Upload
doanhanh
View
227
Download
5
Embed Size (px)
Citation preview
© 2017 Eaton Corporation. All rights reserved.
Arc Flash: What's New in Codes,Standards and Solutions
Electrical Systems: Design - Install - Maintain
David B. DurocherGlobal Industry Manager
Mining & MetalsEaton Corporation
Wilsonville OR [email protected]
November 2017
2 2
Arc Flash & PPE
Protection From Shock & Flash Hazards
An Arc Flash - An electrical arc due to either aphase to ground or phase to phase fault. Causedby many factors - dropped tools, improper workprocedures, etc.
80 percent of all electrical injuries are burnsthat result from the electric arc flash
Arc flashes cause electrical equipment toexplode, resulting in an arc-plasma fireball
Solid copper vaporizes, expands to 67,000times its original volume
Temperatures exceed 19,000 degrees C Detected sound levels of 141.5 decibels Pressure levels of 10,540 Kg per square
meter
3 3
NFPA70E-2018 Standard for Electrical Safety in theWorkplace: (US) and CSA Z462-2018 (Canada)
Quantifies Heat Energy from arc flash in calories/cm2
Recommends fire rated clothing: Personal ProtectiveEquipment (PPE) used during energized work
Recommends study update every 3 years
Standards Addressing Arc Flash HazardsElectrical Workplace Safety
Arc Flash Calculations IEEE 1584-2002 “Guide for Performing Arc
Flash Calculations” It presents formulas for numerically
quantifying heat energy from arc-flash
Includes an Excel Spreadsheet “Arc-FlashHazard Calculator” that performs calculationsusing heat energy formulas
4 4
NFPA70E-2018 Standard for Electrical Safety in theWorkplace: (US) and CSA Z462-2018 (Canada)
Quantifies Heat Energy from arc flash in calories/cm2
Recommends fire rated clothing: Personal ProtectiveEquipment (PPE) used during energized work
Recommends study update every 3 years
Standards Addressing Arc Flash HazardsElectrical Workplace Safety
Arc Flash Calculations IEEE 1584-2002 “Guide for Performing Arc
Flash Calculations” It presents formulas for numerically
quantifying heat energy from arc-flash
Includes an Excel Spreadsheet “Arc-FlashHazard Calculator” that performs calculationsusing heat energy formulas
5 5
Cost of Arc Burn Injuries
~2000 injuries/year in U.S.
An injured worker can spend one day in the hospital foreach single percent of body burned
$10,000 to $15,000,000 USD cost per injury
High personal cost
Other injuries besides thermal burns
6 6
Electrical Injuries Cost More than Other Injuries
Although injuries are infrequent, the very high costsassociated with these injuries make them one of the mostimportant categories of injuries
In one utility, electrical injuries represented <2% of allaccidents, but 28% - 52% of injury costs
7 7
Injury Costs can Last a Lifetime
A study of one utility revealed these costs of asurvivable serious electrical injury
Immediate direct costs…… $250,000 USD Direct costs after year 1….. $1.3 million Indirect costs ……………… $11.24 million
Total ….. $12.8 million*
*1991 dollars. Equivalent in 2003 dollars is $17.4 million
8 8
What’s New in IEEE1584?IEEE 1584-2002 Guide for Performing Arc Flash Calculations
July 2017 Draft Ballot
The draft ballot was successful, over 1000 commentswere received.
A Ballot Resolution Committee was formed to addressALL comments.
After resolutions, the final draft will be recirculated to ALLballoters where each can reaffirm or change their vote.
The draft ballot was approved by 84% of the ballotters
New version of IEEE1584 should be published in 2018.
9 9
What’s New in IEEE1584?IEEE 1584-2002 Guide for Performing Arc Flash Calculations
Planned Changes and Potential Consequences
2002 testing was based on about 100 tests, since thenover 100o tests
Electrode orientation details will be included Six vertical electrode equations One horizontal electrode equation (higher) Some current thinking “we are not seeing burn
injuries sing the 2002 calculations, so is a horizontalcalculation necessary/applicable?”
125kVA and 240V minimum Deleted reference from NFPA70E several cycles
ago The likelihood of an arc event at 208V is very low
10 10
Overarching Trends
Advancing Hazard & Risk concepts Hazard = Does a hazard exist? Yes/No Risk = Likelihood and Severity
Estimate the likelihood of occurrence Estimate the potential severity
Risk Controls Hierarchy = 1) Elimination; 2) Substitution; 3) Engineering controls;
4) Awareness; 5) Administrative controls; 6) PPE
What’s New in NFPA70E-2018?NFPA70E-2018 Standard for Electrical Safety in the Workplace
Definitions
Replace the term “accident” with “incident” “accidental” is replaced with “unintentional” “accidentally” is replaced with “unintentionally”
Replace “short circuit current” with "available fault current” Definition: Fault Current, Available. The largest amount of current
capable of being delivered at a point on the system during a short-circuit condition
11 11
What’s New in NFPA70E-2018?NFPA70E-2018 Standard for Electrical Safety in the Workplace
Definitions
Conditions of Maintenance Definition: the state of the equipment considering the manufacturer’s
instructions, recommendations , and applicable codes, standards andrecommended practices
Exceptions
Two new exceptions have been added to Equipment labelingrequirements
First exception allows retaining labels if they were installed prior tothe effective date of this standard if the labels meet the requirementscontained in the applicable 70E when labels were applied.
Second exception allows supervised Industrial installations, todocument the information required in the labels to be readily availableto persons likely to perform servicing, maintenance and operation.
12 12
What’s New in NFPA70E-2018?NFPA70E-2018 Standard for Electrical Safety in the Workplace
PPE
Requirement that all suppliers or manufacturers of PPE shalldemonstrate conformity with the appropriate product standardswith the following information on the PPE or within manufacturer’sinstructions
Name of the manufacturer Product performance standards Arc Rating where appropriate One of more identifiers such as model, serial number Care instructions
13 13
What’s New in NFPA70E-2018?NFPA70E-2018 Standard for Electrical Safety in the Workplace
Electrical Safety Program Equipment Verification
Electrical Safety Program includes requirement for verificationof integrity of newly installed or modified electrical equipmentto comply with applicable installation codes and standards priorto being placed in service.
MSHA/OSHA hold the user responsible OSHA 1910.399 “only approved equipment will be installed. User
responsible to certify based on testing by manufacturer.”
Example: MV Switchgear Vacuum Replacement Circuit Breakers:ANSI/IEEE Standard C37.09.05 Requirements for Conversion of Power Switchgear
14 14
What’s New in NFPA70E-2018?NFPA70E-2018 Standard for Electrical Safety in the Workplace
Permanently Mounted Voltage Detection
Test & Verify Exception No. 1 : An adequately rated permanentlymounted test device shall be permitted to be used to verify theabsence of voltage of the conductors or circuit parts at the worklocation, provided it meets all following requirements:
It is permanently mounted and installed in accordance with themanufacturer’s instructions and tests the conductors and circuit partsat the point of work
It is listed and labeled for the purpose of verifying the absence ofvoltage
It tests each phase conductor or circuit part both phase-to-phase andphase-to-ground
The test device is verified as operating satisfactorily on any knownvoltage source before and after verifying the absence of voltage.
15 15
What’s New in NFPA70E-2018?NFPA70E-2018 Standard for Electrical Safety in the Workplace
Human Error
Requirement that risk assessment procedure shall address thepotential for human error and its negative consequences onpeople, processes, the work environment and equipment.
Users may need to have a detailed process for performingenergized work and some method of quantifying human error.
16 16
What’s New in the 2017 NEC?NFPA70 National Electrical Code
NEC Article 240.87
Two sections of Article 240.87 address required minimum Arc EnergyReduction for low-voltage fuses and circuit breakers rated 1200A, and higher.
Hierarchy = 1) Elimination; 2) Substitution; 3) Engineering controls; 4)Awareness; 5) Administrative controls; 6) PPE
17 17
Electrical Workplace Safety Standards Summary
The intent of NFPA 70E/CSA Z462 regarding arc flash isto provide guidelines which will limit injury to the onset ofsecond degree burns (1.2 cal/cm2).
Note: The heat reaching the skin of the worker isdependent primarily upon:
Power of the arc at the arc location Distance of the worker to the arc Time duration of the arc exposure
18 18
Device Name Bus kVBus
BoltedFault kA
DeviceBolted
Fault kA
ArcingFault kA
Trip Time(s.)
Bkr.Opening
(s.)
AFBoundary
WorkingDistance
(in.)
IncidentEnergy
(cal/cm2)
HRC
50/51/N FDR-5B 2.40 13.39 13.39 12.94 1.917 0.083 988 36 30.0 #450/51/N FDR-4B 0.48 31.63 25.37 14.06 1.917 0.083 268 18 100.5 DANGERB2_802_102B 0.48 29.9 28.58 15.97 0.19 0 65 18 9.9 #3MaxTripTime @2.0s 12.47 15.65 10.8 10.47 2 0 967 36 29.4 #4EPP_1 0.208 3.74 3.74 2.18 1.934 0 75 18 12.4 #3T_M1-205 FUSE 0.48 22.68 18.84 10.35 2 0 281 24 44.8 DANGER50/51/N FDR-6B 0.48 27.5 26.79 15.16 1.917 0.083 187 18 55.9 DANGER50/51/N FDR-6B 0.48 27.5 26.79 15.16 1.917 0.083 187 18 55.9 DANGERM3_003_2A 0.48 30.47 30.47 16.98 0.32 0 97 18 18.8 #350/51/N FDR-5B 2.40 16.42 13.65 13.13 1.917 0.083 971 36 29.5 #450/51/N FDR-5B 2.40 9.96 8.13 7.89 1.917 0.083 600 36 18.5 #3M3_002_2A 0.48 20.21 19.3 11.42 0.32 0 72 18 11.7 #3M3_001_2D 0.48 27.98 23.9 13.49 0.19 0 62 18 9.2 #3M3_004_2A 0.48 25.88 22.85 12.27 0.32 0 89 24 8.2 #3T_J7_001_FUSE 0.48 17.61 17.18 10.38 2 0 212 18 68.5 DANGERT_M2_001_FUSE 4.16 12.7 11.54 11.15 0.775 0 352 36 11.0 #3T_M2_001_FUSE 4.16 12.7 11.54 11.15 0.775 0 352 36 11.0 #3T_M1-101 FUSE 4.16 11.38 11.38 11.02 1.55 0 637 36 19.6 #3T-M1-102 FUSE 4.16 11.38 11.38 11.02 1.551 0 637 36 19.6 #3T_M1-201 FUSE 0.48 44.25 35.98 17.67 0.429 0 149 24 17.7 #3T_M1-201 FUSE 0.48 44.25 35.98 15.02 1.239 0 267 24 41.5 DANGERT-M1-202 FUSE 0.48 45.79 36.23 16.18 0.723 0 157 18 41.9 DANGERT_M1-204 FUSE 0.48 46.44 35.85 15.98 0.779 0 164 18 44.8 DANGERM3_003_1B 0.48 47.76 34.53 16.75 0.5 0 164 24 20.2 #3T_M1_203_FUSE 0.48 47.76 34.53 14.23 1.976 0 358 24 64.0 DANGERM3_004_2B 0.48 18.21 18.21 10.94 0.32 0 69 18 10.8 #3T_M1_206_FUSE 0.48 23.68 18.75 10.84 2 0 224 18 74.7 DANGER50/51/N FDR-5B 0.48 28.69 26.01 14.63 1.917 0.083 267 18 100.0 DANGERMaxTripTime @2.0s 12.47 15.63 10.79 10.46 2 0 966 36 29.4 #4MaxTripTime @2.0s 12.47 15.63 10.79 10.46 2 0 966 36 29.3 #4MaxTripTime @2.0s 4.16 6.35 3.79 3.74 2 0 416 36 12.9 #3B2_802_102B 0.48 28.39 27.13 15.28 0.19 0 64 18 9.5 #3
Arc Flash Results – Areas for Concern
Typical Result From an NFPA70E Arc FlashHazard Assessment
19 19
Methods/Technologies to Reduce Arc-FlashEnergy, Protecting Personnel and Equipment
Label Equipment & Train Personnel Minimize Risk with Good Safety
Practices Reduce Available Fault Current Faster Clearing Times Move People Further Away Redirect Blast Energy Arc-Flash Preventing Technologies Design the Hazard Out (Safety by
Design)
8 cal/cm2 PPE
40 cal/cm2 PPE
20 20
Bad – Exposed Back of Neck Good – All of Body Protected
Label Equipment & Train PersonnelMinimize Risk with Good Safety Practices
21 21
Faster Clearing TimesZone Selective Interlocking
SD=0.5S
SD=0.3S
SD=0.3S
SD=0.3S
M1
F1 F2 F3X35kA fault current
Without ZSI = 0.5 S:
43.7 Cal/cm2
Greater than Cat. 4 PPE
DANGER!
With ZSI = 0.08 S:7.0 Cal/cm2
FR Shirt & PantsCat. 2 PPE
22 22
LV Power Circuit Breakers – Two Settings Groups Trip Unit Mounted Features
Blue LED “Maintenance Mode” 2 Position Selector Switch:
O/R = OFF/Remote I = LocalON
5 Position Protection Level SelectorSwitch: From L1 (Min) to L5 (Max)Instantaneous
Remote Indication Capabilities Remote Enable Capabilities ARMsTM Selector switch Mounted on
Switchgear Communications
Infra-Red via PDA Various Networks
Faster Clearing TimesARMSTM (Arc Flash Reduction Maintenance System)
23 23
HRC = 1 (< 4 cal/cm2)AF Current = 5.6kAAF Current = 5.6kA
HRC = 3 (11 cal/cm2)
ARMSTM (Arc Flash Reduction Maintenance System)
Faster Clearing TimesARMSTM (Arc Flash Reduction Maintenance System)
24 24
Faster Clearing TimesRetrofit ARMs for LVPCBs
Door MountedComponents
Breaker MountedComponents
Arcflash Reduction Maintenance System
DIGITRIP
Harness
LockoutSwitch
Battery
25 25
2000kVA Unit Substation
NEC Article 240.21(C)2 Allows unprotectedsecondary conductorTransformer Secondary Conductors Not over 3 m(10 ft) Long
Design Limitations• Secondary bus
fault protection• Secondary bus
overload protection
2000kVA5.75%Z
3200A
Faster Clearing TimesARMSTM (Arc Flash Reduction Maintenance System)
EDR4000
To Primary Bkr
26 26
Fault at 480V Switchgear Bus• 31.8kA Symmetrical Fault current• 1167” AF Boundary• 702.4 cal/cm @ 18”• UNAPPROACHABLE:
NFPA70E-2009: Category 4 ishighest category @ 40 cal/cm
Safety: Unit Substation DesignTypical LV Substation with Fused Load-Break Switch
Arc Flash Study Results
Faster Clearing TimesVCP-T Substation Vacuum Retrofill
3200A
125E
13.8kV
480Y/277V
2000kVA5.75%Z
1200A
1200A
1200A
1200A
27 27
15kV VacuumBreaker
Before AfterArc Flash Study ResultsSym. Fault at 480V Switchgear Bus 31.8kA 31.8kAAF Boundary 1167” 18”Cal/cm2 702.4 1.4NFPA70E HRC UNAPPROACHABLE 1
Improved Unit Substation DesignLV Substation with Retrofit Vacuum Primary Breaker
86
ST
Integral50/51 Relay
50/51Relay
Faster Clearing TimesVCP-T Substation Vacuum Retrofill
28 28
Optional Accessory - Electrical Levering Device
ExternalRemoteRacking
Move Personnel Further Away5 to 38kV Switchgear Remote & Integral Racking
Integral RemoteRacking
UniversalRemoteRacking
29 29
MR2 Motorized Racking Device– Integral to switchgear
Remote HMI for indication,Monitoring and Control
RemoteMarshallingPanel
Move Personnel Further AwayRemote Racking HMI or Marshalling Panel
30 30
Redirects Arc Energy and Particulates
Redirect Blast EnergyArc-Resistant Switchgear (ANSI C37.20.7)
Arc Flaps
2000A or 3000A breakerwith Vent1200A can be 1
high or 2 high
ControlSection
VT drawer
15 kV Arc Switchgear
Arc Rated ANSI/NEMA Assemblies
31 31
Traditional Infrared ThermographSurvey using IR Windows orViewports
Specific Visual Inspections
Scheduled regularly for longerintervals between ShutdownMaintenance
Arc-Flash Preventing TechnologiesIR Windows or Viewports
32 32
Safety: Non PPE Unit Substation DesignTypical LV Substation with Replacement VCP-TVacuum Breaker in MSB Assembly
Design the Hazard Out (Safety by Design)VCP-T Substation Vacuum Breaker
33 33
Design the Hazard Out (Safety by Design)VCP-T Substation Vacuum Breaker
LV Switchgear
Substation One-LineAlternate Primary Protection
ZSI
ZSIZSIZSIZSI
5051505150
515051
LVPCBL,S,I800AF800AT
LVPCBL,S,I800AF800AT
(3) 100:5 CT
(3) 3200:5 CT
(3) 3150:1 CURRENT SENSORS
OCRELAY
LVPCBL,S,I800AF800AT
LVPCBL,S,I800AF800AT
LVPCBL,S,I800AF800AT
LVPCBL,S,I800AF800AT
LVPCBL,S,I800AF800AT
LVPCBL,S,I800AF800AT
MVVCBL,S,I600AF3150AT
34 34
Design the Hazard Out (Safety by Design)FlashGard LV Motor Control Centers
ANSI/NEMA FlashGardTM
The industry’s first (and only) LV MCC witha rackable bucket!
35 35
The FlashGardTM Bucket
Bucket Position
Connected
Test
Withdrawn
Handle Mechanism
Device Island
• Start, Stop, Auto, Man
Unit Latch
Breaker
Internal Shutter Position
Open
Closed
Racking Tool Receiver
Starter
Design the Hazard Out (Safety by Design)FlashGard LV Motor Control Centers
36 36
FlashGard - Remote Racking Option DC Motor Wireless Option Attaches Easily Minimal Torque Required 25 Foot Pendant Station Interfaces With Eaton RPR-2
Design the Hazard Out (Safety by Design)FlashGard LV Motor Control Centers
37 37
Case Study Chemical Processing Plant - Overview
“Implementation of an Arc Flash Reduction Maintenance Switch – A Case Study”Thomas Domitrovich, Ken White, IEEE IAS ESW-2012-08
Energized Task: Removing cables from de-energized Cubicle 4 using a rope. “Tool”changed from a rope to a come-along
US Chemical Plant – Review of an Arc Flash incidentoccurring during energized work
Come Along
38 38
Arc Flash ReductionMaintenance System
Maintenance Switch Case Study: Chemical Plant
40 ms
1000kVA transformer upstream 20,918 amps of available fault
current Energy:
17.7 Cal/cm2 : No arc reducingtechnology
2.9 Cal/cm2 : With arc reducingtechnology
PPE utilized - 8 cal/cm2 (the sitestandard PPE clothing)
Come Along
39 39
Light Sensing Relay Marketing ClaimsManufacturer 1 Manufacturer 2
Manufacturer 3
A Look at Light Detection: LV Systems
40 40
Arc Flash Incident Energy isdictated by total clearing time 1,000kVA, 480V, 5.75%Z
Transformer, IFL = 1,204A,ISC = 20,918A, IARC = 11,134A
Software Instantaneous Trip:17.7 Cal/cm2 @ 18”
Light & Current Relay Trip:15.2 Cal/cm2 @18”
Air Circuit Breaker with ArcReduction Maintenance System Trip:2.57 Cal/cm2 @ 18”
Light Detection offers only a marginal benefit versus instantaneoustrip and does not match ARMS total clearing time!
A Look at Light Detection: LV Systems
Light Detected,fires Shut Trip
BreakerContacts
Part
FaultClears
FaultClears
FaultClears
BreakerContacts
Part
Breakercontacts
part
ETUpowers
up
TA fired
4ms
4ms
25ms 16ms 13ms
2ms 35ms 13ms
16ms 13ms
Analogpowers up
SoftwareInstantaneousTrip~58ms
Light SensorTripping aCircuitBreaker~50ms
ARMS Trip~33ms
Tripping DelayTime
Opening Time ArcingTime
Opening Time ArcingTime
DelayTime
Opening TimeArcingTime
DelayTime
Using Chemical Plant Case Study as an example
41 41
Light Detection Systems – Other Considerations
Questions to Ask What is the total clearing time
improvement with lightdetection?
What clearing time valuesshould be included in the arc-flash study?
Our company PSE’s model arc flash exposure with light detectionrelays with zero total clearing time improvement versus instantaneous
Manufacturer’s Position Cannot be responsible for
enhanced level of protection Cannot be responsible for
possible nuisance operation Glass fiber breaking/ shipping
splits UL has no test standard
(UL508)
42 42
Reduces incident energy far belowmethods that rely on a breaker to
clear the fault (e.g. ARMS, ZSI, busdifferential, arc detection relays)
Reduces incident energy far belowmethods that rely on a breaker to
clear the fault (e.g. ARMS, ZSI, busdifferential, arc detection relays)
Arc Quenching System extinguishesan arc flash in less than 4 ms
Arc Quenching System extinguishesan arc flash in less than 4 ms
Dramatically ReducedDowntime
Switchgear can be quicklyreturned to service after anarc flash event for minimal
downtime
Dramatically ReducedDowntime
Switchgear can be quicklyreturned to service after anarc flash event for minimal
downtime
Superior Personnel ProtectionMeets IEEE C37.20.7, Type
2B test guide for internalarcing faults
Superior Personnel ProtectionMeets IEEE C37.20.7, Type
2B test guide for internalarcing faults
Enhanced EquipmentProtection
Protects valuable switchgearassets from arc flash damage
Enhanced EquipmentProtection
Protects valuable switchgearassets from arc flash damage
No plenums, ducts, specialconstruction or venting into the
room
No plenums, ducts, specialconstruction or venting into the
room
“Always-on” system that requires nooperator activation
“Always-on” system that requires nooperator activation
Higher impedance than bolted faultsystems to reduce stress on
upstream equipment
Higher impedance than bolted faultsystems to reduce stress on
upstream equipment
Design the Hazard Out (Safety by Design)Arc Quenching Low Voltage Switchgear
43 43
Arc Quenching System Sequence of Operation1. Arc flash detected by light sensors and
CTs2. Eaton Arc Flash Relay verifies light is from
an arc event and not from normal ACBoperation
3. Arc Flash Relay sends two signals:1) Trigger Arc Quenching Device2) Trip Main Breaker
4. Arc Quenching Device quenches thearc and contains the arc energy
5. Main LV breaker (or upstream MV breaker)opens, de-energizing the lineup
<4ms
Up to50ms
44 44
Arc Quenching Device Specifications 85 kA @ 635 V 30 cycle withstand rating Modbus communications Withdrawable Same size as MDS breaker Through-the-door design Remote racking capability Field-testable Field-replaceable System self-supervision Customer interface on front of device System includes Eaton Arc Flash
Relay (EAFR) and light sensors
45 45
Returning Gear to Service After an Event1. Arc detection relay indicates zone where event
occurred; interlocks main breaker to preventreclosing into the fault
2. Personnel locate and remove the cause of theevent
3. Evaluate and clean the equipment4. Replace Arc Quenching Device – cannot be
serviced or repaireda. Equipment can be reenergized without the Arc Quenching Device
b. Without the Arc Quenching Device, the arc flash protection will be limited tothe Arc Flash Relay and Main Breaker operation
5. Personnel return equipment to normal operatingconditions and reenergize
Equipment downtime is greatly reduced by the ArcQuenching Device as no structures, breakers or bus
will need to be replaced
Relay
MainBreaker
ArcQuenching
Device
46 46
Metal Enclosed Switchgear AlternativesStandard
SwitchgearArc ResistantSwitchgear
Arc QuenchingSwitchgear
Protection IndustryStandard
People(passive)
People,Equipment,
Uptime(active)
Test Guides,Standards C37.20.1 C37.20.1
C37.20.7
C37.20.1C37.20.7UL 2748
The Arc Quenching System can be shipped in any type of new Magnum DS gearincluding standard NEMA 1, NEMA 3R and Arc Resistant construction to create
Arc Quenching Switchgear.
Available Now!Retrofit and MCC Arc Quenching solutions are under development!
© 2017 Eaton Corporation. All rights reserved.
Electrical Systems: Design - Install - Maintain
David B. DurocherGlobal Industry Director
Mining & MetalsEaton Corporation
Wilsonville OR [email protected]
November 2017
Arc Flash: What's New in Codes,Standards and Solutions