DP0418009

Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation and instructions

1. Please read the instruction carefully before you use, please retain it for reference. 2. The picture is only for reference , please prevail in kind

Page 2: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation
Page 3: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

Contents

1. Introduction…….…………………………...……………………..……...1

2. Product overview...……….…………………….….………….…….….2

3. Installation and dimension ……………….…….………....……….….3

3.1 Installation………..………………………………………………………3

3.2 DPT63 …………....……………………………………….…...….…….3

3.3 DPT160……..………......…………………….….……….…….……….4

3.4 DPT250………..………….………………….……..………...…..….....5

4. Operating…….………………….……………..………….….………….7

4.1 Manual operation……………………………………...……..……...….7

4.2 Electrical operating/Manual Mode………………………….......…….8

4.3 Electrical operating/Automatic Mode …..……………………….…....8

4.4 Locking………………………….……………………....….………..…..9

5. Control Unit……………….….………………………....…….......…...10

5.1 Function introduction…….…..………………..……..………....…….10

5.2 Interface ………………..…………….….……….……..……....…….10

5.3 Operation Mode setting....... ……………...................……....……..11

5.4 Function and threshold setting….………………….....…….…..…..12

6. Connections.………………………………………………...…………15

6.1 Main circuit connections.………………….…..………….……...…...15

6.2 Control circuit connections.………….……………….….…..…....….15

7. Maintenance and Troubleshooting…….………...……….……....…15

7.1 Maintenance………………..…...….………………..….………....….15

7.2 Troubleshooting….………...……………………….….…..……...…..16

Page 4: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 1 -

1.Introduction This manual describes the installation and the basic operation of the automatic transfer switches. Use of symbols

Hazardous voltage: warns about a situation where a hazardous voltage may cause physical injury to a person or damage to equipment.

General warning: warns about a situation where something other than electrical equipment may cause physical injury to a person or damage to equipment.

Caution: provides important information or warns about a situation that may have a detrimental effect on equipment.

Information: provides important information about the equipment.

Page 5: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 2 -

2. Product overview Automatic transfer switch (class CB)is used to ensure power supply for different occasions . You can operate the automatic transfer switch either electrically or manually.

1. primary line 2. changeover switch 3. handle for manual operation 4. secondary line 5. control unit 6. control unit connecting wiring

You can choose Type CB010 or CB011 control unit for each type of changeover switch.

Page 6: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 3 -

3. Installation and dimension 3.1 Installation The recommended mounting positions for automatic transfer are horizontal, wall mounted or table mounted.

Do not install the Automatic transfer switches in any position than those described above.

3.2 Type DPT63

× M6×503.5...4Nm

12012

9139

102 113

195

215

435

455

144 186

185

37.5

122= =

80

4- 6.5

Page 7: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 4 -

3.3 Type DPT160

M6 ×40

M6×503.5...4Nm

131

138148

510

122

8037

.5

=

195

215

165 216

4- 6.5

111 122

185

490

Page 8: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 5 -

3.4 Type DPT250 3.4.1 Installation

M6 ×4 0

M6×503.5...4Nm

205

410

430

185

205

131

138148

122= =

37.5

80

4- 6.5

Page 9: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 6 -

3.4.2 Installation for Control unit

The installation and dimension for control unit CB010 and CB011 are the same.

1314

1516

1718

1920

2122

+-

2324

2526

2728

2930

3132

3334

3536

Q1

Q2Q1

Q2

8393

185

197

8293

4- 4.5

3.4.3 Control Unit and Changeover connection

Only an authorised electrician may perform the electrical installation and maintenance of OTM_ automatic transfer switches. Do not attempt any installation or maintenance actions when an OTM_ automatic transfer switch is connected to the electrical mains.

Avoid to attach or insert terminals when the terminal voltage 380V a.c

1314151617181920212212VQ2TQ1TQ2OQ2CQ1OQ1CQ2KQ1K

321MSW1SW2

Page 10: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 7 -

4. Operating

Never open any covers on the product. There may be dangerous external control voltages inside the automatic transfer switch even if the voltage is turned off.

Never handle control cables when the voltage of the automatic transfer switch or external control circuits are connected.

You must operate automatic transfer switch manually before the voltage is connected.

4.1 Manual operation You can operate the automatic transfer switch manually by using the handle that is

included in the delivery. To operate the automatic transfer switch manually: a. Turn selector to the MANU position on control unit. b. Turn the AUTO/MANU selector to the MANU position on changeover switch.

c. Attach the handle by pressing it to the changeover switch until it clicks into place

When mechanism is not parked on ON/I,OFF,ON/II position base on severe abnormalities. You need to tap the handle to make it to the right place, and operate the switch manually. Remark: you need to press the handle and the mechanism and motor off.

d. Operate the changeover switch by handle to the required position(I,O.II).

Page 11: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 8 -

4.2 Electrical operation/Manual Mode Electrical operation is means that turn the knob to sent a signal to operate

changeover switch, U1 colse;U1,U2 open; U2 close.

a.Release the handle from the changeover switch panel by pressing down the locking latch under the switch panel and pulling the handle off.

b.Turn the AUTO/MANU selection switch to AUTO position.

c.Turn the knob to the required position(U1 close;U1,U2 open;U2 close). And the mechanism has delay time function, parameter setting shown in Section 6.

U1 close U1 U2 open U2 close

4.3 Electrical operating/Automatic Mode a. Make sure that the handle has been removed before electrical operation

(automatic mode). b. Turn the AUTO/MANU selection switch to the AUTO position. c. Parameter setting refer to Section 6. d. Control unit can detect and control changeover switch after setting.

The mechanism does not run if A phase and C phase missing of U1 and U2 at the same time, then just only operate the switch manually by using handle.

Page 12: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 9 -

4.4 Locking

4.4.1 Locking the electrical operation You can lock the electrical operation in all position(I,O,II). a.Pull up the locking latch under the changeover switch panel. b.Place the padlock under the latch .

5... 6

The handle cannot be attached when electrical operation is locked.

4.4.2 Locking the manual operation

Manual operation can only be locked on position O. a.Turn the handle to the required position. b.Pull out the clip from the handle and place the padlock on the handle.

The handle cannot be removed when manual operation is locked,and manual operation and electrical operation disable.

Page 13: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 10 -

5. Control unit

Control unit must be disconnected from the main circuit during the insulation test.

Base on the difference function configuration, we have CB010 and CB011 for you to choose. 5.1 Function introduction

CB010 CB011

Under-voltage transfer ×

Over-voltage transfer ×

Phase missing transfer

Delay time setting(s) 1.5 0,3,5,10,15,20,30 Refusing to perform alarm

Release alarm

Phase missing alarm

Over-voltage alarm ×

N pole mistake alarm

Fire fighting

Generator start function ×

5.2 Interface

power state

changeoverswitch state

alarm type

function mode selection

working state

working modeselection

110

70

1

T1

RESET

U 1

UV

90OV

130UV

110

70U 2

90OV

130Ue%

ON

1

alarm

0

3

510

15

20

30

T20

3

510

15

20

30

working state

working modeselection

alarm

function mode selection

CB010 control unit CB011 control unit

Page 14: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 11 -

5.3 Control unit Operation Mode setting

U1 means primary line,U2 means secondary line.

5.3.1 The selection of Operation Mode

Automatic

Mode Manual Mode Electrical operation/Manual Mode

U1 close U1,U2 open U2 close

The setting is activated after the botton lasts more than 1 second in the right position.

5.3.2 Running Mode selection

The function mode setting must be on automatic mode,and the function mode is activated after pressing reset botton.

CB010 control unit

U1 priority/No line priority

ON

1

No line priority

Knob

U1 priority

CB011 control unit 1.The original setting is U1 priority. 2.Manual back switching(base on customer).

Page 15: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 12 -

U1 priority/No line priority U1 priority/Manual back switching

110

70

1

U1

UV

90OV

130UV

110

70U2

90OV

130Ue%

ON

1

110

70U1

UV

90OV

130UV

110

70U2

90OV

130Ue%

ON

1

T1

RESET

0

510

15

30

T20

3

510

15

20

30

T1

RESET

0

510

15

30

T20

3

510

15

20

30

3 20 3 20

1

No line priority

Knob

U1 priority

Manual back switching

Knob

U1 priority

5.4 Control unit function and threshold setting

1. under-voltage transfer When UI has under-voltage fault, control unit sent a signal to transfer to U2. The value of under-voltage threshold is adjustable ,the range:70%~90% Ue. When control unit detects the under-voltage fault of U1 and U2 (less than 70%Ue)at the same time, control unit will sent a signal to transfer to O position.

110

70

1

U1

UV

90OV

130UV

110

70U2

90OV

130Ue%

ON

1

T1

RESET

0

510

15

30

T20

3

510

15

20

30

3 20

U1 under-voltage setting

U2 under-voltage setting

2.Over-voltage transfer When UI has over-voltage fault ,control unit sent a signal to transfer to U2. The value of over-voltage threshold is adjustable ,the range:110%~130% Ue. When control unit detects the over-voltage fault of U1 and U2 at the same time, control unit will sent a signal to transfer to O position.

110

70

1

U1

UV

90OV

130UV

110

70U2

90OV

130Ue%

ON

1

T1

RESET

0

510

15

30

T20

3

510

15

20

30

3 20

U1 over-voltage setting

U2 over-voltage setting

Page 16: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 13 -

3. Phase missing transfer When UI has phase missing fault,control unit sent a signal to transfer to U2. When control unit detects phase missing fault of U1and U2 at the same time,control unit will sent a signal to transfer to O position. Motor operator is not working when A phase and C phase missing at the same time. 4.Delay time setting T1:Power state confirmation time .It means that the time from the controller monitor a failure to confirm it or from monitor the failure is recovered to confirm it. T2:Power supply close delay time .It means that the shortest delay time from O position to I or II position. Remark: delay time threshold:0,3,5,10,15,20,30 seconds.

110

70

1

U1

UV

90OV

130UV

110

70U2

90OV

130Ue%

ON

1

T1

RESET

0

510

15

30

T20

3

510

15

20

30

3 20T1

T2

5.Alarm When control unit sent a conversion signal,the change-over switch execute command failed,then control unit stops to sent a conversion signal and sent a alarm signal. Control unit CB010 Fault light and alarm light blink, and has an alarm sound. Control unit CB011 Refusing to perform light and alarm light blink, and has an alarm sound.

Control unit CB010 do not have refusing to perform light.

You need to press the reset botton to reset to automatic mode of control unit after waiting to the failure relieved.

Page 17: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 14 -

6.Trip alarm When the load failure cause breaker tripped: Control unit CB010 fault light and alarm light blink, and has an alarm sound. Control unit CB011 tripped light and alarm light blink, and has an alarm sound.

When breakers tripped caused by overload or short circuit of primary line, changeover cannot change to secondary line automatically .Then you must to check the cause and finish processing ,kickback the breakers manually.

DPT63 model do not have this function.

7.Phase missing alarm When power supply has phase missing fault: Control unit CB010 fault light and alarm light blink,and has an alarm sound. Control unit CB011 phase missing light and alarm light blink,and has an alarm sound. 8. over-voltage and under-voltage alarm Control unit alarm light and trouble light blink and has an alarm sound when power supply has over-voltage or under-voltage fault. 9. Alarm for N pole wrong connection For 4 pole,when you connect N pole wiring into A,B or C phase: Control unit CB010 fault light and alarm light blink ,and has an alarm sound. Control unit CB011 overvoltage light and alarm light blink ,and has an alarm sound. 10.Fire fighting When fire control centre sent a fire signal to control unit, control unit will sent a conversion signal to transfer the switch to O position.And alarm light blink,has an alarm sound. Connections shown in Section 7.

You need to press the reset botton to reset the automatic mode after fire fighting relieved.

The signal send by fire control centre should be 24V d.c., more than 1 second.

11.Generator Start Automatically As electric power for primary line, and generator for secondary line, control unit will sent out a signal to start generator when there is a fault of power supply, waiting for generator power stable ,then change-over switch will transfer to secondary line. Connections shown in Section 7.

Page 18: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 15 -

6. Connection 6.1 Main circuit connections

3P 4P2P

6.2 Control circuit connections

+-2324252627282930313233343536

13141516171819202122

13141516171819202122

13141516171819202122

*

13141516171819202122

24V d.c.

4321 5 6 7 8 9 10 11 12U1N U1A U1B U1CU2NU2AU2BU2CMSW1SW2

1 2

SW2 SW1

3

M U1N U1A U1B U1CU2NU2AU2BU2C

4P2P

U1N U1A U1B U1CU2NU2AU2BU2C

3P*terminal 23,24 for customers connecting 24V d.c. fire signal that lasts more than 1 second is activate.terminal 25~36:passive contacts for customers connecting, Control unit CB010 do not have generator start function.(3A/250V a.c.,3A/28V d.c.)

Terminalsforcustomers

TerminalsonDPT

Alarm Q1 close Q2 close Q1 trip Q2 trip Fire fightingGenerator start

Motor operation U2 input U1 input

U2 connection U1 connection

monitor signals for two switches

7.Maintenance and troubleshooting 7.1 Maintenance To ensure the reliability of the change-over switch, and should be

periodically (recommended every three months) carried out a transfer test to confirm the change-over switch is working properly.

Page 19: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

- 16 -

7.2 Troubleshooting

S/N state analysis action

1 Power supply normally, the controller without any display

1.Cables are not connected terminals 2.The cable has loosen which it was

connected controller and changeover switch.

1.Check it and connect it again 2.Check it and plug in again

2 Controller is connected, but it can not automatic transfer.

1.Control unit or changeover switch is on manual state, or electrical locking ,or handle mounted.

2.Terminal loose 3.Fuse is broken 4.delay time setting is wrong 5.Fire fighting signal input to controller 6.Voltage is out of the normal range

1.Change to automatic Mode or relieve electrical locking or remove the handle

2.Check it and plug in again 3.Change fuse 4.Modify the delay time setting 5.Cancel the fire fighting signal 6.Check voltage, make sure the

voltage range in 70% ~130%.

3 OTM_C_D transfer continually

1.loose or poor connect between cable and terminal 2.Voltage fluctuating, and the fluctuation range beyond the overvoltage or under voltage setting value

1.Check the connections 2.Reset the value of overvoltage or under-voltage(eg.change115% to 125%) or enlarge changeover delay time setting

4 Primary line is normal, but DPT change to secondary line

terminal connection loose(primary line terminal or control unit connection) Check and troubleshooting

5 Fire fighting fault

1.fire fighting is not 24V d.c. 2.fire fighting signal is in wrong polarity 3.fire fighting signal lasts less than 1 second

Please input the correct fire fighting signal, it must be 24V.d.c.and last more than 1 second.

6 Power supply normally, but control unit display phase lost

1.loose or poor connect between cable and terminal Check and troubleshooting

7

CB010 has been at trouble alarm

1.line loss phase missing 2.N pole is connected mistakenly to A,B

or C phase Check and troubleshooting

8 CB011 has been at overvoltage alarm

1.Line overvoltage 2.N pole is connected mistakenly to A,B or C phase

Check and troubleshooting

Page 20: Automatic transfer switch (Class CB) DPT-CB010/CB011 Installation

ABB Xinhui Low Voltage Switchgear Co., Ltd. Jingzhou Industrial Development Zone, Xinhui District, Jiangmen, Guangdong, 529100 Tel : 0750 632 2200 Fax : 0750 667 7526