44
Issue: 4 3rd July 2018 BA578E Two input General purpose Timer or Clock Issue 4

BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

Issue: 43rd July 2018

BA578ETwo input

General purposeTimer or Clock

Issue 4

Page 2: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

2

1. DESCRIPTION

2. SYSTEM DESIGN2.1 Power supply2.2 Sensor input

2.2.1 Switch contact input2.2.2 Open collector input2.2.3 2-wire proximity detector input2.2.4 Magnetic pick-off input2.2.5 Voltage pulse input

2.3 Remote reset2.4 Status output2.5 Control outputs - optional

3. INSTALLATION3.1 Location3.2 EMC3.3 Installation Procedure3.4 Scale card

4. ACCESSORIES4.1 Display backlight4.2 Control outputs4.3 Scale card

4.4 Tag information

5. OPERATION AS A TIMER5.1 Initialisation5.2 Controls when configured as a Timer5.3 Displays when configured as a Timer5.4 Timer structure5.5 Configuration as a Timer

5.5.1 Accessing configuration functions5.5.2 Summary of Timer configuration functions5.5.3 Instrument function: FunCtion

5.5.4 Input A: inPut-A

5.5.5 Input type: inP . TYPE

5.5.6 Debounce: debounce

5.5.7 Input b: inPut-b

5.4.8 Lower display: di5P-2

5.5.9 Starting & stopping the Timer: 5tAr5toP

5.5.10 Units of display: unit5

5.5.11 Set time: 5Et t

5.5.12 Repeat timing cycle: CYCLE5

5.5.13 Cycle function enable: EnbL

5.5.14 Cycle count: cycl cnt

5.5.15 Restart delay: r5t dela

5.5.16 Adjusting the set time 5Et t fromthe display mode: AC5Et t

5.5.17 Direction of count: uP or dn

5.5.18 Power fail: p-fail

5.5.19 Local reset: LoC rEt

5.5.20 Local total reset: rE5Et . enbl

5.5.21 Local grand total reset: Glr Gtot

5.5.22 External reset: e-r5et

5.5.23 Status output: 5tat

5.5.24 Status output enable: EnbL

5.5.25 Status output on at: 5tat on

5.5.26 Status output off at: 5tat oFF

5.5.27 Status on delay time: 5tatdELA

5.5.28 Control output 1: oP1

5.5.29 Control output enable: EnbL

5.5.30 Control output on at: oP1 on

5.5.31 Control output off at: oP1 oFF

5.5.32 Output on delay time: oP1 dELA

5.5.33 Control output 2: oP2

5.5.34 Reset grand total from within theconfiguration menu: Clr Gtot

5.5.35 Security code: CodE

5.5.36 Reset configuration to factory defaults r5Et dEF

6. TIMER APPLICATION EXAMPLES6.1 Measuring the time that a contact is closed6.2 Controlling a solenoid valve

7. MAINTENANCE when configured as a Timer7.1 Fault finding during commissioning7.2 Fault finding after commissioning7.3 Servicing7.4 Routine maintenance7.5 Guarantee7.6 Customer comments

The BA578E is CE marked to show compliance with the European EMC Directive 2014/30/EU

CONTENTS

Page 3: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

3

8. OPERATION AS A CLOCK8.1 Initialisation and loss of power8.2 Controls when configured as a clock8.3 Displays when configured as a clock8.4 Configuration as a clock

8.4.1 Accessing configuration functions8.4.2 Summary of Clock configuration

functions8.4.3 Instrument function: FunCtion

8.4.4 Display format: di5PLAY

8.4.5 Set clock display time: 5et

8.4.6 Enter synchronising time: 5YnC t

8.4.7 Status output: 5tat

8.4.8 Enable status output: enbl

8.4.9 Status output on and off times:5tat: on 1; 5tat: off 1

5tat: on 2; 5tat: off 2

8.4.10 Control output 1: oP1

8.4.11 Enable Control output 1: EnbL

8.4.12 Control output 1 on and off times:oP 1 : on 1; oP 1 : off 1

oP 1 : on 2; oP 1 : off 2

8.4.13 Control output 2: oP2

8.4.14 Enable control output 2: EnbL8.4.15 Control output 2 on and off times:

oP2 : on 1; oP2 : off 1

oP2 : on 2; oP2 : off 2

8.4.16 Access on & off times from displaymode: AC5P

8.4.17 Security code: CodE

8.4.18 Reset configuration to factory defaults r5Et dEF

9. CLOCK CONFIGRATION EXAMPLE9.1 Configuration procedure

10. MAINTENANCE when configured as a clock10.1 Fault finding during commissioning10.2 Fault finding after commissioning10.3 Servicing10.4 Routine maintenance10.5 Guarantee10.6 Customer comments

Page 4: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

4

Page 5: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

5

1. DESCRIPTIONThe BA578E is a general purpose, panel mountinginstrument with two inputs that can be configuredon-site as a Timer or as a Clock.

As a Timer the BA578E can measure and displaythe elapsed time between external events, or controlexternal events via the status output or optionalcontrol outputs.

When configured as a Clock, the instrument candisplay time in a variety of formats and the optionalcontrol outputs may be configured to turn on and offat pre-set times.

This instruction manual is divided into threesections.

Common features2. System design3. Installations4. Accessories

Timer5. Operation as a timer6. Configuration example7. Maintenance

Clock8. Operation as a clock

9. Configuration example10. Maintenance

This instruction manual supplements theabbreviated instruction sheet supplied with eachinstrument.

2. SYSTEM DESIGNFig 1 illustrates the basic circuit that is used for allBA578E Timer installations. BA578E Clockinstallations are the same, except that the two inputterminals are not used. For simplicity the statusoutput and the optional control outputs aredescribed separately in sections 2.4 and 2.5 of thismanual.

Fig 1 BA578E connections

2.1 Power supplyThe BA578E requires a supply of 10 to 30V dcbetween terminal 1 & 2 and consumes:

10mA without optional backlightplus 16mA for optional backlightplus 6mA when terminals 3 & 4 are linkedplus 6mA when terminals 7 & 8 are linked

2.2 Sensor inputsWhen configured as a Timer both inputs may beconnected to a wide variety of sensors as shown inFig 1. The two BA578E inputs are not used whenthe instrument is configured as a Clock.

The following table shows the instrument's inputswitching thresholds when configured to operatewith various sensors. For reliable operation theBA578E input must fall below the lower thresholdand rise above the upper threshold.

Page 6: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

6

SensorSwitching thresholds

Lower Upper

Switch 100Ω 1000Ω

Proximity detector 1.2mA 2.1mA

Open collector 2kΩ 10kΩ

Magnetic pick-off 0 40mV peak

Voltage pulse low 1.0V 3.0V

Voltage pulse high 3.0V 10.0V

Switch contacts, proximity detectors and opencollector sensors require energising which isachieved by linking two BA578E terminals togetherfor each input, see Fig 5.

2.2.1 Switch contact inputAny switch contact may be directly connected toinput terminals 5 & 6 or 9 &10. The BA578Econtains a separate configurable debounce circuitfor each input to prevent false triggering. Threelevels of debounce protection are available Seesection 5.5.6.

2.2.2 Open collector inputAny sensor with an open collector output such as aopto-isolator may be directly connected to inputterminals 5 & 6 and 9 &10.

2.2.3 2-wire proximity detector inputMost NAMUR 2-wire proximity detectors may beconnected to a BA578E input, providing theminimum operating voltage of the proximity detectoris less than 7.5V. The BA578E contains a separateconfigurable debounce circuit for each input toprevent false triggering. Three levels of debounceprotection are available See section 5.5.6.

2.2.4 Magnetic pick-off input CoiL in the input configuration menu is a low levelvoltage pulse input intended for use with a magneticpick-off sensor. The BA578E contains a separateconfigurable debounce circuit for each input toprevent false triggering. Three levels of debounceprotection are available See section 5.5.6.

2.2.5 Voltage pulse inputTwo voltage pulse input ranges are independentlyselectable for each input in the BA578E Timerconfiguration menu, VoLt5 L and VoLt5 H allowingalmost any sensor with a voltage output to be used:The BA578E contains a separate configurabledebounce circuit for each input to prevent falsetriggering. Three levels of debounce protection areavailable See section 5.5.6.

2.3 Remote resetConnecting the external reset terminals RS1 andRS2 together will reset the BA578E when configuredas a Timer and synchronise the displayed time to apreset time when configured as a Clock.

Note: When used as a Timer the BA578E may alsobe reset from the display mode by operating the &

and * push buttons simultaneously for more thantwo seconds. See 5.5.20

2.4 Status outputAll BA578E instruments have an opto-isolated opencollector output which can be configured to indicatethe status of the instrument, or to perform simplecontrol functions. The output has the followingelectrical parameters:

Ron = 60Ω + 3VRoff = 1MΩImax = 10mA

The status output is a passive circuit i.e. un-poweredopen collector, but it is totally isolated from all othercircuits. Terminals P1 and P2 may be connected toanother instrument that can accept an open collectorinput.

Fig 2 shows how the status output may be used toproduce a voltage output.. The positive terminal ofthe status output P1 is connected to the instrument’spositive supply terminal 1. When the status opencollector output is activated, the voltage on terminalP2 rises to the supply voltage less 3V and a currentflows through the resistor R1. This current isdefined by R1 which should be chosen to limit thecurrent to less than 10mA. For a 24V supply R1should be greater than 2,200Ω.

Fig 2 Generating a voltage status output

Page 7: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

7

2.5 Control outputs (optional)Each of the two factory fitted optional control outputsis a galvanically isolated single pole solid stateswitch as shown in Fig 3. The outputs are polarisedand current will only flow in one direction. TerminalsA1 and A3 should be connected to the positive sideof the supply.

Note: Because of the series protection diode sometest meters may not detect a closed alarm output.

Fig 3 Equivalent circuit of each control output

The solid state output of each control output may beused to switch any dc circuit with parameters of:

V max = 30VI max = 200mA

Fig 4 Typical control output application

3. INSTALLATION

3.1 LocationThe BA578E has a robust glass reinforced Norylenclosure with a toughened glass window. The fronthas IP66 ingress protection and a gasket seals thejoint between the instrument enclosure and thepanel, the rear of the instrument has IP20 ingressprotection.

The BA578E may be installed in any panel providingthat the operating temperature is between -40°C and+70°C. At temperatures below -20°C the displaydigits will change more slowly and the contrast willbe reduced, but the instrument will continue tofunction

Fig 5 shows the overall dimensions of the instrumenttogether with the recommended panel cut-outdimensions. To achieve an IP66 seal between theinstrument enclosure and the instrument panel thesmaller tolerance aperture must be used, and theinstrument must be secured with four panelmounting clamps.

Although the front of the BA578E has IP66protection it should be shielded from continuousdirect sunlight and severe weather conditions.

3.2 EMCThe BA578E complies with the requirements of theEuropean EMC Directive 2014/30/EU. For specifiedimmunity all wiring should be in screened twistedpairs, with the screens earthed at one point.

Page 8: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

8

Recommended panel cut-outdimensions for all installations

Mandatory to achieve an IP66 sealbetween instrument and panel

136 +0.5/-0.0 x 66.2 +0.5/-0.0

DIN 43700138.0 +1.0/ -0.0 x 68 +0.7 -0.0

Support panel wiring to prevent vibration damage

Note: Optional backlight is internally powered

Fig 5 BA578E dimensions & terminals

3.3 Installation Procedure

a. Cut the specified aperture in the panel. Toachieve an IP66 seal between the instrumentenclosure and the instrument panel theaperture must have the tighter tolerancesspecified in Fig 5.

b. Slide the gasket over the body of the BA578Ebefore inserting the instrument into the panelaperture.

c. Firstly ensure that all the panel mountingclamps are closed by turning the knurledscrews fully anti clockwise until the two pips inthe clamp foot align with holes in the clampbody.

d. Place a clamp in the recess on each side of theinstrument, pulling gently to slide it onto thedovetail as shown in Fig 6. Push the knurledscrew slightly forward to engage the thread andtighten by turning clockwise until it is just fingertight. When the clamps are fitted ensure thatthe gasket behind the front panel bezel iscorrectly positioned before fully tightening theclamps to secure the instrument. The maximumrecommended clamp tightening torque is22cNm (1.95 lbf in) which is approximatelyequivalent to finger-tight plus one half turn.Do not over tighten.

e. Four panel mounting clamps are required toachieve an IP66 seal between a BA578E andthe instrument panel.

f. Connect the panel wiring to the rear terminalblock(s) as shown in Fig 5. To simplifyinstallation, the terminals are removable so thatthe panel wiring can be completed before theinstrument is installed. In areas subject tovibration wiring should be secured to preventdamage to the connectors.

Fig 6 Fitting panel mounting clamps

Page 9: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

9

3.4 Scale cardThe BA578E's units of measurement are shown ona printed scale card visible through a window at theright hand side of the display. The scale card ismounted on a flexible strip that is inserted into a slotat the rear of the instrument as shown in Fig 7.Thus the scale card can easily be changed withoutremoving the BA578E from the panel or opening theinstrument enclosure.

New instruments are supplied with a printed scalecard showing the requested units of measurement, ifthis information is not supplied when the instrumentis ordered a blank card will be fitted.

A pack of self-adhesive scale cards printed withcommon units of measurement is available as anaccessory from BEKA associates. Custom printedscale cards can also be supplied - see 4.3

To change a scale card, unclip the tapered end ofthe flexible strip at the rear of the instrument bygently pushing it upwards and pulling it out of theenclosure. Peel the existing scale card from theflexible strip and replace it with a new printed card,which should be aligned as shown below. Do not fita new scale card on top of an existing card.

Install the new scale card by gently pushing theflexible strip into the slot at the rear of theinstrument, when it reaches the internal end-stopsecure it by pushing the end of the flexible stripdownwards so that the tapered section is held by therear panel.

Align the self-adhesive printedscale card onto the flexible stripand insert the strip into theinstrument as shown below.

Fig 7 Inserting the flexible strip carrying the scalecard into slot at the rear of the instrument.

4. ACCESSORIES

4.1 Display backlightThe BA578E Timer or Clock can be supplied with afactory fitted backlight that produce greenillumination enhancing display contrast and enablingit to be read at night or in poor lighting conditions.The backlight is internally powered from theinstrument power supply so no additional wiring isrequired, but the supply current increases as shownbelow.

BA578E configured as Timer

currentconsumption

BA578E Timer or Clock 10mAAdditional for backlight 16mA

Addition with terminals 3 & 4 linked 6mAAddition with terminals 7 & 8 linked 6mA

---------------Total current 38mA max

BA578E configured as Clock

currentconsumption

BA578E Timer or Clock 10mAAdditional for backlight 16mA

---------------Total current 26mA max

4.2 Control outputsAlthough the dual isolated control outputs arefactory fitted options, they are described in the mainbody of this instruction manual as they will be usedfor the majority of applications – see section 2.5. Ifcontrol outputs are required they should be specifiedwhen the instrument is ordered.

4.3 Scale cardThe BA578E has a window on the right hand side ofthe display through which a scale card showing theunits of measurement such as hours can be seen.New instruments are fitted with a scale card showingthe units of measurement specified when theinstrument was ordered, if the units are not specifieda blank scale card will be fitted. A pack of scalecards pre-printed with common units ofmeasurement is available as an accessory. Thesecan easily be fitted on-site to the BA578E withoutopening the instrument enclosure or removing itfrom the panel. See section 3.4 of this instructionmanual.

Custom scale cards for applications requiring lesscommon units of measurement are also available.

Page 10: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

10

4.4 Tag informationNew instruments can be supplied with a tag numberor application information printed onto the rear paneladjacent to the terminals. This information is notvisible from the front of the instrument afterinstallation.

Page 11: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

11

5. OPERATION AS A TIMERWhen configured as a Timer the BA578E canmeasure and display the elapsed time betweenexternal events. The Timer can be started andstopped by remote sensors, or from the front panelpush buttons.

The addition of optional factory fitted isolated controloutputs allows the Timer to control external eventssuch as opening a valve for a predetermined time.Again the Timer can be started and stopped byremote sensors, or from the front panel pushbuttons. Timed events can be repeated using theCYCLE function which enables the BA578E Timer torepeat the timing period up to 99 times, orcontinuously, with a configurable delay betweentimed periods of up to 100 hours.

The BA578E may be configured to time-up fromzero to the set time 5Et t, or to time-down from theset time to zero. Times may be entered anddisplayed in hours, minutes or in seconds, or in acombination of units. Elapsed or remaining time iscontinuously displayed and a separate display maybe activated to show the target set time 5Et t.Throughout the timing cycle the instrument can bepaused and restarted without changing the cycletime. Resetting is accomplished via the front panelpush buttons or a remote contact.

A grand total time is maintained by the instrumentwhich can be viewed by operating the front panelpush buttons and reset from the display mode orfrom within the configuration menu.

Fig 8 shows a simplified block diagram of theBA578E when configured as a Timer. The twoseparate inputs A and b can be individuallyconfigured to accept inputs from a wide variety ofsensors. When the sensor requires energising todetect its state, such as a switch contact, opencollector or a two wire proximity detector, a linkconnected between external terminals of theBA578E supplies power to the sensor inputterminals.

The optically isolated open collector status output isintended for monitoring the Timer's status, but mayalso be used for simple control applications.

The instrument can be supplied with the followingfactory fitted accessories:

Internally powered Backlight

Dual isolated Control Outputs

The optional factory fitted dual isolated solid statecontrol outputs may be independently configured tobe activated in any of the timer's state allowing theBA578E Timer to perform a wide variety of tasks.

5.1 InitialisationEach time power is applied to a BA578Einitialisation is performed. After a short delay thefollowing display sequence occurs:

All segments of the display are activated

BA578E is ready to start functioning usingthe configuration information stored in theinstrument's permanent memory.

Fig 8 BA578E block diagram with Timerconfiguration.

Page 12: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

12

5.2 Controls when configured as a TimerThe BA578E is controlled and configured via fourfront panel push buttons. In the display mode i.e.when the instrument is timing the push buttonfunctions are:

Push Button Functions

& When local control is enabled startsthe Timer. See 5.5.9

* When local control is enables stopsthe Timer. See 5.5.9

) + * Shows the grand total (run time) inhours and tenths of an hourirrespective of Timer configuration.If buttons are held for longer thanten seconds the grand total may bereset to zero if the grand total resetsub-function Glr gtot is enabled inthe LoC r5Et configuration function.See 5.5.21

To reset the grand total to zero fromthe display mode press the) + * buttons for ten secondsuntil CLr. no is displayed. Using the& or * button change the displayto CLr. YE5 and press ).

& + * Resets the Timer to zero or to theset time 5Et t depending onwhether the Timer is configured totime-up or time-down when the twobuttons are operatedsimultaneously for more than threeseconds. This is a configurablefunction. See 5.5.20

( + * When enabled in the configurationmenu, operating these two buttonssimultaneously provides directaccess from the display mode tothe set time 5Et t and, if the repeattiming cycle is enabled, to therestart delay r5t dela See 6.5.16

( + & Shows firmware version

( + ) Accesses the configuration menu

5.3 Displays when configured as a TimerThe BA578E has two digital displays and associatedannunciators as shown on front cover of thismanual.

Elapsed time The upper display shows theelapsed time since the Timerwas started when timing-up fromzero and the remaining timewhen timing-down from the settime. Display may be formattedas hh:mm:ss; hh:mm; mm:ss orss.

Lower display The display options available onthe lower display depend onwhether the Timer repeat cyclefunction CYCLE5, which canrepeat the timing period up to 99times with a configurable delaybetween periods, is enabled.

CYCLE5 disabledThe lower display shows the settime 5ET t or the lower displaymay be disabled if not required.See 5.5.8

CYCLE5 enabledThe lower display shows thetotal number of repeat cyclesrequested together with thenumber of the current cycle.Each operation may be brieflynamed at it's start or periodicallythroughout the cycle.Alternatively the lower displaymay be disabled if not required.See 5.5.8

Reset Activated while elapsed time isannunciator being reset to zero or to the set

time 5ET t.

Status output RTx shown while status outputannunciator is activated.

Grand total Activated when the grand totalannunciator time is being shown on the

upper display.

Control output Show status of both optionalannunciators control outputs.

Page 13: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

13

5.4 Timer structureFig 9 illustrates the Timer structure and function as astate diagram. It applies when the instrument ismeasuring the time between events or is controllingexternal events.

The circles in Fig 9 represent the five Timer states,Reset, Running, Restart-delay, Paused andComplete. The lines between the circles representthe event required to move the Timer betweenstates. e.g. to initiate timing the Timer is movedfrom the Reset state to the Running state by a startevent. This could be an input signal at input A oroperation of the & button. Similarly, to pause theTimer while it is timing, the Timer must be movedfrom the Running state to the Pause state by a stopevent which could be an input on input b oroperation of the * button.

ResetIn this state the Timer is readied for operation.The Timer is stopped and loaded with zero fortiming-up or 5Et t for timing-down.

RunningEntered by a start event from the Reset orPaused states. The Timer times-up to 5et t

or times-down to zero depending upon it'sconfiguration.

PauseEntered by a stop event from Running orRestart-delay. Timer is stopped, a start eventreturns the timer to it's previous state.

Restart-delayEntered automatically from Running. At theend of the delay time automatically returns toRunning.

CompleteEntered automatically from Running whenthere are no more timing cycles to perform.

When the CYCLE5 function is enabled the timingcycle can be specified to repeat up to 99 times, orcan be configured to repeat continuously.

Page 14: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

14

5.5 Configuration as a TimerThe BA578E is configured via the four front panelpush buttons. All the configuration functions arecontained in an easy to use intuitive menu that isshown diagrammatically in Fig 10.

Each menu function is summarised in section 5.5.2of this manual and each summary includes areference to more detailed information.

All new BA578E instruments are supplied configuredas requested at the time of ordering. If configurationis not requested, the BA578E will be supplied withdefault Timer configuration as shown below, but theinstrument can easily be re-configured on-site.

Function Display DefaultAccess code CodE 0000

Function FunCtion ELAP5E

Input A inPut-A oP . CoL

Input b inPut-b oP . CoL

Debounce (each input) dEbounCE dEFAuLt

Display 2 di5P-2 5td

Start stop 5tAr5toP LoCAL

Units unit5 12 : 00 : 00

Set time 5Et t 00 : 00 : 00

Enable repeat cycle CYCLE5 oFF

Access set time from AC5Et t oFF

display mode.Direction of count uP or dn dn

Recovery from power p-fail idle

supply failure.Local total reset t-rE5Et on

Local grand total reset Gt-rE5Et oFF

External reset E-r5et 5td

Enable status output enbl off

Enable control output 1 EnbL oFF

Enable control output 2 EnbL oFF

5.5.1 Accessing configuration functionsThroughout this manual front panel push buttons areshown as &, *, ( and ). Legends displayedby the instrument are shown in a seven segmentfont just as they appear on the instrument e.g.inPut-A and Clr Gtot.

Access to the configuration menu is obtained byoperating the ( and ) push buttonssimultaneously. If the instrument is not protected byan access security code the first parameterFunCtion will be displayed. If a security code otherthan the default code 0000 has already beenentered, the instrument will display CodE. Press( to clear this prompt and enter the security codefor the instrument using the & or * push button toadjust the flashing digit and the ( push button totransfer control to the next digit. If the correct codehas been entered pressing ) will cause the firstparameter FunCtion to be displayed. If an incorrectcode is entered, or a push button is not operatedwithin ten seconds, the instrument will automaticallyreturn to the display mode.

All configuration functions and prompts are shownon the upper eight digit display.

Once within the main configuration menu therequired parameter can be selected by scrollingthrough the menu using the & or * push buttons.The Timer configuration menu is showndiagrammatically in Fig 10.

When returning to the display mode followingreconfiguration, the Timer will display dAtA followedby 5AVE while the new information is stored inpermanent memory.

Page 15: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

15

5.5.2 Summary of Timer configuration functions

This section summarises all the Timer configurationfunctions. When read in conjunction with Fig 10 itprovides a quick aid for configuring the Timer. Ifmore detail is required, each section of thissummary contains a reference to a full description ofthe function.

Display Summary of function

FunCtion Instrument functionDefines the function of the instrument.May be set to:

ELAP5E Timer configurationCloC Clock configuration

All the entries in this Timer summaryassume that the BA578E is configuredas a Timer by selecting ELAP5E.See section 5.5.3

inPut-A Configuration of Input AContains a sub-menu with two sub-functions:

inP.tYPE Selects input sensortype

dEbounCE Defines input debounceSee section 5.5.4

inP . tYPE

Configures the Timer sensor Input A toaccept one of six types of input:

VoLt5 L Voltage pulse <1 >3VVoLt5 H Voltage pulse <3 >10VCoiL Magnetic pick-off Pr . dEt Proximity detector *ContACt Switch contact *oP . CoL Open collector *

* Energise input by linking terminals 3& 4 for Input A.See section 5.5.5

dEbounCE

Defines the level of input debounceapplied to the input A to prevent falsecounting:

dEFAuLt

HEAVY

LiGHt

See section 5.5.6

Display Summary of function

inPut b Configuration of input-bAs configuration of inPut A

* Energise input by linking terminalsterminals 7 & 8 for Input b.See section 5.5.7

di5P-2 Lower displayConfigures the lower display to showset time 5Et t or, when the CYCLE5

repeat function is activated, the restartdelay count-down plus the cycle countnumber.

With CYCLE5 not enabled:

Select Lower display shows5td Set time 5et t

oFF Disables lower display.See section 5.5.8

With CYCLE5 enabled:

Select Lower display shows5td Cycle counts requested

and counts performedwith time-down shownduring requested delayperiod. Brief notificationof timer status i.e. CYCLE

or dELAY at start of eachperiod.

LAbEL Exactly as 5td but withperiodic notification oftimer status i.e. CYCLE ordELAY.

oFF Disables lower display.See section 5.5.8

5tAr5toP Starting and stopping the timerDefines how the Timer is started andstopped.

Start StopControL 1 A input high b input highControL 2 A input low b input lowControL 3 A input high A input lowControL 4 A input low A input highLoCAL & button * button

High and low inputs are specified for avoltage input. For other types ofsensor input, see section 5.5.9

Page 16: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

16

Display Summary of function

unit5 Units of displayEnables the format of the displayedtime to be selected.

12 : 00 : 00 Hours, minutes & seconds12 : 00 Hours & minutes 30 : 00 Minutes & seconds 30 Seconds

Excludes delay of optional controloutputs which is always shown inseconds and the grand total which isalways shown in hours.See section 5.5.10

5Et t Set timeThis is the BA578E Timer's setpoint.When controlling an external event viathe optional control outputs theBA578E will time-down from the settime to zero or time-up from zero to theset time.Note: Timer will only start if a non zerovalue is entered for set time 5et t.See section 5.5.11

CYCLE5 Repeat timing cycleContains a sub-menu with threesub-functions, EnbL, CYCL Cnt andr5t dELA.See section 5.5.12

Cycle function enable EnbL

Enables or disables the cycles functionwithout changing the parameters.See section 5.5.13

Cycle count CYCL Cnt

Defines the number of times that thetimer cycle is repeated.See section 5.5.14

Restart delay r5t dELA

Defines the time delay between timercycles.See section 5.5.15

AC5Et t Access 5Et t from display modeContains two sub-functions, EnbL

which when activated allows the settime 5Et t and restart delay r5t dela

to be adjusted from the display mode.The second sub-function ACCd definesa separate access code to protectaccess to 5Et t from the display mode.See section 5.5.16

Display Summary of function

uP or dn Direction of countDefines whether the Timer times-upfrom zero to the set time 5Et t, ortimes-down from 5Et t to zero.See section 5.5.17

P-FAiL Power FailureDefines how the Timer functions whenpower is restored after a power failure.Contains three alternative optionsidle, Pau5E and continue.

Idle Idle

Timer returns in stopped state as ifhaving completed single timing cycledisplaying Timer value when powerwas lost. Timing resumes when resetfollowed by start instructions arereceived.

Pause pau5e

Timer returns in paused statedisplaying Timer value when powerwas lost. Timing resumes when startinstruction is received.

Continue continue

Timer will continue without any manualintervention.See section 5.5.18

LoC r5Et Local resetContains two sub-functions whichwhen enabled allow the Timer and thegrand total, which represents totalTimer run-time, to be reset to zero viathe front panel push buttons while theTimer is in the display mode.See section 5.5.19

Local total reset r5Et . EnbL

When on is selected, Timer is reset tozero, or 5et t if timing-down, when the& and * buttons are operatedsimultaneously for more than threeseconds in the display mode.See section 5.5.20

Local grand total reset CLr Gtot

When on is selected the grand total,which represents total run-time, maybe reset to zero by operating the) and * buttons simultaneously formore than 10 seconds in the displaymode.See section 5.5.21

Page 17: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

17

Display Summary of function

e-r5et External resetDefines the time taken for closure ofexternal contacts connected toterminals RS1 & RS2 to reset theTimer.

5td 1sfa5t 2ms

See section 5.5.22

5tat op Status output Contains sub-menu with four sub-functions, EnbL, 5tat on, 5tat oFF and5tat . dELA

Note: Output is an open colletor.See section 5.5.23

Status output enable EnbL

Enables or disables the status outputwithout changing any of theparameters.See section 5.5.24

Status output on 5tat on

Status output turns on when the Timerenters the state selected in thisfunction. Output phase can bereversed. See section 5.5.25

Status output off 5tat oFF

Status output turns off when the Timerenters the state selected in thisfunction. Output phase can bereversed.See section 5.5.26

Status on delay 5tat.dELA

Introduces a specified delay betweenthe on condition occurring and thestatus output being activated.See section 5.5.27

oP1 Control output 1 (Optional) Contains sub-menu with four sub-functions, EnbL, oP1 on, oP1 oFF andoP1 dELA.See section 5.5.28

Control output enable EnbL

Enables or disables control output 1without changing the parameters.See section 5.5.29

Display Summary of function

Control output 1 on oP1 on

Control output 1 turns on when theTimer enters the state selected in thisfunction. Output phase can bereversed.See section 5.5.30

Control output 1 off oP1 oFF

Control output 1 turns off when theTimer enters the state selected in thisfunction. Output phase can bereversed.See section 5.5.31

Control output on delay oP1 dELA

Introduces a specified delay betweenthe on condition occurring and controloutput 1 closing.See section 5.5.32

oP2 Control output 2 (Optional) op2

Functions as control output 1.See section 5.5.28 to 5.5.32

CLr Gtot Resets grand total to zeroThis function resets the grand total,which represents the total Timer run-time, from within the configurationmenu when CLr YE5 is selected and5urE is entered to confirm theinstruction.Note: Once reset, the grand total cannot be recovered.See section 5.5.34

CodE Security codeDefines a four digit alphanumeric codethat must be entered to gain access tothe instrument's configuration menu.Default code 0000 disables the securityfunction and allows unrestrictedaccess to all configuration functionswhen the ( and ) buttons areoperated simultaneously in the displaymode.See section 5.5.35

r5Et dEF Reset to factory defaultsResets the BA578E to the Timerfactory default configuration shown insection 5.4 Instruction confirmed byentering 5urE.See section 5.5.36

Page 18: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

18

5.5.3 Instrument function: FunCtion

The BA578E may be configured as a Timer or as aClock. This section of the instruction manualdescribes the Timer, for details of Clockconfiguration see section 8.

To reveal the existing function of the instrumentselect FunCtion from the configuration menu andpress (. If ELAP5E is displayed, the instrument isalready configured as a Timer therefore press ) toreturn to the FunCtion prompt in the configurationmenu. If CloC is displayed, press the * or &

button to change the setting to ELAP5E followed bythe ( button which will result in a 0000 promptbeing displayed with the first digit flashing. This is arequest for the instruction to be confirmed byentering 5urE using the & or * button to adjustthe flashing digit and the ( button to move controlto the next digit. When 5urE has been entered,pressing ) will change the instrument to a Timerand return the instrument to the display mode. Toconfigure the Timer enter the configuration menu bypressing the ( and ) buttons simultaneously untilfunction is displayed.

5.5.4 Input A: inPut-A

The inPut-A function contains two sub-functionsinP . tYPE which defines the type of sensor that maybe connected to the input and dEbounCE whichadjust the amount of input noise rejection.

5.5.5 Input type: inP . tYPE

inP . tYPE is a sub-menu in the inPut-A functionwhich defines the type of input sensor that may beconnected to input A. To check or change the typeof input, select inPut-A in the configuration menuand press ( which will reveal the inP.tYPE prompt,pressing ( again will show the existing input. If setas required press ) twice to return to theconfiguration menu, or repeatedly press the * or& button until the required type of input isdisplayed, then press ) twice to return to theconfiguration menu.

One of following six types of input may be selected:

Display Input type Switchingthresholds

Low HighoPCoL Open collector² 2 10kΩVoLt5 L Voltage pulse low¹ 1 3VVoLt5 H Voltage pulse high¹ 3 10VCoiL Magnetic pick-off 0 40mVPr . dEt Proximity detector² 1.2 2.1mAContACt Switch contact² 100 1000Ω

Notes:1. Maximum voltage input +30V.

2. For sensors connected to input A thatrequire energising i.e. a proximity detector,a switch contact or an open collector,terminals 3 & 4 of the BA578E Timer shouldbe linked together.

3. To function correctly, the input signal mustfall below the lower switching threshold andrise above the higher switching threshold.

5.5.6 Debounce: dEbouncE

dEbouncE is an adjustable sub-menu in theinPut-A' function which prevents the Timermis-functioning when the input has noisy edges,such as those resulting from a mechanical contactclosing and bouncing. Three levels of protectionmay be selected and the amount of debounceapplied depends upon the type of Timer input thathas been selected in the inP . tYPE function.

The following table shows the minimum time that theinput signal must be continuously above the upperinput switching threshold and continuously below thelower switching threshold to ensure that the Timerprocesses the input signal. Input switchingthresholds are shown in section 5.5.5.

De-bouncelevel

Min input pulse width

Type of Input

Contact Allothers

Default 1600µs 40µs

Heavy 3200µs 350µs

Light 400µs 5µs

5.5.7 Input b: inPut-b

The input-b function and sub-functions are identicalto the input-A function & sub-functions described insections 5.5.4, 5.5.5 and 5.5.6.

Notes:1. Maximum voltage input +30V.

2. For sensors connected to input b thatrequire energising i.e. a proximity detector,a switch contact or an open collector,terminals 7 & 8 of the BA578E Timer shouldbe linked together.

3. To function correctly, the input signal mustfall below the lower switching threshold andrise above the higher switching threshold.

Page 19: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

19

5.5.8 Lower display: di5P-2

The configuration options for the lower display varydepending upon whether the repeat timer functioncycle5 is enabled.

CYCLE5 disabledWhen the lower display is enabled it shows theset time 5ET t

CYCLE5 enabledWhen the lower display is enabled it shows thetotal number of repeat cycles requested togetherwith the number of cycles performed. During thedelay time between cycles the display shows thetime until the next cycle starts. Menu options allow each part of the cycle to bebriefly identified at the start of each part, orperiodically throughout the cycle.

To check or change the configuration of the lowerdisplay select di5P-2 from the configuration menuand press ( which will reveal the existing settingwhich can be changed by pressing the * or &

button followed by the ) button to enter theselection and return to the configuration menu.

If the CYCLE5 function is not enabled thefollowing two options are available:

5td Lower display shows the Timer's set time5Et t, to which the BA578E will time-up to,or time-down from, depending upon thedirection of count selected in the uP or dn

function.

oFF Lower display disabled.

If the CYCLE5 function is enabled the followingthree options are available:

5td Lower display shows the number of cyclesrequested together with the current cyclenumber. During the configurable delayperiod between cycles the display times-down from the requested delay to zero. Abrief notification of timer status i.e. CYCLE

or dELAY is shown at the start of eachperiod.

02 -11Current Number of cycles

cycle number. requested, notshown when cycle is

continuously repeated.

LabEL Exactly the same as 5td, but timer statusi.e. CYCLE or dELAY is shown periodically.

oFF Lower display disabled.

5.5.9 Starting & stopping the Timer: 5tAr5toP

The Timer may be started and stopped by signals onInput A and Input b, or by operation of the front panel* or & push buttons.

To check or change the control of the Timer, select5tAr5toP from the configuration menu and press (

which will reveal the existing setting which can bechanged by pressing the * or & button followedby the ) button to enter the selection and return tothe configuration menu. The options available areshown in the following tables.

Voltage inputs and control from front panelDisplay Start Stop

ControL 1 A input high b input highControL 2 A input low b input lowControL 3 A input high A input lowControL 4 A input low A input highLoCAL & button * button

Contact and open collector inputsDisplay Start Stop

ControL 1 A open b openControL 2 A closed b closedControL 3 A open A closedControL 4 A closed A open

Proximity detector inputDisplay Start Stop

ControL 1 A low current b low currentControL 2 A high current b high currentControL 3 A low current A high currentControL 4 A high current A low current

5.5.10 Units of display: unit5

Defines the format of all displayed times, except thedelay time of the status output and optional controloutputs which are always shown in seconds and thegrand total which is always shown in hours andtenths of an hour.

To check or change the units of display, select unit5

from the configuration menu and press ( whichwill reveal the existing setting which can be changedby pressing the * or & button followed by the )

button to enter the selection and return to theconfiguration menu. The options available areshown in the following tables:

Display12 : 00 : 00 Hours, minutes & seconds12 : 00 Hours & minutes* 30 : 00 Minutes & seconds 30 Seconds

* Only available when time specified in seconds for5et t and r5t dela are zero or exactly divisible by60.

The Timer's maximum elapsed time in any format isequivalent to 99hours, 59 minutes & 59 seconds.

Page 20: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

20

Page 21: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

21

Page 22: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

22

5.5.11 Set time: 5Et t

Set time is the Timer's setpoint. When controlling anexternal event via the optional control outputs theBA578E will time-down from the set time to zero ortime-up from zero to the set time.

To check or change the set time, select 5Et t fromthe configuration menu and press ( which willreveal the existing setting displayed in the unitsdefined by the unit5 function with the mostsignificant digit flashing. The flashing digit may beadjusted by pressing the * or & button followedby the ( button to transfer control to the next digit.When set as required, enter the selection and returnto the 5Et t prompt in the configuration menu byoperating the ) button.

Can also be adjusted from Timer display mode, see5.5.16.

Note: If 5Et t is zero the Timer will not functionwhen an external start input is received or the &

button is operated.

5.5.12 Repeat timing cycle: CYCLE5

This a powerful function which allows the BA578Etiming cycle to be repeated up to 99 times orcontinuously with a configurable delay betweencycles of up to 99hours, 59 minutes & 59 seconds.

To check or adjust the repeat timing cycle, selectcycle5 from the configuration menu and press( which will enter a sub-menu containing threesub-functions, EnbL, CYCL Cnt and r5t dELA whichare described in the following sections.

5.5.13 Cycle function enable: EnbL

This sub-function allows the repeat timing cycle tobe enabled or disabled without altering any of therepeat timing cycle parameters. To check or changethe function select EnbL from the repeat timing cyclesub-menu cycle5s and press ( which will reveal ifthe repeat cycle function is on or oFF. The settingcan be changed by pressing the & or * buttonfollowed by the ) button to return to the repeattiming cycle sub-menu.

5.5.14 Cycle count: cycl cnt

This sub-function defines the number of times thetimer cycle is repeated. It may be set to any numberbetween 1 and 99, or to 00 for continuous repetition.To check or change the function select cycl cnt

from the repeat timing cycle sub-menu cycle5 andpress ( which will reveal the number of times thetimer cycle is to be repeated with the mostsignificant flashing. The flashing digit may beadjusted by pressing the * or & button followedby the ( button to transfer control to the next digit.

When set as required, enter the selection and returnto the cycl cnt prompt in the sub-menu by operatingthe ) button.

5.5.15 Restart delay: r5t dela

This sub-function defines the time delay betweenrepeat timing periods. It is shown in the formatselected in the units function and may be set to anytime between zero and the maximum time allowed inthe selected format.

Time format Maximum delay selected in

unit5

12 : 00 : 00 99 : 59 : 59

12 : 00 99 : 59

30 : 00 5999 : 59

30 359999

To check or change the restart delay time selectr5t dela from the repeat timing cycle sub-menucycle5 and press ( which will reveal the delaytime in the selected format with the most significantdigit flashing. The flashing digit may be adjusted bypressing the * or & button followed by the( button to transfer control to the next digit. Whenset as required, enter the selection and return to ther5t dela prompt in the sub-menu by operating the) button.

Can also be adjusted from Timer display mode, see5.5.16.

5.5.16 Adjusting the set time 5Et t and restart delay r5t dela from the display mode: AC5Et t

When this function is enabled the Timer's set time5Et t and restart delay r5t dela can be adjustedfrom the display mode by simultaneously operatingthe ( and * push buttons. Thus allowing anoperator to adjust these parameters without havingaccess to the instrument's configuration menu. Thefunction contains two sub-functions, EnbL whichactivates the function and ACCd which defines aseparate code for access to 5Et t with the Timer inthe display mode.

To check or change the function, select AC5Et t inthe configuration menu and press ( which willreveal the EnbL prompt, pressing ( again will showif the function is on or oFF. If adjustment of the settime from the display mode is not required press the* or & button to select no and then press )

twice to return to the configuration menu. If thefunction is required, select YE5 and press ) toreturn to the EnbL prompt from which ACCd, whichallows a separate access code to be entered, canbe selected by pressing the * or & button.

Page 23: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

23

Access to 5Et t from the display mode may beprotected by a four digit alphanumeric security codewhich must be entered to gain access. Defaultsecurity code 0000 allows unrestricted access. WithACCd displayed, press ( to enter a new accesscode. The Timer will display 0000 with one digitflashing. The flashing digit may be adjusted usingthe * or & push button, when set as requiredoperating the ( button will transfer control to thenext digit. When all the digits have been enteredpress ) twice to return to the AC5Et t prompt in theconfiguration menu. The revised access code will beactivated when the BA578E is returned to thedisplay mode.Please contact BEKA associates sales department ifthe access code is lost.

5.5.17 Direction of count: uP or dn

The Timer may be configured to time-up from zero tothe set time 5Et t while displaying elapsed time, orto time-down from the set time 5Et t to zero whiledisplaying the remaining time.

When the repeat timing cycle function CYCLE5 isenabled, it is recommended that a down count isselected so that the progress of the timer can beobserved with a known completion time i.e. zero. Ifset as an up counter, elapsed time will be displayed,but the set time 5et t at which the timer will stop isnot shown.

To check the direction of count, select uP or dn fromthe configuration menu and press ( which willreveal the existing setting. This can be changed bypressing the * or & button followed by the )

button to enter the selection and return to theconfiguration menu.

5.5.18 Power Fail: P-FAiL

Defines how the Timer powers-up and functionswhen power is restored after a power supplyinterruption. Three options are available, idle,Pau5e and continue.

idle The Timer is stopped in the state it achieveswhen it has timed-up to 5et t or timed-downto zero, with the elapsed or remaining timewhen power was lost shown on the upperdisplay. The Timer must be reset before itcan be restarted. If the repeat timing cycleis in use the number of cycles completedwill be lost when the Timer is reset.

Pau5e The Timer is stopped in the state it achievesfollowing receipt of a stop input to pausetiming – see Fig 9. The elapsed orremaining time when power was lost isshown on the upper display. Timing resumeswhen a start instruction is received. If astart input exists when power is restoredtiming will start immediately.

Continue When power is restored the Timer willcontinue from where it stopped without anymanual intervention.

To check or change the function, select P-fail fromthe configuration menu and press ( which willreveal the existing setting which can be changed bypressing the * or & button followed by the )

button to enter the selection and return to theconfiguration menu.

5.5.19 Local reset: LoC r5Et

The Local reset function contains two separate sub-functions rE5Et . Enbl and Glr Gtot which whenenabled allow the Timer and the grand total to bereset via the instrument's front panel push buttonswhile the Timer is in the display mode.

5.5.20 Local total reset: rE5Et . enbl

rE5Et . enbl is a sub-function in the Loc r5Et functionwhich when activated allows an operator to reset theTimer from the display mode by operating the *

and & push buttons simultaneously for more thanthree seconds.

To check or change the local total reset selectLoC r5Et in the configuration menu and press( which will reveal the rE5Et . enbl prompt, press( again to show if the local total reset is on or oFF.If set as required operate the ) button twice toreturn to the configuration menu, or the * or &

button to change the setting followed by the )

button twice to enter the change and return to theLoC . r5Et prompt in the configuration menu.

Note:The Timer may also be reset remotely byconnecting terminals RS1 and RS2 together.See section 2.3

5.5.21 Local grand total reset: Clr Gtot

The grand total is the total run-time of the Timer thatmay be viewed by operating the ) and * pushbuttons simultaneously in the display mode. Whenactivated clr Gtot allows an operator to reset thegrand total display to zero from the display mode byoperating the ) and * push buttonssimultaneously for more than ten seconds.

clr Gtot is a sub-function in the LoC r5Et menu. Tocheck or change the setting select LoC r5Et in theconfiguration menu and press ( which will revealrE5Et . enbl. Using the & or * button selectclr Gtot and press ( to show if local grand totalreset is on or oFF. If set as required operate the )

button twice to return to the configuration menu, orthe & or * button to change the setting followedby the ) button twice to enter the change andreturn to the LoC r5Et prompt in the configurationmenu.

Page 24: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

24

5.5.22 External resetThe Timer may be reset by connecting terminalsRS1 and RS2 together. This function defines howlong the connection must exist before resettingoccurs. When resetting is performed by a manuallyoperated external push button switch, 5td should bechosen. This requires the contact to be closed forone second before resetting occurs which preventsfalse resetting.

If the Timer is being reset by the a control output orsimilar apparatus Fa5t should be selected.

Select Resetting time5td 1sfa5t 2ms

5.5.23 Status output: 5tat oP

The status output of the Timer is an opto isolatedopen collector that can be used for transmitting thestatus of the Timer to other instruments. It may alsobe used for simple control applications. When theStatus output is on the RTx annunciator on theTimer display is activated.

The status output function contains four sub-functions, EnbL, 5tat on, 5tat oFF and 5tat.dELA. Togain access to the sub-menu select 5tat op in theconfiguration menu and press ( which will showthe EnbL prompt from which the other sub-functionscan be accessed using the & or * button.

The status output may be configured to turn onwhen the Timer enters a selected Timer state and toturn off when the Timer enters another specifiedTimer state. e.g. if run is selected in the 5tat on

sub-function and done is selected the 5tat off

function. The status output will turn on when theTimer enters the run state and will stay on until theTimer enters the done state. Alternatively, the statusoutput phase may be reversed by selecting the n

states such as n re5et.

If the status output is required to be on in only oneTimer state, this can be achieved with the followingconfiguration.

5tat on state required e.g. run

5tat off n state required e.g. n run

In this example when the Timer enters the run statethe status output turns on. When the Timer movesfrom the run to any other state, the status outputturns off.

5.5.24 Status output enable: EnbL

This function allows the status output to be enabledor disabled without altering any other status outputparameters. To check or change the function selectEnbL from the status output sub-menu and press (

to reveal if the status output is on or oFF. Thesetting can be changed by pressing the & or *

button followed by the ) button to return to thestatus output sub-menu.

5.5.25 Status output on : 5tat on

The status output may be configured to turn onwhen the Timer enters any one of the five Timerstates. Alternatively, the status output phase may bereversed by selecting an n state. This will cause thestatus output to turn on when the Timer enters anyother than the specified Timer state. Timer statesare shown in Fig 9.

To define when the status output turns on select5tat on from the sub-menu and press ( to showthe existing setting. Pressing the & or * buttonwill scroll through the options:

Display Status output turns on when Timer enters selected state

re5et Reset state run Running statepau5ed Paused statedelay Restart delay statedone Complete state

Status output turns on when Timer enters any other than the selected state

n re5et Reset state n run Running staten pau5ed Paused staten delay Restart delay staten done Complete state

When the required setting has been selected press) to enter the selection and return to the statusoutput sub-menu.

Page 25: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

25

5.5.26 Status output off : 5tat off

The status output may be configured to turn offwhen the Timer enters any one of the five Timerstates. Alternatively, the status output phase maybe reversed by selecting an n state. This will causethe status output to turn off when the Timer entersany other than the specified Timer state. Timerstates are shown in Fig 9.

To define when the status output is off select5tat off from the sub-menu and press ( to showthe existing setting. Pressing the & or * buttonwill scroll through the options:

Display Status output turns off when Timer enters selected state

re5et Reset state run Running statepau5ed Paused statedelay Restart delay statedone Complete state

Status output turns off when Timer enters any other than the selected state

n re5et Reset state n run Running staten pau5ed Paused staten delay Restart delay staten done Complete state

When the required setting has been selected press) to enter the selection and return to the statusoutput sub-menu.

5.5.27 Status output on delay time: 5tat . dELA

The status output may be delayed from turning on

for a fixed time following the selected conditionoccurring. e.g. when the timer enters the Run state.This delay is useful for many control applications, forexample when the status output is connected to thereset terminals RS1 and RS2 to automatically resetthe BA578E Timer.

This delay can be adjusted in 1 second incrementsup to 32,400 seconds, which is 9 hours. If a delay isnot required zero should be entered. To adjust thedelay select 5tat . dELA from the status output sub-menu and press ( which will reveal the existingdelay time with one digit flashing. The flashing digitcan be adjusted using the & or * button and the( button to move to the next digit. When therequired delay has been entered, press ) to returnto the status output sub-menu.

5.5.28 Control output 1 (optional): op1

Control output 1 is an optional factory fitted,galvanically isolated solid state switch contact whichcan be configured to turn on and off when the Timerenters specified states. When control output 1 is onthe '1' annunciator on the Timer display is activated.

The function contains four sub-functions, EnbL,op1 on, op1 oFF and op1 dELA. To gain access to thesub-menu select op1 in the configuration menu andpress ( which will show the EnbL prompt fromwhich the other sub-functions can be accessedusing the & or * button.

Control output 1 may be configured to turn on whenthe Timer enters a selected Timer state and to turnoff when the Timer enters another specified Timerstate. e.g. if run is selected in the op1 on sub-function and done is selected the op1 off function.Control output 1 will turn on when the Timer entersthe run state and will stay on until the Timer entersthe done state. Alternatively, the control outputphase may be reversed by selecting the n statessuch as n re5et.

If control output 1 is required to be on in only oneTimer state, this can be achieved with the followingconfiguration.

op1 on state required e.g. run

op1 off n state required e.g. n run

In this example when the Timer enters the run statecontrol output 1 turns on. When the Timer movesfrom the run to any other state, control output 1turns off.

The Timer configuration example in section 6.2 ofthis manual illustrate the use of the control outputs.Further examples can be found in Application GuideAG374 which is available on the BEKA website.

5.5.29 Control output 1 enable: EnbL

This function allows control output 1 to be enabledor disabled without altering any other control outputparameters. To check or change the function selectEnbL from the control output 1 sub-menu and press( to reveal if control output 1 is on or oFF. Thesetting can be changed by pressing the & or *

button followed by the ) button to return to thecontrol output 1 output sub-menu.

Page 26: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

26

5.5.30 Control output 1 on : op1 on

Control output 1 may be configured to turn on whenthe Timer enters in any one of the five Timer states.Alternatively, the control output 1 phase may bereversed, by selecting an n state which will causethe control output to turn on when the Timer entersany other than the specified Timer state. Timerstates are shown in Fig 9.

To define when control output 1 turns on selectop1 on from the sub-menu and press ( to show theexisting setting. Pressing the & or * button willscroll through the options:

Display Control output 1 turns on when Timer enters selected state

re5et Reset state run Running statepau5ed Paused statedelay Restart delay statedone Complete state

Control output 1 turns on when Timer enters any other than the selected state

n re5et Reset state n run Running staten pau5ed Paused staten delay Restart delay staten done Complete state

When the required setting has been selected press) to enter the selection and return to the statusoutput sub-menu.

5.5.31 Control output 1 off : op1 off

Control output 1 may be configured to turn off whenthe Timer enters any one of the five Timer states.Alternatively, the phase of control output 1 may bereversed, by selecting an n state which will causethe control output to turn off when the Timer entersany other than the specified Timer state. Timerstates are shown in Fig 9.

To define when control output 1 turns off selectop1 off from the sub-menu and press ( to showthe existing setting. Pressing the & or * buttonwill scroll through the options:

Display Control output 1 turns off when Timer enters selected statere5et Reset state run Running statepau5ed Paused statedelay Restart delay statedone Complete state

Control output 1 turns off when Timer enters any other than the selected state

n re5et Reset state n run Running staten pau5ed Paused staten delay Restart delay staten done Complete state

When the required setting has been selected press) to enter the selection and return to the controloutput 1 sub-menu.

5.5.32 Control output 1 on delay time: op1 dELA

Control output 1 may be delayed from turning on

(output closed) for a fixed time following the selectedcondition occurring. e.g. when the Timer enters therun state. This delay is useful for many controlapplications, for example when the control output isconnected to the reset terminals RS1 and RS2 toautomatically reset the BA578E Timer.

The delay can be adjusted in 1 second incrementsup to 32,400 seconds, which is 9 hours. If a delay isnot required zero should be entered. To adjust thedelay select op1 dELA from the control output 1 sub-menu and press ( which will reveal the existingdelay time with one digit flashing. The flashing digitcan be adjusted using the & or * button and the( button to move to the next digit. When therequired delay has been entered, press ) to returnto the control output 1 output sub-menu.

6.5.33 Control output 2 (optional): op2

Control output 2 is an optional, galvanically isolatedsolid state switch contact which can beindependently configured to turn on and off whenthe Timer is any of it's five states. It's functionsand configuration are identical to control output 1described in sections 5.5.28 to 5.5.32. When controloutput 2 is on the '2' display annunciator is activated.

Page 27: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

27

5.5.34 Reset grand total from within the configuration menu: Clr Gtot

The grand total is the total run-time of the Timer thatmay be viewed by operating the ) and * pushbuttons simultaneously in the display mode.

The grand total can be reset to zero from within theconfiguration menu using this Clr Gtot function, orfrom the display mode if Clr Gtot is activated in thelocal grand total clear function - see 5.5.21

To zero the Timer grand total from within theconfiguration menu select Clr Gtot and press (

which will cause the instrument to display Clr. no

with no flashing. Operate the & or * push buttonuntil Clr . YE5 is displayed and then press ( whichwill result in a 0000 prompt being displayed with thefirst digit flashing. This is a request for theinstruction to be confirmed by entering 5urE usingthe & or * button to adjust the flashing digit andthe ( button to move control to the next digit.Pressing ) will then reset the grand total to zeroand return the Timer to the configuration menu.

Note:Once reset, the grand total can not berecovered.

5.5.35 Security code: CodE

Access to the instrument configuration menu may beprotected by a four digit alphanumeric security codewhich must be entered to gain access. Newinstruments are configured with the default securitycode 0000 which allows unrestricted access to allconfiguration functions.

To enter a new security code select CodE from theconfiguration menu and press ( which will causethe Timer to display 0000 with one digit flashing.The flashing digit may be adjusted using the * or& push button, when set as required operating the( button will transfer control to the next digit.When the new security code has been enteredpress ) to return to the CodE prompt. The revisedsecurity code will be activated when the Timer isreturned to the display mode.

Please contact BEKA associates sales department ifthe security code is lost.

5.5.36 Reset configuration to factory defaultsr5Et dEF

When the BA578E is configured as a Timer thisfunction resets the instrument to the Timer factorydefaults shown in section 5.5.

To reset the configuration select r5Et dEF from theconfiguration menu and press (. The BA578E willdisplay 0000 with the first digit flashing which is arequest to confirm the instruction by entering 5urE.Using the * or & button set the first flashing digitto 5 and press ( to transfer control to the seconddigit which should be set to u. When 5urE has beenentered pressing the ) button will reset all theconfiguration functions and return the instrument tothe display mode.

Note:r5Et dEF does not reset the grand total tozero.

Page 28: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

28

6. TIMER APPLICATION EXAMPLESThis section illustrates two applications for theBA578E when configured as a Timer.

6.1 Measuring the time that a contact is closed.

In this example a BA578E is required to display thetime that a process area contact is closed. Thedisplay is required in hours and minutes and is to bereset to zero by an exterior push button, not by theinstrument front panel push buttons. The operatoris required to zero the grand total by operating the) + * buttons simultaneously. No securitycodes are required to protect access to theconfiguration menu or to the grand total reset.

Figure 11 shows the BA578E connections. Thisexample illustrates how the Timer may be startedand stopped by one input, the second input is notused in this application.

Fig 11 Starting & stopping timer with one input

The required instrument configurations for thisexample are shown below.

Function Display SettingAccess code CodE 0000

Function FunCtion ELAP5E

Input A inPut-A ContACt

De-bounce Input A dEbounCE dEFAuLt

Display 2 di5P-2 oFF

Start stop 5tAr5toP ControL 4

Units unit5 12 : 00

Set time 5Et t 9999 : 59 :59

Local total reset rE5E EnbL oFF

Local grand total reset Clr Gtot on

6.2 Controlling a solenoid valveThis example illustrates how a BA578E Timer canopen a solenoid valve for 5 minutes each time astart button is operated. The operator needs topause the process without affecting the total timethat the valve is open. At the end of the process theTimer is required to automatically reset within 10seconds ready for the next timing cycle to bestarted.

For this application the BA578E Timer requires dualcontrol outputs which are a factory fitted option andshould be specified when the instrument is ordered.

Control output 1 is used to switch the intrinsicallysafe solenoid valve, and control output 2 is wired tothe Timer's reset terminals to perform the automaticresetting at the end of the timing cycle, see Fig 12.

The Timer is configured to perform one timing cyclecycl cnt with a restart delay r5t dela of 5s and Settime 5et t is adjusted to 5 minutes the required timethat that the valve is to be open.

Control outputs are configured so that control outputone is only closed when the timer is in the Run state.Control output 2 is configured to only close when theTimer is in the Done state which occurs after it hasbeen in the Restart-delay state for 5 seconds. Thesequence of events is shown in Fig 12 and theTimer's configuration at the end of this section.

This valve opening process is to be linked to otherprocesses, therefore the status output is required toindicate when the 5 minute valve open period hasbeen completed and when the Timer has been resetand is ready for the next cycle.

When the start button is operated the Timer entersthe Running state and control output 1 closes for 5minutes opening the solenoid valve. At the end ofthe 5 minute period control output 1 opens whichcloses the solenoid valve and the Timer enters theRestart-delay state for 5 seconds followed by theDone state. Control output 2 is configured to closewhen the Timer is in the Done state. Control output2 is externally connected to the Timer's resetterminals which causes the Timer to automaticallyreset ready to start another cycle when the startbutton is operated.

If at any time during the cycle the stop button isoperated the Timer will enter the Pause state whichwill stop the process until the start button is operatedwhen it will resume without shortening the total valveopen time.

Page 29: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

29

Fig 12 Control of valve in a process area.

The required instrument configurations for thisexample are shown below.

Function Display SettingAccess code CodE 0000

Function FunCtion ELAP5E

Input A inPut-A ContACt

Input b inPut-b ContaCt

De-bounce (both inputs) dEbounCE dEFAuLt

Display 2 di5P-2 5td

Start stop 5tAr5toP ControL 2

Units unit5 12 : 00 : 00

Set time 5Et t 00 : 05 : 00

Timer repeat cycle CYCLE5

Enable repeat cycle EnbL on

Cycle count cycl cnt 01

Reset delay r5t dela 0000.05

Access set time from AC5Et - t oFF

display mode.Direction of count uP or dn dn

Power failure p-fail idle

Local total reset rE5Et . EnbL on

Local grand total reset CLr Gtot oFF

External reset e r5et fa5t

Enable control output 1 EnbL on

Control output 1 on at oP1 on run

Control output 1 off at oP1 oFF n run

Control output 1 delay oP1 dELA 00000

Enable control output 2 EnbL on

Control output 2 on at oP2 on done

Control output 2 off at oP2 oFF n done

Control output 2 delay oP2 dELA 00005

Enable status output EnbL on

Status output on at 5tat on re5et

Status output off at 5tat oFF n re5et

Statuss output delay 5tatdELA 00000

In this example local total reset rE5Et . EnbL is on.This enables the Timer to be reset when power isfirst connected by operating the * and & downbutton simultaneously for more than 3 seconds.

Page 30: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

30

7. MAINTENANCE when configured as a Timer

7.1 Fault finding during commissioningIf a BA578E fails to function as a Timer duringcommissioning the following procedure should befollowed:

Symptom Cause Check:

No display No powersupply, or

incorrect wiring.Note: Terminals2, 6, 10 & RS2

areinterconnected

within theinstrument.

That there isbetween 10 and

30V onterminals 1 & 2with terminal 1

positive.

Instrumentconfiguration

menu does notcorrespond withTimer section of

this manual.

BA578E may beconfigured as a

clock.

That FunCtion

in configurationmenu is set toELAP5E not to

CloC.

Timer will notstart.

Timer not reset

Set time 5Et t

has not beenentered.

Reset timer viaexternal contactor by operating

* and &buttons

simultaneouslyif the local total

reset r5Et enbL

function hasbeen activated.

Enter time otherthan zero for

5Et t'.

Timer will notrespond to

sensor inputs.

Input A and/orInput b

incorrectlyconfigured, or

sensorincorrectlyconnected.

Input A andinput b

configurationand that input

energisinglink(s) are

correctly fittedfor selected

sensors.

Controloutput(s) do not

function.

Control outputshave not been

enabled.

Enable ControlOutput(s) in the

configurationmenu.

Unable to enterconfiguration

menu.

Incorrectsecurity code

That the correctsecurity code is

being used.

Contact BEKA ifcode is lost.

7.2 Fault finding after commissioning

ENSURE PLANT SAFETY BEFORESTARTING MAINTENANCE

If a BA578E fails after it has been functioningcorrectly, the following table may help to identify thecause of the failure.

Symptom Cause Check:

No display No powersupply

That there isbetween 10 and

30V onterminals 1 & 2with terminal 1

positive.

Timer will notstart.

Timer not reset Reset timer viaexternal contactor by operating

* and &buttons

simultaneously iflocal total resetrE5Et . EnbL hasbeen activated.

Controloutput(s) do not

function.

Control Outputshave not been

enabled.

Enable ControlOutput(s) in the

configurationmenu.

Unable to enterconfiguration

menu.

Incorrectsecurity code

That the correctsecurity code is

being used.Contact BEKA if

code is lost.

If this procedure does not reveal the cause of thefault, it is recommended that the instrument isreplaced.

Note:If configuration changes are made to any ofthe following functions the Timer will beforced into a fail safe idle condition. Thisstops the Timer in the state it achieveswhen it has timed-up to 5et t or timed-downto 0000. The Timer must be reset before itcan be restarted.

Input A, Input b, 5tart5top, cycle5,up or dn, op1 and op2.

Page 31: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

31

7.3 ServicingWe recommend that faulty BA578E Timers arereturned to BEKA associates or to our local agent forrepair. It is helpful if a brief description of the faultsymptoms is provided.

7.4 Routine maintenanceThe mechanical and electrical condition of theinstrument should be regularly checked. Inspectionfrequency should be chosen to suit theenvironmental conditions.

7.5 GuaranteeInstruments which fail within the guarantee periodshould be returned to BEKA associates or our localagent. It is helpful if a brief description of the faultsymptoms is provided.

7.6 Customer commentsBEKA is always pleased to receive comments fromcustomers about our products and services. Allcommunications are acknowledged and wheneverpossible, suggestions are implemented.

Page 32: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

32

8. OPERATION AS A CLOCKWhen configured as a clock the BA578E can displaylocal time in a variety of twelve or twenty four hourformats. The displayed time can be adjusted viathe front panel push buttons which may be protectedby a user definable four digit security code toprevent unauthorised or accidental adjustment.

The clock may be synchronised to an external timestandard via the instrument's reset terminals. Whenthese two terminals are connected together by anexternal switch contact, the clock display will bereset to a preconfigured time and will resumerunning from this time when the contacts areopened.

The optically isolated status open collector outputcan be used to monitor the clock or to performsimple control functions.

When fitted with the optional galvanically isolatedcontrol outputs the clock can be configured to turneach solid state output on and off twice during eachtwenty four hour period.

Fig 13 shows a simplified block diagram of theBA578E configured as a clock.

The instrument can be supplied with the followingfactory fitted accessories:

Backlight Internally powered

Dual isolated control outputs

Fig 13 BA578E block diagram with clock configuration.

8.1 Initialisation and loss of powerEach time power is applied to a BA578Einitialisation is performed. After a short delay thefollowing display sequence occurs:

All segments of the display are activated

Instrument starts functioning, using theconfiguration information stored in theinstrument's permanent memory.

Following initialisation, the instrument will have aflashing display which is a request for the local timeto be entered. The clock will not start to functionuntil a display time has been entered, or the remotereset contacts are closed and opened tosynchronise the clock to a preconfigured time.

If during normal operation the power supply isinterrupted for more than 30ms, the display willreturn to the flashing condition and the display timewill have to be re-entered. This time may beincreased by powering the Clock from a lightlyloaded instrument supply with large outputcapacitance.

8.2 Controls when configured as a clock The BA578E clock is configured and adjusted viafour front panel push buttons. In the display modei.e. when the instrument is displaying time, the pushbutton functions are:

Push Button Functions

( + & Shows firmware version

( + ) Access to configuration menu

Note: When optional control outputs are fitted, theBA578E clock may be configured to provide directaccess to the control outputs from the display modewhen the ( and * push buttons are operatedsimultaneously. - see section 8.4.16

8.3 Displays when configured as a clockThe BA578E clock has a single digital display plusannunciators.

Time Shows time in selected 12 ordisplay 24 hour format.

Reset Activated while clock is beingannunciator synchronised and external

reset contacts are closed.

Status output RTx shown while status annunciator output is activated.

Control output Show status of both optionalannunciators control outputs.

Page 33: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

33

8.4 Configration as a ClockThe BA578E is configured and calibrated via fourfront panel push buttons. All the configurationfunctions are contained in an easy to use intuitivemenu that is shown diagrammatically in Fig 14.

Each menu function is summarised in section 8.4.2of this manual and each includes a reference tomore detailed information.

All new BA578E instruments are supplied configuredas requested at the time of ordering. If configurationis not requested, the BA578E will be supplied withdefault Timer configuration as shown in section 5.5.

If a BA578E Clock is requested without detailedconfiguration information, the instrument willsupplied with default Clock configuration as shownbelow, but can easily be re-configured on-site.

Function Display DefaultAccess code CodE 0000

Function FunCtion CLoC

Display di5PLAY 12 : 00

Set display time 5Et A 12 : 00 : 00

Syncronise time 5YnC t A 12 : 00 : 00

Enable status output enbl off

Enable control output 1* EnbL oFF

Enable control output 2* EnbL oFF

Enable access alarm AC5P oFF

times from display mode.Access code for alarm ACCd 0000

times from display mode.

Note: * Control outputs are a factory fitted option.

8.4.1 Accessing configuration functionsThroughout this manual push buttons are shown as&, *, ( and ) and legends displayed by theClock are shown in a seven segment font just asthey appear on the instrument e.g. di5PLAY andCodE.

Access to the configuration menu is obtained byoperating the ( and ) push buttonssimultaneously. If the instrument is not protected byan access security code the first parameterFunCtion will be displayed. If a security code otherthan the default code 0000 has already beenentered, the instrument will display CodE. Press( to clear this prompt and enter the security codefor the instrument using the & or * push button toadjust the flashing digit, and the ( push button totransfer control to the next digit. If the correct codehas been entered pressing ) will cause the firstparameter FunCtion to be displayed. If an incorrectcode is entered, or a push button is not operatedwithin ten seconds, the instrument will automaticallyreturn to the display mode.

All configuration functions and prompts are shownon the upper eight digit display.

Once within the main configuration menu therequired parameter can be selected by scrollingthrough the menu using the & or * push button.The Clock configuration menu is showndiagrammatically in Fig 14.

When returning to the display mode followingreconfiguration, the Clock will display dAtA followedby 5AVE while the new information is stored inpermanent memory.

Page 34: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

34

Page 35: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

35

Page 36: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

36

8.4.2 Summary of Clock configuration functions.

This section summarises all the Clock configurationfunctions. When read in conjunction with Fig 14 itprovides a quick aid for configuring the Clock. Ifmore detail is required, each section of thissummary contains a reference to a full description ofthe function.

Display Summary of function

FunCtion Instrument functionDefines the function of theinstrument.May be set to:

ELAP5E TimerCloC Clock

All the entries in this Clockconfiguration summary assume thatthe BA578E is configured as a Clockby selecting CLoC.See section 8.4.3

di5PLAY Display formatDefines the clock display format,four alternatives are available.Select:

12 : 00 Twelve hours without seconds12 : 00 : 00 Twelve hours with seconds24 : 00 Twenty four hours without seconds24 : 00 : 00 Twenty four hours with secondsSee section 8.4.4

5Et Set clock display timeEnables the clock displayed time tobe adjusted, the clock resumesoperation when the instrument isreturned to the display mode.See section 8.4.5

5YnC t Synchronising timeDefines the time to which the clockdisplay is set when the resetterminals RS1 and RS2 areconnected together. The Clockrestarts from the synchronising timewhen terminals RS1 and RS2 aredisconnected.See section 8.4.6

Display Summary of function

5tat op Status output Status output can turn on (opencollector on) and off (open collectoroff) once or twice in each twenty-fourhour period. This function containsfive sub-function:

EnbL Enables Status output anddefines if it turns on and off onceor twice in each 24 hours.

5tat : on 1 Time when oP 1 turns on 1st time5tat : oFF 1 Time when oP 1 turns off 1st time5tat : on 2 Time when oP 1 turns on 2nd time5tat : oFF 2 Time when oP 1 turns off 2nd time

Note: Output is an optically isolated open collector.

See sections 8.4.7 to 8.4.9

oP1 Control output 1 (Optional)Control output 1 can turn on (outputclosed) and off (output open) once ortwice in each twenty-four hour period.This function contains five sub-function:

EnbL Enables output 1 and defines ifit turns on and off once or twicein each 24 hours.

oP 1 : on 1 Time when oP 1 turns on 1st timeoP 1 : oFF 1 Time when oP 1 turns off 1st timeoP 1 : on 2 Time when oP 1 turns on 2nd timeoP 1 : oFF 2 Time when oP 1 turns off 2nd timeSee sections 8.4.10 to 8.4.12

oP2 Control output 2 (Optional)As control output 1 described above.See section 8.4.13 to 8.4.15

AC5P Access control output alarm-timesfrom display mode.Contains two sub-functions, EnbL

which when activated allows thecontrol output times to be adjustedfrom the display mode (displayingtime). The second sub-function ACCd

defines a four digit alphanumericaccess code which may be used toprotect access to the control outputtimes from the display mode. Defaultcode 0000 disables this securityfeature and allows unrestrictedaccess.See section 8.4.16

Page 37: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

37

Display Summary of function

CodE Security codeDefines a four digit alphanumeric codethat may be used to protect access tothe Clock configuration menu. Defaultcode 0000 disables this securityfunction and allows unrestrictedaccess to all configuration functionswhen the ( and ) buttons areoperated simultaneously in the displaymode.See section 8.4.17

r5Et dEF Reset to factory defaultsResets the BA578E to the Clockfactory default configuration shown insection 8.4 Instruction confirmed byentering 5urE.See section 8.4.18

8.4.3 Instrument function: FunCtion

The BA578E may be configured as a Timer or as aClock. This section of the instruction manualdescribes the Clock, for details of Timerconfiguration see section 5.4.

To reveal the existing function of the instrumentselect FunCtion from the configuration menu andpress (. If CLoC is displayed, the instrument isalready configured as a Clock therefore press ) toreturn to the FunCtion prompt in the configurationmenu. If ELAP5E is displayed, press the * or &

button to change the setting to CLoC followed by the( button which will result in a 0000 prompt beingdisplayed with the first digit flashing. This is arequest for the instruction to be confirmed byentering 5urE using the * or & button to adjustthe flashing digit and the ( button to move controlto the next digit. When 5urE has been entered,pressing ) will change the instrument to a Clockand return the instrument to the display mode. Toconfigure the Clock enter the configuration menu bypressing the ( and ) buttons simultaneously untilfunction is displayed.

8.4.4 Display format: di5PLAY

The BA578E Clock may be configured to displaytime in a 12 or 24 hour format with or withoutseconds. When a 12 hour format is selected, AM isdenoted by an A prefix at the left hand side of thedisplay, similarly a P is displayed to denote PM.

To check or change the display format of the Clock,select di5PLAY from the configuration menu andpress ( which will reveal the existing setting whichcan be changed by pressing the * or & buttonfollowed by the ) button to enter the selection andreturn to the configuration menu. The optionsavailable are shown below:

12 : 00 Twelve hour format without seconds12 : 00 : 00 Twelve hour format with seconds24 : 00 Twenty four hour format without seconds24 : 00 : 00 Twenty four hour format with seconds

8.4.5 Set clock display time: 5Et

This function sets the time displayed by the Clockwhich must be entered each time the BA578E Clockis powered. Until a set time is entered the Clock willdisplay a flashing 00 : 00 : 00 or 00 : 00 depending uponhow it has been configured.

To adjust the clock set time, select 5Et from theconfiguration menu and press ( that will show00 : 00 : 00 or the existing set time with the hoursflashing. When setting the clock display timeseconds are always shown. Using the * or &

button adjust the flashing hours and then press (

to transfer control to the minutes display, pressing( again will transfer control to the seconds display.When adjustment is complete press ) to start theClock and return to the 5Et prompt.

Page 38: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

38

8.4.6 Enter synchronising time: 5YnC t

When the external reset terminals RS1 and RS2 areconnected together the clock is stopped and thedisplayed time is set to the synchronising time.When the connection between the reset terminals isremoved, the clock restarts from the synchronisingtime.

To enter the synchronising time, select 5YnC t fromthe configuration menu and press ( which willreveal the existing synchronising time with the hoursflashing. Using the * or & button adjust thehours and then press ( to transfer control to theminutes display, pressing ( again will transfercontrol to the seconds display. When thesynchronising time has been set as required, press) to return to the configuration menu.

8.4.7 Status output: 5tat op

The status output is an optically isolated opencollector that can be used for transmitting the statusof the Clock to other instruments. It may also beused for simple control applications. Status on isindicated by the RTx front panel display annunciator.The function contains five sub-functions allowingthe Status output open collector to be turned on andoff once or twice in each twenty four hour period.

EnbL Number of times status outputturns on & off in 24 hours.

5tat : on 1 First time Status oP turns on 5tat : oFF 1 First time Status oP turns off 5tat : on 2 Second time Status oP turns on5tat : oFF 2 Second time Status oP turns off

To check or change the function of the status outputselect 5tat op from the configuration menu andpress ( which will reveal the first sub-functionEnbL.

8.4.8 Enable Status output: EnbL

This is a sub-function in the Status output function5tat which allows the status output open collector tobe enabled or disabled without changing any of theon or off times and also determines whether thestatus output turns on and off once or twice in eachtwenty four hour period.

Select 5tat in the configuration menu and press (

which will result in the EnbL prompt being displayed.Pressing ( again will enter the sub-function fromwhich one of the three options may be selectedusing the * or & button:

Display Status outputoFF Status output disabledon : 1 Turns on & off once per 24 hourson : 2 Turns on & off twice per 24 hours

When the required option is displayed operating )

will enter the selection and return to the EnbL promptfrom which another sub-function may be selected.

8.4.9 On and off times: 5tat:on 1; 5tat:off 1

5tat:on 2; 5tat:off 2

The status output will have one or two on and offtimes depending upon whether it has beenconfigured to turn on and off once or twice in each24 hour period. - see 8.4.8.

All of the times are adjusted in the same way. Toadjust any of them select 5tat op from theconfiguration menu and press ( which will result inthe EnbL prompt being displayed. The * or &

button will scroll through the sub-functions. Only5tat:on 1 and 5tat:off1 will be present if the statusoutput has been configured to switch on and offonce in a 24 hour period in the EnbL sub-function.

Select the required sub-function

5tat : on1 Time status output turns on first time5tat : oFF1 Time status output turns off first time5tat : on 2 Time status output turns on second time5tat : oFF2 Time status output turns off second time

When selected, pressing ( will show the existingtime with the hours flashing. Using the * or &

button adjust the hours and then press ( totransfer control to the minutes display, pressing (

again will transfer control to the seconds display.When the time has been set as required press ) toreturn to the sub-menu from which another on / offtime may be selected for adjustment. When all theon / off times have been entered, return to theconfiguration menu by pressing the ) button twice.

8.4.10 Control output 1: oP1Control output 1 is an optional factory fittedgalvanically isolated solid state switch contact outputwhich can be configured to turn on (output closed)and off (output open) twice in each twenty-four hourperiod. The control output status is shown by the 1control output display annunciator.

Function oP1 contains a sub-menu with five sub-functions:

EnbL Number of times output 1turns on & off in 24 hours.

oP 1 : on 1 First time oP 1 turns on (closes)oP 1 : oFF 1 First time oP 1 turns off (opens)oP 1 : on 2 Second time oP 1 turns on (closes)oP 1 : oFF 2 Second time oP 1 turns off (opens)

To check or change the function of Control output 1select oP1 from the configuration menu and press( which will reveal the first sub-function EnbL.

Page 39: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

39

8.4.11 Enable Control output 1: EnbL

This is a sub-function in the Control output 1 functionoP1 which allows output 1 to be enabled or disabledwithout changing any of the on or off times and alsodetermines whether output 1 turns on and off onceor twice in each twenty four hour period.

Select oP1 in the configuration menu and press (

which will result in the EnbL prompt being displayed.Pressing ( again will enter the sub-function fromwhich one of the three options may be selectedusing the * or & button:

Display Control output 1oFF Control output 1 disabledon : 1 Turns on & off once per 24 hourson : 2 Turns on & off twice per 24 hours

When the required option is displayed operating )

will enter the selection and return to the EnbL promptfrom which another sub-function may be selected ifcontrol output 1 has not been disabled.

8.4.12 On and off times: oP 1 : on 1; oP 1 : off 1

oP 1 : on 2; oP 1 : off 2

The control output will have one or two on and offtimes depending upon whether control output 1 hasbeen configured to turn on and off once or twice ineach 24 hour period. - see 8.4.11.

All of the times are adjusted in the same way. Toadjust any of them select oP1 from the configurationmenu and press ( which will result in the EnbLprompt being displayed. The * or & button willscroll through the sub-functions. Only oP 1 : on 1 andoP1 : oFF1 will be present if control output 1 has beenconfigured to switch on and off once in a 24 hourperiod in the EnbL sub-function.

Select the required sub-function

oP1 : on1 Time oP1 turns on first timeoP1 : oFF1 Time oP1 turns off first timeoP1 : on2 Time oP1 turns on second timeoP1 : oFF2 Time oP1 turns off second time

When selected, pressing ( will show the existingtime with the hours flashing. Using the * or &

button adjust the hours and then press ( totransfer control to the minutes display, pressing (

again will transfer control to the seconds display.When the time has been set as required press ) toreturn to the sub-menu from which another on / offtime may be selected for adjustment. When all theon / off times have been entered, return to theconfiguration menu by pressing the ) button twice.

8.4.13 Control output 2: oP2Control output 2 is an optional factory fitted outputwhich can be configured to turn on (output closed)and off (output open) twice in each twenty-four hourperiod. The control output status is shown by the 2control output display annunciator.

Function oP2 contains a sub-menu with five sub-functions:

EnbL Number of times output 2turns on & off in 24 hours.

oP 2 : on 1 First time when oP 2 turns on (closes)oP 2 : oFF 1 First time when oP 2 turns off (opens)oP 2 : on 2 Second time when oP 2 turns on (closes)oP 2 : oFF 2 Second time when oP 2 turns off (opens)

To check or change the function of Control output 2select oP2 from the configuration menu and press( which will reveal the first sub-funtion EnbL.

8.4.14 Enable control output 2: EnbL

This is a sub-function in the Control output 2 functionoP2 which allows output 2 to be enabled or disabledwithout changing any of the on or off times and alsodetermines whether output 2 turns on and off onceor twice in each twenty four hour period.Select oP2

in the configuration menu and press ( which willresult in the EnbL prompt being displayed. Pressing( again will enter the sub-function from which oneof the three options may be selected using the * or& button:

Display Control output 2oFF Control output 2 disabledon : 1 Turns on & off once per 24 hourson : 2 Turns on & off twice per 24 hours

When the required option is displayed operating )

will enter the selection and return to the EnbL promptfrom which another sub-function may be selected ifcontrol output 2 has not been disabled.

8.4.15 On and off times: oP2 : on 1; oP2 : off 1

oP2 : on 2; oP2 : off 2

The control output will have one or two on and offtimes depending upon whether control output 2 hasbeen configured to turn on and off once or twice ineach 24 hour period. - see 8.4.14.

All of the times are adjusted in the same way. Toadjust any of them select oP2 from the configurationmenu and press ( which will result in the EnbL

prompt being displayed. The * or & button willscroll through the sub-functions. Only oP21 : on 1

and oP2 : oFF1 will be present if control output 2 hasbeen configured to switch on and off once in a 24hour period in the EnbL sub-function.

Page 40: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

40

Select the required sub-function

oP2 : on1 Time oP2 turns on first timeoP2 : oFF1 Time oP2 turns off first timeoP2 : on2 Time oP2 turns on second timeoP2 : oFF2 Time oP2 turns off second time

When selected pressing ( will show the existingtime with the hours flashing. Using the * or &

button adjust the hours and then press ( totransfer control to the minutes display, pressing (

again will transfer control to the seconds display.When the time has been set as required press ) toreturn to the sub-menu from which another on / offtime may be selected for adjustment. When all theon / off times have been entered, return to theconfiguration menu by pressing the ) button twice.

8.4.16 Access control output on and off times from display mode: AC5P

This function activates a separate menu thatprovides direct access to the control output's on andoff times when the Clock is is the display mode(displaying time). An operator may therefore adjustthe on and off times without having access to theinstrument configuration menu. Further protection isprovided by a separate security code. When thisfunction is enabled the on and off times of the twocontrol outputs may be adjusted from the displaymode by simultaneously operating the ( and *

push buttons. The function contains two sub-functions, EnbL which activates the function andACCd which defines a separate access code thatmay be used to prevent the on and off times beingaccidentally adjusted from the display mode.

To check or change the function, select AC5P in theconfiguration menu and press ( which will revealthe EnbL prompt, pressing ( again will show if thefunction is on or oFF. If adjustment of the controloutput times from the display mode is not requiredpress the * or & button to select off and thenpress ) twice to return to the configuration menu.If the function is required, select on and press ) toreturn to the EnbL prompt from which ACCd, whichallows a separate access code to be entered, canbe selected by pressing the * or & button.

Access to the control output times from the displaymode may be protected by a four digit alphanumericsecurity code which must be entered to gain access.Default security code 0000 allows unrestrictedaccess. With ACCd displayed, press ( to enter anew access code. The BA578E Clock will display0000 with one digit flashing. The flashing digit maybe adjusted using the * or & push button, whenset as required operating the ( button will transfercontrol to the next digit. When all the digits havebeen adjusted press ) twice to return to the AC5P

prompt in the configuration menu. The revisedsecurity code will be activated when the BA578E isreturned to the display mode.

8.4.17 Security code: CodE

Access to the instrument's configuration menu maybe protected by a four digit alphanumeric securitycode which must be entered to gain access. Newinstruments are configured with the default securitycode 0000 which allows unrestricted access to allconfiguration functions.

To enter a new security code select CodE from theconfiguration menu and press ( which will causethe Clock to display 0000 with one digit flashing.The flashing digit may be adjusted using the * or& push button, when set as required operating the( button will transfer control to the next digit.When all the digits have been adjusted press ) toreturn to the CodE prompt. The revised security codewill be activated when the Clock is returned to thedisplay mode.

Please contact BEKA associates sales department ifthe security code is lost.

8.4.18 Reset configuration to factory defaults:r5Et dEF

When the BA578E is configured as a Clock, thisfunction resets the configuration to the Clock factorydefaults shown in sections 8.4 of this manual.

To reset the instrument configuration selectr5Et dEF from the configuration menu and press (.The Clock will display 0000 with the first digit flashingwhich is a request to confirm the instruction byentering 5urE. Using the * or & button set thefirst flashing digit to 5 and press ( to transfercontrol to the second digit which should be set to u.When 5urE has been entered pressing the )

button will reset all the configuration functions to thefactory defaults and return the instrument to thedisplay mode as a Clock with default configuration.

Page 41: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

41

9. CLOCK CONFIGRATION EXAMPLEIn this example a BA578E is required to function asa Clock. Time is to be displayed in a 24 hour formatincluding seconds. For external synchronisation thedisplayed time is required to change to 12 : 00 : 00

when the external reset terminals are connectedtogether.

Both control outputs are required to close and openonce in each 24 hour period. Control output 1 (oP1)is to turn on (close) at 07 : 30 : 00 and off (open) at09 : 30 : 00, control output 2 (oP2) is to turn on (close)at 18 : 00 : 00 and off (open) at 22 : 30 : 00.

For this application the operator needs to adjust thecontrol output on and off times from the displaymode via an access code of 1111. To preventtampering the instrument configuration menu is to beprotected by security code of 1209

9.1 Configuration procedureThe BA578E may be configured as a Clock on-sitewithout disconnection from external wiring.

Step 1 Enter the configuration menuEnter the configuration menu bysimultaneously pressing ( and ).Assuming a security code has not alreadybeen entered the instrument will respond bydisplaying FunCtion which is the first item inthe configuration menu. See Fig 14.

Step 2 Configure instrument as a ClockWith FunCtion displayed press ( to revealthe existing function of the instrument. IfCloc is displayed no change is required,therefore return to the FunCtion prompt bypressing the ) button.If ELAP5E is displayed, press the * or &

button to change the setting to CLoC

followed by the ( button which will result ina 0000 prompt being displayed with the firstdigit flashing. This is a request for theinstruction to be confirmed by entering 5urE

using the & or * button to adjust theflashing digit and the ( button to movecontrol to the next digit. Pressing ) willthen change the instrument to a Clock andreturn the display to FunCtion in theconfiguration menu.See 8.4.3

Step 3 Select display formatUsing the * or & button select di5PLAY inthe configuration menu and press ( whichwill reveal the current display format. Usingthe * or & button select 24 : 00 : 00 which isthe required 24 hour format with secondsand press ) to enter the selection andreturn to the configuration menu.See 8.4.4

Step 4 Enter the synchronisation timeUsing the * or & button select 5YnC t inthe configuration menu and press ( toreveal the current synchronisation time withthe hours flashing. Using the * or &

push button adjust the hours to 12 andpress ( to transfer control to the minutes.Using the * or & push button adjust theminutes to 00 and press ( to transfercontrol to the seconds which should beadjusted to 00, in the same way. When theseconds are set enter the selection andreturn to the 5YnC t prompt in theconfiguration menu by pressing the )

button.See 8.4.6

Step 5 Enable control output 1 and enter the onand off times.Using the * or & button select oP1 in theconfiguration menu and press ( to revealthe EnbL prompt in the control output 1 sub-menu.

In this application control output 1 isrequired to turn on and off once every 24hours. With EnbL displayed press ( andusing the * or & button select on 1

followed by the ) button to return to theEnbL prompt.

The control outputs on time should now beentered by selecting oP1 : on1 in the controloutput 1 sub-menu using the * or &

button. Pressing ( will reveal the existingon time which should be adjusted to07 : 30 : 00 using the * or & button and the( button to transfer control to the followingdigits. When entered return to the oP1 : on1

prompt by pressing the ) button.

The off time should now be entered byselecting oP1 : oFF1 from the sub-menu andadjusting the time to 09 : 30 : 00. Finally press) to return to the oP1 : oFF1 prompt inthe sub-menu and press ) again to returnto oP1 in the configuration menu.

Page 42: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

42

Step 6 Enable control output 2 and enter the onand off times.Using the * or & button select oP2 in theconfiguration menu and press ( to revealthe EnbL prompt in the control output 2 sub-menu. Follow the procedure described instep 5, but set control output 2 to turn on at18 : 00 : 00 and off at 22 : 30 : 00.

Step 7 Allow control outputs times to beadjusted from the display mode & enterseparate security code.Using the * or & button select AC5P in theconfiguration menu and press ( to revealthe EnbL prompt, pressing ( again willshow if this function is on or oFF. Using the* or & button select on followed by ) toreturn to the EnbL prompt. A separatesecurity code which must be entered to gainaccess to the alarm times in the displaymode, is entered in the ACCd function whichmay be selected by operating the * or &

button once. Pressing ) will reveal theexisting access code with one digit flashing.This should be changed to the requiredcode of 1111 by adjusting the flashing digitusing using the * or & button and the (

button to transfer control to the next digit.When 1111 has been entered press )

twice to return to the configuration menu.See 8.4.16

Step 8 Define the configuration menu securitycode.Defining a security code preventsunauthorised access to the configurationmenu. Using the & and * buttons selectCodE from the configuration menu and press( which will reveal 0000 with the first digitflashing. This example requires the securitycode to be 1209, using the & and *

buttons set the flashing digit to 1 and press( to transfer control to the second digit.When all have been entered press ) toreturn to the main configuration menu.See 8.4.17.

Step 9 Return to the display modeThe BA578E is now configured as requiredfor this example. Pressing the ) buttonwill save the configuration and return theBA578E to the display mode with all thedigits flashing indicating that the set timehas to be entered.

Step 10Enter the set timeFinally the current time to be displayed bythe Clock should be entered. Re-enter theconfiguration menu by pressing the ( and) buttons simultaneously which will resultin code being displayed. Pressing ( willallow the access code 1209 to be enteredusing the & or * button to adjust theflashing digit and the ( button to transfercontrol to the next digit. When all four digitshave been adjusted, press ( to enter theconfiguration menu and using the & or *

button select 5Et and press ) which willreveal 00 : 00 : 00 with the hours flashing.Using the & or * button adjust theflashing hours digit and press ( to transfercontrol to the minutes and then to theseconds. When all have been set asrequired, press ) to start the clock fromthe entered time and return to the displaymode.

Page 43: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

43

10. MAINTENANCE when configured as a clock

10.1 Fault finding during commissioningIf a BA578E fails to function as a Clock duringcommissioning the following procedure should befollowed:

Symptom Cause Check:

No display No power supply, orincorrect wiring.

Note: Terminals 2 &RS2 are

interconnectedwithin the

instrument.

That there isbetween 10 and

30V on terminals 1& 2 with terminal 1

positive.

That there are noconnections to

terminals3, 4, 5, 6, 7, 8, 9 &

10.

Configuration menudoes not

correspond with theClock section of this

manual.

BA578E isconfigured as a

Timer.

That FunCtion inconfiguration menuis set to CLoC not to

ELAP5E.

Clock displayflashes

'00 : 00 : 00'

Local time has notbeen entered.

Enter the local timein the 5Et functionof the instrument

configuration menu.

Control output(s) donot function.

Control outputshave not been

enabled.

Enable ControlOutput(s) in the

configuration menu.

Clock will not start Reset terminalsRS1 and RS2 are

connected togetherand the Clock is

continuouslysynchronising.

If reset annunciatoron display isactivated, disconnect

connection betweenRS1 and RS2.

Unable to enterconfiguration menu.

Incorrect securitycode

That the correctsecurity code is

being used.

Contact BEKA ifcode is lost.

10.2 Fault finding after commissioning

ENSURE PLANT SAFETY BEFORESTARTING MAINTENANCE

If a BA578E fails after it has been functioningcorrectly as a Clock, the following table may help toidentify the cause of the failure.

Symptom Cause Check:

No display No power supply That there isbetween 10 and

30V on terminals 1& 2 with terminal 1

positive.

Clock displayflashes 00 : 00 : 00

Instrument powersupply has been

interrupted and localtime has been lost.

Enter the local timein the 5Et functionof the instrument

configuration menu.

Control output(s) donot function.

Control outputshave not been

enabled.

Enable ControlOutput(s) in the

configuration menu.

Clock will not start Reset terminalsRS1 and RS2 are

connected togetherand the Clock is

continuouslysynchronising.

If reset annunciatoron display is

activated, if it isdisconnect

connection betweenRS1 and RS2.

Unable to enterconfiguration menu.

Incorrect securitycode

That the correctsecurity code is

being used.

Contact BEKA ifcode is lost.

If this procedure does not reveal the cause of thefault, it is recommended that the instrument isreplaced.

10.3 ServicingWe recommend that faulty BA578E Clocks arereturned to BEKA associates or to our local agent forrepair.

10.4 Routine maintenanceThe mechanical and electrical condition of theinstrument should be regularly checked. Inspectionfrequency should be chosen to suit theenvironmental conditions.

10.5 GuaranteeInstruments which fail within the guarantee periodshould be returned to BEKA associates or our localagent. It is helpful if a brief description of the faultsymptoms is provided.

Page 44: BA578E Two input General purpose Timer or Clock · Timer 5. Operation as a timer 6. Configuration example 7. Maintenance Clock 8. Operation as a clock 9. Configuration example 10

44

10.6 Customer commentsBEKA is always pleased to receive comments fromcustomers about our products and services. Allcommunications are acknowledged and wheneverpossible, suggestions are implemented.