Upload
vickers
View
233
Download
0
Embed Size (px)
Citation preview
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
1/66
Copyright 1999 Thermo King Corp., Minneapolis, MN, USA
Printed in USA
V-500 10/20, V-500 MAX 10/20
TK 51878-1-OP (Rev. 0, 11/04)
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
2/66
Disclaimer
This manual is published for informational purposes only. Thermo King Corporation makes no
representations or warranties, express or implied, with respect to the information, recommendations and
descriptions contained in this manual and such information, recommendations and descriptions should
not be regarded as all-inclusive or covering all contingencies. If you have questions or require further
information, please contact your local Thermo King dealer.
The procedures described herein should be undertaken only by qualified personnel. Failure to implement
these procedures correctly may cause damage to the Thermo King unit or other property or personal
injury.
Thermo King Corporation and its affiliates shall have no liability in contract or tort (including negligence
and/or strict liability) or otherwise, to any person or entity for any personal injury, property damage or any
other direct, indirect, special or consequential damage or liability whatsoever, arising out of or resulting
from any actions by any person that are contrary to this manual or any of the information,
recommendations or descriptions contained herein or the failure of any person to implement the
procedures described herein correctly or to follow caution and safety decals located on the Thermo King
unit.
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
3/66
Table of ContentsTable of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Hazard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Refrigerant Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
First AidRefrigerant . . . . . . . . . . . . . . . . . . . . . . 11
First AidRefrigerant Oil . . . . . . . . . . . . . . . . . . . 11Safety Decals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . 15
Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16The evaporator is mounted on the ceiling inside the truck
box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Control Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
In-Cab Control Box . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Liquid Injection System . . . . . . . . . . . . . . . . . . . . . . .
Evaporator Drain Tube Heaters . . . . . . . . . . . . . . . . . Electric Standby Operation . . . . . . . . . . . . . . . . . . . .
Oil Separator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Protection Features . . . . . . . . . . . . . . . . . . . . . . . . . .
In-Cab Control Box Description . . . . . . . . . . . . . . . Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Descriptions . . . . . . . . . . . . . . . . . . . . . .
Operating Instructions . . . . . . . . . . . . . . . . . . . . . .
Cab Control Box Operating Instructions . . . . . . . . . . Displaying Return Air Temperature . . . . . . . . . . . Display Setpoint Temperature . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Enter Setpoint Temperature. . . . . . . . . . . . . . . . .
Defrost Mode Operation . . . . . . . . . . . . . . . . . . . Weekly Pretrip Inspection . . . . . . . . . . . . . . . . . .
Unit Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Thermostat Operation . . . . . . . . . . . . . . . . . . . . . . . .
http://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdf8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
4/66
Table of Contents
4
Loading and Enroute Inspections . . . . . . . . . . . . . . 39
Pre-Loading Inspection . . . . . . . . . . . . . . . . . . . . . . . . 39Inspecting the Load . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Enroute Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Maintenance Inspection Schedule . . . . . . . . . . . . . . 49
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Serial Number Locations . . . . . . . . . . . . . . . . . . . . . 63
Emergency Cold Line . . . . . . . . . . . . . . . . . . . . . . . . 65
Recover Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . 66
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
5/66
List of FiguresFigure 1:Fan Warning . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 2:Caution: High Voltage . . . . . . . . . . . . . . . . . . 12Figure 3:Belt Warning . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 4:V-500 Condenser Unit . . . . . . . . . . . . . . . . . 14Figure 5:Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 6:In-Cab Control Box . . . . . . . . . . . . . . . . . . . . 16Figure 7:Unit Components (Model 20) . . . . . . . . . . . . 21Figure 8:Condenser Electric and Capacitor Boxes
(Model 20) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Figure 9:Standard Evaporator . . . . . . . . . . . . . . . . . . . 23
Figure 10:Evaporator with Hot Water and Electric HeatOptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 11:M-13 In-Cab Control Box . . . . . . . . . . . . . . 25Figure 12:Display Screen . . . . . . . . . . . . . . . . . . . . . . 26
Figure 13:On/Off Key & LED . . . . . . . . . . . . . . . . . . .
Figure 14:Celsius/Fahrenheit LED . . . . . . . . . . . . . . . Figure 15:Setpoint Key & Dial . . . . . . . . . . . . . . . . . .
Figure 16:Misc. LEDs . . . . . . . . . . . . . . . . . . . . . . . . Figure 17:Defrost Key & LED . . . . . . . . . . . . . . . . . . .
Figure 18:M-13 In-Cab Control Box . . . . . . . . . . . . . . Figure 19:Setpoint Key . . . . . . . . . . . . . . . . . . . . . . . Figure 20:Entering Setpoint . . . . . . . . . . . . . . . . . . . .
Figure 21:On/Off Key and Defrost Key . . . . . . . . . . . Figure 22:Electric Power Receptacle . . . . . . . . . . . . .
Figure 23:Thermostat Algorithm . . . . . . . . . . . . . . . . Figure 24:Loading Considerations . . . . . . . . . . . . . . .
Figure 25:Condenser and Standby Compressor SeriaNumber Locations . . . . . . . . . . . . . . . . . . . . . . . . . . .
http://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdf8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
6/66
List of Figures
6
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
7/66
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
8/66
Introduction
8
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
9/66
Safety PrecautionsThermo King recommends all services be performed by a
Thermo King dealer. However, there are several general safetypractices you should be aware of:
DANGER: Never operate the unit with the discharge
valve closed because it could cause the compressor to
explode, causing death or serious injury.
WARNING: Always wear goggles or safety glasses
when working with or around the refrigeration
system or battery. Refrigerant or battery acid cancause permanent damage if it comes in contact with
your eyes.
WARNING: Keep hands and loose clothing clear of
fans and belts at all times when the unit is operating
or when opening or closing compressor service
valves.
WARNING: Exposed coil fins can cause painful
lacerations. Service work on the evaporator orcondenser coils is best left to a certified Thermo Ki
technician.
CAUTION: Use extreme caution when drilling ho
in the unit. Drilling into electrical wiring or
refrigerant lines could cause a fire. Never drill int
structural components.
WARNING: Turn all unit On/Off switches to the O
position before opening doors or inspecting any pa
of the unit.
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
10/66
Safety Precautions
10
Electrical Hazard
Refrigerant OilObserve the following precautions when working with or
around refrigerant oil:
RefrigerantAlthough fluorocarbon refrigerants are classified as safe,
observe caution when working with refrigerants or around
areas where they are being used in the servicing of your unit.
WARNING: Disconnect the high voltage power cable
before working on the unit. Units with electric
standby present a potential electrical hazard.
WARNING: Always wear goggles or safety glasses to
protect eyes from refrigerant oil contact.
WARNING: Protect skin and clothing from
prolonged or repeated contact with refrigerant oil.
Rubber gloves are recommended.
WARNING: Wash thoroughly immediately after
handling refrigerant oil to prevent irritation.
DANGER: Fluorocarbon refrigerants may produce
toxic gases. In the presence of an open flame or
electrical short, these gases are severe respiratory
irritants CAPABLE OF CAUSING DEATH.
DANGER: Fluorocarbon refrigerants tend to
displace air and can cause oxygen depletion which
could result in DEATH BY SUFFOCATION. Provide
adequate ventilation in enclosed or confined areas.
WARNING: Fluorocarbon refrigerants evaporate
rapidly, freezing anything they contact if accidentally
released into the atmosphere from the liquid state.
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
11/66
Safety Precautions
First Aid
First AidRefrigerant
Eyes: For contact with liquid, immediately flush eyes withlarge amounts of water. Seek prompt medical attention.
Skin: Flush areas with large amounts of warm water. Do notapply heat. Wrap burns with dry, sterile, bulky dressing to
protect from infection or injury. Seek prompt medical
attention.
Inhalation: Move victim to fresh air and restore breathing ifnecessary. Stay with victim until emergency personnel arrive.
First AidRefrigerant Oil
Eyes: Immediately flush eyes with large amounts of waterat least 15 minutes while holding the eyelids open. Get prom
medical attention.
Skin: Remove contaminated clothing. Wash thoroughly wi
soap and water. Get medical attention if irritation persists.
Inhalation: Move victim to fresh air and restore breathing
necessary. Stay with victim until emergency personnel arriv
Ingestion: Do not induce vomiting. Immediately contactlocal poison control center or physician.
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
12/66
Safety Precautions
12
Safety Decals
Figure 1: Fan Warning
Figure 2: Caution: High Voltage
Figure 3: Belt Warning
AMA145
AMA147
AMA146
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
13/66
Unit Description
IntroductionThe Thermo King V-500 10/20 and V-500 MAX truckrefrigeration systems are two piece units. The unit is designed
for medium-sized trucks and vans carrying fresh produce and
frozen and deep frozen goods.
The condenser is mounted on the front of the truck box or
container. The evaporator is mounted on the cargo
compartment ceiling. The main compressor is powered by the
vehicle engine via a belt. The unit is connected to the
compressor by refrigeration hoses. In electric standby
operation models, the second compressor is driven by an
electric motor.
Control circuits operate on 12 VDC supplied by the truck
batteries for over-the-road operation. The refrigeration system
is protected by a high pressure cutout and a low pressure
cutout.
The in-cab control includes an on/off switch, manual defros
switch, thermometer, thermostat, thermostat adjustments an
indicator lights.
The operating mode is selected automatically: When the uni
connected to an electric power source, engine-driven operat
is automatically blocked. If the vehicle engine is started up
while the power cable is still connected to the electric powe
source, the unit will continue to operate in electric standby
mode. It is not possible to start the engine-driven compress
until the power cable is disconnected from the unit.There are two basic models:
Model 10: Cool and defrost on truck engine driven
compressor operation.
Model 20: Cool and defrost on both truck engine drive
compressor operation and electric standby compressor
operation.
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
14/66
Unit Description
14
Figure 4: V-500 Condenser Unit
Unit Features M-13 In-Cab Control Box with Digital LED Thermometer
(Standard)
Digital Thermometer Electronic Thermostat (Standard)
Defrost Timer (Standard)
Defrost Thermostat
Hot Gas Defrost (Standard)
Manual Defrost Switch (Standard)
Oil Separator (Standard)
Liquid Injection
Main Compressor TM 16 XD
Electric Compressor, Model 20
Evaporator Drain Heaters, Max Units
Electric/00Water Heat, Model 20
Water Heat, Model 10
AMA508
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
15/66
Unit Description
Refrigeration SystemRefrigeration hoses or lines are used to connect the condenser,
the evaporator, the compressor and any other components.
Model 20 units have another compressor and an electric motor
mounted in the condenser section for electric standby
operation.
The engine compressor is driven by a belt from the engine. The
electric standby compressor is connected in parallel with the
engine-driven compressor. The standby compressor is
hermetically sealed with its electric motor. Both compressors
use the same refrigeration system circuit. Check valves isolate
one compressor from the other during operation.
Compressor operation is controlled by the thermostat, whichenergizes the compressor clutch during engine operation or
starts the electric motor and energizes the compressor clutch on
electric standby operation. The refrigeration system is
protected by a high pressure cutout switch and a low pressure
cutout switch.
When plugged into standby power, engine operation is
automatically locked out. If the truck engine is turned on wh
the power cord is still plugged into a power receptacle, the u
will remain working in electric mode; the engine driven
compressor cannot be started until the power cord is unplugg
from the unit as the selection of engine operation or standby
operation is automatic.
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
16/66
Unit Description
16
Figure 5: Evaporator
Evaporator
The evaporator is mounted on the ceiling inside the truck box.
Control CircuitsThe control circuits operate on 12 VDC supplied by the truck
batteries for engine operation. On standby operation, the power
is rectified from an AC transformer.
Figure 6: In-Cab Control Box
In-Cab Control BoxUnit operation is controlled with an in-cab control box, which
is mounted in the truck cab. It includes an On-Off switch,
manual defrost switch, thermometer, thermostat, thermostat
adjustment, and indicator lights.
The TC unit has an additional cab control box to operate the
second compartment. It is switched on and off from the main
cab control box and includes a thermometer, thermostat,
thermostat adjustment and indicator lights.
AMA510
AJA1772
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
17/66
Unit Description
RefrigerantThe V-500-10 and V-500-20 units use R-134a refrigerant. The
V-500 MAX-10 and V-500 MAX-20 units use R-404A
refrigerant.
Liquid Injection SystemAll V-500 models have a liquid injection system to limit
discharge temperature of the engine driven compressor. If the
discharge gas leaving the compressor reaches a temperature of
230 5 F (110 3 C) the liquid injection switch closes,
providing voltage to the liquid injection solenoid. The solenoid
opens a valve, allowing liquid refrigerant to flow from the
liquid line near the drier inlet to the metering orifice attached to
the suction line fitting on the engine driven compressor. As the
refrigerant passes through the metering orifice it expands and
evaporates, cooling the suction gas entering the compressor.
This cooling effect is transferred to the discharge gas leaving
the compressor from the adjacent cavity in the compressor
head. When the discharge gas is cooled to 200 5 F (93 3 C),
the liquid injection switch opens, the liquid injection solenoid
closes and refrigerant no longer flows through the liquid
injection system.
Evaporator Drain Tube HeatersEvaporator heaters are used in MAX units to avoid drain tu
blockage because of ice accumulation inside the evaporator
One heater is located inside each drain tube. These resistive
wire heaters melt the ice while the unit is in DEFROST mo
Electric Standby OperationDuring electric standby operation, the thermostat controls t
operation of the unit by energizing and de-energizing the
power relay, the electric relays, and the heat contactor. The
thermostat places the unit in cool by energizing the motor
contactor and the electric relays.
The thermostat places the unit in null by de-energizing all t
relays and contactors. The thermostat places the unit in heat
energizing the heat contactor.
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
18/66
Unit Description
18
When the power relay and the electric relays are energized,
they close contacts that energize the fan relay, the motor
contactor, and the electric standby compressor clutch.
When the heat contactor is energized, it energizes the electric
evaporator heaters and the fan relay.
Oil SeparatorAn oil separator is a standard feature. The oil separator
separates compressor oil from the refrigerant and returns the
oil to the compressor through the suction line. The oil separator
helps provide positive oil return at high compressor speeds and
low operating temperatures. This feature enhances compressor
lubrication and extends compressor life.
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
19/66
Unit Description
Protection FeaturesHigh Pressure Cutout Switch: The High Pressure CutoutSwitch is a pressure sensitive switch. If the discharge pressure
rises above the switchs opening pressure, the switch stops the
unit. When the discharge pressure falls below the switchs
closing pressure, the switch closes to restart the unit.
Condenser Fan Pressure Switch: This switch helps the
unit to keep the condenser head pressure higher in cool
ambients and on-road. This feature allows better control of the
head pressure and the thermostatic expansion valve, and at the
same time increases the evaporator pressure. Defrost is carried
out quicker in cool ambients and on-road.
Low Pressure Cutout Switch: This switch is a pressure
sensitive switch located in the suction line. If the pressure falls
below acceptable limits, the switch stops unit operation.
U it D i ti
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
20/66
Unit Description
20
Fuses
Fuse 1: Protects the evaporator fan motor (EFM1) from
possible overload.
Fuse 2: Protects the evaporator fan motor (EFM2) frompossible overload.
Fuse 3: Protects:
The engine-driven compressor clutch coil.
Condenser solenoid valve coil (heating option).
Hot gas solenoid valve coil.
Fuse 5: Protects the condenser fan motor (CFM1) from
possible overload.
Fuse 6: Protects the condenser fan motor (CFM2) from
possible overload.
Fuse 7: Protects the evaporator fan motor (EFM3) from
possible overload.
Fuse 4/1: Protects the in-cab control box from possible
overload. It is located inside the in-cab control box.
(Fuses 1, 2, 3 5, 6 and 7 are located on the printed circuit
board.)
Electric Standby Operation Fuses:
Fuse 4 protects the in-cab control box when the unit is in
electric standby mode. Fuse 4 is located on the printed circuitboard (inside the cab control).
Fuse 8 is located in the electric box and protects the
transformer from possible overload.
U it D i ti
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
21/66
Unit Description
Figure 7: Unit Components (Model 20)
1
6
11
AMA511
2
3
4
57
8
12
9
10
1. Filter-Drier 5. Oil Separator 9. Transformer Cover
2. Liquid Sight Glass 6. Electric Standby Compressor 10. Condenser Fans
3. Liquid Injection Valve 7. Condenser Coil 11. AC Compressor Electric Box
4. Liquid Tank 8. Rectifier Heat Sink 12. Defrost Valve
Unit Description
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
22/66
Unit Description
22
Figure 8: Condenser Electric and Capacitor Boxes (Model 20)
AMA512
3
1
4
2
AMA519
1. PC Board 3. Heat Option Contactor
2. Motor Contactor 4. Capacitor Box, single phase only
Unit Description
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
23/66
Unit Description
Figure 9: Standard Evaporator
AMA513
1
2
4
3
AMA5
1. Evaporator Fans 3. Air Temperature Sensor
2. Expansion Valve 4. Defrost Switch
Unit Description
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
24/66
Unit Description
24
Figure 10: Evaporator with Hot Water and Electric Heat Options
AMA525
1
2 3
4
1. Hot Water Heat Defrost Coil 3. High Temperature Limit Switch
2. Electric Heat Element 4. Air Temperature Sensor
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
25/66
In-Cab Control Box DescriptionUnit operation is controlled with an in-cab control box, which
is mounted in the truck cab. It includes an on-off key, manual
defrost key, setpoint key, thermometer, thermostat, thermostat
adjustment, and indicator lights.
Figure 11: M-13 In-Cab Control Box
AJA1772
In-Cab Control Box Description
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
26/66
In Cab Control Box Description
26
DisplayThe display consists of a display screen, keys and indicator
LEDs. The display screen shows the return (box) air
temperature. The screen will display the setpoint temperature if
the setpoint key is pressed.
1. Keys
2. Display Screen
Figure 12: Display Screen
AJA17721 1 2 1
In-Cab Control Box Description
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
27/66
In Cab Control Box Description
Display DescriptionsThis section describes the display screen, keys andLED
indicators.
1. ON-OFF KEY
It is used to Start/Stop the unit. The internal return air
temperature will be automatically displayed.
2. ON LED Indicator
When on, it indicates that the unit has been started by
pressing the on-off key.
Figure 13: On/Off Key & LED
1
2AJA1802
In-Cab Control Box Description
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
28/66
p
28
Figure 14: Celsius/Fahrenheit LED
3. Celsius LED Indicator
When on, it indicates the temperature being displayed is in
Degrees Celsius.
4. Minus Sign
Indicates the temperature being displayed is below zero.
5. Fahrenheit LED Indicator.
When on, it indicates the temperature being displayed is in
Degrees Fahrenheit.
6. Setpoint Adjust Dial
It is used to adjust the setpoint temperature.7. Setpoint Key
It is used to display the setpoint temperature.
Figure 15: Setpoint Key & Dial
3
4
5AJA1803
6
77
AJA1804
In-Cab Control Box Description
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
29/66
p
Figure 16: Misc. LEDs
8. Power Cord LEDWhen on, it indicates the unit is plugged to the A.C.
voltage power supply.
9. AC Overload LED
When on, it indicates the unit has been stopped by the AC
Overload Relay.
Figure 17: Defrost Key & LED
10. Unit Operation LEDWhen on, it indicates the unit is cooling.
When the unit is Stopped by the Thermostat, HPCO or
LPCO, the Unit Operation LED must be OFF and th
ON LED Indicator must remain ON.
11. Defrost LED Indicator
When on, it indicates the unit is working on Defrost Mo
12. Manual Defrost Key
It is used to initiate the Defrost Cycle manually.
8
10
9
AJA1805
11
12AJA1806
In-Cab Control Box Description
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
30/66
30
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
31/66
Operating InstructionsThermo King has applied the newest technological advances to
develop compact devices that controls unit functioning and
displays operating information quickly and accurately. Thisnew Cab Control Box is designed to be used in both new and
existing Thermo King units.
There is nothing complicated about learning to operate the Cab
Control Boxes manufactured by Thermo King, but you will
find that a few minutes studying the contents of this manual
will be time well spent.
This manual is published for informational purposes only and
the information furnished herein should not be considered asall-inclusive or meant to cover all contingencies.
In-Cab Control Boxes manufactured by Thermo King can
work with 12 VDC units.
You can also display at your convenience the thermometer &
the set point temperature in both Celsius or Fahrenheit degrees.
To set the voltage & the Celsius/Fahrenheit selectors, contact
your nearest Thermo King dealer.
Figure 18: M-13 In-Cab Control Box
AJA1772
Operating Instructions
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
32/66
32
Cab Control Box OperatingInstructions
Displaying Return Air TemperatureDuring normal operation (unit is ON and cooling), the ON
LED Indicator, the Unit Operation LED and
Celsius/Fahrenheit LED Indicator should be ON; the return air
temperature should be displayed on the screen. (See Figure
21.)
Display Setpoint Temperature1. During normal operation, press the Setpoint Key to
display the Setpoint Temperature. (See Figure 19.)
1. Setpoint Key
Figure 19: Setpoint Key
1
AJA1809
Operating Instructions
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
33/66
Enter Setpoint Temperature.1. Press the Setpoint Key. The Setpoint Temperature will
displayed on the screen. (See Figure 20.)
2. At the same time, turn the Setpoint Adjust Dial until th
display shows desired temperature.(See Figure 19.)
3. Release the Setpoint Key. The box temperature will be
displayed on the screen. (See Figure 19.)
Defrost Mode Operation
Initiate a Manual Defrost: Pressing the Manual DefrostKey will start the defrost cycle if the evaporator coil
temperature is below 2.2 C (36 F). The defrost LED
will go ON. The unit will return to the cool mode automatica
when the defrost cycle is finished. (See Figure 21.)
1. Setpoint Adjustable Dial
2. Setpoint Key
Figure 20: Entering Setpoint
1
2AJA1807
CAUTION: The Setpoint Temperature can be
changed by turning Setpoint Adjust Dial when
Setpoint Key is not pressed.
Operating Instructions
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
34/66
34
Initiate a Automatic Defrost: The defrost timer will
initiate a defrost cycle if the evaporator coil temperature is
below 2.2 C (36 F). The defrost LED will go ON. The unit will
return to the cool mode automatically when the defrost is
finished.(See Figure 21.)
Stop the Defrost Cycle: Press and release the On-Off Keytwice to stop the defrost cycle. Weekly Pretrip Inspection
The following Weekly Pretrip Inspection should be completed
before loading the truck. While the weekly inspection in not a
substitute for regularly scheduled maintenance inspections, it is
important part of the preventive maintenance program
designed to head off operating problems before they happen.
1. LEAKS. Inspect for refrigerant leaks and worn refrigerantlines. Check for proper refrigerant charge level.
2. BELTS. Inspect for cracks, wear and proper belt tension.
3. MOUNTING BOLTS. Inspect bolts for proper tightening.
4. ELECTRICAL. Electrical connections should be securely
fastened. Wires and terminals should be free of corrosion,
cracks or moisture.
2
1AJA1808
1. On/Off Key
2. Manual Defrost Key
Figure 21: On/Off Key and Defrost Key
Operating Instructions
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
35/66
5. DEFROST DRAINS. Check the defrost drain hose and
fittings to be sure that they are open so condensate can run
out during defrosting. Check the bottom end of drain hose
to be sure that is not plugged or crushed.
6. STRUCTURAL. Visually check for physical damage.
7. REFRIGERANT CHARGE. Start the unit. Check the
sight glass level with the compressor running.
Engine Operation
1. Start the truck engine.
2. Press the on-off switch on the cab control box, the
ON/OFF LED must go ON.
3. Dial the thermostat setting above and below the box
temperature to check thermostat operation on the cab
control box.
4. Set the thermostat at the desired temperature, allow the
unit to run for one-half to one hour (longer if possible)
before loading the truck. Pre-cooling will remove residual
body heat and moisture from the box interior and provide
a good test of the refrigeration system
5. When the unit has finished pre-cooling the truck interio
(evaporator temperature dropped below 36 F (2.2 C),
initiate a defrost cycle with the manual defrost switch. T
defrost cycle should end automatically.
Operating Instructions
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
36/66
36
Electric Standby Operation
1. Connect the external power supply to the power
receptacle. Make sure that the power supply voltage is
correct for the unit. The power cord led should go ON.
2. Press the on-off switch in the cab control box, the ONLED should go ON.
3. Dial the thermostat setting above and below the box
temperature to check thermostat operation on the cab
control box.
Figure 22: Electric Power Receptacle
4. Set the thermostat at the desired temperature, allow the
unit to run for one-half to one hour (longer if possible)
before loading the truck. Pre-cooling will remove residual
body heat and moisture from the box interior and provide
a good test of the refrigeration system
5. When the unit has finished pre-cooling the truck interior
(evaporator temperature dropped below 36 F (2.2 C),
initiate a defrost cycle with the manual defrost switch. The
defrost cycle should end automatically.
NOTE: Even though the truck engine is started the unit will
work on Electric Standby if the power cord is plugged in.
Operating Instructions
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
37/66
Unit OperationUnits cycle between Cool and Null to maintain the box
temperature at the thermostat setpoint. The operating modes
are: Cool, Null, and Defrost.
The thermostat controls the operation of the unit by energizingand de-energizing the Power Relay (PR). When PR is
energized it energizes the evaporator fans, the condenser fans,
and the compressor clutch (or the compressor motor contactor
during electric stand-by operation).
The condenser fan is also controlled by the condenser fan
pressure switch (CFPS) on R-134a units. This normally open
switch monitors the compressor discharge pressure. When the
discharge pressure rises to 180 psi (1241 kPa) the switch closesand energizes the condenser fan. When the discharge pressure
drops below 130 psi (896 kpa) the switch opens and
de-energizes the condenser fan.
Thermostat Operation
Cool
The thermostat energizes the (PR) at box temperatures high
than 5.4 F (3.0 C) above setpoint. The thermostat keeps PRenergized while the box temperature is higher than setpoint
The fans and the compressor run and the unit cools.
Null
The thermostat de-energizes PR at box temperatures lower
than setpoint. The thermostat keeps PR de-energized while
box temperature is lower than 5.4 F (3.0 C) above the setpo
temperature. When PR is de-energized and the unit does nooperate. On TC units PR is de-energized only when the
condition is required from both thermostats.
Operating Instructions
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
38/66
38
Figure 23: Thermostat Algorithm
Defrost
The defrost cycle can be initiated any time the evaporator coil
temperature is below 36 F (2.2 C). Defrost is initiated
automatically by the defrost timer, or manually by pressing the
manual defrost switch.The defrost relay energizes the defrost solenoid valve (and the
condenser solenoid valve on units equipped with the heat
option) to route hot refrigerant gas to the evaporator when PR
is energized. The defrost relay also interrupts power to the
evaporator and condenser fans during defrost.
The defrost cycle will continue until the evaporator coil
temperature rises 8.9 C (48 F), causing the defrost termination
switch to open ending the defrost cycle. Defrost cycle can be
also terminated stopping the unit pressing the ON/OFF Switch
twice.
Temperature
DropTemperature
Rise
3.0 C (5.4 F)
Above Setpoint
Setpoint
NULL
COOL
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
39/66
001
Loading and Enroute InspectionsThermo King refrigeration units are designed to maintain the
required temperature for the product being carried during its
time in transit. Because of the units unique design, special careis required during loading to prevent cargo spoilage.
Pre-Loading Inspection1. Inspect all door seals, including vent doors, for condition
and a tight seal with no air leakage.
2. Inspect the cargo compartment inside and out for damaged
or loose skin and insulation.
3. Inspect the inside of the cargo compartment for damaged
walls, air ducts, floor channels or T flooring, clogged
defrost drain tubes, and clogged or damaged floor
channels which could block the air return, creating
isolated areas in the load that are warmer than the desired
temperature.
4. Pre-cool the cargo compartment. Adjust the setpoint to
desired cargo temperature and allow the unit to run a
minimum of 30 to 60 minutes (longer if possible) befoloading. Check to be certain the setpoint temperature is
correct for the cargo.
Pre-cooling before loading will remove residual heat a
moisture from the cargo compartment and prepare it to
receive the refrigerated load. Pre-cooling also provides
good test of the refrigeration system.
5. Make sure products are pre-cooled to the proper
temperature before loading. Any variance should be noon the manifest.
6. Supervise product loading to make sure that there is
sufficient air space around and through the load so air fl
is not restricted.
Loading and Enroute Inspections
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
40/66
40
Figure 24: Loading Considerations
1. Unit Inspection
2. Good Outside Air Circulation
3. Gaskets Equally Compressed
4. Clear Defrost Drains5. Tight Doors
6.Good Air Circulation AroundLoad
7.Interior and Exterior Walls andInsulation in Good Condition
8.Cargo at Proper TemperaturePrior to Loading
1
6
AMA526
2 3 4
5
7
8
7
Loading and Enroute Inspections
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
41/66
Inspecting the LoadNever assume that the product has been loaded properly. Watch
for and perform the following tasks. It takes only a few
minutes and could save you or your employer considerable
time and money later on.1. Make sure the unit is off before opening the cargo
compartment doors. During operation, the unit blows out
refrigerated air, and draws in outside air.
NOTE: The unit can be run with the doors open if the
truck is backed into a refrigerated warehouse with tight
door seals.
2. Perform a final check of the load temperature. If the load
is too hot or too cold, make a final notation on themanifest.
3. While inspecting to see that the cargo is loaded proper
make sure the evaporator inlets and outlets are not
blocked.
4. Close or supervise the closing of the cargo compartme
doors. Make sure they are securely locked.
5. Check to make sure the unit setpoint is set at the desire
temperature as listed on the manifest.
6. If the unit was stopped, restart using the appropriate
starting procedure outlined in this manual.
7. Repeat the after-start inspection.
8. Defrost the unit 30 minutes after loading by starting a
manual defrost cycle.
CAUTION: Make sure cargo is pre-cooled to the
proper temperature before loading. The unit is
designed to maintain temperature, not cool an
above-temperature load.
Loading and Enroute Inspections
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
42/66
42
Enroute InspectionsNOTE: Enroute inspections are recommended every four
hours for the prevention of damage to the cargo.
1. Note the setpoint to make certain no one has altered the
setting since picking up the load.
2. Note the return air temperature reading. It should be
within the desired temperature range. If the return air
temperature reading is not within the desired temperature
range, it indicates one of the following:
a. The unit has not had sufficient time to pull down the
temperature. Refer to log, if possible, for history of
load (for example, above temperature load, properly
pre-cooled cargo compartment, length of time onroad).
b. The unit is in defrost or has just completed defrost.
NOTE: You can cancel defrost by turning the unit off,
then restarting the unit.
c. The evaporator is plugged with frost. Initiate a manual
defrost cycle. The defrost cycle will be automatically
terminated.
d. Improper air circulation within the cargo
compartment. Inspect the cargo compartment (if
possible) to determine if the evaporator fans are
working and properly circulating the air. Poor air
circulation can be due to improper loading of the
cargo or shifting of the load.
WARNING: The unit may START automatically AT
ANY TIME while it is turned ON. Make sure to turn
the unit OFF before opening unit doors or inspecting
any part of the unit.
Loading and Enroute Inspections
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
43/66
e. The unit may have a low refrigerant charge. If liquid
is not showing in the unit receiver tank sight glass, the
refrigerant charge may be low. Adding refrigerant or
repairing the refrigeration system requires a
competent mechanic. Refer such problems to the
nearest Thermo King dealer or authorized ServiceCenter, or call the Thermo King Cold Line telephone
number shown on the inside back cover of this
manual for referral.
NOTE: If the temperature in the compartment is not
within the desired temperature range, repeat the Enroute
Inspection every 30 minutes until the compartment
temperature comes within the desired temperature range.
3. Initiate a Manual Defrost cycle after each Enroute
Inspection.
CAUTION: Stop the unit if the compartment
temperature remains outside the desired temperatu
range from the setpoint on two consecutive 30 minu
inspections. Contact the nearest Thermo King
Service Center or your company office immediately
Take all necessary steps to protect and maintain
proper load temperature.
Loading and Enroute Inspections
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
44/66
44
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
45/66
Specifications
GENERAL
Main Compressor SELTEC TM-16XD
Electrical Compressor FRASCOLD D211Y
System Oil Capacity Main: 5.1 oz (150 cc)
Standby Operation: 40.1 oz (1200 cc)
Compressor Oil Type Polyol Ester P/N 203-515
Refrigerant 8.1 lbs (3.7 kg) R-404A
8.0 lbs (3.6 kg) R-134a
Defrost Method: Hot gas
Defrost Timer: Initiation Interval Adjustable, 1 hour to 10 hours
Termination Interval Termination is not timed.Defrost is terminated by Klixon
switch.
Specifications
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
46/66
46
ELECTRICAL SYSTEM
Fuses
Fuse 1: Evaporator Fan Motor (EF1) 15 amps
Fuse 2: Evaporator Fan Motor (EF2) 15 ampsFuse 3: Engine-driven Compressor Clutch Coil, Condenser SolenoidValve Coil (heating option), Hot Gas Solenoid Valve Coil
15 amps
Fuse 5: Condenser Fan Motor (CFM1) 15 amps
Fuse 6: Condenser Fan Motor (CFM2) 15 amps
Fuse 7: Evaporator Fan Motor (EF3) 15 amps
Fuse 4: Electric Standby 3 amps
Fuse 4/1: Cab Control Box 3 amps
Condenser Fan Motors (2)
Voltage Full Load rpm Full Load Current
13 Vdc 3000 9.2 Amps
Specifications
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
47/66
Evaporator Fan Motors (3)
Voltage Full Load rpm Full Load Current
13 Vdc 2700 6.2 Amps
Coils for Hot Gas Solenoids
Voltage Current Resistance
12 Vdc 2.3 Amps 5.2 Ohms
AC Electric Motor
Voltage Phase Frequency Full Load Current
208/230 3 60 Hz 14.1 Amps
208/230 1 60 Hz 16.0 Amps
BELT TENSION Check vehicle manufacturer specifications
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
48/66
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
49/66
Maintenance Inspection ScheduleA closely followed maintenance program will help to keep
your Thermo King unit in top operating condition. The
following general schedule is provided to assist in monitoringthat maintenance.
For more specific detail, see the maintenance manual for your
unit and to the PreTrip Inspection chapter in this manual.
After first week of operation:
Check belt tension.
Tighten unit mounting bolts.
Check refrigerant level.
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
50/66
Maintenance Inspection Schedule
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
51/66
Check all unit mounting bolts, brackets, lines, hoses, etc.
Weekly Monthly Semi-
Annual
Annual Inspect/Service These Items
Maintenance Inspection Schedule
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
52/66
52
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
53/66
WarrantyTerms of the Thermo King Warranty are available on request.
Please reference document TK 51350 for the Thermo King
Vehicle-Powered Truck Unit Warranty.
Warranty
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
54/66
54
Gl
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
55/66
001
GlossaryThis glossary is published for informational purposes only and
the information being furnished herein should not be
considered as all-inclusive or meant to cover all contingencies.NOTE: Additional terms not found in the glossary may be
located in the index section of this manual.
accumulator: A device located in the suction line to collectliquid refrigerant and meter it safety back to the compressor as
gas.
ambient air temperature: Temperature of the airsurrounding an object.
amp: Abbreviation for ampere. The basic measuring unit ofelectrical current.
bar: A metric unit of pressure. 1 bar = 100 kPa = 14.5 psi.
Battery Sentry: Part of the CYCLE-SENTRYsystem. The
Battery Sentry module monitors alternator charge rate and will
keep the unit running until the battery is adequately charged.
box temperature: The temperature within atemperature-controlled compartment.
Btu (british thermal unit): The quantity of heat requiredraise the temperature of one pound of water by one degree
Fahrenheit. 1 Btu = 252 calories.
bulkhead: 1)return air bulkhead. A metal or plastic wal
placed at the front of the box to prevent loading of product
tightly against the Thermo King unit. (Loading too close to
unit restricts air flow and system efficiency.) 2) bulkhead
divider. A thick, insulated wall used to separate
compartments of a multi-temperature truck or trailer.calorie: The amount of heat required to raise temperature one gram of water one degree Celsius. 1 calorie = 0.004 Btu
Celsius: The metric unit of temperature measurement. Thpreferred alternate to the term centigrade. Abbreviated C.
centigrade. See Celsius.
Glossary
CFC Chl fl b A hl i b d f i d A f bi i hi h h
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
56/66
56
CFC: Chlorofluorocarbon. A chlorine-based refrigerant
consisting of chlorine, fluorine and carbon. Example: R12. In
many countries it is illegal to release this type of refrigerant to
the atmosphere because chlorine damages the earths
atmosphere. CFC refrigerants are not used in modern Thermo
King units.circuit breaker: A thermal device that automaticallyinterrupts an electrical circuit when the current in the circuit
exceeds the predetermined amperage rating of the breaker. See
amp.
coil: A cooling or heating element made of pipe or tube,formed into a helical or serpentine shape, that may be equipped
with thin metal fins to aid heat transfer.
cold curtains: Flexible vinyl curtains used to reduce airexchange between the refrigerated compartment and the
outside during door openings.
compound gauge: A gauge calibrated in psig (or kPa) tomeasure pressure, and in inches of mercury (Kg/cm2) to
measure vacuum.
compressor: The refrigeration component that compresses
refrigerant vapor and creates refrigerant flow.
condenser: An arrangement of tubing in which the
vaporized and compressed refrigerant is liquefied as heat is
removed.
cycles per second: SeeHertz.
damper door: A door on the evaporator section that closesduring defrost to prevent hot air from entering the refrigeratedcargo compartment.
data logger: An electronic device that monitors and storesunit operating and temperature data for later review. Examples:
DMS, DAS, DRS and AccuTrac.
DE: Dual Evaporator. A multi-temp host unit with two
evaporators capable of refrigerating two separate, longitudinal
compartments.defrost: The removal of accumulated ice from an evaporatorcoil. Periodic defrost is necessary when the evaporator coil is
operating below freezing. Defrost is required more frequently
when the air passing through the evaporator has a high
moisture content.
defrost termination switch: A component that terminates
defrost operation at a specific temperature.
Glossary
d f t ti A lid t t d l th t i iti t d f t t t Th t f th f i ti t th t b
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
57/66
defrost timer: A solid state module that initiates defrost at
selected intervals. Also establishes a maximum defrost
duration if normal circuits malfunction.
dehydrator: A device used to remove moisture fromrefrigerant. Also called a drier.
discharge air temperature: The temperature of air leavingthe evaporator.
drier: See dehydrator.
ECT: A ceiling-mounted Thermo King remote evaporator. SeeEWand TLE.
ERC: Extended Remote Unit Control. (Door switches) Anoption on Thermo King multi-temperature units to improve
temperature control when doors are opened during delivery.When a compartment door is opened, the refrigeration unit for
that compartment may be forced to NULL, defrost, or some
other mode. Opening a compartment door may also affect the
operating mode of other compartments. ERC systems are
connected in a variety of ways to meet customer needs.
ETV (Electronic Throttling Valve) : A device used with a
microprocessor to precisely control the refrigeration system.
evaporator: The part of the refrigeration system that abso
heat during the cooling cycle.
EW: A wall-mounted Thermo King remote evaporator. See
ECTand TLE.
F: See Fahrenheit.Fahrenheit: A unit of temperature measurement used in thUnited States. Abbreviated F.
freeze up: 1) Failure of a refrigeration system to operatenormally due to moisture in the refrigerant and the formatio
of ice at the expansion valve. The expansion valve may be
frozen shut or open, causing improper unit operation in eith
case. 2) The formation of a solid ice mass over the evapora
coil reducing air flow.fuse: An electrical safety device (typically a cartridge)inserted into an electrical circuit. It contains material that w
melt or break when the current is increased beyond a specif
value. When this occurs, the circuit is opened and electrical
current flow is stopped.
Glossary
fusible link: An electrical safet de ice (t picall a short hp (horsepower): A nit of po er eq i alent to 746 atts
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
58/66
58
fusible link: An electrical safety device (typically a short
piece of wire) inserted into an electrical circuit. The wire melts
or breaks when the current is increased beyond a specific
value. When this occurs, the circuit is opened and electrical
current flow is stopped.
HCFC: Hydrochlorofluorocarbon. A chlorine-basedrefrigerant containing hydrogen, chlorine, fluorine and carbon.
Example: R22. Because chlorine damages the earths
atmosphere, in many countries, it is illegal to release this type
of refrigerant to the atmosphere. HCFC refrigerants are not
used in modern Thermo King units.
Hertz: A unit of frequency equal to one cycle per second.
Abbreviated Hz.
HFC: A refrigerant consisting of hydrogen, fluorine andcarbon. Examples: R134a and 404A. HFC refrigerants contain
no chlorine and are, therefore, considered safe for the
environment.
high pressure relief valve: A safety valve on the
refrigeration system that allows refrigerant to escape from the
system if pressure exceeds a predetermined value.
hp (horsepower): A unit of power equivalent to 746 watts
or 550 foot-pounds per second.
HPCO (High Pressure Cut Out Switch): A
pressure-operated switch that opens to stop unit operation
when discharge pressure reaches a predetermined maximum.
invertible: A multi-temperature truck or trailer unit designedto allow the placement of deep-frozen cargo in any
compartment. SeeMulti-Temp.
kPa: Kilopascals. A metric unit of pressure. 1 kPa = 0.01 bar =
0.145 psi.
load: 1) The product being refrigerated and transported.
2) The amount of heat being removed by the refrigeration
system. (For example, a compressor is under a heavy heat loadwhen expected to cool a very warm box.)
LPCO (Low Pressure Cut Out Switch): A
pressure-operated switch that opens to stop unit operation
when suction pressure reaches a predetermined minimum.
modulation: An optional system that reduces load (product)dehydration and avoids top freeze.
Glossary
movable bulkhead: A thick insulated portable wall like psi: Pounds per square inch A unit of pressure
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
59/66
movable bulkhead: A thick, insulated, portable wall-like
device used to compartmentalize a temperature-controlled
truck or trailer. See bulkhead.
Multi-Temp: A Thermo King truck or trailer unit capable ofmaintaining different set-points in multiple compartments.
no. 1 diesel fuel: A grade of diesel fuel formulated toprevent jelling in low ambient temperatures.
no. 2 diesel fuel: A grade of diesel fuel formulated formoderate to warm ambient temperatures.
ohm: An electrical unit measuring the amount of resistance(opposition to the current flow) in an electrical circuit.
pre-cooling: 1) To cool down an empty box
(temperature-controlled area) to the desired load temperatureprior to loading. 2) To cool cargo to a desired temperature
before loading.
pre-heat: The heating of diesel engine glow plugs prior tostart-up. Some engines use an intake manifold heater rather
than glow plugs.
pre-trip inspection: Checking the operation of a
refrigeration system before loading.
psi: Pounds per square inch. A unit of pressure.
1 psi = 0.069 bar = 6.89 kPa.
psig: Pounds per Square Inch Gauge. Pressure in pounds p
square inch as displayed by a gauge calibrated to zero when
open to the atmosphere.
receiver tank: A refrigerant storage device included innearly all Thermo King units.
refrigerant: The medium of heat transfer in a refrigerationsystem which absorbs heat by evaporating at a low temperat
and releases heat by condensing at a higher temperature.
refrigerant oil: A special oil used to lubricate compressor
refrigeration systems.
remote evaporator: A separate evaporator unit located isecond or third compartment of a multi-temperature truck o
trailer unit.
return air bulkhead: A structure (metal or plastic) mounin the front of a trailer and designed to prevent restriction o
return air flow to the Thermo King unit due to improper
loading. See bulkhead.
Glossary
return air temperature: The temperature of the air Vac (volts alternating current): An electric current that
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
60/66
60
return air temperature: The temperature of the air
returning to the evaporator. See box temperature.
rpm: Revolutions per minute.
setpoint: The temperature selected on a thermostat ormicroprocessor controller. This is normally the desired box
temperature.
short cycling: When a refrigeration unit cycles between the
heat and cool modes more often than normal.
sight glass: A system component that permits visualinspection of oil or refrigerant level and condition.
thermostat: A device that controls unit modes of operation tomaintain a selected box temperature.
TLE: Thin-line evaporator. A Thermo King remote evaporatordesigned to be compact (thin) while supplying superior air
flow. SeeECTandEW.
top freeze: When the top portion of perishable cargo is
damaged by freezing temperatures discharged from the
refrigeration unit. This may occur near the front of the box
when product is placed too close to the cold, discharge air flow.
Vac (volts alternating current): An electric current that
reverses direction at regularly recurring intervals.
Vdc (volts direct current): An electric current that flows in
one direction only and is constant in value.
volts: The basic measuring unit of electrical potential.
watt: The basic measuring unit of electrical power.
Index
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
61/66
Index
AAfter Start Inspection37
CCab Control Box Operating Instructions (M-13, M-16,
M-17)32Compressor15Control Circuits16
D
Defrost Mode Operation (M-13, and M-16 only).33
Display26Display Setpoint Temperature32Displaying Return Air Temperature32
E
Electric Standby Operation17Electrical Hazard10ELECTRICAL SYSTEM46Emergency Cold Line65
enroute inspections39, 42Enter Setpoint Temperature.33
Evaporator16Evaporator Drain Tube Heaters17
FFirst Aid-Refrigerant11First Aid-Refrigerant Oil11Fuses20
G
GENERAL45General Display Information26
IIn-Cab Control Box16In-Cab Control Box Description25inspecting load41Introduction13introduction7
Index
K Refrigerant Oil 11
http://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdf8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
62/66
62
K
keypadTK logo27
LLiquid Injection System17loading inspections39loading procedures
pre-loading inspection39
M
Maintenance49Maintenance Inspection Schedule49
O
Oil Separator18Operating Instructions31
Ppre-loading inspection39Protection Features19
RRefrigerant
10
,17
Refrigerant Oil11
SSafety Decals12Safety Precautions9standard display27
T
TK logo key27
U
Unit Description13Unit Features14Unit Operation37
Wwarranty53Weekly Pretrip Inspection34
Serial Number Locations
Serial Number Locations
http://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdfhttp://../Module%20Masters/1_Incab%20Control%20Box%20Desc_M13%20only.pdf8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
63/66
Serial Number LocationsCONDENSER: Nameplate located on the back inside wall ofcondenser frame.
ENGINE DRIVEN COMPRESSOR: Nameplate located oncompressor body. The engine driven compressor is located in
the truck engine compartment.
STANDBY COMPRESSOR: Nameplate located on
compressor body. The Standby compressor is located inside the
Condenser assembly.
1. Condenser Serial Number Location2. Stand By Compressor Serial
Number Location
Figure 25: Condenser and Standby CompressoSerial Number Locations
AMA51
21
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
64/66
Emergency Cold Line
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
65/66
Emergency Cold Line
If you cant get your rig rolling, and you have tried the Thermo
King North American Service Directory (available from any
Thermo King dealer) to reach a dealer without success, then
call the Toll Free Emergency Cold Line Number
(888) 887-2202.
The answering service at the factory will assist you in reach
a dealer to get the help you need. The Cold Line is answered
hours a day by personnel who will do their best to get you
quick service at an authorized Thermo King Dealer.
AKB12
8/12/2019 51878-1-OP V-500 10-20, V-500 MAX 10-20 (Rev 0, 11-04)
66/66
66
Recover Refrigerant
At Thermo King, we recognize the need to preserve the environmentand limit the potential harm to the ozone layer that can result from
allowing refrigerant to escape into the atmosphere.
We strictly adhere to a policy that promotes the recovery and limits
the loss of refrigerant into the atmosphere.
In addition, service personnel must be aware of Federal regulationsconcerning the use of refrigerants and the certification of technicians.
For additional information on regulations and technician certification
programs, contact your local THERMO KING dealer.