6
OPzV solar.power Valve regulated lead-acid batteries for cyclic applications Similar to the illustration Typical applications of HOPPECKE OPzV solar.power Solar-/Off-grid applications Power supply for remote off-grid applications and isolated power networks, drinking water supply systems, healthcare facilities Telecommunications Mobile phone stations BTS-stations Off-grid/on-grid solutions Traffic systems Signalling systems Lighting Motive Power Systems Reserve Power Systems Special Power Systems Service Your benefits with HOPPECKE OPzV solar.power Maintenance-free regarding water refilling - due to innovative Gel-technology Very high cycle stability during PSoC 1 operation - due to tubular plate design with efficient charge current acceptance Maximum compatibility - dimensions according to DIN 40742 Optimal space utilization - due to horizontal arrangement and stacking Higher short-circuit safety even during the installation - based on HOPPECKE system connectors

BATERIAS

Embed Size (px)

Citation preview

Page 1: BATERIAS

OPzV solar.powerValve regulated lead-acid batteries for cyclic applications

Sim

ilar

to t

he il

lust

ratio

n

Typical applicationsof HOPPECKE OPzV solar.power

■ Solar-/Off-grid applications Power supply for remote off-grid

applications and isolated power networks, drinking water supply systems, healthcare facilities

■ Telecommunications Mobile phone stations

BTS-stationsOff-grid/on-grid solutions

■ Traffi c systems Signalling systems

Lighting

Motive Power Systems

Reserve Power SystemsSpecial Power Systems

Service

Your benefi ts with HOPPECKE OPzV solar.power

■ Maintenance-free regarding water refi lling - due to innovative Gel-technology

■ Very high cycle stability during PSoC1 operation - due to tubular plate design with effi cient charge current acceptance

■ Maximum compatibility - dimensions according to DIN 40742

■ Optimal space utilization - due to horizontal arrangement and stacking

■ Higher short-circuit safety even during the installation - based on HOPPECKE system connectors

Page 2: BATERIAS

Form

OPz

V so

lar.

pow

er E

N/0

3.12

/2 K

P

rinte

d in

Ger

man

y

All

deta

ils in

thi

s br

ochu

re a

re b

ased

on

stat

e-of

-the

-art

tec

hnol

ogy.

Our

pro

duct

s ar

e su

bjec

t to

con

stan

t de

velo

pmen

t. W

e th

eref

ore

rese

rve

the

right

to

mak

e ch

ange

s.

Type overviewCapacities, dimensions and weights

OPzV solar.power

Type C100/1.85 V C50/1.85 V C24/1.83 V C10/1.80 V C5/1.77 V max. Weight max.* Length L max.* Width W max.* Height H Fig. Ah Ah Ah Ah Ah kg mm mm mm

4 OPzV solar.power 250 286.9 263.5 243.0 204.1 188.7 18.3 105 208 420 A 5 OPzV solar.power 310 358.6 329.3 303.8 255.1 235.8 22.3 126 208 420 A 6 OPzV solar.power 370 430.3 395.2 364.6 306.1 283.0 26.5 147 208 420 A 5 OPzV solar.power 420 478.2 452.9 427.8 391.4 346.1 29.9 126 208 535 A 6 OPzV solar.power 520 573.9 543.4 513.4 469.7 415.3 35.1 147 208 535 A 7 OPzV solar.power 620 669.5 634.0 599.0 548.0 484.5 42.1 168 208 535 A 6 OPzV solar.power 750 847.3 802.2 762.1 682.0 595.0 48.7 147 208 710 A 8 OPzV solar.power 1000 1129.8 1069.6 1016.2 909.3 793.3 65.9 215 193 710 B10 OPzV solar.power 1250 1412.2 1337.0 1270.2 1136.7 991.7 80.5 215 235 710 B12 OPzV solar.power 1500 1694.7 1604.4 1524.2 1364.0 1190.0 94.6 215 277 710 B12 OPzV solar.power 1700 1955.0 1870.0 1784.9 1544.6 1371.9 110.0 215 277 840 B16 OPzV solar.power 2300 2606.7 2493.3 2379.8 2059.5 1829.2 152.9 215 400 815 C20 OPzV solar.power 2900 3258.3 3116.7 2974.8 2574.3 2286.5 186.5 215 490 815 D24 OPzV solar.power 3500 3910.0 3740.0 3569.8 3089.2 2743.8 222.3 215 580 815 D

16 OPzV solar.power 2300 20 OPzV solar.power 2900 -24 OPzV solar.power 3500

W

L

W

L

4 OPzV solar.power 250 -6 OPzV solar.power 750

8 OPzV solar.power 1000 -12 OPzV solar.power 1700

W

L

W

L

Fig. A Fig. B

Fig. CFig. D

H

C100, C50, C24, C10 and C5 = Capacity at 100 h, 50 h, 24 h, 10 h and 5 h discharge* according to DIN 40742 data to be understood as maximum values

Optimal environmental compatibility - closed loop for recovery of materials in an accredited recycling system

IEC 60896-21IEC 61427 1 Partial State of Charge

0 10 20 30 40 50 60 70 80 90

9000

8000

7000

6000

5000

4000

3000

2000

1000

0

Depth of Discharge DoD [%]

Service life in cycles and Depth of Discharge

Num

ber

of c

ycle

s [n

]

HOPPECKE Batterien GmbH & Co. KG

P.O. Box 1140 · D-59914 Brilon · Germany Bontkirchener Straße 1 · D-59929 Brilon-Hoppecke

Phone +49(0)2963 61-374 Email [email protected] Fax +49(0)2963 61-270 www.hoppecke.com

Page 3: BATERIAS

OPzV bloc solar.powerValve regulated lead-acid batteries for cyclic applications

Sim

ilar

to t

he il

lust

ratio

n

Typical applications of HOPPECKE OPzV bloc solar.power

■ Solar/Off-grid and Leisure Applications

Isolated holiday homes, cottages, alpine huts

■ Storage for direct consumption of photovoltaic (PV) energy

■ Traffi c systems Signalling systems

Lighting

■ Telecommunications Mobile phone stations

BTS-stationsOff-grid/on-grid solutions

Motive Power Systems

Reserve Power SystemsSpecial Power Systems

Service

Your benefi ts with HOPPECKE OPzV bloc solar.power

■ Maintenance-free regarding water refi lling - due to innovative Gel-technology

■ Very high cycle stability during PSoC1 operation - due to tubular plate design with effi cient charge current acceptance

■ Maximum compatibility - dimensions according to DIN 40744

■ Easy assembly and installation - battery lid with integral handle

■ Higher short-circuit safety even during the installation - based on HOPPECKE system connectors

Page 4: BATERIAS

Type overviewCapacities, dimensions and weights

Form

OPz

V bl

oc s

olar

.pow

er E

N/0

3.12

/1 K

P

rinte

d in

Ger

man

y

All

deta

ils in

thi

s br

ochu

re a

re b

ased

on

stat

e-of

-the

-art

tec

hnol

ogy.

Our

pro

duct

s ar

e su

bjec

t to

con

stan

t de

velo

pmen

t. W

e th

eref

ore

rese

rve

the

right

to

mak

e ch

ange

s.

OPzV bloc solar.power

Fig. A Fig. B

6 V 4 OPzV bloc solar.power 250 - 6 V 6 OPzV bloc solar.power 370

L L

W W

H H

12 V 1 OPzV bloc solar.power 70 - 12 V 3 OPzV bloc solar.power 180

Type C100/1.85 V C50/1.85 V C24/1.83 V C10/1.80 V C5/1.77 V Max. Weight max.* Length L max.* Width W max.* Height H Fig. Ah Ah Ah Ah Ah kg mm mm mm

12V 1 OPzV bloc solar.power 70 70.0 65.0 57.6 51.0 45.0 40.0 272 205 383 A12V 2 OPzV bloc solar.power 120 130.0 125.0 117.6 103.0 90.5 52.5 272 205 383 A12V 3 OPzV bloc solar.power 180 200.0 190.0 175.2 154.0 135.5 75.5 380 205 383 A 6V 4 OPzV bloc solar.power 250 270.0 250.0 235.2 205.0 181.0 51.0 272 205 383 B 6V 5 OPzV bloc solar.power 300 330.0 315.0 292.8 250.0 226.0 66.0 380 205 383 B 6V 6 OPzV bloc solar.power 370 400.0 375.0 350.4 308.0 271.5 73.0 380 205 383 B

C100, C50, C24, C10 and C5 = Capacity at 100 h, 50 h, 24 h, 10 h and 5 h discharge* according to DIN 40744 data to be understood as maximum values

Optimal environmental compatibility - closed loop for recovery of materials in an accredited recycling system

IEC 60896-21IEC 61427 1 Partial State of Charge

0 10 20 30 40 50 60 70 80 90

8000

7000

6000

5000

4000

3000

2000

1000

0

Depth of Discharge DoD [%]

Service life in cycles and Depth of Discharge

Num

ber

of c

ycle

s [n

]

HOPPECKE Batterien GmbH & Co. KG

P.O. Box 1140 · D-59914 Brilon · Germany Bontkirchener Straße 1 · D-59929 Brilon-Hoppecke

Phone +49(0)2963 61-374 Email [email protected] Fax +49(0)2963 61-270 www.hoppecke.com

Page 5: BATERIAS

OPzV solar.powerSealed lead-acid batteryfor cyclic applications

Your benefi ts with HOPPECKE OPzV solar.power

■ Maintenance-free with regard to water refi lling - due to innovative Gel-technology

■ Very high discharge cycle stability during Partial State of Charge operation - due to tubular plate design with effi cient charge current acceptance

■ Optimal space utilization - due to horizontal arrangement and stacking

■ Higher external short-circuit safety during installation and operation - based on fully insulated intercell connectors

Motive Power Systems

Reserve Power SystemsSpecial Power Systems

Service

Typical applicationsof HOPPECKE OPzV solar.power

■ Solar-/Off-grid applications Power supply for remote off-grid

applications and isolated power networks

■ Telecommunications Cell phone sites, central offi ce

installations

■ Traffi c systems Signalling systems, lighting

Sim

ilar

to t

he il

lust

ratio

n

Page 6: BATERIAS

OPzV solar.power

Form

OPz

V so

lar.

pow

er U

S/0

4.11

/2 K

P

rinte

d in

Ger

man

y

All

deta

ils in

thi

s br

ochu

re a

re b

ased

on

stat

e-of

-the

-art

tec

hnol

ogy.

Our

pro

duct

s ar

e su

bjec

t to

con

stan

t de

velo

pmen

t. W

e th

eref

ore

rese

rve

the

right

to

mak

e ch

ange

s.

Type overviewCapacities, dimensions and weights

Head Offi ceHOPPECKE Batterien GmbH & Co. KG

P.O. Box 1140 · D-59914 Brilon · GermanyBontkirchener Straße 1 · D-59929 Brilon-Hoppecke

Phone: + 49 (0) 29 63 61-3 74 Email: [email protected]: + 49 (0) 29 63 61-2 70 Internet: www.hoppecke.com

SubsidiaryHOPPECKE Batteries Inc.

1960 Old Cuthbert Road, Suite 130Cherry Hill, NJ 08034 · USA

Phone: + 1 856-616-0032 Email: [email protected]: + 1 856-616-0132 Internet: www.hoppecke-us.com

TypeC

8/1.75 V @

25 °C/77 °F AhC

100/1.85 V @

25 °C/77 °F AhC

100/1.85 V @

20 °C/68 °F Ahmax. Weight

kg/lbsmax.* Length L

mm/inchmax.* Width W

mm/inchmax.* Height H

mm/inchFig.

4 OPzV solar.power 250 208 258 250 20.0 / 44.1 105 / 4.13 208 / 8.19 420 / 16.54 A

5 OPzV solar.power 310 259 319 310 24.0 / 52.9 126 / 4.96 208 / 8.19 420 / 16.54 A

6 OPzV solar.power 370 312 381 370 28.0 / 61.7 147 / 5.79 208 / 8.19 420 / 16.54 A

5 OPzV solar.power 420 394 453 440 31.0 / 68.3 126 / 4.96 208 / 8.19 535 / 21.06 A

6 OPzV solar.power 520 472 577 560 37.0 / 81.6 147 / 5.79 208 / 8.19 535 / 21.06 A

7 OPzV solar.power 620 551 680 660 42.0 / 92.6 168 / 6.61 208 / 8.19 535 / 21.06 A

6 OPzV solar.power 750 691 834 810 50.0 / 110.2 215 / 8.46 208 / 8.19 710 / 27.95 A

8 OPzV solar.power 1000 923 1112 1080 68.0 / 149.9 215 / 8.46 193 / 7.60 710 / 27.95 B

10 OPzV solar.power 1250 1154 1391 1350 82.0 / 180.8 215 / 8.46 235 / 9.25 710 / 27.95 B

12 OPzV solar.power 1500 1376 1617 1570 97.0 / 213.8 215 / 8.46 277 / 10.91 710 / 27.95 B

12 OPzV solar.power 1700 1508 1772 1720 120.0 / 264.6 215 / 8.46 277 / 10.91 840 / 33.07 B

16 OPzV solar.power 2300 2011 2390 2320 165.0 / 363.8 215 / 8.46 400 / 15.75 815 / 32.09 C

20 OPzV solar.power 2900 2521 3018 2930 200.0 / 440.9 215 / 8.46 490 / 19.29 815 / 32.09 D

24 OPzV solar.power 3500 3024 3646 3540 240.0 / 529.1 215 / 8.46 580 / 22.83 815 / 32.09 D

16 OPzV solar.power 2300 20 OPzV solar.power 2900 -24 OPzV solar.power 3500

W

L

W

L

4 OPzV solar.power 250 -6 OPzV solar.power 750

8 OPzV solar.power 1000 -12 OPzV solar.power 1700

W

L

W

L

Fig. AFig. B

Fig. CFig. D

H

C8 and C100 = Capacity at 8 h and 100 h discharge* data to be understood as maximum values

0 10 20 30 40 50 60 70 80 90

9000

8000

7000

6000

5000

4000

3000

2000

1000

0

Depth of Discharge [%]

Service life in cycles and Depth of Discharge

Num

ber

of c

ycle

s [n

]

Environmental responsibility - we offer complete recovery of material in an accredited recycling facility.

IEC 60896-21IEC 61427