55523949 Current Transformer Slide

Embed Size (px)

Citation preview

  • 8/3/2019 55523949 Current Transformer Slide

    1/63

    CURRENTTRANSFORMER

    B Y

    ENG .Yehia Tag Eldin

  • 8/3/2019 55523949 Current Transformer Slide

    2/63

    The main tasks of instrumenttransformer are:

    To transform current, or voltages, from a high value to a valueeasy to handle for relays and instruments.

    21 NI=

    Insulate secondary circuits from the primary.

    permit the use of standard current ratings forsecondary equipment.

    12

  • 8/3/2019 55523949 Current Transformer Slide

    3/63

    APPLICATION

    Current transformers (CT,s) are instrumenttransformers that are used to supply a reducedvalue of current to protective relays , meters and

    o er ns rumen s. CT,s provide isolation from the high voltage

    primary , permit grounding of the secondary

    windings for safety , and step down the magnitudeof the measured current to a value that can besafely handled by the instruments

  • 8/3/2019 55523949 Current Transformer Slide

    4/63

    RATIO

    The most common CT secondary full load currentis 1A or 5A.

    CT ratio are expressed as a ratio of rated primary

    current to t e rate secon ary current . Example

    a 1000/1 A CT will produce 1A of secondary

    current when 1000 A flows through the primary .As the primary current changes the secondarycurrent will vary accordingly.

  • 8/3/2019 55523949 Current Transformer Slide

    5/63

    POLARITY

    All CT,s are subtractive polarity . Polarity refers to the instantaneous direction of the

    primary current with respect to the secondary

    current an is etermine y t e way t etransformer leads are brought out of the case .

    On subtractive polarity transformers the H1

    primary lead and the X1 secondary lead will be onthe same side of the transformer.

  • 8/3/2019 55523949 Current Transformer Slide

    6/63

    CT POLARITY

    P1

    S1

  • 8/3/2019 55523949 Current Transformer Slide

    7/63

    Terminal markings

    GENERAL RULESThe terminal markings shall identify: the primary andsecondary windings; the winding sections, if any; the

    the intermediate tapings, if any

  • 8/3/2019 55523949 Current Transformer Slide

    8/63

  • 8/3/2019 55523949 Current Transformer Slide

    9/63

    GRAPHIC SYMBOLS OF CURRENTTRANSFORMERS

  • 8/3/2019 55523949 Current Transformer Slide

    10/63

    CT RING TYPE

  • 8/3/2019 55523949 Current Transformer Slide

    11/63

    CT

  • 8/3/2019 55523949 Current Transformer Slide

    12/63

    SUMMATION CT

  • 8/3/2019 55523949 Current Transformer Slide

    13/63

    CT EQUIVALENTCIRCUIT

  • 8/3/2019 55523949 Current Transformer Slide

    14/63

    EXCITATIONCURVE

  • 8/3/2019 55523949 Current Transformer Slide

    15/63

    1 Non saturated - zone

    2 intermediate - zone

    3 saturated -zone

  • 8/3/2019 55523949 Current Transformer Slide

    16/63

    TEST RESULT

    current(I) voltage(V)

    0.01 9

    0.04 9

    0.10 9

    0.12 90.14 9

    0.20 9

    0.30 9

    0.40 940.0 9

  • 8/3/2019 55523949 Current Transformer Slide

    17/63

    SECONDARY EXCITINGCURRENT

  • 8/3/2019 55523949 Current Transformer Slide

    18/63

    CT 1200 / 5 ARs 0.0024 ohm/turn

    V = 1200*785.1

    = 1.785 x 240

    = 428.4 v

  • 8/3/2019 55523949 Current Transformer Slide

    19/63

    A C.T consists essentially of an iron core with two windings. Onewinding is connected in the circuit whose current is to be measured.

    The flow of current in the primary winding produces an alternatingflux in the core and this flux induces an e.m.f in the secondarywinding which results in the flow of secondary current when thisw n ng s connecte to an externa c ose c rcu t .

    The magnetic effect of the secondary current , in accordance withfundamental principles , is in opposition to that of the primary and thevalue of the secondary current automatically adjust itself to such a

    value , that the resultant magnetic effect of the primary and secondarycurrents , produce a flux required to induce the e.m.f. necessary to drivethe secondary current through the impedance of the secondary.

  • 8/3/2019 55523949 Current Transformer Slide

    20/63

    TERMS & SPECIFICATIONS

    Thermal continuous current ratingThe thermal continuous current rating

    (r.m.s.value in operates) 1.2 times , or in extended-range

    current trans ormers 1.2 or 2.0 t mes , t e rate current.

  • 8/3/2019 55523949 Current Transformer Slide

    21/63

    Thermal short time current

    Ith

    Ith is the value of current quoted on the rating platewith a duration of 1 sec. whose heating effect thecurrent transformer can withstand without damage

    . .

    KA)Ith =

    Ik =

    (50/f)0.05(tIk +

    Un*3Ssc

  • 8/3/2019 55523949 Current Transformer Slide

    22/63

    Example

    MVA SC = 5000 MVA V = 380 KV

    I k =5000

    I k = 7.597 KA

    Ith =

    I dyn = 2.5 Ith

    )0.05(50/(1Ik +

  • 8/3/2019 55523949 Current Transformer Slide

    23/63

    Dynamic current rating I dyn

    I dyn is the h ighest amplitude of current whosemechanical effects the CT can withstand , with the

    ,(peak value in KA)

    I dyn = 2.5 3 I th

  • 8/3/2019 55523949 Current Transformer Slide

    24/63

    Burden

    Burden = The impedance of the secondary circuit inohms and power factor. The burden is usually

    -absorbed at a specified power-factor at the ratedsecondary current.

  • 8/3/2019 55523949 Current Transformer Slide

    25/63

    EXTERNAL BURDEN

    RB

    LB

    BURDEN=

    VA / I{

  • 8/3/2019 55523949 Current Transformer Slide

    26/63

    To protect instrument and meters from high fault currents the meteringcores must be saturated 10-40 times the rated current depending of the typeof burden.

    The instrument security factor Fs

    PP +

    sib PP

    n+

    =

  • 8/3/2019 55523949 Current Transformer Slide

    27/63

    The main characteristics of protection CT cores are:

    Lower accuracy than for measuring transformer .

    High saturation voltage.

    Little , or no turn correction at all.

    5P and 10P The error is then 5 and 10 at the specified ALF and at

    rated burden.

  • 8/3/2019 55523949 Current Transformer Slide

    28/63

    The Accuracy Limit Factor indicates the over current as a multiple times the

    rated current , up to which the rated accuracy (5P or 10P) is fulfilled (withthe rated burden connected).

    ALFPpPPnib

    in *+

    +=

  • 8/3/2019 55523949 Current Transformer Slide

    29/63

    No. of primary turns = 1 turn

    No. of secondary turns = N turn

    Ip = N * Is

    or s o ow roug ere mus e someea rans ormer

    potential Es = The E.M.F

    Es = Is * R

    Es is produced by an alternating flux in the core.

    dt

    dE s

  • 8/3/2019 55523949 Current Transformer Slide

    30/63

    Flux required to produce Es

    BsCTss zIRIE ** +=

    AB*=

    Where= ux ens ty n t e core

    A = cross-sectional area of core

    NAfBEk ****44.4=

    ( )LCTBss zzzIE ++= Required sk EE f

    Equ. 1

    Equ. 2

  • 8/3/2019 55523949 Current Transformer Slide

    31/63

    CT 2000/5 , Rs =0.31, Imax =40 KA , MaX Flux density =1.6 Tesla

    Find maximum secondary burden permissible if no saturation is to occur.

    Solution

    N=2000/5 = 400Turns

    Is max = 40000/400 = 100Amps

    From Equ.1Vk = 4.44*1.6*20*60*(400/10000) = 340 Volt

    Max burden = 340/100 = 3.4 ohms

    Max connected burden = 3.4 - 0.31 = 3.09

  • 8/3/2019 55523949 Current Transformer Slide

    32/63

    CT ratio are selected to match the maximum load current requirements.

    i.e. the maximum design load current should not exceed the CT ratedcurrent.

    The CT ratio should be large enough so that the CT secondary current doesnot exceed 20 times rated current under the maximum symmetrical primaryfault current.

  • 8/3/2019 55523949 Current Transformer Slide

    33/63

    It is customary to place CT,s on both sides of the breaker. So that theprotection zones will overlap.

    The protection Engineer can determine which side of the breaker is best forCT location .

    All possibilities of fault position should be considered .

  • 8/3/2019 55523949 Current Transformer Slide

    34/63

    The overlap should occur across a C.B, so the C.B lies in both zones for thisarrangement it is necessary to install C.Ts on both sides of the C.B.

    C.T,s mounted on both sides of breaker nounprotected region

    No region un protected

  • 8/3/2019 55523949 Current Transformer Slide

    35/63

    Current transformers mounted on C.B sideonly of breaker fault shown not cleared by

    bus bar protection.

  • 8/3/2019 55523949 Current Transformer Slide

    36/63

    Current transformers mounted on bus barside only of breaker fault shown not

    cleared circuit protection.

    C,B will open by line protection but faultwill last.

  • 8/3/2019 55523949 Current Transformer Slide

    37/63

    IEC standardPROTECTION RATIO 2000/5 A

    POWER 20 VA

    CLASS 5P20

  • 8/3/2019 55523949 Current Transformer Slide

    38/63

    IEC standardMEASURING RATIO 2000/5 A

    POWER 20 VA

    CLASS 0.5SF5

  • 8/3/2019 55523949 Current Transformer Slide

    39/63

    CTclass X THE FOLLOWING INFRMATION IS REQUIRED

    Turns Ratio

    Knee Point Voltage

    Maximum Excitation Current Secondary Circuit Resistance

  • 8/3/2019 55523949 Current Transformer Slide

    40/63

    TPX, TPY AND TPZ current transformers

    CTs of class P, models were developed for CTs of classTPX (closed-core), TPYand TPZ (nonclosed-core). Allmodels are based on known rated values of the CTs.

    ,

    no additional measurements of the parameters of theCTs are needed.

  • 8/3/2019 55523949 Current Transformer Slide

    41/63

    TPX High remanence type CT

    The high remanence type has no limit for theremanence flux. This CT has a magnetic core without

    almost infinite time. In this type of transformers theremanence flux can be up to 70-80% of the saturationflux.

    Typical examples of high remanence type CT are classP, TPS, TPX according to IEC,class P, X according to BS(British Standard) and non gapped class C, K

    according to

  • 8/3/2019 55523949 Current Transformer Slide

    42/63

    TPY Low remanence type CT

    The low remanence type has a specified limit for theremanence flux. This CT is made with a small air gap

    exceed 10% of the saturation flux. The small air gap has only very limited influence on

    the other properties of the CT. Class TPY according to

    IEC is a low remanence type CT.

  • 8/3/2019 55523949 Current Transformer Slide

    43/63

    TPZ Non remanence type CT

    The non remanence type CT has practically negligiblelevel of remanence flux. This type of CT has relatively

    practically zero level. At the same time, these air gapsminimize the influence of the DC-component fromthe primary fault current.

    The air gaps will also reduce the measuring accuracy inthe non-saturated region of operation. Class TPZaccording to IEC is a non remanence type CT.

  • 8/3/2019 55523949 Current Transformer Slide

    44/63

    As a matter of safety, the secondary circuits of acurrent transformer should never be opened underload, because these would then be no secondary mmf

    ,

    current would become exciting current and thus mightinduce a very high voltage in the secondary.

  • 8/3/2019 55523949 Current Transformer Slide

    45/63

    General

    As a matter of safety, the secondary circuits of acurrent transformer should never be opened under

    ,

    to oppose the primary mmf, and all the primary current would become exciting current and thus mightinduce a very high voltage in the secondary.

  • 8/3/2019 55523949 Current Transformer Slide

    46/63

    Ip

    Ie Ze

    XpRp e Rs

    Sec

    g

    h

    c

    Pri

    Is

    EQUIVALENT DIAGRAM

    fVe = EXCITATION VOLTAGE VefIe = CURRENT

    Ze = IMPEDANCEVt = TERMINAL VOLTAGE Vgh

  • 8/3/2019 55523949 Current Transformer Slide

    47/63

    KNEE POINT OR EFFECTIVE POINT OFSATURATION

    ANSI/IEEE: as the intersection of the curve with a 45

    tangent line IEC defines the knee point as the intersection of

    strai ht lines extended from non saturated and

    saturated parts of the excitation curve. IEC knee is higher than ANSI - ANSI more

    conservative.

  • 8/3/2019 55523949 Current Transformer Slide

    48/63

    45 LINE

    ANSI/IEEEKNEE POINT

    Ex

    citation

    Volts

    Knee

    PointVolts

  • 8/3/2019 55523949 Current Transformer Slide

    49/63

    IEC KNEE POINT

    ANSI/IEEKNEE POINT

    EX: READ THE KNEE POINT VOLTAGE

  • 8/3/2019 55523949 Current Transformer Slide

    50/63

    RATIO CONSIDERATIONS

    CURRENT SHOULD NOT EXCEED CONNECTEDWIRING AND RELAY RATINGS AT MAXIMUMLOAD. NOTE DELTA CONNECTD CTs PRODUCE

    1.732 TIMES THE SECONDARY CURRENTS

  • 8/3/2019 55523949 Current Transformer Slide

    51/63

    RATIO CONSIDERATIONS SELECT RATIO TO BE GREATER THAN THE

    MAXIMUM DESIGN CURRENT RATINGS OF THEASSOCIATED BREAKERS AND TRANSFORMERS.

  • 8/3/2019 55523949 Current Transformer Slide

    52/63

    RATIO CONSIDERATIONS

    RATIOS SHOULD NOT BE SO HIGH AS TO,

    ACCOUNT AVAILABLE RANGES.

  • 8/3/2019 55523949 Current Transformer Slide

    53/63

    RATIO CONSIDERATIONS

    THE MAXIMUM SECONDARY CURRENT SHOULDNOT EXCEED 20 TIMES RATED CURRENT. (100 A

  • 8/3/2019 55523949 Current Transformer Slide

    54/63

    RATIO CONSIDERATIONS

    HIGHEST CT RATIO PERMISSIBLE SHOULD BEUSED TO MINIMIZE WIRING BURDEN AND TO

    BTAIN THE HI HE T T APABILITY AND

    PERFORMANCE.

  • 8/3/2019 55523949 Current Transformer Slide

    55/63

    RATIO CONSIDERATIONS

    FULL WINDING OF MULTI-RATIO CTsSHOULD BE SELECTED WHENEVER POSSIBLETO AVOID LOWERING OF THE EFFECTIVEACCURACY CLASS.

  • 8/3/2019 55523949 Current Transformer Slide

    56/63

    Core Demagnetizing The core should be demagnetized as the final test

    before the equipment is put in service. Using theSaturation test circuit a l enou h volta e to the

    secondary of the CT to saturate the core and producea cecondary current of 3-5 amps. Slowly reduce thevoltage to zero before turning off the variac.

    TESTING

  • 8/3/2019 55523949 Current Transformer Slide

    57/63

    Saturation The saturation point is reached when there is a rise in the

    test current but not the voltage.

    Burden

    TESTING

  • 8/3/2019 55523949 Current Transformer Slide

    58/63

    Flashing This test checks the polarity of the CT

    Insulation test

  • 8/3/2019 55523949 Current Transformer Slide

    59/63

    SATURATIONAbnormal high primary current

    High secondary burden

    Combination of the above two factors will result in thecreat on o g ux ens ty n t e current

    transformer iron core.

    When this density reaches or exceeds the design limitof the core , saturation results.

  • 8/3/2019 55523949 Current Transformer Slide

    60/63

    SATURATION The accuracy of the CT becomes very poor.

    The output wave form distorted.

    The result secondary current lower in magnitude.

    The greatest dangerous is loss of protective devicecoordination

  • 8/3/2019 55523949 Current Transformer Slide

    61/63

    SATURATION

  • 8/3/2019 55523949 Current Transformer Slide

    62/63

    list of CT problems usually found at site:

    Shorted CT secondaries

    Open-circuited CT secondaries Miswired CTs

    CTs that had not been wired

    CTs installed backwards

    Incorrect CTs

    Defective CTs

    CTs with incorrect ratios or on the wrong taps

    Mind you, this was just at one site and had been

  • 8/3/2019 55523949 Current Transformer Slide

    63/63

    THANKSYehia Tag ELdin