT THE
WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. ALWAYS USE
DIMENSIONS AS SHOWN. DRAWINGS ARE NOT TO BE SCALED.
PROJECT
SEAL & SIGNATURE DATE:
PROJECT No:
DRAWING BY:
CHK BY:
T. AJAYI
B. AWOSIKA
DWG No:
CADO FILE No:
A R C H I T E C T S
C O N S U L T AN T SP L A N N E R S
BANJI AWOSIKA ARCHITECT P.C.
140-23 Queens Blvd.Jamaica, NY 11435Tel. 1(718) 657 5004Fax. 1(718) 657 2447
B
OF 6
No.
REVISION DATE
SHORING AREA & EXCAVATION DETAIL 03.22.101
D.O.B. No:
9/30/2014
257-19 147th DRIVE.
J: 257-19 147TH DRIVE
QUEENS
202 BEACH 30TH STREET FAR ROCKAWAY
QUEENS NY
EXIST & PROPOSED FRONT ELEVATION
SCALE 1/4"=1'0"
EXIST & PROPOSED REAR ELEVATION
SCALE 1/4"=1'0"
PROPOSED LEFT SIDE ELEVATION
SCALE 1/4"=1'0"
EXIST & PROPOSED RIGHT SIDE ELEVATION
NEW GUARD RAILING (BEYOND)
@ 42" MIN. HT. A.F.F. TYP.
NEW STUCCO FINISH TYP.
NEW STUCCO FINISH TYP.
NEW STUCCO FINISH TYP.
EXIST CELLAR FLOOR
EXIST. GRADE LEVEL
EXIST 1st FL. LEVEL
PROP. FRONT WALL HT.
PROP. ROOF LEVEL
EXIST. GRADE LEVEL
EXIST 1st FL. LEVEL
PROP. FRONT WALL HT.
PROP. ROOF LEVEL
SCALE 1/4"=1'0"
EXIST. GRADE LEVEL
EXIST 1st FL. LEVEL
PROP. FRONT WALL HT.
PROP. ROOF LEVEL
BRICK FINISH TYP.
NEW STUCCO FINISH TYP.
BRICK FINISH TYP.
BRICK FINISH TYP.
BRICK FINISH TYP.
ELEVATIONS, NOTES
THE ARCHITECT SHALL NOT HAVE CONTROL OR CHARGE OF AND
SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS,
DEVIATIONS, TECHNIQUES, SEQUENCES, OR PROCEDURES, OR FOR
SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE
WORK, FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR,
SUBCONTRACTORS OR ANY OTHER PERSONS PERFORMING ANY OF THE
WORK, OR FOR THE FAILURE OF ANY OF THEM TO CARRY OUT THE
WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. ALWAYS USE
DIMENSIONS AS SHOWN. DRAWINGS ARE NOT TO BE SCALED.
PROJECT
SEAL & SIGNATURE DATE:
PROJECT No:
DRAWING BY:
CHK BY:
T. AJAYI
B. AWOSIKA
DWG No:
CADO FILE No:
A R C H I T E C T S
C O N S U L T AN T SP L A N N E R S
BANJI AWOSIKA ARCHITECT P.C.
140-23 Queens Blvd.Jamaica, NY 11435Tel. 1(718) 657 5004Fax. 1(718) 657 2447
B
OF 6
No.
REVISION DATE
SHORING AREA & EXCAVATION DETAIL 03.22.101
D.O.B. No: J: 257-19 147TH DRIVE
QUEENS
202 BEACH 30TH STREET FAR ROCKAWAY
QUEENS NY
EXIST. CELLAR
NEW CONGREGATIONAL HALL
SECTION A-A
unexcavated
EXIST 2 x 10 WD. RAFTERS TYP
CLASS 'C' ROOF W/ 3/4" CDX PLYWOOD SHEATING,
15# SELF TABBING ASPHALT STRIP SHINGLES OVER
30# BUILDING PAPER (TYP.)
NEW ASPHALT SHINGLES TYP
NEW (1) HR FIRE RETED CEILING W/ (1) LAYER OF 5/8" TYPE 'X' G.W.B.
OVER WOOD FURRING STRIPS @ 16" O.C. (TYP)
NEW 2 x 8 WD. JOIST @ 16" 0.C
DENOTES EXTERIOR WALL CONSTRUCTED OF BRICKS
NEW 2 x 10 WD. RAFTERS TYP
CLASS 'C' ROOF W/ 3/4" CDX PLYWOOD, 15# SELF TABBING
ASPHALT STRIP SHINGLES OVER 30# BUILDING PAPER (TYP.)
H.C.TOILET
H.C.TOILET
H.C.TOILET OFFICE
SCALE 1/4"=1'0"
SECTION B-B
NEW MECHANICHAL ROOMEXISTING CELLAR
NEW CONGREGATIONAL HALL
REMOVED & REPLACE EXISTING (1) HR FIRE RATED CEILING W/
(1) LAYER OF 5/8" TYPE 'X' G.W.B. OVER WD. FURRING STRIPS @ 16" O.C.
EXISTING WOOD JOIST FLOOR TO REMAIN
NEW FIN. FLOOR
NEW 3/4 PLYWOOD SUB-FLOOR
SCALE 3/16"=1'0"3
EXIST. PROPOSED ROOF PLAN
REMOVED & REPLACE EXISTING FIBERGLASS INSUL.(R 19)
REMOVED & REPLACE EXISTING (1) HR FIRE RATED CEILING W/
(1) LAYER OF 5/8" TYPE 'X' G.W.B. OVER WD. FURRING STRIPS @ 16" O.C.
15# SELF TABBING ASPHALT STRIP
SHINGLES OVER 30# BUILDING
PAPERCLASS "A" ROOF OVER
3/4" CDX PLYWOOD SHEATING (TYP.)
NYC-MEA-120-79-M
2"x10" RAFTERS
@16" O.C. (TYP.)
2"x1
0" R
AF
TE
RS
@1
6" O
.C
. (T
YP
.)
2"x1
0" R
AF
TE
RS
@1
6" O
.C
. (T
YP
.)
2"x1
0" R
AF
TE
RS
@1
6" O
.C
. (T
YP
.)
2"x1
0" R
AF
TE
RS
@1
6" O
.C
. (T
YP
.)
SLO
PE
SLO
PE
EXIST. FOUNDATION 9" THICK WALL
concrete ram with guard rail@ 42" min. HT. A.F.F. Typ.
SCALE 3/16"=1'0"
SECTIONS, DETAILS
THE ARCHITECT SHALL NOT HAVE CONTROL OR CHARGE OF AND
SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS,
DEVIATIONS, TECHNIQUES, SEQUENCES, OR PROCEDURES, OR FOR
SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE
WORK, FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR,
SUBCONTRACTORS OR ANY OTHER PERSONS PERFORMING ANY OF THE
WORK, OR FOR THE FAILURE OF ANY OF THEM TO CARRY OUT THE
WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. ALWAYS USE
DIMENSIONS AS SHOWN. DRAWINGS ARE NOT TO BE SCALED.
PROJECT
SEAL & SIGNATURE DATE:
PROJECT No:
DRAWING BY:
CHK BY:
T. AJAYI
B. AWOSIKA
DWG No:
CADO FILE No:
A R C H I T E C T S
C O N S U L T AN T SP L A N N E R S
BANJI AWOSIKA ARCHITECT P.C.
140-23 Queens Blvd.Jamaica, NY 11435Tel. 1(718) 657 5004Fax. 1(718) 657 2447
B
OF 6
No.
REVISION DATE
SHORING AREA & EXCAVATION DETAIL 03.22.101
D.O.B. No:
202 BEACH 30TH STREET FAR ROCKAWAY
QUEENS NY