Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
AC Magnetic Field Survey Report
of
Literature Building - 3000 University of California San Diego
for
University of California San Diego La Jolla, California
Report Date: February 15, 2010 FMS Ref: 2010-1082
FIELD MANAGEMENT SERVICES CORP.
123 North Laurel • Los Angeles, California 90048 Telephone (323) 937-1562 • Fax (323) 934-2101
NOTICE
All materials contained in this report are protected by copyright and may not be used by others. All content herein, including but not limited to text, graphics, and other intellectual property, cannot be reproduced except by permission of Field Management Services Corp. and provided that copyright notice appear in all copies and that both the copyright notice and permission notice appear in supporting documentation. Documentation contained in this report may not be reproduced, distributed, published, entered into a database, displayed, modified, used to create derivative works, transmitted, or exploited for distribution to others without the expressed written consent of Field Management Services Corp. Field Management Services Corp. has expressly prepared this report for the party noted as “Client”. Field Management Services Corp. shall be indemnified and held harmless from any losses, damages and costs with respect to the unauthorized use of any information contained in this report. Field Management Services Corp. is only responsible for the content of this report and reference to any other service or information source does not imply an endorsement by Field Management Services Corp.
Table of Contents
________________________________________
BACKGROUND:..........................................................................................................2
ELF OR AC MAGNETIC FIELD CHARACTERISTICS: ...............................................2
UNITS OF MEASURE: ................................................................................................4
SURVEY MEASUREMENT EQUIPMENT:..................................................................4
MEASUREMENT PROCEDURES: .............................................................................5
TEMPORAL VARIATIONS: .........................................................................................6
MEASUREMENT OBSERVATIONS: ..........................................................................7
Attachments
I. Measurement Floor Plans
_________________________________________________________________ © 2010 Field Management Services Corp. - Los Angeles • New York
FIELD MANAGEMENT SERVICES CORP 123 North Laurel • Los Angeles, California 90048 Telephone (323) 937-1562 • Fax (323) 934-2101 DATE: February 15, 2010 FMS REF: 2010-1082 CLIENT: University of California San Diego 9500 Gilman Drive
La Jolla, California 92093 ATTN: Grant Silva Health Physicist PROPERTY: Literature Building - 3000
University of California San Diego La Jolla, California
PROJECT: AC Magnetic Field Survey SCOPE: The scope of this project involved measurement of the magnitude and vector direction of power frequency magnetic fields. Submitted by: FIELD MANAGEMENT SERVICES
UCSD Literature Building - EMF Survey Pg. 2 February 15, 2010
Field Management Services
BACKGROUND: This report documents results of an AC 60 Hz magnetic field survey authorized by the University of California San Diego (UCSD) and conducted by Field Management Services (FMS) of the “Literature Building – 3000” located on the UCSD Campus in La Jolla, California. This survey which involved spot measurements of AC magnetic fields at random locations on all four floors of the building was authorized pursuant to terms of UCSD Purchase Order 10304480 dated January 7, 2010. On January 13 and February 10, 2010, an FMS technical representative visited the UCSD site and conducted detailed measurements of AC magnetic fields present in the areas of interest. To inform the reader, the following general information is provided regarding AC magnetic fields. ELF OR AC MAGNETIC FIELD CHARACTERISTICS: ELF or AC magnetic fields are naturally emitted by current-carrying electrical conductors and devices. The AC magnetic field strength emitted by electrical circuits is directly proportional to the magnitude of electrical current. However, multiple conductor cables carrying balanced currents have a low net emission, a consequence of the natural cancellation of magnetic fields created by currents traveling in opposite directions (or with different phase angles) in adjacent conductors. Rigid metallic conduit generally provides good magnetic field reduction, provided that the feed and return currents are equal, in single-phase circuits, and if all of the currents (both feed and return) are present, in multi-phase circuits. If electrical current from a circuit returns via an alternate path, then magnetic field levels emitted from such a circuit can increase significantly. This condition usually occurs if neutral circuits are “cross connected” or illicit connections are made between a neutral and ground in a building’s electrical distribution system. This is often referred to as “stray”, “ground” or “net-current” conditions.
UCSD Literature Building - EMF Survey Pg. 3 February 15, 2010
Field Management Services
AC magnetic fields decrease naturally in intensity as function of distance (d) from the source. The rate of decrease however, can vary dramatically depending on the source. For example, magnetic fields from motors, transformers, etc. decrease very quickly (1/d3) while circuits in a typical multi-conductor circuit decay slower (1/d2). Magnetic fields from “stray” current on water pipes, building steel, etc. tend to decay much slower (1/d). Simply increasing the distance from the source(s) of an area with elevated magnetic field strengths can often reduce magnetic fields to an acceptable level. Unlike electric fields that are relatively easily shielded by common materials used in commercial construction, magnetic fields are capable of penetrating all but a very few, specially manufactured and installed materials. AC magnetic fields will pass undiminished through earth, concrete and most metals, including lead. The actual AC magnetic field strengths encountered within a given commercial building typically range from under 0.2 mG in open areas to several hundred near electrical equipment.
As previously mentioned AC magnetic fields at relatively low levels are capable of producing interference patterns on computer monitors and have been shown to otherwise interfere with electronic equipment. Available technical literature on the subject indicates that computer monitor interference patterns will occur at background AC magnetic field strengths of approximately 5-10 mG and in certain circumstances in environments as low as 3 mG. State of the art “flat screen” LCD computer monitors and processors utilized in today’s applications are generally immune to interference threats from AC magnetic fields. The possible effects of AC magnetic fields on human health have been extensively studied. FMS, by virtue of this report, makes no attempt to attribute value to either side of the question regarding risk to human health nor, for the purposes of health or safety, does the company assign value to any particular magnetic field level. The US Department of Energy RAPID Program WEB site (www.niehs.nih.gov/emfrapid) and the World Health Organization (www.who.int/peh-emf) are excellent sources for comprehensive information on the EMF health issue.
UCSD Literature Building - EMF Survey Pg. 4 February 15, 2010
Field Management Services
UNITS OF MEASURE: Magnetic flux densities (B) are reported using units of gauss (G). However, it is usually more convenient to report magnetic field levels using milligauss (mG) which is equal to one-thousandth of a gauss (i.e., 1 mG = 0.001 G). Some technical reports also use the unit Tesla (T) or microtesla (.µT); (1 .µT = 0.000001 T) for magnetic flux densities. The conversion between these two units is 1 mG = 0.1µT and 1 µT = 10 mG. SURVEY MEASUREMENT EQUIPMENT: To record AC magnetic field values, the following equipment was utilized: Instrument Manufacturer Model Serial No.
Gauss Meter Dexsil Fieldstar 1000
Magnum 310
31400324
9870535
AC magnetic field measurements were taken using a Dexsil Fieldstar 1000 Gauss meter and a Dexsil Magnum 310 Gauss meter. The meters take readings in three orthogonal planes and calculate the resultant field (square root of the sum of the squares) for the measurement point in space. The Field Star 1000 and Magnum 310 are computer-controlled, three-axis, AC magnetic field exposure meters. Each of the three-axis sensors measures the magnetic field and the on-board computer calculates a resultant field value. The resultant is comparable to a maximum field value and is calculated as the square root of the sum of the squares for all three orthogonal axes Br = √Bx² + By² + Bz². All magnetic field measurements in this report are the RMS (root mean square) values. The Dexsil Magnum 310 and Fieldstar 1000 meters were used to take spot measurements at selected locations on all four floors of the Literature Building.
UCSD Literature Building - EMF Survey Pg. 5 February 15, 2010
Field Management Services
The Field Star 1000 meter also contains an internal sampling mode wherein measurement values can be stored at intervals of 1 second or any number of minutes between 1–15. For this study, the meter was set to record timed data at the rate of 1 sample per second in a First Floor Conference Room study site. At the conclusion of the measurement session, a file name was created, which describes the conditions of the test location, and the data uploaded to a laptop computer that is equipped with interface software. MEASUREMENT PROCEDURES: For this survey, measurement procedures consistent with test protocols and techniques described in ANSI/IEEE Standard 644-1994 & C95.6-2002, IEEE Recommended Practices for Measurement of Electric and Magnetic Fields from AC Power Lines were utilized.
• As shown on attached figures, magnetic field spot measurements were first taken throughout each floor of the Literature Building including hallways and areas adjacent to the Literature Building’s electrical & elevator equipment rooms at a constant height of one meter above floor level. At the request of UCSD representatives, spot magnetic field measurements were also taken on a random basis, in occupied offices on each floor
• Detailed spot measurements were taken in areas immediately adjacent to
the First Floor electrical and elevator equipment rooms and in areas adjacent to the electrical rooms on Floors 2, 3 & 4. Attached enlarged floor plans of these areas provide a more detailed view of magnetic field conditions adjacent to the electrical facilities.
• Note that two sets of AC magnetic field spot measurements were taken in
areas immediately adjacent to each floor’s electrical room; one set with the two hydraulic elevators not in use and a second set of measurements with the elevators in operation.
UCSD Literature Building - EMF Survey Pg. 6 February 15, 2010
Field Management Services
• A supplemental set of detailed AC magnetic field measurements were
taken in a First Floor Conference Room No. 155 utilizing an “x” & “y” grid of equal four foot spacing. Spot measurement values were recorded at each grid intersection point at one meter from the floor surface.
• To determine to what extent if any, AC magnetic field conditions in the
First Floor Conference Room No. 155 may momentarily increase when the nearby elevators are operating, timed magnetic field measurements were taken at a study location as shown on an attached diagram. Timed measurements utilizing a 1 second sample rate were taken for a twenty minute period without the elevators operating and then for an additional ten minute period with each of the two elevators operating in varying lifting and descending sequences to emulate a “busy” elevator operation conditions.
TEMPORAL VARIATIONS: AC magnetic field spot readings taken during magnetic field surveys are accurate only for the specific point in time that they were taken. Magnetic field strengths emanating from electrical equipment such as is adjacent to the measured areas of the Literature Building, will vary with the electric (current) load. It was noted during the January 13 and February 10, 2010 survey visits, that the Literature Building appeared to be at a reasonable level of occupancy and typical of normal day-to-day operations. It is the observation of FMS based on prior experience and observation that it is possible that magnetic field conditions at other times of the year in the Literature Building may be somewhat higher or lower and will vary in relation with the amount activity in the building and ambient external conditions.
UCSD Literature Building - EMF Survey Pg. 7 February 15, 2010
Field Management Services
MEASUREMENT OBSERVATIONS: The following observations are offered after a review by FMS of the data from the January 13 and February 10, 2010 AC magnetic field survey visits to the UCSD Literature Building in areas of interest:
• AC magnetic field levels throughout all occupied areas of the Literature Building, generally were well below 1 mG with many areas near “0” mG.
• As can readily be seen from the attached measurement floor plans for
each level of the Literature Building, the only areas with modestly elevated AC magnetic field levels present were areas adjacent to the central core of the building on each level, which is the location of elevators and electrical rooms. The measurement data demonstrates that magnetic fields from the central core electrical equipment on each floor generally decay at the anticipated 1/d2 rate associated with typical electrical circuits. This suggests that net-current circuit conditions, if present, are negligible.
• The measurement data confirms that relatively short duration increases in
electrical loading in the MS-3 main distribution panel caused by cycling of the elevator hydraulic pumps, causes a like short duration but very minimal increase in the AC magnetic field environment in areas immediately adjacent to the Ground Floor electrical room. Similarly on Floors 2,3 & 4, increases in AC magnetic field levels in areas immediately adjacent to the elevator core and electrical rooms with the elevators operating, were negligible.
• Detailed “grid” measurements taken in Conference Room No. 155 were
generally < 0.1 mG with the exception of a small area in the northwest corner which is adjacent to a small telecom equipment room. An examination of the telecom room revealed the presence of a small electrical breaker panel which explains the source of very modestly elevated AC magnetic field levels in the corner of the conference room.
UCSD Literature Building - EMF Survey Pg. 8 February 15, 2010
Field Management Services
• Data from the 30 minute time study of AC magnetic field levels in a
selected location of Conference Room No. 155 are presented in the attached plot of field values vs time. While it is interesting to note that field levels during the study period, momentarily (several seconds) increased periodically every 5 minutes or so, likely due to cycling of some device such as a refrigerator, etc, it appears as anticipated, that operation of the nearby elevators had no noticeable effect on field levels when compared to the period of time when the elevators were not in operation.
• The detailed grid spot measurements recorded in Conference Room No.
155 failed to confirm the presence of a buried electrical feed circuit which was suspected to transverse an area of the Conference Room. Further investigation by University’s facility maintenance confirmed that the feed circuit did not run beneath the Conference Room, but rather, beneath the main building entrance.
• In sum, the measurement data indicates that AC magnetic field levels in
very limited areas of the Literature Building ground floor immediately adjacent to the ground floor electrical room and in the immediate region of a buried, under slab feed conduit in the building’s entrance hallway, are modestly higher than the background magnetic field; a consequence of close adjacency to electrical circuits. AC magnetic field levels measured outside these areas were generally consistent with ambient AC magnetic field levels typically present in office buildings.
(J)15739
(J)15622
(C)183148
(C)182155
(C)181158
(TM)136191
(TW)135234
1101427
(C)1081355
PATIO
149151
148151
147152
146153
145151
144149
143149
142151
141151
140151
139151
138397
137396
134149
133153
132153
131155
130155
129153
128150
127147
125315
124152
(M)121114
150450
153165
155800
111100
11289
113145
118155
117159
116156
115156
114198
(G)19012243
(M)12019
(M)12238
UP
UP
UPDN
(C)10541
(C)10645
(C)109204
ELEVATOR ELEVATOR
ELEVATORROOM
(CU)1601907
12396
University of California, San DiegoLiterature Building - 3000
AC (60 Hz) Magnetic Field Survey January 13, 2010 - 2:15 PM
Field Management Services Corp.New York - Los Angeles
AC (60 Hz) Magnetic Field LevelsSpot Measurements @ +1 Meter from Floor, Resultant Value in mG
FIRST FLOOR
0.1
0.1
0.1
0.1
0.1
0.3
0.7
0.8
0.6 1 3.9 0.7 0.4 0.1 00
0
00
0
0
0
0
00
0
0.7
0.3
0.2
0.4
0.7
0
0
0 0
0
Confirmed path of 480-277 V Buired feed from MS-2
Elevator PumpEL-3
Elevator PumpEL-4
MS
-380
0 A
mp
Pan
el
University of California, San DiegoLiterature Building - 3000
AC (60 Hz) Magnetic Field Survey January 13, 2010 - 3:55 PM
Field Management Services Corp.New York - Los Angeles
AC (60 Hz) Magnetic Field LevelsSpot Measurements @ +1 Meter from Floor, Resultant Value in mG
Values in Blue - Elevators Being Exercised
FIRST FLOOR(Electrical & Elevator Room)
0.3
0.90.70.40.5
10.5
0.5
0.2 0.2
0.3
1.7
1.3
1
0.70.3
0.3
0.3
0.3
0.5
1.10.70.6
0.6
1.20.5
0.4
2
1.8
1.1
0.80.6
0.7
1.1
0.7
(J)15739
(J)15622
(C)183148
(C)182155
(C)181158
(TM)136191
(TW)135234
1101427
(C)1081355
PATIO
149151
148151
147152
146153
145151
144149
143149
142151
141151
140151
139151
138397
137396
134149
133153
132153
131155
130155
129153
128150
127147
125315
124152
(M)121114
150450
153165
155800
111100
11289
113145
118155
117159
116156
115156
114198
(G)19012243
(M)12019
(M)12238
UP
UP
UPDN
(C)10541
(C)10645
(C)109204
ELEVATOR ELEVATOR
ELEVATORROOM
(CU)1601907
12396
University of California, San DiegoLiterature Building - 3000
AC (60 Hz) Magnetic Field Survey January 10, 2010 - 3:15 PM
Field Management Services Corp.New York - Los Angeles
AC (60 Hz) Magnetic Field LevelsSpot Measurements @ +1 Meter from Floor, Resultant Value in mG
FIRST FLOOR(Conference & Restroom)
4.5 0.7 0.3 0.2 0.1 0.2 0.3 0.3
0.8 0.7 0.8 0.7 0.5 0.9 2.4 5.8 1.5 0.5 0.2
0.4 0.1 0.0 0.0 0.0 0.0 0.1 0.2
0.4 0.1 0.1 0.0 0.0 0.0 0.0 0.0
0.3 0.3 0.3 0.2 0.0 0.0 0.1 0.0
0.5 0.3 0.1 0.1 0.0 0.1 0.1 0.1
2.0 0.5 0.3 0.3 0.1 0.1 0.1 0.1
0.1 0.1 0.0 0.0 0.0 0.1 0.0 0.1
0.2
0.2
0.4
0.4
0.4
0.3
0.9
Refrigerator
Breaker Panel in Closet
Confirmed path of 480-277 V Buired feed from MS-2
Location of Time Study
0
0.5
1
1.5
2
2.5
3
1 301 601 901 1201 1501 1801
AC (60 Hz) Magnetic Field Survey - Timed Measurements February 10, 2010 - 3:40 PM
Field Management Services Corp.New York - Los Angeles
AC (60 Hz) Magnetic Field - One Second Sample RateAt +1 Meter from Floor, Resultant Value in mG
University of California, San DiegoLiterature Building - 3000
FIRST FLOOR(Conference Room)
MG
3:40 pm 4:10 pm
Elevators RunningElevators Not Running
Seconds
Conference Room Time Study Point(See “First Floor Conference Room Diagram for Study Location)
University of California, San DiegoLiterature Building - 3000
AC (60 Hz) Magnetic Field Survey January 13, 2010 - 4:05 PM
Field Management Services Corp.New York - Los Angeles
AC (60 Hz) Magnetic Field LevelsSpot Measurements @ +1 Meter from Floor, Resultant Value in mG
SECOND FLOOR
(C)283P144
(C)282P158
(C)281P156
(M)221P50
255AP147
210P854
(TM)236P158
(TW)235P234
(J)256P21
(J)257P22
(C)209P205
(C)208P1368
253P151
252P151
251P151
250P151
249P151
248P151
247P151
246P316
244P149
242P292
240P308
239P151
254P86
255P420
238P171
237P322
234P149
233P153
232P153
231P155
230P157
229P153
228P151
227P152
226P155
225P154
224P152
223P253
217P322
216P154
215P154
211P108
212P113
213P115
214P200
(G)290P11707
(M)258P14
(M)259P24
(M)220P19
UP
UP
UP
210AP300
210BP68
210CP90 210DP84
(C)205P41 (C)206P45
DN
DN
DN
0.1
0.1
0.4
0.6
0.20.20.3
0
0
0
0
0
0
0
0
0
0
0
00.7
0
000 0
0
0
0
0
University of California, San DiegoLiterature Building - 3000
AC (60 Hz) Magnetic Field Survey January 13, 2010 -4:15 PM
Field Management Services Corp.New York - Los Angeles
AC (60 Hz) Magnetic Field LevelsSpot Measurements @ +1 Meter from Floor, Resultant Value in mG
Values in Blue - Elevators Being Exercised
SECOND FLOOR(Electrical & Elevator Room)
0.5
0.5
0.7
0.6
0.5
0.8
0.9
0.2 0.3
0.8
1.4
0.1
0.10
0.6
0.7
0.40.80.6
0.6
0.9
0.5
1.6
0.2
0.10
0.7
0.8
0.2
University of California, San DiegoLiterature Building - 3000
AC (60 Hz) Magnetic Field Survey January 13, 2010 - 2:21PM
Field Management Services Corp.New York - Los Angeles
AC (60 Hz) Magnetic Field LevelsSpot Measurements @ +1 Meter from Floor, Resultant Value in mG
THIRD FLOOR
(C)383P144
(C)382P158
(C)381P156
(M)321P51
535
(TM)336P158
(TW)335P234
(J)356P21
(J)357P22
(C)308P205
(C)307P1368
355P420
354P237
353P151
352P151
351P151
350P151
349P151
348P151
347P151
346P153
345P151
344P149
343P144
342P151
341P152
340P151
339P151
338P169
337P155
336P162
328P151
329P153
334P149
333P153
332P153
331P155
330P157
327P152
326P155
325P154
324P152
323P251
311P297
312P242
313P198
318P74
317P155
316P154315P
154314P200
(G)390P11707
(M)358P24
(M)359P14
(M)320P19(C)306P45
UP
UP
UP
(C)305P41
DN
DN
DN
829384
155
125
0.1
0.1
0.4
0.8
0.1
0.2
0.100
0
0 0
0
0
0
0
0
0
0
0.2
0.1
0
0
0
0
0
0 0
0
University of California, San DiegoLiterature Building - 3000
AC (60 Hz) Magnetic Field Survey January 13, 2010 -2:40 PM
Field Management Services Corp.New York - Los Angeles
AC (60 Hz) Magnetic Field LevelsSpot Measurements @ +1 Meter from Floor, Resultant Value in mG
Values in Blue - Elevators Being Exercised
THIRD FLOOR(Electrical & Elevator Room)
0.4
0.3
1
1.2
0.5
1
0.6
0.2 0.2
1.3
0.9
0.1
0
0.6
0.6
0.41.30.4
0.9
0.9
0.4
0.9
0.1
0
0.7
0.9
0.1
00
0.6
University of California, San DiegoLiterature Building - 3000
AC (60 Hz) Magnetic Field Survey January 13, 2010 - 3:10 PM
Field Management Services Corp.New York - Los Angeles
AC (60 Hz) Magnetic Field LevelsSpot Measurements @ +1 Meter from Floor, Resultant Value in mG
FOURTH FLOOR
(C)483P144
(C)482P158
(C)481P156
410P750
(TM)458P158
(TW)435P234
(J)456P21
(J)457P22
(C)409P205
(C)408P1368
421P169
455P420
454P237
453P151
452P151
451P151
450P151
449P151
448P151
447P151
446P153
445P151
444P149
443P144
442P151
441P152
440P151
439P151
438P169
437P322
428P151
429P153
434P149
433P153
432P153
431P155
430P157
427P152
426P155
425P154
424P152
423P154
411P262
413P84
416P191
415P204
414P117
(G)490P11707
(M)458P24
(M)459P14
(M)420P19(C)406P45
(M)422P28
UP
UP
UP
(C)405P41CONFERENCE ROOM
ELEVATOR ELEVATOR
DN
DN
412P239
417P155
418P154
410AP62410BP103
410CP65410DP65
DN
419P54
0.1
0.1
0.2
0
0
00
0 0
0
0
0
0
0
0
0
0
0 0
0
0
0 0
0.1
0 0
0
University of California, San DiegoLiterature Building - 3000
AC (60 Hz) Magnetic Field Survey January 13, 2010 -3:00 PM
Field Management Services Corp.New York - Los Angeles
AC (60 Hz) Magnetic Field LevelsSpot Measurements @ +1 Meter from Floor, Resultant Value in mG
Values in Blue - Elevators Being Exercised
FOURTH FLOOR(Electrical & Elevator Room)
0.4
0.1
0.2
0.4
0.4
0
0
0.3
0.1
0.4
0.4
0.2
0.8
0
0
0.2
0.1
00
0.4
0.4
0.3
0.3
0.3
0.3 0.3
0.1
0.2
0.2
0.1
0