ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

Embed Size (px)

Citation preview

Page 1: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

ADT490 TroubleShootingLocating Opens

Page 2: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

2

Power Supply Grounding

‣ Power Supply has circuit -> allows positive & negative outputs to float relative to ground

‣ Green AC input wire -> building Ground‣ Resistance to ground ≤ 10 kΩ

‣ results from abnormal operation‣ Originally, negative was ground

‣ System Fault -> Ground Fault‣ Non specific - one or many‣ Internal or External

Page 3: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

3

Bonding

‣ Exterior raceway components bonder to Ground conductor

‣ reduces interference -> EMI, RFI, & ESI

‣ Easirer to test ground during VI

3

Page 4: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

4

Bonding

4

Page 5: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

5

Ground-to-Ground Short

‣ False Alarm

5

Page 6: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

6

Positive Ground

‣ Higher end panels - may show as Positive on LCD

6

Page 7: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

7

Ground Fault Processing

‣ Often within 1 second to 90 seconds‣ Lower Priority than Alarms, & Supervisory conditions‣ Return to normals even lower Priority

7

Page 8: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

8

Finding Grounds in Small Panels‣ Remove field wiring & install EOLs

‣ Eliminates Panel itself‣ Field

‣ Remove EOL and install field wiring‣ Tag and remove

‣ Find All Circuits with Ground Faults

8

Page 9: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

9

Finding Grounds in Large Panels‣ Modules often have 8 circuits‣ CPU Communicates with modules through cables

9

Page 10: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

10

Finding Grounds in Large Panels‣ Boolean Search through cables

‣ De-energize panel remove cable

‣ Localize to one module‣ Do small panel search when localized

10

Page 11: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

11

Diagnosing Ground Correctly‣ Do not accept LCD info at face value‣ Ground can trigger at 50,000 Ω‣ On positive but can still be detected through

negative wire -> “pass through”

11

Page 12: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

12

Diagnosing Ground Correctly

12

Page 13: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

13

Measuring Grounds on Positive

13

Page 14: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

14

Measuring Grounds on Negative

14

Page 15: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

15

Measuring Grounds

‣ Most consistent method - A‣ Positive lead on panel chassis or ground lug‣ Negative Lead on system or circuit common‣ Always gives 0 to 30 V

15

Page 16: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

16

Measuring Grounds

16

Page 17: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

17

Causes of Grounds

‣ drilled through raceway‣ insulation stripped during insulation‣ wire loose to metal backbox or cover

17

Page 18: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

18

Locating Grounds on Class B Ccts

18

‣ Boolean Search

Page 19: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

19

Locating Grounds on Class A Ccts‣ Boolean Search

19

Page 20: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

20

Boolean Searches for Grounds‣ Same approach as Opens and shorts‣ REMOVE BOTH WIRES

‣ Middle of circuit, remove both wires‣ If ground goes off -> toward EOL‣ f ground stays on -> toward Panel

20

Page 21: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

21

Internal Grounds on Small Panels‣ Remove field circuits with EOLs‣ Check Battery connectors‣ Foreign materials near chassis and mounting screws‣ Remove Circuit board -> closely inspect for foreign

materials ‣ If ground remains -> replace Circuit board

21

Page 22: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground

22

Internal Grounds on Large Panels‣ Boolean search through Card Communication

Ribbons‣ Can sometimes remove card -> Ground clears‣ Replace cards or CPU as appropriate

22