ADT490 TroubleShootingLocating Opens
2
Power Supply Grounding
‣ Power Supply has circuit -> allows positive & negative outputs to float relative to ground
‣ Green AC input wire -> building Ground‣ Resistance to ground ≤ 10 kΩ
‣ results from abnormal operation‣ Originally, negative was ground
‣ System Fault -> Ground Fault‣ Non specific - one or many‣ Internal or External
3
Bonding
‣ Exterior raceway components bonder to Ground conductor
‣ reduces interference -> EMI, RFI, & ESI
‣ Easirer to test ground during VI
3
4
Bonding
4
5
Ground-to-Ground Short
‣ False Alarm
5
6
Positive Ground
‣ Higher end panels - may show as Positive on LCD
6
7
Ground Fault Processing
‣ Often within 1 second to 90 seconds‣ Lower Priority than Alarms, & Supervisory conditions‣ Return to normals even lower Priority
7
8
Finding Grounds in Small Panels‣ Remove field wiring & install EOLs
‣ Eliminates Panel itself‣ Field
‣ Remove EOL and install field wiring‣ Tag and remove
‣ Find All Circuits with Ground Faults
8
9
Finding Grounds in Large Panels‣ Modules often have 8 circuits‣ CPU Communicates with modules through cables
9
10
Finding Grounds in Large Panels‣ Boolean Search through cables
‣ De-energize panel remove cable
‣ Localize to one module‣ Do small panel search when localized
10
11
Diagnosing Ground Correctly‣ Do not accept LCD info at face value‣ Ground can trigger at 50,000 Ω‣ On positive but can still be detected through
negative wire -> “pass through”
11
12
Diagnosing Ground Correctly
12
13
Measuring Grounds on Positive
13
14
Measuring Grounds on Negative
14
15
Measuring Grounds
‣ Most consistent method - A‣ Positive lead on panel chassis or ground lug‣ Negative Lead on system or circuit common‣ Always gives 0 to 30 V
15
16
Measuring Grounds
16
17
Causes of Grounds
‣ drilled through raceway‣ insulation stripped during insulation‣ wire loose to metal backbox or cover
17
18
Locating Grounds on Class B Ccts
18
‣ Boolean Search
19
Locating Grounds on Class A Ccts‣ Boolean Search
19
20
Boolean Searches for Grounds‣ Same approach as Opens and shorts‣ REMOVE BOTH WIRES
‣ Middle of circuit, remove both wires‣ If ground goes off -> toward EOL‣ f ground stays on -> toward Panel
20
21
Internal Grounds on Small Panels‣ Remove field circuits with EOLs‣ Check Battery connectors‣ Foreign materials near chassis and mounting screws‣ Remove Circuit board -> closely inspect for foreign
materials ‣ If ground remains -> replace Circuit board
21
22
Internal Grounds on Large Panels‣ Boolean search through Card Communication
Ribbons‣ Can sometimes remove card -> Ground clears‣ Replace cards or CPU as appropriate
22