BCA SECTION 'J' COMPLIANCE
(J1) BUILDING FABRIC.ALL INSTALLED INSULATOIN TO COMPLY WITH AS4859.1ALL SKY LIGHTS TO WAREHOUSE TO COMPLY WITH PART J1.4 AND TO MANUFACTURER'S SPECIFICATION
ALL EXTERNAL OFFICE WALLS TO BE FITTED WITH WALLINSULATION WITH MIN. R1.0 VALUE AND IN ACCORDANCEWITH PART J1.5 OF BCA.
(J2) EXTERNAL GLAZING.
CONCRETE WALLS TO BE BATTENED OUT (20 TO 30mm GAP)LINED WITH 10mm PLASTERBOARD WALL AND INSULATEDTO MIN. R1.0 VALUE
INTERNAL WALL - NIL REQUIREMENT
FIRST FLOOR OPEN TO FRESH AIR - PROVIDE R1.5 INSULATION
FIRST FLOOR CLOSED UNDERSIDE - NIL REQUIREMENT
ALL EXTERNAL OFFICE GLAZING TO BE SINGLE LEAF WITHGREY TINTING, 6.38mm THICKNESS GREY 40 COMFORTPLUSGLASS. U VALUE 3.6 AND SHGC VALUE 0.50
ALL EXTERNAL GLAZING TO BE IN ACCORDANCE WITH BCASECTION 'J' AND AS1288-1999 AND AS2047
CONTRACTOR'S TO PROVIDE CERTIFICATE OF COMPLIANCESTATING THAT ALL WORKS COMPLIES WITH BCA VOLUME 1,2007 PART J2.
(J3) BUILDING SEALING
ALL OPENINGS TO A BUILDING SUCH AS ROOF, WALLS, DOORS,WINDOWS AND SERVICE PENETRATIONS TO BE SEALED BY MEANSOF SEALER, CAULKING OR SIMILAR APPROVED
(J4) AIR MOVEMENT
N/A
(J5) MECHANICAL VENTILATION & AIR CONDITIONING
MECHANICAL VENTILATION AND AIR-CONDITIONING TO COMPLY WITHPART J5 OF BCA 2007. CONTRACTORS TO PROVIDE CERTIFICATE OF COMPLIANCE STATING AIR CONDITIONING AND MECHANICAL VENTILATIONTO OFFICES AND TOILETS HAS BEEN COMPLY WITH BCA VOLUME 1, 2007 PART J5.
(J6) ARTIFICIAL LIGHTING AND POWER
ARTIFICIAL LIGHTING AND POWER TO COMPLY WITH PART J6 OF THE BCA 2007. CONTRACTOR'S TO PROVIDE CERTIFICATE OF COMPLIANCESTATING ALL LIGHTS AND POWER HAS BEEN INSTALLED IN ACCORDANCETO PART J6.1 TO J6.6 AND J6 OF THE BCA.
(J7) HOT WATER SUPPLY
CONTRACTOR'S TO PROVIDE COMPLIANCE CERTIFICATE STATINGHWS HAS BEEN INSTALLED IN ACCORDANCE WITH AS/NZS 3500 ANDBCA VOLUME 1, 2007, PART J7
(J8) ACCESS FOR MAINTENANCE
ALL SERVICES LOCATED IN THE ROOF MUST BE ACCESSIBLE WITHSUITABLE MEANS.
ALL WORKS MUSH COMPLY WITH PART J8.0 TO J8.2 OF THE BCA
CLIENT:
LOT 45 EFFICIENT DRIVETRUGANINA
PROPOSED WAREHOUSE
SITE:PROJECT:
SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE
25.01.2017 AS SHOWN
PTY. LTD.
6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]
group DWG NO.
AVC15250-A
DATE
JUL. 2015
REV. STATUS:
BP-5
DATEDESCRIPTIONNo. APPROVAL
REVISIONS
DATENo.
DEVELOPMENT
25436
1635
062
0030
00
3000
1025
012
300
1190018986
1234 30886
55005000
1000
5000
4697
PROPOSEDWAREHOUSE
3000
2600
5835
1000
6400
4900
2600 2600 2400 2400 2600 2600
2600
1000
21620
1485
3
321201500147121
2555
0
2555
0
21685
47121
4990
1756
0
2690 10696
94°42' 32.12M
184°
42'
25.5
5M
4°42
'10
.70M
49°5
9'21
.11M
94°42' 47.12M
VOID49
00
150mm
DP 150m
m
DP
150m
m
DP
150m
m
DP 150m
m
DP 150m
m
DP
GROUND LEVEL
SITE COVERAGE
SITE AREA
OFFICE
WAREHOUSE
(GROUND & FIRST FL)TOTAL FLOOR AREA
FIRST FLOOR
TOTAL GROUND FLOOR
485 SQ.M.
OFFICE
1,093 SQ.M.
71 SQ.M.
556 SQ.M.
94 SQ.M.
650 SQ.M.
E.P
T.P
S.P
SE
SW
STREET FIRE HYDRANT
STORMWATER PIT
STORMWATER GRATE
ELECTRICAL PIT
SEWER PIT
TELSTRA PIT
STREET LIGHT POLE
S.SSTREET SIGNAGE
STORMWATER PIT (SIDE ENTRY)SW
EXISTING LEVEL
PROPOSED LEVEL24.11
E.PL ELECTRICAL POLE
EXISTING TREE TO BE RETAINED
EXISTING TREE TO BE REMOVED
2100MM HEIGHT - BLACK PLASTIC COATED CHAIN WIRE MESH FENCE
PROPOSED FENCING
2100MM HEIGHT - BLACK PAINTED STEEL PICKET FENCE
CARPARKING REQUIRE7 SPACES
@1.3/100 SQ.M
CARPARKING SPACESPROVIDED ON SITE 8 SPACES
CARPARKING +1 SPACESSURPLUS OR SHORTFALL
CAR PARKING ANALYSIS
(GROUND & FIRST FL)TOTAL FLOOR AREA
650 SQ.M.
SUBTRACT30.4 SQ.M.LOADING BAY
SUBTRACT44.6 SQ.M.STAIRCASE/VOID
TOTAL NET FLOOR AREA 555.29 SQ.M.
SUBTRACT19.71 SQ.M.
TOILETS
@1.4/100 SQ.M
CLIENT:
LOT 45 EFFICIENT DRIVETRUGANINA
PROPOSED WAREHOUSE
SITE:PROJECT:
SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE
25.01.2017 AS SHOWN
PTY. LTD.
6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]
group DWG NO.
AVC15250-A
DATE
JUL. 2015
REV. STATUS:
BP-5
DATEDESCRIPTIONNo. APPROVAL
REVISIONS
DATENo.
DEVELOPMENT
1000
(TILE)
UP.
3 D
EG
. F
ALL
.047m
m T
RIM
DE
K H
I-T
EN
R
OO
FIN
G
3 D
EG
. F
ALL
.047m
m T
RIM
DE
K H
I-T
EN
R
OO
FIN
G
3 D
EG
. F
ALL
.047m
m T
RIM
DE
K H
I-T
EN
R
OO
FIN
G
3 D
EG
. F
ALL
.047m
m T
RIM
DE
K
HI-T
EN
R
OO
FIN
G
RIDGE LINE ABOVE
760MM WIDE FIBREGLASSROOFLIGHTS WITHSAFETY MESH UNDER
760MM WIDE FIBREGLASSROOFLIGHTS WITHSAFETY MESH UNDER
150mm
DP 150m
m
DP
150m
m
DP
150m
m
DP
150m
m
DP
150m
m
DP 150m
m
DP 150m
m
DP
900
900
VO
ID
REFER TO ENG. PLAN FOR MORE DETAILS
100mm THICK RC CONCRETE SLAB
SINK
6693
FRDG.
16
35
0
5450
150
18686
150
5525 6693 5913 6062
11750
30886
150
18986 11900
15
0
11
27
5
16
05
0
15
0
60
50
15
0
62
00
11
27
5
22
55
0
12
30
0
25136
150150
5913
5300
150
60626693 6693
25436
5525
30886
15
0
99
50
15
0
12
15
0
15
0
10
25
0
11
27
51
12
75
22
55
0
10
00
21
00
10
00
150
5700
W
920
ST
EE
L RO
OF
BE
AM
RE
FE
R T
O
EN
G. P
LAN
FO
R M
OR
E D
ET
AIL
920
T. H.B
870
920
920(TILE)
H.BT.
(TILE)
TOILET
LEGEND
EXIT
DISABLE
W
B
W.C DOORS
HINGES TO ALL
MUST BE PROVIDED
PROVIDE LIFT-OFF
NOTE:
OF DISPOSAL OF
ADEQUATE MEANS
NOTE:
FRL. WITH SOLID CORE
EXIT DOORS MUST BE
SANITARY TOWELS
NOTE:
ALL EXTERNAL WINDOW
DOOR AND SELF CLOSER
FIRE RATED TO 60/60/60
UNLESS ENCLOSED WITH
WHICH IS LOCATED BETWEEN
FACES A PERSON SEEKING
NO STORAGE UNDER STAIR
ACTION ON A SINGLE DEVICE
DOWNWARD ACTION OR PUSHING
EGRESS BY A SINGLE HAND
A KEY FROM THE SIDE THAT
0.9m-1.2m FROM THE FLOOR
NOTE:
READILY OPENABLE WITHOUT
ACCORDANCE WITH
AUSTRALIAN STANDARD
NOTE:
& BCA SECTION (J)
GLAZING TO BE
NOTE:
OUTSIDE AIR.
25 L/S DUCTED THRU
AIR-LOCK AT THE RATE OF
TO BE PROVIDED TO W.C &
MECHANICAL VENTILATION
SPECIFICATIONS REQUIRED PRIOR
TO INSTALLATION
AIR CONDITIONING TO ALL OFFICES
TO BE PROVIDED. TECHNICAL
NOTE:
CLIENT:
LOT 45 EFFICIENT DRIVETRUGANINA
PROPOSED WAREHOUSE
SITE:PROJECT:
SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE
25.01.2017 AS SHOWN
PTY. LTD.
6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]
group DWG NO.
AVC15250-A
DATE
JUL. 2015
REV. STATUS:
BP-5
DATEDESCRIPTIONNo. APPROVAL
REVISIONS
DATENo.
DEVELOPMENT
(TILE)
UP.
150m
m
DP
900
900
VO
ID
SINK
FRDG.
1150 3360 3780
90150
5360 2600
90
8290
1000
2180
1000
1890
1000
2180
1000
150
3500
90
6360
150
150
3690
90
6170
150
10250
400
5300
1000
2100
1000
1200
150
4070
90
1200
90
5600
90
1670
90
2000
150
150
4750
90
4990
W
920
920
T. H.B
870
920
920
90
900
(TILE)
H.BT.
(TILE)
530
530
1245
4265
5000
5405
VO
IDDWN.
T.S
INK
ROOF HATCH900x900
6420
300
3530
1000
2100
1000
1200
125
15300
125
15550
300
7020
6210
5910
125
5785
90
12004585
7503835
6000
5850
125
3535
90
2100
150
125
5725
150
6000
125
8775
1200
90
900
90
900
90
3255
125
125
5025
4950
90
900
90
900
90
3255
125
15550
300
W
870
870
475
195
6570
150m
m
DP
150m
m
DP
150m
m
DP
150m
m
DP
600Wx200D BOX GUTTER
600Wx200D BOX GUTTER
600Wx200D BOX GUTTER
ROOF HATCH900x900
3 D
EG
. F
AL
L
.0
47
mm
T
RIM
DE
K H
I-T
EN
R
OO
FIN
G
3 D
EG
. F
AL
L
.0
47
mm
T
RIM
DE
K H
I-T
EN
R
OO
FIN
G
3 D
EG
. F
AL
L
.0
47
mm
T
RIM
DE
K H
I-T
EN
R
OO
FIN
G
3 D
EG
. F
AL
L
.0
47
mm
T
RIM
DE
K H
I-T
EN
R
OO
FIN
G
3 D
EG
. F
AL
L
.0
47
mm
T
RIM
DE
K H
I-T
EN
R
OO
FIN
G
3 D
EG
. F
AL
L
.0
47
mm
T
RIM
DE
K
HI-T
EN
R
OO
FIN
G
3 D
EG
. F
AL
L
.0
47
mm
T
RIM
DE
K
HI-T
EN
R
OO
FIN
G
3 D
EG
. F
AL
L
.0
47
mm
T
RIM
DE
K
HI-T
EN
R
OO
FIN
G
760MM WIDE FIBREGLASSROOFLIGHTS WITHSAFETY MESH UNDER
760MM WIDE FIBREGLASSROOFLIGHTS WITHSAFETY MESH UNDER
760MM WIDE FIBREGLASSROOFLIGHTS WITHSAFETY MESH UNDER
REQUIREMENTS
AS PER BCA SECTION 'J'
PROVIDE ROOF INSULATION
150m
m
DP 150m
m
DP
150m
m
DP
150m
m
DP150m
m
DP
TOILET
LEGEND
EXIT
DISABLE
W
B
W.C DOORS
HINGES TO ALL
MUST BE PROVIDED
PROVIDE LIFT-OFF
NOTE:
OF DISPOSAL OF
ADEQUATE MEANS
NOTE:
FRL. WITH SOLID CORE
EXIT DOORS MUST BE
SANITARY TOWELS
NOTE:
ALL EXTERNAL WINDOW
DOOR AND SELF CLOSER
FIRE RATED TO 60/60/60
UNLESS ENCLOSED WITH
WHICH IS LOCATED BETWEEN
FACES A PERSON SEEKING
NO STORAGE UNDER STAIR
ACTION ON A SINGLE DEVICE
DOWNWARD ACTION OR PUSHING
EGRESS BY A SINGLE HAND
A KEY FROM THE SIDE THAT
0.9m-1.2m FROM THE FLOOR
NOTE:
READILY OPENABLE WITHOUT
ACCORDANCE WITH
AUSTRALIAN STANDARD
NOTE:
& BCA SECTION (J)
GLAZING TO BE
NOTE:
OUTSIDE AIR.
25 L/S DUCTED THRU
AIR-LOCK AT THE RATE OF
TO BE PROVIDED TO W.C &
MECHANICAL VENTILATION
SPECIFICATIONS REQUIRED PRIOR
TO INSTALLATION
AIR CONDITIONING TO ALL OFFICES
TO BE PROVIDED. TECHNICAL
NOTE:
1. CONTRACTOR SHALL HAVE A PLUMBER'S LICENSE WITH WORKMANSHIP WARRANTY AS PER THE PLUMBING INDUSTRY BOARD & MINISTERIAL ACT REQUIREMENTS.
ALL STORMWATER
4. ALL PIPE MATERIALS SHALL BE D.W.V (SEWER GRADE) AND NOMINATED SIZES USED IN
5. CRUSHED ROCK CLASS 2 - 20mm AGGREGATE SHALL BE USED FOR ALL TRENCH BEDDING
9. A ROAD OPENING PERMIT SHALL BE OBTAINED BY CONTRACTOR PRIOR TO WORKS COMMENCING.8. STAND-OFF BRACKETS SHALL BE USED AT 2-0m INTERVALS FOR ALL DOWNPIPES.
6. ALL TRENCHES TO BE BACKFILLED WITH CLASS 2-20mm AGGREGATE IN COMPACTED LAYERS.
2. ALL STORMWATER WORKS SHALL BE CARRIED OUT IN ACCORDANCE WITH AUSTRALIAN
7. ALL GRATED TRENCHES SHALL BE OF HEAVY DUTY MATERIAL.
3. ALL SURFACE R.L'S AND INVERT PIPES LEVELS SHALL BE VERIFIED BY THE CONTRACTOR
ACCORDANCE WITH THE HYDRAULIC PLAN PROVIDED.
OF DISCHARGETO LEGAL POINT
NOTE:
TO BE CONNECTED
ENERGY EFFICIENCY REQUIREMENTS
STANDARDS AS.3500 3.2/1998.
PRIOR TO WORKS COMMENCING
WALLS - EXTERNAL
INSULATED TO R3.2ROOF / CEILING
BUILDING FABRIC 'R' RATING
LINED WITH PLASTER BOARD
OUT (20mm TO 35mm GAP)
CONCRETE WALLS BATTENED
NIL REQUIREMENTS
(OPEN TO UNDERSIDE)
WALLS - INTERNAL
INSULATED TO R1.0
GLAZING NEEDS TO COMPLY
FIRST FLOOR INSULATED R1.5
FIRST FLOOR
1, 2007.
(CLOSED TO UNDERSIDE)
NIL REQUIREMENTS
EXTERNAL GLAZING
VOL. 1, 2007 PART J2"
CERTIFICATE OF COMPLIANCE
GLAZIER TO PROVIDE
STATING THAT "EXTERNAL
WITH SECTION 'J' OF BCA VOL.
ACCESSIBLE WITH SUITABLE
GLAZING COMPLIES WITH BCA
CERTIFICATE OF COMPLIANCE
IN THE ROOF MUST BE
AIR CONDITIONING
CONDITIONING PROVIDES
STATING THAT "AIR
PLUMBER TO PROVIDE
VENTILATION TO THE OFFICES
MEANS.
LIGHTS & POWER HAS BEEN
LIGHTS & POWER HAS BEEN
VENTILATION TO THE OFFICES
PROVIDED TO COMPLY WITH
BCA VOL. 1, 2007 PART J5"
AS REQUIRE REFER TO NATURAL
PLUMBER TO PROVIDE
CERTIFICATE OF COMPLIANCE
STATING THAT "HWS
COMPLIES WITH AS/NZS
3500 AND BCA VOL. 1, 2007
PART J7
HOT WATER SUPPLY
ALL SERVICES LOCATEDACCESS FOR
MAINTENANCE
PROVIDE ROOF VENTILATION
VENTILATION ANANYSIS
NOTE:
CLIENT:
LOT 45 EFFICIENT DRIVETRUGANINA
PROPOSED WAREHOUSE
SITE:PROJECT:
SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE
25.01.2017 AS SHOWN
PTY. LTD.
6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]
group DWG NO.
AVC15250-A
DATE
JUL. 2015
REV. STATUS:
BP-5
DATEDESCRIPTIONNo. APPROVAL
REVISIONS
DATENo.
DEVELOPMENT
F.L
80
00
30
00
N.G.L
C.L
F.L
C.L3
00
06
00
14
00
PARAPET
4
0
0
0
W
x
4
8
0
0
H
R
O
L
L
E
R
D
O
O
R
SCALE 1:100
WEST ELEVATIONA A1
A1A1C C
F
D D D D D
E E EB
B
B
D D
F.L
80
00
30
00
N.G.L
C.L
F.L
C.L
30
00
60
01
40
0
PARAPET
4
0
0
0
W
x
4
8
0
0
H
R
O
L
L
E
R
D
O
O
R
SCALE 1:100
NORTH ELEVATIONA A1 A A
A1 A1 A1A A C
B
B
B
D D
E
A1
D
D
F
F.L
80
00
30
00
N.G.L
C.L
F.L
C.L
30
00
60
01
40
0
PARAPET
SCALE 1:100
EAST ELEVATION
A1 A1 A1 A1
F.L
80
00
30
00
N.G.L
C.L
F.L
C.L
30
00
60
01
40
0
PARAPET
SCALE 1:100
SOUTH ELEVATION
A1 A1 A1
A
D D
E
C
A1
A1
A1
C
MATERIAL & COLOUR FINISHES SCHEDULE
A1
LEGEND
A
EWOODLAND GREY
COLOURBOND
BLACK
DARK GREY TINTED
COLOUR
DOOR
DSPANDREL GLAZING
COLOURBOND ROLLER
TO COMPLY WITH ENERGY RATINGTINTED WINDOW GLAZING
EXTERNAL MATERIAL
CONCRETE WALLTEXTURE PAINTED
TEXTURE PAINTEDCONCRETE WALL
DULUX, SMOKEBUSH
B
F
ALUMINIUM CLADDING
COLOURBOND CLADDING
SILVER
BLACK
DULUX, HOMEBUSH
COLOURBOND
CLIENT:
LOT 45 EFFICIENT DRIVETRUGANINA
PROPOSED WAREHOUSE
SITE:PROJECT:
SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE
25.01.2017 AS SHOWN
PTY. LTD.
6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]
group DWG NO.
AVC15250-A
DATE
JUL. 2015
REV. STATUS:
BP-5
DATEDESCRIPTIONNo. APPROVAL
REVISIONS
DATENo.
DEVELOPMENT
80
00
30
00
30
00
60
01
40
0
PARAPET
C.L
F.L
C.L
F.L
N.G.L
AS REQUIREDPROVIDE CAPPING3 DEG. FALL
.047mm TRIMDEK HI-TEN ROOFING
STEEL MESH SUPPORTOVER ALUMINIUM SISALATION
PROVIDE FLASHING& CAPPINGAS REQUIRED
LINE OF WALL BEYOND
REFER TO ENG DWG FOR DETAILSROOF BEAM & PURLINS
ON STEEL BRACKETS, FLASHING & CAPPINGAS REQUIRED
600Wx150D BOX GUTTER
REFER TO ENG. DETAILSRC FOOTINGS & SLAB
REFER TO ENG. DETAILSRC FOOTINGS & SLAB
CONCRETE150mm THICK
PANEL WALL
150mm DIA DOWNPIPE
CONCRETE150mm THICK
PANEL WALL
150mm DIA DOWNPIPE
REFER TO ENG DWG FOR DETAILSROOF BEAM & PURLINS
SECTION A-ASCALE 1:100
PROVIDE FLASHING& CAPPINGAS REQUIRED
8000
3000
3000
600
1400
PARAPET
C.L
F.L
C.L
F.L
N.G.L
16. LANDING
1.
20. LANDING
AS REQUIRED
PROVIDE FLASHING& CAPPING
REFER TO ENG. PLANSTEEL FASCIA TRUSS
FOR FURTHER DETAILS
TO BCA SECTION (J) &AS STANDARDS
ALUMINIUM FRAMED WINDOW IN ACCORDANCE
ALUMINIUM FRAMEDSPANDREL GLAZING
COLOURBOND CLADDING REFER TO MATERIAL & FINISHES SCHEDULE
FLASHING & CAPPING AS REQUIREDON STEEL BRACKETS, 600Wx150D BOX GUTTER
AS REQUIREDPROVIDE CAPPING
LINE OF WALL BEYOND
OVER ALUMINIUM SISALATION0.47mm TRIMDEK HI-TEN ROOFING3 DEG. FALL
STEEL MESH SUPPORT BLANKET TO OFFICE ROOF AREA PROVIDE 50mm INSULATION
PROVIDE R3.2 ROOFINSULATION TO ALL OFFICEROOF AREAS FLASHING & CAPPING
ON STEEL BRACKETS, 600Wx150D BOX GUTTER
AS REQUIRED
AS REQUIRED
PROVIDE FLASHING& CAPPING
COLOURBOND CLADDING REFER TO MATERIAL & FINISHES SCHEDULE
PROVIDE WATERPROOFSILICONE
REFER TO ENG. PLANSTEEL FASCIA TRUSS
FOR FURTHER DETAILS
TO BCA SECTION (J) &AS STANDARDS
ALUMINIUM FRAMED WINDOW IN ACCORDANCE
ALUMINIUM CLADDING REFER TO MATERIAL & FINISHES SCHEDULE
FEATURE BOXING
PROVIDE WATERPROOFSILICONE
SPANDREL GLAZINGALUMINIUM FRAMED
ALUMINIUM CLADDING REFER TO MATERIAL & FINISHES SCHEDULE
FEATURE BOXING
CONCRETE PANEL150mm THICK
REFER TO ENG. DETAILSRC FOOTINGS & SLABREFER TO ENG. DETAILS
RC FOOTINGS & SLAB
90x45 MGP10 TIMBER
WITH PAINTED 10mm THICK P'BOARD
FRAME WALL @ 450 CTRS.
STEEL BEAM & PURLIN
DETAILSREFER TO ENG. DESIGN &
90x45 MGP10 TIMBER
WITH PAINTED 10mm THICK P'BOARD
FRAME WALL @ 450 CTRS.
1000
WALL @ 450 CTRS. WITH BOTH90x45 MGP10 TIMBER FRAMED
AT 1000 HIGH FROM F.F.L
SIDE P'BOARD PAINTED FINISH
T&G TIMBER19mm THICK
FLOOR BOARDST&G TIMBER19mm THICK
FLOOR BOARDS
PROVIDE COLOURBONDSOFFIT LINING TO UNDERSIDEOF CARPARK
CONCRETE PANEL150mm THICK
MANUFACTURES SPECIFICATIONS DETAILS
SUSPENDED CEILING TO19mm PLASTERBOARD
SECTION B-BSCALE 1:50
8000
3000
3000
600
1400
PARAPET
C.L
F.L
C.L
F.L
N.G.L
AS REQUIRED
PROVIDE FLASHING& CAPPING
REFER TO ENG. PLANSTEEL FASCIA TRUSS
FOR FURTHER DETAILS
COLOURBOND CLADDING REFER TO MATERIAL & FINISHES SCHEDULE
TO BCA SECTION (J) &AS STANDARDS
ALUMINIUM FRAMED WINDOW IN ACCORDANCE
ALUMINIUM FRAMEDSPANDREL GLAZING
STEEL BEAM & PURLIN
DETAILSREFER TO ENG. DESIGN &
MANUFACTURES SPECIFICATIONS DETAILS
SUSPENDED CEILING TO19mm PLASTERBOARD
19mm THICK T&G TIMBERFLOOR BOARDS
90x45 MGP10 TIMBER
WITH PAINTED 10mm THICK P'BOARD
FRAME WALL @ 450 CTRS.
1000
CONCRETE PANEL150mm THICK
REFER TO ENG. DETAILSRC FOOTINGS & SLAB
OVER ALUMINIUM SISALATION0.47mm TRIMDEK HI-TEN ROOFING3 DEG. FALL
STEEL MESH SUPPORT
PROVIDE R3.2 ROOFINSULATION TO ALL OFFICEROOF AREAS
BLANKET TO OFFICE ROOF AREA PROVIDE 50mm INSULATION
LINE OF WALL BEYOND
SECTION C-CSCALE 1:50
CLIENT:
LOT 45 EFFICIENT DRIVETRUGANINA
PROPOSED WAREHOUSE
SITE:PROJECT:
SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE
25.01.2017 AS SHOWN
PTY. LTD.
6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]
group DWG NO.
AVC15250-A
DATE
JUL. 2015
REV. STATUS:
BP-5
DATEDESCRIPTIONNo. APPROVAL
REVISIONS
DATENo.
DEVELOPMENT
WITH LAMINEX
ABOVE BENCH TOP150H TILEPROVIDE
580 50530
600
TYPICAL KITCHEN CABINET
BENCH TOPBENCH TOP
FINISH TO DOOR
SELECTED 16MM
AND CABINET
THICK MDF OVER
WITH
FINISH
20mm
LAMINEX
SELCTED
BY OWNER
PLUMBING
MDF OVER
FIXTURES
SELECTED
900
SCALE 1:50SCALE 1:50TYPICAL VANITY UNIT
THICK MDF OVER
380
900
50
150
750
FINISH TO DOOR
450
430
WITH LAMINEX
SELECTED 16MM
BY OWNER
SELCTED AND CABINET
PLUMBINGSELECTED
20mm
FIXTURES
LAMINEXWITH MDF OVER
150H TILE
FINISH
PROVIDE
EQ
730
580
ABOVE BENCH TOP
EQ
EQ
EQ
150
THICK MDF OVER
TYPICAL CABINET ELEVATION
SELECTED 16MM
FINISH TO DOOR
1600
PLUMBING
BY OWNERFIXTURES
SELECTEDWITH LAMINEX
AND CABINET
SCALE 1:50
LAMINEX
150H TILE
SELCTED
ABOVE BENCH TOP
PROVIDE
WITH
FINISHBENCH TOP
20mm MDF OVER
150
630
EQ 150
120
900
EQ
EQ
EQEQEQ EQ
616
2216
UP.
VO
ID
901200
90
4950
120090
1290
1200750
3750
1200
SELECTED STEEL HANDRAILREFER TO MANUFACTURER'SFOR FURTHER DETAILS
SELECTED TIMBER STRINGER,TREAD AND RISER
TACTILE GROUND SURFACE
INDICATOR MUST BE PROVIDED
IN ACCORDANCE WITH AS 1428.4
SCALE 1:50
VO
ID
DWN.
SCALE 1:50
1200
750 1200
1950
3750
1200
4950
90
5040
1200
3750
1200
9036
6090
750
120090
660
1290660
3750
1290
SELECTED STEEL HANDRAIL REFERTO MANUFACTURER'S FOR FURTHER DETAILS
SELECTED TIMBER STRINGER, TREAD AND RISER
TACTILE GROUND SURFACE
INDICATOR MUST BE PROVIDED
IN ACCORDANCE WITH AS 1428.4
16. LANDING
1.
20. LANDING
600
3000
3600
F.L
C.L
F.L
1000
900
NOTE:
TIMBER STAIR REFER TO
MANUFACTURER'S FOR
FURTHER DETAILS &
INSTALLATION
SELECTED TIMBER STRINGER,TREAD AND RISER
TIMBER FRAMED BALUSTRADEWALL @ 1000H.
SELECTED STEEL HANDRAILREFER TO MANUFACTURER'SFOR FURTHER DETAILS
TIMBER FRAMED BALUSTRADEWALL @ 1000H.
810
920
450 - 460
1900 MIN
700
MIN
800
MIN
300
MIN
1450
MIN
330
MIN
2300
MIN
425 MIN530 MIN
850 MIN
450 MIN
1400
MIN
1400 MIN 300 250
425
50375
684 90
0
70050 850
890 170
900
MA
X
350 MIN
125 - 150
425 MIN80
0 -
830
900
- 10
001850
MIN
PLAN
870
65080
040
0
400
610-660
200
460
400
50 50
SCALE 1:50AMBULANT DISABILITIES TOILET
900
PLAN ELEVATION
38MM DIA. STAINLESS
FOR FIXING DETAILS
STEEL GRABRAIL. REFER SAFETY RAILS AUSTRALIS P/L
610
- 66
090
0
CIRCULATION SPACE(DOOR MUST NOT INTRUDE)
STANDARD PROJECTION FOR WC
900
460
- 48
0
300MAX
MAX.
HAND RAIL
STRINGER
STRINGER
BA
LUS
TR
AD
E
BA
LUS
TR
AD
E
GOING RIS
ER
CLIENT:
LOT 45 EFFICIENT DRIVETRUGANINA
PROPOSED WAREHOUSE
SITE:PROJECT:
SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE
25.01.2017 AS SHOWN
PTY. LTD.
6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]
group DWG NO.
AVC15250-A
DATE
JUL. 2015
REV. STATUS:
BP-5
DATEDESCRIPTIONNo. APPROVAL
REVISIONS
DATENo.
DEVELOPMENT
32 AMPS 3 PHASE OUTLETS
ELECTRICAL LEGEND
MECHANICAL EXAUST FAN
HIGH BAY 400 WATT METAL HALIDE FITTING TO BE
SELECTED LED DOWN LIGHTS
80 WATT METAL HALIDE WALL MOUNTED
TELEVISION
TELEPHONE
SWITCHED IN PAIRS
WITH WIRE GUARD 1200x300 (T5-1x28W)
EXIT SIGNS
SWITCHBOARD
EMERGENCY LIGHTING
1x36W MAINTAINED)
1 x BATTEN FLUORESCENT CEILING MOUNTED
T-BAR TROFFER FLUORESCENT RECESSED CEILING 1200x300 (T5-2x28W) WITH DIFFUSER COVER
WARE HOUSE AREA (BT136NWG 1x36W
STAIRWELLS AREA (BT218MPR 2x18W)
(2x18W QUICKFIT EXIT, SUSTAINED,150mm LETTERING, NI-CAD BATTERIES)
CAT 5 DATA CABLE
DOUBLE GPO
EXTERNAL SINGLE GPO
PH3
LEGEND
CLIENT:
LOT 45 EFFICIENT DRIVETRUGANINA
PROPOSED WAREHOUSE
SITE:PROJECT:
SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE
25.01.2017 AS SHOWN
PTY. LTD.
6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]
group DWG NO.
AVC15250-A
DATE
JUL. 2015
REV. STATUS:
BP-5
DATEDESCRIPTIONNo. APPROVAL
REVISIONS
DATENo.
DEVELOPMENT