Atmospheric Storage Tanks_Nov 2011

  • Upload
    hanlove

  • View
    213

  • Download
    0

Embed Size (px)

Citation preview

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    1/24

    Energy Practice

    RISK EngInEERIng PoSItIon PaPER

    atmoSPhERIcStoRagE tanKS

    FEbRuaRy 2011

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    2/24

    2 Atmosphric Stora Tas

    contEntS

    Section Title.............................................................................................................................Page

    1. Bacrod ..................................................................................................................................... 3

    2. Objective ......................................................................................................................................... 3

    3. Scop............................................................................................................................................... 3

    4. Slctio of Atmosphric Stora Tas ........................................................................................... 4

    5. Laot ad Spaci.......................................................................................................................... 5

    5.1 Bds (Ds).................................................................................................................................. 6

    6. Primar Cotaimt....................................................................................................................... 7

    6.1 Ta Dsi & Opratio.................................................................................................................. 7

    7. Scodar Cotaimt ................................................................................................................ 10

    7.1 Bd Itrit (la tihtss) ....................................................................................................... 10

    7.2 Trtiar Cotaimt ..................................................................................................................... 11

    8. Orfill Protctio .......................................................................................................................... 12

    9. Maitac ad Ispctio .......................................................................................................... 13

    10. Laa ad Fir Dtctio ............................................................................................................ 14

    10.1 La Dtctio ............................................................................................................................... 14

    10.2 Fir Prtio ad Protctio ....................................................................................................... 14

    11. Fir Fihti Sstms ..................................................................................................................... 16

    11.1 Watr Sstms ............................................................................................................................... 16

    11.2 Foam Fir Fihti Sstms ........................................................................................................... 16

    11.3 Applicatio Rats ........................................................................................................................... 18

    12. Rfrcs to Idstr Losss ........................................................................................................ 19

    13. Rfrcs to Idstr Stadards................................................................................................... 19

    14. Appdics.................................................................................................................................... 20

    Appdix A - Assssmt Chclist ................................................................................................ 20

    Appdix B - Mchaical Compot Chclist for Floati Roof Ta Ispctios ........................ 21

    Appdix C - Loss Icidts............................................................................................................ 22

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    3/24

    Marsh 3

    1. BACkgROunDThr ha b mros icidts i th oil, as ad ptrochmical idstr ioli atmosphric

    stora tas. Data has b compild b a rptabl oprator i th uSA that idicat that

    orfilli of atmosphric stora tas occrs oc i r 3300 filli opratios. I 2009 thr

    wr two sparat icidts jst das apart, o i Jaipr, Idia (Octobr 29) ad o i Sa Ja,

    Prto Rico (Octobr 23) that dmostratd th dstrcti capabilitis of icidts at trmials ad

    ta farms.

    Th Bcfild icidt i th uk i Dcmbr 2005 rsltd i a idpdt istiatio

    commissiod b th Halth ad Saft Commissio i th uk. As a rslt of this, mor idac has

    b proidd to dsirs ad oprators of facilitis. Sch idac has b icldd withi this

    positio papr.

    2. OBJeCTIveTh objcti of this positio papr is to dfi th stadards that wold b xpctd of a r ood

    atmosphric stora facilit i th oil, as ad ptrochmical idstr. Ths stadards ar also

    rflctd i th Marsh er Ris Rai critria. Th ca b sd to dtrmi ris impromt

    opportitis ad also to proid dtaild adic to clits si to impro thir atmosphric

    stora facilitis.

    3. SCOPeTh scop of this positio papr iclds:

    gidac o th appropriat slctio of atmosphric ta dsi for class of prodct to b stord

    gidac o laot ad spaci

    gidac o appropriat mas of sri primar cotaimt

    Sitabl dsi of scodar cotaimt

    Dtctio arramts for loss of primar cotaimt ad firs

    Fir protctio arramts

    exampls of loss icidts ioli atmosphric stora tas

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    4/24

    4 Atmosphric Stora Tas

    4. SeLeCTIOn OF ATMOSPHeRICSTORAge TAnkSTh laot ad ral dsi of a stora facilit shold b basd po

    cosidratios of saft, opratioal fficic ad iromtal protctio. A

    primar cosidratio is sri that th dsi of th stora tas thmsls is

    sitabl for th classificatio of th hdrocarbo bi stord.

    Th tabl blow smmariss th dsi of ta sitabl for ach class of

    hdrocarbo:

    CRuDe OIL

    DeRIvATIve

    CLASS

    DeFInITIOn ReCOMMenDeD

    STORAge TAnk DeSIgn

    Floati

    Roof

    Fixd Roof

    Class 0 Lifid ptrolm ass (LPg)

    Class I Liids which ha flash poits blow

    21C

    Class II (1) Liids which ha flash poits from 21C

    p to ad icldi 55C, hadld blowflash poit

    Class II (2) Liids which ha flash poits from 21C

    p to ad icldi 55C, hadld at or

    abo flash poit

    Class III (1) Liids which ha flash poits abo

    55C p to ad icldi 100C, hadld

    blow flash poit

    Class III (2) Liid which ha flash poits abo 55C

    p to ad icldi 100C, hadld at or

    abo flash poit

    uclassifid Liids which ha flash poits abo

    100C

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    5/24

    Marsh 5

    5. LAyOuT AnD SPACIngIdall, ta laot shold b optimisd to sr that thr is sfficit accss to tas for

    fir fihti ad to miimis th ris of scalatio i th t of a ta fir.

    Miimm spaci for tas is spcifid i th tabl orlaf, althoh Marsh wold

    adocat a miimm sparatio distac of 1x th diamtr of th larst ta with a

    absolt miimm of 15 mtrs, as sch a distac proids sfficit accss for fir

    fihtrs.

    FACTOR MInIMuM SePeRATIOn FROM Any PART OFTHe TAnk

    Btw adjact fixd-roof tas eal to th smallr of th followi:

    (a) th diamtr of th smallr ta;

    (b) half th diamtr of th larr ta;

    (c) ot lss tha 10m (Marsh adocat 15m).

    Btw adjact floati-roof tas 10m for tas p to ad icldi 45m

    diamtr.

    15m for tas or 45m diamtr.

    (Th spaci is dtrmid b th siz of th

    larr ta).

    Btw a floati-roof ta ad a fixd-

    roof ta

    eal to th smallr of th followi:

    (a) th diamtr of th smallr ta;

    (b) half th diamtr of th larr ta;

    (c) ot lss tha 10m (Marsh adocat 15m).

    Btw a rop of small tas ad a

    ta otsid th rop

    15m

    Btw a ta ad th sit bodar,

    a dsiatd o-hazardos ara,

    procss ara or a fixd sorc of

    iitio

    15m

    Sorc: HSg 176. Th stora of flammabl liids i tas.

    O otabl xcptio is th sparatio btw crd tas, whr th dstrcti ffcts

    of a boil or ca xtd from 5 to 10 diamtrs. Thrfor cosidratio shold b i to

    locati crd tas at th d of ta farm istallatios ad with th larst practical

    sparatio from adjact tas.

    Ths distacs shold ol b sd i cojctio with appropriat lls of fir

    protctio (s blow). I th t that tas ar xisti ad do ot coform to th abo

    spaci, th additioal fir protctio shold b cosidrd.

    Floati roof tas, with xtral mtal domd roofs xtdi or th tir roof ara (i..

    itral floati roof tas or tas fittd with odsic doms), ma b cosidrd as fixd

    roof tas for th prpos of ta locatio ad spaci.

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    6/24

    6 Atmosphric Stora Tas

    5.1 BunDS DykeS

    Abo-rod tas shold b

    compltl srrodd b bd walls

    (s also Scodar Cotaimt).

    Ths shold b dsid to offr

    protctio to fir fihtrs. Thrfor

    th bd wall shold b locatd so

    that a rasoabl clos approach ca

    b mad to a ta fir.

    Fir fihti scrs ad stps shold

    b locatd at arios poits arod

    th bd wall to assist th positioi

    ad protctio of fir fihti

    prsol ad ipmt.

    Bds wold ormall b costrctd

    from arth or prfrabl cocrt ad

    shold b larl imprios to liid

    ad capabl of withstadi

    hdrostatic ad hdrodamic

    prssrs to which th cold b

    sbjctd. earth bds shold b

    fittd with a watr rsistat lir ad

    whilst rass rowth is accptabl, it

    shold b rlarl maitaid ad

    pt short.

    Tas shold idall b locatd alo

    withi thir ow bds, althoh

    whr tas shar a commo

    bd, itrmdiat walls p to half

    th hiht of th mai bd walls ado mor tha 0.5 mtrs hih shold

    b proidd to cotrol small spillas

    from o ta affcti aothr.

    Bd floors shold drai to a sil

    locatio complt with smp for th

    rlar rmoal of watr from raifall

    or firwatr tsti. Drais shold

    ormall b pt closd, with th

    drai isolatio al sitatd otsid

    th bd.

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    7/24

    Marsh 7

    6. PRIMARy COnTAInMenT

    6.1 TAnk DeSIgn AnDOPeRATIOn

    Tas shold b dsid to a

    rlat stadard, sch as API 650 or

    BS en 14015.

    I som istacs sil si bottomtas ar a bttr optio tha dobl-

    bottomd tas as ths proid th

    optimm coditios for sri

    itrit of th ta floor b th

    ispctio of ta floor plats.

    Disadatas of dobl-bottom

    dsis icld sttlmt, prodct

    trapmt ad modificatio to

    ozzl compsati plats.

    Whr dobl-bottomd tas ar

    proidd, additioal ispctio

    masrs shold b proidd i

    accordac with a rlat stadard

    sch as eeMuA 183 or BS en 14015.

    La dtctio shold also b

    proidd o dobl-bottomd tas.

    TAnk ROOFS

    Dobl dc roofs o floati rooftas ar prfrrd to sil dc

    roofs with xtral potoos as th

    ar mor stabl ad lss lil to los

    boac.

    For floati roof tas, th watr

    drais to rmo raiwatr from th

    roof shold b ormall closd. To

    sr roofs ar mptid of raiwatr,

    procdrs shold b i plac ad

    followd for th opi ad

    r-closr of als.

    Whr als ar lft ormall

    op, th th followi masrs

    shold b pt i plac:

    Hdrocarbo dtctio i draid

    watr with atomatic isolatio

    Tsti of oprabilit of isolatio

    als ad dtctio sstms (sorlaf)

    venTS

    Tas shold b proidd with a wa

    sam/fraibl roof costrctio, or

    with a mrc t sitabl sizd

    for th worst cas rlii scario,

    to prt orprssr dr all

    rlif coditios. emrc ts

    shold compl with rlatstadards, sch as API 2000.

    It is sstial that th ris of loss of

    cotaimt is proprl maad.

    This ca b achid b th propr

    dsi, opratio, maitac ad

    ispctio of tas. Idal practic is

    otlid blow.

    Th most ffcti wa to prt a

    major accidt at a sit is th

    cotid proisio of sitablprimar cotaimt of th

    flammabl matrials. This is achid

    throh th sitabl dsi,

    costrctio ad maitac of th

    stora sstms i accordac with

    stadards.

    For idac o th most appropriat

    stadards to s for th dsi ad

    costrctio of atmosphric stora

    tas, rfr to th uk HSes riw of

    stadards, Mchaical itrit

    maamt of bl stora tas

    which ca b fod at th followi

    wbsit addrss:

    http://www.hse.gov.uk/research/rrpdf/

    rr760.pdf

    Otlid blow is a smmar of thfatrs cosidrd to b th most

    appropriat for a modr facilit:

    Dobl sals o floati roof tas

    (nB foam dam hihts shold b

    abo th hiht of th ppr rim

    sal to proid sitabl protctio

    aaist a rim sal fir)

    Hih ll alarm ad idpdt

    bac-p hih ll istrmt (with

    xcti actio ol if

    appropriat)

    Cotios atomatic moitori

    of ta cotts, icldi rat of

    cha dri filli/mpti

    Ati-rotatio dics o floati

    roof tas

    Closd watr drais

    Sil si floors

    Ta floor la dtctio o dobl-

    floor tas. This is ormall

    comprisd of a istrmt to

    dtct loss of acm i th itr-

    floor spac

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    8/24

    8 Atmosphric Stora Tas

    Whrr a fixd roof ta is sd forth stora of matrials with a flash

    poit blow 21C (rall o da

    tas, ot rcommdd for lar

    bl stora tas), th flam

    arrstrs shold b proidd o th

    ts to prt iitio of th

    flammabl apors bri bac ito

    th ta. I warmr climats, whr

    prodct srfac tmpratrs cold

    xcd 21C, flam arrstrs shold

    b sd whrr maximm srfac

    tmpratrs cold b withi 10C of

    th flash poit.

    Flam arrstrs shold b icldd i

    prtati maitac rotis to

    sr th do ot bcom blocd

    b scal, pait, ic or othr matrials.

    Flam arrstrs ar ot

    rcommdd for s wh th

    matrial bi stord is liabl to

    polmris or fol th arrstr. D to

    th pottial for bloca,cosratio ts (acm ad

    prssr rlif) shold ot b fittd

    with flam arrstrs.

    Fixd roof tas ca b fittd with a

    as blat (ormall itro) to

    maitai a irt atmosphr i th

    apor spac. nitro sppl

    prssr shold b jst abo

    atmosphric, bt sfficit to

    displac a liid pmpd ot. As abac p, a acm brar shold b

    proidd i th t that itro

    sppl is lost.

    vts or apor rcor sstms

    (oft ti bac to th sorc

    ssl) ar rird. Ths shold b

    dsid to rli prssr slihtl

    abo that of th itro ad at a

    sitabl mari blow th dsi

    prssr of th stora ta.

    RIM SeALS & FOAM DAMSDobl rim sals (of fir-rsistat

    costrctio) ar prfrabl to sil

    sals. D to irrlaritis dri th

    costrctio phas of lar floati

    roof tas, it is lil that a sil sal

    will ot maitai a 100% sal

    btw th ta roof ad ta wall

    alo th tir hiht of th ta

    wall. Thrfor, a scod sal will

    impro th lilihood of achii a

    tiht sal, will rdc missios admiimis th ris of rim sal fir.

    Wh istalli dobl rim sals, th

    hiht of th scod, ppr rim sal

    shold b blow th hiht of th

    foam dam to sr cora

    whr rim sal porrs ar

    actiatd.

    Foam dams shold b proidd with

    itrmitttl-spacd aps to allowth draia of raiwatr. Howr, if

    th aps ar too lar or too

    mros, th ma affct th abilit

    to form a sil cotios foam

    barrir i th t of a fir.

    OveRFLOW

    Cosidratio shold b i to

    proidi sitabl orflow sstms

    to sr that i th t of a taorfilli, th ta cotts ar

    safl rotd ito sitabl scodar

    cotaimt. Additioall, th

    orflow rot shold b dsid to

    miimis trblt flow, rdc th

    srfac ara of flammabl

    hdrocarbo ad rdc th

    ratio of flammabl apors,

    sch as throh splashi. Particlar

    car ds to b ta with

    strthi ris ad firwatr

    disprsio rails arod tas which

    ar spcificall dsid to maximis

    sprad of flids or a tas srfac.

    For xisti tas, cosidratio

    shold b i to modificatios of

    ta top dsi ad to th saf-r-

    roti of orflowi liids.

    vALveS

    All importat als o atmosphric

    tas shold b lablld ad thir

    fctio idicatd.

    Fir-saf sht off als shold b

    proidd, prfrabl atomatic ad

    rmotl opratd sht off/isolatio

    als (ROSOv/ROIv). Th mst b

    fittd clos to th ta o both th

    ilt ad otlt coctios. vals

    mst ithr coform to a

    appropriat stadard, sch as BS en

    ISO 10497 or ialt itratioal

    dsi, or shold b of itrisicall

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    9/24

    Marsh 9

    fir-saf dsi. Sch fatrsicld:

    Mtal-to-mtal sats (scodar

    mtal sats o soft-satd als

    ar accptabl)

    Mst ot b of cast-iro

    costrctio

    Shold ot b wafr-boltd

    (somtims rfrrd to as lo bolt

    flas)

    I rios sbjct to a hih ris of

    artha ad/or rapid rod-

    acclratio, th isolatio als ad

    actators shold also b scrd

    dirctl to th ta wall ad ot to th

    rod. Achori th al to

    srrodi strctrs or th rod

    cold rslt i th al sparati

    from th ta dri xcssi

    ibratios.

    Fatrs of th ROIv shold b:

    Fail saf (or if ot fail saf ha a

    bac-p powr sppl, spciall if

    th mrc pla rirs th

    ta to b draw dow i a

    mrc)

    It shold ot b possibl to ato-

    rst th ROIv

    Adat mari of saft forshtti off th al, with at last

    150% tor aailabl from fll

    op to fll closd

    no maal opratio or orrid

    (.. had whls) which ma

    ihibit th opratio of th ROIv

    Sitabl itrit ad prformac

    to satisf th SIL (Saft Itrit

    Ll) rirmts

    Dsid to miimis prssrsrs o sstm pipwor ad

    coplis, particlarl ship to shor

    flxibl pips

    Ta draia als shold b

    blad off wh ot i s.

    Whr opratios to rmo

    accmlatios of watr from

    drath th prodct ar to b

    codctd, isolatio of th drai

    shold b achid b th s of two

    als i sris. Th scod al ca

    b a tmporar istallatio.

    PIPIng

    I aras whr artha is a

    siificat xposr, all associatd

    pipi o stora tas shold ha

    stp omtr to allow flxi i th

    pipi ad prt pctri of th

    ta dri a artha.

    Sitabl dsid sismic hars

    shold b proidd i artha

    zos, ad pip spports shold ha

    fir protctio withi fir hazard

    zos, .. withi th bdd ara.

    TeSTIng

    Bfor filli tas with flammabl

    liids, la tsti of th istalld

    ta ad associatd pipwor isrird. Hdralic tsti shold

    ol b sd (i.. ot pmatic) as

    stord r i hdrotsti is

    sbstatiall lowr, ad ihrtl

    safr. Howr, air ma b sd as a

    mas of appli prssr to watr-

    filld tas ad pipi.

    Salt watr shold ot b sd to

    hdralicall tst sstms cotaii

    stailss stl.

    HOuSekeePIngDbris withi bds shold b pt at

    a absolt miimm. I additio to

    th chcs withi formalisd

    ispctio ad maitac rotis,

    oprators shold also codct

    frt chcs of tas ad thir

    compots as part of thir rotis

    to sr that th tas ar pt i a

    rasoabl coditio. A sampl of

    itms to chc is icldd i

    Appdix B.

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    10/24

    10 Atmosphric Stora Tas

    7.1 BunD InTegRITyLeAk TIgHTneSS

    Bd wall ad floor costrctio

    shold b la tiht. This iclds th

    proisio of la tiht xpasio

    joits btw diffrt casts of

    cocrt i bd walls ad whrr

    thr ar ptratios i th wall for

    pips. Srfacs shold b maitaid

    crac fr, ad withot a

    discotiitis, ad withot a faild

    joits that ma allow liid miratio.

    As obsrd i major icidts, sch

    as th Bcfild fir of 2005, th

    joits i cocrt bd walls ar

    particlarl sscptibl to th ffcts

    of fir ad/or sbst cooli.

    Thrfor, to maitai itrit, joits

    shold b capabl of rsisti fir.

    Idall, stl plats (watrstops)

    shold b fittd across th ir

    srfac of bd joits ad fir

    salats shold b sd to rplac or

    amt o-fir rsistat matrials.

    Similarl, joits to wall ad floor

    ptratios d to b protctd

    aaist th ffcts of fir.

    Whr dsii protctio plat,

    cosidratio shold b i to

    aoidi wai th wall strctr

    i rlatio to rsistac to fir,

    hdrostatic ad hdrodamic forcs.

    Bd ptratios shold b aoidd

    lss altrati or-wall rotis

    ar ot practical. O xisti bds,

    fitti stl collars or bllows to

    impro fir rsistac at pipwor

    ptratios ma itrodc local

    corrosio iitiatio sits i th

    pipwor ad is ot rcommdd

    lss corrosio prtio ca b

    assrd. Whr corrosio ca ot b

    prtd, joits shold b improd

    b rplaci xisti salats with

    fir-rsistat salats.

    Bd floor ptratio joits ar

    ihrtl wa as failr of th

    itrit is difficlt to prdict ad

    dtct ad ma coti for som

    tim oticd. Costl, floor

    ptratios shold ot b

    icorporatd ito w bd dsis.

    existi bd floor ptratios

    shold b limiatd whrr

    practicabl. Whr flxibl salats

    ar sd i floor ptratio joits,

    ths shold b rplacd with fir-

    rsistat salats.

    Thr ha also b a mbr of

    siificat accidts rslti from

    las of hdrocarbos from tas

    throh th bas of stora tas.

    Thrfor th proisio of a sitabl

    imprios bas (idall cocrt

    with a mmbra lir) or floor la

    dtctio o dobl floor

    cofiratios shold b proidd.

    7. SeCOnDARy COnTAInMenTWhilst priorit shold b i to prti loss of primar cotaimt, adat scodar (ad somtims trtiar)

    cotaimt is cssar for th protctio of th iromt ad to cotai a spillas. I atmosphric ta

    applicatios, scodar cotaimt will b proidd b bd walls.

    Bd capacit shold b sfficit to cotai th larst prdictabl spilla. A bd capacit of 110% of th capacit of

    th larst stora ssl withi th bd will ormall b sfficit. Wh stimati bd capacit, th spac occpid

    b othr tas shold b ta ito accot.

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    11/24

    Marsh 11

    7.2 TeRTIARyCOnTAInMenT

    Trtiar cotaimt d ol b

    cocrd if thr is a siificat ris

    of scodar cotaimt bi

    isfficit to prt a scalatio

    to a major accidt affcti

    prsol, assts or th iromt.

    Firwatr cotaimt is o sch

    xampl. Implmtatio of trtiar

    cotaimt shold thrfor b a

    ris-basd dcisio. Howr, trtiar

    cotaimt shold b:

    Idpdt of scodar

    cotaimt

    Capabl of fll cotaii

    forsabl firwatr ad liid

    polltat olms o th failr of

    scodar cotaimt

    Imprmabl to watr ad

    forsabl traid polltats/

    hdrocarbos

    Of clllar cofiratio to allowsratio ad limit th xtt of

    sprad of polltats ad/or fir

    Robst dr mrc

    coditios, .. loss of lctrical

    sppl

    Capabl of allowi th cotrolld

    momt of cotaid liids

    dr ormal ad mrc

    coditios

    Capabl of aidi th sparatio of

    watr from polltats (.. oil/

    watr sparator)

    Abl to maa raiwatr ad

    srfac watrs

    Mor idac o trtiar

    cotaimt ca b fod i

    docmtatio icldi CIRIA 164

    ad PPg18.

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    12/24

    12 Atmosphric Stora Tas

    All tas shold b fittd with a sitabl hih itrit

    orfill protctio sstm, which shold b dsid to SIL

    1 as a miimm, dpdi po th riss associatd with

    failr.

    Orfill protctio sstms shold b atomatic ad

    phsicall ad lctroicall sparat from th ta

    ai sstm, i.. ha a idpdt ll ai

    sstm ad bac-p ll switch or dplicatd ll

    ai sstm.

    Howr, jstificatio for a sil combid ai ad

    orfill protctio dic cold b mad if th itrit of

    th istrmt is sfficit for th ris of failr.

    Ta ai sstms shold ha a LAH (Hih Ll

    Alarm) to alrt oprators to th stats of th ta which

    is sfficit tim to itrrpt th filli opratio ad

    th sbst actiatio of th bac-p orfill protctio

    dic LAHH (Hih-Hih Ll Alarm). This shold also

    ta ito accot a thrmal xpasio of th flid withi

    th ta. It is importat that LAH shold ot b sd to

    cotrol roti filli.

    Aalo ssors ar prfrrd to diital (switchd)

    ssors (i.. thr ar two aalo ssi lmts o

    th ta), as ths ar abl to alrt whr thr is a falt

    i th primar ll ssor bfor rachi hih ll.

    elctro-mchaical sro as shold b aoidd for

    s with flammabl matrials as ths ar itricat dics

    cosidrd to b lrabl to a mbr of pottial failr

    mods. Modr lctroic a ssors, sch as radar

    as, shold b sd istad.

    Whr practical th LAHH shold ha a xcti actio

    to itrrpt th filli opratio b closi th isolatio

    al ad/or stoppi th pmp. Fatrs of a LAHH ar:

    It shold b st at or blow th tas ratd capacit

    Actiatio of th LAHH is to iitiat a shtdow

    LAHH ma b limitd to a adibl/isal alarm to alrt

    a hma oprator to ra th rird actio. Actiosrird mst b spcifid ad wll docmtd. nB

    sch optios ar ot sitabl for SIL 1 sstms

    Th trip fctio shold icld a adibl/isal alarm

    to prompt a chc that th trip fctio has b

    sccssfl

    I som cass it ma b cssar to trmiat th trasfr

    i a mor radal fashio, sch as b limiti th closr

    rat of th isolatio al to aoid damai orprssrs

    i pstram pipwor. D allowac mst b i to th

    maximm filli rat btw LAHH bi actiatd ad

    th isolatio al fiall closi.

    Th sit rcii a batch or dlir mst ha ltimat

    cotrol ad rsposibilit for stoppi th trasfr ad

    shold ha local sstms ad als to stop th opratio.

    This shold ot thrfor b dr th sol cotrol of a

    atomatic sstm or oprators at a rmot locatio.

    Ta ll istrmtatio ad iformatio displa

    sstms shold b of sfficit accrac ad clarit to

    sr saf plai ad cotrol of prodct trasfr ito

    tas.

    It is prfrabl for tas to b cotiosl ad

    atomaticall moitord for rat of ll cha dri

    trasfr opratios to match th actal rat of trasfr with

    xpctd rats. This wold i a arl idicatio that th

    mai ll ai sstm was ot fctioi corrctl or

    that th icorrct ta was bi filld. Dri ormal

    stora opratios, sch a tool cold also otif oprators

    of a siificat loss of cotaimt.

    It is ot withi th scop of this docmt to dtail th SIL

    dtrmiatio or its implicatios. Howr th followipoits shold b otd:

    It is th Dtholdrs rsposibilit to mt latst

    itratioal stadards, IeC 61511 is a crrt ood

    stadard

    Th appropriat SIL rird shold b spcifid bfor

    dsii ad istalli orfill protctio sstms

    LOPA (Lar of Protctio Aalsis) is a sitabl

    mthodolo to dtrmi SIL

    As orfill protctio sstms ormall fctio

    ifrtl, th shold b priodicall tstd i thir

    tirt to sr th will oprat wh rird

    8. OveRFILL PROTeCTIOn

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    13/24

    Marsh 13

    All tas mst dro rlar

    xtral ad itral (ot-of-sric)

    ispctios to sr thir itrit

    ad as sch, a writt schm of

    xamiatio shold b proidd.

    Orall idac o th sitabl

    mthods ad frc of sch

    ispctios ar dtaild i eeMuA

    159 ad API 653.

    Idiidals rsposibl for th

    formlatio of schms of ispctio

    ad for th ispctio of tas shold

    b comptt ad ha th

    appropriat alificatio for ta

    ispctio ad for th rad of

    matrials sd i costrctio. As a

    miimm, prsol shold b

    comptt to TWIs (Th Wldi

    Istitts) Crtificatio Schm forWldi ad Ispctio, or

    ialt.

    extral ispctios shold b

    codctd o a hihr frc

    tha itral ispctios basd po

    RBI (Ris Basd Ispctio)

    rirmts, or as statd i th

    rlat cods. If acti dradatio

    mchaisms ar fod, th mor

    frt ispctios shold b

    codctd.

    Particlar atttio shold b i

    to islatd stora tas, as

    corrosio dr islatio, ad th

    alit of xtral coatis applid

    prior to islatio, ca ha a

    siificat ffct po ta itrit.

    Thoroh itral ispctio ca ol

    b achid b rmoi a ta from

    sric, clai it ad thcodcti, as a miimm:

    Fll floor sca

    Itral xamiatio of shll to

    alar floor wld

    nDe (no Dstrcti

    examiatio) of alar plat ad

    shll ozzls

    visal ispctio

    Dfrral of itral ispctios shold

    b ris assssd ad approd b a

    sitabl comptt prso. Particlar

    atttio shold b i to tas

    that ha had o prios itral

    ispctio, as th probabilit of floor

    failr will icras with r ar

    that th rcommdd itral is

    xcdd. I sch cass, it is lil

    that a dfrral cold b jstifid.

    Failr of ithr a top or bottom floor

    i dobl-bottomd tas (as

    dtctd throh th failr of

    acm btw plats) shold b

    rctifid withi o ar. Cotid

    opratio i th itrim priod

    pdi rpair shold b spportd

    b a tchical jstificatio spporti

    its fitss for prpos.

    Ta rpairs ad modificatios ar

    spcialist actiitis ad shold ol

    b codctd b sitabl alifid

    prsol with appropriat

    alificatio (as spcifid abo).

    Watr drais o floati roof tas

    shold also b formall icldd i

    roti maitac if ormall lft

    op, icldi a chc that isolatio

    als ca b closd. Th dtctio

    sstms for hdrocarbos shold also

    b tstd o a rlar basis. All tsts

    shold b formall docmtd.

    Potoos shold b icldd i

    formal maitac ad ispctio

    rims as loss of potoos (as a

    rslt of corrosio or lo-trm

    rmoal of potoo cap) will affct

    th stabilit ad boac of th

    dc. Th prsc of flammabl

    apors withi a potoo also

    icrass th ris of apor clod

    xplosio (vCe) withi a potoo.

    Th fctioal itrit of orfill

    protctio sstms is critical to

    sri primar cotaimt.

    Orfill protctio sstms ma b i

    a ormall dormat stat withot

    bi rird to oprat for ma

    ars. For this raso, priodic tsti

    is a sstial lmt i assri

    thir cotii itrit.

    9. MAInTenAnCe AnDInSPeCTIOn

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    14/24

    14 Atmosphric Stora Tas

    10. LeAkAge AnD FIRe DeTeCTIOnIt shold b otd that laa, orflow ad

    fir dtctio ar mitiatio lars ad ot

    prtati lars, ad ar thrfor of

    scodar priorit to orflow ad la

    protctio.

    10.1 LeAk DeTeCTIOn

    Whilst flammabl as dtctio i stora arasis cosidrd to b a ood masr (for hihl

    flammabl matrials), th disprsio of

    flammabl apors is complicatd to prdict, so

    ffcti as dtctio ma ot alwas b

    practical.

    Mor ffcti dtctio of las is lil to b

    proidd b liid hdrocarbo dtctors.

    Tpical locatios wold b i th bd drai,

    ttr or smp, whr hdrocarbos wold

    accmlat. Sch sstms ma b sbjct to

    failrs or sprios alarms (.. d to watr

    collcti i th bd), thrfor cosidratio

    shold b i to si mltipl dtctors at

    mor tha o locatio. Iitiatio of sch alarms

    shold also iitiat a itrrptio of a

    trasfr opratio. This is of particlar

    importac at trmials that ar ormall

    mad.

    Idall CCTv (Closd Circit Tlisio) shold

    b proidd, with sitabl rsoltio ad

    lihti i ta ad bd aras to i opratorsassistac i dtcti ta orflows.

    Oprators shold ot b xpctd to moitor

    ths costatl, thrfor CCTv shold b

    proidd with sstms that dtct ad rspod

    to chas i coditios ad th alrt

    oprators to thos chas.

    FIRe DeTeCTIOn

    For floati roof tas, rim sals shold b

    costatl moitord b th s of liar hatdtctio. Ths shold b locatd clos to th

    top of th sal, ad ot o th foam dam, whr

    th ar lss ffcti i dtcti firs.

    Poit hat dtctors ar rall of lss s for

    lar stora tas, othr tha i th iciit of

    ts, i th lar aras that d to b

    cord. Thrfor, optical flam dtctors,

    proidi a lar zo of dtctio, shold b

    sd for bdd aras.

    10.2 FIRe PRevenTIOn AnDPROTeCTIOn

    BOnDIng & eARTHIng

    B atr of th stora of flammabl liids,

    flammabl atmosphrs ar to b xpctd i

    th iciit of ts, rim sals ad withi th

    tas thmsls. To miimis th ris of

    iitio th ta ad acillar ipmt sholdb fll bodd ad arthd (rodd). A

    maximm rsistac of 10 ohms to arth is

    rcommdd.

    Spcial atttio shold b mad to th

    arthi coctio btw th ta wall ad

    th roof of a floati roof ta. Slidi shts

    (cotactors) btw th wall ad roof oft do

    ot maitai a ood cotact, ths orloadi

    thos shts which ar maitaii a

    coctio. Thrfor, a adat mbr of

    shts shold b proidd ad chcd to

    sr that cotacts ar maitaid.

    D to th risi ad falli of th floati roof,

    xcss lths of arthi cabl ar rird i

    th iciit of th walwa proidi accss to

    th floati roof. Th arthi cabl ca oft b

    srd wh it is trappd btw th whls

    of th accss walwa ad th rails po which

    it rolls, as i xampl show orlaf.

    Rtractabl rodi sstms o modr

    tas wold addrss this.

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    15/24

    Marsh 15

    O of th most commo sorcs of iitio for

    lar tas is lihti. Thrfor, th proisioof sitabl lihti protctio with bodi

    ad arthi wold hlp to miimis this. nFPA

    780 Stadard for th Istallatio of Lihti

    Protctio Sstms proids mor dtails o th

    spcificatio of lihti protctio sstms.

    Som istallatios ar proidd with lihti

    masts itdd to act as prfrtial rots for

    lihti to dischar itslf, as opposd to ia

    th stora ta. This cocpt is ot pro ad

    som partis sst that sch masts act to

    attract lihti to th iciit of th stora

    tas. Thrfor, ths ar ot crrtl

    cosidrd to b a robst mitiatio aaist th

    ffcts of lihti.

    Som matrials ar sscptibl to th ffcts of

    static dri splash-filli. Thrfor, masrs

    shold b ta i sch istacs to prt th

    ratio of lctrostatic chars.

    It is possibl that floati roofs ca bcom

    stabl ad si, mab as a rslt of raiwatraccmlatio, or failr of flotatio dics.

    Oft, foam is applid to proid a blat to

    spprss apor missios ad prt iitio.Howr, if this occrs o tas stori

    matrials, sch as aphtha, that ar sscptibl

    to iitio from splash-filli, carfl

    cosidratio shold b i prior to th

    applicatio of foam. If foam is to b applid, for

    xampl i th t that lctrical storms ar

    xpctd, th this shold b tl applid

    alo th shll wall ad ot b splash-filli to

    th srfac of th matrial.

    ZOnIng

    A dtaild assssmt of th hazardos ara

    classificatio (HAC) of th stora ta, acillar

    ipmt ad bdd ara mst b

    codctd. This shold ta ito accot th

    class of matrial bi stord.

    Th spcificatio of spar-idci ipmt

    shold b sitabl for th HAC zos locatio

    ad shold b mad i accordac with rlat

    lctrical stadards, sch as IP (Istitt of

    Ptrolm) Modl Cod of Saf Practic Part 15,

    ATeX 95, ATeX 137 or BS 5345.

    Damad earthi Cabl

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    16/24

    16 Atmosphric Stora Tas

    Protctio sstms ad fixd fir

    fihti istallatios shold b

    proidd ad compris fixd/smi-

    fixd foam sstms ad cooli watr

    spras. Additioall, accss to th

    tas for mobil fir fihti

    appliacs, ipmt ad matrials

    shold b proidd ii mltipl

    poits of attac with o dad-ds.

    I ma cass it is safr ad mor

    practical to allow a ta fir to br

    itslf ot; for istac, wh thr is

    o chac of scalatio to othr

    tas, littl iromtal xposr

    or whr th riss of fihti th ta

    fir ar ratr tha ot fihti it.

    Two otabl xcptios ar:

    Rim sal firs ths will ta a

    lo tim to br ot

    Crd ta firs ths ar

    sscptibl to boilors d to th

    prsc of watr

    Broad pricipls of watr ad foam

    applicatio ar i blow. Mor

    dtails ar i i th er

    Istitts Modl Cod of Saf

    Practic Part 19: Fir prcatios at

    ptrolm rfiris ad bl stora

    istallatios. Altratil, nFPA 11

    Stadard for Low-, Mdim-, ad

    Hih-expasio Foam ca b sd as

    a rfrc.

    As for procss plat, ddicatd fir-

    prplas shold also b compild for

    stora istallatios. Ths shold

    spcif tp of attac, firwatr ad

    foam applicatio rats, locatio of

    hdrats, smi-fixd istallatios ad

    mobil apparats, firwatr

    cotaimt ad worst casscarios. It is ot withi th rmit of

    this positio papr to dtail

    mrc plas, bt API 2021,

    Maamt of Atmosphric Stora

    Ta Firs, proids som idac i

    this mattr.

    emrc rspos prsol

    shold rci traii o th fir

    prplas, ad rlar xrciss

    shold b codctd to assss thsitabilit of th prpla.

    11.1 WATeR SySTeMS

    Proisio shold b mad for th

    applicatio of cooli watr to fixd

    roof tas cotaii prodcts

    adjact to thos cotaii Class I or

    II (ptrolm) or whrr thr is

    lss tha 1 x diamtr of th larst

    ta btw adjact tas. Iparticlar, thr shold b cooli

    whrr thr is lss tha 15 mtrs

    accss btw tas.

    Whr watr is to b applid to tas,

    watr applicatio rats shold b:

    2 lpm/m for xposd tas

    10 lpm/m for lfd tas (to

    rtical ad iclid srfacs)

    Source: IP 19. Model Code of Safe Practice

    Part 19

    Watr applicatio shold b proidd

    b ithr fixd or smi-fixd sstms.

    It is lil that mobil tdrs

    wold ha sfficit capacit for

    watr stora to mot a prolod

    cooli watr attac o a stora

    ta.

    Watr shold ot b applid to th

    roof ara of floati roof tas as this

    ma rslt i th dstabilisatio ad

    sii of th roof.

    11.2 FOAM FIReFIgHTIng SySTeMS

    Whilst bi a ood cooli mdim

    for tas, watr is ot a sitabl fir

    xtiishi mdim for

    hdrocarbo firs. Thrfor, foam is

    sd for sch applicatios. Th

    dsi of foam fir-fihti sstms,

    b th fixd or mobil, shold b

    sitabl for th tps of firs th

    wold b rird to xtiish (or

    sitabl for th cooli of adjact

    ipmt/tas). Thrfor ach

    facilit ds to ha its ow tailord

    fir fihti sstm. Importat isss

    to cosidr wh dsii ad

    istalli a fir fihti sstmicld:

    Foam ad th foam ijctio/

    proportioi sstms mst b

    compatibl (also importat if th

    spplir of foam is chad)

    Hdralic dsi of foam sstms

    mst b spcifid

    Foam slctio mst b

    appropriat for th tp of fir lil.. AFFF, (Aos Film Formi

    Foam), shold ot b slctd for

    polar solts

    Corrct proportioi of foam that

    ma othrwis rslt i foam that

    dos ot flow (too littl watr) or

    that icl os bac to soltio

    (too mch watr)

    Proisio of facilitis to aid th

    maitac or tsti of

    firfihti sstms

    11. FIRe FIgHTIng SySTeMS

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    17/24

    Marsh 17

    Locatio of ipmt, ..moitors ot too far from tas for

    foam applicatio to ta srfac

    Atttio to a falts i th

    fabricatio ad istallatio of

    hardwar, .. chc als

    istalld th wro wa rod,

    trasport paci still prst

    arod air idctors

    Oc a sstm has b dsid

    ad istalld, it is critical that it iststd. Whilst this ma b xpsi,

    it is critical to sr that th sstm

    actall complts th job it is

    itdd to do. Idall, sstms

    shold b tstd at th mafactrrs

    as it is th chapr, icr ad

    asir to rctif a mistas.

    FLOATIng ROOF TAnk FIReS

    Rim sal firs ar th most commotp of fir o floati roof tas.

    Thr is littl chac of ths

    scalati to othr tas or tri to

    fll srfac ta firs if th dsi,

    maitac ad laot of th tas

    is sitabl. This shold ot b

    cosidrd a rl, howr, as a

    poorl maitaid ta cold los its

    itrit or b lrabl to

    sbst xplosios, prhaps as a

    rslt of apor irss ito o of

    th potoos.

    Rim sal protctio shold ol b

    sd o crtai tps of roofs (i..

    dobl dc, stl potoo, tc). Pa

    roofs for xampl, shold ha fll

    srfac protctio.

    Th applicatio of foam from a rmot

    moitor (i.. o otsid th bd)

    wold ot rprst bst practic as

    it ca crat roof istabilit adpottiall scalat th icidt.

    Additioall, rmot moitors arwastfl of foam ad caot dirct

    th jt so accratl as th objcti

    is to appl foam to th rim sal as

    icl ad tl as possibl

    (irrspcti of th roof ll) ad to

    rtai a complt foam sal for as

    lo as possibl.

    Th most commo ad (arabl)

    most ffcti mthod to cotrol a

    rim sal fir is th applicatio of foam

    ia fixd rim sal porrs o th top of

    th shll wall. e with simpl, fixd

    prpos-bilt sstms, sch as rim

    sal porrs, thr is th dar that

    basic rrors ca b mad so that th

    sstm dos ot oprat as itdd.

    Sch xampls that shold b

    aoidd ar:

    Top of foam dam blow th top of

    th rim sal this is spciall a

    iss whr scodar rim salsha b addd to th ta to

    rdc ta missios. Th top of

    th foam dam shold b at last 50

    mm abo th top of th rim sal,

    bt idall abot 150 mm.

    Too ma or too lar aps at th

    bottom of th foam dam. Th

    prpos of th dam is to hold th

    foam i positio arod th

    circmfrc of th ta to rdc

    th amot of foam dd. This

    srs fficit applicatio to th

    rim sal ad prts cssar

    loads bi placd o th ta roof.

    With lar aps at th bottom of

    th dam, a siificat atit of

    foam cold la to th roof.

    Howr, small, itrmitttl

    spacd drais shold b proidd

    to allow raiwatr to drai awa.

    Icorrct spaci of th foam

    porrs. Modr foams ca flow i

    xcss of 30 mtrs if proportiod

    corrctl, althoh if thr archas to th foam tp, foam

    proportio or watr sppl,

    th th flow charactristics cold

    b affctd so that a foam sal is

    ot possibl.

    Forcd/irrlar additio of foam.

    Th ittio is to appl foam

    tl dow th sid of th ta

    shll so that it forms a

    blat withi th rim sal ara. If

    th porr has b icorrctlpositiod it ma ot appl th

    foam i sch a wa, .. catchi

    o th top d of th sal,

    rslti i splashi ad loss of

    foam to th roof.

    Foam porrs locatd too hih o

    th ta, xposi thm to wid

    ad impairi thir passa to th

    rim sal itslf.

    To orcom ths isss, tstsshold b codctd o th sstm

    to sr it oprats corrctl.

    Dpdi po th mbr of tas

    bi protctd, aal tsti

    frc wold b appropriat.

    Ispctios shold b codctd

    rlarl to sr air ilts to foam

    rators ar clar ad that foam

    porrs ar ot blocd b, for

    xampl, birds sts. Othr oodfatrs to aid ispctio or fir

    fihti i th t of a sstm

    failr ar:

    Walwa arod th top of th

    floati roof ta this ca b th

    wid irdr with a hadrail arod

    th circmfrc. This allows for

    th porrs to b accssd for

    maitac or for fir fihtrs to

    accss th roof with maal hoss.

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    18/24

    18 Atmosphric Stora Tas

    Proid a foam hdrat at th topof th ta (prfrabl at th top of

    th stairs) for fir fihtrs i th

    t of rim sal porrs bcomi

    blocd. This also rirs lss

    ipmt to b carrid p th

    ta i th t of a rim sal fir.

    Carfl cosidratio ds to b

    i as to th saft of prsol

    wh attmpti sch a tactic.

    It is importat that foam ca b

    applid all wll wh thfloati roof is at hih ll ad

    wh it is at low ll.

    Othr foam dlir sstms that ar

    mor complx to ari drs ar:

    Catar sstms foam applid to

    th rim sal b local rators

    locatd dirctl withi th foam dam

    throh a sppl li attachd to th

    roof ia th rolli laddr

    Coflxip sstm foam soltio is

    applid i th sam wa as a catar,

    althoh th sppl pip rs p

    from low ll throh th ta itslfia a coflxip flxibl pip.

    O shot sstms a xtiishi

    at (sch as obsolt Halo) is

    applid at th rim sal i a sil

    brst xtiishi th flams. Whilst

    pottiall ffcti as a iitial

    xtiishr, ths do ot prt

    r-iitio ad rir all th parts,

    icldi clidrs, bi placd o

    th roof. For that raso, Marsh dos

    ot rcommd sch a approach.

    FIXeD ROOF TAnkS

    Similar sstms ca b applid to

    fixd roof tas, with foam

    applicatio to th srfac of th

    prodct throh a fixd or smi-fixd

    sstm, or sb-srfac allowi

    for th foam to float to th srfac of

    th prodct. nFPA 11 Stadard for

    Low-, Mdim-, ad Hih-expasio

    Foam proids a id as to which

    prodcts ad matrials ca b

    protctd b sch sstms.

    exampl of sb-srfac foam applicatio

    apparats

    11.3 APPLICATIOnRATeS

    A miimm of 40 mits attac

    shold b isad i ordr to ha

    a rasoabl chac of sccss i

    xtiishi a fir, ad foam stocs

    shold b sfficit for this dratio;

    a dratio of 60 mits is prfrrd

    for crd oil ta firs.

    Tpical applicatio rats for foam

    soltio ar show blow, althoh

    foam mafactrrs adic o th

    tp of foam ad applicatio shold

    alwas b soht:

    TyPe RATe

    (l/mi/m2)

    APPLIeD WITH MOBILe

    equIPMenT

    Pool firs 5-10*

    Fixd roof tas, Class I

    prodct

    5-10*

    Fixd roof tas, Class II/III

    prodct

    5

    APPLIeD WITH FIXeD OR

    SeMIFIXeD equIPMenT

    Fixd roof ta with porr

    otlt

    4

    Bas ijctio (oils ol) 4

    Floati roof rim sal firs 12

    Floati roof tas (roof ara),

    projctd foam

    6.5

    Floati roof tas (roof ara),

    fixd porrs

    4

    Source: Energy Institutes Model Code

    of Safe Practice Part 19: Fire

    precautions at petroleum refineries and

    bulk storage installations

    *Th hihr rat ma b applid to Class I

    prodcts, icldi asoli cotaii p to

    10% of oxats.

    nFPA 11, Stadard for Low-,

    Mdim-, ad Hih-expasio Foam

    also proids similar applicatio

    rats, althoh thr ar som mior

    diffrcs.

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    19/24

    Marsh 19

    12. ReFeRenCeS TO InDuSTRy LOSSeSexampls of Idstr losss ha b icldd i Appdix C.

    13. ReFeRenCeS TO InDuSTRy STAnDARDSModl Cod of Saf Practic Part 19:

    Fir prcatios at ptrolm

    rfiris ad bl stora

    istallatios. er Istitt,Fbrar 2007. ISBn 978-0-85293-

    437-1.

    BS en 14015. Spcificatio for th

    dsi ad mafactr of sit bilt,

    rtical, clidrical, flat-bottomd,

    abo rod, wldd, stl tas for

    th stora of liids at ambit

    tmpratr ad abo. Fbrar

    2005.

    BS en 61511-1:2004/IeC 61511-

    1:2003 Fctioal saft. Saft

    istrmtd sstms for th procss

    idstr sctor.

    BS en ISO 10497:2004. Tsti of

    als. Fir tp-tsti

    rirmts. British Stadard/

    eropa Stadard/Itratioal

    Oraisatio for Stadardisatio.

    HSg 176. Th stora of flammabl

    liids i tas. HSe. ISBn 0 7176

    1470 0.

    CIRIA Rport 164: Dsi of

    Cotaimt Sstms for th

    Prtio of Watr Polltio from

    Idstrial Accidts. Jaar 1997.

    Costrctio Idstr Rsarch ad

    Iformatio Associatio. ISBn

    086017476X.

    PPg 18. Plai Polic gidac 18:

    eforci Plai Cotrol.

    Dcmbr 1991. ISBn

    9780117525542.

    HSg 244. Rmotl Opratd Shtoff

    vals (ROSOvs) for emrc

    Isolatio of Hazardos Sbstacs -

    gidac o good Practic. Octobr

    2004. ISBn 0717628035.

    API 650. Adddm 3 - Wldd Stl

    Tas for Oil Stora. Octobr 2003.

    Amrica Ptrolm Istitt.

    API 653. Ta Ispctio, Rpair,

    Altratio, ad Rcostrctio, Third

    editio. Dcmbr 2001. Amrica

    Ptrolm Istitt.

    API 2000. vti Atmosphric ad

    Low-prssr Stora Tas, Sixth

    editio. nombr 2009. Amrica

    Ptrolm Istitt.

    API RP 2350. Orfill Protctio forStora Tas i Ptrolm Facilitis,

    Third editio. Jaar 2005.

    nFPA 11 Stadard for Low-, Mdim-,

    ad Hih-expasio Foam, 2010

    editio.

    Bcfild. Th Fial Rport of th

    Fial Istiatio Board. Dcmbr

    2008. Bcfild Major Icidt

    Istiatio Board. http://www.bcfildistiatio.o./

    rports/idx.htm#fial

    Saft ad iromtal stadards

    for fl stora sits. Dcmbr 2009.

    Procss Saft Ladrship grop.

    http://www.hs.o./comah/

    bcfild/fl-stora-sits.pdf

    eeMuA PuB n 159 - usrs id to

    th ispctio, maitac ad

    rpair of abo rod rtical

    clidrical stl stora tas.

    Jaar 2003. eiri

    eipmt ad Matrials usrs

    Associatio.

    eeMuA PuB n 183 - gid for th

    Prtio of Bottom Laa from

    vrtical, Clidrical, Stl Stora

    Tas. Jaar 2004. eiri

    eipmt ad Matrials usrs

    Associatio.

    RR760 - Mchaical itrit

    maamt of bl stora tas.

    HSe.

    http://www.hs.o./rsarch/

    rrpdf/rr760.pdf

    not: RR760 proids a smmar of

    rlat cods ad stadards for th

    assrac of mchaical itrit i

    stora tas. Ths proid a

    assssmt of th most appropriat

    stadards for diffrt lmts of

    maitac ad dsi of facilitis.

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    20/24

    20 Atmosphric Stora Tas

    APPenDIX A ASSeSSMenT CHeCkLIST

    Th followi chclist is basd o a r ood ratd atmosphric stora ta facilit ad ca b

    sd to assss th alit of that facilit ad idtif a aps or aras for impromt.

    eLeMenT/FeATuRe CRITeRIA

    Cotaimt All tas sparatl bdd ad sizd for 110% of capacit. B d walls sizd ad

    dsid to cotai ad prt bd ortoppi (ma icld trtiar cotaimt).

    Laot/Spaci Mts ris-basd ta spaci alatio ad r is alatio aailabl.

    no-crd itr ta spaci al to or ratr tha o diamtr of larst ta ad at

    last 15 mtrs. Crd oil tas sparatd b fi ta diamtrs to prt ris from

    boilor.

    Is trmtatio HLA, HHLA (totall idpdt iclds tappis , trasmittrs, tc.) lid to atomatic

    shtdow of fd. Tmpratr idicator. LLA, LLLA (idpdt) lid to atomatic

    shtdow of pmp ot ad complt with o-li diaostic capabilit (i.. ot simpl

    switch). Shtdow sstm ad compots SIL ratd i accordac with applicatio ad

    locatio. All idicators to cotrol room. Cotios mass balac sstm for ta farm.

    Oli bldi.

    Costrctio Dobl wldd sals o floati roof. Wathr shild. Cocrt bas with imprios

    mmbra ad sids slopd awa from bas wld. Ati rotatio dic o floatrs.

    earthi, lihti codctors. good accss to potoos, ad hadrails o accss wal

    wa arod priphr. Ato bottom watr drai. Ta floor la dtctio with doblfloor.

    Roof draia: raiwatr rcptors ad spill or coctios to prodct (limits watr

    ll to 10).

    Slctio As appropriat to class of prodct.

    Draia of Bds gradi to pmp pit smp. Imprmabl bd matrial.

    eipmt ad Pipwor Brid commo ilt/otlt pipwor ad o ipmt withi bd ara.

    Bd Costrctio ad Coditio no ptratios or aps i th walls. A aps i bd walls shold b sald

    appropriatl with a firproof matrial. Cocrt facd arth wall. Cosidratio i to

    prti bd ortoppi.

    gas Dtctio Bds fittd with flammabl as dtctors for low flash poit matrials capabl of

    sstaii a vCe. Dtctors itrlocd with ta filli sstm to itrrpt trasfr.

    Fir Dtctio Liar Hat Dtctio or fsibl-li/ tb (for r im sals ol). Sstms ar slf

    moitori with stats idicatio to HMI (Hma/Machi Itrfac).

    Fixd Fir Protctio

    - Floati Roof

    Mlti-had foam porrs with foam dam for all tas. Shll cooli watr spra, or s of

    mltipl moitors with proof of rspos capabilit. Sppl from two sparat locatios.

    Foam for bdd ara. Fixd sstm spplis foam.

    Fixd radiat protctio o xposd walls.

    Fixd Fir Protctio

    - Co Roof

    Sbsrfac foam ijctio (for o-polar compods, othrwis foam chambrs). Roof

    ad shll cooli. Foam for bdd ara - dal sppl. Fixd sstms.

    Fixd Fir Protctio

    - Co roof with itral floatr

    Foam porrs. Roof ad shll cooli; bd protctio with foam - dal sppl. Fixd

    sstm.

    14. APPenDICeS

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    21/24

    Marsh 21

    APPenDIX B MeCHAnICALCOMPOnenT CHeCkLIST FORFLOATIng ROOF TAnkInSPeCTIOnS

    Claliss

    Dbris o roof?

    Podi or raiwatr o roof?

    Laa

    Sis of oil or hols o roof?

    Roof Drais

    Cloi of roof drai scr msh?

    Pv vt Msh

    Cloi of Pv t msh?

    emrc Roof Drai

    Cloi of mrc drai msh?

    Wathr Shilds/Sals

    Dama or corrosio? excssi aps btw sal ad shll?

    Potoo Compartmts

    Prsc of watr or oil?

    Cors tiht?

    earthi Cabl

    Dama o cabl or coctios?

    gid Pols

    Dama o id pol rollrs?

    Rolli Laddr

    Dama o whl?

    Roof Drai vals

    eas of momt?

    Bottom of Shll

    Watr pooli?

    Corrosio?

    vtatio?

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    22/24

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    23/24

    Marsh 23

    Icidts with similaritis with th Bcfild icidt of 2005 ar smmarisd blow.

    LOCATIOn DATe AnD TIMe COMMenTS BACkgROunD COMMenTS eXPLOSIOn

    Hosto, Txas,

    uSA

    April 1962 Sr la from asoli ta. Almost widlss

    coditios. Iitio ar adjact hihwa.

    Dscribd as a blast, bt o dtails ar aailabl.

    Batow, Txas,

    uSA

    27 Jaar 1977 Orfilli of a ship with asoli. Fw dtails ar aailabl, bt it is lil that thr

    wold ha b costio.

    Txaco, nwar,nw Jrs, uSA

    7 Jaar 1983Aftr 00.00 hrs

    Orfilli of a ta cotaii ladd asoli.114-379 m3 (80-265 tos) of asoli rlasd.

    Sliht wid, iitio sorc 300m awa.

    Rlatil costd ara. Hih orprssrrportd bt ot atifid. Thr mior xplosios

    prcdd th mai blast.

    napls Harbor,

    Ital

    21 Dcmbr

    1985

    Orfilli of a ta cotaii ladd asoli.

    700 tos scapd. Low wid spd (2 m/s).

    Rlatil costd ara. Th ta ortoppd 1.5

    hors bfor iitio. varios orprssrs

    stimatd from dama aalsis bt th ar

    miimm als (.. 48 Pa).

    St Hrblai,

    Frac

    7 Octobr 1991

    04:00 hors

    La of asoli from a trasfr li ito a bd.

    Wid

  • 7/29/2019 Atmospheric Storage Tanks_Nov 2011

    24/24

    Marsh is o of th Marsh & McLa Compais, tothr with g Carptr, Mrcr, ad

    Olir Wma.

    Th iformatio cotaid hri is basd o sorcs w bli rliabl ad shold b

    drstood to b ral ris maamt ad israc iformatio ol. Th iformatio isot itdd to b ta as adic with rspct to a idiidal sitatio ad caot b rlid

    po as sch.

    I th uitd kidom, Marsh Ltd. is athorisd ad rlatd b th Fiacial Srics Athorit

    Marshs Ris eiri Srics

    tam has b stablishd for or

    25 ars ad is il alifid

    to proid ris maars ad

    drwritrs with th sstial

    iformatio th d to

    dtrmi th riht limit ad

    scop of cor ad th riht pric.

    each mmbr of th tam is a

    alifid ir, with practical

    xpric i dsi,

    costrctio, opratio ad

    maitac across a broad ra

    of oil, as ad ptrochmical riss.

    Th ha all b traid i

    adacd israc sills, i th

    abilit to assss ad aals risad to commicat ffctil

    ad frtl i mor tha o

    laa.

    Th oal is to bild brids

    btw ris iri,

    israc ad ris maamt

    ad btw th clit ad th

    drwritr. At th sam tim, th

    comparati sills of th tam

    prmit a bchmari sstm

    which is a lobal opiio of th

    ris, assssd aaist pr plats

    world-wid.

    From th arlist plai sta to

    th last opratioal phas, th

    iri srics tam is abl

    to cotribt practical ad

    cost-ffcti adic adassistac.

    I additio to tailord

    proramms, th tam has a sris

    of cor pacas, cori

    rthi from maai a major

    mrc to ris rdctio

    dsi fatrs ad saf wori

    practics.

    Th eiri Srics tam ismatchd amo israc

    brors ad ris adisrs bcas

    of th scal of istmt, th

    bradth of xprtis ad th

    xpric it icorporats.

    Mor importatl, th tam ss

    its practical owld ad

    practical sills to commicat a

    ral drstadi of phsical

    riss, thir israc implicatiosad th commrcial oprati

    iromt.

    THe engIneeRIng SeRvICeS TeAM For frthr iformatio, plascotact or local Marsh offic

    or isit or wb sit at: marsh.com

    BeIJIngTl: +86 10 6533 4070Fax: +86 10 8529 8761

    CALgARyTl: +1 403 290 7900

    Fax: +1 403 261 9882

    CAPe TOWnTl: +27 21 403 1940Fax: +27 21 419 3867

    DuBAITl: +971 4 223 7700Fax: +971 4 227 2020

    HOuSTOnTl: +1 713 276 8000Fax: +1 713 276 8888

    LOnDOnTl: +44 (0)20 7357 1000Fax: +44 (0)20 7929 2705

    MADRIDTl: +34 914 569 400Fax: +34 913 025 500

    MOSCOWTl: +7 495 787 7070Fax: +7 495 787 7071

    MuMBAITl: +91 226 651 2900Fax: +91 225 651 2901

    neW yORk

    Tl: +1 212 345 6000Fax: +1 212 345 4853

    OSLOTl: +47 22 01 10 00 Fax: +47 22 01 10 90

    PeRTHTl: +61 8 9289 3888Fax: +61 8 9289 3880

    SAn FRAnCISCOTl: +1 415 743 8000Fax: +1 415 743 8080

    SIngAPOReTl: +65 6327 3150Fax: +65 6327 8845