    Fire Block Sealant FB 1361. Product Description

    3M Fire Block Sealant FB136 is a one component,non-combustible draft,smoke and fireblockingsealant, designed to resisthigh temperatures andsmoke passage in non-rated construction. FireBlock Sealant FB 136meets ASTM E-136,current 2003 InternationalBuilding Code (IBC), 2003International Residential

    Code (IRC), 2003International ResidentialMechanical Code, 2003International Fuel GasCode and NFPA 5000 draft,smoke and fireblockingrequirements.

    3M Fire Block Sealant FB136 features superioradhesion strength, caulkrate and no sag application,plus a halogen-freeformula.

    3M Fire Block Sealant FB136 can be installed with astandard caulking gun,pneumatic pumpingequipment or it can beeasily applied with a puttyknife or trowel. Fire BlockSealant FB 136 will bond toconcrete, brick, metals,wood, plastic and cable

    jacketing. No mixing isrequired.

    Fire Block Sealant FB 136Features:

    Easy clean up withwater

    No special handling,routine disposal

    Thixotropic: Will notsag or run in vertical oroverhead applications

    Halogen-free

    Fast dry: Tack free inapproximately 15minutes

    Minimal shrinkage

    Gray color

    High caulk rate

    2. ApplicationsUse 3M Fire Block SealantFB 136 to seal interiorconstruction voids aroundwires, pipes, HVAC ductsand vents, in wood or steelframed non-ratedconstruction. May also beused around chimney,fireplace and other framinggaps.

    3. Specifications

    ProductThe fireblocking, smokeand draft sealant shall beone-part and non-combustible. The materialshall be thixotropic and beapplicable to overhead,vertical and horizontalapplications. The sealantshall be tested to andpassed the criteria of ASTME 136 Standard TestMethod for Behavior of

    Materials in a Vertical TubeFurnace at 750C (1380F).

    The sealant shall complywith the requirements of theInternational Building Code(IBC), InternationalResidential Code (IRC),International Fire Code(IFC), InternationalMechanical Code (IMC),International Fuel GasCode (IFGC) and NPFA5000.

    4. PerformanceA. Typical Physical Properties

    Unit Value

    Tack Free Time

    (ASTM C679)Minutes at 72F (22C) 15

    Color N/A Gray

    Density Lb./gal. (Kg/l) 14.7 (1.76)

    Adhesion All construction substrates Very Good

    Application Methods Caulk gun

    Solids Percent (%) by weight 70

    VOC Percent (%) by weight 0

    Odor N/A Mild

    B. Fireblocking Properties

    Meets the criteria of ASTM E 136 Standard Test Methodfor Behavior of Materials in a Vertical Tube Furnace at

    750C (1380F).

  • 8/13/2019 3mfireblockfb136 Pds 4327-6

    2/3

    5. Installation Techniques

    For Sealing AroundPenetrations:

    A. Clean annular space orjoint area to be filled withFB 136 to remove allgrease, dirt, oil, wax, loosedebris, etc. If required,install a non-combustiblebacking material to assistin FB 136 Sealant

    installations that havelarge annular spaces.

    B. FB 136 Sealant should beapplied at temperaturesabove 40F (5C) and the

    substrate must be frostfree.

    C. Cut the end of the FB 136tube spout to achieve thedesired bead width whenapplying. Install the FB136 to the desired depth inthe void space until the

    sealant is flush with theadjacent floor or wallsurface.

    D. Tool within five (5) minutesof application with aslightly wetted putty knifeor trowel, if required.

    E. Clean all tools with waterimmediately after use.

    For Patching Firebricksand Sealing AroundWood Burning Stoves:

    A. Clean annular space orjoint area to be filledwith FB 136 to removeall grease, dirt, oil, wax,loose debris, etc. Ifrequired, install a non-combustible backing

    material to assist in FB136 Sealantinstallations that havelarge annular spaces.

    B. FB 136 Sealant shouldbe applied attemperatures above40F (5C) and the

    substrate must be frostfree.

    C. Cut the end of the FB136 tube spout toachieve the desired

    bead width whenapplying.

    D. Install the FB 136 intoany void areas orcrevices.

    E. Tool the FB 136 intovoids or crevices withinfive (5) minutes ofapplication until smoothwith a slightly wettedputty knife or trowel.

    F. Clean the surroundingsurfaces with a damp toweland clean all tools withwater immediately afteruse.

    G. Start a low burning fire untilthe product is dry,approximately 1 hour.Increase heat graduallyuntil the FB 136 has cured,approximately 2 hours. Forfirebrick patching, FB 136should be applied in 1/8 in.layers and allowed to cure24 hours between layersprior to fire curing. Firecuring is not necessary untilthe final layer has beeninstalled.

    6. LimitationsA. FB 136 must not be used in

    areas that are expected tocome into contact withwater or exteriorapplications. FORINTERIOR USE ONLY.

    B. FB 136 must not be used inareas that are subject tocontinuous vibration.

    7. Maintenance

    The FB 136 Sealant is stableunder normal storageconditions and has a one yearshelf life. Normal stock andstock rotation arerecommended. FB 136Sealant is also Freeze-ThawStable; however for maximumshelf life, store between 33F(1C) and 90F (27C)

    8. Availability

    3M Brand Fire Block FB 136 isavailable from Authorized 3MFire Protection ProductsDistributors. It is available inthe standard 10.1 fl. oz.cartridge.

    C. Fireblocking Code RequirementsBuilding Code Section Title

    International BuildingCode (IBC)

    702 Definitions

    705.7 Combustible Framing in Fire Walls

    707.2.6 Shaft Enclosures

    708.4 Continuity (Vertical)

    711.4 Continuity (Horizontal)

    712.3.2.1.3 Penetrations

    716.6.3 Non Fire Resistance Rated Assemblies

    717 Fireblocking

    803.4.1 Direct Attachment and Furred Construction

    804.4.1 Subfloor Construction

    1406.2.4 Fireblocking

    2111.11 Fireplace Clearance

    2111.13 Fireplace Fireblocking

    2113.19 Chimney Clearances

    2113.20 Chimney Fireblocking

    International Fire Code(IFC)

    703.1.1 Fireblocking and Draftstopping

    International ResidentialCode (IRC)

    R502.13 Fireblocking Required

    R602.4 Interior Load-Bearing Walls

    R602.8 Fireblocking Required

    R1001.15 Chimney Clearances

    R1001.16 Chimney Fireblocking

    R1003.11 Fireplace Clearance

    R1003.13 Fireplace Fireblocking

    International ResidentialMechanical Code (IRMC)

    M1601.3.3 Fireblocking (Duct Systems)

    M1801.9 Fireblocking (Chimneys and Vents)

    International ResidentialFuel Gas Code (IRFGC)

    G2425.15.4 Clearances (Chimneys and Vents)

  • 8/13/2019 3mfireblockfb136 Pds 4327-6

    3/3

    Warranty and Limited Remedy. This product will be free from defects in material and manufacture for a

    period of ninety (90) days from date of purchase. 3M MAKES NO OTHER WARRANTIES

    INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY

    OR FITNESS FOR A PARTICULAR PURPOSE. User is responsible for determining whether the 3M

    product is fit for a particular purpose and suitable for users method of application. If this 3M product is

    proved to be defective within the warranty period stated above, your exclusive remedy and 3Ms soleobligation shall be, at 3Ms option, to replace or repair the 3M product or refund the purchase price of the

    3M product.

    Limitation of Liability. Except where prohibited by law, 3M will not be liable for any loss or damages

    arising from the use of this 3M product, whether direct, indirect, special, incidental or consequential,

    regardless of the legal theory asserted, including warranty, contract, negligence or strict liability.

    3Specified Construction Products Department

    3M Center, Building 223-2S-24

    St. Paul, MN 55144-1000

    800 328 1687Recycled paper

    40% pre-consumer

    10% post-consumer

    Litho in U.S.A.

    3M 2004

    BOLGER 4060474

    98-0213-4327-6