Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
Page 1 of 2
Addendum No. 2
Thomas Jefferson Pumping Station Improvements
DWM PROJECT NO. 13-109 SPECIFICATION NO. 226043
For which bids will be opened in the office of the Department of Procurement Services,
Room 103, Chicago, Illinois, 60602 on September 27, 2016 at 11:00 a.m. Central Time:
BIDDER WILL ACKNOWLEDGE RECEIPT OF THIS ADDENDUM
IN THE SPACE PROVIDED ON THE PROPOSAL PAGE
NOTICE OF ADDENDUM Addendum:
The attached drawings and specifications are updated and included as Addendum No. 2:
o Book 3 Table of Contents Pages TOC - 1 to TOC – 4
o 092216 – Non-Structural Metal Framing (New Book 3 specification section)
o 092400 – Portland Cement Plastering (New Book 3 specification section)
o 092613 – Gypsum Veneer Plastering (New Book 3 specification section)
o 092900 – Gypsum Board (New Book 3 specification section)
o A201 “Partial South Elevation”
o A202 “Partial North Elevation”
o A203 “Partial North, South, & West Elevations”
o A204 “West Elevation”
o A205 “East Elevation 1”
o A206 “East Elevation 2”
o A504 “Cornice Repairs”
o C700 “Utility Details” Bidder Questions and Answers: 1. Question: Standard inlet detail 3 on C700 calls outs that 8” ductile iron pipe must be used for connection to
catch basin. However, the Utility Plan on C400 shows 6” perforated PVC connecting the inlets to the catch
basins. Please confirm 8” DIP is not required.
Response: 8” DIP is not required. Refer to revised drawing C700 in Addendum No. 2. 2. Question: On the exterior elevations (sheets A201-A206), keynotes 5, 6, and 18 are listed under the Exterior
Restoration and Repair General Reference Notes but not called out anywhere on the elevations. Please clarify if there is any work to be performed associated with these keynotes.
Response: Notes and corresponding call outs are revised as shown on revised drawings A201- A206 in Addendum No 2. Key note 18 and the call out are on the original drawing A204. Revised drawing A201 also referenced note 18.
Page 2 of 2
3. Question: The plans show some work for which no specifications have been provided, including plaster, gypsum board, and metal framing. Please provide specifications.
Response: Refer to new Book 3 Specification Sections 092216, 092400, 092613, and 092900 in Addendum No. 2.
4. Question: Specification 012200 Unit Prices – Item No.4 lists requirements for 19 different molds for the terra
cotta, and 130 individual units total is listed for replacement in the schedule of prices. Since only a limited number of pieces can be made per individual mold, can the 130 pieces be broken out per mold type?
Response: No. Refer to drawings A207 and A208 for details.
5. Question: Spec Section 051200 Structural Steel Framing includes qualifications requiring the fabricator and
erector to be AISC certified. Can these requirements be waived to allow more competitive bidding?
Response: No.
6. Question: Drawing A504, Note 5 for masonry repairs call for replacing steel members that are exhibiting more
than 20% section loss. Can an allowance or an assumed quantity be provided by the city? Until the steel is
exposed, It is unclear if all lintels will need to be replaced or none. Please advise.
Response: Refer to revised drawing A504 in Addendum No. 2, which requires Commissioner’s approval
prior to steel removal and replacement.
7. Question: Is there any more information regarding the entry and exit loop system? I have talked with vendors
about the system and they need more information as to what type of controller is required along with the
manufacture of the system. Only information I can find is located on drawing E200 for just the operation of the
gate.
Response: The specifications identify the necessary performance requirements for the entry and exit
loop system. The system utilized must meet the requirements dictated in all applicable specification
sections.
8. Question: During scaffolding installation in the pump room, are the painters able to use the crane for moving
scaffolding elements: frames, bracing, etc…?
Response: No.
Jefferson Pump Station Improvements TOC - 1 TABLE OF CONTENTS
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
TABLE OF CONTENTS
SPECIFICATIONS
DIVISION 0 PROCUREMENT AND CONTRACTING REQUIREMENTS
000115 LIST OF DRAWING SHEETS
003126 EXISTING HAZARDOUS MATERIAL INFORMATION
003132 GEOTECHNICAL DATA
DIVISION 1 GENERAL REQUIREMENTS
011000 SUMMARY
011010 SECURITY REQUIREMENTS, HEALTH AND SAFETY PLANS, WORK AREA
CLOSURES, HOT WORK PERMITS
012200 UNIT PRICES
013100 PROJECT MANAGEMENT AND COORDINATION
013350 WEB-BASED PROJECT MANAGEMENT AND COLLABORATION SYSTEM
013516 ALTERATION PROJECT PROCEDURES
014000 QUALITY REQUIREMENTS
015000 TEMPORARY FACILITIES AND CONTROLS
017300 EXECUTION
017419 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
017700 CLOSEOUT PROCEDURES
017840 COMPUTERIZED MAINTENANCE MANAGEMENT SYSTEM DATA
DIVISION 2 EXISTING CONDITIONS
024119 SELECTIVE STRUCTURE DEMOLITION
028250 12-FOOT STEEL FENCE
DIVISION 3 CONCRETE
030130 MAINTENANCE OF CAST-IN-PLACE CONCRETE
033000 CAST-IN-PLACE CONCRETE
035100 GYPSUM DECK REPAIR
035216 LIGHTWEIGHT INSULATING CONCRETE
037300 CONCRETE DECK REPAIR
DIVISION 4 MASONRY
040110 MASONRY CLEANING
040120.63 BRICK MASONRY REPAIR
040120.64 BRICK MASONRY REPOINTING
040140.61 STONE REPAIR
040140.63 TERRA COTTA RESTORATION
042000 UNIT MASONRY
042200 CONCRETE UNIT MASONRY
DIVISION 5 METALS
050170.61 DECORATIVE METAL REPAIR
051200 STRUCTURAL STEEL FRAMING
055000 METAL FABRICATIONS
055213 PIPE AND TUBE RAILINGS
Jefferson Pump Station Improvements TOC - 2 TABLE OF CONTENTS
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
DIVISION 6 WOOD, PLASTICS AND COMPOSITES
061053 MISCELLANEOUS ROUGH CARPENTRY
064116 PLASTIC-LAMINATE-FACED ARCHITECTURAL CABINETS
DIVISION 7 THERMAL AND MOISTURE PROTECTION
075113 COLD-APPLIED BUILT-UP ASPHALT ROOFING
076200 SHEET METAL FLASHING AND TRIM
077000 ROOF AND WALL SPECIALTIES AND ACCESSORIES
077200 ROOF ACCESSORIES
079200 JOINT SEALANTS
DIVISION 8 OPENINGS
081113 HOLLOW METAL DOORS AND FRAMES
085115 ALUMINUM WINDOWS
085653 SECURITY WINDOWS
087100 DOOR HARDWARE
088000 GLAZING
089119 FIXED LOUVERS
DIVISION 9 FINISHES
092216 NON-STRUCTURAL METAL FRAMING (ADDED ADDENDUM NO. 1)
092400 PORTLAND CEMENT PLASTERING (ADDED ADDENDUM NO. 1)
092613 GYPSUM VENEER PLASTERING (ADDED ADDENDUM NO. 1)
092900 GYPSUM BOARD (ADDED ADDENDUM NO. 1)
095113 ACOUSTICAL PANEL CEILINGS
096614 CEMENTITIOUS TERRAZZO FLOORING RESTORATION
096723 RESINOUS FLOORING
099113 EXTERIOR PAINTING
099123 INTERIOR PAINTING
099726 CEMENTITIOUS COATINGS
DIVISION 10 SPECIALTIES
101423 PANEL SIGNAGE
102800 TOILET, BATH, AND LAUNDRY ACCESSORIES
DIVISION 11 EQUIPMENT
113100 RESIDENTIAL APPLIANCES
DIVISION 12 FURNISHINGS
NOT USED
DIVISION 13 SPECIAL CONSTRUCTION
NOT USED
DIVISION 14 CONVEYING EQUIPMENT
NOT USED
DIVISION 21 FIRE SUPPRESSION
NOT USED
Jefferson Pump Station Improvements TOC - 3 TABLE OF CONTENTS
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
DIVISION 22 PLUMBING
220513 BASIC MECHANICAL REQUIREMENTS
220518 ESCUTCHEONS FOR PLUMBING PIPING
220523.12 BALL VALVES FOR PLUMBING PIPING
220529 HANGERS AND SUPPORTS
220553 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
221116 DOMESTIC WATER PIPING
221316 SANITARY WASTE AND VENT PIPINT
221416 WATER DISTRIBUTION PIPING
223400 FUEL-FIRED, DOMESTIC WATER HEATERS
224100 RESIDENTIAL PLUMBING FIXTURES
224213.13 COMMERCIAL WATER CLOSETS
224213.16 COMMERCIAL URINALS
DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING
230503 GENERAL PROVISIONS FOR HVAC WORK
230505 BASIC HVAC MATEIALS AND METHODS
230513 COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT
230593 TESTING, ADJUSTING AND BALANCING FOR HVAC
230700 HVAC INSULATION
230923.12 CONTROL DAMPERS
232300 REFRIGERANT PIPING
233113 METAL DUCTS
233713 DIFFUSERS, REGISTERS AND GRILLES
234100 PARTICULATE AIR FILTRATION
236313 AIR-COOLED REFRIGERANT CONDENSERS
237313 MODULAR INDOOR CENTRAL STATION AIR HANDLING UNITS
238123 ROOM AIR CONDITIONERS
DIVISION 26 ELECTRICAL
260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
260523 CONTROL-VOLTAGE ELECTRICAL POWER CABLES
260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
260533 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
260544 SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING
260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS
262726 WIRING DEVICES
265100 INTERIOR LIGHTING
DIVISION 27 COMMUNICATIONS
NOT USED
DIVISION 28 ELECTRONIC SAFETY AND SECURITY
281300 ACCESS CONTROL SYSTEM
281600 INTRUSION DETECTION
282300 VIDEO SURVEILLANCE
Jefferson Pump Station Improvements TOC - 4 TABLE OF CONTENTS
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
DIVISION 31 EARTHWORK
311000 SITE CLEARING
312000 EARTH MOVING
DIVISION 32 EXTERIOR IMPROVEMENTS
321216 ASPHALT PAVING
321313 CONCRETE PAVING
321443 POROUS UNIT PAVING
321713 PARKING BUMPERS
321723 PAVEMENT MARKINGS
329113 SOIL PREPARATION
329200 SODDED LAWNS
329300 PLANTS
DIVISION 33 UTILITIES
334100 STORM UTUILITY DRAINAGE PIPING
334600 SUBDRAINAGE
END OF TABLE OF CONTENTS
Jefferson Pump Station Improvements 092216 - 1 NON-STRUCTURAL
DWM Project No. 13-109 METAL FRAMING
GEC Project No. 09009.007 Addendum No. 1
SECTION 092216
NON-STRUCTURAL METAL FRAMING
ADDED – ADDENDUM NO. 1
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Non-load-bearing steel framing systems for interior gypsum board assemblies.
2. Suspension systems for interior gypsum ceilings, soffits, and grid systems.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Fire-Test-Response Characteristics: For fire-resistance-rated assemblies that incorporate non-
load-bearing steel framing, provide materials and construction identical to those tested in
assembly indicated, according to ASTM E 119 by an independent testing agency.
B. STC-Rated Assemblies: For STC-rated assemblies, provide materials and construction identical
to those tested in assembly indicated, according to ASTM E 90 and classified according to
ASTM E 413 by an independent testing agency.
2.2 FRAMING SYSTEMS
A. Framing Members, General: Comply with ASTM C 754 for conditions indicated.
1. Steel Sheet Components: Comply with ASTM C 645 requirements for metal unless
otherwise indicated.
2. Protective Coating: Manufacturer’s standard rust-inhibiting coating.
B. Studs and Runners: ASTM C 645. Use steel studs and runners.
1. Steel Studs and Runners:
Jefferson Pump Station Improvements 092216 - 2 NON-STRUCTURAL
DWM Project No. 13-109 METAL FRAMING
GEC Project No. 09009.007 Addendum No. 1
a. Minimum Base-Metal Thickness: As indicated on Drawings or 0.033 inch (0.84
mm) if not indicated on drawings.
b. Depth: As indicated on Drawings
C. Slip-Type Head Joints: Provide the following:
1. Single Long-Leg Runner System: ASTM C 645 top runner with 2-inch- (51-mm-) deep
flanges in thickness not less than indicated for studs, installed with studs friction fit into
top runner and with continuous bridging located within 12 inches (305 mm) of the top of
studs to provide lateral bracing.
a. Products: Subject to compliance with requirements, available products that may be
incorporated into the Work include, but are not limited to, the following:
1) Dietrich Metal Framing; SLP-TRK Slotted Deflection Track.
2) MBA Building Supplies; FlatSteel Deflection Track
3) Steel Network Inc. (The); VertiTrack VTD Series.
4) Superior Metal Trim; Superior Flex Track System (SFT).
5) Telling Industries; [Vertical Slip Track] [Vertical Slip Track II].
D. Firestop Tracks: Top runner manufactured to allow partition heads to expand and contract with
movement of the structure while maintaining continuity of fire-resistance-rated assembly
indicated; in thickness not less than indicated for studs and in width to accommodate depth of
studs.
1. Products: Subject to compliance with requirements, available products that may be
incorporated into the Work include, but are not limited to, the following:
a. Fire Trak Corp.; Fire Trak System[ attached to studs with Fire Trak Posi Klip.
b. Grace Construction Products; FlameSafe FlowTrak System.
c. Metal-Lite, Inc.; The System.
E. Flat Strap and Backing Plate: Steel sheet for blocking and bracing in length and width
indicated.
1. Minimum Base-Metal Thickness: As indicated on Drawings 0.033 inch (0.84 mm).
F. Cold-Rolled Channel Bridging: Steel, 0.053-inch (1.34-mm) minimum base-metal thickness,
with minimum 1/2-inch- (13-mm-) wide flanges.
1. Depth: 1-1/2 inches (38 mm)].
2. Clip Angle: Not less than 1-1/2 by 1-1/2 inches (38 by 38 mm), 0.068-inch- (1.72-mm-)
thick, galvanized steel.
G. Hat-Shaped, Rigid Furring Channels: ASTM C 645.
1. Minimum Base-Metal Thickness: 0.033 inch (0.84 mm).
2. Depth: 7/8 inch (22.2 mm).
H. Resilient Furring Channels: 1/2-inch- (13-mm-) deep, steel sheet members designed to reduce
sound transmission.
Jefferson Pump Station Improvements 092216 - 3 NON-STRUCTURAL
DWM Project No. 13-109 METAL FRAMING
GEC Project No. 09009.007 Addendum No. 1
1. Configuration: hat shaped.
I. Cold-Rolled Furring Channels: 0.053-inch (1.34-mm) uncoated-steel thickness, with minimum
1/2-inch- (13-mm-) wide flanges.
1. Depth: As indicated on Drawings 3/4 inch (19 mm).
2. Furring Brackets: Adjustable, corrugated-edge type of steel sheet with minimum
uncoated-steel thickness of 0.033 inch (0.8 mm).
3. Tie Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, 0.062-inch- (1.59-
mm-) diameter wire, or double strand of 0.048-inch- (1.21-mm-) diameter wire.
J. Z-Shaped Furring: With slotted or nonslotted web, face flange of 1-1/2 inches (32 mm), wall
attachment flange of 7/8 inch (22 mm), minimum uncoated-metal thickness of 0.018 inch (0.45
mm), and depth required to fit insulation thickness indicated.
2.3 SUSPENSION SYSTEMS
A. Tie Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, 0.062-inch- (1.59-mm-)
diameter wire, or double strand of 0.048-inch- (1.21-mm-) diameter wire.
B. Hanger Attachments to Concrete:
1. Anchors: Fabricated from corrosion-resistant materials with holes or loops for attaching
wire hangers and capable of sustaining, without failure, a load equal to 5 times that
imposed by construction as determined by testing according to ASTM E 488 by an
independent testing agency.
a. Type: Postinstalled, expansion anchor.
2. Powder-Actuated Fasteners: Suitable for application indicated, fabricated from
corrosion-resistant materials with clips or other devices for attaching hangers of type
indicated, and capable of sustaining, without failure, a load equal to 5 times that imposed
by construction as determined by testing according to ASTM E 1190 by an independent
testing agency.
C. Wire Hangers: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, 0.16 inch (4.12 mm)
in diameter.
D. Flat Hangers: Steel sheet, in size indicated on Drawings.
E. Carrying Channels: Cold-rolled, commercial-steel sheet with a base-metal thickness of 0.053
inch (1.34 mm) and minimum 1/2-inch- (13-mm-) wide flanges.
1. Depth: As indicated on Drawings
F. Furring Channels (Furring Members):
1. Cold-Rolled Channels: 0.053-inch (1.34-mm) uncoated-steel thickness, with minimum
1/2-inch- (13-mm-) wide flanges, 3/4 inch (19 mm) deep.
2. Steel Studs and Runners: ASTM C 645.
Jefferson Pump Station Improvements 092216 - 4 NON-STRUCTURAL
DWM Project No. 13-109 METAL FRAMING
GEC Project No. 09009.007 Addendum No. 1
a. Minimum Base-Metal Thickness: 0.033 inch (0.84 mm).
b. Depth: As indicated on Drawings
2.4 AUXILIARY MATERIALS
A. General: Provide auxiliary materials that comply with referenced installation standards.
1. Fasteners for Metal Framing: Of type, material, size, corrosion resistance, holding
power, and other properties required to fasten steel members to substrates.
B. Isolation Strip at Exterior Walls: Provide the following:
1. Foam Gasket: Adhesive-backed, closed-cell vinyl foam strips that allow fastener
penetration without foam displacement, 1/8 inch (3.2 mm) thick, in width to suit steel
stud size.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine areas and substrates, with Installer present, and including welded hollow-metal frames,
cast-in anchors, and structural framing, for compliance with requirements and other conditions
affecting performance of the Work.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Suspended Assemblies: Coordinate installation of suspension systems with installation of
overhead structure to ensure that anchors and other provisions for anchorages to building
structure have been installed to receive hangers at spacing required to support the Work and that
hangers will develop their full strength.
1. Furnish concrete inserts and other devices indicated to other trades for installation in
advance of time needed for coordination and construction.
3.3 INSTALLATION, GENERAL
A. Install supplementary framing, and blocking to support fixtures, equipment services, heavy trim,
grab bars, toilet accessories, furnishings, or similar construction.
B. Install bracing at terminations in assemblies.
C. Do not bridge building control and expansion joints with non-load-bearing steel framing
members. Frame both sides of joints independently.
3.4 INSTALLING FRAMED ASSEMBLIES
A. Install framing system components according to spacings indicated, but not greater than
spacings required by referenced installation standards for assembly types.
Jefferson Pump Station Improvements 092216 - 5 NON-STRUCTURAL
DWM Project No. 13-109 METAL FRAMING
GEC Project No. 09009.007 Addendum No. 1
1. Single-Layer Application: 16 inches (406 mm) o.c. unless otherwise indicated.
2. Multilayer Application: 16 inches (406 mm) o.c. unless otherwise indicated.
3. Tile Backing Panels: 16 inches (406 mm)] o.c. unless otherwise indicated.
B. Where studs are installed directly against exterior masonry walls or dissimilar metals at exterior
walls, install isolation strip between studs and exterior wall.
C. Install studs so flanges within framing system point in same direction.
D. Install tracks (runners) at floors and overhead supports. Extend framing full height to structural
supports or substrates above suspended ceilings except where partitions are indicated to
terminate at suspended ceilings. Continue framing around ducts penetrating partitions above
ceiling.
1. Slip-Type Head Joints: Where framing extends to overhead structural supports, install to
produce joints at tops of framing systems that prevent axial loading of finished
assemblies.
2. Door Openings: Screw vertical studs at jambs to jamb anchor clips on door frames;
install runner track section (for cripple studs) at head and secure to jamb studs.
a. Install two studs at each jamb.
b. Install cripple studs at head adjacent to each jamb stud, with a minimum 1/2-inch
(13-mm) clearance from jamb stud to allow for installation of control joint in
finished assembly.
c. Extend jamb studs through suspended ceilings and attach to underside of overhead
structure.
3. Other Framed Openings: Frame openings other than door openings the same as required
for door openings unless otherwise indicated. Install framing below sills of openings to
match framing required above door heads.
4. Fire-Resistance-Rated Partitions: Install framing to comply with fire-resistance-rated
assembly indicated and support closures and to make partitions continuous from floor to
underside of solid structure.
a. Firestop Track: Where indicated, install to maintain continuity of fire-resistance-
rated assembly indicated.
5. Sound-Rated Partitions: Install framing to comply with sound-rated assembly indicated.
6. Curved Partitions:
a. Bend track to uniform curve and locate straight lengths so they are tangent to arcs.
b. Begin and end each arc with a stud, and space intermediate studs equally along
arcs. On straight lengths of no fewer than two studs at ends of arcs, place studs 6
inches (150 mm) o.c.
E. Direct Furring:
1. Screw to wood framing.
2. Attach to concrete or masonry with stub nails, screws designed for masonry attachment,
or powder-driven fasteners spaced 24 inches (610 mm) o.c.
Jefferson Pump Station Improvements 092216 - 6 NON-STRUCTURAL
DWM Project No. 13-109 METAL FRAMING
GEC Project No. 09009.007 Addendum No. 1
F. Z-Furring Members:
1. Erect insulation, specified in Section 072100 "Thermal Insulation," vertically and hold in
place with Z-furring members spaced 24 inches (610 mm) o.c.
2. Except at exterior corners, securely attach narrow flanges of furring members to wall
with concrete stub nails, screws designed for masonry attachment, or powder-driven
fasteners spaced 24 inches (610 mm) o.c.
3. At exterior corners, attach wide flange of furring members to wall with short flange
extending beyond corner; on adjacent wall surface, screw-attach short flange of furring
channel to web of attached channel. At interior corners, space second member no more
than 12 inches (305 mm) from corner and cut insulation to fit.
G. Installation Tolerance: Install each framing member so fastening surfaces vary not more than
1/8 inch (3 mm) from the plane formed by faces of adjacent framing.
3.5 INSTALLING SUSPENSION SYSTEMS
A. Install suspension system components according to spacings indicated, but not greater than
spacings required by referenced installation standards for assembly types.
B. Isolate suspension systems from building structure where they abut or are penetrated by
building structure to prevent transfer of loading imposed by structural movement.
C. Suspend hangers from building structure as follows:
1. Install hangers plumb and free from contact with insulation or other objects within ceiling
plenum that are not part of supporting structural or suspension system.
a. Splay hangers only where required to miss obstructions and offset resulting
horizontal forces by bracing, countersplaying, or other equally effective means.
2. Where width of ducts and other construction within ceiling plenum produces hanger
spacings that interfere with locations of hangers required to support standard suspension
system members, install supplemental suspension members and hangers in the form of
trapezes or equivalent devices.
a. Size supplemental suspension members and hangers to support ceiling loads within
performance limits established by referenced installation standards.
3. Wire Hangers: Secure by looping and wire tying, either directly to structures or to
inserts, eye screws, or other devices and fasteners that are secure and appropriate for
substrate, and in a manner that will not cause hangers to deteriorate or otherwise fail.
4. Flat Hangers: Secure to structure, including intermediate framing members, by attaching
to inserts, eye screws, or other devices and fasteners that are secure and appropriate for
structure and hanger, and in a manner that will not cause hangers to deteriorate or
otherwise fail.
5. Do not connect or suspend steel framing from ducts, pipes, or conduit.
D. Fire-Resistance-Rated Assemblies: Wire tie furring channels to supports.
Jefferson Pump Station Improvements 092216 - 7 NON-STRUCTURAL
DWM Project No. 13-109 METAL FRAMING
GEC Project No. 09009.007 Addendum No. 1
E. Installation Tolerances: Install suspension systems that are level to within 1/8 inch in 12 feet (3
mm in 3.6 m) measured lengthwise on each member that will receive finishes and transversely
between parallel members that will receive finishes.
END OF SECTION 092216
Jefferson Pump Station Improvements 092400 - 1 PORTLAND CEMENT PLASTERING
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
SECTION 092400
PORTLAND CEMENT PLASTERING
ADDED – ADDENDUM NO. 1
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Interior vertical plasterwork.
2. Interior horizontal and nonvertical plasterwork.
B. Related Requirements:
1. Section 092216 "Non-Structural Metal Framing" for non-structural framing and
suspension systems that support gypsum board panels.
2. Section 099123 “Interior Painting”
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Samples for Verification: For each type of factory-prepared finish coat and for each color and
texture specified, 12 by 12 inches, and prepared on rigid backing.
1.4 QUALITY ASSURANCE
A. Mockups: Build mockups to verify selections made under Sample submittals, to demonstrate
aesthetic effects, and to set quality standards for materials and execution.
1. Build mockups for each substrate and finish texture indicated for cement plastering,
including accessories.
a. Size: TBD.
2. For interior plasterwork, simulate finished lighting conditions for review of mockups.
Jefferson Pump Station Improvements 092400 - 2 PORTLAND CEMENT PLASTERING
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
3. Approval of mockups does not constitute approval of deviations from the Contract
Documents contained in mockups unless Architect specifically approves such deviations
in writing.
4. Subject to compliance with requirements, approved mockups may become part of the
completed Work if undisturbed at time of Substantial Completion.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Store materials inside under cover, and keep them dry and protected against damage from
weather, moisture, direct sunlight, surface contamination, corrosion, construction traffic, and
other causes.
1.6 FIELD CONDITIONS
A. Comply with ASTM C 926 requirements.
B. Interior Plasterwork: Maintain room temperatures at greater than 40 deg F (4.4 deg C) for at
least 48 hours before plaster application, and continuously during and after application.
1. Avoid conditions that result in plaster drying out during curing period. Distribute heat
evenly; prevent concentrated or uneven heat on plaster.
2. Ventilate building spaces as required to remove water in excess of that required for
hydrating plaster in a manner that prevents drafts of air from contacting surfaces during
plaster application and until plaster is dry.
C. Factory-Prepared Finishes: Comply with manufacturer's written recommendations for
environmental conditions for applying finishes.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Fire-Resistance Ratings: Where indicated, provide cement plaster assemblies identical to those
of assemblies tested for fire resistance according to ASTM E 119 by a qualified testing agency.
2.2 METAL LATH
A. Expanded-Metal Lath: ASTM C 847, cold-rolled carbon-steel sheet with
ASTM A 653/A 653M, G60 (Z180), hot-dip galvanized-zinc coating.
1. ClarkDietrich™ Building Systems or equivalent manufacturer.
2. Diamond-Mesh Lath: Flat 3.4 lb/sq. yd. (1.8 kg/sq. m).
Jefferson Pump Station Improvements 092400 - 3 PORTLAND CEMENT PLASTERING
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
2.3 ACCESSORIES
A. General: Comply with ASTM C 1063, and coordinate depth of trim and accessories with
thicknesses and number of plaster coats required.
B. Metal Accessories:
1. ClarkDietrich™ Building Systems or equivalent manufacturer.
2. Cornerbeads: Fabricated from zinc.
a. Smallnose cornerbead with expanded flanges; use unless otherwise indicated.
b. Smallnose cornerbead with perforated flanges; use on curved corners.
c. Smallnose cornerbead with expanded flanges reinforced by perforated stiffening
rib; use on columns and for finishing unit masonry corners.
3. Casing Beads: Fabricated from zinc; square-edged style; with expanded flanges.
4. Control Joints: Fabricated from zinc ; one-piece-type, folded pair of unperforated screeds
in M-shaped configuration; with perforated flanges and removable protective tape on
plaster face of control joint.
2.4 MISCELLANEOUS MATERIALS
A. Water for Mixing and Finishing Plaster: Potable and free of substances capable of affecting
plaster set or of damaging plaster, lath, or accessories.
B. Fiber for Base Coat: Alkaline-resistant glass or polypropylene fibers, 1/2 inch (13 mm) long,
free of contaminants, manufactured for use in cement plaster.
C. Fasteners for Attaching Metal Lath to Substrates: ASTM C 1063.
D. Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, not less than 0.0475-inch (1.21-
mm) diameter unless otherwise indicated.
2.5 PLASTER MATERIALS
A. Portland Cement: ASTM C 150/C 150M, Type I.
1. Color for Finish Coats: White.
B. Lime: ASTM C 206, Type S; or ASTM C 207, Type S.
C. Sand Aggregate: ASTM C 897.
1. Color for Job-Mixed Finish Coats: White.
2.6 PLASTER MIXES
A. General: Comply with ASTM C 926 for applications indicated.
Jefferson Pump Station Improvements 092400 - 4 PORTLAND CEMENT PLASTERING
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
1. Fiber Content: Add fiber to base-coat mixes after ingredients have mixed at least two
minutes. Comply with fiber manufacturer's written instructions for fiber quantities in
mixes, but do not exceed 1 lb of fiber/cu. yd. (0.6 kg of fiber/cu. m) of cementitious
materials.
B. Base-Coat Mixes for Use over Metal Lath: Scratch and brown coats for three-coat plasterwork
as follows:
1. Portland Cement Mixes:
a. Scratch Coat: For cementitious material, mix 1 part portland cement and 3/4 to 1-
1/2 parts lime. Use 2-1/2 to 4 parts aggregate per part of cementitious material.
b. Brown Coat: For cementitious material, mix 1 part portland cement and 3/4 to 1-
1/2 parts lime. Use 3 to 5 parts aggregate per part of cementitious material, but not
less than volume of aggregate used in scratch coat.
2. Masonry Cement Mixes:
a. Scratch Coat: Mix 1 part masonry cement and 2-1/2 to 4 parts aggregate.
b. Brown Coat: Mix 1 part masonry cement and 3 to 5 parts aggregate, but not less
than volume of aggregate used in scratch coat.
3. Portland and Masonry Cement Mixes:
a. Scratch Coat: For cementitious material, mix 1 part portland cement and 1 part
masonry cement. Use 2-1/2 to 4 parts aggregate per part of cementitious material.
b. Brown Coat: For cementitious material, mix 1 part portland cement and 1 part
masonry cement. Use 3 to 5 parts aggregate per part of cementitious material, but
not less than volume of aggregate used in scratch coat.
4. Plastic Cement Mixes:
a. Scratch Coat: Mix 1 part plastic cement and 2-1/2 to 4 parts aggregate.
b. Brown Coat: Mix 1 part plastic cement and 3 to 5 parts aggregate, but not less than
volume of aggregate used in scratch coat.
5. Portland and Plastic Cement Mixes:
a. Scratch Coat: For cementitious material, mix 1 part plastic cement and 1 part
portland cement. Use 2-1/2 to 4 parts aggregate per part of cementitious material.
b. Brown Coat: For cementitious material, mix 1 part plastic cement and 1 part
portland cement. Use 3 to 5 parts aggregate per part of cementitious material, but
not less than volume of aggregate used in scratch coat.
C. Base-Coat Mixes for Use over Unit Masonry: Single base (scratch) coat for two-coat
plasterwork on low-absorption plaster bases as follows:
1. Portland Cement Mix: For cementitious material, mix 1 part portland cement and 0 to 3/4
part lime. Use 2-1/2 to 4 parts aggregate per part of cementitious material.
Jefferson Pump Station Improvements 092400 - 5 PORTLAND CEMENT PLASTERING
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
2. Portland and Masonry Cement Mix: For cementitious material, mix 1 part portland
cement and 1 part masonry cement. Use 2-1/2 to 4 parts aggregate per part of
cementitious material.
3. Plastic Cement Mix: Use 1 part plastic cement and 2-1/2 to 4 parts aggregate.
D. Job-Mixed Finish-Coat Mixes:
1. Portland Cement Mix: For cementitious materials, mix 1 part portland cement and 1-1/2
to 2 parts lime. Use 1-1/2 to 3 parts aggregate per part of cementitious material.
2. Masonry Cement Mix: Use 1 part masonry cement and 1-1/2 to 3 parts aggregate.
3. Portland and Masonry Cement Mix: For cementitious materials, mix 1 part portland
cement and 1 part masonry cement. Use 1-1/2 to 3 parts aggregate per part of
cementitious material.
4. Plastic Cement Mix: Use 1 part plastic cement and 1-1/2 to 3 parts aggregate.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates and conditions, with Installer present, for compliance with requirements for
installation tolerances and other conditions affecting performance of the Work.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Protect adjacent work from soiling, spattering, moisture deterioration, and other harmful effects
caused by plastering.
B. Prepare smooth, solid substrates for plaster according to ASTM C 926.
3.3 INSTALLING METAL LATH
A. Metal Lath: Install according to ASTM C 1063.
1. Partition Framing and Vertical Furring: Install flat-diamond-mesh lath.
2. Flat-Ceiling and Horizontal Framing: Install flat-diamond-mesh lath.
3. On Solid Surfaces, Not Otherwise Furred: Install self-furring, diamond-mesh lath.
3.4 INSTALLING ACCESSORIES
A. Install according to ASTM C 1063 and at locations indicated on Drawings.
B. Reinforcement for External (Outside) Corners:
1. Install cornerbead at exterior locations.
Jefferson Pump Station Improvements 092400 - 6 PORTLAND CEMENT PLASTERING
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
2. Install cornerbead at interior locations.
3.5 PLASTER APPLICATION
A. General: Comply with ASTM C 926.
1. Do not deviate more than plus or minus 1/4 inch in 10 feet (6 mm in 3 m) from a true
plane in finished plaster surfaces when measured by a 10-foot (3-m) straightedge placed
on surface.
2. Finish plaster flush with metal frames and other built-in metal items or accessories that
act as a plaster ground unless otherwise indicated. Where casing bead does not terminate
plaster at metal frame, cut base coat free from metal frame before plaster sets and groove
finish coat at junctures with metal.
3. Provide plaster surfaces that are ready to receive field-applied finishes indicated.
B. Bonding Compound: Apply on unit masonry] substrates for direct application of plaster.
C. Walls; Base-Coat Mixes for Use over Metal Lath: For scratch and brown coats, for three-coat
plasterwork with 3/4-inch (19-mm) total thickness, as follows:
1. Portland and masonry cement mixes.
D. Ceilings; Base-Coat Mixes for Use over Metal Lath: For scratch and brown coats, for three-coat
plasterwork and having 3/4-inch (19-mm) total thickness for metal lath on concrete, as follows:
1. Portland and masonry cement mixes.
E. Match surface texture of adjacent surfaces unless otherwise indicated.
3.6 PLASTER REPAIRS
A. Repair or replace work to eliminate cracks, dents, blisters, buckles, crazing and check cracking,
dry outs, efflorescence, sweat outs, and similar defects and where bond to substrate has failed.
3.7 CLEANING AND PROTECTION
A. Remove temporary protection and enclosure of other work after plastering is complete.
Promptly remove plaster from door frames, windows, and other surfaces not indicated to be
plastered. Repair floors, walls, and other surfaces stained, marred, or otherwise damaged during
plastering.
END OF SECTION 092400
Jefferson Pump Station Improvements 092613 - 1 GYPSUM VENEER
DWM Project No. 13-109 PLASTERING
GEC Project No. 09009.007 Addendum No. 1
SECTION 092613
GYPSUM VENEER PLASTERING
ADDED – ADDENDUM NO. 1
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Gypsum veneer plaster and gypsum base for veneer plaster.
2. Gypsum veneer plaster over masonry surfaces.
B. Related Requirements:
1. Section 092216 "Non-Structural Metal Framing" for non-load-bearing steel framing.
2. Section 099123 “Interior Painting”
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings:
1. Show locations, fabrication, and installation of control joints, reveals, and trim; include
plans, elevations, sections, details of components, and attachments to other work.
C. Samples: For the following products:
1. Trim Accessories: Full-size Sample in 10-inch (250-mm) length for each trim accessory.
2. Textured Finishes: Manufacturer's standard sizefor each textured finish and on rigid
backing.
Jefferson Pump Station Improvements 092613 - 2 GYPSUM VENEER
DWM Project No. 13-109 PLASTERING
GEC Project No. 09009.007 Addendum No. 1
1.4 QUALITY ASSURANCE
A. Mockups: Provide a full-thickness finish mockup for each type and finish of gypsum veneer
plaster and substrate to demonstrate aesthetic effects and set quality standards for materials and
execution.
1. Architect will select representative surfaces and conditions for application of each type of
gypsum veneer plaster and substrate.
2. Provide mockups of ceilings and partitions in sizes of at least 10 sq. ft.
3. Apply gypsum veneer plaster, according to requirements for the completed Work, after
permanent lighting and other environmental services have been activated.
4. Subject to compliance with requirements, approved mockups may become part of the
completed Work if undisturbed at time of Substantial Completion.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Deliver materials in original packages, containers, and bundles bearing brand name and
identification of manufacturer or supplier.
B. Store materials inside under cover and keep them dry and protected against damage from
weather, direct sunlight, surface contamination, corrosion, construction traffic, and other causes.
C. Stack panels flat on leveled supports off floor or slab to prevent sagging.
1.6 FIELD CONDITIONS
A. Environmental Limitations: Comply with ASTM C 843 requirements or gypsum veneer plaster
manufacturer's written recommendations, whichever are more stringent.
B. Room Temperatures: Maintain not less than 55 deg F (13 deg C) or more than 80 deg F (27
deg C) for seven days before application of gypsum base and gypsum veneer plaster,
continuously during application, and after application until veneer plaster is dry.
C. Avoid conditions that result in gypsum veneer plaster drying too rapidly.
1. Distribute heat evenly; prevent concentrated or uneven heat on veneer plaster.
2. Maintain relative humidity levels, for prevailing ambient temperature, that produce
normal drying conditions.
3. Ventilate building spaces in a manner that prevents drafts of air from contacting surfaces
during veneer plaster application until it is dry.
D. Do not install panels that are wet, moisture damaged, or mold damaged.
1. Indications that panels are wet or moisture damaged include, but are not limited to,
discoloration, sagging, and irregular shape.
2. Indications that panels are mold damaged include, but are not limited to, fuzzy or
splotchy surface contamination and discoloration.
Jefferson Pump Station Improvements 092613 - 3 GYPSUM VENEER
DWM Project No. 13-109 PLASTERING
GEC Project No. 09009.007 Addendum No. 1
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Source Limitations: Obtain gypsum veneer plaster products, including gypsum base for veneer
plaster, joint reinforcing tape, and embedding material, from single manufacturer.
2.2 PERFORMANCE REQUIREMENTS
A. STC-Rated Assemblies: For STC-rated assemblies, provide materials and construction identical
to those tested in assembly indicated according to ASTM E 90 and classified according to
ASTM E 413 by an independent testing agency.
2.3 GYPSUM VENEER PLASTER
A. One-Component Gypsum Veneer Plaster: ASTM C 587, ready-mixed, smooth, finish-coat
veneer plaster formulated for application directly over substrate without use of separate base-
coat material.
1. Georgia Pacific Building Products
2. National Gypsum Company
3. United States Gypsum Company
B. Two-Component Gypsum Veneer Plaster: ASTM C 587, with separate formulations; one for
base-coat application and one for finish-coat application over substrates.
1. Base Coat:
a. National Gypsum Company
b. United States Gypsum Company
2. Smooth Finish Coat:
a. National Gypsum Company
b. United States Gypsum Company
3. Provide job-aggregated components, as standard for manufacturer, to comply with
manufacturer's written recommendations.
2.4 TRIM ACCESSORIES
A. Standard Trim: ASTM C 1047, provided or approved by manufacturer for use in gypsum veneer
plaster applications indicated.
1. Material: rolled zinc.
2. Shapes:
Jefferson Pump Station Improvements 092613 - 4 GYPSUM VENEER
DWM Project No. 13-109 PLASTERING
GEC Project No. 09009.007 Addendum No. 1
a. Cornerbead.
b. Bullnose bead.
c. LC-Bead: J-shaped; exposed long flange receives veneer plaster.
d. L-Bead: L-shaped; exposed long flange receives veneer plaster.
e. U-Bead: J-shaped; exposed short flange does not receive veneer plaster.
f. Curved-Edge Cornerbead: With notched or flexible flanges.
g. Control joints.
B. Aluminum Trim: Extruded accessories of profiles and dimensions indicated.
1. Fry Reglet Corporation or equivalent manufacturer.
2. Aluminum: Alloy and temper with not less than the strength and durability properties of
ASTM B 221 (ASTM B 221M), Alloy 6063-T5.
3. Finish: Corrosion-resistant primer compatible with veneer plaster.
2.5 JOINT REINFORCING MATERIALS
A. General: Comply with joint strength requirements in ASTM C 587 and with gypsum veneer
plaster manufacturer's written recommendations for each application indicated.
B. Joint Tape:
1. Gypsum Base for Veneer Plaster: As recommended by gypsum veneer plaster
manufacturer for applications indicated
2. Cementitious Backer Units: As recommended by cementitious backer unit manufacturer.
C. Embedding Material for Joint Tape:
1. Gypsum Base for Veneer Plaster: As recommended by gypsum veneer plaster
manufacturer for use with joint-tape material and gypsum veneer plaster applications
indicated.
2. Cementitious Backer Units: As recommended by cementitious backer unit manufacturer
for applications indicated.
2.6 AUXILIARY MATERIALS
A. General: Provide auxiliary materials that comply with referenced product standards and
manufacturer's written recommendations.
B. Bonding Agent: ASTM C 631, polyvinyl acetate.
C. Laminating Adhesive: Adhesive or joint compound recommended by manufacturer for directly
adhering gypsum-base, face-layer panels to backing-layer panels in multilayer construction.
D. Steel Drill Screws: ASTM C 1002 unless otherwise indicated.
1. Use screws complying with ASTM C 954 for fastening panels to steel members from
0.033 to 0.112 inch (0.84 to 2.84 mm) thick.
Jefferson Pump Station Improvements 092613 - 5 GYPSUM VENEER
DWM Project No. 13-109 PLASTERING
GEC Project No. 09009.007 Addendum No. 1
E. Sound Attenuation Blankets: ASTM C 665, Type I (blankets without membrane facing),
produced by combining thermosetting resins with mineral fibers manufactured from glass, slag
wool, or rock wool.
1. Fire-Resistance-Rated Assemblies: Comply with mineral-fiber requirements of assembly.
F. Acoustical Joint Sealant: Manufacturer's standard nonsag, paintable, nonstaining latex sealant
complying with ASTM C 843. Product effectively reduces airborne sound transmission through
perimeter joints and openings in building construction, as demonstrated by testing
representative assemblies according to ASTM E 90.
G. Patching Mortar: Dry-pack patching mortar, consisting of 1 part portland cement to 2-1/2 parts
fine aggregate passing a No. 16 (1.18-mm) sieve, using only enough water for handling and
placing.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Installer present, for compliance with
requirements for installation tolerances and other conditions affecting performance of the Work.
B. Examine panels before installation. Reject panels that are wet, moisture damaged, or mold
damaged.
C. Masonry Substrates: Verify that mortar joints are struck flush.
D. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Masonry Substrates: Prepare according to gypsum veneer plaster manufacturer's written
recommendations and as follows:
1. Clean surfaces to remove dirt, grease, oil, and other foreign matter and deposits that
could impair bond with gypsum veneer plaster.
2. Apply bonding agent on dry masonry substrates.
3.3 GYPSUM VENEER PLASTERING
A. Bonding Agent: Apply bonding agent on dry masonry according to gypsum veneer plaster
manufacturer's written recommendations.
B. Gypsum Veneer Plaster Mixing: Mechanically mix gypsum veneer plaster materials to comply
with ASTM C 843 and with gypsum veneer plaster manufacturer's written recommendations.
Jefferson Pump Station Improvements 092613 - 6 GYPSUM VENEER
DWM Project No. 13-109 PLASTERING
GEC Project No. 09009.007 Addendum No. 1
C. Gypsum Veneer Plaster Application: Comply with ASTM C 843 and with veneer plaster
manufacturer's written recommendations.
1. One-Component Gypsum Veneer Plaster: Trowel apply base coat over substrate to
uniform thickness. Fill all voids and imperfections. Immediately double back with same
mixer batch of plaster to a uniform total thickness of 1/16 to 3/32 inch (1.6 to 2.4 mm).
2. Two-Component Gypsum Veneer Plaster:
a. Base Coat: Hand trowel or machine apply base coat over substrate to a uniform
thickness of 1/16 to 3/32 inch (1.6 to 2.4 mm). Fill all voids and imperfections.
b. Finish Coat: Trowel apply finish-coat plaster over base-coat plaster to a uniform
thickness of 1/16 to 3/32 inch (1.6 to 2.4 mm).
3. Where gypsum veneer plaster abuts only metal door frames, windows, and other units,
groove finish coat to eliminate spalling.
4. Do not apply veneer plaster to gypsum base if paper facing has degraded from exposure
to sunlight. Before applying veneer plaster, use remedial methods to restore bonding
capability to degraded paper facing according to manufacturer's written recommendations
and as approved by Architect.
D. Concealed Surfaces: Do not omit gypsum veneer plaster behind cabinets, furniture, furnishings,
and similar removable items. Omit veneer plaster in the following areas where it will be
concealed from view in the completed Work unless otherwise indicated or required to maintain
fire-resistance and STC ratings:
1. Above suspended ceilings.
2. Behind wood paneling.
E. Gypsum Veneer Plaster Finish: Smooth-troweled finish unless otherwise indicated.
3.4 PROTECTION
A. Protect installed gypsum veneer plaster from damage from weather, condensation, construction,
and other causes during remainder of the construction period.
B. Remove and replace gypsum veneer plaster and gypsum base panels that are wet, moisture
damaged, or mold damaged.
1. Indications that gypsum base panels are wet or moisture damaged include, but are not
limited to, discoloration, sagging, and irregular shape.
2. Indications that gypsum base panels are mold damaged include, but are not limited to,
fuzzy or splotchy surface contamination and discoloration.
END OF SECTION 092613
Jefferson Pump Station Improvements 092900 - 1 GYPSUM BOARD
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
SECTION 092900
GYPSUM BOARD
REVISED – ADDENDUM NO. 1
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes:
1. Interior gypsum board
2. Gypsum board soffit panels
B. Related Requirements:
1. Section 092216 "Non-Structural Metal Framing" for non-structural framing and
suspension systems that support gypsum board panels.
2. Section 099123 “Interior Painting”
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Samples:
1. Trim Accessories: Full-size Sample in 12-inch-long length for each trim accessory
indicated.
1.4 DELIVERY, STORAGE AND HANDLING
A. Store materials inside under cover and keep them dry and protected against weather,
condensation, direct sunlight, construction traffic, and other potential causes of damage. Stack
panels flat and supported on risers on a flat platform to prevent sagging.
1.5 FIELD CONDITIONS
A. Environmental Limitations: Comply with ASTM C 840 requirements or gypsum board
manufacturer's written recommendations, whichever are more stringent.
Jefferson Pump Station Improvements 092900 - 2 GYPSUM BOARD
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
B. Do not install paper-faced gypsum panels until installation areas are enclosed and conditioned.
C. Do not install panels that are wet, those that are moisture damaged, and those that are mold
damaged.
1. Indications that panels are wet or moisture damaged include, but are not limited to,
discoloration, sagging, or irregular shape.
2. Indications that panels are mold damaged include, but are not limited to, fuzzy or
splotchy surface contamination and discoloration.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Fire-Resistance-Rated Assemblies: For fire-resistance-rated assemblies, provide materials and
construction identical to those tested in assembly indicated according to ASTM E 119 by an
independent testing agency.
B. STC-Rated Assemblies: For STC-rated assemblies, provide materials and construction identical
to those tested in assembly indicated according to ASTM E 90 and classified according to
ASTM E 413 by an independent testing agency.
2.2 INTERIOR GYPSUM BOARD
A. Manufacturers: Subject to compliance with requirements, available manufacturers offering
products that may be incorporated into the Work include, but are not limited to, the following:
1. American Gypsum
2. CertainTeed Corp.
3. Georgia-Pacific Gypsum LLC
4. Lafarge North America Inc.
5. National Gypsum Company
6. Temple-Inland
7. USG Corporation
B. Gypsum Wallboard: ASTM C 1396/C 1396M
1. Thickness: 5/8 inch
2. Long Edges: Tapered
C. Gypsum Board, Type X: ASTM C 1396/C 1396M
1. Thickness: 5/8 inch
2. Long Edges: Tapered
Jefferson Pump Station Improvements 092900 - 3 GYPSUM BOARD
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
D. Flexible Gypsum Board: ASTM C 1396/C 1396M. Manufactured to bend to fit radii and to be
more flexible than standard regular-type gypsum board of same thickness.
1. Thickness: 1/4 inch
2. Long Edges: Tapered
E. Gypsum Ceiling Board: ASTM C 1396/C 1396M
1. Thickness: 5/8 inch
2. Long Edges: Tapered
F. Moisture and Mold-Resistant Glass-Mat Gypsum Board: ASTM C 1178/C 1178M, with
moisture- and mold-resistant core encased in a moisture-resistant fiberglass mat.
1. Core: 5/8 inch, Type C as required by fire-resistance-rated assembly indicated on
Drawings.
2. Long Edges: Tapered
3. Mold Resistance: ASTM D 3273, score of 10 as rated according to ASTM D 3274.
4. Comply with ASTM C1658, C1396, C1177 and E136.
5. Manufacturers: Subject to compliance with requirements, available manufacturers
offering products that may be incorporated into the Work include, but are not limited to,
the following:
a. CertainTeed Corp.; GlasRoc Tile Backer
b. Georgia-Pacific Gypsum LLC; DensShield Tile Backer
c. USG Corporation; Sheetrock Brand Glass-Mat Panels Mold Tough
G. Cementitious Backer Units: ANSI A118.9 and ASTM C 1288 or 1325, with manufacturer's
standard edges.
1. Products: Subject to compliance with requirements, provide one of the following:
a. C-Cure; C-Cure Board 990
b. CertainTeed Corp.; BackerBoard
c. Custom Building Products; Wonderboard
d. FinPan, Inc.; Util-A-Crete Concrete Backer Board
e. James Hardie Building Products, Inc.; Hardiebacker
f. National Gypsum Company, Permabase Cement Board
g. USG Corporation; DUROCK Cement Board
2. Thickness: 5/8 inch
3. Mold Resistance: ASTM D 3273, score of 10 as rated according to ASTM D 3274.
Jefferson Pump Station Improvements 092900 - 4 GYPSUM BOARD
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
2.3 SPECIALTY GYPSUM BOARD
A. Gypsum Board, Type C: ASTM C 1396/C 1396M. Manufactured to have increased fire-
resistive capability.
1. Products: Subject to compliance with requirements, available products that may be
incorporated into the Work include, but are not limited to, the following:
a. American Gypsum; Firebloc Type C
b. CertainTeed Corp.; ProRoc Type C
c. Georgia-Pacific Gypsum LLC; Fireguard C
d. Lafarge North America Inc.; Firecheck Type C
e. National Gypsum Company; Gold Bond Fire-Shield C
f. USG Corporation; Firecode C Core
2. Thickness: As required by fire-resistance-rated assembly indicated on Drawings.
3. Long Edges: Tapered
2.4 EXTERIOR GYPSUM BOARD FOR CEILINGS AND SOFFITS
A. Exterior Gypsum Soffit Board: ASTM C 1396/C 1396M, with manufacturer's standard edges.
1. Products: Subject to compliance with requirements, available products that may be
incorporated into the Work include, but are not limited to, the following:
a. American Gypsum; Firebloc Type C
b. CertainTeed Corp.; ProRoc Type C
c. Georgia-Pacific Gypsum LLC; Fireguard C
d. Lafarge North America Inc.; Firecheck Type C
e. National Gypsum Company; Gold Bond Fire-Shield C
f. USG Corporation; Firecode C Core
2. Core: As indicated 5/8 inch (15.9 mm), Type X
2.5 TRIM ACCESSORIES
A. Interior Trim: ASTM C 1047
1. Material: Galvanized coated steel sheet
2. Shapes:
a. Cornerbead
b. Bullnose bead
c. LC-Bead: J-shaped; exposed long flange receives joint compound.
d. L-Bead: L-shaped; exposed long flange receives joint compound.
e. Expansion (control) joint.
f. Curved-Edge Cornerbead: With notched or flexible flanges.
Jefferson Pump Station Improvements 092900 - 5 GYPSUM BOARD
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
B. Exterior Trim: ASTM C 1047
1. Material: Hot-dip galvanized-steel sheet.
2. Shapes:
a. Cornerbead
b. LC-Bead: J-shaped; exposed long flange receives joint compound.
2.6 JOINT TREATMENT MATERIALS
A. General: Comply with ASTM C 475/C 475M.
B. Joint Tape:
1. Interior Gypsum Board: Paper
2. Exterior Gypsum Soffit Board: Paper
3. Tile Backing Panels: As recommended by panel manufacturer.
C. Joint Compound for Interior Gypsum Board: For each coat use formulation that is compatible
with other compounds applied on previous or for successive coats.
1. Embedding and First Coat: For embedding tape and first coat on joints, fasteners, and
trim flanges, use setting-type taping compound.
a. Use setting-type compound for installing paper-faced metal trim accessories.
2. Fill Coat: For second coat, use sandable topping compound.
3. Finish Coat: For third coat, use sandable topping compound.
4. Skim Coat: For final coat of Level 5 finish, use sandable topping compound.
D. Joint Compound for Exterior Applications:
1. Exterior Gypsum Soffit Board: Use setting-type taping compound and setting-type,
sandable topping compound.
E. Backing Panels:
1. Glass-Mat, Water-Resistant Backing Panel: As recommended by backing panel
manufacturer.
2. Cementitious Backer Units: As recommended by backer unit manufacturer.
3. Water-Resistant Gypsum Backing Board: Use setting-type taping compound and setting-
type, sandable topping compound.
2.7 AUXILIARY MATERIALS
A. General: Provide auxiliary materials that comply with referenced installation standards and
manufacturer's written recommendations.
B. Laminating Adhesive: Adhesive or joint compound recommended for directly adhering
gypsum panels to continuous substrate.
Jefferson Pump Station Improvements 092900 - 6 GYPSUM BOARD
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
C. Steel Drill Screws: ASTM C 1002, unless otherwise indicated.
1. Use screws complying with ASTM C 954 for fastening panels to steel members from
0.033 to 0.112 inch thick.
2. For fastening cementitious backer units, use screws of type and size recommended by
panel manufacturer.
D. Sound Attenuation Blankets: ASTM C 665, Type I (blankets without membrane facing)
produced by combining thermosetting resins with mineral fibers manufactured from glass, slag
wool, or rock wool.
1. Fire-Resistance-Rated Assemblies: Comply with mineral-fiber requirements of
assembly.
E. Acoustical Joint Sealant: Manufacturer's standard nonsag, paintable, nonstaining latex sealant
complying with ASTM C 834. Product effectively reduces airborne sound transmission through
perimeter joints and openings in building construction as demonstrated by testing representative
assemblies according to ASTM E 90.
1. Products: Subject to compliance with requirements, provide one of the following:
a. Accumetric LLC; BOSS 824 Acoustical Sound Sealant
b. Grabber Construction Products; Acoustical Sealant GSC
c. Pecora Corporation
d. Specified Technologies, Inc.; Smoke N Sound Acoustical Sealant
e. USG Corporation; SHEETROCK Acoustical Sealant
2. Acoustical joint sealant shall have a VOC content of 250 g/L or less when calculated
according to 40 CFR 59, Subpart D (EPA Method 24).
3. Acoustical joint sealant shall comply with the testing and product requirements of the
California Department of Health Services' "Standard Practice for the Testing of Volatile
Organic Emissions from Various Sources Using Small-Scale Environmental Chambers".
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine areas and substrates including welded hollow-metal frames and framing, with Installer
present, for compliance with requirements and other conditions affecting performance.
B. Examine panels before installation. Reject panels that are wet, moisture damaged, and mold
damaged.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 APPLYING AND FINISHING PANELS, GENERAL
A. Comply with ASTM C 840.
Jefferson Pump Station Improvements 092900 - 7 GYPSUM BOARD
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
B. Install ceiling panels across framing to minimize the number of abutting end joints and to avoid
abutting end joints in central area of each ceiling. Stagger abutting end joints of adjacent panels
not less than one framing member.
C. Install panels with face side out. Butt panels together for a light contact at edges and ends with
not more than 1/16 inch of open space between panels. Do not force into place.
D. Locate edge and end joints over supports, except in ceiling applications where intermediate
supports or gypsum board back-blocking is provided behind end joints. Do not place tapered
edges against cut edges or ends. Stagger vertical joints on opposite sides of partitions. Do not
make joints other than control joints at corners of framed openings.
E. Form control and expansion joints with space between edges of adjoining gypsum panels.
F. Cover both faces of support framing with gypsum panels in concealed spaces (above ceilings,
etc.), except in chases braced internally.
1. Unless concealed application is indicated or required for sound, fire, air, or smoke
ratings, coverage may be accomplished with scraps of not less than 8 sq. ft. in area.
2. Fit gypsum panels around ducts, pipes, and conduits.
3. Where partitions intersect structural members projecting below underside of floor/roof
slabs and decks, cut gypsum panels to fit profile formed by structural members; allow
1/4- to 3/8-inch-wide joints to install sealant.
G. Isolate perimeter of gypsum board applied to non-load-bearing partitions at structural
abutments, except floors. Provide 1/4- to 1/2-inch-wide spaces at these locations and trim edges
with edge trim where edges of panels are exposed. Seal joints between edges and abutting
structural surfaces with sealant.
H. Attachment to Steel Framing: Attach panels so leading edge or end of each panel is attached to
open (unsupported) edges of stud flanges first.
I. STC-Rated Assemblies: Seal construction at perimeters, behind control joints, and at openings
and penetrations with a continuous bead of acoustical sealant. Install acoustical sealant at both
faces of partitions at perimeters and through penetrations. Comply with ASTM C 919 and with
manufacturer's written recommendations for locating edge trim and closing off sound-flanking
paths around or through assemblies, including sealing partitions above acoustical ceilings.
J. Install sound attenuation blankets before installing gypsum panels unless blankets are readily
installed after panels have been installed on one side.
3.3 APPLYING INTERIOR GYPSUM BOARD
A. Install interior gypsum board in the following locations:
1. Wallboard Type: As indicated on Drawings.
2. Type X: Where required for fire-resistance-rated assembly.
3. Flexible Type: As indicated on Drawings Apply in double layer at curved assemblies.
Jefferson Pump Station Improvements 092900 - 8 GYPSUM BOARD
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
4. Ceiling Type: Ceiling surfaces as indicated on Drawings.
5. Moisture- and Mold-Resistant Type: As indicated on Drawings.
6. Type C: Where required for specific fire-resistance-rated assembly indicated.
7. On ceilings, apply gypsum panels before wall/partition board application to greatest
extent possible and at right angles to framing unless otherwise indicated.
8. On partitions/walls, apply gypsum panels vertically (parallel to framing), or horizontally
(perpendicular to framing) unless otherwise indicated or required by fire-resistance-rated
assembly, and minimize end joints.
a. Stagger abutting end joints not less than one framing member in alternate courses
of panels.
b. At stairwells and other high walls, install panels horizontally unless otherwise
indicated or required by fire-resistance-rated assembly.
9. On Z-furring members, apply gypsum panels vertically (parallel to framing) with no end
joints. Locate edge joints over furring members.
10. Fastening Methods: Apply gypsum panels to supports with steel drill screws.
B. Multilayer Application:
1. On partitions/walls, apply gypsum board indicated for base layers and face layers
vertically (parallel to framing) with joints of base layers located over stud or furring
member and face-layer joints offset at least one stud or furring member with base-layer
joints, unless otherwise indicated or required by fire-resistance-rated assembly. Stagger
joints on opposite sides of partitions.
2. On Z-furring members, apply base layer vertically (parallel to framing) and face layer
either vertically (parallel to framing) or horizontally (perpendicular to framing) with
vertical joints offset at least one furring member. Locate edge joints of base layer over
furring members.
3. Fastening Methods: Fasten base layers with screws; fasten face layers with adhesive and
supplementary screw fasteners.
C. Laminating to Substrate: Where gypsum panels are indicated as directly adhered to a substrate
(other than studs, joists, furring members, or base layer of gypsum board), comply with gypsum
board manufacturer's written recommendations and temporarily brace or fasten gypsum panels
until fastening adhesive has set.
D. Curved Surfaces:
1. Install panels horizontally (perpendicular to supports) and unbroken, to extent possible,
across curved surface plus 12-inch-long straight sections at ends of curves and tangent to
them.
2. For double-layer construction, fasten base layer to studs with screws 16 inches o.c.
Center gypsum board face layer over joints in base layer, and fasten to studs with screws
spaced 12 inches o.c.
Jefferson Pump Station Improvements 092900 - 9 GYPSUM BOARD
DWM Project No. 13-109 Addendum No. 1
GEC Project No. 09009.007
3.4 APPLYING EXTERIOR GYPSUM PANELS FOR CEILINGS AND SOFFITS
A. Apply panels perpendicular to supports, with end joints staggered and located over supports.
1. Install with 1/4-inch open space where panels abut other construction or structural
penetrations.
2. Fasten with corrosion-resistant screws.
3.5 FINISHING GYPSUM BOARD
A. General: Treat gypsum board joints, interior angles, edge trim, control joints, penetrations,
fastener heads, surface defects, and elsewhere as required to prepare gypsum board surfaces for
decoration. Promptly remove residual joint compound from adjacent surfaces.
B. Prefill open joints, rounded or beveled edges, and damaged surface areas.
C. Apply joint tape over gypsum board joints, except for trim products specifically indicated as
not intended to receive tape.
D. Gypsum Board Finish Levels: Finish panels to levels indicated below and according to
ASTM C 840:
1. Level 1: Ceiling plenum areas, concealed areas, and where indicated.
2. Level 5: At panel surfaces that will be exposed to view unless otherwise indicated.
a. Primer and its application to surfaces are specified in Section 099123 "Interior
Painting".
3.6 FINISH PARTICLE BOARD/PLYWOOD CEILING PANEL
A. Ceiling panel shall be cut to size and shop painted; install fixed portion of particle board panels
to light gage metal framing system.
3.7 PROTECTION
A. Protect adjacent surfaces from drywall compound and promptly remove from floors and other
non-drywall surfaces. Repair surfaces stained, marred, or otherwise damaged during drywall
application.
B. Protect installed products from damage from weather, condensation, direct sunlight,
construction, and other causes during remainder of the construction period.
C. Remove and replace panels that are wet, moisture damaged, and mold damaged.
1. Indications that panels are wet or moisture damaged include, but are not limited to,
discoloration, sagging, or irregular shape.
2. Indications that panels are mold damaged include, but are not limited to, fuzzy or
splotchy surface contamination and discoloration.
END OF SECTION 092900
THOMAS JEFFERSONPUMPING STATION
2250 W. EASTWOOD AVE.
DEPARTMENT OFWATER MANAGEMENT
CITY OF CHICAGO
IMPROVEMENTS
CHICAGO, IL 60625
THOMAS JEFFERSONPUMPING STATION
2250 W. EASTWOOD AVE.
DEPARTMENT OFWATER MANAGEMENT
CITY OF CHICAGO
IMPROVEMENTS
CHICAGO, IL 60625
PARTIAL NORTHELEVATION
THOMAS JEFFERSONPUMPING STATION
2250 W. EASTWOOD AVE.
DEPARTMENT OFWATER MANAGEMENT
CITY OF CHICAGO
IMPROVEMENTS
CHICAGO, IL 60625
PARTIAL NORTH,SOUTH, & WEST
ELEVATIONS
THOMAS JEFFERSONPUMPING STATION
2250 W. EASTWOOD AVE.
DEPARTMENT OFWATER MANAGEMENT
CITY OF CHICAGO
IMPROVEMENTS
CHICAGO, IL 60625
WEST ELEVATION
THOMAS JEFFERSONPUMPING STATION
2250 W. EASTWOOD AVE.
DEPARTMENT OFWATER MANAGEMENT
CITY OF CHICAGO
IMPROVEMENTS
CHICAGO, IL 60625
EAST ELEVATION 1
THOMAS JEFFERSONPUMPING STATION
2250 W. EASTWOOD AVE.
DEPARTMENT OFWATER MANAGEMENT
CITY OF CHICAGO
IMPROVEMENTS
CHICAGO, IL 60625
EAST ELEVATION 2
THOMAS JEFFERSONPUMPING STATION
2250 W. EASTWOOD AVE.
DEPARTMENT OFWATER MANAGEMENT
CITY OF CHICAGO
IMPROVEMENTS
CHICAGO, IL 60625
CORNICE REPAIRS
THOMAS JEFFERSONPUMPING STATION
2250 W. EASTWOOD AVE.
DEPARTMENT OFWATER MANAGEMENT
CITY OF CHICAGO
IMPROVEMENTS
CHICAGO, IL 60625
UTILITY DETAILS