7Conventional Dry-type Transformer

Embed Size (px)

Citation preview

  • 7/27/2019 7Conventional Dry-type Transformer

    1/2

    Rated primary voltage : 100V - 600V

    CAPACITYNO-LOAD

    LOSSES

    LOAD

    LOSSES

    AT 75 C

    TOTAL

    LOSSES

    AT 75 C

    IMPEDANCE

    AT 75 C

    VOLTAGE

    REGULATION

    AT FULL LOAD

    (P.F.=1)

    (kVA) (Watt) (Watt) (Watt) (%) Load

    (%)

    Full Load

    (%) (%) W L H

    1 16 36 52 2.0 99.69 99.68 3.56 20 300 300 300

    3 45 110 155 2.0 99.68 99.66 3.62 20 300 340 400

    5 75 180 255 2.0 99.68 99.66 3.56 25 350 400 450

    10 150 365 515 2.0 99.68 99.66 3.60 25 350 460 500

    15 230 520 750 3.0 99.69 99.67 3.45 30 350 520 570

    20 350 690 1040 3.0 99.70 99.70 3.44 30 380 580 620

    30 450 1060 1510 3.0 99.68 99.67 3.52 30 400 640 700

    40 580 1480 2060 3.0 99.67 99.65 3.68 30 400 700 750

    50 790 1800 2590 3.0 99.69 99.67 3.58 30 400 760 800

    60 900 2100 3000 3.0 99.68 99.67 3.48 40 450 820 900

    80 1240 2610 3850 3.0 99.70 99.69 3.25 40 500 900 950100 1500 3500 5000 3.0 99.68 99.67 3.48 40 550 1000 1050

    120 1950 4100 6050 3.0 99.70 99.69 3.40 40 550 1000 1100

    150 2050 5200 7250 3.0 99.67 99.65 3.45 40 600 1100 1150

    200 2950 6300 9250 3.0 99.69 99.69 3.15 40 650 1150 1200

    250 3350 6850 10200 3.0 99.70 99.70 2.75 45 700 1200 1300

    300 3850 7850 11700 3.0 99.70 99.70 2.63 45 800 1300 1400

    1. The transformer is designed to operated under the following conditions

    Altitude : Up to 1000 m above sea level

    Ambient air temperature : 40 C maximum

    2. Limits of temperature rise (winding) : not exceeding 100 C

    3. Insulation class : F

    4. Connection symbol : Dyn 115. Reference standard : IEC 76 and ANSI C57.12

    6. Type of cooling : AN (air natural self cooled)

    7. Special vector group and other voltage available upon request

    TME-TDCDT-1909

    TECHNICAL DATA OF CONVENTIONAL DRY TYPE THREE PHASE TRANSFORMER

    Theconten

    tsandspecificationsofthisdatasheetaresubje

    cttochangewithoutpriornotice.

    Nopartofthisdatamaybereproducedwithoutthepriorapp

    rovalofThaiMaxwellElectric.

    EFFICIENCY

    (P.F.=1)NOISE

    LEVEL dB

    (A) : 0.3 m

    OUTLINE DIMENSION

    (APPROX. in mm.)

    Note :

    TOTAL WEIGHT

    (kg)

    105

    155

    185

    250

    295

    335

    390

    450

    1235

    1250

    1440

    545

    600

    705

    830

    950

    935

  • 7/27/2019 7Conventional Dry-type Transformer

    2/2

    Rated primary voltage : 100V - 600V

    CAPACITYNO-LOAD

    LOSSES

    LOAD

    LOSSES

    AT 75 C

    TOTAL

    LOSSES

    AT 75 C

    IMPEDANCE

    AT 75 C

    VOLTAGE

    REGULATION

    AT FULL LOAD

    (P.F.=1)

    (kVA) (Watt) (Watt) (Watt) (%) Load

    (%)

    Full Load

    (%) (%) W L H

    0.1 2 4 6 2.0 99.70 99.70 3.94 20 200 280 170

    0.5 7 18 25 2.0 99.67 99.64 3.56 20 200 280 170

    1 16 35 51 2.0 99.69 99.68 3.46 25 200 280 170

    2 31 72 103 2.0 99.68 99.67 3.56 25 300 300 300

    3 45 100 145 2.5 99.69 99.68 3.31 30 300 300 300

    4 60 130 190 2.5 99.69 99.68 3.23 30 300 300 300

    5 73 170 243 2.5 99.68 99.67 3.37 30 300 340 400

    6 85 210 295 3.0 99.68 99.65 3.48 30 300 340 400

    7 100 230 330 3.0 99.69 99.67 3.28 30 350 400 500

    8 130 280 410 3.0 99.69 99.69 3.48 40 350 400 500

    9 150 310 460 3.0 99.70 99.69 3.43 40 350 450 55010 165 350 515 3.0 99.69 99.69 3.48 40 350 450 550

    15 240 510 750 3.0 99.69 99.69 3.39 40 400 450 650

    20 330 670 1000 3.0 99.70 99.70 3.34 40 400 500 750

    25 410 850 1260 3.0 99.70 99.69 3.39 40 400 500 750

    30 490 990 1480 3.0 99.70 99.70 3.29 45 450 550 800

    35 580 1170 1750 3.0 99.70 99.70 3.33 45 450 550 800

    1. The transformer is designed to operated under the following conditions

    Altitude : Up to 1000 m above sea level

    Ambient air temperature : 40 C maximum

    2. Limits of temperature rise (winding) : not exceeding 100 C

    3. Insulation class : F

    4. Connection symbol : Dyn 115. Reference standard : IEC 76 and ANSI C57.12

    6. Type of cooling : AN (air natural self cooled)

    7. Special vector group and other voltage available upon request

    TME-TDCDT-2009

    TECHNICAL DATA OF CONVENTIONAL DRY TYPE SINGLE PHASE TRANSFORMER

    Theconten

    tsandspecificationsofthisdatasheetaresubjecttochangewithoutpriornotice.

    Nopartofthisdatamaybereproducedwithoutthepriorapp

    rovalofThaiMaxwellElectric.

    EFFICIENCY

    (P.F.=1)NOISE

    LEVEL dB

    (A) : 0.3 m

    OUTLINE DIMENSION

    (APPROX. in mm.)TOTAL WEIGHT

    (kg)

    105

    155

    185

    250

    295

    335

    390

    450

    545

    1250

    1440

    Note :

    600

    705

    830

    950

    935

    1235