7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 1/38
Baseline Market Study on Air
Conditioner Use in Government
Buildings
Final Reportrepared by
October 2011
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 2/38
Baseline Market Study on Air Conditioner Use in Government Buildings
i
Table of Contents1.0 Introduction ........................... .......................... .......................... ......................... ......................... 1
2.0 Respondents .......................... .......................... .......................... ......................... ......................... 1
3.0 Number of Air Conditioners ......................... .......................... ......................... ......................... .... 3
2.1 Window Type Air Conditioners .......................... ......................... .......................... .................... 4
2.2 Split Type Air Conditioners ........................... .......................... ......................... ......................... 4
2.3 Centralized Air Conditioners ......................... .......................... ......................... ......................... 5
4.0 Air Conditioner Capacities ....................... .......................... ......................... ........................... ....... 6
5.0 Age of Air Conditioners ........................... .......................... ......................... ........................... ....... 8
6.0 Sizing of Air Conditioners ........................ .......................... ......................... ........................... ....... 9
7.0 Energy Efficiency Ratio ........................ .......................... ......................... .......................... .......... 12
8.0 Number of Hours in Operation ......................... .......................... ......................... ....................... 15
9.0 Potential Savings from Switching to Air Conditioners with Higher EERs ........................ .............. 16
10.0 Summary of Results ........................ ......................... ........................... ......................... .............. 20
Annexes ................................................................................................................................................ 21
List of Tables
Table 1: List of Respondents .................................................................................................................... 1
Table 2: Top 10 Respondents with the greatest quantity of operational air conditioners ...................... ... 3
Table 3: Top 10 Respondents with the highest number of operational window type air conditioners....... 4
Table 4: Top 10 Respondents with the most number of operational split type air conditioners ................ 5
Table 5: List of Respondents with operational centralized air conditioners ............ ........................... ....... 5
Table 6: Top 10 Respondents with the most number of air cons operating for 10 years or more .............. 9
Table 7: Number of Air Conditioners per range of kJ/sq m ..................................................................... 10
Table 8: Respondents with the most number of undersized air conditioners (<500 kJ/sqm) ................... 10
Table 9: Respondents with the most number of properly sized conditioners (500-550 kJ/sq m) ............. 11Table 10: Respondents with the most number of air conditioners with 551 - 1000 kJ/sq m cooling
capacities .............................................................................................................................................. 11
Table 11: Respondents with the most number of air conditioners with >1000 kJ/sqm cooling capacities12
Table 12: Number of air cons per range of energy efficiency ratio of window type units ........................ 13
Table 13: Number of air cons per range of energy efficiency ratio of split type units ......................... ..... 13
Table 14: Number of air cons per range of energy efficiency rations of split and package type units* .... 14
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 3/38
Baseline Market Study on Air Conditioner Use in Government Buildings
ii
Table 15: Switching Cases and Scenarios................................................................................................ 16
Table 16: Switching Cases and Scenarios for Window Type Air Cons ...................................................... 17
Table 17: Switching Cases and Scenarios for Split Type Air Cons ............................................................ 18
Table 18: Average monthly energy savings per air con ........................................................................... 19
List of Figures
Figure 1: Breakdown of Air Conditioners Types ........................................................................................ 3
Figure 2: Number of units of window type air cons per cooling capacity .................................. ................ 6
Figure 3: Number of units of split type air cons per cooling capacity ........................................................ 7
Figure 4: Number of centralized type units per capacity range ........................ ......................... ................ 7
Figure 5: Operating Ages of Air Conditioners ........................................................................................... 8
Figure 6: Types of Air Conditioners operating for 10 years or more ......................... .......................... ....... 8
Figure 7: Age & EERs for Window Type and Split Type Air Cons ........................... .......................... ......... 14
Figure 8: Energy Savings and Payback Period ......................................................................................... 18
Figure 9: Energy Cost and Savings per Air Conditioner ........................................................................... 19
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 4/38
Baseline Market Study on Air Conditioner Use in Government Buildings
iii
ABSTRACT
The objective of this survey was to gather baseline information in preparation for a technical and
financial feasibility study for promoting efficient air conditioners or replacing inefficient air conditioning
units with more efficient ones among government buildings. Air con inventory and utilization
questionnaires were sent to 120 government agencies and government-owned corporations, of which
54 responded. The survey counted a total of 4,473 air con units installed within the buildings of the 54
respondents. The units were practically evenly divided between window type and split type units.
Centralized air cons comprised only 1% of the total air conditioners. Majority of window type units had
cooling capacities of 18,900-19,000 kJ/h, while units with 60,000 kJ/h cooling capacities are the most
predominant among split type units. Of the total, some 2,040 units included information on their
operating age. More than one-third (39%) of these had been operating for at least 10 years. A close look
at the correlation between age and energy efficiency ratios (EER) suggested that units that are more
than 10 years old do not necessarily have low EER values. In fact, some air cons that are more than 10
years old have very high EERs. Majority (79%) of air cons that reported their EERs were above the new
minimum energy performance standards, or equivalent to 1-star rating, by the Philippine National
Standards. In fact, most had 4-star rating. Replacing all air cons that do not comply with the MEPs with
air cons that have higher EER values have a potential total monthly electricity savings of Php 693,000
(USD16,500) to PhP 981,000 (USD23,360), with paybacks ranging from a high of 30 months to a low of
eight months. In fact, replacing with higher EER air cons significantly reduces the payback period.
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 5/38
Baseline Market Study on Air Conditioner Use in Government Buildings
1
1.0 Introduction
This survey was conducted to gather baseline information on air conditioning utilization among
government buildings in Metro Manila in preparation for an investigation on the technical and
financial feasibility of switching to more efficient air conditioning units or air cons. Air cons inventoryand use questionnaires, which benefitted from the comments and inputs of the United Nations
Environment Programme (UNEP), were sent by the Department of Energy (DOE) to 120 government
agencies. 54 agencies had responded to the survey, and their responses formed the basis of the
present study. The study is of course limited by the quantity and quality of information provided by
the respondents. Many respondents did provide a good quantity of quality data. Nevertheless, data
collected for selected agencies were validated through the ensuing field visits and inspection. The
DOE and International Copper Association South East Asia (ICASEA), with assistance from
CleanEnergy Solutions International (CSI), visited and validated the responses of the Philippine
Health Insurance Corporation, Local Water Utilities Administration, Securities and Exchange
Commission, National Housing Authority, and Department of Public Works and Highways. Indeed,
the visits provided more and better insights on air conditioning utilization among government
buildings. This report was prepared by CSI on behalf of DOE and ICASEA.
2.0 Respondents
The air cons inventory questionnaires were sent to 120 government agencies. 54 responded and are
listed and classified in Table 1. Majority of the respondents (19) are government agencies or
bureaus either directly supervised by the Office of the President or by different government
departments. On the other hand, 16 are Government Owned and Controlled Corporations (GOCCs),
one of which is a development bank. Nine are government executive departments that provided air
con data on their main offices, along with two field or satellite offices. Five are research entities, of
which three are under the Department of Science and Technology, one supervised by the
Department of Agriculture, and one under the Department of Finance. Four of the respondents are
regulatory bodies (Toll Regulatory Board, Games and Amusements Board, Insurance Commission,
and Dangerous Drugs Board). The government-owned television network, People’s Television
Network, also participated in this study.
Table 1: List and Classifications of Respondents
Government Agencies/Bureaus
1. Bureau of Corrections 11. National Youth Commission
2. Bureau of Fire Protection – National
Headquarters
12. Parole and Probation Administration
3. Commission on Population 13. Philippine Coconut Authority
4. Fertilizer and Pesticide Authority 14. Philippine Commission on Good Governance
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 6/38
Baseline Market Study on Air Conditioner Use in Government Buildings
2
5. Fiber Industry Development Authority 15. Philippine Economic Zone Authority
6. Maritime Industry Authority 16. Philippine Information Agency
7. Metropolitan Manila Development Authority 17. Philippine Overseas Employment Administration
8. Mines and Geosciences Bureau 18. Public Attorney's Office
9. National Printing Office 19. Securities and Exchange Commission
10. National Telecommunications Commission
Government Owned and Controlled Corporations
1. Center for International Trade Expositions and
Missions
9. National Kidney and Transplant Institute
2. Cultural Center of the Philippines 10. National Tobacco Administration
3. Land Bank of the Philippines 11. Philippine Health Insurance Corporation
4. Local Water Utilities Administration 12. Philippine Institute For Development Studies
5. National Development Company 13. Philippine National Oil Company
6. National Electrification Administration 14. Philippine Ports Authority
7. National Food Authority 15. Power Sector Assets and Liabilities Management
8. National Housing Authority 16. Small Business Guarantee and Finance
Corporation
Government Executive Departments
1. Department of Energy 6. Department of Social Welfare and Development
2. Department of Environment and Natural
Resources
7. Department of Transportation and
Communication
3. Department of Labor and Employment 8. Department of Social Welfare and Development -
Field Office
4. Department of Public Works and Highways 9. Philippine Army - Field Office
5. Department of Science and Technology - CentralOffice
Research Institutions
1. Advanced Science and Technology Institute 4. National Tax Research Center
2. Bureau of Agricultural Research 5. Science and Technology Information Institute
3. Department of Science and Technology -
Industrial Technology Development Institute
Regulatory Bodies
1. Dangerous Drugs Board 3. Insurance Commission
2. Games and Amusement Board 4. Toll Regulatory Board
Government Television Network
1. People's Television Network
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 7/38
Baseline Market Study on Air Conditioner Use in Government Buildings
3
Window
50%Split
49%
Centralized
1%
3.0 Number of Air Conditioners
A total of 4,473 air conditioners have been reported by the respondents. These consist of window
type units, split type units and centralized air conditioners. Figure 1 shows the breakdown of air con
types. The tally for split type air cons includes both floor standing and wall mounted split units. Thereported air cons are almost equally divided into window and split type units, with centralized units
comprising just a mere 1% of all air cons.
Figure 1: Breakdown of Air Conditioners Types
Among all the respondents, the Department of Public Works and Highways (DPWH) has the highest
number of air conditioners with a total of 662 window and split type units. Following the DPWH are
the Department of Energy (245 air cons) and Department of Science and Technology – Industrial
Development Technology Institute (244 air cons). Table 2 lists the top 10 respondents with the
highest number of operating air conditioners. The units of these 10 agencies comprise 52% of the
total air cons in this study. The complete ranking of all respondents is in Annex 1.
Table 2: Top 10 Respondents with the greatest quantity of operational air conditioners
RespondentNumber of Air
Cons
% of Total No. of
Air Cons
1 Department of Public Works and Highways 662 14.80 %
2 Department of Energy 245 5.48 %
3Department of Science and Technology - Industrial Technology
Development Institute
244 5.45 %
4 Philippine Ports Authority 207 4.63 %
5 Department of Social Welfare and Development, Main Office 194 4.34 %
6 National Food Authority 167 3.73 %
7 Metropolitan Manila Development Authority 164 3.67 %
8 National Housing Authority 163 3.64 %
9 Bureau of Corrections 144 3.22 %
Number of Air Conditioners
Window Type 2232
Split Type 2203
Centralized 38
TOTAL 4,473
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 8/38
Baseline Market Study on Air Conditioner Use in Government Buildings
4
10 Department of Labor and Employment 143 3.20 %
3.1
Window Type Air Conditioners
Window type air conditioners have all its components, namely compressor, condenser, andevaporator coil enclosed in a single box. It is fitted in a slot on a wall or a window sill. The DPWH
uses the most window type air conditioners (358 units). It is followed by the Department of Energy
with 161 units, and by the Metropolitan Manila Development Authority (MMDA) with 149 window
type air cons. The top 10 respondents with the highest number of operating window type air cons
are listed in Table 3.
Annex 2 has the complete ranking of all respondents according to the number of their window type
units.
Table 3: Top 10 Respondents with the highest number of operational window type air conditioners
RespondentNo. of Window
Air Cons
% of
Respondents’
Air Cons
% of Total
Window Air
Cons
1 Department of Public Works and Highways 358 54 % 16.04 %2 Department of Energy 161 66 % 7.21 %
3 Metropolitan Manila Development Authority 149 91 % 6.68 %
4Department of Social Welfare and
Development, Main Office141 73 % 6.32 %
5 Bureau of Corrections 132 92 % 5.91 %
6 National Housing Authority 128 79 % 5.73 %
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 9/38
Baseline Market Study on Air Conditioner Use in Government Buildings
5
7Department of Science and Technology -
Industrial Technology Development Institute127 52 % 5.69 %
8 Mines and Geosciences Bureau 101 85 % 4.53 %
9 Parole and Probation Administration 72 91 % 3.23 %
10Bureau of Fire Protection, National
Headquarters65 96 % 2.91 %
3.2 Split Type Air Conditioners
The split type air conditioner comprises of an indoor unit and an outdoor unit. The outdoor unit
houses the compressor and condenser, while the indoor unit encloses the evaporator coil and
cooling fan. Split type units do not require mounting through walls. It only needs a small hole for the
conduit that connects the indoor and outdoor units. The indoor units of split type air cons may be
wall-mounted or floor-standing.
The Department of Public Works and Highways also has the most number of split type air
conditioners with 304 units. The Philippine Ports Authority follows with 207 split type units, which
are all its air cons. These split type units include both wall-mounted and floor standing split units.
The following table (Table 4) is a list of the top 10 respondents with the most number of installed
split type air conditioners. The complete ranking of respondents based on the number of their
installed split type air cons is in
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 10/38
Baseline Market Study on Air Conditioner Use in Government Buildings
6
Annex 3.
Table 4: Top 10 Respondents with the most number of operational split type air conditioners
RespondentNumber of Split
Air Cons
% of
Respondent’s
Air Cons
% of Total
Split Air Cons
1 Department of Public Works and Highways 304 46 % 13.80 %
2 Philippine Ports Authority 207 100 % 9.40 %
3 National Food Authority 118 71 % 5.36 %
4Department of Science and Technology - Industrial
Technology Development Institute117 48 % 5.31 %
5 National Telecommunications Commission 106 91 % 4.81 %
6 Land Bank of the Philippines 92 94 % 4.18 %
7 Department of Labor and Employment 88 62 % 3.99 %
8 Philippine Overseas Employment Administration 87 74 % 3.95 %
9 Department of Energy 84 34 % 3.81 %
10 Department of Transportation and Communication 72 100 % 3.27 %
3.3
Centralized Air Conditioners
The centralized air conditioning system uses ducts to distribute cooled air, or pipes to distributechilled water to heat exchangers to multiple rooms. Among the 54 respondents, 10 use centralized
air conditioners. Agencies that do not own the centralized air cons they use such as those that lease
space in the buildings they are in are not included in this tally. The complete list of respondents with
operational centralized air conditioners is in Table 5.
Table 5: List of Respondents with operational centralized air conditioners
Respondent
Number of
Centralized Air
Cons
% of
Respondent’s Air
Cons
% of Total
Centralized Air Cons
1 National Electrification Administration 8 30 % 21.05 %
2 Land Bank of the Philippines 6 6 % 15.79 %
National Kidney and Transplant
Institute
6 8 % 15.79 %
3 Cultural Center of the Philippines 5 7 % 13.16 %
4 National Housing Authority 4 2 % 10.53 %
5 Philippine National Oil Company 3 21 % 7.89 %
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 11/38
Baseline Market Study on Air Conditioner Use in Government Buildings
7
6 National Tax Research Center 2 100 % 5.26 %
Philippine Institute For Development
Studies
25 %
5.26 %
7 Local Water Utilities Administration 1 100 % 2.63 %
Security and Exchange Commission 1 2 % 2.63 %
4.0 Air Conditioner Capacities
The succeeding graphs (Figure 2 -
Figure 4) show the breakdown of air con units according to their cooling capacities. Among window
type air cons, units with cooling capacities 18,900 – 19,000 kJ/h are the predominant (totaling 573
units). In the market, these units are more commonly referred to as 2HP units (although there is no
equivalence between the HP and kJ/h ratings). These make up 25% of all window type units
reported.
The 60,000 kJ/h (5 Tons) units are the most commonly used split type air cons (totaling 697 units),
followed very closely by the 36,000 kJ/h (3 Tons) units (612 units). The combined total of air cons
with these two cooling capacities constitutes 60% of all split type units. For centralized air cons, the
most commonly used are the 10 Tons and 140 Tons units (which both total eight units).
Figure 2: Number of units of window type air cons per cooling capacity
4000 -
6500
7200 -
9300
9475 -
9750
10000 -
12380
12660 -
12800
13188 -
13990
16000 -
17020
18900 -
19000
19600 20045 -
22205
24000 25000 -
32000
27 52
180
39
422
113
49
573
411
41
133
36
N u m b e r o f A C U n i t s
kJ/h
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 12/38
Baseline Market Study on Air Conditioner Use in Government Buildings
8
Figure 3: Number of units of split type air cons per cooling capacity
Figure 4: Number of centralized type units per capacity range
<6 6 9 12 18 24 30 36 48 60 72 84 90 120 >120
16 20 3
92 98
312
19
612
6
697
4 4
136
94
6
N u m b e r o f A C U n i t s
in Thousands, kJ/h
10 30 50 60 90 140 200 250 300 350 500
8
2
3
4
3
8
1 1
5
1 1
N u m b e r o f U n i t s
in Tons Refrigeration
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 13/38
Baseline Market Study on Air Conditioner Use in Government Buildings
9
5.0 Age of Air Conditioners
Out of the total 4,473 air con units in this survey, some 2,040 units (46%) have been indicated the
number of years they had been operating. The age of each unit was calculated from the year it was
purchased. It was assumed that the units had been operating since their purchase date. The oldestreported unit is a window type air conditioner installed at the Department of Science and
Technology’s central office, which has been operating for 27 years. Majority (39%) of the air cons
have been operating for 10 years or longer. Figure 5 shows the breakdown of these air cons
according to their ages.
Figure 5: Operating Ages of Air Conditioners
Majority of the units operating for more than 10 years are window type air conditioners. Of the 38
centralized units reported, 12 units had been operating for more than ten years. Figure 6 shows the
types of air conditioners aged 10 years or longer.
Figure 6: Types of Air Conditioners operating for 10 years or more
0 - 1 Years,
434, 21%
2 - 5 Years,
490, 24%
6 - 9 Years,
324, 16%
≥ 10 Years,
792, 39%
0 - 1 Years,
434, 21%
2 - 5 Years,
490, 24%
6 - 9 Years,
324, 16%
Window, 410,
20%
Split, 370, 18%
Centralized,
12, 1%
≥ 10 Years,
792, 39%
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 14/38
Baseline Market Study on Air Conditioner Use in Government Buildings
10
Interestingly, the Department of Energy has the most number of air cons operating for more than 10
years. Out of the total 245 units installed in its office, 163 or 66% are operating for a decade or so.
The top 10 respondents with the most number of air cons installed and operating for more than 10
years are shown in Table 6, while the complete ranking is in
Annex 4 .
Table 6: Top 10 Respondents with the most number of air cons operating for 10 years or more
Respondent
Number of Air
Cons ≥10 Yrs
Old
% of
Respond
ent’s AC
Window Split Centralized
1 Department of Energy 163 66 % 114 49 0
2 National Telecommunications
Commission
77 66 % 2 75 0
3 Department of Social Welfare and
Development, Main Office
66 34 % 33 33 0
4 Department of Labor and Employment 60 42 % 24 36 0
5 Department of Science and Technology -
Industrial Technology DevelopmentInstitute
59 24 % 38 21 0
6 Mines and Geosciences Bureau 58 49 % 58 0 0
7 Department of Science and Technology -
Central Office
52 54 % 30 22 0
8 Insurance Commission 35 67 % 8 27 0
9 National Youth Commission 25 64 % 11 14 0
Department of Environment & Natural 25 57 % 10 15 0
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 15/38
Baseline Market Study on Air Conditioner Use in Government Buildings
11
Resources, National Capital Region
10 National Printing Office 22 30 % 3 19 0
Games and Amusement Board 22 73 % 16 4 0
6.0
Sizing of Air Conditioners
As a general guide for choosing the proper size of air conditioner to cool a room, the Department of
Energy prescribes a cooling capacity of 500 kJ/sq m. This value does not take into account the
number of persons occupying the room nor the shading or sunlight the room receives. For this
study, units with cooling capacities 500 – 550 kJ/sq m are the ones considered properly sized. If a
unit has a cooling capacity below 500 kJ/sq m then it may be considered ‘undersized.’ Air
conditioners that have small cooling capacities or are undersized will continually run to keep up with
cooling a large room. The unit will not efficiently cool the room and will result to higher electricity
bills. Air cons with cooling capacities greater than 550 kJ/sq m are considered ‘oversized.’ These airconditioners will cycle on and off frequently. The efficiency of the typical air conditioner increases
the longer they run. Moreover, air cons that run on longer cycles are more effective in removing
moisture. For short cycles, the evaporating coils do not have enough time to operate at the low
temperature and when the unit stops, the moisture on the coils evaporates back into the indoor air
rather than be removed out of the condensate drain.1
Out of the 54 respondents, 39 indicated the floor area of the rooms cooled by each of their air
conditioners. The cooling capacities per floor area of 2,570 units (57% of total air cons) were
calculated. Table 7 shows the number of units grouped according to the indicated kJ/sq m capacity
ranges.
Table 7: Number of Air Conditioners per range of kJ/sq m
Cooling Capacity
(kJ/sq m)Number of Units Percentage
< 500 944 37%
500 – 550 140 6%
551 – 1000 1,089 42%
≥ 1001 397 15%
TOTAL 2,570 100 %
The table shows that only 6% of the reported air cons are actually properly sized. More than half
(57%) of the units are oversized with 15% operating at double that of the prescribed 500 kJ/sq m.
On the other hand, the main office of the Department of Social Welfare and Development has the
most undersized air cons with 169 units or 87% of its total installed air conditioners. Sixteen (16) out
1 Proctor, John, Katsnelson, Zinoviy, and Brad Wilson, “Bigger is Not Better: Sizing Air Conditioners,” Home Energy
Magazine May/June 1995.
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 16/38
Baseline Market Study on Air Conditioner Use in Government Buildings
12
of the 39 respondents with kJ/sq m values have no properly sized air conditioners. Table 8 shows
the top 10 respondents with the most undersized units, while the ranking of the other respondents
is in Annex 5.
Table 8: Respondents with the most number of undersized air conditioners (<500 kJ/sq m)
Respondent Number of Air Cons
with <500 kJ/sq m
% Respondent’s
Air Cons
1 Department of Social Welfare and Development, Main
Office
169 87%
2 Department of Science and Technology – Industrial
Technology Development Institute
80 33%
3 Mines and Geosciences Bureau 75 63%
4 Bureau of Fire Protection 65 96%
5 Philippine Economic Zone Authority 62 85%
6 Land Bank of the Philippines 57 58%
7 Philippine Overseas Employment Administration 48 41%
8 Department of Science and Technology – Central Office 42 44%
National Kidney and Transplant Institute 42 55%
9 National Tobacco Administration 41 55%
10 National Printing Office 31 42%
National Telecommunications Office 31 27%
As shown in Table 7, only 140 units or 6% of the air cons with kJ/sq m data are properly sized (500 –
550 kJ/sq m). The Department of Science and Technology – Industrial Technology Development
Institute has the most number of properly sized air cons with 22 units. Table 9 shows the top 10
respondents with the most number of properly sized air conditioners. The ranking of the other
respondents with the most properly sized units is in Annex 6.
Table 9: Respondents with the most number of properly sized conditioners (500-550 kJ/sq m)
Respondent Number of Air Cons
with 500-550 kJ/sq m
% per Respondent’s
Air Cons
1 Department of Science and Technology – Industrial
Technology Development Institute
22 9%
2 National Kidney and Transplant Institute 19 25%
3 Department of Environment and Natural Resources -
National Capital Region
13 30%
4 National Telecommunications Commission 10 9%
5 Department of Science and Technology - Central Office 9 9%
Philippine Information Agency 9 23%
National Youth Commission 9 23 %
6 Mines and Geosciences Bureau 8 7%
7 Landbank of the Philippines 6 6%
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 17/38
Baseline Market Study on Air Conditioner Use in Government Buildings
13
8 Public Attorney's Office 5 16%
Fiber Industry Development Authority 5 33%
9 Cultural Center of the Philippines 4 5%
10 Philippine Overseas Employment Administration 3 3%
Almost half of the units with kJ/sq m data have 551 – 1,000 kJ/sq m cooling capacities (see Table 7). Among the
Among the respondents the Metropolitan Manila Development Authority has the most number of air cons with
air cons with cooling capacities in the range 551 – 1000 kJ/sq m. Its oversized units constitute 92% of all its air
all its air cons. Table 10 lists the top 10 respondents with the most oversized (551 – 1,000 BTU/sq m) air
conditioners, while the complete ranking of these respondents is in
Annex 7.
Table 10: Respondents with the most number of air conditioners with 551 - 1000 kJ/sq m cooling capacities
Respondent Number of Air Cons
with 551-1000 kJ/sq m
% Respondent’s
Air Cons
1 Metropolitan Manila Development Authority 151 92%
2 Philippine Ports Authority 145 70%
3 National Food Authority 142 100%
4 Department of Science and Technology - IndustrialTechnology Development Institute
92 38%
5 Department of Transportation and Communication 72 100%
6 National Telecommunications Commission 51 39%
7 Philippine Overseas Employment Administration 40 34%
8 Department of Science and Technology - Central Office 33 34%
9 Philippine Commission on Good Governance 31 58%
10 National Youth Commission 30 92%
People’s Television Network Inc 30 41 %
A considerable number of units with kJ/sq m values have cooling capacities of >1,000 kJ/sq m – which is twice the prescribed 500 kJ/sq m (see Table 7). The Philippine Ports Authority has 47 units
with cooling capacities greater than 1,000 kJ/sq m. The top 10 respondents with the most number of
air cons with cooling capacities >1,000 kJ/sq m is listed in Table 11, while the complete ranking is in
Annex 8.
Table 11: Respondents with the most number of air conditioners with >1000 kJ/sq m cooling capacities
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 18/38
Baseline Market Study on Air Conditioner Use in Government Buildings
14
Respondent Number of Air Cons
with >1000 kJ/sq m
% Respondent’s Air
Cons
1 Philippine Ports Authority 47 23%
2 Department of Science and Technology - Industrial
Technology Development Institute
35 14%
3 Cultural Center of the Philippines 26 35%4 People's Television Network 25 34%
5 Philippine Overseas Employment Administration 24 21%
6 National Telecommunications Commission 23 25%
7 Center for International Trade Expositions and Missions 22 49%
8 Mines and Geosciences Bureau 21 18%
9 National Printing Office 16 22%
10 Games and Bureau Administration 14 47%
7.0
Energy Efficiency Ratio
The Department of Trade and Industry and the Department of Energy has completed the
implementing guidelines for the new standard on Energy Efficiency Ratio and labeling of air
conditioners (PNS 396 Part 1:2007) that establishes star ratings for window and split type air
conditioning units2. (The new standard did not set star ratings for package type and centralized air
conditioners.) Star ratings, moreover, are limited to room air conditioners with cooling capacities
equal to or below 36,000 kJ/h.3 A unit’s star rating depends on its energy efficiency ratio. The
Energy Efficiency Ratio (EER) is defined as:
Equation 1. Energy Efficiency Ratio
The succeeding tables (Table 12,
Table 13,
Table 14) show the number of air conditioning units in the survey per star rating. Out of the 2,232
window type units, the EERs of 727 units (33%) were reported or calculated. For split type units, theEERs of 961 (44%) of the 2,203 units were reported or calculated. These actually include units with
cooling capacities greater than 36,000 kJ/h. For these units, the star ratings of split type units 12,000
– 36,000 kJ/h were used.
2 The implementing guidelines was completed in 2011 and is pending announcement.
3 This is because of the limitation in the capacity of the testing laboratory.
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 19/38
Baseline Market Study on Air Conditioner Use in Government Buildings
15
Table 12: Number of air cons per range of energy efficiency ratio of window type units
Star Rating
<12,000 kJ/Hr 12,000 – 36,000 kJ/Hr
EERs
Number of
Window Type
Units
EERs
Number of
Window Type
Units
< 9.6 42 < 9.1 34
9.6 10 9.1 – 9.2 59
9.7 – 10.2 30 9.3 – 9.9 108
10.3 – 10.7 23 10.0 – 10.4 148
10.8 – 11.5 15 10.5 – 11.4 162
> 11.6 27 > 11.5 69
Table 13: Number of air cons per range of energy efficiency ratio of split type units
Star Rating< 12,000 kJ/Hr 12,000 – 36,000 kJ/Hr
EERsNumber of Split
Type UnitsEERs
Number of Split
Type Units
< 9.6 31 < 9.1 182
9.6 – 9.7 0 9.1 26
9.8 – 10.2 6 9.2 – 9.6 94
10.3 – 11.0 16 9.7 – 10.2 28
11.1 – 12.3 0 10.3 – 11.4 98
> 12.4 0 > 11.5 20
Table 14: Number of air cons per range of energy efficiency rations of split and package type units*
> 36,000 kJ/Hr
EERs*Number of Split Type
Units
< 9.1 64
9.1 0
9.2 – 9.6 47
9.7 – 10.2 57
10.3 – 11.4 104> 11.5 188
* The PNS does not have star rating classifications for split type
units greater than 36,000 kJ/Hr
Majority or 79% of the air conditioners have EER values that comply or are even higher than the
required minimum EER rating by the PNS (“1” star and above) . Of the air conditioners with EER
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 20/38
Baseline Market Study on Air Conditioner Use in Government Buildings
16
values, a big number or 22% (379 units) have “4” star rating. However, almost an equal number or
21% (353 units) have EER values below the required minimum “1” star level. The potential electricity
savings generated by replacing these air cons with “0” star rating with air cons that have higher EER
values will be discussed in a later section.
Figure 7: Age & EERs for Window Type and Split Type Air Cons
9.69.1 9.1
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
17.0
3000 5000 7000 9000 11000 13000 15000 17000 19000 21000 23000 25000 27000 29000 31000 33000 35000
E E R
kJ/h
Age & EERs: Window Type
>=10 Years
6 - 9 Years
2 - 5 Years
0 - 1 Years
9.6 line
9.1 line
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 21/38
Baseline Market Study on Air Conditioner Use in Government Buildings
17
The charts above (Figure 7) show the correlation between age and EERs of the air con units. Both
plots for window and split air conditioners exhibit that units 10 years old and above do not
necessarily have low EER values. In fact, the graphs clearly show that many units that were
purchased more than 10 years ago have EER values that are already higher than the current
minimum standard.
Both charts also suggest that that there is a wide spread in EER values for units with lower cooling
capacities (> 12,000 kJ/Hr). But as the cooling capacities increase, the EER values tend to be higher.
8.0 Number of Hours in Operation
The average number of operating hours for all air conditioners is 8 hours per day. However, the
average operating hours of all air conditioners of the Power Sector Assets and Liabilities
Management Office is 16 hours, and it has several units operating for 24 hours. Some other agencies
whose average operating hours is 10 hours are (1) Department of Science and Technology – CentralOffice, (2) Philippine National Oil Company, (3) People’s Television Network, and (4) National Kidney
Transplant Institute.
9.6 9.69.1 9.1
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.013.0
14.0
15.0
16.0
17.0
5000 15000 25000 35000 45000 55000 65000 75000 85000 95000 105000 115000
E E R s
kJ/h
Age & EERs: Split Type
>=10 Years
6 - 9 Years
2 - 5 Years
0 - 1 Years
9.6 Line
9.1 Line
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 22/38
Baseline Market Study on Air Conditioner Use in Government Buildings
18
9.0 Potential Savings from Switching to More Efficient Air
Conditioners
Potential savings from replacing air conditioners with “0” star rating to units with higher Energy
Efficiency Ratios were investigated under the following cases and scenarios (Table 15):
Table 15: Switching Cases and Scenarios
SWITCHING
SCENARIOS
WINDOW TYPE SPLIT TYPE
CASE 1 CASE 2 CASE 3 CASE 4 CASE 5
Cooling
Capacities< 12,000 kJ/Hr
12,000 – 36,000
kJ/Hr< 12,000 kJ/Hr
12,000 –
36,000 kJ/Hr> 36,000 kJ/Hr
SCENARIO 1
Switching to
EER = 9.6
(PNS)
Switching to
EER = 9.1
(PNS)
Switching to
EER = 9.6
(PNS)
Switching to
EER = 9.1
(PNS)
Switching to
EER = 9.1
SCENARIO 2
Switching to
EER = 11.6
(PNS)
Switching to
EER = 10.98
(Thai
)
Switching to
EER = 10.91
(Chinese MEPS)
Switching to
EER = 10.46
(Malaysian
)
Switching to
EER = 10.3
The monthly electricity costs of operating air conditioners with “0” star rating were calculated using
the following equation:
Equation 2. Monthly Electricity Cost per Aircon
The power input (kW) was either provided by the respondent or calculated from the EER using
Equation 1 . As the air cons have different power input or wattage values, the monthly electricity
cost for each air con was calculated. These were then summed up to get the total monthly electricity
costs for each case. Below are the other input values used:
Hours/day 8 Hours/ day The survey results showed that the average
operating hours for all air cons is 8 hours/day.
Days/month 22 days/month The number of work days in a month.Electricity
Price/kWh
PhP 10.00/kWh The unit cost of electricity charged to
government agencies.
For each case and scenario, air con units with “0” star rating will be replaced with units of higher EER
values. This implies shifting to air cons with lower wattage requirements. The new wattage values
were calculated using Equation 1. The new monthly cost was then calculated using the obtained
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 23/38
Baseline Market Study on Air Conditioner Use in Government Buildings
19
lower wattage values. The difference between the two electricity costs is the savings generated
from the switch. Below is an example of a Case 1 air con under Scenario 1:
kJ/HrCurrent
EER
Current
W
Monthly
Electricity CostNew EER New W
New Monthly
Electricity Cost
Monthly
Savings
8,500 7.7 1100 P1,936.00 9.6 885 P1,557.60 P378.40
The cost of replacing “0” star air cons with more efficient ones was calculated using 2008 air con
prices derived from an ICASEA-commissioned study.4 It was assumed that air cons will be replaced
with units of the same cooling capacity but higher EER. The prices used are shown below.
Cooling Capacity (kJ/h) Price Range (PhP)
W I N D O W 4000 - 8500 7,500 – 11,500
9500 - 12000 12,400 – 15,000
13200 - 18000 15,500 – 21,000
18600 - 35800 20,300 – 37,000
S P L I T
9000 - 12000 13,000 – 15,500
24000 - 36000 25,000 – 36,700
37900 - 63000 38,000 – 61,000
81500 - 145000 77,500 – 135,000
The succeeding tables show the monthly savings, costs of replacement, and payback periods for the
various switching cases and scenarios investigated.
Table 16: Switching Cases and Scenarios for Window Type Air Cons
WINDOW
CASE 1 CASE 2
< 12,000 kJ/h 12,000 – 36,000 kJ/h
Current Scenario 1 Scenario 2 Current Scenario 1 Scenario 2
No. of ACs to be
Replaced42 42 42 34 34 34
EER ≤ 9.5 9.6 11.6 ≤ 9.0 9.1 10.98
Total Monthly
Electricity CostP 91,341 P 64,570 P 53,437 P 191,548 P 123,225 P 102,126
Total Monthly
Savings- P 26,771 P 37,904 - P 69,323 P 89,422
Total Costs of ACReplacement
- P 475,028 P 529,380 - P 689,657 P 731,016
Payback
(months)- 18 14 - 10 8
4 International Institute for Energy Conservation, “Preparatory Activities for Establishing a High Efficiency
Certification Program in the Philippines – Market Analysis and Stakeholder Engagement: Final Report,” March
2009.
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 24/38
Baseline Market Study on Air Conditioner Use in Government Buildings
20
Table 17: Switching Cases and Scenarios for Split Type Air Cons
SPLIT
CASE 3 CASE 4 CASE 5
< 12,000 kJ/Hr 12,000 – 36,000 kJ/Hr > 36,000 kJ/Hr
Curren
t
Scenario
1
Scenario
2Current
Scenario
1Scenario 2 Current
Scenario
1
Scenario
2
No. of ACs to
be Replaced31 31 31 182 182 182
64 64 64
EER ≤ 9.5 9.6 10.91 ≤ 9.0 9.1 10.46 ≤ 9.0 9.1 10.3
Total
Monthly
Electricity
Cost (PHP)
98,525 65,908 57,995 1,176,333 1,002,070 871,782 1,409,743 1,019,626 900,834
Total
Monthly
Savings (PhP)
- 32,616 40,530 - 174,263 304,551 - 390,118 508,909
Total Costs
of Air Con
Replacement
(PhP)
- 440,005 466,282 - 5,281,722 5,441,881 - 4,955,393 5,005,086
Payback
(months)- 13 12 - 30 18 - 13 10
All cases demonstrate a direct correlation between EER values and energy cost savings. Shifting to
air cons with higher EER values will generate greater savings in electricity costs. Moreover, the
savings generated significantly outweighs the cost of replacement. This is shown in Figure 8, where
the payback period decreases with higher EERs (Scenario 1 vs Scenario 2) despite higher cost of air
con replacement.
Figure 8: Energy Savings and Payback Period
18
14
108
1312
30
18
13
10
0
5
10
15
20
25
30
35
0
100,000
200,000
300,000
400,000
500,000
Case 1 Case 2 Case 3 Case 4 Case 5 10
Scenario 2
Scenario 1
Payback
MonthsSavings, PhP
Case 1 Case 2 Case 3 Case 4 Case 5
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 25/38
Baseline Market Study on Air Conditioner Use in Government Buildings
21
Table 18: Average monthly energy savings per air con
WINDOW SPLIT
CASE 1 CASE 2 CASE 3 CASE 4 CASE 5
< 12,000 kJ/Hr 12,000 – 36,000 kJ/Hr < 12,000 kJ/Hr 12,000 – 36,000 kJ/Hr >36,000 kJ/Hr
Scenario
1
Scenario
2
Scenario
1
Scenario
2
Scenario
1
Scenario
2
Scenario
1
Scenario
2
Scenario
1
Scenario
2Switch to
EER9.6 11.6 9.1 10.98 9.6 10.91 9.1 10.46 9.1 10.3
Monthly
Energy
Savings/AC
(PhP)
P 637 P 902 P 2,010 P 2,630 P1,052 P1,307 P957 P1,673 P6,096 P7,952
Figure 9: Energy Cost and Savings per Air Conditioner*
*C = Current Scenario, S1 = Scenario 1, S2 = Scenario 2
Table 18 shows the monthly energy cost savings per air con in each case and scenario. Thesuggested EERs for Scenario 1 in all cases are the (minimum) EER values for the 1-star rating defined
by the Philippine National Standards for air conditioners. Switching to air cons with the minimum 1-
star EER value will already generate substantial energy savings ranging from Php 637 to Php 6,092
per unit. This redounds to annual savings of a minimum of PhP 7,644 to Php 73,104 per unit.
Switching to air conditioners with higher EER values (Scenario 2) will generate even greater annual
savings from Php 10,824 to Php 95,424 per unit.
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 26/38
Baseline Market Study on Air Conditioner Use in Government Buildings
22
Figure 9 compares the average electricity costs and savings in each scenario. It clearly shows that
the energy cost decreases with higher EER values (shifting from Current Scenario to Scenario 1 to
Scenario 2), which results to greater savings in electricity bill. The figure also suggests that greater
savings are generated in air conditioners of higher cooling capacities (Case 2 for window type and
Case 5 for split type).
10.0 Summary of Results
Air conditioner inventory and utilization questionnaires were sent to 120 government agencies and
received 54 responses in return. A summary of the results of this survey is outlined below:
There are a total of 4,473 air conditioner units reported by the respondents.
Half of the air conditioners are window type units and the other half are split type units.Centralized air cons comprise a mere 1% of all units.
The Department of Public Works and Highways (DPWH) has the highest number of air
conditioners, with 662 units. It also owns the most window type units and the most split
type units.
The National Electrification Administration (NEA) owns the most centralized air conditioners
with 8 units.
25% of all window type units have cooling capacities within the range of 18,900 –19,000
kJ/h.
60% of split type units have cooling capacities 60,000 kJ/h or 36,000 kJ/h.
The most commonly used centralized air conditioners are the 6 tons and 140 tons with 8
units each.
More than one-third or 39% of all air cons that reported their age have been operating for
10 years or longer.
57% of air conditioners with cooling capacity per floor area values are oversized having
cooling capacities greater than 550 kJ/sq m.
Majority (79%) of air conditioners that provided their EER values comply with the minimum
“1” star rating mandated by the new Philippine National Standards.
A big part (22%) of air cons with EER values have “4” star rating, while 21% (353 units) have
no star rating or below the minimum PNS required level.
Shifting all “0” star rating air cons to the minimum “1” star level generates a total of
Php693,091 monthly electricity savings, and could reach a total of PhP981,318 monthly if
replaced by units with higher EER values.
Savings generated from shifting to units with higher EER values outweigh the cost of air con
replacement. Payback of cost of replacing air conditioners decrease when shifting to higher
EER values.
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 27/38
Baseline Market Study on Air Conditioner Use in Government Buildings
23
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 28/38
Baseline Market Study on Air Conditioner Use in Government Buildings
24
Annexes
Annex 1: Ranking of Respondents Based on their Total Number of Air Cons
Respondents Number of Air
Cons
% of Total Number
of Air Cons
1 Department of Public Works & Highways 662 14.80 %
2 Department of Energy 245 5.48 %
3 Department of Science and Technology - Industrial Technology
Development Institute/Chemicals & Energy Division
244 5.45 %
4 Philippine Ports Authority 207 4.63 %
5 Department of Social Welfare and Development, Main Office 194 4.34 %
6 National Food Authority 167 3.73 %
7 Metropolitan Manila Development Authority 164 3.67 %
8 National Housing Authority 163 3.64 %
9 Bureau of Corrections 144 3.22 %
10 Department of Labor and Employment 143 3.20 %
11 Mines and Geosciences Bureau 119 2.66 %
12 Philippine Overseas Employment Administration 117 2.62 %
13 National Telecommunications Commission 116 2.59 %
14 Landbank of the Philippines 98 2.19 %
15 Department of Science and Technology - Central Office 96 2.15 %
16 Philippine Coconut Authority 83 1.86 %
17 Parole and Probation Administration 79 1.77 %
18 National Kidney and Transplant Institute 76 1.70 %
19 National Tobacco Administration 75 1.68 %20 Cultural Center of the Philippines 75 1.68 %
21 People's Television Network Inc. 74 1.65 %
22 Philippine Economic Zone Authority 73 1.63 %
23 National Printing Office 73 1.63 %
24 Department of Transportation and Communication 72 1.61 %
25 Bureau of Fire Protection - National Headquarters 68 1.52 %
26 Security and Exchange Commission 55 1.23 %
27 Philippine Commission on Good Governance 53 1.18 %
28 Insurance Commission 52 1.16 %
29 Fertilizer and Pesticide Authority 52 1.16 %30 Commission on Population 48 1.07 %
31 Maritime Industry Authority 45 1.01 %
32 Center for International Trade Expositions and Missions 45 1.01 %
33 Department of Environment and Natural Resources - National
Capital Region
44 0.98 %
34 Philippine Institute For Development Studies 40 0.89 %
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 29/38
Baseline Market Study on Air Conditioner Use in Government Buildings
25
35 Philippine Information Agency 39 0.87 %
36 National Youth Commission 39 0.87 %
37 Bureau of Agricultural Research 39 0.87 %
38 Science and Technology Information Institute 33 0.74 %
39 Dangerous Drugs Board 32 0.72 %
40 Public Attorney's Office 31 0.69 %
41 Games and Amusement Board 30 0.67 %
42 National Electrification Administration 27 0.60 %
43 National Development Company 24 0.54 %
44 Department of Social Welfare and Development - Field Office 21 0.47 %
45 Advance Science and Technology Institute 16 0.36 %
46 Fiber Industry Development Authority 15 0.34 %
47 Philippine National Oil Company 14 0.31 %
48 Philippine Army 14 0.31 %
49 Toll Regulatory Board 13 0.29 %
50 Power Sector Assets and Liabilities Management 10 0.22 %51 Small Business Guarantee and Finance Corporation 8 0.18 %
52 Philippine Health Insurance Corporation 4 0.09 %
53 National Tax Research Center 2 0.04 %
54 Local Water Utilities Administration 1 0.02 %
TOTAL 4473 100 %
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 30/38
Baseline Market Study on Air Conditioner Use in Government Buildings
26
Annex 2: Ranking of Respondents Based on the Number of their Window Type Air Cons
Respondents
Number of
Window Air
Cons
% of
Respondent’s
Air Cons
% of Total
Window Air
Cons
1 Department of Public Works and Highways 358 54 % 16.04 %2 Department of Energy 161 66 % 7.21 %
3 Metropolitan Manila Development Authority 149 91 % 6.68 %
4 Department of Social Welfare and Development, Main
Office
141 73 % 6.32 %
5 Bureau of Corrections 132 92 % 5.91 %
6 National Housing Authority 128 79 % 5.73 %
7 Department of Science and Technology - Industrial
Technology Development Institute/Chemicals & Energy
Division
127 52 % 5.69 %
8 Mines and Geosciences Bureau 101 85 % 4.53 %
9 Parole and Probation Administration 72 91 % 3.23 %
10 Bureau of Fire Protection, National Headquarters 65 96 % 2.91 %
11 National Kidney and Transplant Institute 61 80 % 2.73 %
12 Department of Labor and Employment 55 38 % 2.46 %
13 Department of Science and Technology, Central Office 55 57 % 2.46 %
14 National Tobacco Administration 53 71 % 2.37 %
15 National Food Authority 49 29 % 2.20 %
16 Philippine Coconut Authority 48 58 % 2.15 %
17 Philippine Commission on Good Governance 39 74 % 1.75 %
18 Philippine Institute For Development Studies 38 95 % 1.70 %
19 Maritime Industry Authority 36 80 % 1.61 %
20 Philippine Overseas Employment Administration 30 26 % 1.34 %
21 People's Television Network Inc. 26 35 % 1.16 %
22 National Youth Commission 25 64 % 1.12 %
23 National Printing Office 24 33 % 1.08 %
24 Public Attorney's Office 23 74 % 1.03 %
25 Science and Technology Information Institute 22 67 % 0.99 %
26 Philippine Economic Zone Authority 21 29 % 0.94 %
27 Department of Environment and Natural Resources,
National Capital Region
19 43 % 0.85 %
28 Games and Amusement Board 19 63 % 0.85 %
29 Cultural Center of the Philippines 18 24 % 0.81 %
30 Philippine Information Agency 17 44 % 0.76 %
31 Department of Social Welfare and Developmen, Field Office 15 71 % 0.67 %
32 Fiber Industry Development Authority 13 87 % 0.58 %
33 Commission on Population 12 25 % 0.54 %
34 Security and Exchange Commission 11 20 % 0.49 %
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 31/38
Baseline Market Study on Air Conditioner Use in Government Buildings
27
35 National Electrification Administration 11 41 % 0.49 %
36 Toll Regulatory Board 11 85 % 0.49 %
37 National Telecommunications Commission 10 9 % 0.45 %
38 Insurance Commission 9 17 % 0.40 %
39 Center for International Trade Expositions and Missions 7 16 % 0.31 %
40 Dangerous Drugs Board 7 22 % 0.31 %
41 Bureau of Agricultural Research 5 13 % 0.22 %
42 Philippine Army 4 29 % 0.18 %
43 Philippine National Oil Company 3 21 % 0.13 %
44 National Development Company 2 8 % 0.09 %
TOTAL 2232 100 %
Respondents not included in this list do not use window type air cons.
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 32/38
Baseline Market Study on Air Conditioner Use in Government Buildings
28
Annex 3: Ranking of Respondents Based on the Number of their Split Type Air Cons
Respondents
Number of
Split Type
Air Cons
% of
Respondent’s
Air Cons
% of Total
Split Air
Cons
1 Department of Public Works and Highways 304 46 % 13.80 %2 Philippine Ports Authority 207 100 % 9.40 %
3 National Food Authority 118 71 % 5.36 %
4 Department of Science and Technology - Industrial
Technology Development Institute117 48 % 5.31 %
5 National Telecommunications Commission 106 91 % 4.81 %
6 Landbank of the Philippines 92 94 % 4.18 %
7 Department of Labor and Employment 88 62 % 3.99 %
8 Philippine Overseas Employment Administration 87 74 % 3.95 %
9 Department of Energy 84 34 % 3.81 %
10 Department of Transportation and Communication 72 100 % 3.27 %
11 Department of Social Welfare and Development, Main
Office
53 27 % 2.41 %
12 Cultural Center of the Philippines 52 69 % 2.36 %
13 Philippine Economic Zone Authority 52 71 % 2.36 %
14 Fertilizer and Pesticide Authority 52 100 % 2.36 %
15 National Printing Office 49 67 % 2.22 %
16 People's Television Network Inc. 48 65 % 2.18 %
17 Security and Exchange Commission 43 78 % 1.95 %
18 Insurance Commission 43 83 % 1.95 %
19 Department of Science and Technology, Central Office 41 43 % 1.86 %
20 Center for International Trade Expositions and Missions 38 84 % 1.72 %
21 Commission on Population 36 75 % 1.63 %
22 Philippine Coconut Authority 35 42 % 1.59 %
23 Bureau of Agricultural Research 34 87 % 1.54 %
24 National Housing Authority 31 19 % 1.41 %
25 Department of Environment and Natural Resources,
National Capital Region
25 57 % 1.13 %
26 Dangerous Drugs Board 25 78 % 1.13 %
27 National Tobacco Administration 22 29 % 1.00 %
28 Philippine Information Agency 22 56 % 1.00 %
29 National Development Company 22 92 % 1.00 %
30 Mines and Geosciences Bureau 18 15 % 0.82 %
31 Advance Science and Technology Institute 16 100 % 0.73 %
32 Metropolitan Manila Development Authority 15 9 % 0.68 %
33 Philippine Commission on Good Governance 14 26 % 0.64 %
34 National Youth Commission 14 36 % 0.64 %
35 Bureau of Corrections 12 8 % 0.54 %
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 33/38
Baseline Market Study on Air Conditioner Use in Government Buildings
29
36 Science and Technology Information Institute 11 33 % 0.50 %
37 Games and Amusement Board 11 37 % 0.50 %
38 Philippine Army 10 71 % 0.45 %
39 Power Sector Assets and Liabilities Management 10 100 % 0.45 %
40 National Kidney and Transplant Institute 9 12 % 0.41 %
41 Maritime Industry Authority 9 20 % 0.41 %
42 Public Attorney's Office 8 26 % 0.36 %
43 National Electrification Administration 8 30 % 0.36 %
44 Philippine National Oil Company 8 57 % 0.36 %
45 Small Business Guarantee and Finance Corporation 8 100 % 0.36 %
46 Parole and Probation Administration 7 9 % 0.32 %
47 Department of Social Welfare and Development, Field
Office
6 29 % 0.27 %
48 Philippine Health Insurance Corporation 4 100 % 0.18 %
49 Bureau of Fire Protection, National Headquarters 3 4 % 0.14 %
50 Fiber Industry Development Authority 2 13 % 0.09 %51 Toll Regulatory Board 2 15 % 0.09 %
TOTAL 2203 100 %
Respondents not on the list do not use split type air conditioners.
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 34/38
Baseline Market Study on Air Conditioner Use in Government Buildings
30
Annex 4: Ranking of Respondents based on the Number of Air Cons Operating for 10 Years or More
Respondent
Number of Air
Cons ≥10 Yrs
Old
% of
Respond
ent’s AC
Window Split Centralized
1 Department of Energy 163 66 % 114 49 02 National Telecommunications
Commission
77 66 % 2 75 0
3 Department of Social Welfare and
Development, Main Office
66 34 % 33 33 0
4 Department of Labor and Employment 60 42 % 24 36 0
5 Department of Science and Technology -
Industrial Technology Development
Institute
59 24 % 38 21 0
6 Mines and Geosciences Bureau 58 49 % 58 0 0
7 Department of Science and Technology,
Central Office
52 54 % 30 22 0
8 Insurance Commission 35 67 % 8 27 0
9 National Youth Commission 25 64 % 11 14 0
Department of Environment & Natural
Resources, National Capital Region
25 57 % 10 15 0
10 National Printing Office 22 30 % 3 19 0
11 Games and Amusement Board 22 73 % 16 6 0
12 Science and Technology Information
Institute
19 58 % 10 9 0
13 National Tobacco Administration 17 23 % 16 1 0
14 National Electrification Administration 12 44 % 0 4 815 Department of Social Welfare and
Development, Field Office
11 52 % 9 2 0
16 National Kidney and Transplant Institute 10 13 % 0 9 1
17 Philippine Information Agency 10 26 % 5 5 0
18 Philippine Institute For Development
Studies
9 23 % 9 0 0
19 Bureau of Agricultural Research 8 21 % 5 3 0
20 People's Television Network Inc. 8 11 % 6 2 0
21 Public Attorney's Office 8 26 % 3 5 0
22 Small Business Guarantee and Finance
Corporation
8 100 % 0 8 0
23 Center for International Trade Expositions
and Missions
5 11 % 0 5 0
24 Philippine National Oil Company 3 21 % 0 0 3
TOTAL 792 410 370 12
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 35/38
Baseline Market Study on Air Conditioner Use in Government Buildings
31
Annex 5: Ranking of Respondents based on the number of their air cons which are <500 kJ/sqm
RespondentNumber of Air Cons
with <500 kJ/sqm
% Respondent’s Air
Cons
1 Department of Social Welfare and Development, Main
Office
169 87%
2 Department of Science and Technology – Industrial
Technology Development Institute
80 33%
3 Mines and Geosciences Bureau 75 63%
4 Bureau of Fire Protection 65 96%
5 Philippine Economic Zone Authority 62 85%
6 Landbank of the Philippines 57 58%
7 Philippine Overseas Employment Administration 48 41%
8 Department of Science and Technology – Central Office 42 44%
National Kidney and Transplant Institute 42 55%
9 National Tobacco Administration 41 55%
10 National Printing Office 31 42%
National Telecommunications Office 31 27%
11 Fertilizer and Pesticide Authority 26 50 %
12 National Food Authority 25 15 %
13 Cultural Center of the Philippines 23 31 %
14 Public Attorney's Office 18 58 %
15 National Development Company 16 67 %
16 Philippine Ports Authority 13 6 %
17 Philippine Information Agency 11 28 %
Philippine Commission on Good Governance 11 21 %
18 Power Sector Assets and Liabilities Management 8 80 %
Small Business Guarantee and Finance Corporation 8 100 %
19 Fiber Industry Development Authority 7 47 %
20 Dangerous Drugs Board 6 19 %
National Electrification Administration 6 22 %
Toll Regulatory Board 6 46 %
21 Department of Social Welfare and Development, Field
Office
4 19 %
People's Television Network Inc. 4 5 %
22 Department of Environment and Natural Resources,
National Capital Region
3 7 %
Philippine Army 3 21 %
23 Center for International Trade Expositions and Missions 2 4 %
24 Local Water Utilities Administration 1 100 %
TOTAL 944
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 36/38
Baseline Market Study on Air Conditioner Use in Government Buildings
32
Annex 6: Ranking of Respondents according to the number of air cons which are 500-550 kJ/sqm
RespondentNumber of Air Cons
with 500-550 BTU/sqm
% per Respondent’s
Air Cons
1 Department of Science and Technology – Industrial
Technology Development Institute
22 9 %
2 National Kidney and Transplant Institute 19 25 %
3 Department of Environment and Natural Resources -
National Capital Region
13 30 %
4 National Telecommunications Commission 10 9 %
5 Department of Science and Technology - Central Office 9 9 %
Philippine Information Agency 9 23 %
National Youth Commission 9 23 %
6 Mines and Geosciences Bureau 8 7 %
7 Landbank of the Philippines 6 6 %
8 Public Attorney's Office 5 16 %
Fiber Industry Development Authority 5 33 %
9 Cultural Center of the Philippines 4 5 %
10 Philippine Overseas Employment Administration 3 3 %
Center for International Trade Expositions and Missions 3 7 %
Bureau of Agricultural Research 3 8 %
11 Philippine Economic Zone Authority 2 3 %
National Development Company 2 8 %
Philippine Ports Authority 2 1 %
National Electrification Administration 2 7 %
12 Department of Social Welfare and Development, Main
Office
1 1 %
National Printing Office 1 1 %
Fertilizer and Pesticide Authority 1 2 %
People's Television Network Inc. 1 1 %
TOTAL 140
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 37/38
Baseline Market Study on Air Conditioner Use in Government Buildings
33
Annex 7: Ranking of Respondents based on their number of air cons which are 551 - 1000 kJ/sqm
RespondentNumber of Air Cons
with 551-1000 kJ/sqm
% Respondent’s
Air Cons
1 Metropolitan Manila Development Authority 151 92%
2 Philippine Ports Authority 145 70%
3 National Food Authority 142 100%
4 Department of Science and Technology - Industrial
Technology Development Institute
92 38%
5 Department of Transportation and Communication 72 100%
6 National Telecommunications Commission 51 39%
7 Philippine Overseas Employment Administration 40 34%
8 Department of Science and Technology - Central Office 33 34%
9 Philippine Commission on Good Governance 31 58%
10 National Youth Commission 30 92%
People's Television Network Inc. 30 41 %
11 Bureau of Agricultural Research 25 64 %12 Dangerous Drugs Board 22 69 %
13 National Tobacco Administration 21 28 %
Department of Environment and Natural Resources,
National Capital Region
21 48 %
14 Landbank of the Philippines 20 20 %
15 Center for International Trade Expositions and Missions 18 40 %
16 National Printing Office 17 23 %
Cultural Center of the Philippines 17 23 %
17 Games and Amusement Board 16 53 %
18 Mines and Geosciences Bureau 15 13 %
Philippine Information Agency 15 38 %
19 Fertilizer and Pesticide Authority 13 25 %
20 Public Attorney's Office 8 26 %
21 National Electrification Administration 7 26 %
22 Department of Social Welfare and Development, Main
Office
6 3 %
Department of Social Welfare and Development, Field
Office
6 29 %
National Development Company 6 21 %
23 Toll Regulatory Board 5 38 %
24 Philippine Army 4 29 %
Philippine Health Insurance Corporation 4 100 %
25 Power Sector Assets and Liabilities Management 2 20 %
Philippine National Oil Company 2 14 %
26 National Kidney and Transplant Institute 1 1 %
Fiber Industry Development Authority 1 7 %
TOTAL 1,088
7/25/2019 Aircon Survey
http://slidepdf.com/reader/full/aircon-survey 38/38
Baseline Market Study on Air Conditioner Use in Government Buildings
Annex 8: Ranking of Respondents based on the number of their air cons which are >1000 kJ/sqm
RespondentNumber of Air Cons
with >1000 kJ/sqm
% Respondent’s Air
Cons
1 Philippine Ports Authority 47 23%
2 Department of Science and Technology - IndustrialTechnology Development Institute
35 14%
3 Cultural Center of the Philippines 26 35%
4 People's Television Network 25 34%
5 Philippine Overseas Employment Administration 24 21%
6 National Telecommunications Commission 23 20 %
7 Center for International Trade Expositions and Missions 22 49%
8 Mines and Geosciences Bureau 21 18%
9 National Printing Office 16 22%
10 Games and Bureau Administration 14 47%
11 National Tobacco Administration 13 17 %
Metropolitan Manila Development Authority 13 8 %
12 Fertilizer and Pesticide Authority 12 23 %
13 Philippine Commission on Good Governance 11 21 %
Department of Social Welfare and Development - Field
Office
11 52 %
Bureau of Agricultural Research 11 28 %
14 Philippine Economic Zone Authority 9 12 %
Landbank of the Philippines 9 9 %
Department of Science and Technology - Central Office 9 9 %
Philippine National Oil Company 9 64 %
15 National Kidney and Transplant Institute 8 11 %
16 Department of Environment and Natural Resources -
National Capital Region
7 16 %
Philippine Army 7 50 %
17 National Electrification Administration 4 15 %
18 Philippine Information Agency 3 8 %
Dangerous Drugs Board 3 9 %
19 Department of Social Welfare and Development, Main
Office
2 1 %
Fiber Industry Development Authority 2 13 %
20 National Development Company 1 4 %
Toll Regulatory Board 1 8 %
TOTAL 398