800kV DC Transmission

IEEE General Meeting, Tampa FL, June 2007

Chris HorwillConsultant FACTS

Page 3: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References3 3

Potential market for 800kV DC projects

Page 4: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References4 4

UHVDC Prospects 600kV-800kV

Northern Lights

2014-2020

Madeira2012

WestCoreach 3 terminalSouth W 2012South E 2013

Chicken Neck4 terminal

Phase 1 2009Phase 2 2011

Irkutsk (Russia)-Beijing:

2015

Yunnan-Guangdong: 2009Xiangliaba-Shanghai: 2011Jingping-East China: 2012

Xiluodu-Hunan: 2014Humeng-Shandong: 2015

Nuozhadu-Guangdong: 2015Xiluodu-Hanzhou: 2015Humeng-Tianjing: 2016

Jinsha River I-East China: 2016Humeng-Liaoning: 2018

Jinsha River II-Fujian: 2018Hami-Central China: 2018

Jinsha River II-East China: 2019

WestCor4 terminalNorth 2018

In-service dates

Page 5: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References5 5

NWPG

NCPG

NEPG

CCPG

ECPG

CSG

Xizang

Qinghai

Xinjiang

Gansu

Ningxia

Shaanxi

Shanxi Shandong

Hebei

Inner Mongolia Beijing

Heilongjiang

Jilin

Liaoning

Tianjin

JiangsuHenan

Hubei

HunanJiangxi

Fujian

Anhui

Zheijang

GuangdongGuangxiYunnan

Guizhou

Chongqing& Sichuan

Hainan

Taiwan

Yunnan-Guangdong800kV, 5000MW, 2009

SWPG

800kV HVDC projects planned in China 2009-2019Year is project in service

Shanghai

Hami- Central China800kV, 6400MW, 2018

Humeng-Liaoning800kV, 6400MW, 2018

Jinsha River II-Fujian800kV, 6400MW, 2018

Jinsha River II-East China800kV, 6400MW, 2019

Jinping-East China800kV, 6400MW, 2012

Humeng-Tianjin800kV, 6400MW, 2016

Jinsha River I-East China800kV, 6400MW, 2016

Xiluodu-Hunan800kV, 6400MW, 2014

Nuozhadu-Guangdong800kV, 6000MW, 2015

Xiluodu-Hangzhou800kV, 6400MW, 2015

Humeng-Shandong800kV, 6400MW, 2015

Irkutsk (Rusia)-Beijing800kV, 6400MW, 2015

Xianjiaba-Shanghai800kV, 6400MW, 2011

Page 6: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References6 6

Benefits of HVDC at 800kV

Large HVDC schemes, 5000MW – 6400MW are used to access hydro power resources, hence renewable energy with no CO2 emissions

HVDC is more economic than AC for schemes with transmission distances longer than 700km

800kV DC reduces the overall transmission losses

Right of way is smaller than 2 off 500kV HVDC or 5 off 500kV AC alternatives

Page 7: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References7 7

Transmission options for up to 6400MW

1 off ±800kV tower

2 off ±500kV towers

5 off 500kV AC towers

Page 8: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References8 8

Scheme Configuration

Page 9: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References9 9

Assumed Scheme Rating

6400MW

+/-800kV, 4000A Bipole

Single pole rating 3200MW

Single phase 2 winding converter transformers

Page 10: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References10 10

1 x 12 Pulse Converter Per Pole

One Pole Only Shown

Page 11: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References11 11

1 x 12 Pulse Converter Per Pole

Transformer fundamental frequency rating approximately620MVA

Unlikely this can be transported to generation end

Converter trip removes up to 3200MWThis may be difficult for the grid to manageMay not be acceptable for availability reasons

Valve would need to be designed for much higher capacitive inrush currents at commutationNo bypass switches

AREVA T&D has chosen to concentrate on multiple converter options

2 x 12 pulse series connected converters per pole

Page 12: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References12 12

2 x 12 Pulse Series Connected Converters

One Pole Only Shown

Page 13: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References13 13

Series bridges 400kV + 400kV

Equal sizes of switched blocks

Would allow common transformer design

Would this be economic?

Would this be useful to operator?

Could have different valve winding bushings

Valve design would be common and the voltage within present experience

Maximum bypass switch voltage 400kV

Maximum switched block 1600MW

Staged build step is 400kV

Page 14: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References14 14

2 x 12 Pulse Series Connected Converters

Series connected converters have already been used for 600kVdcTransformer fundamental frequency rating approximately 320MVA

Should be possible to transport to generation end

Converter trip removes up to 1600MWThis should be acceptable

DC component or single pole line fault removes 3200MWThis would be extremely infrequent

Assuming equal bridge sizes:Valve voltage less than present maximum rating

6 pulse bridge = 200kVToday 6 pulse bridge = 250kV

Need bypass switches of 400kV

Page 15: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References15 15

2 x 12 Pulse Parallel Connected Converters

One Pole Only Shown

Page 16: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References16 16

2 x 12 Pulse Parallel Connected Converters

Parallel connected converters have been used on multi-terminal schemes:

SACOI (Italy – Corsica – Sardinia)New England (Canada – USA)

Each converter needs to be 800kV as one blockTransformer fundamental frequency rating approximately 320MVA

Should be possible to transport to generation end

Converter trip removes up to 1600MW800kVdc circuit breakers would be required to trip single converter

Valve would need to be designed for much higher capacitive inrush currents at commutationDo not need bypass switches

Page 17: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References17 17

800kV PoleBasic Assumptions

2 off Series connected, 12 pulse bridges per pole

1 phase, 2 winding converter transformers

1 valve hall per 12 pulse bridge

2 hanging bi-valves per phase

Indoor DC area common to both bridges

Page 18: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References18 18

Single Line DiagramOne Pole

HVDC line

HVDCfilter

LVDCFilter

Valve Hall

M

MY

Electrode/LVDC l ine

M

M

M

M

Y

M

M

Y

DCCT

Voltagedivider

-V1

- V2

-V3

M

M

M

M

MY

∆Y

M

M

Y

-V1

- V2

-V3

M

M

M

SmoothingReactor

M

M

M

M

M

M

NeutralReactor

Voltagedivider

DCCT

ConverterTransformer

ConverterTransformer

DC Filter

DCCT

DCCT

DCCT

DCCT

-S -AC

-S -DC

-IT

Neutral bus disc onnecter

protectionNeutral

BusSwitch

Page 19: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References19 19

Single line DiagramOne 12 – pulse bridge

Page 20: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References20 20

Thyristor Valve

Page 21: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References21 21

Thyristor Valves

Page 22: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References22 22

AREVA Suspended Valve

DC Neutral

DC Midpoint

HVDC

AC (∆)

AC (Y)

Approx 26m, 70T

Single suspended valve: too tall and heavy!

Page 23: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References23 23

Valve HallEarth plane

5m

8.5m

400kV

800kV

26m

Earth plane

400kV

4m

1m

17.5m

Page 24: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References24 24

State-of-the-art Valve - Introduced 2003Key attributes:

Enhanced capacityUp to 500kV, 4000A as single block

FlexibleThyristors up to 150mm diameter

Greater power density giving reduced space

Significantly cheaper than previous valves

Rapid thyristor replacement without disturbing power connections or cooling pipe-work

Due to thyristor clamped assembly system

Direct water/glycol cooled

Suspended structure to ease seismic qualification

Standardized and modularized for flexibility

Page 25: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References25 25

H400 Valve Module comprising 2 valve sectionsBuilding Block

Thyristor Clamped Assemblies

Page 26: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References26 26

Thyristor Clamped Assembly

Loading adaptor for thyristor changing tool

Thyristor

GRP clamping straps

Heatsinkwith coolant connection

Power connection

Page 27: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References27 27

Example of 12 pulse Thyristor Valve

Page 28: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References28 28

Converter Transformer

Page 29: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References29 29

Converter Transformers

Page 30: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References30 30

Converter Transformer for 800kVArrangement

Page 31: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References31 31

Converter Transformer for 800kVTechnical Challenges

DC side bushings

Oil free designs required

Composite insulation rather than porcelain

Solid insulation/Gas insulation?

Mechanical strength due to extreme length.

Page 32: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References32 32

Converter Transformer for 800kVSchematic diagram

400kV AC Bushing

400kV or 800kV DC

H

L

B

10m

4.5m

8m

Page 33: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References33 33

Valve Hall Layout

Page 34: 800kV DC Transmission - uidaho.eduece.uidaho.edu/hvdcfacts/Presentations/CHorwill.pdf · 800kV DC Transmission IEEE General Meeting, Tampa FL, ... Right of way is smaller than 2 off

> Title of presentation - Date - References34 34

Upper Voltage Block Valve Hall

400kV to 800kV