Upload
erfin-l-saputra
View
207
Download
42
Embed Size (px)
Citation preview
5/21/2018 Bahaya Listrik - K3
1/42
BAHAYA LISTRIK BAGI MANUSIA
PT PLN (Persero)
UDIKLAT BOGOR
BAHAYA LISTRIK-1
SHOCK
(TERKEJUT) PINGSAN
TERBAKAR
KEMATIAN
BAHAYA YANG DITIMBULKAN OLEH ARUS / TEGANGAN LISTRIK
TERHADAP MANUSIA ADALAH :
Doc:Anton/03/04/ags
5/21/2018 Bahaya Listrik - K3
2/42
FAKTOR YANG MEMPENGARUHI AKIBAT
SENGATAN LISTRIK
Besarnya tegangan
Besarnya Arus
Kondisi tubuh
Waktu
Jenis tegangan AC / DC
5/21/2018 Bahaya Listrik - K3
3/42
DENYUT JANTUNG YANG TERSENGAT LISTRIK
BAHAYA LISTRIK-2
KEADAAN NORMAL TERKENA SENGATAN LISTRIK
DENYUT NORMAL :
80 KALI PER MENIT ---> DIPERINTAHKAN 100KALI PER MENIT
PT PLN (Persero)
UDIKLAT BOGOR
Doc:Anton/03/04/ags
5/21/2018 Bahaya Listrik - K3
4/42
MEDAN LISTRIK DAN MEDAN MAGNET
MEDAN LISTRIK [KV / M]MEDAN MAGNET [mT]
MEDAN LISTRIK DAN MEDAN MAGNET DI TEMPAT
KERJA :
SUTR, SUTM, SUTT, SUTET
MESIN PENDINGIN, MESIN KETIK ELEKTRONIK,
MESIN PENDINGI, MESIN PHOTO COPY
MESIN LAS
ALAT KERJA KOMPUTER DAN PRINTERMESIN KOMPRESOR, DAN LAIN-LAIN
PT PLN (Persero)
UDIKLAT BOGOR
BAHAYA LISTRIK-3
Doc:Anton/03/04/ags
5/21/2018 Bahaya Listrik - K3
5/42
MEDAN LISTRIK ADALAH SUATU MEDANATAU LAPANGAN YANG DAPAT
MENIMBULKAN GAYA PADA PERTIKEL
BERMUATAN LISTRIK YANG TERLETAK
DALAM MEDAN TERSEBUT.
MEDAN LISTRIK ITU SENDIRI TIMBUL OLEHADANYA PARTIKEL BERMUATAN LISTRIK
ATAU DENGAN KATALAIN OLEH ADANYA
TEGANGAN LISTRIK
MEDAN LISTRIK BERKURANG KEKUATANNYASELARAS DENGAN BERTAMBAHNYA JARAK
DARI SUMBER SATUAN DARI MEDAN LISTRIK
ADALAH [Kv/M].
PT PLN (Persero)
UDIKLAT BOGOR
BAHAYA LISTRIK-4
MEDAN LISTRIK
Doc:Anton/03/04/ags
5/21/2018 Bahaya Listrik - K3
6/42
MEDAN MAGNET ADALAH SUATU MEDANATAU LAPANGAN YANG DAPAT
MENIMBULKAN GAYA PADA BENDA-
BENDA MAGNET ATAU PARTIKEL
BERMUATAN LISTRIK.
MEDAN MAGNET DITIMBULKAN OLEHBENDA-BENDA MAGNET ATAU
KONDUKTOR YANG DIALIRI ARUS LISTRIK
ADA BEBERAPA BESARAN DARI MEDAN
MAGNET, SALAH SATUNYA ADALAHINDUKSI MEDAN MAGNET ATAU RAPAT
FLUKS MAGNET.
SATUANNYA T (TESLA) ATAU G (GAUSS)
ATAU Wb/m2(WEBER/METER PERSEGI)
PT PLN (Persero)
UDIKLAT BOGOR
BAHAYA LISTRIK-5
MEDAN MAGNET
Doc:Anton/03/04/ags
5/21/2018 Bahaya Listrik - K3
7/42
POLA MEDAN LISTRIK DAN MEDAN MAKNIT
DARI SUATU KONDUKTOR YANG MENGALIRKAN ARUS LISTRIK
PT PLN (Persero)
UDIKLAT BOGOR
BAHAYA LISTRIK-6
+ +
KONDUKTOR
BERTEGANGAN
MEDAN LISTRIK
MEDAN MAGNET
TANAH/BUMI TANAH/BUMI
Doc:Anton/03/04/ags
PT PLN (P ) BAHAYA LISTRIK 7
5/21/2018 Bahaya Listrik - K3
8/42
MEDAN LISTRIK YANG ADA DI ALAM
PT PLN (Persero)
UDIKLAT BOGOR
BAHAYA LISTRIK-7
ANTARA IONOSFIR DAN PERMUKAAN BUMI : UDARA
CERAH
100 500 VOLT / METER
AWAN MENDUNG YANG MENGANDUNG POTENSIAL PETIR
MEMBANGKITKAN MEDAN LISTRIK
3000 30.000 VOLT / METER
Doc:Anton/03/04/ags
PT PLN (P ) BAHAYA LISTRIK 8
5/21/2018 Bahaya Listrik - K3
9/42
MEDAN MAKNIT ( DI ALAM )
PT PLN (Persero)
UDIKLAT BOGOR
BAHAYA LISTRIK-8
MENYELIMUTI BUMI, KEKUATANNYA
40 70 microTesla
IT = 1000. mT ----> T = TESLA
IG = 1000. mG ----> G = GAUSS
IT = 10.000 . G.
Doc:Anton/03/04/ags
5/21/2018 Bahaya Listrik - K3
10/42
SUMBERMEDAN LISTRIK DAN MEDAN MAGNET
DARI ALAM :MEDAN LISTRIK DAN MEDAN MAGNETTELAH ADA DI ALAM SEJAK BUMI DANALAM SEMESTA INI DICIPTAKAN
ATMOSFIR YANG MENYELIMUTI BUMIMEMPUNYAI LAPISAN IONOSFIR YANGMENIMBULKAN MEDAN LISTRIK
BUMI MERUPAKAN MAGNET RAKSASAYANG MENIMBULKAN MEDAN MAGNETSEHINGGA BISA MENGGERAKKAN
JARUM KOMPAS
MEDAN MAGNET BUMI
IONOSFIRMEDAN LISTRIKIONOSFIR
40-70 T
CUACA CERAH
0.1-0.5 kV/m
AWAN MENDUNG
3-30 kV/m
5/21/2018 Bahaya Listrik - K3
11/42
MEDAN LISTRIK DAN MEDAN MAGNETBUATAN MANUSIA
ML DAN MM DARI PERALATAN RUMAHTANGGA.
LAMPU MEJA YANG MENYALA, DISAMPINGADA ML JUGA AKAN DIBANGKITKAN MM.
MEDAN LISTRIK (E)
MEDAN Magnet (B)
SUTT / SUTET YANG BERTEGANGANDAN BERARUS LISTRIK, DISAMPINGMENIMBULKAN ML (E), JUGA AKANMENIMBULKAN MM (B).
PT PLN (Persero) BAHAYA LISTRIK-7
5/21/2018 Bahaya Listrik - K3
12/42
MEDAN LISTRIK
PADA PERALATAN LISTRIK
PT PLN (Persero)
UDIKLAT BOGOR
BAHAYA LISTRIK 7
PERALATANMEDAN LISTRIK
(VOLT / METER)
SELIMUT LISTRIK 250
STEREO SET 90
LEMARI PENDINGIN 60
SETRIKA LISTRIK 60
PENGERING RAMBUT 40
TV BERWARNA 3016
LAMPU PIJAR 2
PENYEDOT DEBU
Doc:Anton/03/04/ags
PT PLN (Persero) BAHAYA LISTRIK-10
5/21/2018 Bahaya Listrik - K3
13/42
MEDAN MAGNET
PADA PERALATAN LISTRIK
PT PLN (Persero)
UDIKLAT BOGOR
MEDAN MAGNET ( T)PERALATAN3 CMPERALATAN 30 CM 100 CM
6 - 2000PENGERING RAMBUT 0,01 - 7 0,01 - 0,3
15 - 1500ALAT CUKUR 0,08 - 5 0,01 - 0,3
4000 - 800BOR LISTRIK 2 - 3,5 0,08 - 0,2
60 - 700MIXER 0,6 - 10 0,02 - 0,025
2,5 - 50TELEVISI 0,04 - 2 0,01 - 0,15
8 - 30SETRIKA LISTRIK 0,12 - 0,3 0,01 - 0,025
0,5 - 1,7LEMARI PENDINGIN 0,01 - 0,25 < 0,01
Doc:Anton/03/04/ags
PT PLN (Persero) BAHAYA LISTRIK -11
5/21/2018 Bahaya Listrik - K3
14/42
HASIL PENGUKURAN KUAT MEDAN MAGNET DI BAWAH SUTET 500 KV
KRIAN- PAITON OLEH ITS
PT PLN (Persero)
UDIKLAT BOGOR
109
8
7
6
5
4
3
2
1
0
-25 -15 -12 -9 -7,5 -6 -3 0 3 6 7,5 9 12 15 25
AS TENGAH TOWERAmbang batas WHO = 1000 mG
MEDAN MAGNET Jarak Mendatar (m) Obyek Pengukuran : SUTT 500 kVlokasi Ds. Senambung KrianTgl. 13 Juli 1997
waktu : Pkl. 15.30-16.30
Doc:Anton/03/04/ags
PT PLN (Persero) BAHAYA LISTRIK-12
5/21/2018 Bahaya Listrik - K3
15/42
HASIL PENGUKURAN KUAT MEDAN LISTRIK
DI BAWAH SUTET 500 KV KRIAN- PAITON OLEH ITS
( )
UDIKLAT BOGOR
5
4
3
2
1
0
-25 -15 -12 -9 -7,5 -6 -3 0 3 6 7,5 9 12 15 25
AS TENGAH TOWERAmbang batas WHO = 5 kV/m
MEDAN LISTRIK Jarak Mendatar (m) Obyek Pengukuran : SUTT 500 kVlokasi Ds. Senambung KrianTgl. 13 Juli 1997
waktu : Pkl. 15.30-16.30
Doc:Anton/03/04/ags
PT PLN (Persero) BAHAYA LISTRIK-13
5/21/2018 Bahaya Listrik - K3
16/42
HASIL PENGUKURAN KUAT MEDAN MAGNET
DI BAWAH SUTET 150 KV SAWAHAN BARAT OLEH ITS
UDIKLAT BOGOR
10
9
8
7
6
5
4
3
2
1
0
-25 -15 -12 -9 -7,5 -6 -3 0 3 6 7,5 9 12 15 25
AS TENGAH TOWERAmbang batas WHO = 1000 mG
MEDAN MAGNET Jarak Mendatar (m) Obyek Pengukuran : SUTT 150 kV
lokasi Jl. Raya Darmo II SurabayaTgl. 13 Juli 1997
waktu : Pkl. 17.00 - 17.30
KuatMedan
Magnet(mG)
Doc:Anton/03/04/ags
PT PLN (Persero) BAHAYA LISTRIK-14
5/21/2018 Bahaya Listrik - K3
17/42
PEDOMAN NILAI AMBANG BATAS
KUAT MEDAN LISTRIK DAN KUAT MEDAN MAGNET YANG
DIPAKAI PLN
UDIKLAT BOGOR
PERATURAN MEDAN LISTRIK MEDAN MAGNET
STANDAR PLN (SPLN NO.
112/1994)
INIRC MENGENAI PETUNJUK
BATAS-BATAS PEMAPARAN
TERHADAP MEDAN LISTRIK
DAN MEDAN MAGNET (EMF)
50/60 HZ/REKOMENDASI WHO
IRPS 1990
WORKING HOUR E
(MAX) : 10 kV/m
CONTINOUSLY
E (MAX) : 5 Kv/m
WORKING HOUR B
(MAX) : 0,5 mt
CONTINOUSLY B (MAX)
: 0,1 mt
REFERENSI : KEPUTUSAN DIREKSI PT PLN (Persero ) NO. 031.K/008/DIR/1997 TANGGAL 14
APRRIL 1997
Doc:Anton/03/04/ags
5/21/2018 Bahaya Listrik - K3
18/42
APA PENGARUH ARUS INDUKSI AKIBATMEDAN LISTRIK DAN MEDAN MAGNET DARI SUTT / SUTET
BAGI TUBUH MANUSIA
REKOMENDASIIRPA/INIRC/WHO UNTUK ML5 KV/M (20%)DAN MM 0,1mT (2%)MASIH JAUH DIBAWAH PAJANAN YANG
SETARA
ATAS DASAR INI PARAAHLI BERPENDAPAT BAHWATIDAK MUNGKIN MEDAN
LISTRIK DAN MEDANMAGNET TERSEBUT AKAN
MENIMBULKAN EFEKPENTING
ARUS INDUKSIMENGALIR
DIANTARA CELL DANTIDAK MENEMBUSCELL
RAPAT ARUS YANG SECARAALAMIAH TERJADI DIDALAMTUBUH MANUSIA ADALAH
KIRA-KIRA 10 mA/m2SETARADENGAN PAJANAN ML25
KV/MMM 5 mT
Referensi :1. National Institute of Envirromental Health Sciens and US. Departement of Energy (1995)
Questions and Answers Abouat EMF2. IRPA/INIRC (International Radiation Protection / International Non - Ionizing Radiation Commitee) 1990
Health Physics Volume 58, January 1990
5/21/2018 Bahaya Listrik - K3
19/42
TUBUH MANUSIA DALAMMEDAN LISTRIK DAN MEDAN MAGNET
Dibawah pengaruh Medan Magnet
Medan Magnet(B)
Dibawah pengaruh Medan Listrik
Medan Listrik(E)
Referensi :Prof. H. KARNER Technical University Braunschweigh, Influence of Electrostatic & Magnetic field on Biological Systems 1992
MEDAN LISTRIK : I/E = 15 A/kV/m
MEDAN MAGNET : I/B = 1 A/ T
PADA TUBUH AKAN MENGALIR ARUSINDUKSI, YANG SEBAGAI PEDOMANBESARNYA ADALAH :
SESUAI IEC 479-1 ARUS SAMPAIDENGAN 500 A MASIH TIDAK TERASAYAITU SETARA DENGAN 33 KV/m DAN500 T
REKOMENDASI IRPA/INIRC/WHO UNTUKML 5 KV/M (15%)DAN MM 0,1 mT (20%)MASIH JAUH DI BAWAH PAJANAN
YANG TERASA
5/21/2018 Bahaya Listrik - K3
20/42
PENGARUH MEDAN MAGNET TERHADAP EFFEK RANGSANGANPADA ORGAN - ORGAN BIOLOGIS
Kerapatan arus induksi magnetik : Otak = 0,25 nA/cm2
/ TJantung = 0,25 nA/cm2 / T
EFFEK ARUS INDUKSI NILAI BATAS
Batas
KepekaanTerhadap
Rangsangan
Kerapatan arus otak pada
keadaan tak aktip Effek rangsangan
Bahaya Biologis
Fibrillasi jantung
+ 0,1 A/Cm2
> 10 A/Cm2
> 100 A/Cm2
> 500 A/Cm2
Referensi :Anderson, L. : Biological effects of 50/60 Hz field 2nd International Non Ionazing Radiation Workshop,Vancouver BC - Canada, May 10-14, 1992
Reomendasi IRPA/INIRC/WHO untuk waktu terbatas < 100 T (25%)
KUAT MM YANGMENGINDUKSI
400 T40 mT
400 mT
2 T
(Dapat disimpulkan bahwa Rekomendasi WHO tersebut sangat aman)
5/21/2018 Bahaya Listrik - K3
21/42
PENGARUH MEDAN LISTRIK TERHADAP EFFEK RANGSANGANPADA ORGAN - ORGAN BIOLOGIS
Referensi :Anderson, L. : Biological effects of 50/60 Hz field 2nd International Non Ionazing Radiation Workshop,Vancouver BC - Canada, May 10-14, 1992
EFFEK ARUS INDUKSI NILAI BATAS
Batas
KepekaanTerhadap
Rangsangan
Kerapatan arus otak
pada keadaan tak aktip Effek rangsangan
Bahaya Biologis
Fibrillasi jantung
+ 0,1 A/Cm2> 10 A/Cm2
> 100 A/Cm2
> 500 A/Cm2
< 5 kV/m
KUAT ML YANGMENGINDUKSI
40 kV/m77 kV/m
770 kV/m
4.000 kV/m
Kerapatan Arus induksi LISTRIK : Otak = 2,5 nA/cm2
/ (kV/m)Jantung = 130 nA/cm2 / (kV/m)
Reomendasi IRPA/INIRC/WHO untuk waktu terbatas(Dapat disimpulkan bahwa Rekomendasi WHO tersebut sangat
aman)
5/21/2018 Bahaya Listrik - K3
22/42
SEMAKIN TINGGI FREKWENSI MAKAPANJANG GELOMBANG SEMAKIN PENDEKDAN ENERGI YANG DIBANGKITKANSEMAKIN BESAR
RADIASI PENGION SEPERTI SINARGAMMA, SINAR X DAN SEBAGIAN SINARULTRA VIOLET MENYEBABKAN IONISASI
YANG DAPAT MEMECAHKAN IKATAN
MOLEKUL DAN MERUSAK SEL GENETIK
JARINGAN TRANSMISI DENGANFREKWENSI EKSTRIM RENDAH (50 Hz)MEMBANGKITKAN ENERGI YANG SANGATKECIL DAN TIDAK MENYEBABKAN
PEMANASAN ATAUPUN IONISASI
SPEKTRUM FREKWENSI MEDAN LISTRIKDAN MEDAN MAGNET
22
20
18
16
14
12
10
8
6
4
2
ELECTROMAGNETIC SPECTRUM
10
10
10
10
10
10
10
0
10
10
10
10
RADIASIPENGION
SINAR X
SINAR GAMMA
50 Hz
ARUS SEARAH
15-30 KHz&
50-90 Hz
CAHAYA TERLIHAT
12345678#90# 800-900 MHz
MICROWAVE2450 MHz
(DALAM OVEN)
Hz
SEBAGIAN SINAR ULTRA VIOLET
Referensi :National Instituteof Envirromental Health Sciens and US. Departement of EnergyQuestions and Answers Abouat EMF Electric and Magnetic Fields Associated with the use of Electric Power. January 1995.
PT PLN (Persero)
UDIKLAT BOGOR
BAHAYA LISTRIK-15
5/21/2018 Bahaya Listrik - K3
23/42
MACAM-MACAM TEGANGAN YANG TIMBUL
AKIBAT ARUS BOCOR / KESALAHAN KE
TANAH TERHADAP ORANG YANG BERADA DI
SEKITAR INSTALASI TENAGA LISTRIK :
TEGANGAN SENTUH
TEGANGAN LANGKAH
TEGANGAN PINDAH
UDIKLAT BOGOR
Doc:Anton/03/04/ags
PT PLN (Persero)UDIKLAT BOGOR
BAHAYA LISTRIK-16
5/21/2018 Bahaya Listrik - K3
24/42
TABEL : BESAR DAN LAMA TEGANGAN SENTUH MAKSIMUM
BESAR TEGANGAN SENTUH (V)
AC (RMS) DC
< 50 < 120
50 120
75 140
90 160
110 175
150 200
220 250
280 310
LAMA SENTUHAN
MAKSIMUM (DETIK)
-
5,0
1,0
0,5
0,2
0,1
0,05
0,03
U OGO
Doc:Anton/03/04/ags
PT PLN (Persero)UDIKLAT BOGOR
BAHAYA LISTRIK-17
5/21/2018 Bahaya Listrik - K3
25/42
SESEORANG TIDAK BOLEHMENYENTUH WALAU SEKEJAPPUN
PERALATAN DENGAN TEGANGAN DI
ATAS 100 VOLT
ATURAN UMUM :
Doc:Anton/03/04/ags
PT PLN (Persero)
UDIKLAT BOGOR
BAHAYA LISTRIK-18
5/21/2018 Bahaya Listrik - K3
26/42
BATASAN BESARNYA ARUS LISTRIK YANG
MENGALIR MELALUI TUBUH MANUSIA SERTAPENGARUH LANGSUNG YANG DIRASAKAN :
ARUS PERSEPSI (PERCEPTION CURRENT)
ARUS MEMPENGARUHI OTOT (LETGO CURRENT)
ARUS FIBRILASI (FIBRILLATING CURRENT)
ARUS REAKSI (REACTION CURRENT)
Doc:Anton/03/04/ags
PT PLN (Persero)UDIKLAT BOGOR
BAHAYA LISTRIK-19
5/21/2018 Bahaya Listrik - K3
27/42
PENGARUH ARUS LISTRIK PADA TUBUH MANUSIA
BESARNYA ARUS PENGARUH PADA TUBUH MANUSIA
BELUM DIRASAKAN PENGARUHNYA0 0,9 mA
BARUS TERASA ADANYA ARUS LISTRIK0,9 1,2 mA
MULAI TERASA SEAKAN-AKAN ADA YANG
MERAYAP DIDALAM TANGAN1,2 1,6 mA
TANGAN SAMPAI KESIKU MERASA KESEMUTAN1,6 6,0 mA
TANGAN MULAI KAKU, RASA KESEMUTAN MAKIN
BERTAMBAH
6,0 8,0 mA
RASA SAKIT TIDAKTERTAHANKAN PENGHANTAR
MASIH DAPAT DILEPASKAN DENGAN GAYA YANG
BESAR SEKALI
13 15,0 mA
OTOT TIDAK SANGGUP LAGI MELEPASKAN
PENGHANTAR15 20,0 mA
DAPAT MENGAKIBATKAN KERUSAKAN PADATUBUH MANUSIA20 50,0 mA
BATAS ARUS YANG DAPAT MENYEBABKAN
KEMATIAN50 100,0 mA
Doc:Anton/03/04/ags
PT PLN (Persero)UDIKLAT BOGOR
BAHAYA LISTRIK-22
5/21/2018 Bahaya Listrik - K3
28/42
PENELITIAN Dr. ANIES - UNIVERSITAS DIPENOGORO
(1993)DARI HASIL PENGUKURAN TERNYATA KUAT MEDAN LISTRIK DAN
KUAT MEDAN MAGNET DARI SUTT/SUTET MASIH JAUH DIBAWAH
AMBANG BATAS YANG DIREKOMENDASIKAN WHO/IRPA SEHINGGA
DALAM BATAS TERTENTU (DIATAS) SUTT/SUTET TIDAK AKANMENIMBULKAN MASALAH KESEHATAN, NAMUN KETAKUTAN SERTA
KEKHAHAWATIRAN MASYARAKAT ADALAH WAJAR DAN SEBAGAI
UPAYA UNTUK MEPERKECIL DAMPAK NEGATIF SUTT / SUTET
TERHADAP KESEHATAN MASYARAKAT, PERLU DILAKUKANPENYULUHAN YANG EFEKTIF KEPADA MASYARAKAT UMUM.
Doc:Anton/03/04/ags
PT PLN (Persero)UDIKLAT BOGOR
BAHAYA LISTRIK-23
5/21/2018 Bahaya Listrik - K3
29/42
PENELITIAN SOSIOLOGI KASNODIHARDJO DAN SOESANTO (1995)
PENELITIAN-PENELITIAN SOSIOLOGI KASNODIHARDJO DAN
SOESANTO (1995) DAN GANIHARTONO (1995), YANG BERUSAHA
MENILIK KEADAAN DAN HUBUNGAN SOSIAL EKONOMI DAN
GANGGUAN SUTET 500 KV YANG DIKELUHKAN PENDUDUKDIDAERAH CIBINONG DAN BEKASI JAWA BARAT, TELAH
MENUNJUKAN BAHWA TIDAK ADA HUBUNGAN LANGSUNG ANTARA
KETERPAPARAN PENDUDUK YANG BERADA DIBAWAH JARINGAN
SUTET DENGAN PENYAKIT YANG DILAPORKAN ATAUPUN TINGKAT
KESEHATAN MASYARAKAT
Doc:Anton/03/04/ags
PT PLN (Persero)UDIKLAT BOGOR
BAHAYA LISTRIK-24
5/21/2018 Bahaya Listrik - K3
30/42
PENELITIAN BUDI HARYANTO SKM, MSc BALITBANG DEPKES RI
(1995/ 1996)
TIDAK ADA KORELASI ANTARA GANGGUAN KESEHATAN SEPERTI
SAKIT KEPALA, KELELAHAN SEPERTI SAKIT KEPALA, KELELAHAN
MENTAL, PUSING KEPALA, KEGUGURAN, SUSAH TIDUR,
BRADYCARDIA, TACHYCARDIA, INDIKASI TUMOR DAN LEUKIMIA
TERHADAP PAJANAN MEDAN LISTRIK DAN MEDAN MAGNET
Doc:Anton/03/04/ags
PT PLN (Persero)UDIKLAT BOGOR
BAHAYA LISTRIK-25
5/21/2018 Bahaya Listrik - K3
31/42
PENELITIAN Ir. SYARIFUDIN MAHMUDSYAH M. Eng
FAKULTAS ELEKTRO- ITS
DARI HASIL PENELITIAN MENGENAI DAMPAK MEDAN
ELEKTROMAGNETIK AKIBAT PEMAKAIAN TENAGA LISTRIK
KHUSUSNYA SUTT 150 KV / SUTET 500 KV PADA DAERAH SINGOSARI
GRESIK SERTA DHARMAHUSADA INDAH SURABAYA, DARI HASILPENGUKURAN MEDAN ELEKTROMAGNETIK AKIBAT SUTT / SUTET
DIPEROLEH DATA BAHWA KUAT MEDAN LISTRIK DAN KUAT MEDAN
MAGNET MASIH JAUH DIBAWAH LEVEL TOLERANSI BERDASARKAN
STANDAR IRPA DAN INRC. MASALAH YANG DIHADAPI PENDUDUK
LEBIH CONDONG KEPADA MASALAH PSIKOLOGIS DAN TUNTUNAN
MENDAPATKAN GANTI RUGI.
Doc:Anton/03/04/ags
PT PLN (Persero)UDIKLAT BOGOR
BAHAYA LISTRIK-26
5/21/2018 Bahaya Listrik - K3
32/42
KERJASAMA LEMBAGA PENELITIAN MASYARAKAT
ITB - FAKULTAS KEDOKTERAN UNIVERSITAS INDONESIA(1996/ 1997)
TIDAK ADA KORELASI FREKUENSI GANGGUAN KESEHATAN
MASYARAKAT YANG TERPAJAN MEDAN LISTRIK DAN MEDAN
MAGNET DARI SUTET BERHUBUNGAN DENGAN JARAK TEMPAT
TINGGAL TERHADAP JARINGAN, DAN JUGA TIDAK ADA PENGARUH
DARI BESAR DAN LAMANYA PEMAJANAN MEDAN LISTRIK DAN
MEDAN MAGNET TERHADAP DERAJAT KELAINAN FUNGSI SISTEM
TUBUH.
Doc:Anton/03/04/ags
BAHAYA LISTRIK-27PT PLN (Persero)UDIKLAT BOGOR
5/21/2018 Bahaya Listrik - K3
33/42
K E S I M P U L A N
DENGAN DEMIKIAN UNTUK
SEMENTARADAPAT
DISIMPULKAN BAHWA SAMPAI
SAAT INI BESARNYA MEDAN
LISTRIK DAN MEDAN MAGNETYANG BERADA DIBAWAH DAN
SEKITAR SUTT / SUTET YANG
ADA DI INDONESIA BELUM
MEMBAHAYAKAN BAGI
KESEHATAN PENDUDUK
Doc:Anton/03/04/ags
BAHAYA LISTRIK-28
5/21/2018 Bahaya Listrik - K3
34/42
BAHAYA LISTRIK PADA TEGANGAN TINGGI / EKSTRA TINGGI
BAHAYA LISTRIK PADA TEGANGAN TINGGI / EKSTRA TINGGI
BAHAYA LISTRIK PADA INSTALASI TEGANGAN TINGGI / EKSTRA YANG PALING
DOMINAN ADALAH GRADIEN TEGANGAN TINGGI ATAU TEGANGAN EKTRA
TINGGI ITU SENDIRI TERHADAP MAHLUK HIDUP MAUPUN TERHADAP BENDA-
BENDA LAIN YANG BERADA PADA DAERAH SEKITARNYA
SEBAGAI CONTOH SALURAN UDARA TEGANGAN TINGGI (SUTT) DIMANASALURAN TENAGA LISTRIK YANG MENGGUNAKAN KAWAT TELANJANG
(PENGHANTAR) DI UDARA BERTEGANGAN ANTARA 35 KV SAMPAI DENGAN 245
KV SESUAI STANDAR DI BIDANG KETENAGALISTRIKAN
SALURAN UDARA TEGANGAN EKSTRA TINGGI (SUTET) DIMANA SALURAN
TENAGA LISTRIK YANG MENGGUNAKAN KAWAT TELANJANG (PENGHANTAR) DI
UDARA BERTEGANGAN DI ATAS 245 KV SESUAI STANDAR DI BIDANG
KETENAGALISTRIKAN
Doc:Anton/03/04/ags
BAHAYA LISTRIK-29
5/21/2018 Bahaya Listrik - K3
35/42
PADA SAAT INI LAHAN YANG TERSEDIA TERASA SEMAKIN SEMPIT
KARENA PESATNYA PERKEMBANGAN DISEGALA BIDANG DEMIKIAN
PULA PERTUMBUHAN PENDUDUK YANG CUKUP BESAR, SEHINGGA
JALUR YANG DILALUI SUTT ATAU SUTET KEMUNGKINAN TIDAK DAPAT
MENGHINDARI DAN TERPAKSA HARUS MELEWATI DAERAH DENGAN
KEADAAN TERTENTU, SEPERTI DAERAH PEMUKIMAN YANG PADAT
BAHAYA LANGSUNG TERHADAP TEGANGAN TINGGI / EKSTRA TINGG
TERHADAP MANUSIA / MAHLUK HIDUP LAINNYA ADALAH SENGATAN
LANGSUNG JIKA YANG BERSANGKUTAN BERSENTUHAN/ MEMEGANGTEGANGAN TINGGI / EKTRA TINGGI, ATAUPUN TERKENA TEGANGAN
SISA PADA INSTALASI TENAGA LISTRIK
UNTUK MENGANTISIPASI BAHAYA LISTRIK PADA TEGANGAN TINGGI /
EKSTRA TINGGI TELAH DITETAPKAN ADANYA JARAK AMAN
TERHADAP INSTALASI TEGANGAN TINGGI / EKSTRA TINGGDIMAKSUD YANG DISEBUT RUANG BEBAS DAN RUANG AMAN
TERUTAMA DISEKITAR SUTT / SUTET
Doc:Anton/03/04/ags
BAHAYA LISTRIK-30
5/21/2018 Bahaya Listrik - K3
36/42
RUANG BEBAS
RUANG BEBAS ADALAH RUANG SEKELILING PENGHANTAR (KAWAT LISTRIK)
SUTT ATAU SUTET YANG BESARNYA TERGANTUNG TEGANGAN, TEKANAN
ANGIN DAN SUHU KAWAT PENGHANTAR
RUANG TERSEBUT HARUS DIBEBASKAN DARI ORANG MAHLUK HIDUP LAINMAUPUN BENDA APAPUN DEMI KESELAMATAN ORANG, MAHLUK DAN BENDA
LAIN TERSEBUT DEMIKIAN PULA KEAMANAN DARI SUTT ATAU SUTET ITU
SENDIRI
Doc:Anton/03/04/ags
BAHAYA LISTRIK-31
5/21/2018 Bahaya Listrik - K3
37/42
RUANG AMAN
RUANG AMAN ADALAH RUANG YANG BERADA DILUAR RUANG BEBAS YANG
TANAHNYA MASIH DAPAT DIMANFAATKAN
DALAM RUANG AMAN PENGARUH MEDAN LISTRIK DAN KUAT MEDAN MAKNET
SUDAH DIPERTIMBANGKAN DENGAN MENGACU KEPADA PERATURAN YANG
BERLAKU. UNTUK MENDIRIKAN BANGUNAN DI DALAM RUANG AMAN, TETAP
DIPERLUKAN IJIN MENDIRIKAN BANGUNAN (IMB) DARI PEMERINTAH DAERAH
Doc:Anton/03/04/ags
BAHAYA LISTRIK-32
5/21/2018 Bahaya Listrik - K3
38/42
FAKTOR-FAKTOR YANG MEMPENGARUHI RUANG BEBAS DAN RUANG AMAN
RUANG BEBAS DAN RUANG AMAN DAPAT DIATUR BESARNYA SESUAI
DENGAN KEBUTUHAN PADA SAAT MEMPERSIAPKAN RANCANG BANGUN
PADA SAAT MEMPERSIAPKAN RANCANG BANGUN TERSEBUT, RUANG AMAN
DAPAT DIPERLUAS DENGAN CARA MENINGGIKAAN MENARA DAN ATAU
MEMPERPENDEK JARAK ANTARA MENARA, SEHINGGA BILA ADA
PEMUKIMAN YANG AKAN DILINTASI SUTT ATAU SUTET YANG AKAN
DIBANGUN BERADA DIDALAM RUANG YANG AMAN
FAKTOR-FAKTOR YANG MENENTUKAN RUANG BEBAS DAN RUANG AMANADALAH TEGANGAN KEKUATAN ANGIN DAN SUHU DISEKITAR PENGHANTAR
a. TEGANGAN
MAKIN BESAR TEGANGAN YANG BEKERJA PADA PENGHANTAR MAKIN
BESAR JARAK BEBAS MINIMUM (CLEARANCE) YAITU JARAK YANG
TERPENDEK DIIJINKAN ANTARA KAWAT PENGHANTAR DAN BENDA ATAUKEGIATAN LAIN SESUAI DENGAN ANGKA-ANGKA YANG TERTERA PADA
TABEL V-I
Doc:Anton/03/04/ags
BAHAYA LISTRIK-34
5/21/2018 Bahaya Listrik - K3
39/42
b. ANGIN
MAKIN BESAR TEKANAN ANGIN, MAKIN BESAR AYUNAN KAWAT
PENGHANTAR KE KIRI ATAU KE KANAN, PADA SUATU GAWANG (JARAK
ANTARA DUA MENARA) AYUNAN YANG TERBESAR KARENA PENGARUH
ANGIN ADALAH PADA KAWAT PENGHANTAR YANG LENGKUNGANNYA PALING
RENDAH SEDANGKAN AYUNAN SEMAKIN KECIL KE ARAH MENARA
c. SUHU KAWAT PENGHANTAR
MAKIN BESAR SUHU YANG MEMPENGARUHI KAWAT PENGHANTAR MAKINMENGENDOR KAWAT PENGHANTAR TERSEBUT, SEHINGGA ANDONGANNYA
MENJADI LEBIH BESAR, HAL INI SUDAH DIPERHITUNGKAN PADA SAAT
MENDESAIN SUTT ATAU SUTET TERSEBUT
KENAIKAN SUHU TERSEBUT DISEBABKAN OLEH SUHU DISEKELILING DAN
SUHU YANG DIAKIBATKAN OLEH BESARNYA ARUS YANG MENGALIR PADA
KAWAT PENGHANTAR
Doc:Anton/03/04/ags
PT PLN (Persero)UDIKLAT BOGOR
BAHAYA LISTRIK-21
JARAK BEBAS MINIMUM ANT PENGHANTAR SUTT / SUTET DGN TANAH ATAU
BENDA LAIN
5/21/2018 Bahaya Listrik - K3
40/42
BENDA LAIN
Catatan :
NO LOKASISUTT 66 KV
(M)SUTT 150 KV
(M)SIRKIT
GANDA (M)
SIRKIT TUNGGAL
(M)
SUTET 500 KV
LAPANGAN TERBUKA ATAU DAERAH TERBUKA
DAERAH DENGAN KEADAAN TERTENTU :
2.1. BANGUNAN TIDAK TAHAN API
2.2. BANGUNAN TAHAN API
2.3. LALU LINTAS JALAN / JALAN RAYA
2.4. POHON - POHON PADA UMUMNYA, HUTAN,
PERKEBUNAN
2.5. LAPANGAN OLAH RAGA
2.6. SUTT LAINNYA, PENGHANTAR UDARA TM,
JARINGAN TELEKOMUNIKASI, ANTENA
RADIO, ANTENA TELEVISI DAN KERETA
GANTUNG
2.7. REL KERETA BIASA
2.8. JEMBATAN BESI, RANGKA BESIPENAHAN
PENGHANTAR, KERETA LISTRIK TERDEKAT
DSB.
2.9. TITIK TERTINGGI TIANG KAPAL PADA
KEDUDUKAN AIR PASANG / TERTINGGI PADA
LALU LINTAS AIR
1
2
6,5
12,5
3,5
8
3,5
12,5
3
8
3
3
7,5
13,5
4,5
9
4,5
13,5
4
9
4
4
10
14
8,5
15
8,5
14
8,5
15
8,5
8,5
11
15
8,5
15
8,5
15
8,5
15
8,5
8,5
Doc:Anton/03/04/ags
U D I K L A T B O G O R PROSEDUR K3 PADA INSTALA SI TM-TR - 16
5/21/2018 Bahaya Listrik - K3
41/42
DAERAH BERBAHAYA & JARAK AMAN
BAGIAN BERTEGANGAN
BAGIAN BERBAHAYA
JARAK
AMAN
PENTANAHAN
BAGIAN BERBAHAYA
BAGIAN
TEGANGAN
PENTANAHAN
JARAK AMAN
Doc:Anton/01/04/ags
PT PLN (Persero)UDIKLAT BOGOR
BAHAYA LISTRIK-20
JARAK MINIMUM AMAN KERJA MENURUT
5/21/2018 Bahaya Listrik - K3
42/42
Doc:Anton/03/04/ags
JARAK MINIMUM AMAN KERJA MENURUT
PUIL 2000
TEGANGAN ( U )
( Antar phasabumi dlm KV )
1
12
20
70150
500
JARAK MINIMUM
( CM )
50
60
75
100125
300