    ENGLISH

    Thank you for choosing Delta DVP-SV#1/DVP-SV2#1. The SV/SV2 is a 28-point (16 input + 12 output) PLC MPU, offering various instructions and with 16k(SV)/30k(SV2) steps program memory, able to connect to all Slim type series extension models, including digital I/O (max. 512 points), analog modules (for A/D, D/A conversion and temperature measurement) and all kinds of high-speed extension modules. 4 groups of high-speed (200kHz) pulse output and 2 two-axis interpolation instructions satisfy all kinds of applications. DVP-SV/SV2 is small in size and easy to install. Note #1: DVP28SV11R/T is represented by SV, and DVP28SV11R2/T2/S2 is represented by SV2.

    This instruction sheet only provides introductory information on electrical specifications, general specifications, installation and wiring. For detalied infromation on programming and intructions, please refer to DVP-PLC Application Manual: Programming. For information about optional peripherals, please see individual product instuction sheet or DVP-PLC Application Manual: Special Modules.

    This is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may occur.

    DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all the wiring again before switching on the power. Make sure the groud terminal is correctly grounded in order to prevent electromagnetic interference. DO NOT touch any internal when the power is switched off.

    Product Profile

    Direct fastening hole

    Nameplate [ Figure 1 ]

    I/O terminal

    COM1(RS-232)program I/O communication port

    Left-side module connection port

    DIN rail clip

    RUN/STOP switch

    I/O indicator

    VR0: M1178 /D1178enabledcorresponding value

    VR1: M1179 enabled/D1179corresponding value

    POWER/RUN/BAT.LOW/ERROR indicator

    COM1(RS-232) receivingcommunication (Rx) indicator

    COM2(RS-485) sendingcommunication (Tx) indicator

    2

    3

    4

    7

    8

    5

    6

    9

    11

    12

    13

    1

    10

    3PIN removable terminal(standard component) I/O module

    positioning hole

    [ Figure 2 ]

    I/O module connection port

    COM2(RS-485) communication port (Master/Slave)

    Power input portI/O module fastening clip

    Mounting slot(35mm)

    Power input connectioncable (standard component)

    14

    15

    16

    17

    18

    19

    20

    21

  • - 2 -

    Electrical Specifications Model

    Item DVP28SV11R DVP28SV11R2 DVP28SV11T DVP28SV11T2 DVP28SV11S2

    Power supply voltage

    24VDC (-15% ~ 20%) (with counter-connection protection on the polarity of DC input power)

    Inrush current Max. 2.2A@24VDC

    Fuse capacity 2.5A/30VDC, Polyswitch Power consumption 6W

    Insulation resistance > 5M (all I/O point-to-ground: 500VDC)

    Noise immunity

    ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV, Analog & Communication I/O: 1kV Damped-Oscillatory Wave: Power Line: 1kV, Digital I/O: 1kV RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

    Grounding The diameter of grounding wire shall not be less than that of the wiring terminal of the power. (When PLCs are in use at the same time, please make sure every PLC is properly grounded.)

    Operation / storage

    Operation: 0C ~ 55C (temperature); 50 ~ 95% (humidity); pollution degree 2 Storage: -25C ~ 70C (temperature); 5 ~ 95% (humidity)

    Agency approvals UL508 European community EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC

    Vibration / shock immunity

    International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

    Weight (g) 260 260 240 240 230

    Input Point 24VDC single common port input Spec.

    Items 200kHz 20kHz 10kHz

    Input No. X0, X1, X4, X5 X10, X11, X14, X15 X6, X7, X12, X13, X16, X17 Input voltage (10%) 24VDC, 5mA Input impedance 4.7k 3.3k 4.7k

    OffOn > 4mA (16.5V) > 6mA (18.5V) > 4mA (16.5V) Action level OnOff < 1.5mA (8V) < 2.2mA (8V) < 1.5mA (8V) OffOn < 150ns < 3.5s < 8s Response

    time OnOff < 3s < 20s < 60s Filter time Adjustable within 10 ~ 60ms by D1020, D1021 (Default: 10ms)

    Output Point Transistor Spec.

    Items Relay High-speed Low-speed

    Output No. Y0 ~ Y7, Y10 ~ Y13 Y0 ~ Y4, Y6 Y5, Y7, Y10 ~ Y13 Y14 ~ Y17,

    Y20 ~ #1 Max. frequency 1Hz 200kHz 10kHz 1kHz Working voltage 250VAC, < 30VDC 30VDC #2 Max. load Resistive 1.5A/1 point (5A/COM) 0.3A/1 point @ 40C

    Inductive #3 9W (30VDC) Max. load

    Lamp 20WDC/100WAC 1.5W (30VDC)

    OffOn 0.2s 20s

  • - 3 -

    #3: Life curves

    Contact Current(A)0.50.1 0.2

    50

    0.3 0.7 1 2

    200300

    500

    100

    100020003000

    Ope

    ratio

    n(X

    10)3

    120VAC Resistive30VDC Inductive(t=7ms)

    240VAC Inductive(cos 0.4)=120VAC Inductive(cos =0.4)

    30VDC Inductive ( t=40ms)

    [ Figure 3 ] I/O Configuration

    Input Output I/O configuration Model Power

    Point Type Point Type Relay Transistor (NPN) Transistor

    (PNP)

    DVP28SV11R DVP28SV11R2 Relay

    DVP28SV11T DVP28SV11T2

    Transistor(NPN)

    DVP28SV11S2

    24VDC 16 DC

    (Sink Or Source)

    12

    Transistor(PNP)

    S/SX0X1X2X3X4X5X6X7S/SX10X11X12X13

    X15X16X17

    C0Y0Y1Y2

    Y3Y4Y5

    Y6Y7

    Y10

    Y11Y12Y13

    C1

    C2

    C3X14

    S/SX0X1X2X3X4X5X6X7S/SX10X11X12X13

    X15X16X17

    C0Y0Y1C1

    C2Y4Y5

    Y6Y7

    Y12Y13

    C3

    Y2Y3

    C4Y10Y11

    X14

    S/SX0X1X2X3X4X5X6X7S/SX10X11X12X13

    X15X16X17

    UP0ZP0Y0Y1

    Y4Y5Y6

    Y12Y13

    Y7

    Y2Y3

    Y10Y11

    X14

    UP1ZP1

    Installation

    [ Figure 4 ]390

    3

    70

    101

    109.

    4

    53.2

    Unit: mm

    Please install the PLC in an enclosure with sufficient space around it to allow heat dissipation. See [Figure 5]. Direct Mounting: Use M4 screw according to the dimension of the product. DIN Rail Mounting: When mounting the PLC to 35mm DIN rail, be sure to use the retaining clip to stop any side-to-side movement of the PLC and reduce the chance of wires being loose. The retaining clip is at the bottom of the PLC. To secure the PLC to DIN rail, pull down the clip, place it onto the rail and gently push it up. To remove the PLC, pull the retaining clip down with a flat screwdriver and gently remove the PLC from DIN rail. See [Figure 6].

    Wiring 1. Use 22-16AWG (1.5mm) single or multiple core wire on

    I/O wiring terminals. See the figure in the right hand side for its specification. PLC terminal screws should be tightened to 1.90 kg-cm (1.65 in-lbs) and please use only 60/75C copper conductor.

    22-16AWG

    < 1.5mm

    [ Figure 6 ]

  • - 4 -

    2. DO NOT wire empty terminal. DO NOT place the I/O signal cable in the same wiring circuit.

    3. DO NOT drop tiny metallic conductor into the PLC while screwing and wiring. Tear off the sticker on the heat dissipation hole for preventing alien substances from dropping in, to ensure normal heat dissipation of the PLC.

    Power Supply The power input of DVP-SV/SV2 is DC. When operating DVP-SV/SV2, note the following points: 1. The power is connected to two terminals, 24VDC and 0V, and the range of power is

    20.4 ~ 28.8VDC. If the power voltage is less than 20.4VDC, the PLC will stop running, all outputs go Off, and the ERROR LED indicator will start to blink continuously.

    2. The power shutdown for less than 10ms will not affect the operation of the PLC. However, the shutdown time that is too long or the drop of power voltage will stop the operation of the PLC, and all outputs will go off. When the power returns to normal status, the PLC will automatically resume the operation. (Please take care of the latched auxiliary relays and registers inside the PLC when doing the programming).

    Safety Wiring Since DVP-SV/SV2 is only compatible with DC power supply, Deltas power supply modules (DVPPS01/DVPPS02) are the suitable power supplies for DVP-SV/SV2. We suggest you install the protection circuit at the power supply terminal to protect DVPPS01 or DVPPS02. See the figure below.

    1 AC power supply: 100 ~ 240VAC, 50/60Hz 2 Breaker 3 Emergency stop: This button cuts off the system power supply when accidental

    emergency takes place. 4 Power indicator 5 AC power supply load 6 Power supply circuit protection fuse (2A) 7 DVPPS01/DVPPS02 8 DC power supply output: 24VDC, 500mA 9 DVP-PLC (main processing unit) 10 Digital I/O module

    Input Point Wiring There are 2 types of DC inputs, SINK and SOURCE. (See the example below. For detailed point configuration, please refer to the specification of each model.)

    DC Signal IN SINK mode Input point loop equivalent circuit

    +24V

    24G

    S/S

    X0

    24VDC

    X1 [ Figure 8 ]

  • - 5 -

    DC Signal IN SOURCE mode Input point loop equivalent circuit

    +24V

    24G

    S/S

    X0

    24VDC

    X1 [ Figure 9 ]

    Output Point Wiring 1. DVP-SV/SV2 has two output modules, relay and transistor. Be aware of the

    connection of shared terminals when wiring output terminals. 2. Output terminals, Y0, Y1, and Y2, of relay models use C0 common port; Y3, Y4, and

    Y5 use C1 common port; Y6, Y7, and Y10 use C2 common port; Y11, Y12, and Y13 use C3 common port. See [Figure 10].

    When the output points are enabled, their corresponding indicators on the front panel will be on.

    3. The output terminals Y0 and Y1 of the transistor (NPN) model are connected to the common terminals C0. Y2 and Y3 are connected to the common terminal C1. Y4 and Y5 are connected to the common terminal C2. Y6 and Y7 are connected to the common terminal C3. Y10, Y11, Y12, and Y13 are connected to the common terminal C4. See [Figure 11a]. The output terminals Y0~Y7 on the transistor (PNP) model are connected to the common terminals UP0 and ZP0. Y10~Y13 are connected to the common terminals UP1 and ZP1. See [Figure 11b].

    4. Isolation circuit: The optical coupler is used to isolate signals between the circuit

    inside PLC and input modules.

    Relay (R) output circuit wiring

  • - 6 -

    1 DC power supply 2 Emergency stop: Uses external switch

    3 Fuse: Uses 5~10A fuse at the shared terminal of output contacts to protect the output circuit4 Transient voltage suppressor (SB360 3A 60V): Extends the life span of contact.

    1. Diode suppression of DC load: Used when in smaller power [Figure 13] 2. Diode + Zener suppression of DC load: Used when in larger power and frequent On/Off

    [Figure 14] 5 Incandescent light (resistive load) 6 AC power supply 7 Manually exclusive output: For example, Y3 and Y4 control the forward running and reverse

    running of the motor, forming an interlock for the external circuit, together with the PLC internal program, to ensure safe protection in case of any unexpected errors.

    8 Neon indicator 9 Absorber: Reduces the interference on AC load [Figure 15]

    Transistor output circuit wiring

    Transistor output (NPN) Transistor output (PNP)

    [ Figure 17 ] [ Figure 18 ]

    VDC+

    Smal ler power

    D

    [ F ig ure 19 ] D: 1N4001 diode or equi valent com ponen t

    C

    Y VDC+

    Smal ler power

    D

    [ F ig ure 20] D: 1N4001 diode or equi valent com ponent

    Y

    UP

    ZP

    ZD D

    La rger power andf requent on/of f

    ZD: 9V Z ener, 5W [ F ig ure 21 ] D: 1N4001 diode or equi valent com ponen t

    C

    Y

    VDC+

    ZDD

    ZD: 9V Z ener, 5W [ F ig ure 22 ] D: 1N4001 diode or equi valent com ponent

    ZP

    UP

    VDC +

    Y

    VDC

    +Larger power and

    frequent on/of f

    1 DC power supply 2 Emergency stop 3 Circuit protection fuse

    4 The output of the transistor model is open collector. If Y0/Y1 is set to pulse output, the output current has to be bigger than 0.1A to ensure normal operation of the model. 1. Diode suppression: Used when in smaller power [Figure 19] and [Figure 20] 2. Diode + Zener suppression: Used when in larger power and frequent On/Off [Figure 21]

    [Figure 22] 5 Manually exclusive output: For example, Y2 and Y3 control the forward running and reverse

    running of the motor, forming an interlock for the external circuit, together with the PLC internal program, to ensure safe protection in case of any unexpected errors.

  • - 7 -

    BAT.LOW LED Indicator After the 24 V DC power is switched off, the data in the latched area will be stored in the SRAM memory, and the rechargeable battery will supply power to the SRAM memory. Therefore, if the battery is damaged or cannot be charged, the data in the program and latched area will be lost. If you need to permanently store the data in the program and latched data register, please refer to the mechanism of storing the data in the Flash ROM permanently and the mechanism of restoring the data in Flash ROM stated below. Mechanism of storing the data in the Flash ROM permanently: You can use WPLSoft (Options -> PLCFlash) to indicate whether to permanently store the data in the latched area in Flash ROM memory (the new indicated data will replace all data previously saved in the memory). Mechanism of restoring the data in Flash ROM: If the rechargeable battery is in low voltage, resulting in possible loss of data in the program, the PLC will automatically restore the data in the latched area in the program and device D of Flash ROM into SRAM memory (M1176 = On) next time when DC24V is re-powered. The ERROR LED flashing will remind you that if the recorded program is able to resume its execution. You only need to shut down and re-power the PLC once to restart its operation (RUN). 1. The rechargeable lithium-ion battery in DVP-SV/SV2 is mainly used on the latched

    procedure and data storage. 2. The lithium-ion battery has been fully charged in the factory and is able to retain the

    latched procedure and data storage for 6 months. If DVP-SV/SV2 has not been powered for less than 3 months, the life of the battery does not decrease. To prevent the electricity emitted by the battery from resulting in short life of the battery, before disconnecting DVP-SV/SV2 for a long time, you need to power DVP-SV/SV2 for 24 hours to charge the battery.

    3. If the lithium-ion battery is put in an environment in which temperature is above 40oC, or if it is charged for more than 1000 times, its effect becomes bad, and the time for which the data can be stored is less than 6 moths.

    4. The lithium-ion battery is rechargeable, and has a longer life span than an ordinary battery. However, it still has its own life cycle. When the power in the battery is not sufficient to retain the data in the latched area, please send it to the distributor for repair.

    5. Please be aware of the date of manufacturing. The charged battery can sustain for 6 months from its date of manufacture. If you find that the BAT.LOW indicator stays on after PLC is powered, it means the battery voltage is low and the battery is being charged. DVP-SV/SV2 has to remain on for more than 24 hours to fully charge the battery. If the indicator turns from on to flash (every 1 second), it means that the battery cannot be charged anymore. Please correctly process your data in time and send the PLC back to the distributor for repair.

    Accuracy (second /month) of RTC Temperature (C/F) 0/32 25/77 55/131

    Max. inaccuracy (second) -117 52 -132

  • - 8 -

    DVP DVP-SV#1/SV2#1 28 16 + 12 PLC 16k(SV)/30k(SV2) steps I/O 512A/DD/A I/O 200kHz #1SV DVP28SV11R/T SV2 DVP28SV11R2/T2/S2

    DVP-PLC DVP-PLC

    OPEN TYPE/

    1 [Figure 1] [Figure 2]

    1 I/O 12 COM1RS-2322 13 DIN 3 COM1RS-232Rx 14 COM2RS-485Master/Slave4 COM2RS-485Tx 15 5 16 3PIN 6 RUNSTOP 17 7 VR0M1178 D1178 18 I/O 8 VR1M1179 D1179 19 I/O 9 20 DIN (35mm) 10 21 I/O 11

    DVP28SV11R DVP28SV11R2 DVP28SV11T DVP28SV11T2 DVP28SV11S2

    24VDC (-15% ~ 20%) Max. 2.2A@24VDC 2.5A/30VDC (Polyswitch) 6W > 5M 500VDC

    ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV, Analog & Communication I/O: 1kV Damped-Oscillatory Wave: Power Line: 1kV, Digital I/O: 1kV RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

    PLC

    0C ~ 55C50 ~ 95% 2 -25C ~ 70C5 ~ 95%

    UL508 European community EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC

  • - 9 -

    DVP28SV11R DVP28SV11R2 DVP28SV11T DVP28SV11T2 DVP28SV11S2

    IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 260g 260g 240g 240g 230g

    24VDC 200kHz 20kHz 10kHz

    No. X0, X1, X4, X5 X10, X11, X14, X15 X6, X7, X12, X13, X16, X17

    10% 24VDC, 5mA

    4.7k 3.3 k 4.7 k

    OffOn > 4mA (16.5V) > 6mA (18.5V) > 4mA (16.5V)

    OnOff < 1.5mA (8V) < 2.2mA (8V) < 1.5mA (8V)

    OffOn < 150ns < 3.5s < 8s OnOff < 3s < 20s < 60s

    D1020 D1021 10 ~ 60 ms (10ms)

    No. Y0 ~ Y7, Y10~Y13 Y0 ~ Y4, Y6Y5, Y7,

    Y10~Y13 Y14~Y17,

    Y20~#1 1Hz 200kHz 10kHz 1kHz

    250VAC, < 30VDC 30VDC #2 1.5A/1 point (5A/COM) 0.3A/1 @ 40C

    #3 9W (30VDC)

    20WDC/100WAC 1.5W (30VDC) OffOn 0.2s 20s

  • - 10 -

    1. / 22-16AWG (1.5mm) 4

    PLC 1.90 kg-cm (1.65 in-lbs) 60/75C 2. 3. PLC PLC

    DVP-SV/SV2 1. 24VDC 0V 20.4 ~ 28.8VDC

    20.4VDC PLC OffERROR LED 2. 10ms PLC

    PLC OffPLC PLC

    DVP-SV/SV2 DC Only (DVPPS01/DVPPS02) DVP-SV/SV2 DVPPS01/DVPPS02 4 [Figure 7]

    1 100 ~ 240VAC, 50/60Hz 2 3 4 5 6 2A 7 DVPPS01/DVPPS02 8 24VDC500mA 9 DVP PLC 10 /

    DC SINK SOURCE 5 [Figure 8][Figure 9]

    1. DVP-SV/SV2 PLC

    2. Y0Y1Y2 C0 Y3Y4Y5 C1 Y6Y7

    Y10 C2 Y11Y12Y13 C3 5 [Figure 10]

    3. NPN Y0Y1 C0 Y2Y3 C1 Y4Y5 C2 Y6Y7 C3 Y10Y11Y12Y13 C4 5 [Figure 11a]PNP Y0 ~Y7 UP0ZP0 Y10 ~Y13 UP1ZP1 5 [Figure 11b]

    4. PLC

    5 [Figure 12]

    1 2

    3 5 ~ 10A 4

    1. DC 6 [Figure 13] 2. DC +Zener On/Off

    6 [Figure 14] 5 6

  • - 11 -

    7 Y3 Y4 PLC

    8 9 6 [Figure 15]

    6 [Figure 17][Figure 18] 1 2 3 4 (Open Collector) Y0/Y1

    0.1A 1. 6 [Figure 19][Figure 20] 2. +Zener On/Off 6 [Figure 21]

    [Figure 22]

    5 Y2 Y3 PLC

    BAT.LOW 24V SRAM SRAM D Flash ROM WPLSoft -->

    PLCFlash D Flash ROM Flash ROM

    PLC Flash ROM D SRAM PLC (RUN)

    1. DVP-SV/SV2

    2. 6

    24

    3. 40oC 1000 6

    4.

    5. 6 BAT.LOW DVP-SV/SV2 24 1 PLC

    (C/F) 0/32 25/77 55/131

    -117 52 -132

  • - 12 -

    DVP DVP-SV#1/SV2#1 28 16 + 12 PLC 16k(SV)/30k(SV2) steps I/O 512 A/DD/A I/O 200kHz #1SV DVP28SV11R/T SV2 DVP28SV11R2/T2/S2

    DVP-PLC DVP-PLC

    (OPEN TYPE)

    1 [Figure 1] [Figure 2]

    1 I/O 12 COM1RS-232/ 2 13 DIN 3 COM1RS-232Rx 14 COM2RS-485Master/Slave4 COM2RS-485)Tx 15 5 16 3PIN 6 RUNSTOP 17 7 VR0M1178 D1178 18 I/O 8 VR1M1179 D1179 19 I/O 9 20 DIN 35mm 10 21 I/O 11

    DVP28SV11R DVP28SV11R2 DVP28SV11T DVP28SV11T2 DVP28SV11S2

    24VDC (-15% ~ 20%) Max. 2.2A@24VDC 2.5A/30VDC (Polyswitch) 6W > 5M 500VDC

    ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV, Analog & Communication I/O: 1kV Damped-Oscillatory Wave: Power Line: 1kV, Digital I/O: 1kV RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

    PLC

    0C ~ 55C50 ~ 95% 2 -25C ~ 70C5 ~ 95%

    UL508 European community EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC

  • - 13 -

    DVP28SV11R DVP28SV11R2 DVP28SV11T DVP28SV11T2 DVP28SV11S2

    IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 260g 240g 230g

    24VDC 200kHz 20kHz 10kHz

    No. X0, X1, X4, X5 X10, X11, X14, X15 X6, X7, X12, X13, X16, X17 10% 24VDC, 5mA 4.7k 3.3k 4.7k

    OffOn > 4mA (16.5V) > 6mA (18.5V) > 4mA (16.5V)

    OnOff < 1.5mA (8V) < 2.2mA (8V) < 1.5mA (8V) OffOn < 150ns < 3.5s < 8s

    OnOff < 3s < 20s < 60s D1020 D1021 10 ~ 60 ms (10ms)

    No. Y0 ~ Y7, Y10 ~ Y13 Y0 ~ Y4, Y6 Y5, Y7, Y10 ~ Y13 Y14 ~ Y17,

    Y20 ~ #1 1Hz 200kHz 10kHz 1kHz 250VAC, < 30VDC 30VDC #2

    1.5A/1 point (5A/COM) 0.3A/1 @ 40C #3 9W (30VDC)

    20WDC/100WAC 1.5W (30VDC) OffOn 0.2s 20s

  • - 14 -

    1. / 22-16AWG (1.5mm) 4

    PLC 1.90 kg-cm (1.65 in-lbs) 60/75C 2. 3. PLC PLC

    DVP-SV/SV2 1. 24VDC 0V 20.4VDC ~ 28.8VDC

    20.4VDC PLC OffERROR LED 2. 10ms PLC

    PLC OffPLC PLC

    DVP-SV/SV2 DC Only (DVPPS01/DVPPS02) DVP-SV/SV2 DVPPS01/DVPPS02 4 [Figure 7] 1 100 ~ 240VAC, 50/60Hz 2 3 4 5 6 2A 7 DVPPS01/DVPPS02 8 24VDC500mA 9 DVP PLC 10 /

    DC DC 5 [Figure 8][Figure 9]

    1. DVP-SV/SV2 PLC

    2. Y0Y1Y2 C0 Y3Y4Y5 C1 Y6Y7

    Y10 C2 Y11Y12Y13 C3 5 [Figure 10]

    3. NPN Y0Y1 C0 Y2Y3 C1 Y4Y5 C2 Y6Y7 C3 Y10Y11Y12Y13 C4 5 [Figure 11a]PNP Y0 ~Y7 UP0ZP0 Y10 ~Y13 UP1ZP1 5 [Figure 11b]

    4. PLC

    5 [Figure 12]

    1 2 3 5 ~ 10A 4

    1. DC 6 [Figure 13] 2. DC +Zener On/Off 6

    [Figure 14] 5 6 7 Y3 Y4

    PLC 8 9 6 [Figure 15]

  • - 15 -

    6 [Figure17][Figure18]

    1 2 3 4 (Open Collector) Y0/Y1

    0.1A 1. 6 [Figure 19][Figure20] 2. +Zener On/Off 6 [Figure 21]

    [Figure 22] 5 Y2 Y3

    PLC

    BAT.LOW 24V SRAM SRAM D Flash ROM WPLSoft -->

    PLCFlash D Flash ROM Flash ROM

    1 PLC Flash ROM D SRAM PLC (RUN)

    1. DVP-SV/SV2

    2. 6

    24

    3. 40oC 1000 6

    4.

    5. 6 BAT.LOW DVP-SV/SV2 24 1 PLC

    (C/F) 0/32 25/77 55/131

    -117 52 -132

  • - 16 -

    ....... TRKE .........

    Delta DVP-SV#1/SV2#1 serisi rnleri setiiniz iin teekkrler. SV/SV2 serisi 28 nokta (16 giri + 12 k) bir PLC MPU'dur. 16k(SV)/30k(SV2) step program hafzas ile birok komut destei salar. Tm modler tip serisi ilave modlleri ile balant destekler. (Digital I/O modlleri (max. 512 nokta), analog modller (A/D, D/A evrim ve scaklk lm) ve tm yksek hzl ilave modller.). 4-grup yksek-hzl (200kHz) pulse k ve 2-eksen interpolasyon komutlar ile tm uygulamalara uygun zmler sunar. DVP-SV/SV2 serisi kk boyutlu olup kurulumu ok kolaydr. Not #1: DVP28SV11R/T SV olarak temsil edilir ve DVP28SV11R2/T2/S2 SV2 olarak temsil edilir. Bu bilgi dkman sadece rnn elektriksel zellikleri, genel zellikleri, kurulumu ve

    balants ile ilgili aklamalar salar. Komutlar ve programlama ile ilgili detayl bilgi sahibi olmak iin ltfen DVP-PLC Application Manual: Programming e baknz. Opsiyonel evre donanmlar hakknda daha fazla bilgi sahibi olmak iin, ilgili donanma ait bilgi dokmanna bakabilir veya DVP-PLC Application Manual: Special Modules inceleyebilirsiniz.

    DVP-SV/SV2 AIK TP bir rndr. PLC toz, rutubet, elektrik oku ve titreimden uzak yerlerede muhafaza edilmelidir. Ayrca kiisel ve/veya maddi zararlar nlemek iin rne yetkili olmayan kiilerin mdahale etmesini engeleleyecek koruyucu nlemler alnmaldr. (rnn kurulduu panoya kilit konulmasvb).

    rnn giri/k terminallerine kesinlikle AC power balamaynz, aksi halde rn zarar grebilir. rne enerji vermeden nce tm balantlarn doru olduunu kontrol ediniz. Elektromanyetik grlty nlemek iin PLCnin dzgn topraklandna emin olunuz . Enerji varken rn terminallerine dokunmaynz.

    rn Grn Ltfen ngilizce (English) blmde ekil 1[Figure 1] ve ekil 2 [Figure 2]ye baknz.

    Elektriksel zellikler Model

    Madde DVP28SV11R DVP28SV11R2 DVP28SV11T DVP28SV11T2 DVP28SV11S2

    Power supply voltaj 24VDC (-15% ~ 20%) (DC power giri ters balant (polarite) korumas

    Ani Akm Max. 2.2A@24VDC

    Sigorta Kapasitesi 2.5A/30VDC, Polyswitch

    G Tketimi 6W

    zolasyon direnci > 5M (Tm I/O nokta-ground: 500VDC)

    Ses Bakl

    ESD (IEC 61131-2, IEC 61000-4-2): 8kV Hava Dearj EFT (IEC 61131-2, IEC 61000-4-4): G Hatt: 2kV, Dijital I/O: 1kV, Analog & Haberleme I/O: 1kV Snml-Salnml Dalga: G Hatt: 1kV, Dijital I/O: 1kV RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

    Topraklama Topraklama kablosunun kesiti power terminal kablosunun kesitinden kk olmamaldr. (Birok PLC ayn anda kullanlaca zaman, ltfen her bir PLCnin dzgn topraklandndan emin olunuz.)

    alma / Saklama alma: 0C ~ 55C (scaklk); 50 ~ 95% (rutubet); kirlenme derece 2 Saklama: -25C ~ 70C (scaklk); 5 ~ 95% (rutubet)

    Acente Onaylar UL508 Avrupa Topluluu EMC Directive 89/336/EEC ve Low Voltage Directive 73/23/EEC

    Titreim / ok direnci

    Uluslararas standartlar: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

    Arlk (g) 260 260 240 240 230

    Giriler

    24VDC tek ortak port girii zellikMadde 200kHz 20kHz 10kHz

    Giri No. X0, X1, X4, X5 X10, X11, X14, X15 X6, X7, X12, X13, X16, X17 Giri voltaj (10%) 24VDC, 5mA Giri empedans 4.7k 3.3k 4.7k

    OffOn > 4mA (16.5V) > 6mA (18.5V) > 4mA (16.5V) Aktif seviye

    OnOff < 1.5mA (8V) < 2.2mA (8V) < 1.5mA (8V)

  • - 17 -

    Giriler

    24VDC tek ortak port girii zellikMadde 200kHz 20kHz 10kHz

    OffOn < 150ns < 3.5s < 8s Cevap Zaman OnOff < 3s < 20s < 60s Filtre zaman D1020, D1021den 10 ~ 60ms aras ayarlanabilir (Varsaylan: 10ms)

    klar Transistor zellik

    Madde Rle Yksek-hz Dk-hz

    k No. Y0 ~ Y7, Y10 ~ Y13 Y0 ~ Y4, Y6 Y5, Y7, Y10 ~ Y13 Y14 ~ Y17,

    Y20 ~ #1 Maksimum frekans 1Hz 200kHz 10kHz 1kHz alma Voltaj 250VAC, < 30VDC 30VDC#2

    Rezistif 1.5A/1 nokta (5A/COM) 0.3A/1 nokta @ 40Cde

    Endktif #3 9W (30VDC) Maksimum yk Lamba 20WDC/100WAC 1.5W (30VDC) OffOn 0.2s 20s

  • - 18 -

    2. 10 msden daha ksa sreli enerji kesintisi durumunda PLCnin almas etkilenmez. Eer enerji kesintisi veya voltaj dme sresi daha uzun ise PLCnin almas durur ve tm klar OFF olur. PLC belemesi normal seviyeye geldiinde PLC otomatik olarak almasna geri dner. (PLC program yazlaca zaman kalc yardmc rle ve registerlerin kullanmna dikkat ediniz).

    Gvenli Balant

    DVP-SV/SV2 serisi PLC rnleri DC beslemeli olup, Deltann g kayna rnleri olan (DVPPS01/DVPPS02), DVP-SV/SV2 PLClerin beslemesi iin ok elverilidir. DVPPS01 veya DVPPS02 rnlerini korumak iin kullanclarn koruyucu devre kullanmas nerilir. ngilizce (English) blmde ekil 7 [Figure 7]ye baknz. AC g kayna:100 ~ 240VAC, 50/60Hz Devre Kesici Acil Stop: Acil bir durum meydana geldiinde bu buton sistemin beslemesini keser. Power indikatr AC g kayna yk G kayna devre koruma sigortas (2A) DVPPS01/DVPPS02 DC g kayna k: 24VDC, 500mA DVP-PLC (Ana ilemci nitesi) Digital I/O modl

    Giri Balants 2 eit DC giri balants vardr, SINK ve SOURCE. (Aadaki rnee baknz. Detayl konfigrasyon iin, her bir modelin zelliklerini inceleyiniz.)

    DC Sinyal IN SINK mod Giri balant edeer devresi (ngilizce (English) blmde ekil 8 [Figure 8]e baknz.)

    DC Sinyal IN SOURCE mod Giri balant edeer devresi (ngilizce (English) blmde ekil 9 [Figure 9]e baknz.)

    k Balants 1. DVP-SV/SV2 serisi rnlerde rle ve transistor olmak zere 2 tip k modl vardr. k

    balantlarn yaparken ortak terminallerin kullanmna dikkat ediniz. 2. Rle k tip PLClerde ngilizce (English) blmde ekil 10 [Figure 10]da grld gibi Y0,

    Y1 ve Y2 k terminalleri C0 ortak terminalini; Y3, Y4 ve Y5 C1 ortak terminalini; Y6, Y7 ve Y10 C2 ortak terminalini; Y11, Y12 ve Y13 ise C3 ortak terminalini kullanr. klar aktif olduu zaman, n panelde bu klara karlk gelen indikatrler ON olur.

    3. Transistor(NPN) k tip PLClerde ngilizce (English) blmde ekil 11a [Figure 11a]da grld gibi Y0, ve Y1 C0 ortak terminalini; Y2, ve Y3 C1 ortak terminalini; Y4 ve Y5 C2 ortak terminalini; Y6 ve Y7 C3 ortak terminalini; Y10, Y11, Y12 ve Y13 ise C4 ortak terminalini kullanr. Transistor(PNP) k tip PLClerde ngilizce (English) blmde ekil 11b [Figure 11b]de grld gibi Y0~Y7 klar UP0 ve ZP0 ortak terminalini; Y10~Y13 klar UP1 ve ZP1 ortak terminalini kulllanr.

    4. zolasyon devresi: PLC ve giri modlleri devreleri arasnda sinyal izolasyonu iin optokuplr kullanlr.

    Rle (R) k devre balants (ngilizce (English) blmde ekil 12 [Figure 12]ye baknz.)

    DC g kayna Acil stop: Harici anahtar kullanr Sigorta: k devrelerini korumak iin k kontaklarnn ortak terminallerinde 5~10A sigorta

    kullanlr Ani voltaj bastrma (SB360 3A 60V): Kontak mrn uzatr.

    1. DC yk diyot bastrma: Kk glerde kullanlr (ngilizce (English) blmde ekil13 [Figure 13]e baknz.)

    2. DC yk Diyot + Zener bastrma: Byk g ve sk On/Off durumunda kullanlr. (ngilizce (English) blmde ekil13 [Figure 13]e baknz.)

    Akkor lamba (rezistif yk) AC g kayna Manual tek k: rnein, Y3 ve Y4 klar motorun ileri ve geri hareketini kontrol etsin,

    beklenmeyen bir hatann olumasn daha gl nlemek iin PLCnin dahili programndan baka klar harici olarak birbirlerin nne balanabilir.

    Neon indikatr Dalga Emici: AC yk zerindeki grlty drmek iin ( ngilizce (English) blmde ekil15 [Figure

    15]e baknz.) Transistor (T) k devre balants (ngilizce (English) blmde ekil17 [Figure 17] ~ ekil 22 [Figure 22]ye baknz.)

    DC g kayna Acil stop Devre koruma sigortas

  • - 19 -

    Transistr modelinin k open collector dr. Eer Y0/Y1 pulse k ayarlanmsa, normal almay salamak iin, k akm 0.1Aden byk olmaldr. 1. Diyot bastrma: Kk glerde kullanlr (ngilizce (English) blmde ekil19 [Figure 19] ve

    ekil20 [Figure 20]ye baknz.) 2. Diyot + Zener bastrma: Byk g ve sk On/Off durumlarnda kullanlr. (ngilizce (English)

    blmde ekil21 [Figure 21] ve ekil22 [Figure 22]ye baknz.) Manual tek k: rnein, Y2 ve Y3 klar motorun ileri ve geri hareketini kontrol etsin,

    beklenmeyen bir hatann olumasn daha gl nlemek iin PLCnin dahili programndan baka klar harici olarak birbirlerin nne balanabilir.

    BAT.LOW LED indikatr BAT.LOW indikatr pilin voltaj dt zaman ON olur. Bu durum olutuu zaman, PLC iindeki program ve kalc datalarn silinmemesi iin en ksa srede pili deitiriniz. 24V DC power kesildikten sonra, kalc alan iindeki data SRAM hafzaya kaydedilir ve yeniden arj edilebilir pil SRAM hafzay besler. Bundan dolay, eer pil zarar grr veya arj edilemez ise, program ve kalc alan iindeki data kaybolur. Program ve kalc registerlerin iindeki datalarn srekli saklanmas gerekiyorsa, ltfen aadaki veriyi Flash ROM iine kalc kaydetme mekanizmasn inceleyiniz. Veriyi Flash ROM ierisine Kalc Kaydetme Mekanizmas: Kalc alandaki datalar Flash ROM memorye srekli kaydetmek iin WPLSoft Program (Options -> PLCFlash) kullanlr. (Yeni tanmlanm tm datalar hafzaya nceden kaydedilen datalarla yer deitirir). Veriyi Flash ROM ierisinden Geri arma Mekanizmas: Eer yeniden arj edilebilir pil voltaj derse, programda oluan data kayb sonucunda, PLC, DC24V ile yeniden enerjilendirildiinde programdaki kalc alanlardaki verileri ve Flash ROM ierisindeki D registerlarn SRAM hafzasna (M1176=On) otomatik olarak geri ykleyecektir. ERROR LED'in flash yapmas kullancya programn almasna (RUN) devam etmesi isteniyorsa, bir kez PLC beslemesini kapatp yeniden enerji verilmesi gerektiini bildirir. 1. DVP-SV/SV2 ierisindeki arj edilebilir lityum-iyon pil esas olarak veri saklama ve latch

    prosedrleri iin kullanlr. 2. Lityum-iyon pil retimden kmadan nce kalc prosedr ve datalar 6 ay boyunca

    saklayabilecek ekilde tamamen arj edilir. Eer SV/SV2 nitesi 3 ay kullanlmaz ve enerjilenmez ise pil mr azalmaz. Pil tarafndan elektrik yaylmas sonucu pilin mrnn azalmasn nlemek iin, uzun sre enerjisiz kalacak DVP-SV/SV2nin beslemesini kesmeden nce pili arj etmek iin 24 saat boyunca DVP-SV/SV2nin enerji altnda olmas gerekir.

    3. Eer Lityum-iyon pil ortam scakl 40oC zerinde olan bir ortama konulmu ise yada 1000 defadan fazla arj edilmi ise, bu durum pile kt etki yapacak ve data saklama sresi 6 ayn altna decektir.

    4. Lityum-iyon pil yeniden arj edilebilir bir pildir ve dier pillere gre daha uzun mrldr. Bununla birlikte yinede bir alma mrne sahiptir. Eer pil ierisindeki g kalc alandaki datalar tutmaya yeterli gelmez ise ltfen rn tamir iin teknik servisimize gnderiniz.

    5. Ltfen PLCnin retim tarihine dikkat ediniz; arj edilen pil bu tarihten itibaren 6 ay boyunca dayanabilir. PLC enerjilendikten sonra BAT.LOW indikatrn ON olduu fark edilirse, pil voltaj dm ve pilin arj edildii anlamna gelir. Bu durumda pilin tamamen arj olmas iin DVP-SV/SV2 PLC 24 saat boyunca enerjili kalmaldr. Bu durumda indikatr ONdan 1 saniyelik flash konuma geerse bu pilin artk arj edilemeyeceinin gstergesidir. Bu durumda program ve datalarn yedeini dzgn bir ekilde aldktan sonra pil deiimi iin rn teknik servisimize gnderiniz.

    RTC Doruluu (saniye/ay) Scaklk (C/F) 0/32 25/77 55/131

    Maksimum sapma (saniye) -117 52 -132

    TRKYETHALATI FRMA:F.A.S.T. Fabrika Aygtlar Sistem Teknolojisi Ltd.ti.

    Fast Plaza Atilla lhan Cad No:5334750 Ataehir/ STANBULT: +90 216 574 9434 F: +90 216 574 1660E: [email protected] W: www.fastltd.net

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile () /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure false /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles false /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /DocumentCMYK /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /UseDocumentProfile /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice