AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A Pool air handling units 3 Air Master BCP PrinciPle schemes DescriPtion The range of Air Master BCP Series are dehumidification units by cooling circuit, with total condensing heat recovery, specially designed for conventional covered pools and other dehumidification applications. These units have been designed for indoor or outdoor installations. Consult specific applications (marine atmospheres, high concentrations of salts or chemical agents, high temperatures, etc.). Cooling capacity: Heating capacity: 92,1 to 179,9 kW 69,5 to 148,7 kW range Air Master BCP: 3 cooling circuits, 3 compressors, 7 models: 320 / 360 / 400 / 440 / 480 / 555 / 610 oPerating limits Air intlet dry temperature Maximum: 35ºC (65% RH - 29ºC WB) Minimum: 18ºC (90% RH - 17ºC WB) Condenser water intlet temperature Maximum: 50ºC Minimum: 20ºC C1 C2 C3 Evaporator coil Condenser coil Hot water coil Discharge fan Plates exchanger Plates exchanger for boiler water Boiler Pool Heating and dehumidification of covered pools Optimized energy consumption Electronic control

Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Embed Size (px)

Citation preview

Page 1: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

3

Air M

aste

r BC

P

PrinciPle schemesDescriPtion

The range of Air Master BCP Series are dehumidification units by cooling circuit, with total condensing heat recovery, specially designed for conventional covered pools and other dehumidification applications. These units have been designed for indoor or outdoor installations.

Consult specific applications (marine atmospheres, high concentrations of salts or chemical agents, high temperatures, etc.).

Cooling capacity:

Heating capacity:

92,1 to 179,9 kW69,5 to 148,7 kW

rangeAir Master BCP: 3 cooling circuits, 3 compressors, 7 models:

• 320 / 360 / 400 / 440 / 480 / 555 / 610

oPerating limitsAir intlet dry temperature

Maximum: 35ºC (65% RH - 29ºC WB)

Minimum: 18ºC (90% RH - 17ºC WB)

Condenser water intlet temperature

Maximum: 50ºC

Minimum: 20ºC

C1

C2

C3

Evaporatorcoil

Condensercoil

Hot watercoil

Discharge fan

Platesexchanger

Platesexchanger

for boiler water

BoilerPool

Heating and dehumidification of covered pools

Optimized energy consumption

Electronic control

Page 2: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A4

Air Master BCPUnits comPositionStandard equipment

- Sandwich-panel casing made up in galvanized steel plate of 1 mm covered with polyester paint outside and inside, with glass fiber insulation of 25 mm.

- Support frame and hinged doors to access to the sections of the unit.

- Panels and doors with rubber joints to ensure watertightness.

- Sheet butt-strap between modules for outdoor installation.

Internal air circuit

- G3 filter renewable mounted on frame.- Direct expansion chiller coil with copper tubes and aluminium fins,

with polyurethane coating.

- Condenser coil with copper tubes and aluminium fins, with polyu-rethane protection (air condenser) and of welded plates (water condenser).

- Stainless steel condensates drain pan with drainage outlet. This pan is inclinated towards the drainage outlet so that the water does not stagnate in the pan, avoiding sanitary problems.

- Centrifugal fan of galvanized plate driven by belts and pulleys. Kit mounted over anti-vibratory supports and attached to the panel by means of flexible pipe.

- Air by-pass damper, with manual fit.

Cooling circuit

- Unit of three cooling circuits:• All circuits participate in the air dehumidification when evaporating

on coil.

• One of the circuits is condensed over a special SMO-254 welded with copper, filled with pool water, recovering part of the energy from the evaporation process.

• The other two circuits condensate over an air coil located at the evaporator air outlet, heating the cold and dry air, before discharge over the optional hot water coil.

- Three Scroll hermetic compressors with heat insulation, motor tem-perature integral protection, mounted over anti-vibratory supports.

- Thermostatic expansion valve with external equalization.

- Antiacid dryer filter.

Protections- High and low pressure pressostats.

- Main door switch.

- Protection fuses of the compressor(s) and motorfan(s) power supply.

- Control circuit automatic switch.

- Temperature limit thermostat at the inlet of the dehumidification coil.

- Compressor anti-short-cycle timer.

- Double access door to the fan.

Electrical panel

- Complete electrical panel, totally wired.- General ground plug.

- Compressor(s) and motorfan(s) contactors.

GESCLIMA PRO electronic controlGESCLIMA PRO electronic control by microprocessor composed by main board (CPU) and user terminal ( pGD control), with the following functions:

- Dehumidification control.

- Temperature control (optional) (with hot water coil and/or plates exchanger of boiler water).

- Anti-short-cycle timings.

- Water circuit pump control.

- Selection of configuration and operating parameters.

- Failures diagnosis and general alarm.

Optional functions:

- Enthalpic free-cooling and control of external air gates minimum opening.

- Optional electrical heaters control.

- Proportional control of hot water coil.

- Control of plates exchanger of boiler water (optional).

- Air flow control.

- Fouled filters detection.

- Fire thermostat.

- Daily and weekly scheduling.

- Connection to a building management system by PC with Carel, Modbus or LonWorks communication protocol, for managing and control of up to 200 units.

oPtions- Copper tubes and copper fins coils.- 1 or 2 stages electrical heaters with built-in control.

- Hot water coil for post-heating with three ways proportional valve, with polyurethane coating or in copper-copper.

- Plates exchanger ( AISI 316L Steel) and joints (Nitrile) to reach the operating conditions and maintain the vessel temperature, by three ways proportional valve with control depending on the vessel water temperature.

* Optionally Titanium plates.

* Optionally Butilum joints.

- Fouled filters differential pressostat.

- High flow in discharge and return of air circuit.

- G4 and F7 filters.

- Manual damper for ext. air intake.

- Mixing box of 2 dampers, with motorized dampers

- Mixing box of 3 dampers, with motorized dampers and centrifugal return fan.

- Flexible connections of the hot water coil (except connections with flange).

Page 3: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

5

Air M

aste

r BC

P

technical characteristics

PCBretsaMriA 023 063 004 044 084 555 016

tiucricriA

yticapacnoitacifidimuheD � )h/gk( 5,66 8,77 8,28 1,39 0,001 2,611 5,621

)Wk(yticapacgnitaeH 5,96 5,58 49 0, 9,111 7,901 2,421 7,841

yticapacgnilooC � )Wk( 1,29 8,901 0,511 2,231 4,831 0,061 9,971

tupnirewoP � )Wk( 6,22 3,62 3,92 2,13 1,33 9,63 0,54

m(wolfrialanimoN 3 )h/ 000.61 000.81 000.02 000.22 000.42 577.72 000.03

).G.W.mm(.sserpcitats.liavA 1,91 5,71 7,91 6,61 2,71 5,61 8,81

rebmuN/epytnaF 1/lagufirtneC

)Wk(rewoP 5,5 5,5 5,7 5,7 5,7 5,7 11

tiucricriA

wolfhgihfo

)lanoitpo(

m(wolfrialanimoN 3 )h/ 000.42 000.72 000.03 000.33 000.63 526.14 000.34

).G.W.mm(.sserpcitats.liavA 9,61 9,12 9,81 8,51 2,81 4,71 4,91

rebmuN/epytnaF 1/lagufirtneC

)Wk(rewoP 5,7 11 11 11 11 51 5,81

retaW

resnednoc

yticapacgnitaeH � )Wk( 7,93 1,34 8,24 0,44 2,45 1,56 2,56

m(wolfretawlanimoN 3 )h/ 8,6 4,7 4,7 6,7 3,9 2,11 2,11

porderusserP ).G.W.m( 6,0 8,0 8,0 7,0 8,0 7,0 8,0

snoitcennocciluardyH 05-ND ø "2/11 36-ND ø "2

liocretawtoH

)lanoitpo(

yticapacgnitaeH � )Wk( 2,031 4,831 1,541 3,561 3,971 3,112 7,612

m(wolfretawlanimoN 3 )h/ 8,6 2,7 5,7 6,8 4,9 11 3,11

).G.W.m(porderusserP 6,1 8,1 2,1 2,1 4,1 7,1 ,1 6

snoitcennocciluardyH "2

regnahcxesetalP

retawreliobrof

)lanoitpo(

yticapacgnitaeH � )Wk( 002 053 005

)llafCº71(wolF m( 3 )h/ 6,01 7,71 3,52

).G.W.m(porderusserP)edisreliobdnaedisloop(

9,0 ,0 8 ,0 8

snoitcennocciluardyhdedaerhT "2 "2/12

srosserpmoC

epyT llorcS

segatsºN/srosserpmocºN 3/3

yrevocer/stiucricriaºN 1/2

emulovliO )l(7,1+3,3

3,3/

3,3+3,3

3,3/

3,3+0,4

3,3/

0,4+0,4

3,3/

0,4+0,4

0,4/

2,6+2,6

2,6/

2,6+0,8

2,6/

ylppusrewoP ortueN+arreiT+soliH3

mumixaM

tupnirewop004 V / III hp / 05 )A(zH 1,78 1,99 2,201 2,201 2,201 2,021 5,441

tnaregirfeR

T epy c704-R

gnimrawetamilC)PWC(laitnetop � 5,2561

daoL )gk( 1,81 2,32 6,32 2,82 2,82 5,33 3,43

snoisnemiD

L htgne )mm( )577.1+586.2(046.4

htdiW )mm( 402.2

thgieH )mm( 306.1 228.1 831.2

thgieW )gk( 096.2 568.2 049.2 063.3 583.3 059.3 050.4

ØgniniardsetasnednoC "4/11

À Unit cooling dehumidification capacity. For unit selection, it should be taken into account the dehumidification which provides fresh air of ventilation (UNE 100011).

Á Cooling capacity for air inlet temperature conditions of 28ºC and 65% RHÂ Total power input by compressor and motorfans under nominal conditions.Ã Heating capacity for recovery circuit water 28 / 33ºC. Ä Water from boiler for hot water coil 82 / 65ºC.Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to one kilogram of carbon dioxide over a period of 100 years.

Page 4: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A6

Air Master BCPretUrn fan technical characteristics (oPtional)

maximUm cUrrents (a)

niveaUx sonores dB(A)

n Sound power level

Sound power level at the discharge of fan and at the intake of return fan (optional), to take into account for the silencer calculation:

n Sound pressure level

Measure conditions: in free field, measured at 5 meters of distance, directivity 2 and at 1,5 meters from floor.

NOTE: The sound pressure level depends on the installation conditions and, therefore, it is given only as an approximate guide.

PCBretsaMriA 023 063 004 044 084 555 016

wolflanimoN

).G.W.mm(erusserpcitats.liavA 7,41 9,31 7,51 4,41 4,41 61 2,41

epytnaF rebmuN/ 1/lagufirtneC

)Wk(rewoP 3 4 3 3 3 4 4

)lanoitpo(wolfhgiH

erusserpcitats.liavA .mm( W ).G. 7,21 0,61 5,01 5,31 8,9 8,02 1,52

epytnaF rebmuN/ 1/lagufirtneC

)Wk(rewoP 5,5 5,7 5,7 5,7 5,7 11 11

PCBretsaMriA 023 063 004 044 084 555 016

wolflanimoN

nafegrahcsiD )A(Bd 6,18 5,18 5,28 8,18 6,28 6,18 2,48

nafnruteR po( t )lanoi )A(Bd 4,68 5,98 1,97 4,67 3,87 5,77 8,87

)lanoitpo(wolfhgiH

nafegrahcsiD )A(Bd 3,58 8,78 4,68 4,48 3,68 4,88 4,98

nafnruteR )lanoitpo( )A(Bd 3,38 3,68 7,88 0,58 0,78 4,68 3,78

PCBretsaMriA 023 063 004 044 084 555 016

tinudradnatS )A(Bd 4,07 2,07 7,27 5,27 3,27 6,27 8,47

Air Master BCP 320 360 400 440 480 555 610

Compressors 400 V / III ph / 50 Hz 75 87 87 87 87 105 120

Discharge fan(400 V / III ph / 50 Hz)

Nominal flow 11,6 11,6 14,7 14,7 14,7 14,7 22

With bags filter (optional) 14,7 14,7 14,7 22 22 22 29

High flow (optional) 14,7 22 22 22 22 29 37

High flow with bags filter (optional)

22 29 29 29 29 37 42

Return fan(400 V / III ph / 50 Hz)

Nominal flow (optional) 6,9 9 6,9 6,9 6,9 9 9

With bags filter (optional) 6,9 9 6,9 6,9 6,9 9 9

High flow (optional) 11,6 14,7 14,7 14,7 14,7 22 22

High flow with bags filter (optional)

11,6 14,7 14,7 14,7 14,7 22 22

Page 5: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

7

Air M

aste

r BC

P

Weights by moDUles (kg)PCBretsaMriA 023 063 004 044 084 555 016

wolFlanimoN

dradnatStnempiuqe

eludomegrahcsiD 527 537 577 588 588 040.1 070.1

eludomgnilooC 569.1 031.2 561.2 574.2 005.2 019.2 089.2

lanoitpO

seludom

eludomretlifsgaB 597 597 597 009 009 550.1 550.1

srepmad2eludomxobgnixiM 048 048 048 559 559 521.1 521.1

srepmadlaretal3eludomxobgnixiM 087 087 087 578 578 520.1 520.1

srepmadreppu3eludomxobgnixiM 549 549 549 070.1 070.1 052.1 052.1

eludomnafnruteR 018 518 558 089 589 061.1 061.1

rehtOslanoitpo

retawreliobrofregnahcxesetalP 022 022 022 042 042 552 552

sliocretawtoH 021 021 021 031 031 051 051

)lanoitpo(wolfhgiH

dradnatStnempiuqe

eludomegrahcsiD 477 308 428 049 049 980.1 312.1

eludomgnilooC 269.1 721.2 161.2 374.2 594.2 909.2 089.2

lanoitpO

seludom

eludomretlifsgaB 597 597 597 009 009 550.1 550.1

srepmad2eludomxobgnixiM 048 048 048 559 559 521.1 521.1

srepmadlaretal3eludomxobgnixiM 877 877 877 478 478 120.1 120.1

srepmadreppu3eludomxobgnixiM 839 839 839 360.1 360.1 442.1 442.1

eludomnafnruteR 968 878 878 400.1 400.1 112.1 112.1

rehtOslanoitpo

retawreliobrofregnahcxesetalP 022 022 022 042 042 552 552

sliocretawtoH 021 021 021 031 031 051 051

hyDraUlic connections

epiPretemaid

tiucricretawreliobtoH tiucricretawlooP

liocretawtohhtiW setalphtiWregnahcxe

htiW regnahcxesetalp +

liocretawtoh

taehhtiWyrevocer

taehhtiWyrevocer +

regnahcxesetalp

004/063/023 uC"8/12 dedaerht uC"8/12 dedaerht uC"8/52 dedaerht CVP05-ND dedaerht CVP36-ND dedaerht

084/044 uC"8/12 dedaerht uC"8/52 dedaerht tS"3 egnalf CVP05-ND dedaerht CVP57-ND dedaerht

016/555 uC"8/12 dedaerht uC"8/52 dedaerht tS"3 egnalf CVP36-ND dedaerht CVP09-ND dedaerht

electrical heater (oPtional)Available capacities

Assembly inside the unit.

egatloV zH05/hpIII/V004

)Wk(rewoP 6 9 21 51 81 42 72 63 45

)A(tnerruC 7,8 0,31 3,71 7,12 0,62 6,43 0,93 0,25 0,87

Page 6: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A8

Air Master BCPPressUre DroPs

In the water condenser

In the plates exchanger for boiler water (optional)

In the hot water coil (optional)

BCP-480

BCP-555

BCP-610

BCP-320/360

BCP-400/440

Pressuredropm.w.g

Flow

BCP-440/480

BCP-555/610

BCP-320/360/400

Pressure dropm.w.g

Flow

BCP-400

BCP-320/360

BCP-555/610

BCP-440/480

Pressuredropm.w.g

Flow

Page 7: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

9

Air M

aste

r BC

P

hyDraUlic circUit, PrinciPle scheme

corrosion resistancestnetnocretaW stinU reppochtiwsregnahcxE

gnidlew

Hp eulav 9-7

ISxedninoitarutaS)eulavHpatled(

2,0+<0<2,0-

ssendrahlatoT Hdº 51-6

vitcudnoC yti mc/Sµ 005...01

secnatsbusderetliF l/gm 03<

C sedirolh l/gm(000.02< seulavreppu :

)tlusnoc

enirolhceerF l/gm tlusnoc

edihplusnegordyH l/gm 50,0<

ainommA l/gm 2<

setahpluS l/gm 001<

etanobracnegordyH l/gm 003<

/etanobracnegordyHsetahpluS

l/gm 1>

sedihpluS l/gm 1<

setartiN l/gm 001<

setirtiN l/gm 1,0<

norI l/gm 2,0<

senagnaM e l/gm 1,0<

dicacinobraceerF l/gm 02<

NOTE: The values stated are guide values which show variations under particular operating conditions.

NOTE: Consult Assembly Recommendations included on pag 41 of this manual.

WARNING: If the pool water is introduced directly into the unit water condenser, the addition of chlorine should never be carried out before the inlet to this condenser.

Watercondenser

Plates exchangerfor boiler water

(optional)

Hot watercoil

(optional )

PLATES

WA TER

EXCHANGER

COIL

CIRCUITDRAIN

CUT-OFF

DAM PER

3-WAYS VALVE

VALVE

VALVE

AIRVENT

LEGEND

The plates exchangers of Air Master BCP units are made up of SMO-254 stainless steel, and the material used for the plates welding is pure copper.

On the following table it is shown the water corrosion resistance for these materials with different compositions. Values out of these ranges can suppose corrosion problems in plates exchangers.

Page 8: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A10

Air Master BCP

PCBretsaMriA A B C D E F G H I J K L M U V W Y

wolflanimoN

063/023 0464 4022 3061 128 465 615 384 204 0041 805 237 23 8064 6921 342 2051 5902

004 0464 4022 3061 247 227 755 027 204 0041 805 237 23 8064 6921 342 2051 5902

084/044 0464 4022 2281 996 808 695 608 204 0041 415 368 23 8064 6921 342 2051 5902

016/555 0464 4022 8312 056 409 636 409 203 0061 286 368 23 8064 6921 342 2051 5902

wolfhgiH

063/023 0464 4022 3061 247 227 755 027 204 0041 805 237 23 8064 6921 342 2051 5902

004 0464 4022 3061 996 808 695 608 204 0041 805 237 23 8064 6921 342 2051 5902

084/044 0464 4022 2281 056 409 636 608 204 0041 415 368 23 8064 6921 342 2051 5902

016/555 0464 4022 8312 056 409 636 409 203 0061 286 368 23 8064 6921 342 2051 5902

Dimensions schemes

Air Master BCP standard (mm)

Keep this spacefree for installationand maintenance

A

M

D E

B

F

G

H I

C

J

K

L

Y

WUU V M12

a b

Door switch

Condensates draining

1

4

2

3 c

d

Power supply

500mm 500mm

1700

mm

PCBretsaMriA a b c d

snoitcennocciluardyH 052 2231 212 291

IMPORTANT: For optional assemblies which do not appear in this documentation, consult dimensions.

4 Circuit outlet of pool water

3 Circuit inlet of pool water

2 Circuit outlet of boiler hot water

1 Circuit inlet of boiler hot water

Note: See pipe diameters in the hydraulic connections panelNote: All accesses are on the right, in the air flow senseNote: It is required to leave a minimum space to access to condensates draining located on the left, in the sense of air flow

Page 9: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

11

Air M

aste

r BC

P

Air Master BCP with bags filter (optional) (mm)

PCBretsaMriA a b c d

snoitcennocciluardyH 052 2231 212 291

IMPORTANT: For optional assemblies which do not appear in this documentation, consult dimensions.

4 Circuit outlet of pool water

3 Circuit inlet of pool water

2 Circuit outlet of boiler hot water

1 Circuit inlet of boiler hot water

Note: See pipe diameters in the hydraulic connections panelNote: All accesses are on the right, in the air flow senseNote: It is required to leave a minimum space to access to condensates draining located on the left, in the sense of air flow

500mm 500mm

1700

mm

Keep this spacefree for installationand maintenance

A

M

D E

B

F

G

N

H I

C

J

K

L

Y

WW UU VV M12

a b

Door switch

Condensates draining

1

4

2

3 c

d

Power supply

PCBretsaMriA A B C D E F G H I J K L M N U V W Y

wolflanimoN

063/023 4836 4022 3061 128 465 615 384 204 0041 805 237 23 8064 4471 6921 342 2051 5902

004 4836 4022 3061 247 227 755 027 204 0041 805 237 23 8064 4471 6921 342 2051 5902

084/044 4836 4022 2281 996 808 695 608 204 0041 415 368 23 8064 4471 6921 342 2051 5902

016/555 4836 4022 8312 056 409 636 409 203 0061 286 368 23 8064 4471 6921 342 2051 5902

wolfhgiH

063/023 4836 4022 3061 247 227 755 027 204 0041 805 237 23 8064 4471 6921 342 2051 5902

004 4836 4022 3061 996 808 695 608 204 0041 805 237 23 8064 4471 6921 342 2051 5902

084/044 4836 4022 2281 056 409 636 608 204 0041 415 368 23 8064 4471 6921 342 2051 5902

016/555 4836 4022 8312 056 409 636 409 203 0061 286 368 23 8064 4471 6921 342 2051 5902

Page 10: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A12

Air Master BCPAir Master BCP with mixing module of 2 dampers, upper fresh air damper (optional) (mm)

PCBretsaMriA a b c d

snoitcennocciluardyH 052 2231 212 291

IMPORTANT: For optional assemblies which do not appear in this documentation, consult dimensions.

4 Circuit outlet of pool water

3 Circuit inlet of pool water

2 Circuit outlet of boiler hot water

1 Circuit inlet of boiler hot water

Note: See pipe diameters in the hydraulic connections panelNote: All accesses are on the right, in the air flow senseNote: It is required to leave a minimum space to access to condensates draining located on the left, in the sense of air flow

500mm500mm

1700

mm

Keep this spacefree for installationand maintenance

A

M

D E

B

F

G

N

H I

C

J

K

L

Y

WW UU VV M12

a b

Door switch

Condensates draining

1

4

2

3 c

d

Power supplyO P

R

S

PCBretsaMriA A B C D E F G H I J K L M N O P R S U V W Y

wolflanimoN

063/023 4836 4022 3061 128 465 615 384 204 0041 805 237 23 8064 4471 431 368 205 0021 6921 342 2051 5902

004 4836 4022 3061 247 227 755 027 204 0041 805 237 23 8064 4471 431 368 205 0021 6921 342 2051 5902

084/044 4836 4022 2281 996 808 695 608 204 0041 415 368 23 8064 4471 431 368 205 0021 6921 342 2051 5902

016/555 4836 4022 8312 056 409 636 409 203 0061 286 368 23 8064 4471 431 368 253 0051 6921 342 2051 5902

wolfhgiH

063/023 4836 4022 3061 247 227 755 027 204 0041 805 237 23 8064 4471 431 368 205 0021 6921 342 2051 5902

004 4836 4022 3061 996 808 695 608 204 0041 805 237 23 8064 4471 431 368 205 0021 6921 342 2051 5902

084/044 4836 4022 2281 056 409 636 608 204 0041 415 368 23 8064 4471 431 368 205 0021 6921 342 2051 5902

016/555 4836 4022 8312 056 409 636 409 203 0061 286 368 23 8064 4471 431 368 253 0051 6921 342 2051 5902

Page 11: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

13

Air M

aste

r BC

P

Air Master BCP with mixing module of 2 dampers, upper fresh air damper and bags filter (optional) (mm)

PCBretsaMriA a b c d

snoitcennocciluardyH 052 2231 212 291

IMPORTANT: For optional assemblies which do not appear in this documentation, consult dimensions.

4 Circuit outlet of pool water

3 Circuit inlet of pool water

2 Circuit outlet of boiler hot water

1 Circuit inlet of boiler hot water

Note: See pipe diameters in the hydraulic connections panelNote: All accesses are on the right, in the air flow senseNote: It is required to leave a minimum space to access to condensates draining located on the left, in the sense of air flow

500mm

1700

mm

Keep this spacefree for installationand maintenance

A

M

D E

B

F

G

N

H I

C

J

K

Y

WW UU VV M12

a b

Door switch

Condensates draining

1

4

2

3 c

d

Power supply

NL

W V

500mm

O P

R

S

PCBretsaMriA A B C D E F G H I J K L M N O P R S U V W Y

wolflanimoN

063/023 8218 4022 3061 128 465 615 384 204 0041 805 237 23 8064 4471 431 368 205 0021 6921 342 2051 5902

004 8218 4022 3061 247 227 755 027 204 0041 805 237 23 8064 4471 431 368 205 0021 6921 342 2051 5902

084/044 8218 4022 2281 996 808 695 608 204 0041 415 368 23 8064 4471 431 368 205 0021 6921 342 2051 5902

016/555 8218 4022 8312 056 409 636 409 203 0061 286 368 23 8064 4471 431 368 253 0051 6921 342 2051 5902

wolfhgiH

063/023 8218 4022 3061 247 227 755 027 204 0041 805 237 23 8064 4471 431 368 205 0021 6921 342 2051 5902

004 8218 4022 3061 996 808 695 608 204 0041 805 237 23 8064 4471 431 368 205 0021 6921 342 2051 5902

084/044 8218 4022 2281 056 409 636 608 204 0041 415 368 23 8064 4471 431 368 205 0021 6921 342 2051 5902

016/555 8218 4022 8312 056 409 636 409 203 0061 286 368 23 8064 4471 431 368 253 0051 6921 342 2051 5902

Page 12: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A14

Air Master BCPAir Master BCP with return fan, mixing module with lateral dampers (optional) (mm)

PCBretsaMriA a b c d

snoitcennocciluardyH 052 2231 212 291

IMPORTANT: For optional assemblies which do not appear in this documentation, consult dimensions.

4 Circuit outlet of pool water

3 Circuit inlet of pool water

2 Circuit outlet of boiler hot water

1 Circuit inlet of boiler hot water

Note: See pipe diameters in the hydraulic connections panelNote: All accesses are on the right, in the air flow senseNote: It is required to leave a minimum space to access to condensates draining located on the left, in the sense of air flow

500mm 500mm

2300

mm

Keep this spacefree for installationand maintenance

D E

O

Q R

P

LN

B

F

G

N

A

M

H I

C

J

K

SBST

Y

WW UU VV

M12

a b

Door switch

Condensates draining

1

4

2

3 c

d

Power supply

1200

mm

PCBretsaMriA A B C D E F G H I J K L M N O P Q R S T U V W Y

wolflanimoN

063/023 8218 4022 3061 128 465 615 384 204 0041 805 237 23 8064 4471 3981 497 4262 497 038 4683 6921 342 2051 5902

004 8218 4022 3061 247 227 755 027 204 0041 805 237 23 8064 4471 3981 497 4262 497 038 4683 6921 342 2051 5902

084/044 8218 4022 2281 996 808 695 608 204 0041 415 368 23 8064 4471 5181 498 6852 498 038 4683 6921 342 2051 5902

016/555 8218 4022 8312 056 409 636 409 203 0061 286 368 23 8064 4471 5181 498 6852 498 038 4683 6921 342 2051 5902

wolfhgiH

063/023 8218 4022 3061 247 227 755 027 204 0041 805 237 23 8064 4471 3981 497 4262 497 038 4683 6921 342 2051 5902

004 8218 4022 3061 996 808 695 608 204 0041 805 237 23 8064 4471 3981 497 4262 497 038 4683 6921 342 2051 5902

084/044 8218 4022 2281 056 409 636 608 204 0041 415 368 23 8064 4471 5181 498 6852 498 038 4683 6921 342 2051 5902

016/555 8218 4022 8312 056 409 636 409 203 0061 286 368 23 8064 4471 5181 498 6852 498 038 4683 6921 342 2051 5902

Page 13: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

15

Air M

aste

r BC

P

Air Master BCP with return fan, mixing module with upper dampers (optional) (mm)

PCBretsaMriA a b c d

snoitcennocciluardyH 052 2231 212 291

IMPORTANT: For optional assemblies which do not appear in this documentation, consult dimensions.

4 Circuit outlet of pool water

3 Circuit inlet of pool water

2 Circuit outlet of boiler hot water

1 Circuit inlet of boiler hot water

Note: See pipe diameters in the hydraulic connections panelNote: All accesses are on the right, in the air flow senseNote: It is required to leave a minimum space to access to condensates draining located on the left, in the sense of air flow

500mm 500mm

1700

mm

Keep this spacefree for installation and maintenance

D E

B

F

G

A

M

H I

C

J

K

LN

Y

WW UU VV M12

a b

Door switch

Condensates draining

1

4

2

3 c

d

Power supply

V Z

O

Q RP Q

S

T

PCBretsaMriA A B C D E F G H I J K L M N O P Q R S T U V W Y Z

wolflanimoN

063/023 2658 4022 3061 128 465 615 384 204 0041 805 237 23 8064 4471 8712 0981 568 422 205 0021 6921 342 2051 5902 8391

004 2658 4022 3061 247 227 755 027 204 0041 805 237 23 8064 4471 8712 0981 568 422 205 0021 6921 342 2051 5902 8391

084/044 2658 4022 2281 996 808 695 608 204 0041 415 368 23 8064 4471 8712 0981 568 422 205 0021 6921 342 2051 5902 8391

016/555 2658 4022 8312 056 409 636 409 203 0061 286 368 23 8064 4471 8712 0981 568 422 205 0051 6921 342 2051 5902 8391

wolfhgiH

063/023 2658 4022 3061 247 227 755 027 204 0041 805 237 23 8064 4471 8712 0981 568 422 205 0021 6921 342 2051 5902 8391

004 2658 4022 3061 996 808 695 608 204 0041 805 237 23 8064 4471 8712 0981 568 422 205 0021 6921 342 2051 5902 8391

084/044 2658 4022 2281 056 409 636 608 204 0041 415 368 23 8064 4471 8712 0981 568 422 205 0021 6921 342 2051 5902 8391

016/555 2658 4022 8312 056 409 636 409 203 0061 286 368 23 8064 4471 8712 0981 568 422 205 0051 6921 342 2051 5902 8391

Page 14: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A16

Air Master BCPAir Master BCP, return fan, mixing module with lateral dampers and bags filter (optional) (mm)

PCBretsaMriA a b c d

snoitcennocciluardyH 052 2231 212 291

IMPORTANT: For optional assemblies which do not appear in this documentation, consult dimensions.

4 Circuit outlet of pool water

3 Circuit inlet of pool water

2 Circuit outlet of boiler hot water

1 Circuit inlet of boiler hot water

Note: See pipe diameters in the hydraulic connections panelNote: All accesses are on the right, in the air flow senseNote: It is required to leave a minimum space to access to condensates draining located on the left, in the sense of air flow

500mm 500mm

2300

mm

Keep this spacefree for installationand maintenance

1200

mm

AD E

a b

O

Q R

P

LN

B

F

G

N N

H I

C

Y

J

K

SBST

WW UU VV M12

Door switch

Condensates draining

1

4

2

3 c

d

Power supply

M

PCBretsaMriA A B C D E F G H I J K L M N O P Q R S T U V W Y

wolflanimoN

063/023 2789 4022 3061 128 465 615 384 204 0041 805 237 23 8064 4471 3981 497 4262 497 038 4683 6921 342 2051 5902

004 2789 4022 3061 247 227 755 027 204 0041 805 237 23 8064 4471 3981 497 4262 497 038 4683 6921 342 2051 5902

084/044 2789 4022 2281 996 808 695 608 204 0041 415 368 23 8064 4471 5181 498 6852 498 038 4683 6921 342 2051 5902

016/555 2789 4022 8312 056 409 636 409 203 0061 286 368 23 8064 4471 5181 498 6852 498 038 4683 6921 342 2051 5902

wolfhgiH

063/023 2789 4022 3061 247 227 755 027 204 0041 805 237 23 8064 4471 3981 497 4262 497 038 4683 6921 342 2051 5902

004 2789 4022 3061 996 808 695 608 204 0041 805 237 23 8064 4471 3981 497 4262 497 038 4683 6921 342 2051 5902

084/044 2789 4022 2281 056 409 636 608 204 0041 415 368 23 8064 4471 5181 498 6852 498 038 4683 6921 342 2051 5902

016/555 2789 4022 8312 056 409 636 409 203 0061 286 368 23 8064 4471 5181 498 6852 498 038 4683 6921 342 2051 5902

Page 15: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

17

Air M

aste

r BC

P

Air Master BCP with return fan, mixing module with upper dampers and bags filter (optional) (mm)

PCBretsaMriA a b c d

snoitcennocciluardyH 052 2231 212 291

IMPORTANT: For optional assemblies which do not appear in this documentation, consult dimensions.

4 Circuit outlet of pool water

3 Circuit inlet of pool water

2 Circuit outlet of boiler hot water

1 Circuit inlet of boiler hot water

Note: See pipe diameters in the hydraulic connections panelNote: All accesses are on the right, in the air flow senseNote: It is required to leave a minimum space to access to condensates draining located on the left, in the sense of air flow

500mm 500mm

1700

mm

Keep this space free for installation andmaintenance

D E

B

F

G

A

M

H I

C

J

K

LN

Y

WW UU VV M12

a b

Door switch

Condensates draining

1

4

2

3 c

d

Power supply

V Z

O

Q RP Q

S

T

N

W V

PCBretsaMriA A B C D E F G H I J K L M N O P Q R S T U V W Y Z

wolflanimoN

063/023 60301 4022 3061 128 465 615 384 204 0041 805 237 23 8064 4471 8712 0981 568 422 205 0021 6921 342 2051 5902 8391

004 60301 4022 3061 247 227 755 027 204 0041 805 237 23 8064 4471 8712 0981 568 422 205 0021 6921 342 2051 5902 8391

084/044 60301 4022 2281 996 808 695 608 204 0041 415 368 23 8064 4471 8712 0981 568 422 205 0021 6921 342 2051 5902 8391

016/555 60301 4022 8312 056 409 636 409 203 0061 286 368 23 8064 4471 8712 0981 568 422 205 0051 6921 342 2051 5902 8391

wolfhgiH

063/023 60301 4022 3061 247 227 755 027 204 0041 805 237 23 8064 4471 8712 0981 568 422 205 0021 6921 342 2051 5902 8391

004 60301 4022 3061 996 808 695 608 204 0041 805 237 23 8064 4471 8712 0981 568 422 205 0021 6921 342 2051 5902 8391

084/044 60301 4022 2281 056 409 636 608 204 0041 415 368 23 8064 4471 8712 0981 568 422 205 0021 6921 342 2051 5902 8391

016/555 60301 4022 8312 056 409 636 409 203 0061 286 368 23 8064 4471 8712 0981 568 422 205 0051 6921 342 2051 5902 8391

Page 16: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A18

Air Master BCPPressUre DroPs

n Discharge with nominal flow

n Return with nominal flow (optional)

n Discharge with high flow

n Return with high flow (optional)

NOTE: The pressure drops in the hot water coil and in gravimetric filters have been considered as drops of the standard unit. If the unit includes some of the other optionals, its corresponding drops should be added to those of the standard unit.

0

5

10

15

20

25

30

35

40

45

1280

0

1340

0

1400

0

1460

0

1520

0

1580

0

1640

0

1700

0

1760

0

F7 Bags filter

Mixing box (2 or 3 dampers)

Standard unit

Hot water coil

Air Master BCP-320 Nominal Flow: 16.000 m3/hAvail. Press.: 19,1 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

5

10

15

20

25

30

35

40

45

1920

0

2000

0

2080

0

2160

0

2240

0

2320

0

2400

0

2480

0

2560

0

2640

0

F7 Bags filter

Mixing box (2 or 3 dampers)

Standard unit

Hot water coil

Air Master BCP-320 Nominal Flow: 24.000 m3/hAvail. Pressure: 16,9 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

1

2

3

4

5

1280

0

1340

0

1400

0

1460

0

1520

0

1580

0

1640

0

1700

0

1760

0

Standard unit

Mixing box (3 dampers)

Air Master BCP-320 Nominal Flow: 16.000 m3/hAvail. Press.: 14,7 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

1

2

3

4

5

1920

0

2000

0

2080

0

2160

0

2240

0

2320

0

2400

0

2480

0

2560

0

2640

0

Standard unit

Mixing box (3 dampers)

Air Master BCP-320 Nominal Flow: 24.000 m3/hAvail. Press.: 12,7 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

Page 17: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

19

Air M

aste

r BC

P

n Discharge with nominal flow

n Return with nominal flow (optional)

n Discharge with high flow

n Return with high flow (optional)

NOTE: The pressure drops in the hot water coil and in gravimetric filters have been considered as drops of the standard unit. If the unit includes some of the other optionals, its corresponding drops should be added to those of the standard unit.

0

5

10

15

20

25

30

35

40

45

1440

0

1500

0

1560

0

1620

0

1680

0

1740

0

1800

0

1860

0

1920

0

1980

0

F7 bags filter

Mixing box (2 or 3 dampers)

Standard unit

Hot water coil

Air Master BCP-360 Nominal Flow: 18.000 m3/hAvailable Pressure: 17,5 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

5

10

15

20

25

30

35

40

45

2160

0

2260

0

2360

0

2460

0

2560

0

2660

0

2760

0

2860

0

2960

0

F7 Bags filter

Mixing box (2 or 3 dampers)

Standard unit

Hot water coil

Air Master BCP-360 Nominal Flow: 27.000 m3/hAvail. Press.: 21,9 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

1

2

3

4

5

1440

0

1500

0

1560

0

1620

0

1680

0

1740

0

1800

0

1860

0

1920

0

1980

0

Standard unit

Mixing box (3 dampers)

Air Master BCP-360 Nominal Flow: 18.000 m3/hAvail. Press.: 13,9 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

1

2

3

4

5

2160

0

2260

0

2360

0

2460

0

2560

0

2660

0

2760

0

2860

0

2960

0

Standard unit

Mixing box (3 dampers)

Air Master BCP-360 Nominal Flow: 27.000 m3/hAvail. Press.: 16,0 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

Page 18: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A20

Air Master BCP

0

5

10

15

20

25

30

35

40

45

1600

0

1660

0

1720

0

1780

0

1840

0

1900

0

1960

0

2020

0

2080

0

2140

0

2200

0

Bags filter F7

Mixing box (2 or 3 dampers)

Standard unit

Hot water coil

Air Master BCP-400 Nominal Flow: 20.000 m3/hAvail. Press.: 19,7 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

5

10

15

20

25

30

35

40

45

2400

0

2500

0

2600

0

2700

0

2800

0

2900

0

3000

0

3100

0

3200

0

3300

0

Bags filter F7

Mixing box (2 or 3 dampers)

Standard unit

Hot water coil

Air Master BCP-400 Nominal Flow: 30.000 m3/hAvail. Press.: 18,9 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

1

2

3

4

5

2400

0

2500

0

2600

0

2700

0

2800

0

2900

0

3000

0

3100

0

3200

0

3300

0

Standard unit

Mixing box (3 dampers)

Air Master BCP-400 Nominal Flow: 30.000 m3/hAvail. Press.: 10,5 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

1

2

3

4

5

1600

0

1660

0

1720

0

1780

0

1840

0

1900

0

1960

0

2020

0

2080

0

2140

0

2200

0

Standard unit

Mixing box (3 dampers)

Air Master BCP-400 Nominal Flow: 20.000 m3/hAvail.Press.: 15,7 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (m

m.W

.G.)

n Discharge with nominal flow

n Return with nominal flow (optional)

n Discharge with high flow

n Return with high flow (optional)

NOTE: The pressure drops in the hot water coil and in gravimetric filters have been considered as drops of the standard unit. If the unit includes some of the other optionals, its corresponding drops should be added to those of the standard unit.

Page 19: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

21

Air M

aste

r BC

P

0

5

10

15

20

25

30

35

40

45

1760

0

1820

0

1880

0

1940

0

2000

0

2060

0

2120

0

2180

0

2240

0

2300

0

2360

0

2420

0

Bags filter F7

Mixing box (2 or 3 dampers)

Standard unit

Hot water coil

Air Master BCP-440 Nominal Flow: 22.000 m3/hAvail. Press.: 16,6 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

5

10

15

20

25

30

35

40

45

2700

0

2800

0

2900

0

3000

0

3100

0

3200

0

3300

0

3400

0

3500

0

3600

0

Bags filter F7

Mixing box (2 or 3 dampers)

Standard unit

Hot water coil

Air Master BCP-440 Nominal Flow: 33.000 m3/hAvail. Press.: 15,8 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

1

2

3

4

5

1760

0

1820

0

1880

0

1940

0

2000

0

2060

0

2120

0

2180

0

2240

0

2300

0

2360

0

2420

0

Standard unit

Mixing box (3 dampers)

Air Master BCP-440 Nominal Flow: 22.000 m3/hAvail. Press.: 14,4 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

1

2

3

4

5

2700

0

2800

0

2900

0

3000

0

3100

0

3200

0

3300

0

3400

0

3500

0

3600

0

Standard unit

Mixing box (3 dampers)

Air Master BCP-440 Nominal Flow: 33.000 m3/hAvail. Press.: 13,5 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

n Discharge with nominal flow

n Return with nominal flow (optional)

n Discharge with high flow

n Return with high flow (optional)

NOTE: The pressure drops in the hot water coil and in gravimetric filters have been considered as drops of the standard unit. If the unit includes some of the other optionals, its corresponding drops should be added to those of the standard unit.

Page 20: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A22

Air Master BCP

0

5

10

15

20

25

30

35

40

45

2900

0

3000

0

3100

0

3200

0

3300

0

3400

0

3500

0

3600

0

3700

0

3800

0

3900

0

Bags filter F7

Mixing box (2 or 3 dampers)

Standard unit

Hot water coil

Air Master BCP-480 Nominal Flow: 36.000 m3/hAvail. Press.: 18,2 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

5

10

15

20

25

30

35

40

45

1920

0

2000

0

2080

0

2160

0

2240

0

2320

0

2400

0

2480

0

2560

0

2640

0

Bags filter F7

Mixing box (2 or 3 dampers)

Standard unit

Hot water coil

Air Master BCP-480 Nominal Flow: 24.000 m3/hAvail. Press.: 17,2 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

1

2

3

4

5

2900

0

3000

0

3100

0

3200

0

3300

0

3400

0

3500

0

3600

0

3700

0

3800

0

3900

0

Standard unit

Mixing box (3 dampers)

Air Master BCP-480 Nominal Flow: 36.000 m3/hAvail. Press.: 9,8 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

1

2

3

4

5

1920

0

2000

0

2080

0

2160

0

2240

0

2320

0

2400

0

2480

0

2560

0

2640

0

Standard unit

Mixing box (3 dampers)

Air Master BCP-480 Nominal Flow: 24.000 m3/hAvailable Pressure: 14,4 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

n Discharge with nominal flow

n Return with nominal flow (optional)

n Discharge with high flow

n Return with high flow (optional)

NOTE: The pressure drops in the hot water coil and in gravimetric filters have been considered as drops of the standard unit. If the unit includes some of the other optionals, its corresponding drops should be added to those of the standard unit.

Page 21: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

23

Air M

aste

r BC

P

0

1

2

3

4

5

3400

0

3500

0

3600

0

3700

0

3800

0

3900

0

4000

0

4100

0

4200

0

4300

0

4400

0

4500

0

Standard unit

Mixing box (3 dampers)

Air Master BCP-555 Nominal Flow: 41.625 m3/hAvail. Press.: 20,8 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

1

2

3

4

5

2220

0

2300

0

2380

0

2460

0

2540

0

2620

0

2700

0

2780

0

2860

0

2940

0

3020

0

Standard unit

Mixing box (3 dampers)

Air Master BCP-555 Nominal Flow: 27.750 m3/hAvail. Press.: 16,0 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

5

10

15

20

25

30

35

40

45

3400

0

3500

0

3600

0

3700

0

3800

0

3900

0

4000

0

4100

0

4200

0

4300

0

4400

0

4500

0

Bags filter F7

Mixing box (2 or 3 dampers)

Standard unit

Hot water coil

Air Master BCP-555 Nominal flow: 41.625 m3/hAvail. Press.: 17,4 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

5

10

15

20

25

30

35

40

45

2220

0

2300

0

2380

0

2460

0

2540

0

2620

0

2700

0

2780

0

2860

0

2940

0

3020

0

Bags filter F7

Mixing box (2 or 3 dampers)

Standard unit

Hot water coil

Air Master BCP-555 Nominal Flow: 27.750 m3/hAvail. Press.: 16,5 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

n Discharge with nominal flow

n Return with nominal flow (optional)

n Discharge with high flow

n Return with high flow (optional)

NOTE: The pressure drops in the hot water coil and in gravimetric filters have been considered as drops of the standard unit. If the unit includes some of the other optionals, its corresponding drops should be added to those of the standard unit.

Page 22: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A24

Air Master BCP

0

5

10

15

20

25

30

35

40

45

3500

0

3600

0

3700

0

3800

0

3900

0

4000

0

4100

0

4200

0

4300

0

4400

0

4500

0

4600

0

4700

0

Bags filter F7

Mixing box (2 or 3 dampers)

Standard unit

Hot water coil

Air Master BCP-610 Nominal Flow: 43.000 m3/hAvail. Press.: 19,4 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

5

10

15

20

25

30

35

40

45

2400

0

2500

0

2600

0

2700

0

2800

0

2900

0

3000

0

3100

0

3200

0

3300

0

Bags filter F7

Mixing box (2 or 3 dampers)

Standard unit

Hot water coil

Air Master BCP-610 Nominal Flow: 30.000 m3/hAvail. Press.: 18,8 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

1

2

3

4

5

3500

0

3600

0

3700

0

3800

0

3900

0

4000

0

4100

0

4200

0

4300

0

4400

0

4500

0

4600

0

4700

0

Standard unit

Mixing box (3 dampers)

Air Master BCP-610 Nominal Flow: 43.000 m3/hAvail. Press.: 22,3 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

0

1

2

3

4

5

2400

0

2500

0

2600

0

2700

0

2800

0

2900

0

3000

0

3100

0

3200

0

3300

0

Standard unit

Mixing box (3 dampers)

Air Master BCP-610 Nominal Flow: 30.000 m3/hAvail. Press.: 14,2 mm.W.G.

Flow (m3/h)

Pre

ssur

e dr

op (

mm

.W.G

.)

n Discharge with nominal flow

n Return with nominal flow (optional)

n Discharge with high flow

n Return with high flow (optional)

NOTE: The pressure drops in the hot water coil and in gravimetric filters have been considered as drops of the standard unit. If the unit includes some of the other optionals, its corresponding drops should be added to those of the standard unit.

Page 23: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

25

Air M

aste

r BC

P

fans characteristics n Discharge fan with nominal flow

n Return fan with nominal flow (optional)

NOTE: The graphic point shows the operating nominal point. The curve that passes through this point is the nominal installation curve (this curve shows the aspect of other possible curves of installation).

The motor to select is that whose curve is above the operating point.

If there is a motor change, consult the price supplement.

0

5

10

15

20

25

30

35

40

45

50

12800 13400 14000 14600 15200 15800 16400 17000 17600

7,5 kW

510 rpm

570 rpm

650 rpm

730 rpm

5,5 kW

450 rpm

4 kW

820 rpm 850 rpm

3 kW

Air Master BCP-320 Nominal Flow: 16.000 m3/hAvail. Press.: 19,1 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

0

5

10

15

20

25

30

12800 13300 13800 14300 14800 15300 15800 16300 16800 17300

650 rpm

510 rpm

2,2 kW

3 kW450 rpm

4 kW

570 rpm

1,5 kW

Air Master BCP-320 Nominal Flow: 16.000 m3/hAvail. Press.: 14,7 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

Page 24: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A26

Air Master BCP

n Discharge fan with high flow

n Return fan with high flow (optional)

NOTE: The graphic point shows the operating nominal point. The curve that passes through this point is the nominal installation curve (this curve shows the aspect of other possible curves of installation).

The motor to select is that whose curve is above the operating point.

If there is a motor change, consult the price supplement.

0

5

10

15

20

25

30

19200 20200 21200 22200 23200 24200 25200 26200

481 rpm

510 rpm 542 rpm

510 rpm

5,5 kW

4 kW

403 rpm

428 rpm

452 rpm

350 rpm3 kW

Air Master BCP-320 Nominal Flow: 24.000 m3/hAvail. Press.: 12,7 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

0

5

10

15

20

25

30

19200 20200 21200 22200 23200 24200 25200 26200

481 rpm

510 rpm 542 rpm

510 rpm

5,5 kW

4 kW

403 rpm

428 rpm

452 rpm

350 rpm3 kW

Air Master BCP-320 Nominal Flow: 24.000 m3/hAvail. Press.: 12,7 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

Page 25: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

27

Air M

aste

r BC

P

0

5

10

15

20

25

30

35

40

45

50

14400 15000 15600 16200 16800 17400 18000 18600 19200 19800

3 kW

510 rpm

570 rpm

650 rpm

730 rpm

7,5 kW

4 kW

820 rpm

5,5 kW

450 rpm

Air Master BCP-360 Nominal Flow: 18.000 m3/hAvail. Press.: 17,5 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

0

5

10

15

20

25

30

14400 15400 16400 17400 18400 19400

650 rpm

510 rpm

2,2 kW 3 kW

450 rpm

4 kW

570 rpm

1,5 kW

730 rpm

Air Master BCP-360 Nominal Flow: 18.000 m3/hAvail. Press.: 13,9 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

n Discharge fan with nominal flow

n Return fan with nominal flow (optional)

NOTE: The graphic point shows the operating nominal point. The curve that passes through this point is the nominal installation curve (this curve shows the aspect of other possible curves of installation).

The motor to select is that whose curve is above the operating point.

If there is a motor change, consult the price supplement.

Page 26: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A28

Air Master BCP

0

5

10

15

20

25

30

35

40

45

50

21600 22700 23800 24900 26000 27100 28200 29300

11 kW

510 rpm

570 rpm

650 rpm

730 rpm

7,5 kW4 kW 5,5 kW

850 rpm

15 kW

Air Master BCP-360 Nominal Flow: 27.000 m3/hAvail. Press.: 21,9 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

820 rpm

0

5

10

15

20

25

30

21600 22600 23600 24600 25600 26600 27600 28600 29600

481 rpm

510 rpm

542 rpm

7,5 kW

403 rpm

452 rpm

574 rpm

3 kW

4 kW

5,5 kW

428 rpm

Air Master BCP-360 Nominal flow: 27.000 m3/hAvail. Press.: 16,0 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

n Discharge fan with high flow

n Return fan with high flow (optional)

NOTE: The graphic point shows the operating nominal point. The curve that passes through this point is the nominal installation curve (this curve shows the aspect of other possible curves of installation).

The motor to select is that whose curve is above the operating point.

If there is a motor change, consult the price supplement.

Page 27: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

29

Air M

aste

r BC

P

0

5

10

15

20

25

30

35

40

45

50

16000 17100 18200 19300 20400 21500

5,5 kW

510 rpm

570 rpm

650 rpm

730 rpm

7,5 kW

450 rpm4 kW

820 rpm

Air Master BCP-400 Nominal Flow: 20.000 m3/hAvail. Pressure: 19,7 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

0

5

10

15

20

25

30

16000 17000 18000 19000 20000 21000 22000

428 rpm

452 rpm

481 rpm

510 rpm

2,2 kW1,5 kW

3 kW

4 kW

300 rpm

350 rpm

403 rpm

Air Master BCP-400 Nominal Flow: 20.000 m3/hAvail. Press.: 15,7 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

n Discharge fan with nominal flow

n Return fan with nominal flow (optional)

NOTE: The graphic point shows the operating nominal point. The curve that passes through this point is the nominal installation curve (this curve shows the aspect of other possible curves of installation).

The motor to select is that whose curve is above the operating point.

If there is a motor change, consult the price supplement.

Page 28: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A30

Air Master BCP

0

5

10

15

20

25

30

35

40

45

50

24000 25000 26000 27000 28000 29000 30000 31000 32000 33000

7,5 kW

481 rpm

452 rpm

403 rpm

428 rpm

5,5 kW4 kW

11 kW

722 rpm683 rpm

644 rpm

609 rpm

574 rpm

542 rpm

510 rpm

15 kW

Air Master BCP-400 Nominal Flow: 30.000 m3/hAvail. Press.: 18,9 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

0

5

10

15

20

25

30

24000 25000 26000 27000 28000 29000 30000 31000 32000 33000

481 rpm

510 rpm

542 rpm

7,5 kW

609 rpm

452 rpm

574 rpm

4 kW

5,5 kW

428 rpm

644 rpm

Air Master BCP-400 Nominal Flow: 30.000 m3/hAvail. Press.: 10,5 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

n Discharge fan with high flow

n Return fan with high flow (optional)

NOTE: The graphic point shows the operating nominal point. The curve that passes through this point is the nominal installation curve (this curve shows the aspect of other possible curves of installation).

The motor to select is that whose curve is above the operating point.

If there is a motor change, consult the price supplement.

Page 29: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

31

Air M

aste

r BC

P

0

5

10

15

20

25

30

35

40

45

50

17600 18500 19400 20300 21200 22100 23000 23900

4 kW

730 rpm

650 rpm

570 rpm

510 rpm

450 rpm

5,5 kW

7,5 kW

11 kW

Air Master BCP-440 Nominal Flow: 22.000 m3/hAvail. Press.: 16,6 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

0

5

10

15

20

25

30

17600 18600 19600 20600 21600 22600 23600

3 kW

4 kW

304 rpm320 rpm

341 rpm

359 rpm

382 rpm

403 rpm

428 rpm

250 rpm

280 rpm

2,2 kW

1,5 kW

Air Master BCP-440 Nominal Flow: 22.000 m3/hAvail. Pressure: 14,4 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

n Discharge fan with nominal flow

n Return fan with nominal flow (optional)

NOTE: The graphic point shows the operating nominal point. The curve that passes through this point is the nominal installation curve (this curve shows the aspect of other possible curves of installation).

The motor to select is that whose curve is above the operating point.

If there is a motor change, consult the price supplement.

Page 30: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A32

Air Master BCP

0

5

10

15

20

25

30

35

40

45

50

26400 27400 28400 29400 30400 31400 32400 33400 34400 35400

7,5 kW5,5 kW

11 kW

362 rpm

385 rpm

343 rpm

405 rpm

458 rpm

486 rpm

519 rpm

548 rpm

585 rpm620 rpm

431 rpm

4 kW

15 kW

Air Master BCP-440 Nominal Flow: 33.000 m3/hAvail. Press.: 15,8 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

0

5

10

15

20

25

30

26400 27400 28400 29400 30400 31400 32400 33400 34400 35400

7,5 kW

4 kW304 rpm

320 rpm

341 rpm

359 rpm

382 rpm

403 rpm

428 rpm

452 rpm 481 rpm

5,5 kW

Air Master BCP-440 Nominal Flow: 33.000 m3/hAvail. Press.: 13,5 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

n Discharge fan with high flow

n Return fan with high flow (optional)

NOTE: The graphic point shows the operating nominal point. The curve that passes through this point is the nominal installation curve (this curve shows the aspect of other possible curves of installation).

The motor to select is that whose curve is above the operating point.

If there is a motor change, consult the price supplement.

Page 31: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

33

Air M

aste

r BC

P

0

5

10

15

20

25

30

35

40

45

50

19200 20100 21000 21900 22800 23700 24600 25500 26400

7,5 kW

650 rpm

570 rpm

510 rpm

450 rpm

5,5 kW4 kW

11 kW

Air Master BCP-480 Nominal Flow: 24.000 m3/hAvail. Press.: 17,2 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

0

5

10

15

20

25

30

19200 20200 21200 22200 23200 24200 25200 26200

3 kW

4 kW

304 rpm320 rpm

341 rpm

359 rpm

382 rpm

403 rpm

428 rpm

280 rpm

2,2 kW

1,5 kW

250 rpm

452 rpm

Air Master BCP-480 Nominal Flow: 24.000 m3/hAvail. Press.: 14,4 mm.W.G.Avail.Press. (mm.W.G.)

Flow (m3/h)

n Discharge fan with nominal flow

n Return fan with nominal flow (optional)

NOTE: The graphic point shows the operating nominal point. The curve that passes through this point is the nominal installation curve (this curve shows the aspect of other possible curves of installation).

The motor to select is that whose curve is above the operating point.

If there is a motor change, consult the price supplement.

Page 32: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A34

Air Master BCP

0

5

10

15

20

25

30

35

40

45

50

28800 29800 30800 31800 32800 33800 34800 35800 36800 37800 38800

11 kW

450 rpm

570 rpm

510 rpm

5,5 kW 7,5 kW

650 rpm

15 kW

18,5 kW

Air Master BCP-480 Nominal Flow: 36.000 m3/hAvail. Press.: 18,2 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

0

5

10

15

20

25

30

28800 30800 32800 34800 36800 38800

7,5 kW4 kW

320 rpm

341 rpm

359 rpm

382 rpm

403 rpm

428 rpm

452 rpm 481 rpm

5,5 kW

11 kW

Air Master BCP-480 Nominal Flow: 36.000 m3/hAvail. Press: 9,8 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

n Discharge fan with high flow

n Return fan with high flow (optional)

NOTE: The graphic point shows the operating nominal point. The curve that passes through this point is the nominal installation curve (this curve shows the aspect of other possible curves of installation).

The motor to select is that whose curve is above the operating point.

If there is a motor change, consult the price supplement.

Page 33: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

35

Air M

aste

r BC

P

0

5

10

15

20

25

30

35

40

45

50

22200 23200 24200 25200 26200 27200 28200 29200 30200

5,5 kW

450 rpm

600 rpm

500 rpm

3 kW 4 kW

400 rpm

11 kW

7,5 kW

300 rpm

350 rpm

Air Master BCP-555 Nominal Flow: 27.775 m3/hAvail. Press.: 16,5 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

0

5

10

15

20

25

30

22200 23200 24200 25200 26200 27200 28200 29200 30200

343 rpm

2,2 kW

3 kW

4 kW

362 rpm

385 rpm

343 rpm

405 rpm

300 rpm

250 rpm

Air Master BCP-555 Nominal Flow: 27.775 m3/hAvail. Press.: 16,0 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

n Discharge fan with nominal flow

n Return fan with nominal flow (optional)

NOTE: The graphic point shows the operating nominal point. The curve that passes through this point is the nominal installation curve (this curve shows the aspect of other possible curves of installation).

The motor to select is that whose curve is above the operating point.

If there is a motor change, consult the price supplement.

Page 34: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A36

Air Master BCP

0

5

10

15

20

25

30

35

40

45

50

33300 34300 35300 36300 37300 38300 39300 40300 41300 42300 43300 44300 45300

11 kW

450 rpm

570 rpm

510 rpm

5,5 kW 7,5 kW

15 kW

650 rpm

18,5 kW

Air Master BCP-555 Nominal Flow: 41.625 m3/hAvail. Press.: 17,4 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

0

5

10

15

20

25

30

33300 35300 37300 39300 41300 43300 45300

343 rpm

5,5 kW

4 kW

7,5 kW

362 rpm

385 rpm

405 rpm

300 rpm

11 kW

431 rpm 458 rpm

Air Master BCP-555 Nominal Flow: 41.625 m3/hAvail. Press.: 20,8 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

n Discharge fan with high flow

n Return fan with high flow (optional)

NOTE: The graphic point shows the operating nominal point. The curve that passes through this point is the nominal installation curve (this curve shows the aspect of other possible curves of installation).

The motor to select is that whose curve is above the operating point.

If there is a motor change, consult the price supplement.

Page 35: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

37

Air M

aste

r BC

P

0

5

10

15

20

25

30

35

40

45

50

24000 25000 26000 27000 28000 29000 30000 31000 32000 33000

7,5 kW

450 rpm

600 rpm

500 rpm

4 kW 5,5 kW

400 rpm

11 kW

350 rpm

15 kW

Air Master BCP-610 Nominal Flow: 30.000 m3/hAvail. Press.: 18,8 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

0

5

10

15

20

25

30

24000 25000 26000 27000 28000 29000 30000 31000 32000 33000

343 rpm

3 kW

4 kW

5,5 kW

362 rpm

385 rpm405 rpm

300 rpm

250 rpm

Air Master BCP-610 Nominal Flow: 30.000 m3/hAvail. Press.: 14,2 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

n Discharge fan with nominal flow

n Return fan with nominal flow (optional)

NOTE: The graphic point shows the operating nominal point. The curve that passes through this point is the nominal installation curve (this curve shows the aspect of other possible curves of installation).

The motor to select is that whose curve is above the operating point.

If there is a motor change, consult the price supplement.

Page 36: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

Pool air handling units

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A38

Air Master BCP

0

5

10

15

20

25

30

35

40

45

50

34400 36400 38400 40400 42400 44400 46400

11 kW400 rpm

600 rpm

500 rpm

7,5 kW 15 kW

700 rpm22 Kw

450 rpm

18,5 kW

Air Master BCP-610 Nominal Flow: 43.000 m3/hAvail. Press.: 19,4 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

0

5

10

15

20

25

30

34400 36400 38400 40400 42400 44400 46400

343 rpm

5,5 kW

4 kW

7,5 kW

362 rpm

385 rpm

405 rpm

300 rpm

11 kW

431 rpm 458 rpm

Air Master BCP-610 Nominal Flow: 43.000 m3/hAvail. Press.: 25,1 mm.W.G.Avail. Press. (mm.W.G.)

Flow (m3/h)

n Discharge fan with high flow

n Return fan with high flow (optional)

NOTE: The graphic point shows the operating nominal point. The curve that passes through this point is the nominal installation curve (this curve shows the aspect of other possible curves of installation).

The motor to select is that whose curve is above the operating point.

If there is a motor change, consult the price supplement.

Page 37: Air Master BCP - CIAT UK · PDF fileAir Master BCP DescriPtion PrinciPle ... Nominal air flow ... Å Climate warming potential of one kg of greenhouse-effect fluored gas relative to

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.651 A

Pool air handling units

39

Air M

aste

r BC

P

assembly recommenDations

LocationAir handling units Air Master BCP Series are indoor or outdoor units (optional).

A free space all around the unit should be kept (consult dimensions schemes), for maintenance and normal operation.

Mind special care on the location of the unit, selecting a suitable place according to the environment requirements (place, noise projection, etc.) and only accessible for authorized persons.

Avoid specially the location of units in those places frequented by under 14 years old people. If needed a barrier should be placed in order to protect the equipment from unathorized personnel.

All the units are tested when manufactured and have complete refrigerant load.

Hydraulic connections

Provide the accessories necessary on each hydraulic circuit (expansion vessel, air vents, safety valves, shut-off valves next to components which need maintenance, etc.).

Flexible couplings are recommended between the unit for connecting pipework to the unit, in order to avoid possible transmission of vibrations or stress in the unit and the lines. These couplings are compulsory when the unit is mounted on a frame or on antivibratory supports.

Respect the water flow direction mentioned on the unit or on dimensions schemes.

A water mesh filter is compulsory to be placed at the inlet of pool pump (for particles of Ø > 1 mm), in order to avoid the soiling of the unit hydraulic circuit. A good maintenance of this filter will avoid corrosion problems in the plates exchanger, and it will improve the heat efficiency of the unit. Not fulfill this recommendation could make useless the plates exchanger of the unit.

After a long shutdown of the unit, it is recommended to fill up the hydrau-lic circuit of the exchanger completely with distilled water. Leave the exchanger filled with no flow water or empty may cause corrosion problems in the plates of the exchanger.

Electrical connections

Required electrical connections are indicated in the electrical diagram included within the unit.

These connections follow the current regulations. The equipment has a complete electrical panel, only the main power supply should be installed (protections should be provided by the installer: main switch, differential, etc.).

Check that the power supply corresponds to the voltage listed on the name plate and that it keeps constant.

Start-up

Some problems can appear when starting-up the units, many of them due to the starting-up conditions:

• Insufficient water flow. Too high temperature differences between water inlet and outlet, due to:

- Insufficient trap.

- Small water circulation pump or function on the wrong direction.

- Other situations that block the right water flow.

• Recirculation of air caused by any obstacle in the intake or in the discharge of this.

Before starting-up the unit, to avoid these problems, check the electrical and hydraulic connections, verify the right operation of the pool water circulation pump, the filling and purging of hydraulic circuit, etc.