Page 1 of 1 2010 ASHRAE. All rights reserved.
ERRATA SHEET FOR FIRST PRINTING OF ANSI/ASHRAE STANDARD 62.1-2010
Ventilation for Acceptable Indoor Air Quality
July 7, 2010
The corrections listed in this errata sheet apply to the first printing of ANSI/ASHRAE Standard 62.1-2010. The first printing is identified on the outside back cover as “Product Code: 86152 5/10”. The shaded item has been added since the previously published errata sheet dated June 17, 2010 was distributed.
NOTICE: ASHRAE now has a list server for Standing Standards Project Committee 62.1 (SSPC 62.1). Interested parties can now subscribe and unsubscribe to the list server and be automatically notified via e-mail when activities and information related to the Standard is available. To sign up for the list server please visit Project Committee List Servers on the Standards and Guidelines section of the ASHRAE website at http://www.ashrae.org/publications/detail/15620.
Page Erratum
9 Section 5.16.3.2.5. Change Section 5.16.3.2.5 as follows:
(Note: Additions are shown in underline and deletions are shown in strikethrough.) 5.16.3.2.5 Class 2 air shall not be recirculated or transferred to Class 1 spaces.
12 Table 6-1 Minimum Ventilation Rates in Breathing Zone. Correct the following
Default Values in Table 6-1: (Note: Additions are shown in underline and deletions are shown in strikethrough.)
Occupancy Category
People Outdoor Air Rate
Rp
Area Outdoor Air Rate
Ra Notes
Default Values
Air Class
Occupant Density
(see Note 4)
Combined Outdoor Air Rate (see Note 5)
cfm/person L/s•person cfm/ft2 L/s•m2 #/1000 ft2
or #/100 m2 cfm/person L/s·person
General
Break rooms 5 2.5 0.06 0.3 25 710 3.55.1 1
Coffee stations 5 2.5 0.06 0.3 20 811 45.5 1