U.S. AIR FORCE MUNITIONS FACILITIES

STANDARDS GUIDE

Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

31 May 2004

CONTRACT NUMBER: F41624-00-D-8028 Task Order 0217

Prepared By: URS Group, Inc.

7720 North 16th Street, Suite 100 Phoenix, AZ 85020

ARCHIVED

Page 3: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

ARCHIVED

Page 4: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

TABLE OF CONTENTS

Munitions Facilities Assessment Checklists i

INTRODUCTION PURPOSE AND SCOPE .................................................................................................................... 1-1 APPROACH .................................................................................................................................... 1-1

Maintenance Facilities ..................................................................................................... 1-2 Storage Facilities.............................................................................................................. 1-2 Transportation Facilities .................................................................................................. 1-2 Administration Facilities.................................................................................................. 1-2

ARCHIVED

Page 5: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

ARCHIVED

Page 6: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

INTRODUCTION

Munitions Facilities Assessment Checklists 1

P u r p o s e a n d S c o p e

This volume of the Munitions Guide provides a facility assessment checklist for each of the 21 Civil Engineer Real Property Category Codes (Cat Codes) identified in Volume I of this guide.

The facility assessment checklists serve multiple purposes. The checklists can be used to evaluate the condition of existing facilities and compare them against the standards contained in this document. These checklists may also be used to assist in the planning process for new construction. On the checklists, additional space is provided after each component to add items/features that may be unique to a local facility. Potential users of the assessment checklists include munitions, civil engineering, safety, and security forces agencies. The checklists are easily downloaded and provide a standardized format for munitions facilities condition assessments.

A p p r o a c h

The objective of this process is to collect data on facility conditions, assess deficiencies, and evaluate and rank local needs to assist in assigning priorities for facility requirements. Some of the elements included in the checklists are facility structure, utilities, security, pavements, and explosives safety. The list of prioritized projects will assist in the formulation of the capital improvements plan for local munitions facilities.

The sequence of checklists follows the same philosophy as Volume I. That is, the 21 Cat Codes for munitions facilities are divided into four classes. The munitions facilities in each class are listed below by Cat Code. Abbreviations and acronyms are not defined on the checklists. Please refer to Volume I, Chapter 5, “References, Forms, Abbreviations and Acronyms, and Terms.”

Assessment Checklist Application

As a first use of thesechecklists, HQ USAF/ILMW initiated a globaleffort in FY03 to develop acapital improvement planto improve the overallcondition of munitionssupport infrastructure atAir Force, Air NationalGuard, and Air ForceReserve Commandinstallations worldwide. ARCHIV

ED

Page 7: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

30 April 2004

Munitions Facilities Assessment Checklists 2

Maintenance Facilities

171-875 Munitions Loading Crew Training Facility

212-212 Missile Assembly Shop/Integrated Maintenance Facility (IMF)

212-213 Tactical Missile/Glide Weapons Maintenance Shop

215-552 Weapons and Release Systems Shop

215-582 Surveillance and Inspection Shop

216-642 Conventional Munitions Shop

218-712 Aircraft Support Equipment Shop/Storage Facility (Aerospace Ground Equipment (AGE) Facility) – Used for Munitions Support Equipment Maintenance

Storage Facilities

422-253 Multi-cubicle Magazine Storage

422-256 Rocket Check Out and Assembly Storage

422-257 Segregated Magazine Storage

422-258 Above Ground Magazine Storage

422-264 Storage Igloo (Earth-covered Magazine)

422-265 Inert Spares Storage

422-271 Module Barricaded Storage

422-275 Ancillary Explosives Facility (Classification Yards, Holding Yard, Inspection Station, Interchange Yard, Loading Dock, Ready Explosives Facility, and Bomb Preload Station/Munitions Assembly Conveyor (MAC) pad)

Transportation Facilities

116-662 Pad, Dangerous Cargo

422-277 Flight Line Munitions Holding Point

851-147 Roads (Streets) – Primary and Alternate Explosives Movement Routes

852-261 Vehicle Parking Operations – Used for Munitions Sub Pool Parking

890-158 Load and Unload Platform (Railhead) – Used for Munitions Operations

Administration Facilities

610-144 Munitions Administration Facility

ARCHIVED

Page 8: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

ARCHIVED

Page 9: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

5.1 2 3

6.

Remarks

Facility may need high security hasps and an intrusion detection system.

If applicable, provide protection from propagating explosions from the flight line,

Remarks

*Does the training areas' size and shape meet mission needs?

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*Are there any safety or security write-ups on the facility from the latest inspections?*Does the facility user have the site plan or license available?

Remarks

3

Work Stoppage/Life-Safety Hazard

1 2 3

Remarks

4.or in a covered space such as a dock or hangar.Training is conducted in a classroom, outdoor covered aircraft parking area,

3Constructed of steel, brick, or concrete material.3.

*Does location of facility detract from mission performance?

Remarks

II.

*Does the facility design allow for known future mission changes?

*Operating space to meet training needs to allow for safe clearances around aircraft during handling of munitions.

Doesn't Meet

*Classroom size dependent upon number of trainees and amount of training aids required.

Meets

*Adequate space for training aircraft and respective support equipment.

Facility Purpose: This facility provides training for munitions loading crews to acquire and maintain their required proficiency.Facility Components

Mission RequirementsAssess the overall condition of the facility with respect to mission impact.

Sq Footage Year Built Date Last Inspection

Remarks

Meets Does Not Meet*Are there any outstanding AF Forms 332?*Does the base master plan reflect the current facility category code?

FACILITIES ASSESSMENT CHECKLISTCategory Code 171-875 -- Munitions Loading Crew Training Facility

Installation Name Location Facility Bldg NumberInsp. Date MAJCOM

Mission Design Requirements Design Requirements Mission Impact**

1

1. Space Requirements.

*Storage space for storing training aids, training munitions, and support equipment .

3

2

1 2 3

1 2

Remarks

2. Apron for dock or hangar must permit safe operation of handling equipment and movement of training aircraft.

1 2

1

ARCHIVED

Page 10: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

Facility must have:

9.1 2 3

III.

1. Explosives Safety: Criteria:

1 2 3

Walls: Criteria:

*Free of leaks.

Doors: Criteria:

*Serviceable ramps to traverse hangar door thresholds available (if required).

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*No signs of failure, separation, or curling.

*Doors swing/roll freely and fit in jambs.*Locks and security hasps are in good condition.

1 2 3

*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements.

*Grounding -- A means to dissipate static electricity buildup is installed; static bonds and grounds are tested for resistance and continuity; and records are on hand as per AFI 32-1065.

*Placards -- Explosives limits and fire/chemical symbols are displayed. *General -- Facility has good drainage and is vermin resistant.

*Latrine facilities.

Facility Conditions General Conditions Mission Impact**Satisfactory Unsatisfactory

1

Meets Doesn't MeetMission Impact**

*Windows -- Made of blast-resistant material if within the explosives clear zone.

*Interior -- Structural members and cross bracing are free from deterioration, adequate soundproofing insulation installed, caulking around wall penetrations watertight, and there are no unauthorized attachments that may compromise the design function.

1 2 3

Remarks

Design Requirements

Remarks

*Overhead doors must raise and lower smoothly, and can be locked in place.

4.

*Safety mechanisms are in place to prevent accidental or inadvertent closing.

1 2 3

Remarks

Roof: (Circle One) Shingle Metal Gravel Rolled Frangible Concrete Criteria:

3.

*Attachments are secure.

Remarks

*Exterior -- Clean, intact, and free from damage. Paint and caulking are in good condition and water tight.

2.

Remarks

8. Facility must have a serviceable lightning protection system as required by NFPA 780, Chapter 3.

2 3

3

Remarks

7.

Mission Design Requirements (Continued)

*Supply, tool, and equipment room.

Remarks

*Inspections -- Annual weapons safety, ground safety, and facility inspections are performed.

Facility must be constructed with DDESB approval if located within the explosives clear zone.

*Siting Requirements --Facility may be sited or licensed in accordance with DoD 6055.9 STD and AFMAN 91-201. Any exceptions are properly identified and risk assessments are performed.

1 2

*Ready room with personnel lockers available.

*Minimum 1,500 sq. ft (139 m2) administrative area.

2

ARCHIVED

Page 11: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Floors: Criteria:

Ceiling : Criteria:

HVAC: Criteria:

*Filters are clean.

Facility Electrical: Criteria: *All wiring is in conduit.

Remarks

*Junction boxes are spark-proof and watertight.

Work Stoppage/Life-Safety Hazard

Facility Conditions (Continued) General ConditionsUnsatisfactorySatisfactory

Mission Impact**

*Start/stop control switch is properly mounted.*Damper controls and motors are in good working order.

*Ground devices are free of corrosion.*Support equipment may have special electrical requirements.

Remarks

8. 1 2

*Wiring is in conduits and insulation is intact.

*Stand-alone equipment (boiler and chiller units) is well maintained.

*Electrical control and switchgear is properly tagged, labeled, and housed.

1

*Switch box plates are water and dust tight.

*Transfer switch and breaker panels are operable.*Generator and back-up power is available and in good repair.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*If required, appropriate surge protection devices will be installed.

*May need special power requirements for test equipment.*Switches and breakers contain lightning arrestors and surge protectors.*No hazardous materials [polychlorinated biphenyls (PCBs)] are present.*Transformers are free of leaks, are closed, and are weather-proof.

7.

*Switches are in spark-proof enclosures.

*Central equipment (heat exchangers, pumps, and fans) is clean and well maintained.*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.

1 2 3

3

2 3

Remarks

6.

*No obvious hazards to personnel on the floor.*No visible damage, watermarks, or sagging.

1 2 3

Remarks

5.

*Concrete is in good condition, without cracks and with a smooth surface to allow easy aircraft and equipment movement.

3

ARCHIVED

Page 12: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Criteria:

Criteria:

Criteria:

General Conditions

*Facility is clean.

Remarks

*Fire extinguishers readily available.

Satisfactory UnsatisfactoryMission Impact**Facility Conditions (Continued)

*Fire Drills -- Conducted at least every six months.*Vegetation Control -- Exercised around the facility.*Emergency Evacuation -- Sufficient stairs available (if applicable); when possible, a minimum of two 32-inch wide outward-opening doors within 75 feet for emergency evacuation.

*Pipes, Valves, and Fittings -- Outside components are protected from vehicles and other moving objects; piping penetrating the facility must be grounded; and shut-off valves are readily accessible.

Natural Gas Storage and Distribution (as applicable):

Remarks

1 2

*Cathodic Protection -- A system must be installed, corrosion free, and the sacrificial plate (anode) volume is 25 percent or better.

*Flammable and combustible materials are properly stored.

*Piping penetrating the facility is grounded.

*Steam and hot water lines are grounded.

*Fire Alarm -- Panel is marked and accessible.

Fire Protection/Prevention:

*Sprinkler System -- Piping is properly installed and supported; system is free of leaks; sprinkler heads are properly positioned; and the system shut-off valve is readily accessible and unobstructed.*AFFF and Carbon Dioxide Bottles -- Supported, secured, and inspections are current.

31

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

1 2 3

*Heating Water Treatment -- Filters are properly installed and water-conditioning equipment is maintained current.*Steam/Hot Water Generation -- Temperature and cooling controls are operable; pressure valve is operable; lines are anchored; and system provides sufficient quantities.

Central Steam / Hot Water Generation and Distribution:

Work Stoppage/Life-Safety Hazard

11.

12.

*Regulators -- Must be accessible, supported, and leak-free.*Storage Tanks -- Must be securely anchored to their support structure, must have pressure relief valves, are protected from vehicular damage, and tank surface and connections must be free of corrosion.

3

1 2 3

*Drainage systems support holding tanks, and drain and waste facilities are properly maintained.

*Pull Stations -- Well-located and alarms are audible.*Halon System -- Inspections are current; instructions are posted; and halon bottles are supported and secured.

*Detectors -- Well-located and operable.

Remarks

10. 2

9.

*Shut-off valves are clearly marked.

Plumbing and Mechanical Systems:

*Meters are operable.*Piping is free of corrosion and located away from moving equipment.*Valves and piping are free of leaks.

*Pressure regulators are installed and operable.

Remarks

4

ARCHIVED

Page 13: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Pavements: Criteria:

Grounds: Criteria:

Criteria:

Criteria:

1

gates are operable.

*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to prevent erosion.*Fencing (if applicable) -- Security fencing is installed and is in good repair; vegetation is controlled around fencing; and rail-driven

313.

1 2

Water Supply and Distribution: 1 2

*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

*Elevated Tanks -- Containment areas are free of debris; tanks are in good repair; and support structures are stable and in good repair.*Water Treatment -- Filters are installed and conditioning equipment is maintained.

3

*Pipes, Valves, and Fittings -- Located below grade; cathodic protection is installed; valves and meters are operable; and pipes entering the facility must be grounded.

*Well/Water Source -- Quality testing records are current and water supply is adequate.

Remarks

15.

14. 1

Remarks

*Sidewalks and Miscellaneous Pads -- Sidewalks are in good repair; pads are in good repair; and pads are sufficiently sized for aircraft and equipment.

2 3

*Lighting -- Facility security lights are installed; sufficient lighting for night operations; and no burnt out lights.

Remarks

2

Satisfactory Unsatisfactory

*Parking -- Properly sited; sufficient room to maneuver; type of pavement supports gross weight of assigned equipment; adequate spaces; and lots are properly marked.

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.

Mission Impact**General ConditionsFacility Conditions (Continued)

*LPS components are grounded and all metallic penetrations are bonded.*Surge protection is provided.

3Lightning Protection System (LPS) Installed:

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

Remarks

16.

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.*LPS inspection documentation being properly maintained.

*Meets NFPA 780, Chapter 3 (Ordinary Structures) and MIL-HDBK-419 requirements.

5

ARCHIVED

Page 14: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

17. Lighting:Criteria:

18.Criteria:***

General Conditions

21

Mission Impact**Satisfactory Unsatisfactory

Unique Local Facility Features:1 2 3

Facility Conditions (Continued)

No

RemarksNo

Yes

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.*Computer Usage -- Lighting is adequate but not too bright to cause glare or discomfort.

Remarks*No burnt out bulbs.

Remarks

*General Illumination Guidelines -- Hallways require a minimum of 5 foot-candles (54 meter-candles) of light while detailed work may require 100 foot-candles (1,076 meter-candles). Bio-Environmental Engineering is contacted to ensure proper illumination is available.

*Fluorescent Fixtures -- If not designed with self-locking tubes, must have a retaining device.*Stairs and Ramps -- Must be illuminated with at least 5 foot-candles (54 meter-candles) of light.

3

Work Stoppage/Life-Safety Hazard

IV. Summary

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes

Yes No

6

ARCHIVED

Page 15: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

maintenance involving component and subsystem replacement, and perform bench checks on certain components.

Meets

*Does location of facility detract from mission performance?

Remarks

II. Mission Design Requirements Design Requirements Mission Impact**Doesn't Meet

FACILITIES ASSESSMENT CHECKLISTCategory Code 212-212 -- Missile Assembly Shop/Integrated Maintenance Facility (IMF)

Installation Name Location Facility Bldg NumberInsp. Date MAJCOM

Sq Footage Year Built Date Last Inspection

Meets Does Not MeetAssess the overall condition of the facility with respect to mission impact.

*Are there any outstanding AF Forms 332?*Does the base master plan reflect the current facility category code?

Facility Purpose: This facility is used to transfer and prepare standoff missiles for operational use, perform organizational-level

Facility ComponentsMission Requirements

1 2 3

Remarks

1. Floors must be strengthened to support missile handling trailers and associated support equipment.

1 2 3

Remarks

2. Bay doors and loading dock size must be commensurate with asset size and handling requirements.

1 2 3

Remarks

3. Facility size depends on the missile systems to be handled.

1 2 3

Remarks

4. Requires space for electrical power and hydraulic units. May require 400Hz, 3-phase power.

1 2 3

Remarks

5. One overhead traverse-mounted crane rated at 4,000 lbs. (1,814 kg) is required for support equipment handling.

Remarks

7.

operations rule.

Facility must have drive-through work bays. *Number of bays dependent upon mission and interpretation of concurrent

1 2 3

*Are there any safety or security write-ups on the facility from the latest inspections?*Does the facility user have the site plan available?

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Do the bays' size and shape meet mission needs?

*Does the facility design allow for known future mission changes?

1 2 3

Remarks

6. Facility requires a separate utility room for low and high air pressure systems (150 and 3,500 psig (1,034 and 24,131 kPa respectively) lines for each bay), emergency power generators, and HVAC.

1

ARCHIVED

Page 16: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

Facility must have:

10.1 2 3

11. 1 2 3

III.

1. Explosives Safety: Criteria:

1 2 3

Walls: Criteria:

*Free of leaks.

Doors: Criteria:

Remarks

Facility may need explosive-proof lighting fixtures if a Class I (explosive vapors) or Class II (explosive dust) environment is part of the mission.

*Placards -- Explosives limits and fire/chemical symbols are displayed. *Inspections -- Annual ground and explosives safety and facility inspections are performed.*Concurrent Operations -- MAJCOM interpretation of concurrent operations rules are being followed; factors must consider whether walls protrude through ceiling.

Facility must be able to control fuel vapor emissions.

*General -- Facility has good drainage and is vermin resistant.

Remarks

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201, Q-D requirements are satisfied, net explosives weight limits are not exceeded, and commensurate measures are in-place. Any exceptions are properly identified and risk assessments are performed.

1 2 3

Remarks

8.*Tool, supply, and equipment room.*Ready and training room.

*Approximately 1,500 sq. ft. (139 m2) administrative area.

2 3

Remarks

9. Facility must have serviceable lightning protection and grounding systems.

Remarks

*Exterior -- Clean, intact, and free from damage. Paint and caulking are in good condition and water tight.

2.

*Bay walls -- 12-in (305 mm) thick reinforced (2,500 psi) (17,237 kPa) concrete, in good condition, with no unauthorized attachments.

1 2 3

Remarks

Roof: (Circle One) Shingle Metal Gravel Rolled Frangible Concrete Criteria:

3.

*Attachments are secure.

Remarks

*Overhead doors raise and lower smoothly, and can be locked in place.

4.

*Safety mechanisms are in place to prevent accidental or inadvertent closing.

Design Requirements

*Grounding -- A means to dissipate static electricity buildup is installed; static bonds and grounds are tested for resistance and continuity and records are on hand as per AFI 32-1065.

Mission Design Requirements (Continued)Meets Doesn't Meet Mission Impact**

*Lighting -- Explosive-proof lights are used in Class I (explosives fuel/vapors) and Class II (explosives dust) environments; UL-approved lights are acceptable for all other environments.

*Latrine facilities.

Facility Conditions General Conditions Mission Impact**Satisfactory Unsatisfactory

1

*Wiring -- Wires to structures are underground at least 50 feet (15 m) away and have lightning arrestors and surge protection. Conduits require bonding to the facility at point of entry.*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements. *Windows -- Made of blast-resistant-material.

*Interior -- Structural members and cross bracing are free from deterioration, and there are no unauthorized attachments that may compromise the design function.

1 2 3

Remarks

*No signs of failure, separation, or curling.

*Doors swing/roll freely and fit in jambs.*Locks and security hasps are in good condition.

1 2 3

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

2

ARCHIVED

Page 17: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Floors: Criteria:

Ceiling : Criteria:

Criteria:

HVAC: Criteria:

*Filters are clean.

Facility Electrical: Criteria: *All wiring is in conduit.

1 2 3

Remarks

5.

*Concrete is in good condition, without cracks and with a smooth surface to allow easy equipment movement.

1 2 3

Remarks

6.

*No obvious hazards to personnel on the floor.*No visible damage, watermarks, or sagging.

3

Remarks

*Permanently mounted systems are electrically bonded to the facility.

7.

*System in good repair.*Certification and proof-load records are up-to-date.*Traverse movement is smooth and unimpaired.

Hoist and Lifting Crane:

8.

*Switches are in spark-proof enclosures.

*Central equipment (heat exchangers, pumps, and fans) is clean and well maintained.*Ductwork and accessories are well supported, insulation intact, and outlet diffusers are clean.

1 2 3

Remarks

Remarks

9. 1 2 3

*Switch box plates are water and dust tight.

*Transfer switch and breaker panels are operable.*Generator and back-up power is available and in good repair.

1 2

*Wiring is in conduits and insulation is intact.

*Stand-alone equipment (boiler and chiller units) is well maintained.

*Electrical control and switchgear is properly tagged, labeled, and housed.

*Start/stop control switch is properly mounted.*Damper controls and motors are in good working order.

*Ground devices are free of corrosion.*Support poles are in good condition and located at least 50 feet (15 m) away from

Facility Conditions (Continued) General ConditionsUnsatisfactorySatisfactory

Mission Impact**

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*If required, appropriate surge protection devices will be installed.

*Substations are away from explosives operations.*Switches and breakers contain lightning arrestors.*No hazardous materials [polychlorinated biphenyls (PCBs)] are present.*Transformers are free of leaks, are closed, and are weather-proof.

*Junction boxes are spark-proof and watertight.

Work Stoppage/Life-Safety Hazard

3

ARCHIVED

Page 18: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Criteria:

Criteria:

Criteria:

10.

*Halon System -- Inspections are current; instructions are posted; and halon bottles are supported and secured.

*Detectors -- Well-located and operable.

Remarks

11.2

*Piping penetrating the facility is grounded.

Remarks

1 2 3

*Drainage systems support holding tanks, and drain and waste facilities are properly maintained.

*Pull Stations -- Well-located and alarms are audible.

Work Stoppage/Life-Safety Hazard

12.

13.

*Regulators -- are accessible, supported, and leak-free.*Storage Tanks -- are securely anchored to their support structure, have pressure relief valves, are protected from vehicular damage, and tank surface and connections are free of corrosion.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

1 2 3

*Heating Water Treatment -- Filters are properly installed and water-conditioning equipment is maintained.*Steam/Hot Water Generation -- Temperature and cooling controls are operable; pressure valve is operable; lines are anchored; and system provides sufficient quantities.

Central Steam / Hot Water Generation and Distribution:

*Shut-off valves are clearly marked.

Plumbing and Mechanical Systems:

*Meters are operable.*Piping is free of corrosion and located away from moving equipment.*Valves and piping are free of leaks.

*Pressure regulators are installed and operable.

*Steam and hot water lines are grounded.

*Fire Alarm -- Panel is marked and accessible.

Fire Protection/Prevention:

*Sprinkler System -- Piping is properly installed and supported; system is free of leaks; sprinkler heads are properly positioned; and the system shut-off valve is readily accessible and unobstructed.*AFFF and Carbon Dioxide Bottles -- Supported, secured, and inspections are current.

31

*Fire Drills -- Conducted at least every six months.*Vegetation Control -- Exercised within 50 ft (15 m) of above-ground facilities.*Emergency Evacuation -- Sufficient stairs available (if applicable); when possible, a minimum of two 32-in (812 mm) wide outward-opening doors within 75 ft (23 m) for emergency evacuation.

*Pipes, Valves, and Fittings -- Outside components are protected from vehicles and other moving objects; piping penetrating the facility is grounded; and shut-off valves are readily accessible.

Natural Gas Storage and Distribution (as applicable):

Remarks

1 2 3

*Cathodic Protection -- a system is installed, corrosion free, and the sacrificial plate (anode) volume is 25 % or more.

Remarks

Facility Conditions (Continued) General ConditionsSatisfactory Unsatisfactory

Mission Impact**

4

ARCHIVED

Page 19: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Pavements: Criteria:

Grounds: Criteria:

Criteria:

Criteria:

*Meets NFPA 780 and MIL-HDBK-419 requirements.

3

*LPS inspection documentation is being properly maintained.

Remarks

18.

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.*LPS components are grounded and all metallic penetrations are bonded.*Side-flash protection is provided through separation.*Surge protection is provided.

General Conditions

*Parking -- Properly sited; sufficient room to maneuver; type of pavement supports gross weight of assigned equipment; adequate spaces;and lots are properly marked.

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.

Facility Conditions (Continued)Mission Impact**

Compressed Air Generation and Distribution: Satisfactory Unsatisfactory

*Lighting -- Perimeter security lights are installed and lighting is sufficient for night operations. No burnt out lights.

Remarks

16. 1

1 2

*Sidewalks, Structures, and Miscellaneous Pads -- Sidewalks are in good repair; pads are in good repair; and pads are sufficiently sized for equipment.

2 3

*Pipes, Valves, and Fittings -- Piping is located below grade; cathodic protection is installed; and valves, dehydrators, and meters are operable.

Remarks

15.

*Well/Water Source -- Quality testing records are current and water supply is adequate.

Remarks

*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

3

*Compressors -- Tank and accessories are secured; foundation is paved or padded; data plate is legible; and pressure regulators and release valves are operable.

14. 1 2 3

*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to prevent erosion.*Fencing -- Security fencing is installed and is in good repair; vegetation is controlled around fencing; and rail-driven gates are operable.

*Pipes, Valves, and Fittings -- Located below grade; cathodic protection is installed; valves and meters are operable; and pipes entering the facility are grounded.

Remarks

17.

*Elevated Tanks -- Containment areas are free of debris; tanks are in good repair; and support structures are stable and in good repair.*Water Treatment -- Filters are installed and conditioning equipment is maintained.

Water Supply and Distribution: 1 2 3

Lightning Protection System (LPS) Installed: 1 2

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

5

ARCHIVED

Page 20: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

19. Lighting:Criteria:

20.Criteria:

21.Criteria:

22.Criteria:

*No burnt out bulbs.

Hydraulic Unit:

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.*Computer Usage -- Lighting is adequate but not too bright to cause glare or discomfort.

Remarks

2 31

Remarks

*Unit is clean.

*Hoses and fittings are in good condition.*Fluid reservoir is operable.

*Service records are available and current.

*General Illumination Guidelines -- Hallways require a minimum of 5 foot-candles (54 meter-candles) of light while detailed work may require 100 foot-candles (1,076 meter-candles). Bio-Environmental Engineering is contacted to ensure proper illumination is available.

Unique Local Facility Features: 1 2 3

*Electrical cables are in good repair.

*Fluorescent Fixtures -- If not designed with self-locking tubes, have a retaining device.*Stairs and Ramps -- Are illuminated with at least 5 foot-candles (54 meter-candles) of light.

21

Mission Impact**Satisfactory Unsatisfactory

3

Facility Conditions (Continued) General Conditions

2 3

*Piping, Valves, and Fittings -- Piping outside berm area is protected; piping penetrating facility is grounded; and no leaks.*Pumps -- Regulators installed and properly work; and maximum pressure placarded.

Liquid Fuel Storage and Distribution: 1

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

Remarks

*Tanks -- Supported and securely anchored; contents clearly labeled; free from corrosion; fitted with liquid level gauges; have vent devices; and located in bermed area to contain contents.*Secondary Containment -- Container is free of cracks and leaks; sufficient for volume; free of litter and other objects. *Cathodic Protection -- Installed; free of corrosion; and sacrificial plate volume is 25% or +.

Remarks

6

ARCHIVED

Page 21: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

IV. Summary

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes No

YesYes No

No

Remarks

7

ARCHIVED

Page 22: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

*Does the facility design allow for known future mission changes?

3

1 2 3

Remarks

6. Facility requires a separate utility room for low and high air pressure systems (150 and 3,500 psi (1,034 and 24,131 kPa, respectively) lines for each bay) and HVAC.

*Do the bays' size and shape meet mission needs?

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Are there any safety or security write-ups on the facility from the latest inspections?*Does the facility user have the site plan available?

Remarks

7.

interpretation of concurrent operations rule).*Drive-through paint booth may be required dependent on mission.

Facility must have drive-through work bays. *A minimum of three 30 ft X 50 ft (9 m X 15 m) bays (dependent upon mission and

1 2

1 2 3

Remarks

5. One overhead traverse-mounted crane rated at 4,000 lbs. (1,814 kg) is required in each bay.

1 2 3

Remarks

4. Requires space for electrical power units and converter systems consisting of: *115VAC, 60 Hz single-phase electricity.*115VAC, 400 Hz, 3-phase electricity.

1 2 3

Remarks

3. Facility size depends on the missile/munitions systems to be handled.

1 2 3

Remarks

2. Bay doors a minimum 10 ft H X 17 ft W (3 m X 5 m) and loading dock size commensurate with asset size and handling requirements.

1 2 3

Remarks

1. A test cell room for electrical and resistance checks of rocket motors (if required for on-hand systems).

Facility Purpose: This facility is designed to perform missile and glide munitions assembly and disassembly inspections, testing, and repair. Facility Components

Mission RequirementsMeets Does Not Meet

Assess the overall condition of the facility with respect to mission impact.

*Are there any outstanding AF Forms 332?*Does the base master plan reflect the current facility category code?

Insp. Date MAJCOMSq Footage Year Built Date Last Inspection

FACILITIES ASSESSMENT CHECKLISTCategory Code 212-213 -- Tactical Missile/Glide Weapon Maintenance Shop

Installation Name Location Facility Bldg Number

*Does location of facility detract from mission performance?

Remarks

II. Mission Design Requirements Design Requirements Mission Impact**Meets Doesn't Meet

1

ARCHIVED

Page 23: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

Facility must have:

III.

1. Explosives Safety: Criteria:

1 2 3

Walls: Criteria:

*Free of leaks.

Doors: Criteria: 3

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Wiring -- Wires to structures are underground at least 50 ft (15 m) away and have lightning arrestors and surge protection.*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements. *Windows -- Made of blast-resistant material.

*Interior -- Structural members and cross bracing are free from deterioration, caulking around wall penetrations is watertight, and there are no unauthorized attachments that may compromise the design function.

1 2 3

Remarks

*Lighting -- Explosive-proof lights are used in Class I (explosives fuel/vapors) and Class II (explosives dust) environments; UL-approved lights are acceptable for all other environments.

*Latrine facilities.

Facility Conditions General Conditions Mission Impact**Satisfactory Unsatisfactory

Mission Design Requirements (Continued)Meets Doesn't Meet

Mission Impact**Design Requirements

*Grounding -- A means to dissipate static electricity buildup is installed; static bonds and grounds are tested for resistance and continuity and records are on hand as per AFI 32-1065.

Remarks

*Overhead doors raise and lower smoothly, and can be locked in place.

4.

*Safety mechanisms are in place to prevent accidental or inadvertent closing.

*Doors swing/roll freely and fit in jambs.*Locks and security hasps are in good condition.

1 2

Remarks

Roof: (Circle One) Shingle Metal Gravel Rolled Frangible Concrete Criteria:

3.

*Attachments are secure.*No signs of failure, separation, or curling.

*Bay walls -- 12-in (305 mm) thick reinforced (2,500 psig) (1,034 kPa) concrete, in good condition, with no unauthorized attachments.

1 2 3

2 3

Remarks

9. Facility must have serviceable lightning protection and grounding systems. 1

1 2 3

Remarks

8.*Tool, supply, and equipment room.*Ready and training room.

*Approximately 1,500 sq. ft. (139 m2) administrative area.

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201, Q-D requirements are satisfied, net explosives weight limits are not exceeded, and commensurate measures are in-place. Any exceptions are properly identified and risk assessments are performed.

2.

*General -- Facility has good drainage and is vermin resistant.

*Placards -- Explosives limits and fire/chemical symbols are displayed. *Inspections -- Annual ground and explosives safety and facility inspections are performed.*Concurrent Operations -- MAJCOM interpretation of concurrent operations rules are being followed; factors must consider whether walls protrude through ceiling.

Remarks

*Exterior -- Clean, intact, and free from damage. Paint and caulking are in good condition and water tight.

2

ARCHIVED

Page 24: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Floors: Criteria:

Ceiling : Criteria:

Criteria:

HVAC: Criteria:

*Filters are clean.

Facility Electrical: Criteria: *All wiring is in conduit.

Work Stoppage/Life-Safety Hazard

Mission Impact**

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*If required, appropriate surge protection devices will be installed.

*Substations are away from explosives operations.*Switches and breakers contain lightning arrestors.*No hazardous materials [polychlorinated biphenyls (PCBs)] are present.*Transformers are free of leaks, are closed, and are weather-proof.

*Junction boxes are spark-proof and watertight.

*Ground devices are free of corrosion.*Support poles are in good condition and located at least 50 feet (15 m) away from

*Stand-alone equipment (boiler and chiller units) is well maintained.

*Electrical control and switchgear is properly tagged, labeled, and housed.

*Start/stop control switch is properly mounted.*Damper controls and motors are in good working order.

1 2

*Wiring is in conduits and insulation is intact.

Facility Conditions (Continued) General ConditionsUnsatisfactorySatisfactory

Remarks

9. 1 2 3

*Switch box plates are water and dust tight.

*Transfer switch and breaker panels are operable.*Generator and back-up power is available and in good repair.

8.

*Switches are in spark-proof enclosures.

*Central equipment (heat exchangers, pumps, and fans) is clean and well maintained.*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.

1 2 3

Remarks

3

Remarks

*Permanently mounted systems are electrically bonded to the facility.

7.

*System in good repair.*Certification and proof-load records are up-to-date.*Traverse movement is smooth and unimpaired.

Hoist and Lifting Crane:

1 2 3

Remarks

6.

*No obvious hazards to personnel on the floor.*No visible damage, watermarks, or sagging.

1 2 3

Remarks

5.

*Concrete is in good condition, without cracks and with a smooth surface to allow easy equipment movement.

3

ARCHIVED

Page 25: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Criteria:

Criteria:

Criteria:

Facility Conditions (Continued) General ConditionsSatisfactory Unsatisfactory

Mission Impact**

*Fire Drills -- Conducted at least every six months.*Vegetation Control -- Exercised within 50 ft (15m) of above-ground facilities.*Emergency Evacuation -- Sufficient stairs available (if applicable); when possible, a minimum of two 32-in (812 mm) wide outward-opening doors within 75 ft (23 m) for emergency evacuation.

*Pipes, Valves, and Fittings -- Outside components are protected from vehicles and other moving objects; piping penetrating the facility must be grounded; and shut-off valves are readily accessible.

Natural Gas Storage and Distribution (as applicable):

Remarks

1 2 3

*Cathodic Protection -- A system is installed, corrosion free, and the sacrificial plate (anode) volume is 25 % or more.

*Steam and hot water lines are grounded.

*Fire Alarm -- Panel is marked and accessible.

Fire Protection/Prevention:

*Sprinkler System -- Piping is properly installed and supported; system is free of leaks; sprinkler heads are properly positioned; and the system shut-off valve is readily accessible and unobstructed.*AFFF and Carbon Dioxide Bottles -- Supported, secured, and inspections are current.

31

*Shut-off valves are clearly marked.

Plumbing and Mechanical Systems:

*Meters are operable.*Piping is free of corrosion and located away from moving equipment.*Valves and piping are free of leaks.

*Pressure regulators are installed and operable.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

1 2 3

*Heating Water Treatment -- Filters are properly installed and water-conditioning equipment is maintained current.*Steam/Hot Water Generation -- Temperature and cooling controls are operable; pressure valve is operable; lines are anchored; and system provides sufficient quantities.

Central Steam / Hot Water Generation and Distribution:

Remarks

12.

13.

*Regulators -- Are accessible, supported, and leak-free.*Storage Tanks -- Are securely anchored to their support structure, have pressure relief valves, are protected from vehicular damage, and tank surface and connections are free of corrosion.

Remarks

1 2 3

*Drainage systems support holding tanks, and drain and waste facilities are properly maintained.

Work Stoppage/Life-Safety Hazard

10.

*Halon System -- Inspections are current; instructions are posted; and halon bottles are supported and secured.

*Detectors -- Well-located and operable.

Remarks

11.2

*Piping penetrating the facility is grounded.

*Pull Stations -- Well-located and alarms are audible.

4

ARCHIVED

Page 26: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Pavements: Criteria:

Grounds: Criteria:

Criteria:

Criteria:

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

Lightning Protection System (LPS) Installed: 1 2

*Elevated Tanks -- Containment areas are free of debris; tanks are in good repair; and support structures are stable and in good repair.*Water Treatment -- Filters are installed and conditioning equipment is maintained.

Water Supply and Distribution: 1 2 3

*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to prevent erosion.*Fencing -- Security fencing is installed and is in good repair; vegetation is controlled around fencing; and rail-driven gates are operable.

*Pipes, Valves, and Fittings -- Located below grade; cathodic protection is installed; valves and meters are operable; and pipes entering the facility must be grounded.

Remarks

17.

*Well/Water Source -- Quality testing records are current and water supply is adequate.

1 2 3

Remarks

*Sidewalks and Miscellaneous Pads -- Sidewalks are in good repair; pads are in good repair; and pads are sufficiently sized for equipment.

2 3

*Pipes, Valves, and Fittings -- Piping is located below grade; cathodic protection is installed; and valves, dehydrators, and meters are operable.

Remarks

15.

16. 1

2

Compressed Air Generation and Distribution:

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. No burnt out lights.

Remarks

*Parking -- Properly sited; sufficient room to maneuver; type of pavement supports gross weight of assigned equipment; adequate spaces; and lots are properly marked.*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

3

*Compressors -- Tank and accessories are secured; foundation is paved or padded; data plate is legible; and pressure regulators and release valves are operable.

14.

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.

Facility Conditions (Continued) General ConditionsSatisfactory Unsatisfactory

Mission Impact**

1

18.

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.*LPS components are grounded and all metallic penetrations are bonded.*Side-flash protection is provided through separation.*Surge protection is provided.*Meets NFPA 780 and MIL-HDBK-419 requirements.

3

*LPS inspection documentation is being properly maintained.

Remarks

5

ARCHIVED

Page 27: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

19. Lighting:Criteria:

20.Criteria:

21.Criteria:

22.Criteria:

*Tanks -- Supported and securely anchored; contents clearly labeled; free from corrosion; fitted with liquid level gauges; have vent devices; and located in bermed area to contain contents.*Secondary Containment -- Container free of cracks and leaks; sufficient for volume; free of litter and other objects. *Cathodic Protection -- Installed; free of corrosion; and sacrificial plate volume is 25% or +.

Remarks

Liquid Fuel Storage and Distribution: 1

3

Facility Conditions (Continued) General Conditions

21

Mission Impact**Satisfactory Unsatisfactory

Unique Local Facility Features:1 2 3

*Electrical cables are in good repair.

*General Illumination Guidelines -- Hallways require a minimum of 5 foot-candles (54 meter-candles) of light while detailed work may require 100 foot-candles (1,076 meter-candles). Bio-Environmental Engineering is contacted to ensure proper illumination is available.

*Fluorescent Fixtures -- If not designed with self-locking tubes, have a retaining device.

Remarks

Remarks

*Unit is clean.

*Hoses and fittings are in good condition.*Fluid reservoir is operable.

*Service records are available and current.

2 3

*Piping, Valves, and Fittings -- Piping outside berm area is protected; piping penetrating facility is grounded; and no leaks.*Pumps -- Regulators installed and properly work; and maximum pressure placarded.

YesYes No

No

Work Stoppage/Life-Safety Hazard

IV. Summary

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes No

Hydraulic Unit:

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.

*Stairs and Ramps -- Are illuminated with at least 5 foot-candles (54 meter-candles) of light.

Remarks

1

*No burnt out bulbs.*Computer Usage -- Lighting is adequate but not too bright to cause glare or discomfort.

Remarks

2 3

6

ARCHIVED

Page 28: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

Racks (MER).

5.1 2 3

6

Remarks*Powered Trailers -- 120, 220, and 440 VAC 60 Hz (440VAC outlets copiously spaced in and around facility).

*Does the facility design allow for known future mission changes?

Facility may need high security hasps and an intrusion detection system.

Electrical Power Requirements.*Non-Powered Trailers -- 120 and 220VAC, 60 Hz

1 2 3

Remarks

*Do the bays' size and shape meet mission needs?

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*Are there any safety or security write-ups on the facility from the latest inspections?*Does the facility user have the site plan or license available?

1 2 3

*For B-1 units.

One monorail overhead hoist minimum 10-ton (10,160 kg) capacity.

Remarks

3.*Floor must be rated at 250 psig (1,724 kPa) footprint and 50,000 lb. (22,680 kg) trailer weight.

1. Space Requirements.

*6,000 sq ft (557 m2) storage space w/supporting office space for four people.*Storage space for mobility support equipment (if applicable).

*6,000 sq ft (557 m2) for 12 Primary Assigned Aircraft (PAA) B-52 units w/heavy adapter stores/MER beams and cluster racks.*Additional 5,000 sq ft (464 m2) for each subsequent 12 PAA B-52 unit.*5,000 sq ft (464 m2) for 12 PAA B-1units.*Additional 3,000 sq ft (279 m2) for each subsequent 12 PAA B-1 tasking.

Facility Purpose: This facility provides space for overhaul and repair of aircraft release and gun systems.Facility Components

Mission Requirements

Remarks

Meets Does Not MeetAssess the overall condition of the facility with respect to mission impact.

*Are there any outstanding AF Forms 332?*Does the base master plan reflect the current facility category code?

Insp. Date MAJCOMSq Footage Year Built Date Last Inspection

FACILITIES ASSESSMENT CHECKLISTCategory Code 215-552 -- Weapons and Release Systems Shop

Installation Name Location Facility Bldg Number

Doesn't Meet

*Does location of facility detract from mission performance?

Remarks

II. Mission Design Requirements Design Requirements Mission Impact**

1

Meets

2 3

*11,500 sq ft (1,068 m2) for single wing aircraft w/MERs.

1 2 3*10,530 sq ft (978 m2) for single-wing aircraft not equipped w/Multiple Ejector

*Dispatch office.*Gun and/or ejector cleaning room.*Alternate Mission Equipment storage area.

1

*Spare gun storage.*Support equipment storage area.

B-1 facilities.

2 3

Remarks

2. Bay door size must be commensurate with the size of the support equipment, guns, and ejector racks.

*Bay drive-through capability with 12 ft X 12 ft (3.7 m X 3.7 m) doors.

Remarks

4.*For B-52 units.

Work Stoppage/Life-Safety Hazard1

ARCHIVED

Page 29: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

Facility must have:

9.1 2 3

10.

III.

1. Explosives Safety: Criteria:

1 2 3

Walls: Criteria:

*Free of leaks.

Doors: Criteria:

321

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*No signs of failure, separation, or curling.

*Doors swing/roll freely and fit in jambs.*Locks and security hasps are in good condition.

1 2 3

*Windows -- Made of blast-resistant material if within the explosives clear zone.

*Interior -- Structural members and cross bracing are free from deterioration, adequate soundproofing insulation installed, caulking around wall penetrations watertight, and there are no unauthorized attachments that may compromise the design function.

1 2 3

Remarks

*Placards -- Explosives limits and fire/chemical symbols are displayed.

*Latrine facilities.

Facility Conditions General Conditions Mission Impact**Satisfactory Unsatisfactory

1

Remarks

*Overhead doors raise and lower smoothly, and can be locked in place.

4.

*Safety mechanisms are in place to prevent accidental or inadvertent closing.

1 2 3

Remarks

Roof: (Circle One) Shingle Metal Gravel Rolled Frangible Concrete Criteria:

3.

*Attachments are secure.

Remarks

*Exterior -- Clean, intact, and free from damage. Paint and caulking are in good condition and water tight.

2.

2 3

Remarks

8. Facility must have a serviceable lightning protection system.

Meets Doesn't MeetMission Impact**Design Requirements

*Siting Requirements --Facility is sited or licensed in accordance with DoD 6055.9 STD and AFMAN 91-201. Any exceptions are properly identified and risk assessments are performed.

*General -- Facility has good drainage and is vermin resistant.

Remarks

Remarks

*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements.

*Inspections -- Annual weapons safety, ground safety, and facility inspections are performed.

Facility must be constructed with DDESB approval if sited.

*Grounding -- A means to dissipate static electricity buildup is installed; static bonds and grounds are tested for resistance and continuity and records are on hand as per AFI 32-1065.

1 2 3

Remarks

7.*Tool, supply, bench stock, and equipment room.*Ready and/or training room with personnel lockers available.

*Approximately 1,500 sq ft (139 m2) administrative area.

Facility power requirements are driven by systems being worked on.

Mission Design Requirements (Continued)

2

ARCHIVED

Page 30: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Floors: Criteria:

Ceiling : Criteria:

Criteria:

HVAC: Criteria:

*Filters are clean.

Facility Electrical: Criteria: *All wiring is in conduit.

*Junction boxes are spark-proof and watertight.

Work Stoppage/Life-Safety Hazard

*May need special power requirements for test equipment.*Switches and breakers contain lightning arrestors.*No hazardous materials [polychlorinated biphenyls (PCBs)] are present.*Transformers are free of leaks, are closed, and are weather-proof.

*Start/stop control switch is properly mounted.

Facility Conditions (Continued) General ConditionsUnsatisfactorySatisfactory

Mission Impact**

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*If required, appropriate surge protection devices are installed.

*Damper controls and motors are in good working order.

*Ground devices are free of corrosion.*Support equipment may have special electrical requirements.

1 2

*Wiring is in conduits and insulation is intact.

*Stand-alone equipment (boiler and chiller units) is well maintained.

*Electrical control and switchgear is properly tagged, labeled, and housed.

Remarks

9. 1 2 3

*Switch box plates are water and dust tight.

*Transfer switch and breaker panels are operable.*Generator and back-up power is available and in good repair.

8.

*Switches are in spark-proof enclosures.

*Central equipment (heat exchangers, pumps, and fans) is clean and well maintained.*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.

1 2 3

Remarks

3

Remarks

*Permanently mounted systems are electrically bonded to the facility.

7.

*System is in good repair.*Certification and proof-load records are up-to-date.*Traverse movement is smooth and unimpaired.

Hoist and Lifting Crane:

1 2 3

Remarks

6.

*No obvious hazards to personnel on the floor.*No visible damage, watermarks, or sagging.

1 2 3

Remarks

5.

*Concrete is in good condition, without cracks, and with a smooth surface to allow easy movement of equipment.*Adequate drainage with oil-water separator in maintenance work bays.

3

ARCHIVED

Page 31: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Criteria:

Criteria:

Criteria:

Remarks

Work Stoppage/Life-Safety Hazard

*Fire extinguishers readily available.

Satisfactory UnsatisfactoryMission Impact**Facility Conditions (Continued) General Conditions

*Fire Drills -- Conducted at least every six months.*Vegetation Control -- Exercised around the facility.*Emergency Evacuation -- Sufficient stairs available (if applicable); when possible, a minimum of two 32-in (812 mm) wide outward-opening doors within 75 ft (23 m) for emergency evacuation.

*Pipes, Valves, and Fittings -- Outside components are protected from vehicles and other moving objects; piping penetrating the facility must be grounded; and shut-off valves are readily accessible.

Natural Gas Storage and Distribution (as applicable):

Remarks

1 2

*Cathodic Protection -- A system is installed, corrosion free, and the sacrificial plate (anode) volume is 25 % or +.

*Facility is clean.

*Steam and hot water lines are grounded.

*Fire Alarm -- Panel is marked and accessible.

Fire Protection/Prevention (as applicable):

*Sprinkler System -- Piping is properly installed and supported; system is free of leaks; sprinkler heads are properly positioned; and the system shut-off valve is readily accessible and unobstructed.*AFFF and Carbon Dioxide Bottles -- Supported, secured, and inspections are current.

3

*Flammable and combustible materials are properly stored.

*Emergency eyewash and shower stations installed.

*Shut-off valves are clearly marked.

Plumbing and Mechanical Systems:

*Meters are operable.*Piping is free of corrosion and located away from moving equipment.*Valves and piping are free of leaks.

*Pressure regulators are installed and operable.

1 2

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

1 2 3

*Heating Water Treatment -- Filters are properly installed and water-conditioning equipment is maintained current.

12.

13.

*Regulators -- Are accessible, supported, and leak-free.*Storage Tanks -- Are securely anchored to their support structure, have pressure relief valves, are protected from vehicular damage, and tank surface and connections are free of corrosion.

Remarks

3

3

*Drainage systems support holding tanks, and drain and waste facilities are properly maintained.

*Pull Stations -- Well-located and alarms are audible.

*Steam/Hot Water Generation -- Temperature and cooling controls are operable; pressure valve is operable; lines are anchored; and system provides sufficient quantities.

Central Steam / Hot Water Generation and Distribution:

10.

*Halon System -- Inspections are current; instructions are posted; and halon bottles are supported and secured.

*Detectors -- Well-located and operable.

Remarks

11. 2

*Piping penetrating the facility is grounded.

1

4

ARCHIVED

Page 32: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Pavements: Criteria:

Grounds: Criteria:

Criteria:

Criteria:

*Compressors -- Tank and accessories are secured; foundation is paved or padded; data plate is legible; and pressure regulators and release valves are operable.

14.Unsatisfactory

Mission Impact**

Lightning Protection System (LPS) Installed: 1 2

*Elevated Tanks -- Containment areas are free of debris; tanks are in good repair; and support structures are stable and in good repair.*Water Treatment -- Filters are installed and conditioning equipment is maintained.

Water Supply and Distribution: 1 2 3

*Pipes, Valves, and Fittings -- Located below grade; cathodic protection is installed; valves and meters are operable; and pipes entering the facility must be grounded.

*Well/Water Source -- Quality testing records are current and water supply is adequate.

Remarks

17.

*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

gates (if present) are operable.

*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to help prevent erosion.*Fencing (if applicable) -- Security fencing is installed and is in good repair; vegetation is controlled around fencing; and rail-driven

Remarks

*Sidewalks and Miscellaneous Pads -- Sidewalks are in good repair; pads are in good repair; and pads are sufficiently sized for equipment.

2 3

*Pipes, Valves, and Fittings -- Piping is located below grade; cathodic protection is installed; and valves, dehydrators, and meters are operable.

Remarks

15.

*Lighting -- Facility security lights are installed; sufficient lighting for night operations; and no burnt out lights.

Remarks

16. 1

*Parking -- Properly sited; sufficient room to maneuver; type of pavement supports gross weight of assigned equipment; adequate spaces; and lots are properly marked.

1 2

31Compressed Air Generation and Distribution: 2

3

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.

Facility Conditions (Continued) General ConditionsSatisfactory

*LPS components are grounded and all metallic penetrations are bonded.*Surge protection is provided.*Meets NFPA 780 and MIL-HDBK-419 requirements.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

3

*LPS inspection documentation being properly maintained.

Remarks

18.

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.

5

ARCHIVED

Page 33: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

19. Lighting:Criteria:

20.Criteria:

General Conditions

21

Mission Impact**Satisfactory Unsatisfactory

Unique Local Facility Features:1 2 3

Remarks

*Fluorescent Fixtures -- If not designed with self-locking tubes, have a retaining device.*Stairs and Ramps -- Are illuminated with at least 5 foot-candles (54 meter-candles) of light.

3

Facility Conditions (Continued)

No

Remarks

*General Illumination Guidelines -- Hallways require a minimum of 5 foot-candles (54 meter-candles) of light while detailed work may require 100 foot-candles (1,076 meter-candles). Bio-Environmental Engineering is contacted to ensure proper illumination is available.

No

YesYes No

Work Stoppage/Life-Safety Hazard

IV. Summary

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.*Computer Usage -- Lighting is adequate but not too bright to cause glare or discomfort.

Remarks*No burnt out bulbs.

6

ARCHIVED

Page 34: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

*Does the facility design allow for known future mission changes?

3

1 2 3

Remarks

6. Facility requires a separate utility room for a low air pressure system (150 psig (1,034 kPa) lines for each bay) and HVAC.

*Do the bays' size and shape meet mission needs?

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Are there any safety or security write-ups on the facility from the latest inspections?*Does the facility user have the site plan available?

Remarks

7.

operations rule.*Drive-through paint booth may be required dependent on mission.

Facility must have drive-through work bays. *Number of bays dependent upon mission and interpretation of concurrent

1 2

1 2 3

Remarks

5. One overhead traverse-mounted crane rated at 4,000 lbs. (1,814 kg) is required. Cranes and hoists may need special safety devices for nonconventional weapons systems.

1 2 3

Remarks

4. Requires space for electrical power units and converter systems consisting of: *115VAC, 60 Hz single-phase electricity.*115VAC, 400 Hz, three-phase electricity.

1 2 3

Remarks

3. Facility size depends on munitions systems being handled. Minimum single bay size for a fighter wing is 3,940 sq ft (336 m2). Bomber wings require a minimum 2,090 sq ft (194 m2).

1 2 3

Remarks

2. Bay doors a minimum 10 ft H X 16 ft W (3 m X 4.8 m) and loading dock size commensurate with asset size and handling requirements.

Facility Purpose: This facility is used to perform initial assembly, bench test, inspection, and minor maintenance of various conventional

Facility ComponentsMission RequirementsMeets Does Not Meet

Assess the overall condition of the facility with respect to mission impact.

*Are there any outstanding AF Forms 332?*Does the base master plan reflect the current facility category code?

Insp. Date MAJCOMSq Footage Year Built Date Last Inspection

FACILITIES ASSESSMENT CHECKLISTCategory Code 215-582 -- Surveillance and Inspection Shop

Installation Name Location Facility Bldg Number

Remarks

II. Mission Design Requirements Design Requirements Mission Impact**Meets

and nonconventional munitions and their respective components to include electro-optical and laser-guided bomb kits.

Doesn't Meet

1 2 3

Remarks

1.

*Does location of facility detract from mission performance?

Bay doors require high security hasps and may need an intrusion detection system dependent on security category of assets being inspected.

1

ARCHIVED

Page 35: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

Facility must have:

10.1 2 3

III.

1. Explosives Safety: Criteria:

1 2 3

Walls: Criteria:

*Free of leaks.

Doors: Criteria:

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*No signs of failure, separation, or curling.

*Doors swing/roll freely and fit in jambs.*Locks and security hasps are in good condition.

1 2 3

*Wiring -- Wires to structures are underground at least 50 ft (15 m) away and have lightning arrestors and surge protection.*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements. *Windows -- Made of blast-resistant material.

*Interior -- Structural members and cross bracing are free from deterioration, caulking around wall penetrations watertight, and there are no unauthorized attachments that may compromise the design function.

1 2 3

Remarks*General -- Facility has good drainage and is vermin resistant.

*Lighting -- Explosive-proof lights are used in Class I (explosives fuel/vapors) and Class II (explosives dust) environments; UL-approved lights are acceptable for all other environments.

*Latrine facilities.

Facility Conditions General Conditions Mission Impact**Satisfactory Unsatisfactory

Mission Design Requirements (Continued)Meets Doesn't Meet

Mission Impact**Design Requirements

*Grounding -- A means to dissipate static electricity buildup is installed; static bonds and grounds are tested for resistance and continuity and records are on hand as per AFI 32-1065.

Remarks

*Overhead doors raise and lower smoothly, and can be locked in place.

4.

*Safety mechanisms are in place to prevent accidental or inadvertent closing.

1 2 3

Remarks

Roof: (Circle One) Shingle Metal Gravel Rolled Frangible Concrete Criteria:

3.

*Attachments are secure.

Remarks

*Exterior -- Clean, intact, and free from damage. Paint and caulking are in good condition and water tight.

2.

*Bay walls -- 12-in (305 mm) thick reinforced (2,500 psig) (17,236 kPa) concrete, in good condition, with no unauthorized attachments.

2 3

Remarks

9. Facility must have serviceable lightning protection and grounding systems. 1

1 2 3

Remarks

8.*Tool, supply, and equipment room.*Ready and training room.

*Approximately 1,500 sq. ft. (139 m2) administrative area.

Facility may need explosive-proof lighting fixtures if a Class I (explosive vapors) or Class II (explosive dust) environment is part of the mission.

*Placards -- Explosives limits and fire/chemical symbols are displayed. *Inspections -- Annual ground and explosives safety and facility inspections are performed.*Concurrent Operations -- MAJCOM interpretation of concurrent operations rules are being followed; factors must consider whether walls protrude through ceiling.

Remarks

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201, Q-D requirements are satisfied, net explosives weight limits are not exceeded, and commensurate measures are in-place. Any exceptions are properly identified and risk assessments are performed.

2

ARCHIVED

Page 36: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Floors: Criteria:

Ceiling : Criteria:

Criteria:

HVAC: Criteria:

*Filters are clean.

Facility Electrical: Criteria: *All wiring is in conduit.

*No hazardous materials [polychlorinated biphenyls (PCBs)] are present.*Transformers are free of leaks, are closed, and are weather-proof.*If required, appropriate surge protection devices will be installed.

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Generator and back-up power is available and in good repair.*Substations are away from explosives operations.*Switches and breakers contain lightning arrestors.

Facility Conditions (Continued) General ConditionsUnsatisfactorySatisfactory

Mission Impact**

*Start/stop control switch is properly mounted.*Damper controls and motors are in good working order.

*Ground devices are free of corrosion.*Support poles are in good condition and located at least 50 feet (15 m) away from facilities.

1 2

*Wiring is in conduits and insulation is intact.

*Stand-alone equipment (boiler and chiller units) is well maintained.

*Electrical control and switchgear is properly tagged, labeled, and housed.

9. 1 2 3

*Switch box plates are water and dust tight.

*Transfer switch and breaker panels are operable.*Junction boxes are spark-proof and watertight.

8.

*Switches are in spark-proof enclosures.

*Central equipment (heat exchangers, pumps, and fans) is clean and well maintained.*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.

1 2 3

Remarks

3

Remarks

*Permanently mounted systems are electrically bonded to the facility.

7.

*System in good repair.*Certification and proof-load records are up-to-date.*Traverse movement is smooth and unimpaired.

Hoist and Lifting Crane:

1 2 3

Remarks

6.

*No obvious hazards to personnel on the floor.*No visible damage, watermarks, or sagging.

1 2 3

Remarks

5.

*Concrete is in good condition, without cracks and with a smooth surface to allow easy equipment movement.

3

ARCHIVED

Page 37: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Criteria:

Criteria:

Criteria:

Satisfactory UnsatisfactoryMission Impact**Facility Conditions (Continued) General Conditions

*Fire Drills -- Conducted at least every six months.*Vegetation Control -- Exercised within 50 ft (15 m) of above-ground facilities.*Emergency Evacuation -- Sufficient stairs available (if applicable); when possible, a minimum of two 32-in (812 mm) wide outward-opening doors within 75 ft (23 m) for emergency evacuation.

*Pipes, Valves, and Fittings -- Outside components are protected from vehicles and other moving objects; piping penetrating the facility are grounded; and shut-off valves are readily accessible.

Natural Gas Storage and Distribution (as applicable):

Remarks

1 2 3

*Cathodic Protection -- a system must be installed, corrosion free, and the sacrificial plate (anode) volume is 25 % or +.

12.

*Steam and hot water lines are grounded.

*Fire Alarm -- Panel is marked and accessible.

Fire Protection/Prevention:

*Sprinkler System -- Piping is properly installed and supported; system is free of leaks; sprinkler heads are properly positioned; and the system shut-off valve is readily accessible and unobstructed.*AFFF and Carbon Dioxide Bottles -- Supported, secured, and inspections are current.

31

*Shut-off valves are clearly marked.

Plumbing and Mechanical Systems:

*Meters are operable.*Piping is free of corrosion and located away from moving equipment.*Valves and piping are free of leaks.

*Pressure regulators are installed and operable.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

1 2 3

*Heating Water Treatment -- Filters are properly installed and water-conditioning equipment is maintained current.*Steam/Hot Water Generation -- Temperature and cooling controls are operable; pressure valve is operable; lines are anchored; and system provides sufficient quantities.

Central Steam / Hot Water Generation and Distribution:

Remarks

13.

*Regulators --are accessible, supported, and leak-free.*Storage Tanks -- are securely anchored to their support structure, have pressure relief valves, are protected from vehicular damage, and tank surface and connections are free of corrosion.

Remarks

1 2 3

*Drainage systems support holding tanks, and drain and waste facilities are properly maintained.

Work Stoppage/Life-Safety Hazard

10.

*Halon System -- Inspections are current; instructions are posted; and halon bottles are supported and secured.

*Detectors -- Well-located and operable.

Remarks

11.2

*Piping penetrating the facility is grounded.

*Pull Stations -- Well-located and alarms are audible.

4

ARCHIVED

Page 38: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Pavements: Criteria:

Grounds: Criteria:

Criteria:

Criteria:

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

Remarks

1 218.

*Elevated Tanks -- Containment areas are free of debris; tanks are in good repair; and support structures are stable and in good repair.*Water Treatment -- Filters are installed and conditioning equipment is maintained.

Water Supply and Distribution: 2

*Erosion Control -- Area is free of erosion with suitable vegetation to help prevent erosion.*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.

1 2 3

*Fencing -- Security fencing is installed and is in good repair; vegetation is controlled around fencing; and rail-driven gates are operable.

*Pipes, Valves, and Fittings -- Located below grade; cathodic protection is installed; valves and meters are operable; and pipes entering the facility must be grounded.

Remarks

17.

*Well/Water Source -- Quality testing records are current and water supply is adequate.

1 3

*Sidewalks and Miscellaneous Pads -- Sidewalks are in good repair; pads are in good repair; and pads are sufficiently sized for equipment.

2 3

*Pipes, Valves, and Fittings -- Piping is located below grade; cathodic protection is installed; and valves, dehydrators, and meters are operable.

Remarks

15.

16. 1

2

Compressed Air Generation and Distribution:

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. No burnt out lights.

Remarks

*Parking -- Properly sited; sufficient room to maneuver; type of pavement supports gross weight of assigned equipment; adequate spaces; and lots are properly marked.*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

3

*Compressors -- Tank and accessories are secured; foundation is paved or padded; data plate is legible; and pressure regulators and release valves are operable.

14.

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.

Facility Conditions (Continued) General ConditionsSatisfactory Unsatisfactory

Mission Impact**

1

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.*LPS components are grounded and all metallic penetrations are bonded.*Side-flash protection is provided through separation.

Remarks*Meets NFPA 780 and MIL-HDBK-419 requirements.

3

*LPS inspection documentation is being properly maintained.

*Surge protection is provided.

Lightning Protection System (LPS) Installed:

5

ARCHIVED

Page 39: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

19. Lighting:Criteria:

20.Criteria:

21.Criteria:

22.Criteria:

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Tanks -- Supported and securely anchored; contents clearly labeled; free from corrosion; fitted with liquid level gauges; have vent devices; and located in bermed area to contain contents.*Secondary Containment -- Container free of cracks and leaks; sufficient for volume; free of litter and other objects. *Cathodic Protection -- Installed; free of corrosion; and sacrificial plate volume is 25% or more.

Remarks

*Piping, Valves, and Fittings -- Piping outside berm area is protected; piping penetrating facility is grounded; and no leaks.*Pumps -- Regulators installed and properly work; and maximum pressure placarded.

Liquid Fuel Storage and Distribution: 1 2 3

3

Satisfactory UnsatisfactoryFacility Conditions (Continued) General Conditions

Unique Local Facility Features:1 2 3

*Electrical cables are in good repair.

*General Illumination Guidelines -- Hallways require a minimum of 5 foot-candles (54 meter-candles) of light while detailed work may require 100 foot-candles (1,076 meter-candles). Bio-Environmental Engineering is contacted to ensure proper illumination is available.

21

Mission Impact**

2 3

*Fluorescent Fixtures -- If not designed with self-locking tubes, have a retaining device.*Stairs and Ramps -- Are illuminated with at least 5 foot-candles (54 meter-candles) of light.

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.*Computer Usage -- Lighting is adequate but not too bright to cause glare or discomfort.

Remarks

Remarks

*Unit is clean.

*Hoses and fittings are in good condition.*Fluid reservoir is operable.

*Service records are available and current.

Hydraulic Unit: 1

*No burnt out bulbs.

6

ARCHIVED

Page 40: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

No

Remarks

Yes No

IV. Summary

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes No

Yes

7

ARCHIVED

Page 41: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

*Does location of facility detract from mission performance?

Remarks

II. Mission Design Requirements Design Requirements Mission Impact**Meets Doesn't Meet

FACILITIES ASSESSMENT CHECKLISTCategory Code 216-642 -- Conventional Munitions Shop

Installation Name Location Facility Bldg NumberInsp. Date MAJCOM

Sq Footage Year Built Date Last Inspection

Meets Does Not MeetAssess the overall condition of the facility with respect to mission impact.

*Are there any outstanding AF Forms 332?*Does the base master plan reflect the current facility category code?

Facility Purpose: This facility accommodates munitions assembly/disassembly, corrosion control, time compliance technical order

Facility Componentscompletion, and repair on various munitions components and containers.

Mission Requirements

1 2 3

Remarks

1. Bay doors require high security hasps on bays if an intrusion detection system is being utilized.

1 2 3

Remarks

2. Bay doors a minimum 10 ft H X 16 ft W (3 m X 4.9 m) and loading dock size commensurate with asset size and handling requirements.

1 2 3

Remarks

3. Facility size depends on the munitions systems to be handled.

1 2 3

Remarks

4. Requires space for electrical power units and converter systems consisting of: *115VAC, 60 Hz single-phase electricity.*220VAC, 60 Hz, three-phase electricity (if applicable).

1 2 3

Remarks

5. One overhead traverse-mounted crane rated at 4,000 lbs. (1,814 kg) is required.

Remarks

7.

interpretation of concurrent operations rule).*Drive-through paint booth may be required dependent on mission.

Facility must have drive-through work bays. *A minimum of three 30 ft X 50 ft (9 m X 15 m) bays (dependent upon mission and

1 2

*Are there any safety or security write-ups on the facility from the latest inspections?*Does the facility user have the site plan available?

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Do the bays' size and shape meet mission needs?

*Does the facility design allow for known future mission changes?

3

1 2 3

Remarks

6. Facility requires a separate utility room for low air pressure system (150 psi (1,034 kPa) lines for each bay) and HVAC.

1

ARCHIVED

Page 42: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

Facility must have:

III.

1. Explosives Safety: Criteria:

1 2 3

Walls: Criteria:

*Free of leaks.

Doors: Criteria:

*Placards -- Explosives limits and fire/chemical symbols are displayed. *Inspections -- Annual ground and explosives safety and facility inspections are performed.*Concurrent Operations -- MAJCOM interpretation of concurrent operations rules are being followed; factors must consider whether walls protrude through ceiling.

*General -- Facility has good drainage and is vermin resistant.

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201, Q-D requirements are satisfied, net explosives weight limits are not exceeded, and commensurate measures are in-place. Any exceptions are properly identified and risk assessments are performed.

1 2 3

Remarks

8.*Tool, supply, and equipment room.*Ready and training room.

*Approximately 1,500 sq. ft. (139 m2) administrative area.

2 3

Remarks

9. Facility must have serviceable lightning protection and grounding systems.

Remarks

*Exterior -- Clean, intact, and free from damage. Paint and caulking are in good condition and water tight.

2.

*Bay walls -- 12-in (305 mm) thick reinforced (2,500 psig) (17,236 kPa) concrete, in good condition, with no unauthorized attachments.

1 2 3

Remarks

Roof: (Circle One) Shingle Metal Gravel Rolled Frangible Concrete Criteria:

3.

*Attachments are secure.

Remarks

*Overhead doors raise and lower smoothly, and can be locked in place.

4.

*Safety mechanisms are in place to prevent accidental or inadvertent closing.

Design Requirements

*Grounding -- A means to dissipate static electricity buildup is installed; static bonds and grounds are tested for resistance and continuity and records are on hand as per AFI 32-1065.

Mission Design Requirements (Continued)Meets Doesn't Meet

Mission Impact**

*Lighting -- Explosive-proof lights are used in Class I (explosives fuel/vapors) and Class II (explosives dust) environments; UL-approved lights are acceptable for all other environments.

*Latrine facilities.

Facility Conditions General Conditions Mission Impact**Satisfactory Unsatisfactory

1

*Wiring -- Wires to structures are underground at least 50 ft (15 m) away and have lightning arrestors and surge protection. Conduits require bonding to the facility at point of entry.*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements. *Windows -- Made of blast-resistant material.

*Interior -- Structural members and cross bracing are free from deterioration, caulking around wall penetrations watertight, and there are no unauthorized attachments that may compromise the design function.

1 2 3

Remarks

*No signs of failure, separation, or curling.

*Doors swing/roll freely and fit in jambs.*Locks and security hasps are in good condition.

1 2 3

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

2

ARCHIVED

Page 43: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Floors: Criteria:

Ceiling : Criteria:

Criteria:

HVAC: Criteria:

*Filters are clean.

Facility Electrical: Criteria: *All wiring is in conduit.

*Concrete is in good condition, without cracks and with a smooth surface to allow easy equipment movement.

1 2 3

Remarks

5.

1 2 3

Remarks

6.

*No obvious hazards to personnel on the floor.*No visible damage, watermarks, or sagging.

3

Remarks

*Permanently mounted systems are electrically bonded to the facility.

7.

*System is in good repair.*Certification and proof-load records are up-to-date.*Traverse movement is smooth and unimpaired.

Hoist and Lifting Crane:

8.

*Switches are in spark-proof enclosures.

*Central equipment (heat exchangers, pumps, and fans) is clean and well maintained.*Ductwork and accessories are well supported, insulation intact, and outlet diffusers are clean.

1 2 3

Remarks

Remarks

9. 1 2 3

*Switch box plates are water and dust tight.

*Transfer switch and breaker panels are operable.*Generator and back-up power is available and in good repair.

1 2

*Wiring is in conduits and insulation is intact.

*Stand-alone equipment (boiler and chiller units) is well maintained.

*Electrical control and switchgear is properly tagged, labeled, and housed.

*Start/stop control switch is properly mounted.*Damper controls and motors are in good working order.

*Ground devices are free of corrosion.*Support poles are in good condition and located at least 50' (15 m) away from facilities.

Facility Conditions (Continued) General ConditionsUnsatisfactorySatisfactory

Mission Impact**

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*If required, appropriate surge protection devices will be installed.

*Substations are away from explosives operations.*Switches and breakers contain lightning arrestors.*No hazardous materials [polychlorinated biphenyls (PCBs)] are present.*Transformers are free of leaks, are closed, and are weather-proof.

*Junction boxes are spark-proof and watertight.

Work Stoppage/Life-Safety Hazard

3

ARCHIVED

Page 44: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Criteria:

Criteria:

Criteria:

10.

*Halon System -- Inspections are current; instructions are posted; and halon bottles are supported and secured.

*Detectors -- Well-located and operable.

Remarks

11.2

*Piping penetrating the facility is grounded.

Remarks

1 2 3

*Drainage systems support holding tanks, and drain and waste facilities are properly maintained.

*Pull Stations -- Well-located and alarms are audible.

Work Stoppage/Life-Safety Hazard

12.

13.

*Regulators -- Are accessible, supported, and leak-free.*Storage Tanks -- Are securely anchored to their support structure, have pressure relief valves, are protected from vehicular damage, and tank surface and connections are free of corrosion.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

1 2 3

*Heating Water Treatment -- Filters are properly installed and water-conditioning equipment is maintained current.*Steam/Hot Water Generation -- Temperature and cooling controls are operable; pressure valve is operable; lines are anchored; and system provides sufficient quantities.

Central Steam / Hot Water Generation and Distribution:

*Shut-off valves are clearly marked.

Plumbing and Mechanical Systems:

*Meters are operable.*Piping is free of corrosion and located away from moving equipment.*Valves and piping are free of leaks.

*Pressure regulators are installed and operable.

*Steam and hot water lines are grounded.

*Fire Alarm -- Panel is marked and accessible.

Fire Protection/Prevention:

*Sprinkler System -- Piping is properly installed and supported; system is free of leaks; sprinkler heads are properly positioned; and the system shut-off valve is readily accessible and unobstructed.*AFFF and Carbon Dioxide Bottles -- Supported, secured, and inspections are current.

31

*Fire Drills -- Conducted at least every six months.*Vegetation Control -- Exercised within 50 ft (15 m) of above-ground facilities.*Emergency Evacuation -- Sufficient stairs available (if applicable); when possible, a minimum of two 32-in (812 mm) wide outward-opening doors within 75 ft (23 m) for emergency evacuation.

*Pipes, Valves, and Fittings -- Outside components are protected from vehicles and other moving objects; piping penetrating the facility is grounded; and shut-off valves are readily accessible.

Natural Gas Storage and Distribution (as applicable):

Remarks

1 2 3

*Cathodic Protection -- A system is installed, corrosion free, and the sacrificial plate (anode) volume is 25 % or more.

Remarks

Facility Conditions (Continued) General ConditionsSatisfactory Unsatisfactory

Mission Impact**

4

ARCHIVED

Page 45: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Pavements: Criteria:

Grounds: Criteria:

Criteria:

Criteria:

*Meets NFPA 780 and MIL-HDBK-419 requirements.

3

*LPS inspection documentation being properly maintained.

Remarks

18.

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.*LPS components are grounded and all metallic penetrations are bonded.*Side-flash protection is provided through separation.*Surge protection is provided.

General Conditions

*Parking -- Properly sited; sufficient room to maneuver; type of pavement supports gross weight of assigned equipment; adequate spaces; and lots are properly marked.

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.

Facility Conditions (Continued)Mission Impact**

Compressed Air Generation and Distribution: Satisfactory Unsatisfactory

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. No burnt out lights.

Remarks

16. 1

1 2

*Sidewalks, Structures, and Miscellaneous Pads -- Sidewalks are in good repair; pads are in good repair; and pads are sufficiently sized for equipment.

2 3

*Pipes, Valves, and Fittings -- Piping is located below grade; cathodic protection is installed; and valves, dehydrators, and meters are operable.

Remarks

15.

*Well/Water Source -- Quality testing records are current and water supply is adequate.

Remarks

*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

3

*Compressors -- Tank and accessories are secured; foundation is paved or padded; data plate is legible; and pressure regulators and release valves are operable.

14. 1 2 3

*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to prevent erosion.*Fencing -- Security fencing is installed and is in good repair; vegetation is controlled around fencing; and rail-driven gates are operable.

*Pipes, Valves, and Fittings -- Located below grade; cathodic protection is installed; valves and meters are operable; and pipes entering the facility must be grounded.

Remarks

17.

*Elevated Tanks -- Containment areas are free of debris; tanks are in good repair; and support structures are stable and in good repair.*Water Treatment -- Filters are installed and conditioning equipment is maintained.

Water Supply and Distribution: 1 2 3

Lightning Protection System (LPS) Installed: 1 2

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

5

ARCHIVED

Page 46: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

19. Lighting:Criteria:

20.CriteriaUnique Local Facility Features: 1 2 3

Work Stoppage/Life-Safety Hazard

IV. Summary

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes No

YesYes No

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.*Computer Usage -- Lighting is adequate but not too bright to cause glare or discomfort.

Remarks

Remarks

*No burnt out bulbs.

No

Remarks

*General Illumination Guidelines -- Hallways require a minimum of 5 foot-candles (54 meter-candles) of light while detailed work may require 100 foot-candles (1,076 meter-candles). Bio-Environmental Engineering is contacted to ensure proper illumination is available.

*Fluorescent Fixtures -- If not designed with self-locking tubes, must a retaining device.*Stairs and Ramps -- Are illuminated with at least 5 foot-candles (54 meter-candles) of light.

21

Mission Impact**Satisfactory Unsatisfactory

3

Facility Conditions (Continued) General Conditions

6

ARCHIVED

Page 47: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

One overhead hoist:

8. Electrical Power Requirements.*Non-Powered Trailers -- 120 and 220VAC, 60 Hz.

Remarks*Powered trailers -- 120, 220, and 440 VAC 60 Hz (440VAC outlets copiously spaced in and around facility).

*Does the facility design allow for known future mission changes?

1 2 3

Remarks

6. Facility requires a separate utility room for low air pressure system (120 psig (827 kPa) lines for each bay) and HVAC.

*Do the bays' size and shape meet mission needs?

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*Are there any safety or security write-ups on the facility from the latest inspections?

Work Stoppage/Life-Safety Hazard

Remarks

7. Facility must have drive-through work bays with adjacent work benches. *Number of bays dependent upon mission and number of assigned trailers.

1 2 3

1 2 3

Remarks

5.*For Powered trailers -- Minimum 10-ton (10,160 kg) capacity.

1 2 3

Remarks

4. For powered munitions trailers, an additional 230 sq ft (21 m2) is authorized for each additional trailer stored indoors. (Consult the MAJCOM CE and Munitions functionals for indoor trailer storage requirements.)

1 2 3

Remarks

3. Facility size depends on the amount of assigned support equipment. Refer to AFH 32-1084, Table 7.9, for space requirements.

Remarks

2. Bay door size must be commensurate with the size of the support equipment.

Facility Purpose: This facility is used to inspect, maintain, repair, and service assigned powered and non-powered Munitions Materiel

Facility ComponentsMission Requirements

Insp. Date MAJCOMSq Footage Year Built Date Last Inspection

FACILITIES ASSESSMENT CHECKLISTCategory Code 218-712 -- Aircraft Support Equipment Shop/Storage Facility [Aerospace Ground

Installation Name Location Facility Bldg NumberEquipment (AGE) Facility] -- Used for Munitions Support Equipment Maintenance

Remarks

II. Mission Design Requirements Design Requirements Mission Impact**

1

Doesn't MeetProper ventilation and exhaust systems installed and functional in administrative office area and maintenance work bays.

1 2 3

*Are there any outstanding AF Forms 332?*Does the base master plan reflect the current facility category code?

Remarks

1.

Handling Equipment (MMHE).

*Does location of facility detract from mission performance?

Meets Does Not MeetAssess the overall condition of the facility with respect to mission impact.

*Does the facility user have the site plan available if the facility is located within the explosives clear zone arc?

*For Non-powered Trailers -- Minimum 5-ton (5,080 kg) capacity.

Meets

2 3

1 2 3

1

ARCHIVED

Page 48: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

Facility must have:

11.1 2 3

12.

III.

1. Explosives Safety: Criteria:

1 2 3

Walls: Criteria:

*Free of leaks.

Doors: Criteria:

*Complies with OSHA, EPA, and state environmental control measures.

Wash Rack (Indoor or Outdoor).*Equipped with hot and cold running water.*Has floor drainage with an oil-water separator.*Has power receptacles and compressed air.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*No signs of failure, separation, or curling.

*Doors swing/roll freely and fit in jambs.*Locks and security hasps are in good condition.

1 2 3

*Windows -- Made of blast-resistant material if within the explosives clear zone.

*Interior -- Structural members and cross bracing are free from deterioration, adequate soundproofing insulation installed, caulking around wall penetrations watertight, and there are no unauthorized attachments that may compromise the design function.

1 2 3

Remarks*General -- Facility has good drainage and is vermin resistant.

*Latrine facilities.

Facility Conditions General Conditions Mission Impact**Satisfactory Unsatisfactory

1

Mission Design Requirements (Continued)Meets Doesn't Meet

Mission Impact**Design Requirements

Remarks

*Overhead doors raise and lower smoothly, and can be locked in place.

4.

*Safety mechanisms are in place to prevent accidental or inadvertent closing.

1 2 3

Remarks

Roof: (Circle One) Shingle Metal Gravel Rolled Frangible Concrete Criteria:

3.

*Attachments are secure.

Remarks

*Exterior -- Clean, intact, and free from damage. Paint and caulking are in good condition and water tight.

2.

2 3

Remarks

10. Facility must have serviceable lightning protection system as per NFPA 780, Chapter 3 (Ordinary Structures).

1 2 3

Remarks

9.*Tool, supply, bench stock, and equipment room.*Ready and/or training room with personnel lockers available.

*Approximately 1,500 sq ft (139 m2) administrative area.

Remarks

Remarks

If facility is located within the explosives clear zone, facility must be constructed with DDESB approval since it would be considered an exposed site.

*Inspections -- Annual ground safety and facility inspections are performed.

*Siting Requirements -- If required, facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201. Any exceptions are properlyidentified and risk assessments are performed.

2

ARCHIVED

Page 49: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Floors: Criteria:

Ceiling : Criteria:

Criteria:

HVAC: Criteria:

*Filters are clean.

Facility Electrical: Criteria: *All wiring is in conduit.

Work Stoppage/Life-Safety Hazard

UnsatisfactorySatisfactoryMission Impact**

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*If required, appropriate surge protection devices are installed.

*May need explosive-proof fixtures.*Switches and breakers contain lightning arrestors.*No hazardous materials [polychlorinated biphenyls (PCBs)] are present.*Transformers are free of leaks, are closed, and are weather-proof.

*Junction boxes are spark-proof and watertight.

Facility Conditions (Continued) General Conditions

*Start/stop control switch is properly mounted.*Damper controls and motors are in good working order.

*Ground devices are free of corrosion.*Support equipment may have special electrical requirements.

1 2

*Wiring is in conduits and insulation is intact.

*Stand-alone equipment (boiler and chiller units) is well maintained.

*Electrical control and switchgear is properly tagged, labeled, and housed.

Remarks

9. 1 2 3

*Switch box plates are water and dust tight.

*Transfer switch and breaker panels are operable.*Generator and back-up power is available and in good repair.

8.

*Switches are in spark-proof enclosures.

*Central equipment (heat exchangers, pumps, and fans) is clean and well maintained.*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.

1 2 3

Remarks

3

Remarks

*Permanently mounted systems will be electrically bonded to the facility.

7.

*System is in good repair.*Certification and proof-load records are up-to-date.*Traverse movement is smooth and unimpaired.

Hoist and Lifting Crane:

1 2 3

Remarks

6.

*No obvious hazards to personnel on the floor.*No visible damage, watermarks, or sagging.

1 2 3

Remarks

5.

*Concrete is in good condition, without cracks and with a smooth surface to allow easy equipment movement.*Adequate drainage with oil-water separator in maintenance work bays.

3

ARCHIVED

Page 50: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Criteria:

Criteria:

Criteria:

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Facility Conditions (Continued) General ConditionsSatisfactory Unsatisfactory

Mission Impact**

*Fire Drills -- Conducted at least every six months.*Vegetation Control -- Exercised around the facility.*Emergency Evacuation -- Sufficient stairs available (if applicable); when possible, a minimum of two 32-in (812 mm) wide outward-opening doors within 75 ft (23 m) for emergency evacuation.

*Pipes, Valves, and Fittings -- Outside components are protected from vehicles and other moving objects; piping penetrating the facility are grounded; and shut-off valves are readily accessible.

Natural Gas Storage and Distribution (as applicable):

Remarks

1 2

*Flammable and combustible materials are properly stored.*Facility is clean.

*Cathodic Protection -- A system must be installed, corrosion free, and the sacrificial plate (anode) volume is 25% or more.

*Steam and hot water lines are grounded.

*Fire Alarm -- Panel is marked and accessible.

Fire Protection/Prevention:

*Sprinkler System -- Piping is properly installed and supported; system is free of leaks; sprinkler heads are properly positioned; and the system shut-off valve is readily accessible and unobstructed.*AFFF and Carbon Dioxide Bottles -- Supported, secured, and inspections are current.

3

*Fire extinguishers readily available.

*Emergency eyewash and shower stations installed.

*Shut-off valves are clearly marked.

Plumbing and Mechanical Systems:

*Meters are operable.*Piping is free of corrosion and located away from moving equipment.*Valves and piping are free of leaks.

*Pressure regulators are installed and operable.

1 2 3

Work Stoppage/Life-Safety Hazard

1 2 3

*Heating Water Treatment -- Filters are properly installed and water-conditioning equipment is maintained current.

12.

13.

*Regulators -- Are accessible, supported, and leak-free.*Storage Tanks -- Are securely anchored to their support structure, have pressure relief valves, are protected from vehicular damage, and tank surface and connections are free of corrosion.

Remarks

3

*Drainage systems support holding tanks, and drain and waste facilities are properly maintained.

*Pull Stations -- Well-located and alarms are audible.

*Steam/Hot Water Generation -- Temperature and cooling controls are operable; pressure valve is operable; lines are anchored; and system provides sufficient quantities.

Central Steam / Hot Water Generation and Distribution:

10.

*Halon System -- Inspections are current; instructions are posted; and halon bottles are supported and secured.

*Detectors -- Well-located and operable.

Remarks

11. 2

*Piping penetrating the facility is grounded.

1

4

ARCHIVED

Page 51: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Pavements: Criteria:

Grounds: Criteria:

Criteria:

Criteria:

3

*Compressors -- Tank and accessories are secured; foundation is paved or padded; data plate is legible; and pressure regulators and release valves are operable.

14.

1 2

2 3

Lightning Protection System (LPS) Installed: 1 2

*Elevated Tanks -- Containment areas are free of debris; tanks are in good repair; and support structures are stable and in good repair.*Water Treatment -- Filters are installed and conditioning equipment is maintained.

Water Supply and Distribution: 1 2 3

*Pipes, Valves, and Fittings -- Located below grade; cathodic protection is installed; valves and meters are operable; and pipes entering the facility must be grounded.

*Well/Water Source -- Quality testing records are current and water supply is adequate.

Remarks

17.

*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

gates are operable.

*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to help prevent erosion.*Fencing (if applicable) -- Security fencing is installed and is in good repair; vegetation is controlled around fencing; and rail-driven

Remarks

*Sidewalks and Miscellaneous Pads -- Sidewalks are in good repair; pads are in good repair; and pads are sufficiently sized for equipment.

2 3

*Pipes, Valves, and Fittings -- Piping is located below grade; cathodic protection is installed; and valves, dehydrators, and meters are operable.

Remarks

15.

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations; and no burnt out lights.

Remarks

16. 1

*Parking -- Properly sited; sufficient room to maneuver; type of pavement supports gross weight of assigned equipment; adequate spaces; and lots are properly marked.

1Compressed Air Generation and Distribution:

Mission Impact**

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.

Facility Conditions (Continued) General ConditionsSatisfactory Unsatisfactory

*Meets NFPA 780 and MIL-HDBK-419 requirements.

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.*LPS components are grounded and all metallic penetrations are bonded.*Surge protection is provided.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

3

*LPS inspection documentation being properly maintained.

Remarks

18.

5

ARCHIVED

Page 52: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

19. Lighting:Criteria:

20.Criteria:

21.Criteria:

22.Criteria:

*Tanks -- Supported and securely anchored; contents clearly labeled; free from corrosion; fitted with liquid level gauges; have vent devices; and located in bermed area to contain contents.*Secondary Containment -- Container free of cracks and leaks; sufficient for volume; free of litter and other objects. *Cathodic Protection -- Installed; free of corrosion; and sacrificial plate volume is 25% or more.

Remarks

2 3

*Piping, Valves, and Fittings -- Piping outside berm area is protected; piping penetrating facility is grounded; and no leaks.*Pumps -- Regulators installed and properly work; and maximum pressure placarded.

Liquid Fuel Storage and Distribution (as applicable): 1

21

Mission Impact**Satisfactory Unsatisfactory

Unique Local Facility Features:1 2 3

*Electrical cables are in good repair.

Remarks

*Unit is clean.

*Hoses and fittings are in good condition.*Fluid reservoir is operable.

*Service records are available and current.

1

*Fluorescent Fixtures -- If not designed with self-locking tubes, must have a retaining device.*Stairs and Ramps -- Must be illuminated with at least 5 foot-candles (54 meter-candles) of light.

3

*General Illumination Guidelines -- Hallways require a minimum of 5 foot-candles (54 meter-candles) of light while detailed work may require 100 foot-candles (1,076 meter-candles). Bio-Environmental Engineering is contacted to ensure proper illumination is available.

Remarks

Facility Conditions (Continued) General Conditions

Hydraulic Unit (as applicable):

Yes NoNo

Remarks

Work Stoppage/Life-Safety Hazard

IV. Summary

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes No

Yes

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.*Computer Usage -- Lighting is adequate but not too bright to cause glare or discomfort.

Remarks

2 3

*No burnt out bulbs.

6

ARCHIVED

Page 53: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

ARCHIVED

Page 54: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

6.1 2 3

7.1 2 3

Meets

Remarks

3

Remarks

1. Constructed of concrete.

*Does location of facility detract from mission performance?

Remarks

II. Mission Design Requirements Design Requirements Mission Impact**Doesn't Meet

FACILITIES ASSESSMENT CHECKLISTCategory Code 422-253 -- Multi-cubicle Magazine Storage

Installation Name Location Facility Bldg NumberInsp. Date MAJCOM

Sq Footage Year Built Date Last Inspection

Meets Does Not MeetAssess the overall condition of the facility with respect to mission impact.

*Are there any outstanding AF Forms 332?*Does the base master plan reflect the current facility category code?

Facility Purpose: This facility is used to store small quantities of explosives. Facilities are ideal for segregating compatibility groups and storing munitions assets belonging to custody accounts.Facility Components

Mission Requirements

1 2

1 2 3

Remarks

2. Doors are made of steel and are the hinged, roll-up, or rolling type.

1 2 3

Remarks

3. Constructed with approval of the DDESB.

1 2 3

Remarks

4. Size dependent upon mission needs.

*Are there any safety or security write-ups on the facility from the latest inspections?

*Does the facility user have the site plan available?

Work Stoppage/Life-Safety Hazard

Remarks

5. Facility requires a serviceable lightning protection system.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Doors must have high-security hasps. May need an intrusion detection system.

*Does the multi-cubicle magazine size and shape meet mission needs?

Facility may require HVAC for climate control.

*Does the facility design allow for known future mission changes?

1 2 3

Remarks

1

ARCHIVED

Page 55: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

8.

III.

1. Explosives Safety: Criteria:

1 2 3

Criteria:

*Free of leaks.

4.Criteria:

5.Criteria:

*Roll-up doors must raise and lower smoothly.

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201, Q-D requirements are satisfied, net explosives weight limits are not exceeded, and commensurate measures are in-place. Any exceptions are properly identified and risk assessments are performed.

*General -- Facility has good drainage and is vermin resistant.

*Individual cells -- If 12-in (305 mm) reinforced concrete substantial dividing walls or equivalent protection is used, up to 425 lbs. (193 kg) of 1.1 munitions may be stored in each bay without totaling up the NEW of the entire facility or requiring compatibility with the adjoining cells. Store munitions a minimum of 3 ft (.9 m) from any dividing wall (see AFMAN 91-201).

Remarks

*Must meet "2 degree" rule.

2.

*No substantial erosion.*Top of barricade wall must be at least 3 ft ( .9 m) wide.

1 2 3

*Interior -- Surfaces clean, intact, and free from damage; no unauthorized attachments that may compromise the design function; and caulking around wall penetrations watertight.

3

Remarks

Roof: Criteria:

3.

*Attachments are secure.

1 2

Walls:

*Exterior -- Clean; free from damage; intact; paint and caulking in good condition.

3

2

Facility Conditions General ConditionsUnsatisfactory

Mission Impact**

Apron in front of door must permit safe operation of handling equipment. 3

Remarks

Remarks

*No signs of failure.

1 2

Remarks

Doors:1

Mission Design Requirements (Continued) Design RequirementsMeets Doesn't Meet

*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements.

Barricade Walls (if applicable):

1 2

*Placards -- Explosives limits and fire/chemical symbols are displayed. Signs may be posted on the individual doors.*Inspections -- Annual ground and explosives safety and facility inspections are performed.

Mission Impact**Satisfactory

3

*Doors swing/roll freely and fit in jambs.*Locks and security hasps are in good condition.*Safety mechanisms are in place to prevent accidental closing.*Serviceable ramps to traverse thresholds (If required).

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

2

ARCHIVED

Page 56: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

6.Criteria:

7. Ceiling:Criteria:

Criteria:

Pavements: Criteria:

Grounds: Criteria:

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.

1

*Facility is kept clean and free of combustible materials.

39.

*Fire Drills -- Conducted at least every six months.

Remarks

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. No burnt out lights.

Remarks

10. 1

*Parking -- Properly sited; sufficient room to maneuver; and type of pavement supports gross weight of assigned equipment.

*Pads -- Pads are in good repair; and pads are sufficiently sized for equipment.

2 3

*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

Fire Protection/Prevention: 3

*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to help prevent erosion.

2

*Fencing -- Security fencing is installed and is in good repair; and vegetation is controlled around fencing. Remarks

Facility Conditions (Continued) General ConditionsSatisfactory Unsatisfactory

Mission Impact**

Floors: 1 3 3

*Concrete is in good condition without cracks and with a smooth surface to allow easy equipment movement.Remarks

1 2 3

*No visible damage or watermarks.*No obvious hazards to personnel on the floor.

Remarks

*Vegetation Control -- Exercised within 50 ft (15 m) of above-ground facilities.*Fire extinguishers are available during operations.

*Flammables and combustibles are not stored in close proximity to the facility.

8.21

3

ARCHIVED

Page 57: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

11.Criteria:

12.Criteria:

Criteria:

14. Lighting:Criteria:

15Criteria:***

General ConditionsFacility Conditions (Continued)Mission Impact**

Satisfactory Unsatisfactory

*No burnt out bulbs.

Remarks

21 3

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.

Remarks

Remarks

*Meets NFPA 780 and MIL-HDBK-419 requirements.

3

*LPS inspection documentation being properly maintained.

Lightning Protection System (LPS) Installed: 2

Unique Local Facility Features:1 2 3

3HVAC:

*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.

Remarks

1 2

*Central equipment is clean and well maintained.*Wiring is in conduits and insulation is intact.

2 3

*All wiring is in conduit.*Ground devices are free of corrosion.

Facility Electrical:1

*Support poles are in good condition and located at least 50' (15 m) away from facilities.*Switch box plates are water and dust tight.

*Junction boxes are spark-proof and watertight.*Switches and breakers contain lightning arrestors.

*Switches are in spark-proof enclosures.

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

13.

*General Illumination Guidelines -- Bio-Environmental Engineering is contacted to ensure proper illumination is available.

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.

1

4

ARCHIVED

Page 58: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

No

IV. Summary

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes No

YesYes

No

Remarks

5

ARCHIVED

Page 59: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

3

5. Constructed with approval of the DDESB. 1 2 3

3

*Do the facility's size and shape meet mission needs?

1

Remarks

2

*Does the facility design allow for known future mission changes?

*Are there any safety or security write-ups on the facility from the latest inspections?*Does the facility user have the site plan or license available?

Remarks

6. Facility must have serviceable lightning protection and grounding systems.

1 2

Remarks

12-in (305 mm) thick reinforced concrete walls must be present so the rockets can face the walls during maintenance operations and storage.

4.

1 2 3

Remarks

3. Facility size is 11,160 sq ft (1,037 m2) but may vary dependent on the weapons being used. Size includes field office area.

1 2 3

Remarks

2. Bay doors must be a minimum of 3/8 in (19 mm) thick steel.

1 2 3

Remarks

1. Bay doors require high security hasps. An intrusion detection system may be required.

Facility Purpose: This facility is unique in that it serves as an operating location to accommodate the assembly, disassembly, and electrical check out of rockets as well as providing a site to store built-up rockets. Since the advent of the MK 66 rocket, electrical continuity checks of rocket motors is rare. The facility is now often used for other operations (e.g., flare and chaff buildup, argon recharging, etc.). Facility Components

Mission RequirementsMeets Does Not Meet

Assess the overall condition of the facility with respect to mission impact.

Insp. Date MAJCOMSq Footage Year Built Date Last Inspection

FACILITIES ASSESSMENT CHECKLISTCategory Code 422-256 -- Rocket Check Out and Assembly Storage

Installation Name Location Facility Bldg Number

*Are there any outstanding AF Forms 332?*Does the base master plan reflect the current facility category code?

*Does location of facility detract from mission performance?

Remarks

II. Mission Design Requirements Design Requirements Mission Impact**Meets Doesn't Meet

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

1

ARCHIVED

Page 60: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

1. Explosives Safety: Criteria:

1 2 3

Walls: Criteria:

*Free of leaks.

Doors: Criteria:

Floors: Criteria:

Ceiling : Criteria:

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*No signs of failure, separation, or curling.

*Doors swing freely and fit in jambs.*Locks and security hasps are in good condition.

1 2 3

1 2 3

*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements.

*Interior -- Structural members and cross bracing are free from deterioration, caulking around wall penetrations watertight, and there are no unauthorized attachments that may compromise the design function.

1 2 3

Remarks

*Facilities Located Outside the MSA -- Has an approved license.

Facility Conditions General Conditions Mission Impact**Satisfactory Unsatisfactory

*Grounding -- A means to dissipate static electricity buildup is installed; static bonds and grounds are tested for resistance and continuity and records are on hand as per AFI 32-1065.*Lighting -- Explosive-proof lights are used in Class I (explosives fuel/vapors) and Class II (explosives dust) environments; UL-approved lights are acceptable for all other environments.*Wiring -- Wires to structures are underground at least 50 ft (15 m) away and have lightning arrestors and surge protection. Conduits require bonding to the facility at point of entry.

Remarks

6.

*No obvious hazards to personnel on the floor.*No visible damage, watermarks, or sagging.

1 2 3

Remarks

5.

Remarks

4.

*Safety mechanisms are in place to prevent accidental or inadvertent closing.

1 2 3

Remarks

Roof: (Circle One) Shingle Metal Gravel Rolled Frangible Concrete Criteria:

3.

*Attachments are secure.

Remarks

*Exterior -- Clean, intact, and free from damage. Paint and caulking are in good condition and water tight.

2.

*Bay walls -- 12-in (305 mm) thick reinforced (2,500 psig) (17,236 kPa) concrete, in good condition, with no unauthorized attachments.

*General -- Facility has good drainage and is vermin resistant.

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201, Q-D requirements are satisfied, net explosives weight limits are not exceeded, and commensurate measures are in-place. Any exceptions are properly identified and risk assessments are performed. See AFMAN 91-201 for special guidance on ES and PES categorization.

*Placards -- Explosives limits and fire/chemical symbols are displayed. *Inspections -- Annual ground and explosives safety and facility inspections are performed.*Concurrent Operations -- MAJCOM interpretation of concurrent operations rules are being followed; factors must consider whether walls protrude through ceiling.

*Concrete is in good condition, without cracks and with a smooth surface to allow easy equipment movement.

*Smoking prohibited within 50 ft (15 m) of explosives.*Windows -- Made of blast-resistant material.

2

ARCHIVED

Page 61: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

HVAC: Criteria:

*Filters are clean.

Facility Electrical: Criteria: *All wiring is in conduit.

Criteria:

*Switches and breakers contain lightning arrestors and surge protection.*No hazardous materials [polychlorinated biphenyls (PCBs)] are present.*Transformers are free of leaks, are closed, and are weather-proof.

*Junction boxes are spark-proof and watertight.

UnsatisfactorySatisfactoryMission Impact**

*Substations are away from explosives operations.

*Start/stop control switch is properly mounted.*Damper controls and motors are in good working order.

*Ground devices are free of corrosion.*Support poles are in good condition and located at least 50 feet (15 m) away from facilities.

*Wiring is in conduits and insulation is intact.

*Stand-alone equipment (boiler and chiller units) is well maintained.

Facility Conditions (Continued) General Conditions

1

*Fire Drills -- Conducted at least every six months.

*Vegetation Control -- Exercised within 50 ft (15 m) of above-ground facilities.*Emergency Evacuation -- A minimum of two 32-in (812 mm) wide outward-opening doors within 75 ft (23 m) for emergency evacuation.

Remarks

*White Phosphorous (WP) -- A water supply (e.g., barrel) and a safety kit containing flame-proof gloves, face shield, and skin covering, must be available when handling unpackaged WP items.

*Electrical control and switchgear is properly tagged, labeled, and housed.

*Halon System -- Inspections are current; instructions are posted; and halon bottles are supported and secured.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Pull Stations -- Well-located and alarms are audible.*Detectors -- Well-located and operable.

9.2

Remarks

*Fire Alarm -- Panel is marked and accessible.

Fire Protection/Prevention:

*Sprinkler System -- Piping is properly installed and supported; system is free of leaks; sprinkler heads are properly positioned; and the system shut-off valve is readily accessible and unobstructed.*AFFF and Carbon Dioxide Bottles -- Supported, secured, and inspections are current.

3

8. 1 2 3

*Switch box plates are water and dust tight.

*Transfer switch and breaker panels are operable.

7.

*Switches are in spark-proof enclosures.

*Central equipment (heat exchangers, pumps, and fans) is clean and well maintained.*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.

1 2 3

Remarks

3

ARCHIVED

Page 62: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Criteria:

Pavements: Criteria:

Grounds: Criteria:

Criteria: 3

*Parking -- Properly sited; sufficient room to maneuver; and type of pavement supports gross weight of assigned equipment.

*Fencing -- Security fencing is installed and is in good repair; and vegetation is controlled around fencing.

*Pipes, Valves, and Fittings -- Located below grade; cathodic protection is installed; valves and meters are operable; and pipes entering the facility must be grounded.

Remarks

14. Water Supply and Distribution: 1 2

13. 1

*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

3

*Sidewalks and Miscellaneous Pads -- Sidewalks are in good repair; pads are in good repair; and pads are sufficiently sized for equipment.

2 3

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.

Facility Conditions (Continued) General Conditions

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. No burnt out lights.

Satisfactory UnsatisfactoryMission Impact**

3

*Compressors -- Tank and accessories are secured; foundation is paved or padded; data plate is legible; and pressure regulators and release valves are operable.

12.

11. Plumbing and Mechanical Systems:

*Pressure regulators are installed and operable.*Shut-off valves are clearly marked.

*Drainage systems support holding tanks, and drain and waste facilities are properly maintained.*Meters are operable.*Piping is free of corrosion and located away from moving equipment.*Valves and piping are free of leaks.

2 3

*Pipes, Valves, and Fittings -- Piping is located below grade; cathodic protection is installed; and valves, dehydrators, and meters are operable.

*Piping penetrating the facility is grounded.

Compressed Air Generation and Distribution (as applicable): 1

1 2

Remarks

*Well/Water Source -- Quality testing records are current and water supply is adequate.

Remarks

1 2

*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to prevent erosion.

*Elevated Tanks -- Containment areas are free of debris; tanks are in good repair; and support structures are stable and in good repair.*Water Treatment -- Filters are installed and conditioning equipment is maintained.

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

Remarks

*Steam and hot water lines are grounded.

10.

4

ARCHIVED

Page 63: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Criteria:

17. Lighting:Criteria:

18.Criteria

21 3

*Meets NFPA 780 and MIL-HDBK-419 requirements.

3

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.*LPS components are grounded and all metallic penetrations are bonded.

1 2 3

*Assembly Stands -- Are secured to the facility or workbench and must be grounded.

Remarks

Work Stoppage/Life-Safety Hazard

16.

*General Illumination Guidelines -- Are illuminated with at least 5 foot-candles (54 meter-candles) of light. Detailed work may require 100 foot-candles (1,076 meter-candles) . Bio-Environmental Engineering is contacted to ensure proper illumination is available.

*LPS inspection documentation being properly maintained.

*Fluorescent Fixtures -- If not designed with self-locking tubes, must have a retaining device.*Ramps -- Are illuminated with at least 5 foot-candles (54 meter-candles) of light.

*Side-flash protection is provided through separation.

Unique Local Facility Features: 1 2 3

*Surge protection is provided.

Remarks

15. Installed Support Equipment:

Lightning Protection System (LPS) Installed: 1 2

*Storage Racks -- Are securely affixed to the facility..

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.*Computer Usage -- Lighting is adequate but not too bright to cause glare or discomfort.

Remarks

Remarks

*No burnt out bulbs.

Facility Conditions (Continued) General ConditionsMission Impact**

Satisfactory Unsatisfactory

5

ARCHIVED

Page 64: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

No

Remarks

IV. Summary

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes No

YesYes No

6

ARCHIVED

Page 65: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

6.1 2 3

7.1 2 3

Remarks

*Does the magazine size and shape meet mission needs?

Facility may require HVAC for climate control.

*Does the facility design allow for known future mission changes?

1 2 3

Doors must have high-security hasps. May need an intrusion detection system.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

5. Facility requires a serviceable lightning protection system.

*Are there any safety or security write-ups on the facility from the latest inspections?

*Does the facility user have the site plan available?

Work Stoppage/Life-Safety Hazard

Remarks

1 2 3

Remarks

4. Size dependent upon mission needs.

1 2 3

Remarks

3. Constructed with approval of the DDESB.

Remarks

2. Doors are made of steel and are the hinged, roll-up, or rolling type.

2

1 2 3

Facility Purpose: This facility is used to store small quantities of explosives. Facilities are ideal for segregating compatibility groups and storing munitions assets belonging to custody accounts.Facility Components

Mission Requirements

1

Meets Does Not MeetAssess the overall condition of the facility with respect to mission impact.

*Are there any outstanding AF Forms 332?*Does the base master plan reflect the current facility category code?

Insp. Date MAJCOMSq Footage Year Built Date Last Inspection

FACILITIES ASSESSMENT CHECKLISTCategory Code 422-257 -- Segregated Magazine Storage

Installation Name Location Facility Bldg Number

*Does location of facility detract from mission performance?

Remarks

II. Mission Design Requirements Design Requirements Mission Impact**Doesn't MeetMeets

Remarks

3

Remarks

1. Constructed of concrete.

1

ARCHIVED

Page 66: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

8.

III.

1. Explosives Safety: Criteria:

1 2 3

Criteria:

*Free of leaks.

4.Criteria:

5.Criteria:

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Locks and security hasps are in good condition.*Safety mechanisms are in place to prevent accidental closing.*Serviceable ramps to traverse thresholds (If required).

Remarks

3

*Doors swing/roll freely and fit in jambs.

*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements.

Barricade Walls (if applicable):

1 2

*Placards -- Explosives limits and fire/chemical symbols are displayed. *Inspections -- Annual ground and explosives safety and facility inspections are performed.

Mission Impact**Satisfactory

Mission Design Requirements (Continued) Design RequirementsMeets Doesn't Meet

1 2

Remarks

Doors:1

Remarks

*No signs of failure.

Unsatisfactory

Mission Impact**

Apron in front of door must permit safe operation of handling equipment. 3

Remarks

Facility Conditions General Conditions

1 2

Walls:

*Exterior -- Clean; free from damage; intact; paint and caulking in good condition.

3

2

3

*Interior -- Surfaces clean, intact, and free from damage; no unauthorized attachments that may compromise the design function; and caulking around wall penetrations watertight.

3

Remarks

Roof: Criteria:

3.

*Attachments are secure.

*Individual cells -- If 12-in (305 mm) reinforced concrete substantial dividing walls or equivalent protection is used, up to 425 lbs. (195 kg) of 1.1 munitions may be stored in each bay without totaling up the NEW of the entire facility or requiring compatibility with the adjoining cells. Store munitions a minimum of 3 ft (.9 m) from any dividing wall (see AFMAN 91-201).

Remarks

*Meets "2 degree" rule.

2.

*No substantial erosion.*Top of barricade wall are at least 3 ft (.9 m) wide.

1 2

*General -- Facility has good drainage and is vermin resistant.

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201, Q-D requirements are satisfied, net explosives weight limits are not exceeded, and commensurate measures are in-place. Any exceptions are properly identified and risk assessments are performed.

*Roll-up doors must raise and lower smoothly.

2

ARCHIVED

Page 67: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

6.Criteria:

7. Ceiling:Criteria:

Criteria:

Pavements: Criteria:

Grounds: Criteria:

*Fire extinguishers are available during operations.

*Flammables and combustibles are not stored in close proximity to the facility.

8.21

*No visible damage or watermarks.*No obvious hazards to personnel on the floor.

Remarks

*Vegetation Control -- Exercised within 50 feet (15 m) of above-ground facilities.

*Concrete is in good condition without cracks and with a smooth surface to allow easy equipment movement.Remarks

1 2 3

Satisfactory UnsatisfactoryMission Impact**

Floors: 1 3 3

Facility Conditions (Continued) General Conditions

*Fencing -- Security fencing is installed and is in good repair; and vegetation is controlled around fencing. Remarks

*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to help prevent erosion.

2

*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

Fire Protection/Prevention: 3

*Pads -- Pads are in good repair; and pads are sufficiently sized for equipment.

2 3

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. No burnt out lights.

Remarks

10. 1

*Parking -- Properly sited; sufficient room to maneuver; and type of pavement supports gross weight of assigned equipment.

39.

*Fire Drills -- Conducted at least every six months.

Remarks

*Facility is kept clean and free of combustible materials.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.

1

3

ARCHIVED

Page 68: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

11.Criteria:

12.Criteria:

Criteria:

14. Lighting:Criteria:

15Criteria:

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

13.

*General Illumination Guidelines -- Bio-Environmental Engineering is contacted to ensure proper illumination is available.

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.

1

*Support poles are in good condition and located at least 50' (15 m)away from facilities.*Switch box plates are water and dust tight.

*Junction boxes are spark-proof and watertight.*Switches and breakers contain lightning arrestors.

*Switches are in spark-proof enclosures.

2 3

*All wiring is in conduit.*Ground devices are free of corrosion.

Facility Electrical:1

3HVAC:

*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.

Remarks

1 2

*Central equipment is clean and well maintained.*Wiring is in conduits and insulation is intact.

Unique Local Facility Features:1 2 3

*Meets NFPA 780 and MIL-HDBK-419 requirements.

3

*LPS inspection documentation being properly maintained.

Lightning Protection System (LPS) Installed: 2

Remarks

21 3

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.

Remarks

Remarks

*No burnt out bulbs.

UnsatisfactoryGeneral ConditionsFacility Conditions (Continued)

Mission Impact**Satisfactory

4

ARCHIVED

Page 69: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

No

Remarks

IV. Summary

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes No

YesYes No

5

ARCHIVED

Page 70: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

7.1 2 3

8.1 2 3

Meets

Remarks

3

Remarks

1. Constructed of various non-combustible materials (e.g., steel, concrete, clay tile, sheet metal, etc.).

Doesn't Meet

2

1 2

*Does location of facility detract from mission performance?

Remarks

II. Mission Design Requirements Design Requirements Mission Impact**

FACILITIES ASSESSMENT CHECKLISTCategory Code 422-258 -- Above Ground Magazine Storage

Installation Name Location Facility Bldg NumberInsp. Date MAJCOM

Sq Footage Year Built Date Last Inspection

Meets Does Not MeetAssess the overall condition of the facility with respect to mission impact.

*Are there any outstanding AF Forms 332?*Does the base master plan reflect the current facility category code?

Facility Purpose: This facility is used to store all types of explosives. Facility Components

Mission Requirements

1

3

Remarks

2. Doors are made of steel and be hinged, sliding, or roll-up type.

1 2 3

Remarks

3. Constructed with approval of the DDESB.

1 2 3

Remarks

4. Size dependent upon mission needs.

3

Remarks

5. Provides limited protection from propagating explosions to/from adjacent storage sites and operating locations.

1 2

*Are there any safety or security write-ups on the facility from the latest inspections?

*Does the facility user have the site plan available?

Work Stoppage/Life-Safety Hazard

Remarks

6. Facility requires a serviceable lightning protection system.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Doors must have high-security hasps. May need an intrusion detection system.

*Does the igloo size and shape meet mission needs?

Facility may require HVAC for climate control.

*Does the facility design allow for known future mission changes?

1 2 3

Remarks

1

ARCHIVED

Page 71: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

9.

III.

1. Explosives Safety: Criteria:

1 2 3

Criteria:

*Free of leaks.

4.Criteria:

5.Criteria:

*Lighting -- Explosive-proof lights are used in Class I (explosives fuel/vapors) and Class II (explosives dust) environments; UL-approved lights are acceptable for all other environments.*Wiring -- Wires to structures are underground at least 50 feet (15 m) away and have lightning arrestors and surge protection. Conduits require bonding to the facility at point of entry.

*Overhead doors must raise and lower smoothly.

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201, Q-D requirements are satisfied, net explosives weight limits are not exceeded, and commensurate measures are in-place. Any exceptions are properly identified and risk assessments are performed.

*General -- Facility has good drainage and is vermin resistant.

Remarks

*Meets "2 degree" rule.

2.

*No substantial erosion.*Top of barricade wall is at least 3 ft. (.9 m) wide.

1 2 3

*Interior -- Surfaces clean, intact, and free from damage; no unauthorized attachments that may compromise the design function; and caulking around wall penetrations watertight.

3

Remarks

Roof: (Circle One) Rolled Metal Shingle Frangible Gravel Concrete Criteria:

3.

*Attachments are secure.

3

1 2

*Earth-covering at least 24 in. (609 mm) deep (if applicable).*No excessive erosion (if earth-covered).

Walls:

*Exterior -- Clean; free from damage; intact; paint and caulking in good condition.

Facility Conditions General ConditionsUnsatisfactory

Mission Impact**

Apron in front of door must permit safe operation of handling equipment. 3

Remarks

Remarks

*No signs of failure.

1 2

Remarks

Doors:1

Mission Design Requirements (Continued) Design RequirementsMeets Doesn't Meet

*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements.

Barricade Walls (if applicable):

1 2

*Placards -- Explosives limits and fire/chemical symbols are displayed. *Inspections -- Annual ground and explosives safety and facility inspections are performed.

Mission Impact**Satisfactory

2 3

*Doors swing/roll freely and fit in jambs.*Locks and security hasps are in good condition.*Safety mechanisms are in place to prevent accidental closing.*Serviceable ramps to traverse thresholds (If required).

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

2

ARCHIVED

Page 72: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

6.Criteria:

7. Ceiling:Criteria:

Criteria:

Pavements: Criteria:

Grounds: Criteria:

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.

1

*Facility is kept clean and free of combustible materials.

39.

*Fire Drills -- Conducted at least every six months.

Remarks

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. No burnt out lights.

Remarks

10. 1

*Parking -- Properly sited; sufficient room to maneuver; and type of pavement supports gross weight of assigned equipment.

Miscellaneous Pads -- Pads are in good repair; and pads are sufficiently sized for equipment.

2 3

*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

Fire Protection/Prevention: 3

*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to help prevent erosion.

2

*Fencing -- Security fencing is installed and is in good repair; and vegetation is controlled around fencing. Remarks

Facility Conditions (Continued) General ConditionsSatisfactory Unsatisfactory

Mission Impact**

Floors: 1 3 3

*Concrete is in good condition without cracks and with a smooth surface to allow easy equipment movement.Remarks

1 2 3

*No visible damage or watermarks.*No obvious hazards to personnel on the floor.

Remarks

*Ventilator fusible links are serviceable.

*Vegetation Control -- Exercised within 50 ft (15 m) of above-ground facilities and within 5 ft (1.5 m) of ventilators.*Fire extinguishers are available during operations.

*Flammables and combustibles are not stored in close proximity to the facility.

8.21

*Emergency Evacuation -- Sufficient stairs available (if applicable); when possible, a minimum of two 32-in (812 mm) wide outward-opening doors within 75 ft (23 m) for emergency evacuation.

3

ARCHIVED

Page 73: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

11.Criteria:

12.Criteria:

Criteria:

14. Lighting:Criteria:

15.Criteria:

General ConditionsFacility Conditions (Continued)Mission Impact**

Satisfactory Unsatisfactory

*No burnt out bulbs.

Remarks

21

Work Stoppage/Life-Safety Hazard

2

3

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.

Lightning Protection System (LPS) Installed:

Remarks

Remarks

Unique Local Facility Features: 1 2 3

3HVAC:

*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.Remarks

1 2

3

*All wiring is in conduit.*Ground devices are free of corrosion.

Facility Electrical:1

13.

*General Illumination Guidelines -- Bio-Environmental Engineering is contacted to ensure proper illumination is available.

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.

1

*Meets NFPA 780 and MIL-HDBK-419 requirements.

3

*LPS inspection documentation being properly maintained.

*If required, appropriate surge protection devices will be installed.Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*Support poles are in good condition and located at least 50 ft (15 m) away from facilities.*Switch box plates are water and dust tight.

*Junction boxes are spark-proof and watertight.*Switches and breakers contain lightning arrestors.

*Switches are in spark-proof enclosures.

2

4

ARCHIVED

Page 74: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Remarks

No

IV. Summary

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes No

NoYesYes

5

ARCHIVED

Page 75: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

7.1 2 3

8.1 2 3

Remarks

*Does the igloo size and shape meet mission needs?

Facility may require HVAC for climate control.

*Does the facility design allow for known future mission changes?

1 2 3

1 2

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Doors must have high-security hasps. May need an intrusion detection system.

6. Facility requires a serviceable lightning protection system.

*Are there any safety or security write-ups on the facility from the latest inspections?

*Does the facility user have the site plan available?

Work Stoppage/Life-Safety Hazard

3

Remarks

5. Must provide protection from propagating explosions to/from adjacent storage sites and operating locations.

1 2 3

Remarks

4. Size dependent upon mission needs. (Typical size is 26 ft X 80 ft of 7.9 m X 24.3 m). .

1 2 3

Remarks

3. Constructed with approval of the DDESB.

1 2 3

Remarks

2. Doors are made of heavy blast-resistant steel.

3

Remarks

1. Constructed of steel or concrete arch. 2

Facility Purpose: This facility is used to store all types of explosives. It is the preferred structure for storing mass-detonating explosives. Facility Components

Mission Requirements

1

Meets Does Not MeetAssess the overall condition of the facility with respect to mission impact.

*Are there any outstanding AF Forms 332?*Does the base master plan reflect the current facility category code?

Insp. Date MAJCOMSq Footage Year Built Date Last Inspection

FACILITIES ASSESSMENT CHECKLISTCategory Code 422-264 -- Storage Igloo

Installation Name Location Facility Bldg Number

*Does location of facility detract from mission performance?

Remarks

II. Mission Design Requirements Design Requirements Mission Impact**Doesn't MeetMeets

Remarks

1

ARCHIVED

Page 76: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

9.

III.

1. Explosives Safety: Criteria:

1 2 3

Criteria:

*Free of leaks.

4.Criteria:

5.Criteria:

*Lighting -- Explosive-proof lights are used in Class I (explosives fuel/vapors) and Class II (explosives dust) environments; UL-approved lights are acceptable for all other environments.*Wiring -- Wires to structures are underground at least 50 ft (15 m) away and have lightning arrestors and surge protection. Conduits require bonding to the facility at point of entry.

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Doors swing/roll freely and fit in jambs.*Locks and security hasps are in good condition.*Safety mechanisms are in place to prevent accidental closing.*Serviceable ramps to traverse thresholds (if required).

Remarks

Doors:1 2 3

*Interior -- Surfaces clean, intact, and free from damage; no unauthorized attachments that may compromise the design function; and caulking around wall penetrations watertight.

1 2

3

Remarks

*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements.

Barricade Walls (if applicable):

1 2

*Placards -- Explosives limits and fire/chemical symbols are displayed. *Inspections -- Annual ground and explosives safety and facility inspections are performed.

Mission Design Requirements (Continued) Design RequirementsMeets Doesn't Meet

Remarks

*No signs of failure.

3

Mission Impact**Satisfactory Unsatisfactory

Mission Impact**

Apron in front of door must permit safe operation of handling equipment.

Facility Conditions General Conditions

1 2

*Earth-covering at least 24 in (609 mm) deep.*No excessive erosion.

Walls:

*Front wall -- Clean; free from damage; and intact.*Minimum 24 inches (609 mm ) earth-covering on rear and side walls.

3

Remarks

Roof: (Circle One) Steel Concrete Criteria:

3.

*Attachments are secure.

Remarks

*Meets "2 degree" rule.

2.

*No substantial erosion.*Top of barricade wall is at least 3 ft (.9 m) wide.

1 2 3

*General -- Facility has good drainage and is vermin resistant.

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201, Q-D requirements are satisfied, net explosives weight limits are not exceeded, and commensurate measures are in-place. Any exceptions are properly identified and risk assessments are performed.

2

ARCHIVED

Page 77: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

6.Criteria:

7. Ceiling:Criteria:

Criteria:

Pavements: Criteria:

Grounds: Criteria:

*No visible damage or watermarks.*No obvious hazards to personnel on the floor.

Remarks

*Ventilator fusible links are serviceable.

*Vegetation Control -- Exercised within 50 ft (15 m) of above-ground facilities and within 5 ft (1.5 m) of ventilators.*Fire extinguishers are available during operations.

*Flammables and combustibles are not stored in close proximity to the facility.

8.2

*Concrete is in good condition without cracks and with a smooth surface to allow easy equipment movement.Remarks

1 2 3

Satisfactory UnsatisfactoryMission Impact**

Floors:1 3 3

Facility Conditions (Continued) General Conditions

*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to help prevent erosion.*Fencing -- Security fencing is installed and is in good repair; and vegetation is controlled around fencing.

Remarks

*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

3

Fire Protection/Prevention: 31

*Parking -- Properly sited; sufficient room to maneuver; and type of pavement supports gross weight of assigned equipment.

*Miscellaneous Pads -- Pads are in good repair; and pads are sufficiently sized for equipment.

2 3

Remarks

10. 1

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.

1 2

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. No burnt out lights.

9.

*Fire Drills -- Conducted at least every six months.

Remarks

*Facility is kept clean and free of combustible materials.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

3

ARCHIVED

Page 78: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

11.Criteria:

12.Criteria:

Criteria:

14. Lighting:Criteria:

15.Criteria:

*LPS inspection documentation being properly maintained.*An LPS is Installed -- System features include air terminals and low impedance paths to ground.

*If required, appropriate surge protection devices are installed.Remarks

*Support poles are in good condition and located at least 50 ft (15 m) away from facilities.*Switch box plates are water and dust tight.

*Junction boxes are spark-proof and watertight.*Switches and breakers contain lightning arrestors.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

13.

*General Illumination Guidelines -- Bio-Environmental Engineering is contacted to ensure proper illumination is available.

*Surge protection is provided.

1

*Meets NFPA 780 and MIL-HDBK-419 requirements.

*Switches are in spark-proof enclosures.

2 3

*All wiring is in conduit.*Ground devices are free of corrosion.

Facility Electrical:1

3HVAC:

*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.Remarks

1 2

Unique Local Facility Features:1 2 3

3

*Side-flash protection is provided through separation.

Lightning Protection System (LPS) Installed: 2

*LPS components are grounded and all metallic penetrations are bonded.

Remarks

21 3

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.

Remarks

Remarks

*No burnt out bulbs.

General ConditionsFacility Conditions (Continued)Mission Impact**

Satisfactory Unsatisfactory

4

ARCHIVED

Page 79: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

No

Remarks

IV. Summary

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes No

YesYes No

5

ARCHIVED

Page 80: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

7.1 2 3

8.1 2 3

(See NFPA 780, Chapter 3, Ordinary Structures)

Remarks

*Does the facility size and shape meet mission needs?

Facility may require HVAC for climate control.

*Does the facility design allow for known future mission changes?

1 2 3

1 2

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Doors may have high-security hasps depending on contents. May need an intrusion detection system.

6. Facility requires a serviceable lightning protection system if it is determined the safety of the personnel and value of the facility and/or stored assets warrant it.

*Are there any safety or security write-ups on the facility from the latest inspections?

*Does the facility user have the site plan available (if applicable)?

Work Stoppage/Life-Safety Hazard

3

Remarks

5. Provides limited protection from propagating explosions from adjacent storage sites and operating locations.

1 2 3

Remarks

4. Size dependent upon mission needs.

1 2 3

Remarks

3. Constructed with approval of the DDESB if within the explosives clear zone.

1 2 3

Remarks

2. Doors vary in size and are made of steel and be hinged, sliding, or roll-up type.

3

Remarks

1. Constructed of various non-combustible materials (e.g., steel, concrete, clay tile, sheet metal, etc.).

2

Facility Purpose: This facility is used to store all types of inert munitions components.Facility Components

Mission Requirements

1

Meets Does Not MeetAssess the overall condition of the facility with respect to mission impact.

*Are there any outstanding AF Forms 332?*Does the base master plan reflect the current facility category code?

Insp. Date MAJCOMSq Footage Year Built Date Last Inspection

FACILITIES ASSESSMENT CHECKLISTCategory Code 422-265 -- Inert Spares Storage

Installation Name Location Facility Bldg Number

*Does location of facility detract from mission performance?

Remarks

II. Mission Design Requirements Design Requirements Mission Impact**Doesn't MeetMeets

Remarks

1

ARCHIVED

Page 81: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

9.

10.1 2 3

III.

1. Explosives Safety: Criteria:

1 2 3

*Free of leaks.

3.Criteria:

4.Criteria:

Work Stoppage/Life-Safety Hazard

1 2 3

1 2

1 2

Remarks

Facility must be identified as a warehouse to store accountable munitions components.

*Inspections -- Annual ground and explosives safety and facility inspections are performed (as required).

Mission Design Requirements (Continued) Design RequirementsMeets Doesn't Meet

3

Remarks

*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements.

Remarks

*No signs of failure.

3

Mission Impact**Satisfactory Unsatisfactory

Mission Impact**

Apron in front of door must permit safe operation of handling equipment.

Facility Conditions General Conditions

1 2

Walls:

*Exterior -- Clean; free from damage; intact; paint and caulking in good condition.*Interior -- Surfaces clean, intact, and free from damage; no unauthorized attachments that may compromise the design function; and caulking around wall penetrations watertight.

3

Remarks

Remarks

Doors:

2.

*Doors swing/roll freely and fit in jambs.*Locks and security hasps are in good condition.*Safety mechanisms are in place to prevent accidental closing.*Serviceable ramps to traverse thresholds (If required).

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*Attachments are secure.

Roof: (Circle One) Rolled Metal Shingle Frangible Gravel Concrete Criteria:

*General -- Facility has good drainage and is vermin resistant.

*Siting Requirements -- Facility is sited as an exposed site if within the explosives clear zone as per DoD 6055.9 STD and AFMAN 91-201.

*Overhead doors must raise and lower smoothly.

2

ARCHIVED

Page 82: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

5.Criteria:

6. Ceiling:Criteria:

Criteria:

Pavements: Criteria:

Grounds: Criteria:

*No visible damage or watermarks.*No obvious hazards to personnel on the floor.

Remarks

*Vegetation Control -- Exercised within 50 ft (15 m) of above-ground facilities.*Fire extinguishers are available during operations.

*Flammables and combustibles are properly stored in the facility.

7.2

*Emergency Evacuation -- Suffifient stairs available (if applicable); when possible, a minimum of two 36-in (.9 m) doors within 75 ft

*Concrete is in good condition without cracks and with a smooth surface to allow easy equipment movement.Remarks

1 2 3

Floors:1 3 3

Facility Conditions (Continued) General ConditionsSatisfactory Unsatisfactory

Mission Impact**

*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to help prevent erosion.*Fencing -- Security fencing is installed and is in good repair; and vegetation is controlled around fencing.

Remarks

*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

3

Fire Protection/Prevention: 31

*Parking -- Properly sited; sufficient room to maneuver; and type of pavement supports gross weight of assigned equipment.

*Miscellaneous Pads -- Pads are in good repair; and pads are sufficiently sized for equipment.

2 3

Remarks

9. 1

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.

1 2

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. No burnt out lights.

Remarks

8.

*Fire Drills -- Conducted at least every six months.

*Facility is kept clean and free of combustible materials.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

3

ARCHIVED

Page 83: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

10.Criteria:

11.Criteria:

Criteria:

13. Lighting:Criteria:

14Criteria:

*If required, appropriate surge protection devices will be installed.Remarks

2 3

*All wiring is in conduits.*Ground devices are free of corrosion.

Facility Electrical:

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*Switch box plates are water and dust tight.*Junction boxes are watertight.*Switches and breakers contain lightning arrestors.

*Surge protection is provided.

*LPS inspection documentation being properly maintained.

Lightning Protection System (LPS) Installed (if applicable): 2

Work Stoppage/Life-Safety Hazard

12.

*General Illumination Guidelines -- Bio-Environmental Engineering is contacted to ensure proper illumination is available.

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.

1

*Meets NFPA 780, Chapter 3 (Ordinary Structures), and MIL-HDBK-419 requirements.

3

1

3HVAC:

*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.Remarks

1 2

Unique Local Facility Features:1 2 3

Remarks

21 3

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.

Remarks

Remarks

*No burnt out bulbs.

UnsatisfactoryGeneral ConditionsFacility Conditions (Continued)

Mission Impact**Satisfactory

4

ARCHIVED

Page 84: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

No

Remarks

IV. Summary

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes No

YesYes No

5

ARCHIVED

Page 85: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

magazines do not exist. Outdoor storage is considered a temporary expedient measure and is not preferred for munitions.

Meets

*Does location of facility detract from mission performance?

Remarks

II. Mission Design Requirements Design Requirements Mission Impact**Doesn't Meet

2 3

Remarks

FACILITIES ASSESSMENT CHECKLISTCategory Code 422-271 -- Module Barricaded Storage

Installation Name Location Facility Bldg NumberInsp. Date MAJCOM

Sq Footage Year Built Date Last Inspection

Meets Does Not MeetAssess the overall condition of the facility with respect to mission impact.

*Are there any outstanding AF Forms 332?*Does the base master plan reflect the current facility category code?

Facility Purpose: This facility provides field storage of large quantities of explosives in minimum land areas where earth-covered

Facility ComponentsMission Requirements

11. Barricade walls constructed of non-fragmenting materials (typically soil with no large rocks or debris in it). May have a non-combustible lightweight shed orroof covering.

1 2 3

Remarks

2. Pads may be asphalt, concrete, rock, AM-2 matting or packed soil.

1 2 3

Remarks

3. Constructed with approval of the DDESB and the responsible MAJCOM.

3

Remarks

4. Size dependent upon mission needs. 1 2

*Are there any safety or security write-ups on the facility from the latest inspections?*Does the facility user have the site plan available?

Work Stoppage/Life-Safety Hazard** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*Does the facility design allow for known future mission changes?

1 2 3

1 2 3

Remarks

5. Must provide protection from propagating explosions to/from adjacent storage sites and operating locations.

Remarks

6. Facility requires a serviceable lightning protection system.

1

ARCHIVED

Page 86: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

1. Explosives Safety: Criteria:

1 2 3

Barricade Walls: Criteria:

*Free of leaks.

Criteria:

Pavements: Criteria:

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Placards -- Explosives limits and fire/chemical symbols are displayed. *Inspections -- Annual ground and explosives safety and facility inspections are performed.*General -- Facility has good drainage.

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201, Q-D requirements are satisfied, net explosives weight limits are not exceeded, and commensurate measures are in-place. Any exceptions are properly identified and risk assessments are performed.

*Pad permits uninhibited stacking of assets and use of handling equipment.

Remarks

*Meets "2 degree" rule.

2.

*No substantial erosion.*Top of barricade wall is at least 3 ft (.9 m) wide.

1 2 3

2 3

Remarks

Roof: (Circle One) Metal Rolled Frangible Criteria:

3.

*Attachments are secure.

5.

*Fire Drills -- Conducted at least every six months.

*Facility is kept clean and free of combustible materials.

*Vegetation Control -- Exercised within 50 ft (15 m) of above-ground facilities.*Fire extinguishers are available during operations.

Remarks

Facility Conditions General Conditions

Remarks

Mission Impact**Satisfactory Unsatisfactory

Remarks

*No signs of failure, separation, or curling.

Fire Protection/Prevention: 31

4.2

1

*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

3

*Parking -- Properly sited; sufficient room to maneuver; type of pavement supports gross weight of assigned equipment; adequate spaces; and lots are properly marked.

*Flammables and combustibles are not stored in close proximity to the facility.

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.

1 2

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. No burnt out lights.

2

ARCHIVED

Page 87: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Grounds: Criteria:

Criteria:

8. Lighting:Criteria:

9.Criteria:

Work Stoppage/Life-Safety Hazard

IV. Summary

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes

Yes No

Facility Conditions (Continued) General ConditionsMission Impact**

Satisfactory Unsatisfactory

*Meets NFPA 780 and MIL-HDBK-419 requirements.

3

*LPS inspection documentation being properly maintained.

Lightning Protection System (LPS) Installed: 2

No

Remarks

Remarks

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.

Remarks

Remarks

*No burnt out bulbs.

No

Yes

7.

*General Illumination Guidelines -- Bio-Environmental Engineering is contacted to ensure proper illumination is available.

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.

21 3

1

Unique Local Facility Features:1 2 3

6. 1

*Miscellaneous Pads -- Pads are in good repair; adequate drainage is available; and pads are sufficiently sized for equipment.

2 3

*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to help prevent erosion.*Fencing -- Security fencing is installed and is in good repair; and vegetation is controlled around fencing.

Remarks

3

ARCHIVED

Page 88: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

II.a.

*Does the facility's shape and size meet mission needs?*Does the facility user have a copy of the site plan available?

Mission Design RequirementsGeneral Requirements

*Are there any safety or security write-ups on the facility from the latest inspections?

Doesn't Meet

*Does the facility meet Q-D and facility guideline requirements?*Does the facility design allow for known future mission changes?*Does location of facility detract from mission performance?

Remarks

Design Requirements Mission Impact**Meets

*Are there any outstanding AF Forms 332?

2 3

Remarks

3. Ground surfaces may require paving or other hardened surface (AM-2 matting, stone, etc.) as warranted by traffic and operational requirements.

1

2 3

Remarks

2. Fencing may be required based upon security needs and location of assets.

Overhead cover may be required to protect personnel from the sun and other elements.

1

Facility Components

included are rail classification yards, holding yards, inspection stations, interchange yards, loading docks, ready explosives facilities, and bomb preload stations/MAC pads. The facility Is primarily used for holding, inspecting, temporarily storing, transferring, or loading munitions in the transportation or handling mode.

Mission Requirements

2 3

*Does the base master plan reflect the current facility category code?

1

Does Not MeetAssess the overall condition of the facility with respect to mission impact.

*Do the systems and sub-systems operate as designed?

Sq Footage Year Built Date Last InspectionFacility Purpose: This designation is applicable to pads, locations, revetments, and other facilities (excluding aircraft parking). Facilities

FACILITIES ASSESSMENT CHECKLISTCategory Code 422-275 -- Ancillary Explosives Facility

Installation Name Location Facility Bldg NumberInsp. Date MAJCOM

Note: The quantity and type of ancillary explosives facilities required will vary with the following conditions: - Operational mission requirements; number and type of functions, operations, or special munitions activities.- Type and quality of munitions to be stored or handled; war reserve materiel (WRM) munitions, operating and training munitions, combat munitions, and special activities as area reserve storage/redistribution/munitions airlift.- Site characteristics; physical limits, expansion capabilities, type, and arrangement of existing facilities, and objectives of the base master plan.-Type of proposed storage structures required or preferred.

Meets

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Remarks

1.

Work Stoppage/Life-Safety Hazard

1

ARCHIVED

Page 89: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

b.1.

2.

3.

4.

5.

6. Lightning protection is required. 1 2 3

Remarks

3base.

Remarks

Remarks

Rails and related track material must be bonded, grounded, and insulated from the 1 2 3

1 2

Classification Yard Requirements (used for receiving, dispatching and switching rail cars containing explosives)

1 2 3Rail trackage will have standard gauge, clearance, and weight as required by interstate/host nation regulations.

Remarks

Rail trackage will connect with the common carrier delivering shipments to the

remaining track.

Remarks

7. Paved surfaces are sufficient to handle traffic volume, and vehicle and munitions materiel handling equipment turning radii and gross weights. 1 2 3

Remarks

Amount of rail trackage dependent upon volume of traffic. 1 2 3

Remarks

1 2 34. Barricades may be required based upon the location, quantity, and class of explosives involved.

Remarks

5. Access roads may be required.

Design RequirementsMission Design Requirements (Continued)Meets Doesn't Meet

Mission Impact**

2 3

Remarks

2Tracks should be looped to permit two ways to exit. 31

1

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

2

ARCHIVED

Page 90: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

6.

7.

c.

1.

2.

3.

4.

5.

6.

Remarks

Vegetation control is strictly enforced along trackage (as applicable).

Remarks

Tracks should be looped to permit two ways to exit (as applicable). 1 2 3

Remarks

Rails and related track material must be bonded, grounded, and insulated from the 1 2 3remaining track (as applicable).

Remarks

Rail trackage will have standard gauge, clearance, and weight as required by 1 2 3interstate/host nation regulations (as applicable).

1 2 3

Holding Yard Requirements (area used to hold explosives-laden carriers for limited periods -- may contain rail cars, ISO containers, or trucks)

1 2 3

2 3classification yard.

Remarks

Intermagazine quantity-distance criteria applies between other PESs and the 1

2 3

Remarks

Vegetation control is strictly enforced along trackage. 1

Sited as above ground magazines.

Remarks

Area size dependent upon mission needs.

Remarks

1 2 3

Work Stoppage/Life-Safety Hazard

Mission Design Requirements (Continued) Design Requirements Mission Impact**Meets Doesn't Meet

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

3

ARCHIVED

Page 91: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

7.

d.

1.

2.

3.

4.

5.

6.

Inspection Station Requirements (used to accommodate trucks or rail cars during the time incoming vehicles and their explosives cargo are inspected)

1 2 3Quantity-distance criteria does not apply if solely used as an inspection station.

Remarks

2 3populated areas, flightlines, and other explosives.

Remarks

Located as remote as possible from hazardous areas such as POL sites, 1

2 3

Remarks

Area size dependent upon mission needs. 1

2 3interstate/host nation regulations (as applicable).

Remarks

Rail trackage will have standard gauge, clearance, and weight as required by 1

2 3remaining track (as applicable).

Remarks

Rails and related track material must be bonded, grounded, and insulated from the 1

3

Remarks

Tracks should be looped to permit two ways to exit (as applicable). 1 2

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

2 3

Remarks

If designated as a Secure Holding Area as per the Defense Transportation 1

*Access control.*Perimeter fencing.*Automatically-timed lighting positioned to not expose/silhouette guards and extend 25 ft (7.6 m) beyond the secure holding area.*Barriers at entry control points.*Emergency communications to include a duress system to notify law enforcement personnel.*Primary and emergency power that starts automatically when primary power fails.

Mission Design Requirements (Continued) Design Requirements Mission Impact**Meets Doesn't Meet

Regulation, Chapter 205, it must comply with DoD 5100.76M:

*IDS or CCTV if guard does not have direct visual observation of the area.*Warning signs posted every 100 ft (30 m).

4

ARCHIVED

Page 92: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

7.

e.

1.

2.

3.

4.

5.

6.

7.

1 2 3

Mission Design Requirements (Continued) Design Requirements Mission Impact**Meets Doesn't Meet

Vegetation control is strictly enforced along trackage (as applicable).

Remarks

Quantity-distance criteria does not apply if the exchange is made and the 1 2 3vehicle/railcars are moved promptly.

Remarks

Located as remote as possible from hazardous areas such as POL sites, 1 2 3populated areas, flightlines, and other explosives.

Remarks

May be located together with the Inspection Station. 1 2 3

Remarks

Area size dependent upon mission needs. 1 2 3

Remarks

Rail trackage will have standard gauge, clearance, and weight as required by 1 2 3interstate/host nation regulations (as applicable).

Remarks

Rails and related track material must be bonded, grounded, and insulated from the 1 2 3remaining track (as applicable).

Remarks

Tracks should be looped to permit two ways to exit (as applicable). 1 2 3

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

Interchange Yard Requirements (used for the interchange of explosives-laden trucks, trailers, or rail cars between the common carrier and DoD activities)

5

ARCHIVED

Page 93: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

8.

f.

1.

2.

3.

4.

5.

6.

7.

Vegetation control is strictly enforced along trackage (as applicable). 1 2 3

Mission Design Requirements (Continued)

Remarks

Site the loading dock as an operating location if used to transfer munitions 1 2 3between transportation modes.

Remarks

Loading docks used to support multiple storage or operating locations are 1 2 3considered above-ground magazines for quantity-distance purposes.

Remarks

Quantity-distance criteria does not apply to loading docks used to support a single 1 2 3PES.

3interstate/host nation regulations (as applicable).

Remarks

Area size dependent upon mission needs. 1 2 3

Work Stoppage/Life-Safety Hazard

Remarks

Rails and related track material must be bonded, grounded, and insulated from the 1 2 3remaining track (as applicable).

Remarks

Tracks should be looped to permit two ways to exit (as applicable). 1 2 3

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Remarks

Remarks

Rail trackage will have standard gauge, clearance, and weight as required by 1 2

Loading Dock Requirements (ground-level or elevated structure used for transferring explosives between any two modes of transportation)

Design Requirements Mission Impact**Meets Doesn't Meet

6

ARCHIVED

Page 94: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

8.

g.

1.

h.

1.

III. Facility Conditionsa.1. Explosives Safety:

Criteria: 1 2 3

*Windows -- Made of blast-resistant material. *Smoking prohibited within 50 ft (15 m) of explosives.

General

1

Mission Impact**

1 2 3

2

*Grounding -- A means to dissipate static electricity buildup (as applicable); static bonds and grounds are tested for resistance and continuity and records are on hand as per AFI 32-1065.

General ConditionsSatisfactory Unsatisfactory

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201, Q-D requirements are satisfied, net explosives weight limits are not exceeded, and commensurate measures are in place. Any exceptions are properly identified and risk assessments are performed.*Placards -- Explosives limits and fire/chemical symbols are displayed. *Inspections -- Annual ground and explosives safety and facility inspections are performed.

2. All electrical equipment installed and maintained in accordance with explosives safety requirements.

Remarks

3

Remarks

3. On-site safety placarding safety information is provided and is legible.

*Lighting -- Explosive-proof lights are used in Class I (explosives fuel/vapors) and Class II (explosives dust) environments; UL-approved lights are acceptable for all other environments.*Wiring -- Wires to structures are underground at least 50 ft (15 m) away and have lightning arrestors and surge protection. Conduits require bonding to the facility at point of entry.

*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements. *General -- Facility has good drainage.

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

31 2

2 3

Remarks

Ready Explosives Facility Requirements (facility or designated area, usually near the flightline, where munitions and components are temporarily positioned awaiting transfer to aircraft--may be used for combat aircraft or as a cargo marshalling area)Site the ready explosives facility as an above-ground magazine. 1

Site the bomb preload station as an operating location. 1

Bomb Preload Station Requirements (Munitions Assembly Conveyor -- consists of equipment such as gantries and conveyors used to inspect, assemble, and load bombs on ejection racks--equipment configuration dependent upon mission)

2 3

Remarks

Remarks

Vegetation control is strictly enforced along trackage (as applicable).

Mission Design Requirements (Continued) Design Requirements Mission Impact**Meets Doesn't Meet

7

ARCHIVED

Page 95: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Criteria:

Pavements: Criteria:

Grounds: Criteria:

Criteria:

Facility Conditions (Continued) General Conditions Mission Impact**Satisfactory Unsatisfactory

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. No burnt out lights.

2. Barricade Walls (as applicable):

2 3

1 2 3

*Meets "2-degree" rule.*Top of barricade wall is at least 3 ft (.9 m) wide. *No substantial erosion

Remarks

3. Fire Protection/Prevention: 1

2 3

*Fire Drills -- Conducted at least every six months.

*Fire extinguishers are available during operations.*Facility is kept clean and free of combustible materials.

*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.*Parking -- Properly sited; sufficient room to maneuver; type of pavement supports gross weight of assigned equipment; adequate spaces; and lots are properly marked.*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

*Vegetation Control -- Exercised within 50 ft (15 m) of above-ground facilities and along rail trackage.

*Flammables and combustibles are not stored in close proximity to the facility.Remarks

4. 1

*Pad -- Permits uninhibited stacking of assets and use of handling equipment.Remarks

5. 1 2 3

*Miscellaneous Pads -- Pads are in good repair; adequate drainage is available; and pads are sufficiently sized for equipment.*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to help prevent erosion.*Fencing -- Security fencing is installed and is in good repair; and vegetation is controlled around fencing.

1 2 3

*An LPS is Installed -- System features include air terminals, masts, and catenaries for low impedance paths to ground.*LPS components are grounded and all metallic penetrations are bonded.*Side-flash protection is provided through separation.

Work Stoppage/Life-Safety Hazard** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*Meets NFPA 780 and MIL-HDBK-419 requirements. Remarks

Remarks

6. Lightning Protection System (LPS) Installed:

*LPS inspection documentation being properly maintained as per AFI 32-1065.

8

ARCHIVED

Page 96: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

7. Lighting:Criteria:

8. Criteria:

b. Classification Yard:Criteria:

c.Criteria:

d.Criteria:

Remarks

*Track switches operable and well maintained.*All connectors are present and tight.

*Ties in good condition and firmly set in ballast. *Ballast is clean and well compacted. *All connectors are present and tight.

*Track switches operable and well maintained.

*Track in alignment and true to grade. *Ties in good condition and firmly set in ballast. *Ballast is clean and well compacted.

31 2Inspection Station (as applicable):

Remarks

3

*Free of leaks.*Attachments are secure.

Roof (as applicable): (Circle one) Metal Rolled Frangible Concrete1 2

1 2

Facility Conditions (Continued) General Conditions

*General Illumination Guidelines -- Bio-Environmental Engineering is contacted to ensure proper illumination is available.*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.*No burnt out bulbs.

3

Remarks

*Track in alignment and true to grade.

1 2 3Holding Yard (as applicable):

Remarks

*No signs of failure, separation, or curling.Remarks

1 2 3

*Track in alignment and true to grade.

Mission Impact**Satisfactory Unsatisfactory

*Ties in good condition and firmly set in ballast. *Ballast is clean and well compacted. *All connectors are present and tight. *Track switches operable and well maintained.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

9

ARCHIVED

Page 97: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

e.Criteria:

f.Criteria:

g.Criteria:

h.Criteria:

**All wiring is in conduit.

*Dock is adequate width to permit maneuvering of loading equipment.

Bomb Preload Station (Munitions Assembly Conveyor):

*Edges are sound and intact; no crumbling. *Dock plates/ramp extensions operable. *Bumpers are securely fastened and in good repair.*Safety markings are visible and clean.

3

*Ties in good condition and firmly set in ballast.*Ballast is clean and well compacted.

Interchange Yard (as applicable): 1 2 3

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Track in alignment and true to grade.

Remarks

Loading Dock: 1 2 3

*All connectors are present and tight. *Track switches operable and well maintained.

3

*Foundation in good condition, free of cracks.

Remarks

Ready Explosives Facility: 1 2

*Ramp is constructed at safe grade.

**Transfer switch and breaker panels are operable.**Generator and back-up power is available and in good repair.

**Switches and breakers contain lightning arrestors.

*Use General Criteria in section IIIa (above).Remarks

1 2

**Transformers are free of leaks, are closed, and are weather-proof.

*All gantries and conveyors are functioning properly.

**If required, appropriate surge protection devices will be installed.

Remarks

*Facility electrical.

**Ground devices are free of corrosion.**Support poles are in good condition and located at least 50 feet (15 m) away **Switch box plates are water and dust tight.**Switches are in spark-proof enclosures.**Junction boxes are spark-proof and watertight.

**Energy management and controls transfer switches operable and waterproof, breaker panels operable and waterproof or dustproof, automatic controls operable, grounded, and well maintained, and battery charger operable and protected from weather.

Facility Conditions (Continued) General Conditions Mission Impact**Satisfactory Unsatisfactory

**Substations are away from explosives operations.

**No hazardous materials [polychlorinated biphenyls (PCBs)] are present.

10

ARCHIVED

Page 98: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

i.Criteria

Yes No

Remarks

No

Remarks

Work Stoppage/Life-Safety Hazard

IV. Summary

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes No

Yes

Unique Local Facility Features: 1 2 3

Mission Impact**Satisfactory Unsatisfactory

III. Facility Conditions (Continued) General Conditions

11

ARCHIVED

Page 99: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

ARCHIVED

Page 100: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

3

Remarks

7. Provide revetments if required by Q-D safety criteria or if use results in a net reduction in construction and land acquisition costs. 1 2

1 2 3

Remarks

Category code 116-642, Paved Shoulders, are authorized (minimum 25 feet (7.6 m) and up to 50 feet (15 m) for C-5, E-4, and Boeing 747 aircraft).

6.

2 3

Remarks

4. Provide blue, flush-type, taxiway lights on the edge of the pads as per AFI 32-1044 and AFMAN 32-1076.

Mission Design Requirements Design Requirements Mission Impact**Meets

Remarks

Insp. Date MAJCOM

Meets

1.

FACILITIES ASSESSMENT CHECKLISTCategory Code 116-662 -- Pad, Dangerous Cargo

Installation Name Location Facility Bldg Number

Remarks

Sq Footage Year Built Date Last InspectionFacility Purpose: The dangerous cargo pad, commonly referred to as a "hot cargo pad," is used to frequently load and unload explosives

II.

1

Facility Components

and other dangerous materials on cargo aircraft where existing aprons cannot be used without violating Q-D safety criteria. The pad is also used to park explosives-laden cargo aircraft and is considered to be an above-ground magazine for Q-D calculation purposes.

Mission Requirements

2 3

*Does the base master plan reflect the current facility category code?

1

Does Not MeetAssess the overall condition of the facility with respect to mission impact.

Use medium-load pavement for the pad and its access taxiway.

Locate the pad to satisfy Q-D safety criteria as per AFMAN 91-201 and DoD STD 6055.9.

*Are there any outstanding AF Forms 332?*Does the size and shape of the pad meet mission needs?

*Does the facility user have the site plan available?

5.

1 2 3

Aircraft and munitions load handling equipment grounding points provided. 1

Remarks

Remarks

3. Aircraft tiedown anchors installed.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

2

*Are there any safety or security write-ups on the facility from the latest inspections? *Does location of facility detract from mission performance?

Doesn't Meet

*Does the facility meet Q-D and facility guideline requirements?

3

2 3

Remarks

2.

1

*Does the facility design allow for known future mission changes?

1

ARCHIVED

Page 101: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

9.1 2 3

10.1 2 3

III.

1. Explosives Safety: Criteria: 1 2 3

Criteria:

Criteria:

*Flammables and combustibles are not stored in close proximity to the pad.Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Fire Drills -- Conducted at least every six months.*Vegetation Control -- Exercised within 50 ft (15 m) of aboveground facilities.*Fire extinguishers are available during operations.*Pad is kept clean and free of combustible materials.

2 3

Remarks

3. Fire Protection/Prevention: 1 2 3

*Lighting -- UL-approved lights are acceptable for this environment.

*Meets "2-degree" rule.*Top of barricade wall is at least 3 ft (.9 m) wide. *No substantial erosion.

Remarks

2. Barricade Walls (as applicable): 1

38.

1 2

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201, Q-D requirements are satisfied, net explosives weight limits are not exceeded, and commensurate measures are in-place. Any exceptions are properly identified and risk assessments are performed. *Placards -- Explosives limits and fire/chemical symbols are displayed.

If installation supports other than an aerial port of embarkation/debarkation (APOE/APOD), a circular pad with a 110 ft (35.5 m) radius (4.225 sq. yds. (3,533 m2)) is authorized.

Remarks

APOE/APODs that store or process in-transit explosives require two pads to accommodate C-141, C-5, C-17, and Boeing 747 aircraft (additional pads may be

Remarks

Remarks

Provide a means to post applicable safety placarding.

*Inspections -- Annual ground and explosives safety and facility inspections are performed.

required if there is a high volume of activity). The area for each pad is 8,900 sq. yds (7,442 m2). Each pad can be sited for up to 30,000 pounds (13,610 kg) net explosives weight of hazard class/division 1.1 munitions.

Meets Doesn't MeetII. Mission Design Requirements (Continued) Design Requirements Mission Impact**

*Grounding -- A means to dissipate static electricity buildup for the cargo aircraft and munitions (as required); static bonds and grounds are tested for resistance and continuity and records are on hand as per AFI 32-1065.

Facility Conditions General Conditions Mission Impact**Satisfactory Unsatisfactory

2

ARCHIVED

Page 102: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Pavements: Criteria:

Criteria:

6. Lighting:Criteria:

8.Criteria

*Surfaces are smooth and even, and allow for easy movement of equipment, aircraft, and munitions.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

1 2 3

Remarks

*Miscellaneous Pads -- Pads are in good repair; adequate drainage is available; and pads are sufficiently sized for equipment.*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.

Facility Conditions (Continued) General ConditionsMission Impact**

Satisfactory Unsatisfactory

*Erosion Control -- Area is free of erosion with suitable vegetation to help prevent erosion.

Work Stoppage/Life-Safety Hazard

*General Illumination Guidelines -- Bio-Environmental Engineering is contacted to ensure proper illumination is available.*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting in proximity of aircraft.*No burnt out bulbs.

Remarks

*Properly positioned and constructed to protect personnel and adjacent aircraft.*Surface free of erosion, corrosion, or other degradation.

Unique Local Facility Features:

*Pad permits uninhibited stacking of assets and use of handling equipment.

Remarks

5. 1 2 3Grounds (as applicable):

*Pavement markings are legible.

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. Lighting must not impact pilot safety. No burnt out lights.*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.*Parking -- Properly sited; sufficient room to maneuver; type of pavement supports gross weight of assigned equipment; and adequate spaces.*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

4. 1 2 3

1 2 3

Remarks

1 2 37. Revetments: Criteria:

Remarks

3

ARCHIVED

Page 103: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

IV. Summary

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes No

YesYes No

No

Remarks

4

ARCHIVED

Page 104: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

II.

1.1 2 3

2.1 2 3

3.1 2 3

4.1 2 3

5.1 2 3

6.1 2 3

7.1 2 3

*Does the facility's shape and size meet mission needs?*Does the facility user have a copy of the site plan available?

Remarks

Area can be secured in accordance with AFI 31-101.

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

Remarks

Fire extinguishers are provided.

Remarks

Capability to post fire/chemical symbols.

Remarks

Explosives limits posted.

Signs posted to prohibit smoking within 50 ft (15 m) of the holding point.

Mission Impact*

Fenced pad.

Design RequirementsMeets Doesn't Meet

Signs posted to keep out unauthorized personnel.

*Does location of facility detract from mission performance?

Remarks

Insp. Date MAJCOM

Meets

Mission Design Requirements

Sq Footage

FACILITIES ASSESSMENT CHECKLISTCategory Code 422-277 -- Flight Line Munitions Holding Point

Installation Name Location Facility Bldg Number

Year Built Date Last InspectionFacility Purpose: A flight line munitions holding point is used to accumulate a limited quantity (not to exceed one day's supply) of assembled

Facility Components

munitions at an assembly point for subsequent delivery to aircraft on the flight line or subsequent return to the MSA. This operating concept is optional based upon local capabilities and mission requirements. (Note: This facility is also known as a Holding Area Munitions (HAMS) yard.)

Mission Requirements*Does the base master plan reflect the current facility category code? Does Not MeetAssess the overall condition of the facility with respect to mission impact.

*Are there any open AF Forms 332?*Are there any existing safety or security discrepancies on the holding area?

*Does the facility meet Q-D and facility guide requirements?

Remarks

Remarks

*Does the facility design allow for known future mission changes?

1

ARCHIVED

Page 105: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

II.

8.1 2 3

9.1 2 3

10.1 2 3

11.1 2 3

12.1 2 3

13.1 2 3

14.1 2 3

15.1 2 3

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

Meets Doesn't Meet

Remarkssupport.)

Pad size of sufficient size to accommodate unit's daily munitions requirements and allow for safe movement of munitions materiel handling equipment.

Remarks

Lightning protection provided (unless interferes with safety-of-flight operations).

Personnel shelter large enough to hold the assigned personnel with a bay window overlooking entire fenced area and entrance. (Note: Typical size is 250 sq ft (14 m2) or larger.)

Remarks

Remarks

A second, manually-operated gate for drive-through capability.

Remarks

An electrical, motor-driven rail access gate for vehicle access remotely controlled from the personnel shelter.

Remarks

Sufficient grounding points available to attach grounding cables for ammunition loading systems.

Area lighting of sufficient intensity to permit night operations.

Electrical utilities have the required separation from the holding area. (Distances are dependent upon amount of voltage the lines carry and functions the lines

Design Requirements Mission Impact*Mission Design Requirements (Continued)

Remarks

Remarks

2

ARCHIVED

Page 106: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

1. Explosives Safety: Criteria: 1 2 3

Criteria:

Criteria:

*Pad is sited so forward firing munitions are headed in direction of least populated area and mission-critical assets.

2. Walls (in personnel shelter):

*Site is free of electromagnetic radiation.

1 2 3

*General -- Facility has good drainage and is vermin resistant. *Windows -- Made of blast-resistant material.

*Exterior -- Clean, intact, and free from damage. Paint and caulking are in good condition and water tight.*Interior -- Structural members and cross bracing are free from deterioration, caulking around wall penetrations watertight, and there are no unauthorized attachments that may compromise the design function.

Remarks

Remarks

1 2 3

Roof (on personnel shelter): (Circle One) Shingle Metal Gravel Rolled Frangible Concrete

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*Overhead doors raise and lower smoothly, and can be locked in place.*Doors swing/roll freely and fit in jambs.*Locks and security hasps are in good condition.*Safety mechanisms are in place to prevent accidental or inadvertent closing.

Remarks

4. Doors (in personnel shelter):

Criteria: *Free of leaks.*Attachments are secure.*No signs of failure, separation, or curling.

1 2 33.

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201, Q-D requirements are satisfied, net explosives weight limits are not exceeded, and commensurate measures are in-place. Any exceptions are properly identified and risk assessments are performed. *Placards -- Explosives limits and fire/chemical symbols are displayed. *Inspections -- Annual ground and explosives safety and facility inspections are performed.*Grounding -- A means to dissipate static electricity buildup from personnel and ammunition loading systems is installed; static bonds and grounds are tested for resistance and continuity and records are on hand as per AFI 32-1065.

Work Stoppage/Life-Safety Hazard

III. Facility Conditions General Conditions Mission Impact**Satisfactory

*Smoking prohibited within 50 ft (15 m) of explosives.

*Lighting -- Explosive-proof lights are used in Class I (explosives fuel/vapors) and Class II (explosives dust) environments; UL-approved lights are acceptable for all other environments.*Wiring -- Wires to structures are underground at least 50 ft (15 m) away and have lightning arrestors and surge protection. Conduits require bonding to the facility at point of entry.

*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements.

Unsatisfactory

Remarks

3

ARCHIVED

Page 107: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Criteria:

Criteria:

*Filters are clean.

Criteria: *All wiring is in conduit.

6. HVAC (in personnel shelter as applicable): 1 2 3

*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.*Central equipment (heat exchangers, pumps, and fans) is clean and well maintained.*Wiring is in conduits and insulation is intact.*Electrical control and switchgear is properly tagged, labeled, and housed.

*Stand-alone equipment (boiler and chiller units) is well maintained.*Start/stop control switch is properly mounted.*Damper controls and motors are in good working order.

Remarks

7. Facility Electrical (in personnel shelter): 1 2 3

*Generator and back-up power is available and in good repair.*Substations are away from explosives operations.

*Ground devices are free of corrosion.

*Switch box plates are water and dust tight.*Switches are in spark-proof enclosures.

*Support poles are in good condition and located at least 50 ft (15 m) away from facilities.

*No visible damage, watermarks, or sagging.*No obvious hazards to personnel on the floor.

Remarks

*Energy management and controls transfer switches operable and waterproof; breaker panels operable and waterproof or dustproof; automatic controls operable, grounded, and well maintained, and battery charger operable and protected from weather.

*Switches and breakers contain lightning arrestors.*No hazardous materials [polychlorinated biphenyls (PCBs)] are present.*Transformers are free of leaks, are closed, and are weather-proof.*If required, appropriate surge protection devices will be installed.

*Junction boxes are spark-proof and watertight.*Transfer switch and breaker panels are operable.

5. Ceiling (in personnel shelter) : 1 2 3

III. Facility Conditions (Continued) General Conditions Mission Impact**Satisfactory Unsatisfactory

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

4

ARCHIVED

Page 108: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Criteria:

Criteria:

Pavements: Criteria:

Grounds: Criteria:

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting in proximity of aircraft on the flight line.

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

*Sidewalks and Miscellaneous Pads -- Sidewalks are in good repair; pads are in good repair; and pads are sufficiently sized for equipment.*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to prevent erosion.*Fencing -- Security fencing is installed and is in good repair; and vegetation is controlled around fencing.

Remarks

11. 1 2 3

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. No burnt out lights.

*Roads -- Pavement is structurally sound and supports explosives-laden vehicles and munitions materiel handling equipment weights; drainage is sufficient; markings are legible; and is sufficient in width.*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage.

Remarks

10. 1 2 3

*Fire Drills -- Conducted at least every six months.*Vegetation Control -- Exercised within 50 ft (15 m) of above-ground facilities.*Emergency Evacuation -- Sufficient stairs available (if applicable); when possible, a minimum of two 32-in (812 mm) wide outward-opening doors with panic hardware within 75 ft (23 m) for emergency evacuation.

*Fire Extinguishers -- Supported, secured, and inspections are current.

2 39.

8. Plumbing and Mechanical Systems (in personnel shelter as applicable):

*Fire Alarm -- Panel is marked and accessible.*Detectors -- Well located and operable.*Pull Stations -- Well-located and alarms are audible.

1

*Sprinkler System -- Piping is properly installed and supported; system is free of leaks; sprinkler heads are properly positioned; and the system shut-off valve is readily accessible and unobstructed.

Fire Protection/Prevention (as applicable):

1 2 3

*Drainage systems support holding tanks, and drain and waste facilities are properly maintained.*Meters are operable.*Piping is free of corrosion and located away from moving equipment.*Valves and piping are free of leaks.*Piping penetrating the facility is grounded.*Pressure regulators are installed and operable.*Shut-off valves are clearly marked.*Steam and hot water lines are grounded.

Remarks

III. Facility Conditions (Continued) General Conditions Mission Impact**Satisfactory Unsatisfactory

5

ARCHIVED

Page 109: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Criteria:

Criteria:

15. Criteria:

*No burnt out bulbs.

1 2 3

*LPS inspection documentation being properly maintained.

Remarks

*Equipment is operable and in well maintained enclosure.

Lighting:

*Fluorescent Fixtures -- If not designed with self-locking tubes, must have a retaining device.*Stairs and Ramps -- Are illuminated with at least 5 foot-candles (54 meter-candles) of light.*General Illumination Guidelines -- Hallways require a minimum of 5 foot-candles (54 meter-candles) of light while detailed work may require 100 foot-candles (1,076 meter-candles). Bio-Environmental Engineering is contacted to ensure proper illumination is available.*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.

*Surge protection is provided.*Meets NFPA 780 and MIL-HDBK-419 requirements.

Remarks

*An LPS is Installed -- System features include air terminals, masts, and overhead wires that provide a low impedance path to ground.*LPS components are grounded and all metallic penetrations are bonded.*Side-flash protection is provided through separation.

*Equipment location is clearly marked and visible.

*Equipment located in waterproof and dustproof enclosure.Remarks

14. Lightning Protection System (LPS) Installed (if applicable): 1 2 3

Remarks

13. Communications (as applicable): Criteria

1 2 3

*Well/Water Source -- Quality testing records are current and water supply is adequate.*Pipes, Valves, and Fittings -- Located below grade; cathodic protection is installed; valves and meters are operable; and pipes entering the facility are grounded.*Elevated Tanks -- Containment areas are free of debris; tanks are in good repair; and support structures are stable and in good repair.*Water Treatment -- Filters are installed and conditioning equipment is maintained.

12. Water Supply and Distribution (in personnel shelter): 1 2 3

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;Work Stoppage/Life-Safety Hazard

Facility Conditions (Continued) General ConditionsIII. Mission Impact**Satisfactory Unsatisfactory

1 2 316

Remarks

Revetments (as applicable).: *Installed and in good order to protect personnel and adjacent aircraft.

6

ARCHIVED

Page 110: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

17.CriteriaUnique Local Facility Features: 1 2 3

Work Stoppage/Life-Safety Hazard

IV. Summary

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order discrepancies restore the building to an operational condition?Remarks

Yes No

YesYes No

Remarks

No

Remarks

Facility Conditions (Continued) General Conditions Mission Impact**Satisfactory Unsatisfactory

7

ARCHIVED

Page 111: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

3.1 2 3

Roadway supports the maximum loaded vehicle weights associated with explosives movement for the installation.

Remarks

Remarks

4. Roadway and adjacent area permit proper drainage.1 2 3

Remarks

II. Mission Design Requirements Design Requirements Mission Impact**Meets

Insp. Date MAJCOMSq Footage N/A Year Built Date Last Inspection

explosives movements on an installation by avoiding populated areas and mission-critical facilities and equipment. The installation determines the routes and explosives classes and limits for movements outside the munitions storage area (MSA) and publishes this information in local directives. Explosives movement routes are properly designated on the D-8 Tab, in coordination with the Base Civil Engineer. (NOTE: The assessment of Category Code 851-147 will also include roads within the MSA.)

Does Not Meet

Note: Portions of explosives movement routes may be part of the overall base infrastructure and may include roads or streets that are part of the general base circulation. Inspection of roadways must be coordinated with the Base Civil Engineer.

Meets

*Does location of the movement route detract from mission performance?

Facility ComponentsMission Requirements

*Does the base master plan reflect the current facility category code?

FACILITIES ASSESSMENT CHECKLISTCategory Code 851-147 - Road (Street) -- Used for Explosives Movement Routes

Installation Name Location Facility Bldg Number N/A

Assess the overall condition of the facility with respect to mission impact

Facility Purpose: Although not an actual facility, the purpose of an explosives movement routes are to safely support all phases of

*Does the movement route meet Q-D and facility guide requirements?

1. Route avoids areas where high traffic, housing, schools, child development centers, youth centers, hospitals, recreational, commercial, or mission critical

*Are there any existing safety or security discrepancies affecting the movement route?*Are there any open AF Forms 332?

1 2 3

Route has adequate geometry and composition to accommodate the required turning radii of munitions trailers.

Doesn't Meet

Remarksfunctions are located.

*Does the movement route location and design allow for known future mission changes?

1 2 3

Remarks

2.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

1

ARCHIVED

Page 112: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

1.1 2 3

2.1 2 3

3. 1 2 3

7. 1 2 3

8.Criteria:

Remarks

3

Remarks

6. Roadway drainage structures are structurally sound and maintained to allow proper drainage. 1 2 3

1 2 3

Pavement markings are legible.

4. Roadway paving is structurally sound with no discernable hazards.

Remarks

Remarks

Remarks

Rail crossings are level and smooth.

Rail crossings are marked and visibly unimpaired.

3

Signage is present and legible.

Remarks

Unique Local Facility Features: 1

Facility Conditions Mission Impact**Satisfactory

2

Remarks

III.

5.

Work Stoppage/Life-Safety Hazard

IV. Summary

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order restore the route to an operational condition?Remarks

Yes No

YesYes No

Remarks

No

Remarks

UnsatisfactoryGeneral Conditions

2Shoulder is structurally sound with no discernable hazards. 1

2

ARCHIVED

Page 113: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

3.1 2 3

Remarks

Remarks

*Does location of the parking area detract from mission performance?Remarks

II. Mission Design Requirements Design Requirements Mission Impact**Meets

Insp. Date MAJCOM

Meets

FACILITIES ASSESSMENT CHECKLISTCategory Code 852-261 - Vehicle Parking Operations – Used for Munitions Sub Pool Parking

Installation Name Location Facility Bldg Number

Sq Footage Year Built Date Last InspectionFacility Purpose: Provide parking for munitions support organizational vehicles for functions required for 24-hour access to a substantial

Facility Components

amount of their assigned vehicles. This area is also used to perform daily and weekly operator maintenance on the vehicles. In harsh environmental climates, an indoor parking facility may be required.

Mission Requirements*Does the base master plan reflect the current facility category code? Does Not MeetAssess the overall condition of the facility with respect to mission impact.

*Does the parking area meet Q-D (as applicable) and facility guide requirements?

Government vehicle parking areas located at least 100 ft. (30 m)or intraline distance away from explosives locations.

Remarks

1. Paved or stabilized surface (concrete, asphalt, AM-2 matting, or packed stone).

*Are there any outstanding AF Forms 332?

Security fencing at least 6 ft. (1.83 m) high with controlled entry gate(s) to meet local security requirements (as applicable).

3

1 2 3

2

*Are there any existing safety or security discrepancies on the parking area?

Proper lighting is installed to meet security requirements (as applicable).

Doesn't Meet

*Does the parking area location/facility and design allow for known future mission changes?

1 2 3

Remarks

2.

4.

5. Space requirements are calculated using AFH 32-1084, Table 20.1. 1

1 2

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

3

Remarks

1

ARCHIVED

Page 114: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

1. 1 2 3

b. Lighting:Criteria:

2.1 2 3

3.1 2 3

4.1 2 3

*Ground devices in place and corrosion-free.

*Pull boxes and cabinets weatherproof.

*Pad shoulder is structurally sound. *Paving surface properly drains (i.e., no standing water).

*Structurally sound without cracks.

*In extremely cold climate areas, sufficient quantity of properly rated outlets to support vehicle heaters.

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

Facility Electrical (if applicable): a. Transformers and switches:

Facility Conditions

*Markings are present and legible.

*Adequate drainage (i.e., no standing water).

Mission Impact**Satisfactory

Remarks

Remarks

Remarks

Pad Access Roads: Criteria:

III.

Pavements: Criteria:

General ConditionsUnsatisfactory

Remarks

Criteria: *Condition of exposed conduits and cables.

*Signage present and legible (as applicable).

*Paving is structurally sound. *Shoulders are structurally sound and maintained. *Drainage system structurally sound and well maintained. *Width of roadway sufficient for access of vehicles. *Pavement load design supports vehicle weight. *Markings are present and legible.

*Unwanted vegetation is maintained away from fence.

Grounds: a. Fencing (as applicable):Criteria:*Fence fabric, support posts, and hardware in good condition. *Manual or motor driven rail gates are operable and well maintained and safety guards are in place. *Gates are of sufficient width to maintain drive-through capability. *Fence system provides proper security for area.

1 2 3

*General Illumination Guidelines -- Bio-Environmental Engineering is contacted to ensure proper illumination is available.*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.*No burnt out bulbs.

2

ARCHIVED

Page 115: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

4. 1 2 3

5. 1 2 3

*Free of leaks.

7.Criteria:

8.Criteria:

9.Criteria:

Mission Impact**Satisfactory Unsatisfactory

2 3

*Area is free of erosion. *Area is well maintained and free of unwanted vegetation growth.

*Attachments are secure.*No signs of failure.

Explosives Safety (as applicable): Criteria:

Remarks

III. Facility Conditions (Continued) General Conditions

Remarks

b. Erosion control: Criteria:

*A minimum of 100 ft. (30 m) or intraline distance is maintained between an explosives location and the vehicle parking sub pool area. *Parking areas within the explosives clear zone arc are annotated on explosives siting documentation.

6.

Remarks

1Roof (if required for indoor facility): Criteria:

*Area has sufficient cover of vegetation.

2 3

*Exterior -- Clean; free from damage; intact; paint and caulking in good condition.*Interior -- Surfaces clean, intact, and free from damage; no unauthorized attachments that may compromise the design function; and caulking around wall penetrations watertight.

Walls (if required for indoor facility): 1

Remarks

Doors (if required for indoor facility):1 2 3

*Doors swing/roll freely and fit in jambs.*Locks and security hasps are in good condition.*Safety mechanisms are in place to prevent accidental closing.*Serviceable ramps to traverse thresholds (If required).*Roll-up doors must raise and lower smoothly.

Remarks

Floors (if required for indoor facility): 1 3 3

*Concrete is in good condition without cracks and with a smooth surface to allow easy equipment movement.Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

3

ARCHIVED

Page 116: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

10.Criteria:

11. 1 2 3

12.Criteria:

Criteria:

14.Criteria:***

*Doors are adequately sized to permit unobstructed egress.*Parking facility, if present, is sized to protect authorized vehicles from weather.

Remarks

Structures (as applicable): Criteria:

Unique Local Facility Features: 1 2 3

IV. Summary

Photographic Documentation (If yes, please attach)

Are work orders (Air Force Form 332) required for discrepancies?Will completion of "332" work order restore the route to an operational condition?Remarks

Yes No

YesYes No

Remarks

No

Remarks

Remarks

HVAC (if required for indoor facility):

*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.*Central equipment is clean and well maintained.*Wiring is in conduits and insulation is intact.

31 2

1 2 3

Unsatisfactory

*No visible damage or watermarks.*No obvious hazards to personnel on the floor.

Remarks

Ceiling (if required for indoor facility):

13. Lightning Protection System (LPS) Installed (if required for indoor facility): 1 2 3

*LPS inspection documentation being properly maintained.*An LPS is Installed -- System features include air terminals and low impedance paths to ground.*Meets NFPA 780, Chapter 3 (Ordinary Structures) requirements.

Remarks

III. Facility Conditions (Continued) General Conditions Mission Impact**Satisfactory

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

4

ARCHIVED

Page 117: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

3.1 2 3

*Does the facility user have the site plan available? *Do the railhead's' size and layout meet mission needs?

Remarks

8. Loading ramp. 1 2

Remarks

7. Track layout should be looped to allow two ways of exit. 1 2 3

Railroad trackage and infrastructure must be compatible with the common carrier.

Remarks

1 2 3

3

Remarks

Remarks

9 Lightning protection.

6.

3

II. Mission Design Requirements Design Requirements Mission Impact**Meets

Insp. Date MAJCOM

Meets

Sq Footage Year Built Date Last InspectionFacility Purpose: The purpose of a railhead is to load and unload railcars. The assets may be transferred to/from the railcar to other modes

Facility Components

of transportation or entered into the unit's munitions storage magazines. The railhead may be elevated or at ground level depending on the existing topography. The facility attributes may range from a simple concrete loading dock to a complex structure.

Mission Requirements

1 2

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

FACILITIES ASSESSMENT CHECKLISTCategory Code 890-158 - Load and Unload Platform (Railhead) – Used for Munitions Operations

Installation Name Location Facility Bldg Number

*Does the base master plan reflect the current facility category code? Does Not MeetAssess the overall condition of the facility with respect to mission impact.

*Does the railhead meet Q-D and facility guideline requirements?

Access road (if required) can accommodate the weight and turning radius of handling equipment.

Remarks

1. Paved or stabilized surface (concrete, asphalt, AM-2 matting, or packed stone) for use of associated handling equipment. 1 2 3

Remarks

*Are there any outstanding AF Forms 332?

Security fencing at least 6 ft (1.8 m) high with controlled entry gate(s) to meet local security requirements (as applicable).

3

1 2 3

21

*Are there any safety or security write-ups on the railhead from the latest inspections?

Proper lighting is installed to meet local operational and security requirements (as applicable).

Doesn't Meet

*Does the railhead location and design allow for known future mission changes?

1 2

*Does location of the railhead detract from mission performance?Remarks

3

Remarks

2.

4.

5. Cover may be required for protection from the weather and sun rays.

1

ARCHIVED

Page 118: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

1. Explosives Safety: Criteria: 1 2 3

Criteria:

Criteria:

Work Stoppage/Life-Safety Hazard

*Safety mechanisms are in place to prevent accidental or inadvertent closing.

*Windows -- Made of blast-resistant material. *General -- Facility has good drainage and is vermin resistant.

3

1

Remarks

3

Walls (as applicable):

Criteria: *Free of leaks.

Doors (as applicable):

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201, Q-D requirements are satisfied, net explosives weight limits are not exceeded, and commensurate measures are in-place. Any exceptions are properly identified and risk assessments are performed. Intraline distance applies to all transfer operations involving explosives except RO/RO and ISO containers.*Placards -- Explosives limits and fire/chemical symbols are displayed. *Inspections -- Annual ground and explosives safety and facility inspections are performed.

*Lighting -- Explosive-proof lights are used in Class I (explosives fuel/vapors) and Class II (explosives dust) environments; UL-approved lights are acceptable for all other environments.

3.

Remarks

*Exterior -- Clean, intact, and free from damage. Paint and caulking are in good condition and water tight.

Remarks

4.

*Doors swing/roll freely and fit in jambs.*Locks and security hasps are in good condition.

2

1 2

Remarks

*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements. *Smoking prohibited within 50 ft (15 m) of explosives-laden railcars.

2.

III.

*Overhead doors raise and lower smoothly, and can be locked in place.

*Interior -- Structural members and cross bracing are free from deterioration, caulking around wall penetrations watertight, and there are no unauthorized attachments that may compromise the design function.

Roof (as applicable): 1

Facility Conditions Mission Impact**Satisfactory

*Wiring -- Wires to structures are underground at least 50 ft (15 m) away and have lightning arrestors and surge protection. Conduits require bonding to the facility at point of entry.

(Circle One) Shingle Metal Gravel Rolled Frangible Concrete

Unsatisfactory

*Grounding -- A means to dissipate static electricity buildup is installed; static bonds and grounds are tested for resistance and continuity and records are on hand as per AFI 32-1065.

2 3

General Conditions

*Attachments are secure.*No signs of failure, separation, or curling.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

2

ARCHIVED

Page 119: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Floors: Criteria:

Criteria:

Criteria:

*Filters are clean.

Criteria: *All wiring is in conduit.

III. Facility Conditions (Continued) General Conditions Mission Impact**Satisfactory Unsatisfactory

6.

*Concrete is in good condition, without cracks and with a smooth surface to allow easy equipment movement.Remarks

5. 1

*Energy management and controls transfer switches operable and waterproof, breaker panels operable and waterproof or dustproof, automatic controls operable, grounded, and well maintained, and battery charger operable and protected from weather.

Remarks

*Ground devices are free of corrosion.*Support poles are in good condition and located at least 50 feet (15 m) away from facilities.*Switch box plates are water and dust tight.

Facility Electrical (as applicable):

1

31 2

3

*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.

2HVAC (as applicable): 7.

*Generator and back-up power is available and in good repair.*Substations are away from explosives operations.*Switches and breakers contain lightning arrestors and surge protection.*No hazardous materials [polychlorinated biphenyls (PCBs)] are present.*Transformers are free of leaks, are closed, and are weather-proof.

Remarks

*Wiring is in conduits and insulation is intact.*Electrical control and switchgear is properly tagged, labeled, and housed.

*Start/stop control switch is properly mounted.

Remarks*Damper controls and motors are in good working order.

8.

*If required, appropriate surge protection devices are installed.

2 3

*No visible damage, watermarks, or sagging.*No obvious hazards to personnel on the floor.

Ceiling (as applicable) :

*Stand-alone equipment (boiler and chiller units) is well maintained.

*Switches are in spark-proof enclosures.

*Central equipment (heat exchangers, pumps, and fans) is clean and well maintained.

2 3

1

*Junction boxes are spark-proof and watertight.*Transfer switch and breaker panels are operable.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

3

ARCHIVED

Page 120: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Criteria:

Pavements: Criteria:

Grounds: Criteria:

*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage. *Railhead ramp and dock of sufficient size, paving is structurally sound, and safety signs are present and legible.*Rail crossings are level and smooth and clearly marked to enhance visibility.

*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to prevent erosion.*Fencing -- Security fencing is installed and is in good repair; vegetation is controlled around fencing; and rail-driven gates are operable.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*Emergency Evacuation -- Sufficient stairs available (if applicable); when possible, a minimum of two 32-in (812 mm) wide outward-opening doors within 75 ft (23 m) for emergency evacuation.

Remarks

11. 1 2 3

*Pull Stations -- Well-located and alarms are audible.*Halon System -- Inspections are current; instructions are posted; and halon bottles are supported and secured.*Fire Drills -- Conducted at least every six months.*Vegetation Control -- Exercised within 50 ft (15 m) of above-ground facilities and along the railroad right-of-way.

*Sprinkler System -- Piping is properly installed and supported; system is free of leaks; sprinkler heads are properly positioned; and the system shut-off valve is readily accessible and unobstructed.*AFFF and Carbon Dioxide Bottles -- Supported, secured, and inspections are current.*Fire Alarm -- Panel is marked and accessible.*Detectors -- Well-located and operable.

*Steam and hot water lines are grounded.Remarks

10. Fire Protection/Prevention (as applicable): 1 2 3

*Valves and piping are free of leaks.*Piping penetrating the facility is grounded.*Pressure regulators are installed and operable.*Shut-off valves are clearly marked.

9.31 2

Plumbing and Mechanical Systems (as applicable):

12. 1

Remarks

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. No burnt out lights.

Work Stoppage/Life-Safety Hazard

2 3

*Piping is free of corrosion and located away from moving equipment.

Unsatisfactory

*Roads -- Pavement is structurally sound and supports loaded vehicles; drainage is sufficient; markings are legible; and is sufficient in width.

*Sidewalks and Miscellaneous Pads -- Sidewalks are in good repair; pads are in good repair; and pads are sufficiently sized for equipment.

*Drainage systems support holding tanks, and drain and waste facilities are properly maintained.

Remarks

Facility Conditions (Continued) General Conditions Mission Impact**Satisfactory

*Meters are operable.

4

ARCHIVED

Page 121: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Criteria:

a. Trackage

Criteria:

*Area adjacent to pad drains.

*Track in alignment and true to grade.

3

Remarks

16. Trackage and Infrastructure: 3

Remarks

1 2 3

*Foundation in good condition, free of cracks. *Edges are sound and intact; no crumbling. *Dock plates/ramp extensions operable. *Bumpers are securely fastened and in good repair. *Safety markings are visible and clean. *Ramp is constructed at safe grade. *Dock is adequate width to permit maneuvering of loading equipment.

b. Loading Dock:

*All connectors are present and tight.

2

1 2

14. Communications (as applicable): Criteria:

1

Criteria: *Ties in good condition and firmly set in ballast. *Ballast is clean and well compacted. *Track switches operable and well maintained.

*Pipes, Valves, and Fittings -- Located below grade; cathodic protection is installed; valves and meters are operable; and pipes entering the facility are grounded.*Elevated Tanks -- Containment areas are free of debris; tanks are in good repair; and support structures are stable and in good repair.*Water Treatment -- Filters are installed and conditioning equipment is maintained.

Remarks

2 3

*Equipment location is clearly marked and visible.

*Equipment located in waterproof and dustproof enclosure.

Remarks

*Equipment is operable and well maintained enclosure.

13. 1 2 3

*Well/Water Source -- Quality testing records are current and water supply is adequate.

Water Supply and Distribution (as applicable):

Facility Conditions (Continued) General Conditions Mission Impact**Satisfactory Unsatisfactory

Remarks

*Size of ramp and dock is sufficient to meet mission requirements. *Paving is structurally sound without cracks. *Pad shoulder is structurally sound. *Paving surface drains (i.e., no standing water). *Pavement markings are legible. *Safety signs are present and legible.

15. Railhead Ramp and Dock: 1

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

5

ARCHIVED

Page 122: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

18. Lighting:Criteria:

19.Criteria:

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

Yes NoRemarksWill completion of "332" work order discrepancies restore the building to an operational condition?

Remarks

Are work orders (Air Force Form 332) required for discrepancies? Yes

IV. Summary

Remarks

Photographic Documentation (If yes, please attach) Yes

No

No

Unique Local Facility Features:1 2 3

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.*No burnt out bulbs.

Remarks

*Stairs and Ramps -- Must be illuminated with at least 5 foot-candles (54 meter-candles) of light.*General Illumination Guidelines -- Hallways require a minimum of 5 foot-candles (54 meter-candles) of light while detailed work may require 100 foot-candles (1,076 meter-candles). Bio-Environmental Engineering is contacted to ensure proper illumination is available.

1 2

*Meets NFPA 780 and MIL-HDBK-419 requirements. Remarks

3

*Fluorescent Fixtures -- If not designed with self-locking tubes, must have a retaining device.

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.*LPS components are grounded and all metallic penetrations are bonded.*Side-flash protection is provided through separation.*Surge protection is provided.

1 2 3

*LPS inspection documentation being properly maintained.

17. Lightning Protection System (LPS) Installed:

Facility Conditions (Continued) General Conditions Mission Impact**Satisfactory Unsatisfactory

6

ARCHIVED

Page 123: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

ARCHIVED

Page 124: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

Inspector Unit POCType Constr.

I.

*Local area network for operation of Munitions Control 2000.Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds;

*Dedicated phone lines to Explosives Ordnance Disposal, Fire Department, Security Forces, Command Post, Maintenance Operations Center,

*Flooring able to support weight of safes.*Rooms completely enclosed, air conditioned, and heated.*Sufficient 110VAC power outlets to run equipment, status boards, computers, battery chargers, and radio base stations.

all munitions work centers, and Command Operations Center.

*Floors covered with an industrial grade carpet.*Standby power and emergency power required.*Two dedicated land mobile radio networks.*Secure voice communications capability.

1 2 3

*Solid wood or metal door with a peephole or video monitoring device and electrical or mechanical lock.

4. Munitions Control requires: *Construction to meet Controlled Area requirements outlined in AFI 31-101.

1 2 3

Remarks

3. Dependent on threat analysis, semi-hardened, splinter protected, or hardened construction criteria may apply.

1 2 3

Remarks

2. A non-interruptible power supply is required to maintain operational capability.

1 2 3

Remarks

1. Facility size dependent upon local requirements. Refer to AFH 32-1084, Tables 3.2 and 3.3, to help calculate the required square footage.

II. Mission Design Requirements Mission Requirements Impact**Meets Does Not Meet

*Are there any safety or security write-ups on the facility from the latest inspections?*Does location of facility detract from mission performance?

*Does the facility design allow for known future mission changes?Remarks

*Do the facility's size and shape meet mission needs?

*Does the base master plan reflect the current facility category code? Meets Does Not Meet*Are there any outstanding AF Forms 332?

Control, Flight/Squadron Leadership, Dispatch, Training, etc.. One facility may be used or the functions may exist in a multitude of facilities. ( Note: This category code does not apply to field offices located in operational facilities.)

Facility ComponentsAssess the overall condition of the facility with respect to mission impact. Mission Requirements

Sq Footage Year Built Date last InspectionFacility Purpose: These facilities house several administrative functions to include Munitions Operations, Combat Ammunition System, Munitions

Work Stoppage/Life-Safety Hazard

FACILITIES ASSESSMENT CHECKLISTCategory Code 610-144 -- Munitions Administration Facility

Installation Name Location Facility Bldg NumberInsp. Date MAJCOM

1

ARCHIVED

Page 125: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

3. Lighting:Criteria:

annotated on the Unit Committed Munitions List.

*Emergency lighting and exit signs installed.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

Remarks

*Insulation is in place and in good condition. *Facility has received regular maintenance actions.*Seismic features have been included in initial construction.*Security is consistent with function occurring in space.

*Columns and Exterior Wall -- Physical condition is sound and well maintained. *Outer surfaces have received coating of waterproofing/paint. *All door and window penetrations are caulked. *Outer surfaces are clean, pointed or painted.

1 2 3

*Foundation -- Structure has not settled, cracked or deteriorated.

4. Facility Structures: Criteria:

*Excessive Lighting -- Avoided to prevent glare and harsh shadows. This is very important for exterior lighting.*Computer Usage -- Lighting is adequate but not too bright to cause glare or discomfort.*No burnt out bulbs.

Remarks

3

*Fluorescent Fixtures -- If not designed with self-locking tubes, must have a retaining device.*Stairs and Ramps -- Must be illuminated with at least 5 foot-candles (54 meter-candles) of light.*General Illumination Guidelines -- Hallways require a minimum of 5 foot-candles (54 meter-candles) of light while detailed work may require 100 foot-candles (1,076 meter-candles). Bio-Environmental Engineering is contacted to ensure proper illumination is available.

1 2

*Feeder capacity into facility is sufficient for all functions collectively.*Panel breaker box capacity for facility is sufficient for all functions collectively. *Outlets number and location is sufficient for function occurring within each functional area.

Remarks

1 2 3

*System provides adequate service capacity for functions occurring in facility.

2. Facility Electrical: Criteria:

*Sub-systems operate as designed.*Facility meets facility guide requirements.*All the systems operational.

Remarks

1 2 3

*Assess the overall conditions of the facility.

1. Components: Criteria:

Remarks

Facility Conditions General Conditions Impact**Satisfactory Unsatisfactory

5. A training area is required for teaching the Combat Munitions Training Program. Size of the training room dependent upon the mission and types of munitions 1 2 3

2

ARCHIVED

Page 126: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

*Free of leaks.

Ceiling : Criteria:

Walls: Criteria:

unauthorized attachments that may compromise the design function.

*Exterior -- Clean, intact, and free from damage. Paint and caulking are in good condition and water tight.*Interior -- Structural members and cross bracing are free from deterioration, caulking around wall penetrations watertight, and there are no

*No visible damage, watermarks, or sagging.*No obvious hazards to personnel on the floor.*Security is consistent with functions occurring in space.*Ceiling system/material is suitable for function occurring in space.

*Attachments are secure.

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

*Physical condition is good and well maintained. *Air infiltration (in/out) is within acceptable limits.*Security is consistent with functions occurring in space.*Shard protection required if facility is within the explosives clear zone arc.

1 2 3

*Windows are functional.

9. Window Systems: Criteria:

Remarks

Remarks

8. 1 2 3

*No signs of failure, separation, or curling.Remarks

7. 1 2 3

1 2 3Criteria:

*Security is consistent with function occurring in space.Remarks

*Floor loading is within initial design limits.*Seismic features have been included in initial construction.

6. Roof: (Circle One) Shingle Metal Gravel Rolled Frangible Concrete

*Floor is structurally sound and free of settlement, cracks or deterioration.*Floor finish is intact and well maintained.

Facility Conditions (Continued) General ConditionsUnsatisfactory

5. Floor Systems: Criteria: 1 2 3

Mission Impact**Satisfactory

3

ARCHIVED

Page 127: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Doors: Criteria:

HVAC: Criteria:

Criteria:

*Filters are clean.*Electrical control and switchgear is properly tagged, labeled, and housed.

*Central equipment (heat exchangers, pumps, and fans) is clean and well maintained.*Wiring is in conduits and insulation is intact.

*Stand-alone equipment (boiler and chiller units) is well maintained.*Start/stop control switch is properly mounted.*Damper controls and motors are in good working order.

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

*Emergency Evacuation -- Sufficient stairs available (if applicable); when possible, a minimum of two 32-in (812 mm) wide outward-opening doors with panic hardware within 75 ft (23 m) for emergency evacuation.

Remarks

*Pull Stations -- Well-located and alarms are audible.*Halon System -- Inspections are current; instructions are posted; and halon bottles are supported and secured.*Fire Drills -- Conducted at least every six months.*Vegetation Control -- Exercised within 50 ft (15 m) of above-ground facilities.

*Sprinkler System -- Piping is properly installed and supported; system is free of leaks; sprinkler heads are properly positioned; and the system

*AFFF and Carbon Dioxide Bottles -- Supported, secured, and inspections are current.*Fire Alarm -- Panel is marked and accessible.*Detectors -- Well-located and operable.

shut-off valve is readily accessible and unobstructed.

Remarks

12. Fire Protection/Prevention: 1 2 3

* Efficient/power consumption is within energy audit standards. *System maintains acceptable temperature levels for all seasons. *System is reliable and maintainable.*Security is consistent with functions occurring in space.

* System capacity is sufficient to service all spaces.*Temperature/cooling controls are operable and secured.*Noise level is acceptable for functions occurring in facility.

*Doors swing/roll freely and fit in jambs.

*Safety mechanisms are in place to prevent accidental or inadvertent closing.

2 3

*Ductwork and accessories well supported, insulation intact, and outlet diffusers are clean.

Remarks*Security is consistent with functions occurring in space.

11. 1

Facility Conditions (Continued) General Conditions Mission Impact**Satisfactory

*Door leaf is solid core or metal and free of deterioration.*Frame is intact, solid, and free of deterioration.*Fire rating is consistent with rest of structure.

*Overhead doors must raise and lower smoothly, and can be locked in place.

*Locks and security hasps are in good condition.

10. 1 2 3

Unsatisfactory

4

ARCHIVED

Page 128: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Pavements: Criteria:

Grounds: Criteria:

15. Explosives Safety: Criteria: 1 2 3

Criteria:

and any exceptions are properly identified and risk assessments are performed.

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

*Well/Water Source -- Quality testing records are current and water supply is adequate.*Pipes, Valves, and Fittings -- Located below grade; cathodic protection is installed; valves and meters are operable; and pipes entering the

*Elevated Tanks -- Containment areas are free of debris; tanks are in good repair; and support structures are stable and in good repair.*Water Treatment -- Filters are installed and conditioning equipment is maintained.

facility must be grounded.

*Windows -- Made of blast-resistant material if within the explosives clear zone arc. *General -- Facility has good drainage and is vermin resistant.

Remarks

16. Water Supply and Distribution: 1 2 3

*Siting Requirements -- Facility is sited in accordance with DoD 6055.9 STD and AFMAN 91-201 (if required), Q-D requirements are satisfied,

*Inspections -- Annual ground and explosives safety and facility inspections are performed.*Lighting -- UL-approved lights are acceptable.*Installed Equipment -- Meets NFPA 70 and AFI 32-1065 requirements.

Remarks

Facility Conditions (Continued) General Conditions Mission Impact**Satisfactory Unsatisfactory

*Sidewalks and Miscellaneous Pads -- Sidewalks are in good repair; pads are in good repair; and pads are sufficiently sized for equipment.*Landscaping -- Grass, trees, and shrubs are maintained; and grounds are free of holes and other hazards.*Erosion Control -- Area is free of erosion with suitable vegetation to prevent erosion.*Fencing -- Security fencing is installed and is in good repair; vegetation is controlled around fencing; and rail-driven gates are operable.

*Drainage -- Structures are sound and maintained; and areas are free of debris and blockage. Remarks

14. 1 2 3

*Lighting -- Perimeter security lights are installed and sufficient lighting for night operations. No burnt out lights.*Roads -- Pavement is structurally sound and supports loaded vehicles; markings are legible; and is sufficient in width.*Parking -- Properly sited; sufficient room to maneuver; type of pavement supports gross weight of assigned equipment; adequate spaces;

*Roadway and adjacent area drains contain no standing water.and lots are properly marked.

13. 1 2 3

5

ARCHIVED

Page 129: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

III.

Criteria:

Criteria:

Criteria:

Facility Conditions (Continued) General Conditions Mission Impact**Satisfactory Unsatisfactory

19. 1Lightning Protection: 2 3

*Meets NFPA 780 and MIL-HDBK-419 requirements.

*LPS inspection documentation being properly maintained.

damage, and tank surface and connections are free of corrosion.

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

Remarks

*Piping penetrating the facility is grounded.*Pressure regulators are installed and operable.*Shut-off valves are clearly marked.*Steam and hot water lines are grounded.

*Drainage systems support holding tanks, and drain and waste facilities are properly maintained.*Meters are operable.*Piping is free of corrosion and located away from moving equipment.*Valves and piping are free of leaks.

Remarks

18. Plumbing and Mechanical Systems: 1 2 3

*Cathodic Protection -- A system is installed, corrosion free, and the sacrificial plate (anode) volume is 25% or +.*Pipes, Valves, and Fittings -- Outside components are protected from vehicles and other moving objects; piping penetrating the facility must be

*Regulators -- Are accessible, supported, and leak-free.*Storage Tanks -- Are securely anchored to their support structure, have pressure relief valves, are protected from vehicular

grounded; and shut-off valves are readily accessible.

17. Natural Gas Storage and Distribution: 1 2 3

*An LPS is Installed -- System features include air terminals and low impedance paths to ground.*Surge protection is provided.

6

ARCHIVED

Page 130: Air Force Munitions Facilities Standards Guide, Volume 2 · 2018-04-25 · U.S. AIR FORCE MUNITIONS FACILITIES STANDARDS GUIDE Volume II MUNITIONS FACILITIES ASSESSMENT CHECKLISTS

20.Criteria:

IV. Summary

Will completion of "332" work order discrepancies restore the building to an operational condition? Yes NoRemarks

Remarks

** Impact: 1 - Minimal or No Impact 2 - Degraded Impact with "Work Arounds" 3 - Critical Impact - No Suitable Work Arounds; Work Stoppage/Life-Safety Hazard

Photographic Documentation (If yes, please attach) Yes NoRemarks

Are work orders (Air Force Form 332) required for discrepancies? Yes No

Unique Local Facility Features:1 2 3

7

ARCHIVED