Upload
david-jenkins
View
216
Download
3
Embed Size (px)
Citation preview
www.elsevier.com/locate/enbuild
Energy and Buildings 37 (2005) 485–492
A design tool for predicting the performances of light pipes
David Jenkins*, Tariq Muneer, Jorge Kubie
School of Engineering, Napier University, Edinburgh EH105DT, UK
Received 18 May 2004; received in revised form 11 August 2004; accepted 14 September 2004
Abstract
Light pipes are simple means of directing daylight (diffuse and direct light) into interior spaces. Previous work by the authors described the
initial work on a luminous flux and illuminance predictive model for straight light pipes, using a basic equation for illuminance distribution as
a function of horizontal distance. Further work has now produced a model that uses the cosine law of illuminance to describe the distribution of
light from the light pipe diffuser as well as takes into account pipe elbow pieces or bends. The resulting illuminance model can be described as
a quartic cosine model. By producing a ‘‘luxplot’’ prediction for any given light pipe application, it is possible to maximise the potential of
these daylight providers and design their configuration to suit any given need. As part of this study, wide-ranging illuminance and luminous
flux data were collected both for the formulation of this model (as the formula is semi-empirical) and its validation.
# 2004 Elsevier B.V. All rights reserved.
Keywords: Light pipes; Daylight; Modelling; Lighting
1. Introduction
Much literature has been published that highlights the
problems associated with a lack of daylight illumination in
places such as office spaces and schools [1]. Additionally, a
large amount of energy is consumed within the UK that is a
result of electric lighting. For example, recent statistics
published by the Department for Trade and Industry [2],
show that approximately 53.5 million tonnes of oil
equivalent is associated with electrical lighting/appliances
in the domestic and industrial sectors.
One method for optimising the available daylight would
be to use light pipes. These are simple light guides, varying
in size depending on the application, that reflect the sunlight
and diffuse skylight into a given interior space. By using
devices such as light pipes, the daytime energy consumption
can be significantly reduced in buildings throughout the
country. This obviously requires a reasonably accurate
design tool so that it is possible to put forward a specific
* Corresponding author.
E-mail addresses: [email protected],
[email protected] (D. Jenkins).
0378-7788/$ – see front matter # 2004 Elsevier B.V. All rights reserved.
doi:10.1016/j.enbuild.2004.09.014
configuration for any situation that might require a minimum
illuminance at a specific level.
The basic passive light pipe design considered for this
study is a collector on the roof of a building attached to
reflective tubing (forming the pipe itself) that reached a
diffuser/emitter at ceiling level. There are however different
types of light pipes that vary in pipe transmittance, collector
transmittance and diffuser transmittance. The pipe con-
sidered for this study has a reflectivity of 95% and is made
from polished aluminium sheets. The light is therefore
transported via multiple specular reflection through the pipe
itself. The collector is a hemispherical polycarbonate top
dome and has, in previous literature [3], been given a
transmission of 88%. The diffuser is also made from clear
polycarbonate material and has a stippled finish that, while
letting a significant amount of light through, diffuses the
light throughout the room. The non-uniform nature of this
diffuser can, for short pipes under clear sky conditions,
produce asymmetric light distributions that are difficult (or
impossible) to predict. The detail of this problem is
discussed in previous modelling work by the authors [4]
but the model is justified by using an overcast sky
approximation. Clear sky predictions can still be calculated
but the actual distribution of light may be inaccurate for
D. Jenkins et al. / Energy and Buildings 37 (2005) 485–492486
List of symbols
A pipe aspect ratio
Eex external illuminance (lux)
Ein internal illuminance (lux)
Etheory internal illuminance determined from theory
alone (lux)
lu luminous intensity distribution (candela)
r pipe radius (m)
Tpipe transmission of pipe material per unit aspect
ratio
V vertical distance of pipe diffuser to point of
measurement/prediction (m)
Greek letters
b diffuser area (m2)
x elbow reduction factor
f luminous flux of pipe (=fSP for straight pipe)
(lumen)
fSP luminous flux of straight pipe (lumen)
’ angle of pipe elbow (8)u angle between line from diffuser to point of
measurement and line normal to diffuser centre
(8)t total pipe transmission
tdiffuser transmission of diffuser
tdome transmission of top dome
v solid angle of light distribution from diffuser
(steradian)
certain scenarios; however, the predictions can still be a
good indicator of the general light level in a given room.
The actual transmission of the diffuser alone has not been
measured but, from mathematical procedures, the combined
transmission of the dome and diffuser is approximated in
Section 2.1.
The modelling approach that is taken is semi-empirical so
measurements were taken as part of this study. This appears
to be the most effective method, mainly because light pipe
transmissions (particularly for aluminium pipes that may
have imperfections along their lengths) can be difficult to
ascertain from pure theory. The aim of the model is to be
able to predict both the luminous flux and illuminance of any
size light pipe (with or without elbow sections), for any
situation. To produce this kind of versatility, measurements
are taken over the range of pipe diameters 0.3 m–0.53 m and
pipe lengths of 0.6 m–5.4 m.
2. Modelling procedure
It has already been stated that parts of this modelling
procedure has been discussed elsewhere [4]. However, rather
than just mention the new areas that have been developed,
the whole procedure will be summarised to clarify the step-
by-step approach taken (although much of this is subtly
different to the previous article referenced).
2.1. Luminous flux predictions
The theory used for producing the luminous flux model is
as follows. Consider a light pipe of cross-sectional radius r,
for an external illuminance Eex, and flux transmission t. The
cross-sectional area of the pipe will therefore be pr2. The
flux of light at the top of the pipe, f0, will be a product of the
external illuminance and light pipe area, or:
f0 ¼ Eexpr2 (1)
The total luminous flux output for a straight pipe, fSP, will
therefore be:
fSP ¼ tEexpr2 (2)
This is the basic equation behind the luminous flux
model. Eex and r are measurables for any given situation, so
it is just t that needs to be ascertained. While various papers
have sought to predict the transmission of pipes through
theory alone [5], the problem that often arises is that there
are a large number of variables to account for, some of which
are difficult to quantify. As a result, it was decided to
use data to approximate the transmission of a pipe as a
function of aspect ratio (the ratio of the pipe length to pipe
diameter).
The necessary data was obtained from a test-shed at
Nottingham University. A 0.3 m diameter pipe was
measured with lengths ranging from 0.6 m to 5.4 m and,
using a photometric integrator to measure the pipe luminous
flux at the diffuser and a global illuminance sensor to
measure the external illuminance, a relationship between
aspect ratio and pipe transmission was ascertained.
Specifically it was found that:
t ¼ 0:82e�0:11A (3)
where A is the aspect ratio of the pipe. It can be seen that, for
zero length, the transmission is still not unity; this is due to
the collector and diffuser absorbing a fraction of the light.
The coefficient of 0.82 implies a combined transmission of
collector and diffuser of 0.82. The results therefore imply
that, if the dome were attached directly to the diffuser, 82%
of the light would be transmitted from outside. This value is
somewhat larger than might be expected for the materials
involved, and would ideally require further investigation.
Incidentally, if this value was inaccurate, it would not affect
the illuminance predictions (Eq. (13)) due to the use of an
empirical constant (that would accommodate any inaccuracy
in this respect).
Eq. (3) can now be substituted into Eq. (2) to give:
fSP ¼ 0:82Eex e�0:11Apr2 (4)
and this is the semi-empirical model to predict the luminous
flux from a straight light pipe.
D. Jenkins et al. / Energy and Buildings 37 (2005) 485–492 487
Although this procedure was applied to a specific light
pipe design (as defined in introduction), it can easily be
modified for other pipe designs. Firstly, if the combined
transmission of the collector and diffuser is known (or can be
measured), then this can be substituted into Eq. (4) instead of
the ‘‘0.82’’ value. If another pipe has a different reflectivity,
this can also be accounted for. The exponential term in Eq.
(4) is directly related to the pipe reflectivity. In actual fact,
e�0.11 gives the transmission of the pipe material per unit
aspect ratio so this can easily be altered for any other pipe.
This is especially important as films now exist that, through
total internal reflection, can produce reflectivities of 98%
and above, so any model should ideally be able to
accommodate this. Hence, Eq. (4) can be generalised to:
fSP ¼ ðtdometdiffuserÞTpipeEexpr2 (5)
where tdome and tdiffuser are the transmissions of the dome
and diffuser, respectively, and Tpipe is the transmission of a
piece of pipe of unit aspect ratio.
2.2. Theoretical light distribution from a point source
The ideal way of modelling the horizontal distribution
would be to use a theoretical form that is validated by actual
data. This would remove the need for using pure measure-
ments to construct the distribution of light from the diffuser.
Data can be used to optimise any empirical coefficients
involved or that are introduced for accuracy. The approach
taken is to use modified theory, and then through data apply
an empirical factor to produce the required results.
Fig. 1 shows a point source of light illuminating a
horizontal plane. From the inverse square law of illumi-
nance, the illuminance (E) directly below the a light source
is given by:
E ¼ I0
V2(6)
where I0 is the luminous intensity (in candela) at the point
directly below the point source.
The illuminance received at point P, a direct distance D
from the point source, will be related to the luminous
intensity at angle u(Iu) by:
E ¼ Iucos u
D2(7)
Fig. 1. Point source of light illuminating horizontal plane.
and by simple trigonometry,
D ¼ V
cos u(8)
giving:
Etheory ¼ Iucos3 u
V2(9)
This expression is the ‘‘cos3 law of illuminance’’ [6] and
can be used to describe the horizontal distribution of light
from a point source.
2.3. Deriving relationship for actual light
distribution from light pipe
The source of light in question, i.e. the light pipe diffuser,
is not actually a point source (although it can be approxi-
mated as one for large distances away from the diffuser). If
the source is approximated to a flat disc shape, the area of the
diffuser ‘‘seen’’ by any given point (b0) is a factor of cos u
smaller than the actual surface area (where u is defined in
Fig. 1) or, for diffuser surface area b:
b0 ¼ bcos u (10)
The quantities that were measured as part of this work
were the luminous flux leaving the diffuser (fSP for straight
pipe) and illuminance at some point below the diff-
user,so it is desirable to have Eq. (9) expressed in these
terms.
Luminous flux and intensity can be related by the solid
angle, v, in the equation:
Iu ¼fSPcos u
v(11)
where the cos u term comes from Eq. (10) and accounts for
the difference in horizontal distribution between a point
source and a source of given surface area (for a point source,
emitting equalling in all directions, the intensity distribution
would just be the ratio of the luminous flux over the solid
angle without the cos u factor, as discussed in literature [6]).
Substituting this into Eq. (9) gives:
Etheory ¼ fSPcos4 u
vV2(12)
There are still slight modifications that have to be made to
this. Firstly, the empirical constant, g, must be placed in
front of this equation so that, when comparing data with
predictions, the optimum match can be found. It follows
from this that Eq. (12) will not be equal to the actual
predicted illuminance. This is probably due to the slightly
non-Lambertian distribution of light from the pipe diffuser. g
will just be a number and will include the solid angle term v
(=2p) for simplicity. If a suitable empirical term is found that
is accurate for a wide range of data, then this task is
relatively straightforward. If the term is largely different for
a wide range of datasets, then some variable (i.e. a factor that
varies between each set of measurements taken) has not been
accounted for. In fact, over the measurements that were
D. Jenkins et al. / Energy and Buildings 37 (2005) 485–492488
taken for this study, the empirical term is found to be
approximately constant at 0.494 (in that this value achieves
the best comparison with all data). This includes all constant
terms identified. The final equation for the internal
illuminance at any point is then:
Ei ¼ 0:494fSPcos4 u
V2(13)
This is proposed as being suitable for all straight light
pipes. It should be noted that this does not include
contribution from internally reflected components, although
the data collected would have had a small reflected
component anyway (as the illuminance data was collected
from real-life scenarios rather than test environments). It is
reasoned that, although the internally reflected component
from light pipes should be an area of investigation, the fact
that the light from light pipes is directly vertically
downwards (as opposed to windows which tend to project
light onto walls) means that this component will not be as
significant as with windows. Also, the floor of a given room
is typically not very reflective and so the internally reflected
component would be reduced as a result.
The next step of the modelling procedure is to apply a
factor for elbow pieces.
2.4. Ascertaining effects of pipe elbows
Measurements of the losses due to pipe elbows were
carried out, with the help of Nottingham University, on
bends ranging from 58 to 758. From this data the following
expression was derived:
x ¼ e�0:0052’ (14)where ’ is the angle of the pipe elbow in degrees and x is the
ratio of a pipe with an elbow to that of a straight pipe of equal
length.
This expression is purely derived from measurements but
its ‘‘form’’ was deduced partly from theory. Fig. 2 refers to
Fig. 2. Measurements (and ‘‘theory’’) with trendline taken at Nottingham Uni
the theoretical trend line. This is deduced from the following
calculations.
The simplest way of approaching this is to consider a
single elbow of known angle (for example, 158). For a given
percentage loss, say a, it is proposed that the losses of other
elbows can be estimated by working in multiples of the
original angle (this is shown to be a suitable approximation
in Fig. 1).
Working on this principle, the following process shows
the theoretical loss for a number of bends, n.
For straight pipe, output = fSP
For one elbow with percentage loss ‘‘a’’, output = fSP � afSP
For two identical elbows, output = fSP � afSP � a(fSP -
� afSP)
Continuing this produces the general formula:
x ¼ ð1 � aÞn (15)
where x is previously defined.
Mathematically, this is equivalent to the formula:
x ¼ enlnð1�aÞ (16)
where n is the ‘‘number of bends’’. So, for example, if the
loss associated with a 158 bend is 8.5%, then a = 0.085 and n
will be a multiple of 158 (so, to produce an estimate for 308,n will be 2).
The above equations are not meant as cast-iron solutions
to the elbow loss problem. They do however show that an
exponential form between elbow angle and percentage loss
would be expected and so they are useful in finding the
correct form of equation to use to fit a trend line to the data
points (as has been done in Fig. 2). They can be directly
compared to Eq. (14) to calculate the properties a and n.
Using the measurements for the 158 elbow produces the
trend line shown in Fig. 2. This is actually quite close to the
trend line derived purely from measurements (as would be
expected), with the small difference probably being due to
versity (January 13–17, 2003) for elbow pieces of 0.3 m diameter pipe.
D. Jenkins et al. / Energy and Buildings 37 (2005) 485–492 489
Fig. 3. Examples of different configuration of same pipe components.
the fact that, for example, a 308 elbow will not have precisely
the same effect as two 158 elbows (due the nature of the
elbow pieces).
3. Proposed light pipe predictive model
The described mathematical treatment and the use of
data have enabled an equation for any configuration of light
pipe (straight or elbowed) to be derived. This will now
be expressed explicitly and validated against collected
data.
3.1. Final expression for light pipe predictions
To incorporate Eq. (14) into the expressions for the
straight pipe models is relatively straightforward. For a pipe
with a single elbow piece, Eq. (14) is multiplied by the
predicted output for a straight pipe (Eq. (13)). For multiple
elbow pieces, this operation is repeated for the second, third,
etc. elbows. The assumption is made that the position of each
Fig. 4. Luminous flux measurements (from April 5 to 14, 2002, Nottingh
elbow is not important; only the angle of the bend in each
case. For example, it is assumed that, both pipes in Fig. 3
would produce the same outputs.
The internal luminous flux from a pipe with n number of
elbows, fi, is thus given by:
fi ¼Yn
1
xnfSP (17)
or more explicitly:
fi ¼ 0:822Yn
1
xnEex e�0111Apr2 (18)
whereQ
is the product sign (read as ‘‘the product of . . .’’).Therefore, for a pipe with no elbow pieces, fi will just equal
fSP.
Finally, we have an expression that can be proposed for
the illuminance at any point below a light pipe, for any size
light pipe, and with any number of elbows. Using Eq. (13)
for a straight pipe gives Eq. (19) for n pipe elbows:
Ei ¼ 0:494Yn
1
xn
fSPcos4 u
V2(19)
where x is given in Eq. (14). It should be stressed that the
straight pipe luminous flux has been used here and the
effects of pipe elbows applied after this. An alternative
procedure would have been to apply the pipe elbow effects
to the luminous flux prediction (of Eq. (4)) and then use this
for finding illuminances. Eq. (19) is the final equation that all
internal illuminance predictions are based on in this study.
Expanding this further so that it is in terms of inputs only
(where it is assumed that luminous flux will not be known by
the user of the equation) gives:
Ei ¼ 0:406Y’n
’1
e�0:0052’ Eex e�0:111Apr2cos4 u
V2(20)
The value of 0.406 is an empirical constant that is a
product of all derived constants from the collected data. Its
am University) and predictions for straight 0.3 m pipe, 1.2 m long.
D. Jenkins et al. / Energy and Buildings 37 (2005) 485–492490
Fig. 5. Illuminance measurements (July 17, 2002, Nottingham University) and predictions for straight 0.45 m diameter pipe, 3 m long. Taken at vertical
distance of 2 m and horizontal distance of 1 m from pipe diffuser.
value is partly dependent on the transmissions of the diffuser
and top dome; as these are always the same for this study, the
value is assumed (and proven within the limits of the data
collected) to be constant.
3.2. Validation with data
Several pipe configurations were measured in various
sites ranging from 0.3 m to 0.53 m in diameter and 0.6 m to
6 m in length (as well as elbows of varying angles). For
conciseness, a small selection of this data will be shown as a
brief validation of the model.
Fig. 4 shows luminous flux measurements compared to
the model (of Eq. (4)) for data over a period of ten days.
Fig. 5 is a comparison of illuminance data and the straight
Fig. 6. Illuminance measurements (September 14–15, 2002, office in High Wyc
elbows. Taken 1.5 m directly below pipe diffuser.
pipe illuminance model (of Eq. (13)) and finally Fig. 6 uses
Eq. (20) to compare predictions of the elbowed (i.e. final)
model with data. All predictions matched the collected data
(for the dimensions described in Section 1) satisfactorily and
suggested the models to be valid design tools for light pipe
illuminance and luminous flux predictions. The next stage is
to display predictions, particularly illuminance predictions,
in an accessible way.
3.3. Displaying predictions
3.3.1. Luminous flux predictions
Luminous flux predictions can easily be displayed in
tabular form, as they do not describe information regard–
ing the distribution of light. As a result, in the current
ombe) and predictions for 0.53 m diameter pipe, 1.2 m long, with two 308
D. Jenkins et al. / Energy and Buildings 37 (2005) 485–492 491
Fig. 7. Spreadsheet for luminous flux model.
framework, a simple spreadsheet can be used which requires
simple inputs and the output can be displayed on the
same page (see Fig. 7). The final luminous flux outputs of the
light pipes can then be compared to the luminous flux
associated with different electric lighting fixtures of given
efficacies.
3.3.2. Illuminance predictions
A slightly more detailed form for displaying illuminance
predictions is recommended so as to appreciate the total
light that is received by a given room. Several MS-Excel
spreadsheets can be used together to produce a ‘‘luxplot’’
that provides a colour representation of the illuminance
distribution across a two-dimensional horizontal plane. Such
a luxplot can be produced for any size room, with any
Fig. 8. Input page for illuminance model (using smallest version
number of pipes, of any dimension or configuration (and
with any number of elbows). In the current framework, an
input page (Fig. 8) provides all the information needed by
the internal calculations of the model, and defines a grid co-
ordinate system across the area in question (the grid is
usually split into squares of 0.5 m � 0.5 m) This informa-
tion is used to calculate, for each pipe in the room, the
illuminance at every point within the grid. Then the
illuminances at each point form each pipe are simply added
to produce a grid of illuminance values across this area. A
simple VBA macro is then run to convert these values into
colours. The final output (see Fig. 9), which can be produced
in seconds, is then a good representation of the light
distribution predicted in that room for the configuration
defined.
for a maximum of 10 m � 10 m room and for nine pipes).
D. Jenkins et al. / Energy and Buildings 37 (2005) 485–492492
Fig. 9. Final luxplot output (for values inputted in Fig. 8).
4. Conclusions
Through the use measurements and refined theory, a
model has been formulated that predicts the luminous flux
and illuminance (below diffuser) of any number and any size
light pipes (with any number of elbows) in a room of any
dimensions. The predictions for single pipes have been
tested against data and (as seen in Figs. 4–6), the results are
satisfactory.
The illuminance model should be used with caution when
considering clear sky predictions, as the actual illuminance
distribution predicted (particularly for short pipes) may not
be accurate. However, in such a case it is probable that the
magnitude of the values given would still be indicative of the
performance of that pipe (or pipes) involved in the
prediction. Nevertheless, the performance of the model
will be more satisfactory when compared to data from
overcast skies, as is the case for many daylight-associated
models.
The main purpose of the model is to accurately calculate
the light pipe(s) needed to maintain a specific light level in a
room. Therefore, for any given room, an estimate can be
formulated for the time period throughout the year (based on
external illuminance approximations) that electrical lighting
can be switched off (or reduced). From this, it will then be
possible to quantify the energy savings (and, using published
statistics relating energy consumption with pollutant
production [7,8], the reduction in pollutant emissions)
associated with the reduction of daytime electrical lighting.
References
[1] Heschong Mahone Group, Daylighting in Schools—An Investigation
into the Relationship Between Daylighting and Human Performance,
August 20, Oaks, CA, 1999.
[2] DTI UK Energy Sector Indicators Report, 2003.
[3] D.J. Carter, The measured and predicted performance of passive solar
light pipe systems, Lighting Research and Technology 34 (1) (2002)
39–52.
[4] D. Jenkins, T. Muneer, Modelling light pipe performances—a natural
daylighting solution, Building and Environment 38 (2003) 965–972.
[5] L. Shao, A.A. Elmualim, I. Yohannes, Mirror light pipes: daylighting
performance in real buildings, Lighting Research and Technology 30
(1) (1998) 37–44.
[6] D.C. Pritchard, Lighting, Addison Wesley Longman Ltd., 1999.
[7] G. Weir, T. Muneer, Life Cycle Analysis of double-glazed windows,
Energy Conversion and Management 39 (1) (1998) 243–356.
[8] E.S. Rubin, C.I. Davidson, Introduction to Engineering and the
Environment, McGraw-Hill, Boston, 2001.