COMMERCIALWater Source/Geothermal Heat Pump
3-6 Tons
Submittal Data
English Language/IP Units
SD2750AU 09/18
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 2
Versatec Variable Speed Series3-6 Tons 60Hz
Model Nomenclature
Electrical AvailabilityVS ECM
VoltageModel
036 048 060 072
208-230/60/1 • • • •
208-230/60/3 • • • •
460/60/3 • • • •
575/60/3 N/A N/A N/A N/A
8/25/2016Legend:NA = Not Available• = Voltage available in this size
Vintage* – Factory Use
Non-Standard OptionsSS – Standard
Drain Pan Option0 – Composite, No Secondary Connection1 – Composite, Secondary Connection2 – Stainless Steel, No Secondary Connection3 – Stainless Steel, Secondary Connection
Air Coil Option3 – All-Aluminum, Uncoated 4 – All-Aluminum, AlumiSealTM
Filter OptionA – 1" MERV 4B – 2" MERV 13
Cabinet Option0 – Unpainted Cabinet, Filter Rail1 – Painted Cabinet, Filter Rail2 – Unpainted Cabinet, 4-Sided Filter Rack3 – Painted Cabinet, 4-Sided Filter Rack
Electrical OptionN – NoneD – Disconnect
Aurora Advanced Control OptionA – StandardE – AuroraTM DDCF – AuroraTM DDC w/Lon
Water Control OptionN – NoneR – Water Flow RegulatorV – Modulating ValveF – Flow Meter
Rev.:
Vintage* – Factory Use–
Non-Standard OptionsSS – Standard–
Drain Pan Option0 – Composite– , No Secondary Connection1 – Composite– , Secondary Connection2 – Stainless Steel– , No Secondary Connection3 – Stainless Steel– , Secondary Connection
Air Coil Option3 – All-Aluminum– , Uncoated 4 – All-Aluminum– , AlumiSealTM
Filter OptionA – 1– " MERV 4B – 2– " MERV 13
Cabinet Option0 – Unpainted Cabinet– , Filter Rail1 – Painted Cabinet– , Filter Rail2 – Unpainted Cabinet– , 4-Sided Filter Rack3 – Painted Cabinet– , 4-Sided Filter Rack
Electrical OptionN – None–D – Disconnect–
Aurora Advanced Control OptionA – Standard–E – Aurora– TM DDCF – Aurora– TM DDC w/Lon
Water Control OptionN – NoneR – Water Flow RegulatorV – Modulating ValveF – Flow Meter
Rev.:
1-2 3 4-6 7 8 9
Model TypeUV – Versatec Variable
Speed
Cabinet Configuration V – Vertical H – Horizontal
Unit Capacity (MBTUH)036, 048, 060, 072
Discharge ConfigurationT – Top (Vertical)E – End (Horizontal)S – Side (Horizontal)
Return Air ConfigurationL – LeftR – Right
Voltage0 – 208-230/60/13 – 208-230/60/34 – 460/60/3
Refrigeration Option 0 – None 2 – HWG Only w/o Pump 6 – Hot Gas Bypass
Blower Options 1 – Variable Speed ECM Blower
Water Coil Option C – Copper, Uninsulated D – Copper, Insulated N – CuproNickel, Uninsulated P – CuproNickel, Insulated
Sound Kit Option A – None B – Sound Kit
10 11 12 14UV V 036 T L 0 0 1 C A N
13A15
N16
peersatepeed
nfigurcalontal
city (M8, 060
Conf(Vert(Hori
e (Hor
Conf
ht
6060
ti
wpa
ec
ra
M0,
figticizriz
fig
117
A18
319
020
SS21-22
*23
VVVVVV
ed
nnsulatedlated, UninsulatedInsulated
0/0/
o
w/oas
c V
ti
MB0
gucazozo
gu
d ECM Blower
13
n
o Pumpss
Var
on
BTU072
uraal)ontaont
ura
r
UH)2
ation
al)al)
ation
riableee
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 3
Versatec Variable Speed Series3-6 Tons 60Hz
AHRI DataVS ECM MotorsAHRI/ASHRAE/ISO 13256-1English (IP) Units
Flow Rate
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
ModelCapacity
ModulationCooling
EWT 86°FHeating
EWT 68°FCooling
EWT 59°FHeating
EWT 50°F
Cooling Brine Full Load 77°F Part Load 68°F
Heating Brine Full Load 32°F Part Load 41°F
gpm cfm Capacity
Btuh EER
Btuh/W Capacity
Btuh COP
Capacity Btuh
EER Btuh/W
Capacity Btuh
COP Capacity
Btuh EER
Btuh/W Capacity
Btuh COP
036Full 9 1300 37,500 17.8 46,000 5.4 43,000 28.0 37,000 4.4 39,000 21.0 29,000 3.8
Part 7 700 9,500 21.0 11,000 7.0 11,000 48.0 8,000 5.5 10,500 36.0 7,000 4.4
048Full 12 1600 47,500 16.6 60,000 5.4 53,000 26.0 46,000 4.7 48,000 20.0 38,000 3.8
Part 8 850 13,000 25.0 15,000 7.8 15,000 50.0 12,000 5.5 14,000 41.0 10,000 4.9
060Full 17 1800 60,000 15.4 73,000 4.8 63,000 24.0 57,000 4.2 62,000 17.8 45,000 3.7
Part 10 1200 16,000 21.0 17,000 7.8 18,000 45.0 14,000 5.3 18,000 36.0 11,000 4.4
072Full 20 2000 70,000 14.0 90,000 4.6 78,000 21.0 72,000 4.0 71,500 16.4 58,000 3.4
Part 12 1400 19,500 20.4 23,000 7.4 24,000 40.0 18,000 5.4 22,000 34.0 15,000 4.8
8/25/16Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperatureHeating capacities based upon 68°F DB, 59°F WB entering air temperatureAll ratings based upon 208V operation
All UV Series product is safety listed under UL1995 thru ETL and performance listed with AHRI in accordance with standard 13256-1.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 4
Versatec Variable Speed Series3-6 Tons 60Hz
Vertical Dimensional Data
1
28
ACCESSPANEL
AIR COIL
AIR
CO
IL S
IDE
AIR C
OIL SID
E
AIR COIL
5
POWER SUPPLY1" (25.4 mm) KNOCKOUT
LOW VOLTAGE1/2" (12.7 mm)
KNOCKOUT
CONDENSATE 3/4"PVC GLUE SOCKET
P
Q
B
RN
A
FRONT FRONT
C
D
EH
1.62
W
1.62
D
EH
C
1.62
1.62
L LK
J
Q
P B
S N
M M
A
AIR COIL
5
CONDENSATE 3/4"PVC GLUE SOCKET
1
2
6
8
7
8
78
6
STANDARD FILTER BRACKETS FOROPEN RETURN APPLICATIONS
DELUXE FILTER BRACKET ACCESSORYFOR DUCTABLE RETURN APPLICATIONS
KLL
J
2' (61 cm)Service Access Left Return
(Right Return opposite side)
2' (61 cm)Service Access
Field InstalledDuct Flange
ACCESSPANEL
ACCESSPANEL
ACCESSPANEL
TU
V
ACCESSPANEL
ACCESSPANEL
ACCESSPANEL
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 5
Versatec Variable Speed Series3-6 Tons 60Hz
Vertical Dimensional Data cont.
LL
1.8 in.[4.6 cm]
AlternativePowerLocation
Disconnect Located on thisSide for a Right Return
DisconnectLocation
PowerSupply
Vertical Shown inLeft Return Configuration
Vertical Models LL
036 15.3 [38.9]
048 14.3 [36.3]
060 14.3 [36.3]
072 14.3 [36.3]
Dimensions in inches [cm] 08/25/16
Vertical DisconnectWhen using disconnect, do not use dimension L from the standard vertical dimensional data. Use dimension LL from the vertical disconnect dimensional data.
6 7 8
1 2 3 4 5 J K Lusing delux e filter rack (±0.10 in)
A B C D E F G H Loop Knockout 1/2" cond 1/2" cond 1" cond M N P Q R S T U V W
Width Depth Height* In OutHWG
InHWG Out
Cond- ensate
Water FPT HWG Prov isions
Low Voltage
Low Voltage
Power Supply
Filter Rack
Supply Width
Supply Depth
Return Depth
Return Height
038in. 25.5 31.2 44.2 2.6 7.6 1.4 4.4 10.8 1" 0.875 10.1 6.1 8.1 2.2 18.0 18.0 6.6 4.6 6.3 1.6 28.1 26.1 2.0
cm. 64.8 79.2 112.3 6.6 19.3 3.6 11.2 27.4 25.4 mm 22.2 mm 25.7 15.5 20.6 5.6 45.7 45.7 16.8 11.7 16.0 4.1 71.4 66.3 5.1
049in. 25.5 31.2 48.2 2.6 7.6 1.4 4.4 10.8 1" 0.875 10.1 6.1 8.1 2.2 18.0 18.0 6.6 4.6 6.3 1.6 28.1 30.0 2.0
cm. 64.8 79.2 122.4 6.6 19.3 3.6 11.2 27.4 25.4 mm 22.2 mm 25.7 15.5 20.6 5.6 45.7 45.7 16.8 11.7 16.0 4.1 71.4 76.2 5.1
064-072in. 25.5 31.2 52.2 2.6 7.6 1.4 4.4 10.8 1" 0.875 10.1 6.1 8.1 2.2 18.0 18.0 6.6 5.0 6.4 1.6 28.1 34.0 2.0
cm. 64.8 79.2 132.6 6.6 19.3 3.6 11.2 27.4 25.4 mm 22.2 mm 25.7 15.5 20.6 5.6 45.7 45.7 16.8 12.7 16.3 4.1 71.4 86.4 5.1
Vertical
Models
Overall CabinetWater Connections
Electrical KnockoutsDischarge Connection **Return Connection
duct flange installed (±0.10 in)
036
048
060-072
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 6
Versatec Variable Speed Series3-6 Tons 60Hz
Horizontal Dimensional Data
BB
C C
L
M
NP
L
M
PN
V W
U
A
L
M
PN
C
L
MC
A
P N
D
EJ
1.7 1.7
H
2.12.1
H
LR DIVIDER LINE
RR DIVIDERLINE
COMPRESSOR SECTION
AIR HANDLERSECTION
UNIT HANGER DETAIL
RIGHT RETURN END DISCHARGE LEFT RETURN
END DISCHARGE
END DISCHARGE END DISCHARGE
SIDE DISCHARGE SIDE DISCHARGE
RIGHT RETURN LEFT RETURN
FRONTFRONT
CMP CMP
AP AP
CONDENSATE"X" PVC SIZE CONDENSATE
"X" PVC SIZE
RR FRONT VIEW
BLOWEROUTLET
BLOWEROUTLET
RIGHT RETURN SIDE DISCHARGE LEFT RETURN SIDE DISCHARGE
RIGHT RETURN SIDE VIEW LEFT RETURN SIDE VIEW
FILTER RACK CONNECTIONFILTER RACK CONNECTION
CP CPFRONTFRONT
AIR COIL AIR COIL
LR FRONT VIEW
D
EK
J
K
1.7 1.7
J
K J
K
CP
CP
1.5 1.5
BLOWEROUTLET
BLOWEROUTLET
FRONT FRONT
CMP
AP
CMP
AP
AP
AP
AIR
CO
IL S
IDE
AIR C
OIL SID
E
1/2" KNOCKOUT
1/2" KNOCKOUT
1" KNOCKOUT
1" KNOCKOUT
1" KNOCKOUT
1" KNOCKOUT
1/2" KNOCKOUT
1/2" KNOCKOUT
SQ S Q
T T
R
BP
BP
FILT
ER R
ACKFILTER
RAC
K
2.3
STANDARD FILTER CHANNEL
STANDARD FILTER CHANNEL
RR FILTER PLACEMENT
LR FILTER PLACEMENT
DELUXE FILTER RACK OPTION SHOWN DELUXE FILTER RACK OPTION SHOWN
A
2.3
DELUXE FILTERRACK OPTION
(SHOWN)
R
L
MC
A
P N
2.1
H
LEFT RETURN END DISCHARGE
BLOWEROUTLET
AIR C
OIL SID
E
FILTER R
ACK
2.3
DELUXE FILTER RACK OPTION SHOWN
A
L
M
PN
C
H
2.1
RIGHT RETURN END DISCHARGE
BLOWEROUTLET
AIR
CO
IL S
IDE
FILT
ER R
ACK
DELUXE FILTER RACK OPTION SHOWN
2.3
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 7
Versatec Variable Speed Series3-6 Tons 60Hz
Horizontal Dimensional Data cont.
2.1 in.[5.3 cm]
KK
Disconnect Locatedon this Side for a
Left Return
DisconnectLocation
Power Supply
Horizontal Shown inRight Return Configuration
Horizontal Models KK
036 10.2 [25.9]
048-72 11.2 [28.4]
Dimensions in inches [cm] 08/25/16
Horizontal DisconnectWhen using disconnect, do not use dimension K from the standard horizontal dimensional data. Use dimension KK from the horizontal disconnect dimensional data.
Overall CabinetWater Connections
1 2 3 J K
HorizontalModels
A B C D E H Loop 1/2" cond 1" cond L M N P Q R S T
Width Depth Height* In OutCond- ensate Water FPT
Low Voltage
Power Supply
Supply
WidthSupply Depth
Return Depth
Return Height
038in. 25.5 57.0 21.2 1.8 6.8 0.8 1" 9.2 9.1 4.9 13.6 13.2 4.6 40.4 18.6 2.3 1.4
cm. 64.8 144.8 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1 12.4 34.5 33.5 11.7 102.6 47.2 5.8 3.6
049in. 25.5 63.0 21.2 1.8 6.8 0.8 1" 9.2 9.1 4.9 13.6 13.2 4.6 45.4 18.6 2.3 1.4
cm. 64.8 160.0 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1 12.4 34.5 33.5 11.7 115.3 47.2 5.8 3.6
064in. 25.5 70.0 21.2 1.8 6.8 0.8 1" 9.2 9.1 4.9 13.6 13.2 4.6 45.4 18.6 2.3 1.4
cm. 64.8 177.8 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1 12.4 34.5 33.5 11.7 115.3 47.2 5.8 3.6
072in. 25.5 75.0 21.2 1.8 6.8 0.8 1" 9.2 9.1 4.9 13.6 13.2 4.6 45.4 18.6 2.3 1.4
cm. 64.8 190.5 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1 12.4 34.5 33.5 11.7 115.3 47.2 5.8 3.6
Electrical Knockouts Discharge Connectionduct flange installed (±0.10 in)
Return Connectionusing delux e filter rack option (±0.10 in)
036
048
060
072
X
3/4"
1.9
3/4"
1.9
3/4"
1.9
3/4"
1.9
PVC Size
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 8
Versatec Variable Speed Series3-6 Tons 60Hz
Hanger Bracket Locations
Hanger Dimensions
ModelHanger Kit
Part NumberUnit Hanger Dimensions
A B C H
036in.
99S500A0453.8 28.1 24.4 n/a
cm 136.7 71.4 62.0 n/a
048in.
99S500A0461.8 28.1 24.4 n/a
cm 157.0 71.4 62.0 n/a
060in.
99S500A0368.8 28.1 24.4 36.0
cm 174.8 71.4 62.0 91.4
072in.
99S500A0368.8 28.1 24.4 42.0
cm 174.8 71.4 62.0 106.7
8/25/16
Weight Distribution
ModelVertical
Shipping Weight
HorizontalShippingWeight
Horizontal Weight Distribution
Front Back
D E F G
036lb. 400 415 155 105 80 65
kg [181] [188] [70] [48] [36] [30]
048lb. 410 420 165 110 85 70
kg [186] [191] [75] [50] [39] [32]
060lb. 450 460 140 120 100 85
kg [204] [209] [64] [54] [45] [39]
072lb. 485 495 155 130 105 90
kg [220] [225] [70] [59] [48] [41]
8/25/16
BC
A
H
E
D
G
F
Left
D
E
F
G
Right
Vibration Isolator
Washer
Hex Nuts(not supplied)
Bolt andLockwasher
3/8”Threaded Rod(not supplied)
CompressorSection
CompressorSection
Air HandlerSection
Air HandlerSection
H
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 9
Versatec Variable Speed Series3-6 Tons 60Hz
Physical Data
Model 036 048 060 072Compressor (1 each) Variable Speed Scroll
Factory Charge R410A, oz [kg] Vertical 82 [2.32] 96 [2.72] 98 [2.78] 132 [3.74]
Factory Charge R410A, oz [kg] Horizontal 82 [2.32] 96 [2.72] 126 [3.57] 132 [3.74]
ECM Blower Motor & BlowerBlower Motor Type/Speeds VS ECM Variable Speed
Blower Motor- hp [W] VS ECM 1/2 [373] 1 [746] 1 [746] 1 [746]
Blower Wheel Size (Dia x W), in. [mm] VS ECM 11 x 10 [279 x 254]
11 x 10 [279 x 254]
11 x 10 [279 x 254]
11 x 10 [279 x 254]
Coax and Water PipingWater Connections Size - FPT - in [mm] 1" [25.4] 1" [25.4] 1" [25.4] 1" [25.4]
HWG Connection Size - Female Sweat I.D. - in [mm] (Vertical Only) 1/2" [12.7] 1/2" [12.7] 1/2" [12.7] 1/2" [12.7]
Coax & Piping Water Volume - gal [l] 1.3 [4.9] 1.6 [6.1] 1.6 [6.1] 2.3 [8.7]
VerticalAir Coil Dimensions (H x W), in. [mm] 28 x 25
[711 x 635]32 x 25
[813 x 635]36 x 25
[914 x 635]36 x 25
[914 x 635]
Air Coil Total Face Area, ft2 [m2] 4.9 [0.451] 5.6 [0.520] 6.3 [0.585] 6.3 [0.585]
Air Coil Tube Size, in [mm] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5]
Air Coil Number of rows 3 3 4 4
Filter Standard - 1" [25mm] Pleated MERV 4 Throwaway, in [mm] 28 x 30 [711 x 762]
32 x 30 [813 x 762]
36 x 30 [914 x 762]
30 x 36 [762 x 914]
Filter Standard - 2" [51mm] Pleated MERV 13 Throwaway, in [mm] 28 x 30 [711 x 762]
32 x 30 [813 x 762]
30 x 36 [762 x 914]
30 x 36 [762 x 914]
HorizontalAir Coil Dimensions (H x W), in. [mm] 20 x 35
[508 x 889]20 x 40
[508 x 1016]20 x 45
[508 x 1143]20 x 45
[508 x 1143]
Air Coil Total Face Area, ft2 [m2] 4.9 [0.451] 5.6 [0.520] 6.3 [0.585] 6.3 [0.585]
Air Coil Tube Size, in [mm] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5]
Air Coil Number of rows 3 3 4 4
Filter Standard - 1" [25mm] Pleated MERV 4 Throwaway, in [mm] 2 - 18 x 20 [457 x 508]
1 - 20 x 22 [508 x 559] 1 - 20 x 20 [508 x 508]
1 - 20 x 25 [508 x 635] 1 - 20 x 22 [508 x 559]
1 - 20 x 25 [508 x 635] 1 - 20 x 22 [508 x 559]
Filter Standard - 2" [51mm] Pleated MERV 13 Throwaway, in [mm] 1 - 20 x 37 [508 x 940]
1 - 20 x 20 [508 x 508] 1 - 20 x 22 [508 x 559]
1 - 20 x 25 [508 x 635] 1 - 20 x 22 [508 x 559]
1 - 20 x 25 [508 x 635] 1 - 20 x 22 [508 x 559]
8/25/16
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 10
Versatec Variable Speed Series3-6 Tons 60Hz
Electrical Data
ModelRated
VoltageVoltageMin/Max
Compressor BlowerMotorFLA
TotalUnitFLA
MinCircAmp
MaxFuse/
HACR BreakerMCC RLA LRA*
036208-230/60/1 187/253 26.0 16.7 60.0 4.3 21.0 25.2 40
208-230/60/3 187/253 18.0 11.5 60.0 4.3 15.8 18.7 30
460/60/3 414/506 12.0 7.7 25.0 4.3 12.0 13.9 20
048208-230/60/1 187/253 26.0 16.7 60.0 7.7 24.4 28.6 60
208-230/60/3 187/253 18.0 11.5 60.0 6.7 18.2 21.1 30
460/60/3 414/506 12.0 7.7 25.0 6.0 13.7 15.6 20
060208-230/60/1 187/253 38.0 24.4 60.0 7.7 32.1 38.2 60
208-230/60/3 187/253 24.0 15.4 60.0 6.7 22.1 26.0 40
460/60/3 414/506 15.0 9.6 25.0 6.0 15.6 18.0 25
072208-230/60/1 187/253 38.0 24.4 60.0 7.7 32.1 38.2 60
208-230/60/3 187/253 24.0 15.4 60.0 6.7 22.1 26.0 40
460/60/3 414/506 15.0 9.6 25.0 6.0 15.6 18.0 25
8/25/16HACR circuit breaker in USA only* - Based on AC input current protection to compressor drive.
Blower Performance Data
VS ECM Blower Performance
*VS Compressor speed is given for the factory default cfm settings. When the cfm default settings are changed it will change the relationship to the compressor speed that is shown in the table.
Factory settings are at recommended L, H, and Aux positions “G” may be located anywhere within the airfl ow table“L” setting should be located < or = to “H” setting“H” setting MUST be located within the shaded cfm range“Aux” setting MUST be equal to or greater than “H” setting“Aux” setting MUST be equal to or greater than the minimum allowable cfm for the auxilliary heater kit (see auxiliary heat ratings)CFM is controlled within 5% up to the maximum ESPMax ESP includes allowance for wet coil and 1” MERV 4
Model Max ESPAir Flow Speed Settings
1 2 3 4 5 6 7 8 9 10 11 12
036 0.50
285 380 525 675 815 980 1100 1220 1330 1440 1540 1575
G L H Aux
*1-2 *3-4 *5-6 *7-8 *9-10 *11-12
048 0.75
475 620 730 850 1020 1140 1270 1400 1520 1650 1790 1925
G L H Aux
*1-2 *3-4 *5-6 *7-8 *9-10 *11-12
060 0.75
400 600 830 1050 1230 1400 1560 1700 1870 2010 2140 2265
G L H Aux
*1-2 *3-4 *5-6 *7-8 *9-10 *11-12
072 0.75
400 600 830 1050 1230 1400 1560 1700 1870 2010 2140 2265
G L H-Aux
*1-2 *3-4 *5-6 *7-8 *9-10 *11-12
1/25/17
Versatec Variable Speed Series
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 11
Versatec Variable Speed Series3-6 Tons 60Hz
Blower Performance Data cont.
ECM Speed Info
1▶ 2 ◀ G 3 4 5 6 7 8 9 10 11 12
Option ◀▶ Enter ◙
ECM Speed Info
1 2 G▶ 3 ◀ Lo 4 5 6 7 8 9 10 11 12
Option ◀▶ Enter ◙
ECM Speed Info
1 2 G 3 Lo 4 5▶ 6 ◀ Hi 7 8 9 10 11 12
Option ◀▶ Enter ◙
ECM Speed Info
1 2 G 3 Lo 4 5 6 Hi 7 8 9▶10 ◀ Aux 11 12
Option ◀▶ Enter ◙
ECM Speed Info
Blower Only Speed 3Lo Compressor 6Hi Compressor 9Aux Heat 10
Want To Change?
YesOption ◀▶
NoEnter ◙
Cooling Airfl ow Setup
--- ECM Only ---The airfl ow will be
adjusted by the chosenamount in cooling mode.
Adjustment:-15%
Want To Change?
YesOption ◀▶
NoEnter ◙
Cooling Airfl ow Setup
--- ECM Only ---The airfl ow will be
adjusted by the chosenamount in cooling mode.
Adjustment:-15%
Change ▼▲ Enter ◙
Setting Blower Speed - Variable Speed ECM The ABC board’s Yellow Confi g LED will fl ash the current ECM blower speed selections for G, low, and high continuously with a short pause in between. The speeds can also be confi rmed with the AID Tool under the Setup/ECM Setup screen. The Aux will not be fl ashed but can be viewed in the AID Tool. The ECM blower motor speeds can be fi eld adjusted with or without using an AID Tool.
Variable speed ECM Setup without an AID ToolThe blower speeds for G only, Low (Y1), and High (Y2/Aux) can be adjusted directly at the Aurora ABC board which utilizes the push button (SW1) on the ABC board. This procedure is outlined in the ECM Confi guration Mode portion of the Aurora ‘Base’ Control System section. The Aux cannot be set manually without an AID Tool.
Variable speed ECM Setup with an AID ToolA much easier method utilizes the AID Tool to change the airfl ow using the procedure below. First navigate to the Setup screen and then select ECM Setup. This screen displays the current ECM settings. It allows the technician to enter the setup screens to change the ECM settings.
Change the highlighted item using the ◄ and ► buttons and then press the ◙ button to select the item.
Selecting YES will enter ECM speed setup, while selecting NO will return to the previous screen.
ECM Speed Setup - These screens allow the technician to select the G, low, high, and auxiliary heat blower speed for the ECM blower motor. Change the highlighted item using the ▲ and ▼ buttons. Press the ◙ button to select the speed.
After the auxiliary heat speed setting is selected the AID Tool will automatically transfer back to the ECM Setup screen.
Cooling Airfl ow Setup - These screens allow the technician to select -15%, -10%, -5%, None or +5% change from the heating airfl ow. Change the adjustment percentage using the ▲ and ▼ buttons. Press the ◙ button to save the change.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 12
Versatec Variable Speed Series3-6 Tons 60Hz
Defi nitions
ABBREVIATIONS AND DEFINITIONS:
cfm = airflow, cubic feet/minuteEWT = entering water temperature, Fahrenheitgpm = water flow in gallons/minuteWPD = water pressure drop, psi and feet of waterEAT = entering air temperature, Fahrenheit (dry bulb/wet bulb)HC = air heating capacity, MBtu/hTC = total cooling capacity, MBtu/hSC = sensible cooling capacity, MBtu/hkW = total power unit input, kilowattsHR = total heat of rejection, MBtu/h
HE = total heat of extraction, MBtu/hHWC = hot water generator capacity, MBtu/hEER = Energy Efficient Ratio = BTU output/Watt inputCOP = Coefficient of Performance = Btu output/Btu inputLWT = leaving water temperature, °FLAT = leaving air temperature, °FTH = total heating capacity, MBtu/hLC = latent cooling capacity, MBtu/hS/T = sensible to total cooling ratio
Operating Limits
Operating LimitsCooling Heating
(°F) (°C) (°F) (°C)
Air Limits
Min. Ambient Air 45 7.2 45 7.2
Rated Ambient Air 80 26.7 70 21.1
Max. Ambient Air 100 37.8 85 29.4
Min. Entering Air 50 10.0 40 4.4
Rated Entering Air db/wb 80.6/66.2 27/19 68 20.0
Max. Entering Air db/wb 110/83 43/28.3 80 26.7
Water Limits
Min. Entering Water 30 -1.1 20 -6.7
Normal Entering Water 50-110 10-43.3 30-70 -1.1
Max. Entering Water 120 48.9 90 32.2
NOTE: Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependant upon three primary factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 13
Versatec Variable Speed Series3-6 Tons 60Hz
Correction Factor Tables
Cooling Capacity Corrections
EnteringAir WB ºF
TotalClg Cap
Sensible Cooling Capacity Multipliers - Entering DB ºF PowerInput
Heat ofRejection60 65 70 75 80 80.6 85 90 95 100
55 0.898 0.723 0.866 1.048 1.185 * * * * * * 0.985 0.913
60 0.912 0.632 0.880 1.078 1.244 1.260 * * * * 0.994 0.927
65 0.967 0.694 0.881 1.079 1.085 1.270 * * * 0.997 0.972
66.2 0.983 0.655 0.842 1.040 1.060 1.232 * * * 0.999 0.986
67 1.000 0.616 0.806 1.000 1.023 1.193 1.330 * * 1.000 1.000
70 1.053 0.693 0.879 0.900 1.075 1.250 1.404 * 1.003 1.044
75 1.168 0.687 0.715 0.875 1.040 1.261 1.476 1.007 1.141
11/10/09NOTE: * Sensible capacity equals total capacity at conditions shown.
Airfl ow CorrectionsAirfl ow Cooling Heating
cfm Per Ton of Clg
% of Nominal Total Cap Sens Cap Power Heat of Rej Htg Cap Power Heat of Ext
240 60 0.922 0.786 0.910 0.920 0.943 1.150 0.893
275 69 0.944 0.827 0.924 0.940 0.958 1.105 0.922
300 75 0.959 0.860 0.937 0.955 0.968 1.078 0.942
325 81 0.971 0.894 0.950 0.967 0.977 1.053 0.959
350 88 0.982 0.929 0.964 0.978 0.985 1.031 0.973
375 94 0.992 0.965 0.982 0.990 0.993 1.014 0.988
400 100 1.000 1.000 1.000 1.000 1.000 1.000 1.000
425 106 1.007 1.034 1.020 1.010 1.007 0.990 1.011
450 113 1.012 1.065 1.042 1.018 1.013 0.983 1.020
475 119 1.017 1.093 1.066 1.026 1.018 0.980 1.028
500 125 1.019 1.117 1.092 1.033 1.023 0.978 1.034
520 130 1.020 1.132 1.113 1.038 1.026 0.975 1.038
11/10/09
Heating CorrectionsEnt Air DB °F Htg Cap Power Heat of Ext
45 1.062 0.739 1.158
50 1.050 0.790 1.130
55 1.037 0.842 1.096
60 1.025 0.893 1.064
65 1.012 0.945 1.030
68 1.005 0.976 1.012
70 1.000 1.000 1.000
75 0.987 1.048 0.970
80 0.975 1.099 0.930
11/10/09
Operating LimitsCooling Heating
(°F) (°C) (°F) (°C)
Air Limits
Min. Ambient Air 45 7.2 45 7.2
Rated Ambient Air 80 26.7 70 21.1
Max. Ambient Air 100 37.8 85 29.4
Min. Entering Air 50 10.0 40 4.4
Rated Entering Air db/wb 80.6/66.2 27/19 68 20.0
Max. Entering Air db/wb 110/83 43/28.3 80 26.7
Water Limits
Min. Entering Water 30 -1.1 20 -6.7
Normal Entering Water 50-110 10-43.3 30-70 -1.1
Max. Entering Water 120 48.9 90 32.2
NOTE: Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependent upon three primary factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 14
Versatec Variable Speed Series3-6 Tons 60Hz
Antifreeze Corrections
Antifreeze TypeAntifreeze% by wt
Cooling Capacity
Heating Capacity
Pressure Drop
EWT - degF [DegC] 90 [32.2] 30 [-1.1] 30 [-1.1]
Water 0 1.000 1.000 1.000
10 0.991 0.973 1.075
20 0.979 0.943 1.163
Ethylene Glycol 30 0.965 0.917 1.225
40 0.955 0.890 1.324
50 0.943 0.865 1.419
10 0.981 0.958 1.130
20 0.969 0.913 1.270
Propylene Glycol 30 0.950 0.854 1.433
40 0.937 0.813 1.614
50 0.922 0.770 1.816
10 0.991 0.927 1.242
20 0.972 0.887 1.343
Ethanol 30 0.947 0.856 1.383
40 0.930 0.815 1.523
50 0.911 0.779 1.639
10 0.986 0.957 1.127
20 0.970 0.924 1.197
Methanol 30 0.951 0.895 1.235
40 0.936 0.863 1.323
50 0.920 0.833 1.399
Warning: Gray area represents antifreeze concentrations greater than 35% by weight and should be avoided due to the extreme performance penalty they represent.
Catalog performance can be corrected for antifreeze use. Please use the following table and note the example given.
Antifreeze Correction ExampleAntifreeze solution is Propylene Glycol 20% by weight. Determine the corrected heating and cooling performance at 30°F and 90°F respectively as well as pressure drop at 30°F for a Versatec Ultra Series US*024-PSC.
The corrected cooling capacity at 90°F would be: 24,500 Btu/h x 0.969 = 23,740 Btu/h
The corrected heating capacity at 30°F would be: 19,000 Btu/h x 0.913 = 17,347 Btu/h
The corrected pressure drop at 30°F and 6 gpm would be: 10.5 ft. hd x 1.270 = 13.34 ft. hd.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 15
Versatec Variable Speed Series3-6 Tons 60Hz
Pressure Drop
Model gpmPressure Drop (psi)
30°F 50°F 70°F 90°F 110°F
036
5.0 1.5 1.2 0.9 0.5 0.2
7.0 2.2 1.9 1.6 1.2 0.9
9.0 3.0 2.7 2.3 2.0 1.7
11.0 4.9 4.6 4.3 4.0 3.7
048
6.0 1.6 1.3 1.0 0.6 0.3
9.0 2.4 2.1 1.7 1.4 1.1
12.0 3.4 3.1 2.7 2.4 2.1
15.0 5.7 5.3 5.0 4.7 4.3
060
8.0 1.8 1.6 1.3 1.1 0.8
12.0 3.8 3.3 2.9 2.4 1.9
16.0 6.5 6.0 5.6 5.1 4.6
20.0 9.7 9.1 8.5 8.0 7.4
072
12.0 3.2 3.0 2.8 2.6 2.4
15.0 4.5 4.1 3.8 3.4 3.0
18.0 6.0 5.6 5.3 4.9 4.5
21.0 7.8 7.4 7.1 6.7 6.3
8/25/16
Valve gpm CvPressure
Drop (psi)
1"
6.0 16.1 0.14
9.0 16.8 0.29
12.0 17.4 0.47
15.0 18.1 0.69
1"
6.0 16.1 0.14
9.0 16.8 0.29
12.0 17.4 0.47
15.0 18.1 0.69
1"
9.0 16.8 0.29
12.0 17.4 0.47
16.0 18.3 0.76
20.0 19.2 1.09
1"
12.0 17.4 0.47
15.0 18.1 0.69
18.0 18.7 0.92
24.0 20.1 1.43
8/25/16
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 16
Versatec Variable Speed Series3-6 Tons 60Hz
036 - Min Load - Performance Data
EWT °F
Flow gpm
WPD HEATING - EAT 70°F COOLING - EAT 80/67°F
psi FT HC MBtu/h
Power kW
HE MBtu/h
LAT °F COP HWC
MBtu/hTC
MBtu/hSC
MBtu/hS/T
RatioPower
kWHR
MBtu/h EER HWC MBtu/h
20
3.0 0.51 1.17Operation not recommended
Operation not recommended5.0 1.69 3.90
7.0 2.40 5.54 5.0 0.48 3.4 76.6 3.05 0.9
30
3.0 0.34 0.79 Operation not recommended Operation not recommended
5.0 1.52 3.51 5.9 0.51 4.1 77.7 3.39 0.9 11.6 10.1 0.87 0.22 12.4 53.6 ---
7.0 2.23 5.16 5.9 0.51 4.2 77.9 3.40 1.0 11.8 10.2 0.87 0.21 12.5 57.1 ---
40
3.0 0.30 0.69 Operation not recommended Operation not recommended
5.0 1.35 3.13 7.2 0.52 5.4 79.5 4.05 1.0 11.4 10.0 0.87 0.25 12.3 45.0 ---
7.0 2.07 4.77 7.3 0.53 5.5 79.7 4.07 1.1 11.5 10.1 0.87 0.24 12.4 47.9 ---
50
3.0 0.27 0.62 8.4 0.53 6.6 81.2 4.68 1.1 11.1 9.7 0.87 0.32 12.2 35.3 0.7
5.0 1.19 2.74 8.6 0.54 6.7 81.3 4.69 1.2 11.2 9.9 0.88 0.29 12.2 38.5 0.6
7.0 1.90 4.39 8.7 0.54 6.8 81.5 4.70 1.2 11.3 10.0 0.88 0.28 12.3 41.1 0.6
60
3.0 0.25 0.58 9.7 0.55 7.8 82.9 5.17 1.3 11.3 10.0 0.89 0.36 12.5 31.0 0.8
5.0 1.02 2.35 9.9 0.56 8.0 83.0 5.18 1.3 11.4 10.1 0.89 0.35 12.6 32.9 0.8
7.0 1.73 4.00 10.0 0.57 8.1 83.2 5.20 1.4 11.6 10.3 0.89 0.34 12.7 34.6 0.7
70
3.0 0.21 0.49 11.0 0.57 9.0 84.6 5.62 1.4 10.7 9.6 0.90 0.44 12.2 24.3 1.0
5.0 0.85 1.97 11.2 0.58 9.2 84.8 5.64 1.5 10.8 9.7 0.90 0.42 12.2 25.9 1.0
7.0 1.57 3.62 11.3 0.59 9.3 85.0 5.65 1.5 11.0 9.9 0.90 0.41 12.4 27.3 0.9
80
3.0 0.19 0.44 11.6 0.63 9.5 85.4 5.43 1.6 9.7 8.9 0.91 0.53 11.5 18.3 1.3
5.0 0.69 1.58 11.8 0.64 9.6 85.6 5.44 1.7 9.9 9.0 0.91 0.51 11.6 19.5 1.2
7.0 1.40 3.23 12.0 0.64 9.8 85.9 5.46 1.7 10.1 9.2 0.91 0.49 11.8 20.5 1.1
90
3.0 0.17 0.39 12.3 0.68 9.9 86.2 5.27 1.8 9.1 8.5 0.93 0.57 11.0 16.1 1.6
5.0 0.52 1.20 12.5 0.69 10.1 86.5 5.28 1.9 9.3 8.6 0.93 0.54 11.1 17.2 1.5
7.0 1.23 2.85 12.7 0.70 10.3 86.7 5.30 1.9 9.4 8.8 0.93 0.52 11.2 18.1 1.4
100
3.0 0.14 0.32
Operation not recommended
Operation not recommended
5.0 0.35 0.81 8.6 8.0 0.93 0.59 10.6 14.5 1.8
7.0 1.06 2.46 8.7 8.2 0.94 0.57 10.7 15.3 1.7
110
3.0 0.12 0.28 Operation not recommended
5.0 0.18 0.43 7.9 7.4 0.94 0.64 10.1 12.3 2.1
7.0 0.90 2.07 8.0 7.6 0.94 0.62 10.1 12.9 2.1
120
3.0 0.09 0.21 Operation not recommended
5.0 0.02 0.04 7.7 7.2 0.94 0.71 10.1 10.9 2.6
7.0 0.73 1.69 7.8 7.4 0.95 0.69 10.1 11.4 2.5
8/24/2016
700 CFM
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 17
Versatec Variable Speed Series3-6 Tons 60Hz
036 - Full Load - Performance Data
EWT °F
Flow gpm
WPD HEATING - EAT 70°F COOLING - EAT 80/67°F
psi FT HC MBtu/h
Power kW
HE MBtu/h
LAT °F COP HWC
MBtu/hTC
MBtu/hSC
MBtu/hS/T
RatioPower
kWHR
MBtu/h EER HWC MBtu/h
20
5.0 1.69 3.90Operation not recommended
Operation not recommended7.0 2.40 5.54
9.0 3.17 7.32 26.0 2.25 18.3 86.5 3.39 2.6
30
5.0 1.52 3.51 Operation not recommended Operation not recommended
7.0 2.23 5.16 31.1 2.52 22.5 90.1 3.61 2.8 42.6 30.9 0.73 1.52 47.8 28.0 ---
9.0 3.00 6.93 31.6 2.55 22.9 90.5 3.62 2.9 43.0 31.2 0.73 1.44 47.9 29.9 ---
40
5.0 1.35 3.13 Operation not recommended Operation not recommended
7.0 2.07 4.77 34.8 2.59 26.0 92.8 3.94 3.1 43.8 32.0 0.73 1.62 49.3 27.0 ---
9.0 2.83 6.54 35.4 2.62 26.4 93.2 3.95 3.2 44.2 32.4 0.73 1.54 49.5 28.7 ---
50
5.0 1.19 2.74 38.0 2.62 29.0 95.1 4.25 3.4 44.7 32.5 0.73 1.88 51.1 23.8 2.0
7.0 1.90 4.39 38.6 2.66 29.5 95.5 4.25 3.5 45.0 33.2 0.74 1.73 50.9 26.0 1.9
9.0 2.67 6.16 39.2 2.69 30.0 95.9 4.27 3.6 45.5 33.5 0.74 1.64 51.1 27.7 1.8
60
5.0 1.02 2.35 42.7 2.67 33.6 98.4 4.69 3.8 43.2 31.7 0.73 1.98 50.0 21.8 2.4
7.0 1.73 4.00 43.4 2.71 34.2 98.9 4.70 4.0 43.8 32.2 0.74 1.89 50.2 23.2 2.3
9.0 2.50 5.77 44.1 2.74 34.7 99.4 4.71 4.1 44.6 32.9 0.74 1.83 50.8 24.3 2.2
70
5.0 0.85 1.97 47.5 2.72 38.2 101.8 5.11 4.3 41.8 30.2 0.72 2.14 49.1 19.6 3.0
7.0 1.57 3.62 48.2 2.76 38.8 102.3 5.13 4.4 42.4 30.7 0.72 2.04 49.4 20.8 2.9
9.0 2.33 5.39 48.9 2.79 39.4 102.9 5.14 4.6 43.3 31.3 0.72 1.97 50.0 22.0 2.8
80
5.0 0.69 1.58 47.6 2.75 38.2 101.9 5.06 4.8 39.7 29.9 0.75 2.38 47.9 16.7 3.8
7.0 1.40 3.23 48.3 2.79 38.8 102.4 5.08 5.0 40.3 30.3 0.75 2.27 48.1 17.7 3.6
9.0 2.17 5.00 49.1 2.83 39.4 102.9 5.09 5.1 41.2 31.0 0.75 2.20 48.7 18.7 3.4
90
5.0 0.52 1.20 47.7 2.79 38.2 102.0 5.02 5.4 37.3 29.2 0.78 2.63 46.2 14.2 4.7
7.0 1.23 2.85 48.5 2.83 38.8 102.5 5.03 5.6 37.9 29.7 0.78 2.51 46.4 15.1 4.5
9.0 2.00 4.62 49.2 2.86 39.4 103.0 5.04 5.8 38.6 30.3 0.78 2.43 46.9 15.9 4.3
100
5.0 0.35 0.81
Operation not recommended
Operation not recommended
7.0 1.06 2.46 36.3 29.4 0.81 2.96 46.4 12.3 5.3
9.0 1.83 4.23 36.9 30.0 0.81 2.86 46.6 12.9 5.1
110
5.0 0.18 0.43 Operation not recommended
7.0 0.90 2.07 34.6 29.1 0.84 3.40 46.2 10.2 6.4
9.0 1.66 3.85 35.1 29.7 0.85 3.30 46.4 10.6 6.2
120
5.0 0.02 0.04 Operation not recommended
7.0 0.73 1.69 32.7 28.2 0.86 3.76 45.5 8.7 7.7
9.0 1.50 3.46 33.2 28.8 0.87 3.65 45.6 9.1 7.5
8/24/2016
1300 CFM
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 18
Versatec Variable Speed Series3-6 Tons 60Hz
048 - Min Load - Performance Data
EWT °F
Flow gpm
WPD HEATING - EAT 70°F COOLING - EAT 80/67°F
psi FT HC MBtu/h
Power kW
HE MBtu/h
LAT °F COP HWC
MBtu/hTC
MBtu/hSC
MBtu/hS/T
RatioPower
kWHR
MBtu/h EER HWC MBtu/h
20
4.0 0.75 1.73Operation not recommended
Operation not recommended6.0 1.80 4.15
8.0 2.34 5.41 7.93 0.77 5.31 78.6 3.03 1.6
30
4.0 0.62 1.43 Operation not recommended Operation not recommended
6.0 1.63 3.77 8.26 0.72 5.81 79.0 3.37 1.7 15.05 11.19 0.74 0.34 16.2 43.9 ---
8.0 2.18 5.02 8.38 0.73 5.90 79.1 3.38 1.8 15.20 11.30 0.74 0.33 16.3 46.8 ---
40
4.0 0.55 1.27 Operation not recommended Operation not recommended
6.0 1.46 3.38 10.35 0.70 7.95 81.3 4.33 1.9 14.79 11.10 0.75 0.36 16.0 40.9 ---
8.0 2.01 4.64 10.50 0.71 8.08 81.4 4.34 1.9 14.94 11.21 0.75 0.34 16.1 43.6 ---
50
4.0 0.51 1.18 12.25 0.67 9.94 83.3 5.32 2.1 14.43 10.79 0.75 0.41 15.8 35.0 1.1
6.0 1.30 3.00 12.44 0.68 10.10 83.5 5.33 2.1 14.53 11.01 0.76 0.38 15.8 38.2 1.0
8.0 1.84 4.25 12.63 0.69 10.26 83.8 5.35 2.2 14.68 11.12 0.76 0.36 15.9 40.7 1.0
60
4.0 0.47 1.09 13.47 0.66 11.23 84.7 6.00 2.3 13.77 10.43 0.76 0.42 15.2 32.5 1.3
6.0 1.13 2.61 13.68 0.67 11.41 84.9 6.01 2.4 13.96 10.59 0.76 0.40 15.3 34.5 1.2
8.0 1.68 3.87 13.89 0.68 11.59 85.1 6.03 2.5 14.20 10.81 0.76 0.39 15.5 36.3 1.2
70
4.0 0.45 1.04 15.34 0.65 13.14 86.7 6.96 2.6 13.42 10.22 0.76 0.53 15.2 25.5 1.6
6.0 0.96 2.23 15.58 0.65 13.35 87.0 6.97 2.7 13.63 10.38 0.76 0.50 15.3 27.1 1.5
8.0 1.51 3.49 15.82 0.66 13.56 87.2 6.99 2.8 13.91 10.59 0.76 0.49 15.6 28.6 1.5
80
4.0 0.43 0.99 16.81 0.62 14.70 88.3 7.99 2.9 13.06 9.96 0.76 0.62 15.2 21.0 2.1
6.0 0.80 1.84 17.07 0.62 14.94 88.6 8.01 3.0 13.26 10.11 0.76 0.59 15.3 22.3 2.0
8.0 1.34 3.10 17.33 0.63 15.17 88.9 8.03 3.1 13.53 10.32 0.76 0.58 15.5 23.5 1.9
90
4.0 0.41 0.95 18.27 0.59 16.27 89.9 9.14 3.3 12.67 9.79 0.77 0.73 15.2 17.3 2.6
6.0 0.63 1.46 18.55 0.59 16.52 90.2 9.16 3.4 12.87 9.95 0.77 0.70 15.3 18.4 2.5
8.0 1.18 2.72 18.83 0.60 16.78 90.5 9.18 3.5 13.13 10.15 0.77 0.68 15.4 19.4 2.3
100
4.0 0.38 0.88
Operation not recommended
Operation not recommended
6.0 0.46 1.07 11.52 9.32 0.81 0.86 14.4 13.4 3.1
8.0 1.01 2.33 11.69 9.52 0.81 0.83 14.5 14.1 2.9
110
4.0 0.37 0.85 Operation not recommended
6.0 0.30 0.69 10.10 8.70 0.86 1.01 13.6 10.0 3.7
8.0 0.84 1.95 10.25 8.88 0.87 0.99 13.6 10.4 3.6
120
4.0 0.35 0.81 Operation not recommended
6.0 0.13 0.30 8.88 8.16 0.92 1.23 13.1 7.2 4.5
8.0 0.68 1.56 9.02 8.33 0.92 1.20 13.1 7.5 4.3
8/24/2016
850 CFM
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 19
Versatec Variable Speed Series3-6 Tons 60Hz
048 - Full Load - Performance Data
EWT °F
Flow gpm
WPD HEATING - EAT 70°F COOLING - EAT 80/67°F
psi FT HC MBtu/h
Power kW
HE MBtu/h
LAT °F COP HWC
MBtu/hTC
MBtu/hSC
MBtu/hS/T
RatioPower
kWHR
MBtu/h EER HWC MBtu/h
20
6.0 1.80 4.15Operation not recommended
Operation not recommended9.0 2.57 5.93
12.0 3.57 8.24 35.0 2.99 24.8 88.3 3.43 4.8
30
6.0 1.63 3.77 Operation not recommended Operation not recommended
9.0 2.40 5.54 37.8 3.10 27.2 89.9 3.57 5.2 58.7 41.0 0.70 1.56 64.0 37.6 ---
12.0 3.40 7.85 39.0 3.14 28.3 90.6 3.64 5.3 59.3 41.4 0.70 1.48 64.3 40.1 ---
40
6.0 1.46 3.38 Operation not recommended Operation not recommended
9.0 2.23 5.16 44.4 3.30 33.2 93.7 3.95 5.7 57.3 40.1 0.70 1.87 63.7 30.6 ---
12.0 3.23 7.47 45.8 3.34 34.4 94.5 4.02 5.8 57.9 40.5 0.70 1.77 63.9 32.6 ---
50
6.0 1.30 3.00 48.9 3.44 37.1 96.3 4.16 6.2 55.5 38.4 0.69 2.37 63.6 23.5 3.2
9.0 2.07 4.77 51.1 3.49 39.1 97.6 4.28 6.4 55.9 39.2 0.70 2.18 63.4 25.6 3.0
12.0 3.07 7.08 52.6 3.54 40.6 98.5 4.36 6.5 56.5 39.6 0.70 2.07 63.6 27.3 2.9
60
6.0 1.13 2.61 53.2 3.52 41.2 98.8 4.43 7.0 53.2 37.6 0.71 2.66 62.3 20.0 3.9
9.0 1.90 4.39 55.7 3.58 43.5 100.2 4.56 7.2 53.9 38.2 0.71 2.54 62.6 21.2 3.7
12.0 2.90 6.70 57.4 3.62 45.0 101.2 4.65 7.4 54.9 39.0 0.71 2.46 63.3 22.3 3.5
70
6.0 0.96 2.23 60.5 3.73 47.7 103.0 4.75 7.9 49.7 37.1 0.75 2.92 59.7 17.0 4.9
9.0 1.73 4.00 63.2 3.79 50.3 104.6 4.89 8.1 50.5 37.7 0.75 2.79 60.0 18.1 4.6
12.0 2.73 6.31 65.2 3.83 52.1 105.7 4.98 8.3 51.5 38.5 0.75 2.70 60.7 19.1 4.4
80
6.0 0.80 1.84 65.7 3.76 52.9 106.0 5.12 8.8 47.0 35.6 0.76 3.30 58.3 14.2 6.2
9.0 1.57 3.62 68.7 3.82 55.7 107.8 5.28 9.1 47.7 36.1 0.76 3.15 58.5 15.1 5.9
12.0 2.57 5.93 70.8 3.86 57.6 109.0 5.37 9.4 48.7 36.9 0.76 3.05 59.1 16.0 5.6
90
6.0 0.63 1.46 71.0 3.79 58.1 109.1 5.49 9.9 45.2 34.7 0.77 3.65 57.6 12.4 7.7
9.0 1.40 3.24 74.2 3.84 61.1 110.9 5.65 10.2 45.9 35.2 0.77 3.48 57.8 13.2 7.4
12.0 2.40 5.55 76.5 3.89 63.2 112.3 5.76 10.6 46.8 35.9 0.77 3.37 58.3 13.9 7.0
100
6.0 0.46 1.07
Operation not recommended
Operation not recommended
9.0 1.23 2.85 43.5 33.7 0.78 3.85 56.6 11.3 9.2
12.0 2.23 5.16 44.1 34.4 0.78 3.73 56.9 11.8 8.7
110
6.0 0.30 0.69 Operation not recommended
9.0 1.07 2.47 40.8 32.2 0.79 4.20 55.2 9.7 11.2
12.0 2.07 4.78 41.4 32.9 0.79 4.09 55.4 10.1 10.7
120
6.0 0.13 0.30 Operation not recommended
9.0 0.90 2.08 35.9 30.7 0.86 4.61 51.7 7.8 13.5
12.0 1.90 4.39 36.5 31.4 0.86 4.47 51.7 8.2 12.9
8/24/2016
1600 CFM
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 20
Versatec Variable Speed Series3-6 Tons 60Hz
060 - Min Load - Performance Data
EWT °F
Flow gpm
WPD HEATING - EAT 70°F COOLING - EAT 80/67°F
psi FT HC MBtu/h
Power kW
HE MBtu/h
LAT °F COP HWC
MBtu/hTC
MBtu/hSC
MBtu/hS/T
RatioPower
kWHR
MBtu/h EER HWC MBtu/h
20
6.0 1.32 3.05Operation not recommended
Operation not recommended8.0 2.16 4.99
10.0 3.04 7.01 8.50 0.75 5.94 76.6 3.32 1.9
30
6.0 1.20 2.77 Operation not recommended Operation not recommended
8.0 1.80 4.16 9.09 0.79 6.41 77.0 3.39 2.0 22.47 18.48 0.82 0.32 23.6 71.0 ---
10.0 2.80 6.47 9.23 0.80 6.51 77.1 3.40 2.0 22.70 18.67 0.82 0.30 23.7 75.7 ---
40
6.0 1.08 2.49 Operation not recommended Operation not recommended
8.0 1.68 3.88 11.42 0.79 8.73 78.8 4.25 2.2 21.33 17.81 0.83 0.34 22.5 62.2 ---
10.0 2.56 5.92 11.60 0.80 8.88 78.9 4.26 2.2 21.55 17.99 0.83 0.33 22.7 66.3 ---
50
6.0 0.96 2.22 13.55 0.78 10.89 80.5 5.09 2.4 20.05 16.78 0.84 0.40 21.4 50.1 4.2
8.0 1.56 3.60 13.76 0.79 11.06 80.6 5.10 2.5 20.20 17.13 0.85 0.37 21.5 54.7 4.0
10.0 2.33 5.38 13.97 0.80 11.24 80.8 5.12 2.5 20.40 17.30 0.85 0.35 21.6 58.3 3.8
60
6.0 0.84 1.94 15.76 0.82 12.97 82.2 5.64 2.7 19.05 16.39 0.86 0.53 20.9 35.8 5.1
8.0 1.44 3.33 16.01 0.83 13.17 82.4 5.65 2.8 19.30 16.65 0.86 0.51 21.0 38.0 4.9
10.0 2.09 4.84 16.25 0.84 13.38 82.5 5.67 2.8 19.64 16.99 0.87 0.49 21.3 40.0 4.6
70
6.0 0.72 1.66 18.09 0.85 15.20 84.0 6.26 3.0 17.66 16.12 0.91 0.66 19.9 26.7 6.4
8.0 1.32 3.05 18.37 0.86 15.44 84.2 6.28 3.1 17.93 16.37 0.91 0.63 20.1 28.5 6.1
10.0 1.86 4.29 18.65 0.87 15.69 84.4 6.30 3.2 18.30 16.70 0.91 0.61 20.4 30.0 5.8
80
6.0 0.60 1.39 21.17 0.88 18.18 86.3 7.08 3.4 16.46 15.97 0.97 0.81 19.2 20.3 8.1
8.0 1.20 2.77 21.50 0.89 18.47 86.6 7.09 3.5 16.72 16.21 0.97 0.77 19.4 21.6 7.7
10.0 1.62 3.75 21.83 0.90 18.76 86.8 7.12 3.6 17.06 16.55 0.97 0.75 19.6 22.8 7.4
90
6.0 0.48 1.11 24.25 0.91 21.16 88.7 7.84 3.8 15.79 15.44 0.98 0.97 19.1 16.3 10.2
8.0 1.08 2.49 24.63 0.92 21.49 89.0 7.86 3.9 16.04 15.68 0.98 0.93 19.2 17.3 9.7
10.0 1.39 3.21 25.00 0.93 21.83 89.3 7.88 4.1 16.37 16.00 0.98 0.90 19.4 18.3 9.2
100
6.0 0.36 0.83
Operation not recommended
Operation not recommended
8.0 0.96 2.22 15.51 15.09 0.97 1.10 19.3 14.1 12.1
10.0 1.15 2.66 15.75 15.40 0.98 1.06 19.4 14.8 11.5
110
6.0 0.24 0.55 Operation not recommended
8.0 0.84 1.94 14.90 14.50 0.97 1.26 19.2 11.8 14.8
10.0 0.92 2.12 15.13 14.80 0.98 1.23 19.3 12.3 14.1
120
6.0 0.12 0.28 Operation not recommended
8.0 0.72 1.66 13.99 13.62 0.97 1.42 18.8 9.8 17.9
10.0 0.68 1.58 14.20 13.90 0.98 1.38 18.9 10.3 17.0
8/24/2016
1200 CFM
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 21
Versatec Variable Speed Series3-6 Tons 60Hz
060 - Full Load - Performance Data
EWT °F
Flow gpm
WPD HEATING - EAT 70°F COOLING - EAT 80/67°F
psi FT HC MBtu/h
Power kW
HE MBtu/h
LAT °F COP HWC
MBtu/hTC
MBtu/hSC
MBtu/hS/T
RatioPower
kWHR
MBtu/h EER HWC MBtu/h
20
8.0 2.16 4.99Operation not recommended
Operation not recommended12.0 4.04 9.32
16.0 6.74 15.56 43.0 3.77 30.1 90.1 3.34 5.6
30
8.0 1.80 4.16 Operation not recommended Operation not recommended
12.0 3.80 8.78 47.6 4.12 33.5 92.5 3.38 6.0 75.2 50.3 0.67 1.73 81.2 43.4 ---
16.0 6.50 15.02 49.0 4.17 34.8 93.2 3.44 6.1 76.0 50.8 0.67 1.64 81.6 46.3 ---
40
8.0 1.68 3.88 Operation not recommended Operation not recommended
12.0 3.56 8.23 54.4 4.34 39.6 96.0 3.67 6.6 72.9 49.1 0.67 2.12 80.1 34.4 ---
16.0 6.26 14.47 56.1 4.39 41.1 96.8 3.74 6.7 73.6 49.5 0.67 2.01 80.5 36.7 ---
50
8.0 1.56 3.60 58.6 4.49 43.3 98.1 3.82 7.2 70.0 46.9 0.67 2.71 79.3 25.8 4.2
12.0 3.33 7.69 61.2 4.56 45.7 99.5 3.94 7.4 70.5 47.8 0.68 2.50 79.0 28.2 4.0
16.0 6.03 13.93 63.1 4.61 47.4 100.5 4.01 7.5 71.2 48.3 0.68 2.37 79.3 30.1 3.8
60
8.0 1.44 3.33 64.3 4.69 48.3 101.1 4.02 8.0 65.8 44.4 0.68 2.95 75.8 22.3 5.1
12.0 3.09 7.15 67.2 4.76 51.0 102.6 4.14 8.3 66.6 45.1 0.68 2.81 76.2 23.7 4.9
16.0 5.79 13.38 69.3 4.82 52.9 103.6 4.21 8.5 67.8 46.0 0.68 2.72 77.1 24.9 4.6
70
8.0 1.32 3.05 70.2 4.89 53.6 104.1 4.21 9.0 61.2 43.2 0.71 3.39 72.8 18.0 6.4
12.0 2.86 6.60 73.4 4.96 56.5 105.8 4.33 9.3 62.1 43.9 0.71 3.23 73.2 19.2 6.1
16.0 5.56 12.84 75.7 5.03 58.5 106.9 4.41 9.6 63.4 44.8 0.71 3.13 74.1 20.3 5.8
80
8.0 1.20 2.77 73.6 5.12 56.2 105.9 4.22 10.2 57.5 41.7 0.73 3.95 70.9 14.5 8.1
12.0 2.62 6.06 77.0 5.19 59.2 107.6 4.34 10.5 58.3 42.4 0.73 3.77 71.2 15.5 7.7
16.0 5.32 12.30 79.3 5.26 61.4 108.8 4.42 10.8 59.5 43.2 0.73 3.65 72.0 16.3 7.4
90
8.0 1.08 2.49 77.0 5.34 58.8 107.6 4.22 11.4 54.6 40.3 0.74 4.28 69.2 12.8 10.2
12.0 2.39 5.52 80.5 5.43 62.0 109.4 4.35 11.8 55.5 40.9 0.74 4.08 69.4 13.6 9.7
16.0 5.09 11.75 83.0 5.49 64.3 110.7 4.43 12.2 56.6 41.7 0.74 3.95 70.1 14.3 9.2
100
8.0 0.96 2.22
Operation not recommended
Operation not recommended
12.0 2.15 4.97 53.5 40.2 0.75 4.37 68.4 12.3 12.1
16.0 4.85 11.21 54.3 41.0 0.75 4.22 68.8 12.9 11.5
110
8.0 0.84 1.94 Operation not recommended
12.0 1.92 4.43 51.3 39.5 0.77 4.63 67.1 11.1 14.8
16.0 4.62 10.67 52.1 40.3 0.77 4.50 67.5 11.6 14.1
120
8.0 0.72 1.66 Operation not recommended
12.0 1.68 3.89 47.5 38.7 0.81 5.15 65.1 9.2 17.9
16.0 4.38 10.12 48.2 39.5 0.82 5.00 65.3 9.6 17.0
8/24/2016
1800 CFM
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 22
Versatec Variable Speed Series3-6 Tons 60Hz
072 - Min Load - Performance Data
EWT °F
Flow gpm
WPD HEATING - EAT 70°F COOLING - EAT 80/67°F
psi FT HC MBtu/h
Power kW
HE MBtu/h
LAT °F COP HWC
MBtu/hTC
MBtu/hSC
MBtu/hS/T
RatioPower
kWHR
MBtu/h EER HWC MBtu/h
20
6.0 1.24 2.87Operation not recommended
Operation not recommended9.0 1.99 4.59
12.0 3.39 7.82 12.73 0.96 9.45 78.4 3.89 2.4
30
6.0 1.13 2.61 Operation not recommended Operation not recommended
9.0 1.80 4.16 13.67 1.01 10.24 79.0 3.98 2.5 22.47 18.48 0.82 0.32 23.6 71.0 ---
12.0 3.20 7.39 13.88 1.02 10.40 79.2 3.99 2.6 22.70 18.67 0.82 0.30 23.7 75.7 ---
40
6.0 1.02 2.35 Operation not recommended Operation not recommended
9.0 1.61 3.73 16.35 1.01 12.90 80.8 4.74 2.8 21.79 19.79 0.91 0.45 23.3 48.6 ---
12.0 3.01 6.96 16.60 1.02 13.10 81.0 4.75 2.9 22.02 19.99 0.91 0.43 23.5 51.8 ---
50
6.0 0.90 2.09 18.73 1.00 15.31 82.4 5.48 3.1 21.70 19.50 0.90 0.61 23.8 35.3 1.5
9.0 1.43 3.29 19.02 1.02 15.56 82.6 5.49 3.1 21.86 19.90 0.91 0.57 23.8 38.6 1.5
12.0 2.83 6.53 19.31 1.03 15.81 82.8 5.51 3.2 22.08 20.10 0.91 0.54 23.9 41.1 1.4
60
6.0 0.79 1.82 21.18 1.02 17.72 84.0 6.11 3.4 23.26 21.68 0.93 0.70 25.7 33.1 1.9
9.0 1.24 2.86 21.51 1.03 18.00 84.2 6.12 3.5 23.57 22.02 0.93 0.67 25.9 35.2 1.8
12.0 2.64 6.10 21.84 1.04 18.28 84.4 6.14 3.6 23.98 22.47 0.94 0.65 26.2 37.0 1.7
70
6.0 0.68 1.56 23.64 1.03 20.11 85.6 6.71 3.9 21.89 20.61 0.94 0.87 24.9 25.2 2.3
9.0 1.05 2.43 24.00 1.05 20.43 85.9 6.72 4.0 22.23 20.93 0.94 0.83 25.1 26.8 2.2
12.0 2.45 5.67 24.37 1.06 20.75 86.1 6.74 4.1 22.69 21.35 0.94 0.80 25.4 28.3 2.1
80
6.0 0.56 1.30 25.64 1.05 22.06 87.0 7.16 4.3 20.51 19.60 0.96 1.05 24.1 19.6 3.0
9.0 0.87 2.00 26.04 1.06 22.41 87.2 7.18 4.5 20.83 19.91 0.96 1.00 24.2 20.9 2.8
12.0 2.27 5.23 26.43 1.08 22.76 87.5 7.20 4.6 21.26 20.32 0.96 0.97 24.6 22.0 2.7
90
6.0 0.45 1.04 27.65 1.07 24.01 88.3 7.60 4.9 18.92 18.03 0.95 1.23 23.1 15.4 3.7
9.0 0.68 1.57 28.07 1.08 24.39 88.6 7.62 5.0 19.21 18.31 0.95 1.17 23.2 16.4 3.5
12.0 2.08 4.80 28.50 1.09 24.77 88.8 7.64 5.2 19.61 18.69 0.95 1.14 23.5 17.3 3.4
100
6.0 0.34 0.78
Operation not recommended
Operation not recommended
9.0 0.49 1.14 18.33 17.49 0.95 1.35 22.9 13.6 4.4
12.0 1.89 4.37 18.61 17.84 0.96 1.30 23.1 14.3 4.2
110
6.0 0.22 0.51 Operation not recommended
9.0 0.31 0.71 17.34 16.66 0.96 1.51 22.5 11.5 5.4
12.0 1.71 3.94 17.61 17.00 0.97 1.47 22.6 12.0 5.1
120
6.0 0.11 0.25 Operation not recommended
9.0 0.12 0.27 16.06 15.68 0.98 1.65 21.7 9.7 6.5
12.0 1.52 3.51 16.30 16.00 0.98 1.60 21.8 10.2 6.2
8/24/2016
1400 CFM
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 23
Versatec Variable Speed Series3-6 Tons 60Hz
072 - Full Load - Performance Data
EWT °F
Flow gpm
WPD HEATING - EAT 70°F COOLING - EAT 80/67°F
psi FT HC MBtu/h
Power kW
HE MBtu/h
LAT °F COP HWC
MBtu/hTC
MBtu/hSC
MBtu/hS/T
RatioPower
kWHR
MBtu/h EER HWC MBtu/h
20
15.0 4.69 10.83Operation not recommended
Operation not recommended18.0 6.19 14.29
21.0 7.99 18.45 58.0 5.00 40.9 94.9 3.40 7.1
30
15.0 4.50 10.40 Operation not recommended Operation not recommended
18.0 6.00 13.86 63.1 5.30 45.0 97.2 3.49 7.6 78.2 51.5 0.66 3.17 89.0 24.7 ---
21.0 7.80 18.02 65.0 5.37 46.7 98.1 3.55 7.8 79.0 52.0 0.66 3.00 89.2 26.3 ---
40
15.0 4.31 9.96 Operation not recommended Operation not recommended
18.0 5.81 13.43 69.4 5.58 50.3 100.1 3.65 8.4 79.2 51.9 0.66 3.64 91.6 21.8 ---
21.0 7.61 17.59 71.5 5.65 52.3 101.1 3.71 8.6 80.0 52.4 0.66 3.45 91.7 23.2 ---
50
15.0 4.13 9.53 72.4 5.76 52.7 101.5 3.68 9.2 79.6 51.3 0.64 4.46 94.8 17.8 4.6
18.0 5.63 13.00 75.7 5.85 55.7 103.0 3.79 9.4 80.1 52.3 0.65 4.11 94.2 19.5 4.4
21.0 7.43 17.15 78.0 5.92 57.8 104.1 3.86 9.7 81.0 52.9 0.65 3.90 94.3 20.8 4.2
60
15.0 3.94 9.10 85.9 6.12 65.1 107.8 4.12 10.3 76.7 50.5 0.66 4.66 92.6 16.5 5.6
18.0 5.44 12.57 89.8 6.21 68.6 109.6 4.24 10.6 77.8 51.3 0.66 4.44 92.9 17.5 5.3
21.0 7.24 16.72 92.6 6.29 71.1 110.9 4.31 10.9 79.1 52.4 0.66 4.30 93.8 18.4 5.1
70
15.0 3.75 8.67 89.9 6.48 67.8 109.6 4.07 11.6 74.3 49.8 0.67 4.87 91.0 15.2 7.0
18.0 5.25 12.13 94.0 6.57 71.6 111.5 4.19 11.9 75.5 50.5 0.67 4.65 91.4 16.2 6.7
21.0 7.05 16.29 96.9 6.66 74.2 112.9 4.27 12.3 77.0 51.6 0.67 4.50 92.4 17.1 6.4
80
15.0 3.57 8.24 94.6 6.66 71.9 111.8 4.16 13.0 72.5 49.1 0.68 5.20 90.3 14.0 8.9
18.0 5.07 11.70 98.9 6.77 75.8 113.8 4.28 13.4 73.7 49.8 0.68 4.96 90.6 14.9 8.4
21.0 6.87 15.86 102.0 6.85 78.6 115.2 4.36 13.8 75.2 50.8 0.68 4.80 91.6 15.7 8.0
90
15.0 3.38 7.81 99.3 6.85 75.9 114.0 4.25 14.7 67.2 48.3 0.72 5.42 85.7 12.4 11.1
18.0 4.88 11.27 103.8 6.96 80.0 116.1 4.37 15.1 68.3 49.0 0.72 5.17 85.9 13.2 10.6
21.0 6.68 15.43 107.0 7.04 83.0 117.5 4.45 15.6 69.7 50.0 0.72 5.00 86.7 13.9 10.1
100
15.0 3.19 7.37
Operation not recommended
Operation not recommended
18.0 4.69 10.84 62.9 46.6 0.74 5.94 83.1 10.6 13.2
21.0 6.49 15.00 63.8 47.5 0.74 5.75 83.4 11.1 12.5
110
15.0 3.01 6.94 Operation not recommended
18.0 4.51 10.41 57.1 44.1 0.77 6.68 79.9 8.5 16.1
21.0 6.31 14.57 58.0 45.0 0.78 6.50 80.2 8.9 15.3
120
15.0 2.82 6.51 Operation not recommended
18.0 4.32 9.98 50.3 41.3 0.82 7.69 76.5 6.5 19.5
21.0 6.12 14.13 51.1 42.1 0.83 7.46 76.5 6.8 18.5
8/24/2016
2000 CFM
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 24
Versatec Variable Speed Series3-6 Tons 60Hz
Wiring Schematics
Commercial Variable Speed - 208-230/60/1
Violet(14)
TRV
CC
HP
Condensate
Black(10)
Black(9)
Blue(8)
Blue(7)
LP
Black
Black
FP2
TYellow
Yellow
FP1
Orange(2)
Orange(1)
RV
Black(15)
GreenBrown(23)
Violet(42)
Blue(24)
Yellow(25)
Green/Yellow(28)AID Tool
Communica ng Thermostat
SUC
P
BLOWER CT
HW HW
HOT WATEROPTION
Blue
Blue
NO TE: 6
SCT
P8
MOT
OR P6
RS48
5 P7
ZONE P9
ABC
STEP
PER
ANA
ACC2
DHDI
V
NO
CO
M
K6
NO
CO
M
K5
C R L1 L1 L2 L2P1
2P1
0P5
P11
CR(-)(+) CR(-)(+) CR(-)(+)
P4P2
K1K2
K3
HA2
HA1
SGI
LOO
PVS
DAT
AVS
PUM
PPU
MPSL
AVE
P3
V+CRTXRX +5
P14
LLT
P1LA
TFL
OW
LWT
EWT
CT2
43
CT2
43
CT1
21
CT1
21
StatusG
DISC
HP1
6
P17
P18
P15
(Aurora Expansion Board)AXB™
See Figure 1 for DHW wiring.
SW1
Modbus Add. IDFuture Use
12345
ONOFF
Future UseAcc 2 – Dip 4Acc 2 – Dip 5
CFM
P13
P4
SW1
P5JW2
P9
LO
O/B
Y2WDH
P8 P7
RS485 NET RS485 NET
P6
RS485 EXP
P3
SW2
On
Future Use L Output Type
CC – Dual/SingleAcc – Dip 5Acc – Dip 4
RV – B/OFP2 – 15°F/30°FFP1 – 15°F/30°F
Com1LED5
Com2LED5
Test Mode
F1-3A
P1
C
PWM
12345678
ALMALGACC COMACC NOACC NC
RC
GY1
EH2CEH1CCOC R - +C R - +
Off
Faul tLED1
R
StatusLED3
ConfigLED2
CC2 CC F C R F FG CC CCGCC2HI
CC2LO
CC2G REVREVFP1 FP1 FP2 FP2 LPS LPSHPSHPS
Aurora Base Control(ABC)
K1-RV Relay
K2-CC Relay
K3-CC2 Relay
K4-Fan RelayK5-Alarm Relay
K6-Acc Relay
F
R
C
CCGY1C
R
ESLS
P2EH1
YG G
G
CS
+5C
S+5
21
CC
INOU
T
Pink(140)Pink(139)
T Purple
Purple
GNDOUT5DC
324
Green(134)White(133)Brown(132)
324
FL OW M ETER
Gray(136)
Gray(135)
White
WhiteT
White
White
Black
Black
Orange
Orange
Dehumidification Output
Accessory 2 Output
Analog Output 0-10VDC
VS Drive Fan
AUXILIARY HEAT CT
NO TE: 5
Blue (254) T Blue (255)
GNDOUT
RedWhiteBlack PRESSURE
TRANSDUCER5DC3
21
T
Black
Red
GNDOUT5DC
123
White
PRESSURE TRANSDUCER
1234
+X1X2Y1
5 Y2
ELECTRONIC EXPANSION
VALVE
Orange
Red
Yellow
Black
Gray
Gray (60)RH
Gray
(61)
Thermistor
Relay Coi l
Switch - Condensate OverflowSwitch - High pressure
Switch - Low pressure
Polarized connector
Factory Low Voltage WiringFactory Line Vol tage WiringField Low Voltage WiringField Line Voltage Wi ringOptional BlockDC Voltage PCB Traces
Internal JunctionQuick Connect Terminal
Field Wiring Lug
Ground
Relay Con tacts – N.O., N.C.
Field Zone Sensor Wi ring
Legend
L1
Capacitor
T
123
CC – Compressor ContactorCO – Condensate Overflow SensorES – Emergency ShutdownHP – High Pressure SwitchLP – Low Pressure SwitchFD – Freeze De tection SensorF1 – Fuse
Fuse
Light Emitti ng Diode - GreenG
Light Emitti ng Diode - YellowY
Light Emitti ng Diode - RedR
SW1 – Push buttonSW2 – DIP package 8 positionRB – Blower RelayRV – Reversing Valve Coi lPGM – Phase Guard Moni torRH – Reheat Valve Coi l
Black
Black
1 – Optional, factory installed unit mounted disconnect.2 – Swap blue and red leads for 208V operation.3 – Optional, factory installed modulating valve.
Notes:
4 – On units with a Perfect Speed 1 hp ECM blower motor, the blower’s low voltage harness from the board with the P12 connector will connect to a jumper harness that is connected to the blower motor.5 - Wires provided for Auxiliary Heat low voltage control . Wires are secured at blower.6 – Brown blower power wire routed through Current Transducer two times.
T Brown(253)
Brown(252)
VS
GND24 VAC
0-10DC
12
3
R
C
ABC BOARD
AXB BOARD
OPTIONAL MODULATING VALVE
12
Red
WhiteGreen
Brown
Brown
Black
Black
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 25
Versatec Variable Speed Series3-6 Tons 60Hz
Wiring Schematics cont.
Commercial Variable Speed - 208-230/60/1
NOTE 6
ECM BlowerMotor
P112 3 4 51
Green
16 112 15 10
PWM
C1 C2R G
33
CFM
L2 L1
CCT2 T1
T1T3
T2
Black
RedMetal Flexible Conduit
Ferrite Toroid
Green
YellowU
V
W
L
N
Gnd
A1HPS
DSCH TEMP
RS485
Black
EmersonVariable Speed
Drive
A23
14
2
T
H1
H2PFC Reactor
Green
BLOWERCURRENT TRANSDUCER
(CT)
DisconnectNeutralGround
L1 L1
L2 L2
L3 L3
Unit Power Supply208-230-265/60/1
G
Black (95)
Red (97)
Green (93)
EMI Filter
L1 OUT
L2 OUT
L1 IN
L2 IN
Brown
Orange
Transfo rmer
Blue230V265V Black
Red208V
Yellow
Black/White
24V
Yellow
Green
High Pressure SwitchYellow
BrownBrown
Black
GND
Black
Yellow
Ferrite Toroid
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 26
Versatec Variable Speed Series3-6 Tons 60Hz
Wiring Schematics cont.
Commercial Variable Speed - 460/60/3
Violet(14)
TRV
CC
HP
Condensate
Black(10)
Black(9)
Blue(8)
Blue(7)
LP
Black
Black
FP2
TYellow
Yellow
FP1
Orange(2)
Orange(1)
RV
Black(15)
GreenBrown(23)
Violet(42)
Blue(24)
Yellow(25)
Green/Yellow(28)AID Tool
Communica ng Thermostat
SUC
P
BLOWER CT
HW HW
HOT WATEROPTION
Blue
Blue
NO TE: 5
SCT
P8
MOT
OR P6
RS48
5 P7
ZONE P9
ABC
STEP
PER
ANA
ACC2
DHDI
V
NO
CO
M
K6
NO
CO
M
K5
C R L1 L1 L2 L2P1
2P1
0P5
P11
CR(-)(+) CR(-)(+) CR(-)(+)
P4P2
K1K2
K3
HA2
HA1
SGI
LOO
PVS
DAT
AVS
PUM
PPU
MPSL
AVE
P3
V+CRTXRX +5
P14
LLT
P1LA
TFL
OW
LWT
EWT
CT2
43
CT2
43
CT1
21
CT1
21
StatusG
DISC
HP1
6
P17
P18
P15
(Aurora Expansion Board)AXB™
See Figure 1 for DHW wiring.
SW1
Modbus Add. IDFuture Use
12345
ONOFF
Future UseAcc 2 – Dip 4Acc 2 – Dip 5
CFM
P13
P4
SW1
P5JW2
P9
LO
O/B
Y2WDH
P8 P7
RS485 NET RS485 NET
P6
RS485 EXP
P3
SW2
On
Future Use L Output Type
CC – Dual/SingleAcc – Dip 5Acc – Dip 4
RV – B/OFP2 – 15°F/30°FFP1 – 15°F/30°F
Com1LED5
Com2LED5
Test Mode
F1-3A
P1
C
PWM
12345678
ALMALGACC COMACC NOACC NC
RC
GY1
EH2CEH1CCOC R - +C R - +
Off
Faul tLED1
R
StatusLED3
ConfigLED2
CC2 CC F C R F FG CC CCGCC2HI
CC2LO
CC2G REVREV FP1 FP1 FP2 FP2 LPS LPSHPSHPS
Aurora Base Control(ABC)
K1-RV Relay
K2-CC Relay
K3-CC2 Relay
K4-Fan RelayK5-Alarm Relay
K6-Acc Relay
F
R
C
CCGY1C
R
ESLS
P2EH1
YG G
G
CS
+5C
S+5
21
CC
INOU
T
Pink(140)Pink(139)
T Purple
Purple
GNDOUT5DC
324
Green(134)White(133)Brown(132)
324
FL OW M ETER
Gray(136)
Gray(135)
White
WhiteT
White
White
Black
Black
Orange
Orange
Dehumidification Output
Accessory 2 Output
Analog Output 0-10VDC
VS Drive Fan
AUXILIARY HEAT CT
NO TE: 4
Blue (254) T Blue (255)
GNDOUT
RedWhiteBlack PRESSURE
TRANSDUCER5DC3
21
T
Black
Red
GNDOUT5DC
123
White
PRESSURE TRANSDUCER
1234
+X1X2Y1
5 Y2
ELECTRONIC EXPANSION
VALVE
Orange
Red
Yellow
Black
Gray
DisconnectNeutralGround
L1 L1
L2 L2
L3 L3
Unit Power Supply460/60/3
G
Black (95)
Red (97)
Green (93)
Gray (60)RH
Gray
(61)
Black
Black
T Brown(253)
Brown(252)
VS
GND24 VAC
0-10DC
12
3
R
C
ABC BOARD
AXB BOARD
OPTIONAL MODULATING VALVE
12
Red
WhiteGreen
Brown
Orange
Transfo rmer
Blue460V
Black
Yellow
Black/White
24V
Brown
Brown
Black
Black
L2L3
CCT2T3
L1
T1
Blue
Black
Red
Gray (94)
Yellow (96)
N
L1
L2
L3
PB1
Black (54)
Blue (55)
Red (56)
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 27
Versatec Variable Speed Series3-6 Tons 60Hz
Wiring Schematics cont.
Commercial Variable Speed - 460/60/3
Current Transducer (CT)
Thermistor
Light emi tting diode - Green
Relay coil
Capacitor w/ bleed resistor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Polarized connector
Factory Low voltage wi ringFactory Line vol tage wiringField low voltage wiringField l ine voltage wi ringOptional blockDC Voltage PCB tracesJunctionQuick connect terminal
Wire nut
Field wi re lug
Ground
Fuse
CC -CO -K5 -K6 -CR3 -CR4 -
F1 and F2 -
WCL -
HE -HP -
LP -
PB1, PB2 - PS -RV -SW1 -SW1 -SW2 -
TS -
Compressor ContactorCondensate overflow sensorDHW pump relayLoop pump relay
Fuses
Water Coil Limit Sensor
Heater elementHigh pressure switch
Low pressure switch
Power blocksPower stripReversing Valve coilDIP package 5 position AXBTEST MODE ABC BoardDIP package 8 position ABC Board
Thermal limit swi tch
Legend
Relay Con tacts-N.O., N.C.
G
T
132P
L1
PSC Fan Speed RelayPSC Fan Power Relay
ER1 to ER4 - Aux heat stage relays
HWL - Hot water limit sensorSC - Start Contactor
Start RelaySR -
CS - Compressor Solenoid
Breaker
09/15/16
NO TE 5
ECM BlowerMotor
P112 3 4 51
Green
16 112 15 10
PWM
C1 C2R G
33
CFM
T1T3
T2
Black
RedMetal Flexible Conduit
Ferrite Toroid
Green
Yellow
Black
T
PFC Reactor
Green
BLOWERCURRENT TRANSDUCER
(CT)
1 – Optional, factory installed unit mounted disconnect.2 – Optional, factory installed modulating valve.
Notes:
3 – On units with a Perfect Speed 1 hp ECM blower motor, the blower’s low voltage harness from the board with the P12 connector will connect to a jumper harness that is connected to the blower motor.4 - Wires provided for Auxiliary Heat low voltage control . Wires are secured at blower .5 – Brown blower power wire routed through Current Transducer two times.
Green
Red
Black
Blue
EMI Fi lter
L1 OUT
L2 OUTL2 IN
L3 IN L3 OUT
L1 IN
GND
Ferrite Toroid
High Pressure SwitchYellow
BrownBrown
DC BOARD
UVW
L3
L2
L1
A1HPS
DSCH TEMP
RS485
EmersonVariable Speed
Drive A23
14
2DC-OUT
DC+OUT
Gnd
DC+IN
DC-OUT
DC-IN
DC+OUT
DC+IN DC-INGreen
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 28
Versatec Variable Speed Series3-6 Tons 60Hz
Commercial Variable Speed
Wiring Schematics cont.
Vari
ab
le S
pe
ed
Dri
ve
Ad
dit
ion
sA
BC
Acti
on
AID
To
ol
Dis
pla
y a
nd
His
tory
Inte
lliZ
on
e2
an
d T
he
rmo
stat
Dis
pla
y
Re
d F
au
lt L
ED
LE
D F
lash
C
od
e *
Lo
cko
ut
Re
set/
R
em
ove
Fau
lt C
on
dit
ion
Su
mm
ary
AB
C G
ree
n
Sta
tus
LE
DA
BC
Re
d
Fau
lt L
ED
ABC & AXB Basic Faults
No
rmal -
No
Fau
lts
Off
-
Fau
lt-I
np
ut
1N
oA
uto
Tst
at
inp
ut
err
or.
Au
tore
set
up
on
co
nd
itio
n r
em
oval.
No
rmal
Co
de 1
Fau
lt-H
igh
Pre
ssu
re2
Yes
Hard
or
So
ftH
P s
wit
ch
has
trip
ped
(>
60
0 p
si)
Lo
cko
ut
Co
de 2
Lo
cko
ut
- E
2
Hig
h P
ress
Lo
cko
ut
- E
2
Hig
h P
ress
Fau
lt-L
ow
Pre
ssu
re3
Yes
Hard
or
So
ftL
ow
Pre
ssu
re S
wit
ch
has
trip
ped
(<
40
psi
fo
r 3
0 c
on
tin
ou
s se
c.)
Lo
cko
ut
Co
de 3
Lo
cko
ut
- E
3
Lo
w P
ress
Lo
cko
ut
- E
3
Lo
w P
ress
Fau
lt-F
reeze D
ete
cti
on
FP
24
Yes
Hard
or
So
ftF
reeze p
rote
cti
on
sen
sor
has
trip
ped
(<
30
deg
F f
or
30
co
nti
nu
ou
s se
c.)
Lo
cko
ut
Co
de 4
Lo
cko
ut
- E
4
Fre
eze D
ete
cti
on
FP
2L
ocko
ut
- E
4
Fre
eze D
ete
cti
on
FP
2
Fau
lt-F
reeze D
ete
cti
on
FP
15
Yes
Hard
or
So
ftF
reeze p
rote
cti
on
sen
sor
has
trip
ped
(<
15 o
r 3
0 d
eg
F f
or
30
co
nti
nu
ou
s se
c.)
Lo
cko
ut
Co
de 5
Lo
cko
ut
- E
5
Fre
eze D
ete
cti
on
FP
1L
ocko
ut
- E
5
Fre
eze D
ete
cti
on
FP
1
Fau
lt-C
on
den
sate
Overf
low
7Y
es
Hard
or
So
ftC
on
den
sate
sw
itch
has
sho
wn
co
nti
nu
ity f
or
30
co
nti
nu
ou
s se
c.
Lo
cko
ut
Co
de 7
Lo
cko
ut
- E
7 C
on
den
sate
Lo
cko
ut
- E
7 C
on
den
sate
Fau
lt-O
ver/
Un
der
Vo
ltag
e8
No
**A
uto
Inst
an
tan
eo
us
Vo
ltag
e is
ou
t o
f ra
ng
e. **
Co
ntr
ols
sh
ut
do
wn
un
til re
solv
ed
.L
ocko
ut
Co
de 8
Lo
cko
ut
- E
8
Over/
Un
der
vo
ltag
eL
ocko
ut
- E
8
Over/
Un
der
vo
ltag
e
Fau
lt-F
P1
& 2
Sn
sr E
rro
r11
Yes
Hard
or
So
ftIf
FP
1 o
r 2 S
en
sor
Err
Lo
cko
ut
Co
de 1
1L
ocko
ut
- E
11 F
P1/
FP
2 S
en
sor
Err
or
Lo
cko
ut
- E
11 F
P1/
FP
2 S
en
sor
Err
or
Miscellaneous
No
n-C
riti
cA
XB
Sn
srE
rr13
No
Au
toA
ny O
ther
Sen
sor
Err
No
rmal
Co
de 1
3A
lert
- E
13 N
on
-Cri
tical A
XB
Sen
sor
Err
or
Ale
rt -
E13
No
n-C
riti
cal A
XB
Sen
sor
Err
or
Cri
ticA
XB
Sn
srE
rr14
Yes
Hard
or
So
ftS
en
sor
Err
fo
r E
EV
or
HW
Lo
cko
ut
Co
de 1
4L
ocko
ut
- E
14 C
riti
cal A
XB
Sen
sor
Err
or
Lo
cko
ut
- E
14 C
riti
cal A
XB
Sen
sor
Err
or
Ala
rm-H
otW
tr15
No
Au
toH
W o
ver
limit
or
log
ic lo
cko
ut.
HW
pu
mp
deacti
vate
d.
No
rmal
Co
de 1
5A
lert
- E
15 H
ot
Wate
r Te
mp
Lim
itN
o D
isp
lay
Fau
lt-V
arS
pd
Pu
mp
16N
oA
uto
Ale
rt is
read
fro
m P
WM
feed
back.
No
rmal
Co
de 1
6A
lert
- E
16 V
ar
Sp
d P
um
p E
rrA
lert
- E
16 V
ar
Sp
d P
um
p E
rr
No
t U
sed
17N
oA
uto
IZ2 C
om
Fau
lt. A
uto
rese
t u
po
n c
on
dit
ion
rem
oval.
No
rmal
Co
de 1
7W
arn
ing
- E
17 IZ
2 C
om
m E
rro
rW
arn
ing
- E
17 IZ
2 C
om
m E
rro
r
No
n-C
ritC
om
Err
18N
oA
uto
An
y n
on
-cri
tical co
m e
rro
rN
orm
al
Co
de 1
8A
lert
- E
18 N
on
-Cri
tical C
om
mu
nic
a-
tio
n E
rro
rA
lert
- E
18 N
on
-Cri
tical C
om
mu
nic
a-
tio
n E
rro
r
Fau
lt-C
ritC
om
Err
19N
oA
uto
An
y c
riti
cal co
m e
rro
r. A
uto
rese
t u
po
n c
on
dit
ion
rem
oval
No
rmal
Co
de 1
9A
lert
- E
19 C
riti
cal C
om
mu
nic
ati
on
Err
or
Ale
rt -
E19
Cri
tical C
om
mu
nic
ati
on
Err
or
Ala
rm -
Lo
w L
oo
p P
ress
ure
21
No
Au
toL
oo
p p
ress
ure
is
belo
w 3
psi
fo
r m
ore
th
an
3 m
inu
tes
No
rmal
Co
de 2
1A
lert
- E
21
Lo
w L
oo
p P
ress
ure
No
Dis
pla
y
Ala
rm -
Ho
me A
uto
mati
on
123
No
Au
toC
lose
d c
on
tact
inp
ut
is p
rese
nt
on
Dig
2 in
pu
t -
Text
is c
on
fig
ura
ble
No
rmal
Co
de 2
3A
lert
- E
23
Sele
cte
d c
ho
ice
Ale
rt -
E23
Sele
cte
d c
ho
ice
Ala
rm -
Ho
me A
uto
mati
on
224
No
Au
toC
lose
d c
on
tact
inp
ut
is p
rese
nt
on
Dig
3 in
pu
t -
Text
is c
on
fig
ura
ble
No
rmal
Co
de 2
4A
lert
- E
24
Sele
cte
d C
ho
ice
Ale
rt -
E24
Sele
cte
d C
ho
ice
Copeland VS Drive
Dera
te-D
riveTe
mp
41
No
Au
toD
rive T
em
p h
as
reach
ed
cri
tical H
igh
Tem
pD
era
ted
Co
de 4
1W
arn
ing
! D
era
ted
- E
41
Dri
veTe
mp
Warn
ing
! D
era
ted
- E
41
Dri
veTe
mp
Dera
te-O
utP
wrL
mt
46
No
Au
toS
up
ply
Vo
ltag
e is
low
or
Max P
wr
is r
each
ed
du
e t
o h
igh
pre
ssu
reD
era
ted
Co
de 4
6W
arn
ing
! D
era
ted
- E
46
Ou
tPw
rLm
tW
arn
ing
! D
era
ted
- E
46
Ou
tPw
rLm
t
Fau
lt-D
isTm
pS
nr
51
Yes
Hard
or
So
ftD
isch
arg
e S
en
sor
(Sd
) is
> 2
80
F o
r in
valid
(-7
6 t
o 3
92 F
)L
ocko
ut
Co
de 5
1L
ocko
ut!
- E
51
Dis
Tm
pS
nr
Lo
cko
ut!
- E
51
Dis
Tm
pS
nr
Fau
lt-S
ucP
rsS
nr
52
Yes
Hard
or
So
ftS
ucti
on
Pre
ssu
re (
P0
) is
invalid
(0
to
29
0 p
si)
Lo
cko
ut
Co
de 5
2L
ocko
ut!
- E
52 S
ucP
rsS
nr
Lo
cko
ut!
- E
52 S
ucP
rsS
nr
Fau
lt-C
on
Prs
Sn
r5
310
x
then
Y
es
Hard
or
So
ftJu
mp
er
mis
sin
g f
rom
dri
ve p
in A
1 to
A2
No
rm t
hen
L
ocko
ut
Co
de 5
3L
ocko
ut!
- E
53
Co
nP
rsS
nr
Lo
cko
ut!
- E
53
Co
nP
rsS
nr
Fau
lt-L
ow
Su
pV
olt
54
Yes
Hard
or
So
ftS
up
ply
Vo
ltag
e is
<17
5 V
(19
0V
to
rese
t) o
r p
ow
ere
d o
ff/o
n t
oo
qu
ickly
(<
30
se
c.)
.L
ocko
ut
Co
de 5
4L
ocko
ut!
- E
54
Lo
wS
up
Vo
ltL
ocko
ut!
- E
54
Lo
wS
up
Vo
lt
Fau
lt-O
utE
nvelo
p5
510
x
then
Y
es
Hard
or
So
ftC
om
p O
pera
tin
g o
ut
of
envelo
pe m
ore
th
an
90
sec. R
etr
y 1
0x.
No
rm t
hen
L
ocko
ut
Co
de 5
5L
ocko
ut!
- E
55
Ou
tEnvelo
pL
ocko
ut!
- E
55
Ou
tEnvelo
p
Fau
lt-O
verC
urr
nt
56
Yes
Hard
or
So
ftO
ver
cu
rren
t tr
ipp
ed
by p
hase
lo
ss, eart
h f
au
lt, sh
ort
cir
cu
it. C
heck m
oto
r w
ind
ing
s/w
irin
g c
on
necti
on
sL
ocko
ut
Co
de 5
6L
ocko
ut!
- E
56
OverC
urr
nt
Lo
cko
ut!
- E
56
OverC
urr
nt
Fau
lt-O
ver/
Un
derV
olt
57
Yes
Hard
or
So
ftO
ver/
Un
der
AC
in
pu
t vo
ltag
e o
r O
ver/
Un
der
DC
Bu
s V
olt
ag
e
Lo
cko
ut
Co
de 5
7L
ocko
ut!
- E
57 O
ver/
Un
der
Vo
ltL
ocko
ut!
- E
57 O
ver/
Un
der
Vo
lt
Fau
lt-H
iDri
vTe
mp
58
Yes
Hard
or
So
ftO
ver
tem
pera
ture
of
PF
C-I
GB
T/P
ow
er
Mo
du
le. C
heck d
rive a
irfl
ow
/co
mp
res-
sor
op
era
tio
nL
ocko
ut
Co
de 5
8L
ocko
ut!
- E
58
HiD
rivTe
mp
Lo
cko
ut!
- E
58
HiD
rivTe
mp
Fau
lt-D
rvIn
tErr
MO
C/A
OC
59
Yes
Hard
or
So
ftM
icro
ele
ctr
on
ic/E
EP
RO
M f
au
lt h
as
occu
rred
. C
heck c
om
mu
nic
ati
on
s/P
ow
er
Cycle
/DC
Bu
s V
olt
L
ocko
ut
Co
de 5
9L
ocko
ut!
- E
59
Drv
IntE
rrL
ocko
ut!
- E
59
Drv
IntE
rr
Fau
lt-M
ult
Safe
Md
61
Yes
Hard
or
So
ftC
om
mu
nic
ati
on
/Co
nfi
gu
rati
on
Err
or
has
occu
rred
L
ocko
ut
Co
de 6
1L
ocko
ut!
- E
61
Mu
ltS
afe
Md
Lo
cko
ut!
- E
61
Mu
ltS
afe
Md
Fau
lt-P
FC
-IG
BT/O
pen
Sen
sor
62
Yes
Hard
or
So
ftP
ow
er
Mo
du
le T
em
p L
ow
/Op
en
Sen
sor
Fau
lt/P
FC
-IG
BT
Tem
p L
ow
Lo
cko
ut
Co
de 6
2L
ocko
ut!
- E
62 L
ow
Tem
pL
ocko
ut!
- E
62 L
ow
Tem
p
Fau
lt-L
imit
Lo
cko
ut
63
Yes
Hard
or
So
ftD
isch
arg
e T
em
p/o
rHig
h D
rive T
em
p/o
rOp
en
Sen
sor
fau
lt lim
its
have b
een
re
ach
ed
Lo
cko
ut
Co
de 6
3L
ocko
ut!
- E
63
Fau
ltL
imt
Lo
cko
ut!
- E
63
Fau
ltL
imt
Counter
Syst
em
Rese
t
99
No
Au
toS
yst
em
Rese
t C
ou
nte
r H
isto
ryN
AC
od
e 9
9F
au
lt H
isto
ry -
E9
9 S
ysR
ese
tN
o D
isp
lay
No
te: *A
ll co
des
>11
u
se lo
ng
fla
sh f
or
ten
s d
igit
an
d s
ho
rt f
lash
fo
r th
e o
nes
dig
it. 2
0, 3
0, 4
0, 5
0 e
tc. are
skip
ped
!
A
lert
' is
a n
on
cri
tical se
nso
r o
r fu
ncti
on
th
at
has
faile
d. N
orm
al o
pera
tio
n o
f th
e h
eat
pu
mp
is
main
tain
ed
bu
t se
rvic
e is
desi
red
at
som
e p
oin
t.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 29
Versatec Variable Speed Series3-6 Tons 60Hz
Commercial Variable Speed
DESCRIPTION SW2-4 SW2-5Cycle with Blower ON ONCycle with Compressor OFF OFFWater Valve Slow Opening ON OFFCycle with Comm. T-stat Hum Cmd OFF ON
ABC SW2 Accessory Relay
SW1-4 SW1-5 DESCRIPTIONON ON Cycles with BlowerOFF ON Cycles with CC rst stage compressor or compressor spd 1-12ON OFF Cycles with CC2 second stage of compressor or comp spd 7-12OFF OFF Cycles with DH from ABC board
AXB Accessory 2 DIP Se ngs
Thermistor
Relay Coi l
Switch - Condensate OverflowSwitch - High pressure
Switch - Low pressure
Polarized connector
Factory Low Voltage WiringFactory Line Vol tage WiringField Low Voltage WiringField Line Voltage Wi ringOptional BlockDC Voltage PCB Traces
Internal Ju nctionQuick Con nect Terminal
Field Wiring Lug
Ground
Relay Con tacts – N.O., N.C.
Field Zone Sensor Wi ring
Legend
L1
Capacitor
T
123
CC – Compressor ContactorCO – Condensate Overflow SensorES – Emergency ShutdownHP – High Pressure SwitchLP – Low Pressure SwitchFD – Freeze De tection SensorF1 – Fuse
Fuse
Light Emitti ng Diode - GreenG
Light Emitti ng Diode - YellowY
Light Emitti ng Diode - RedR
SW1 – Push buttonSW2 – DIP package 8 positionRB – Blower RelayRV – Reversing Valve Coi lPGM – Phase Guard Moni torRH – Reheat Valve Coi l
Wiring Schematics cont.
CC2
Fact
ory
Fault
ALG
ALM
LSES
ACC
c
Status
AuroraTM BaseControl
RV – K1
CC
2
CC – K2
CC Hi – K3
Fan – K4
Alarm – K5
Acc – K6
ACC
no
ACC
nc
O/BCRLO G Y1 Y2 W DH
3A-F
use
O/BCRLO G Y1 Y2 W DH
LOG
HICCGCCFGFR
HPHPLP
FP2FP2FP1
REVREV
CFM
PWM
ECM PWM
Fact
ory
Factory Fan Connection
R R
CC
C
C
R
(-)
(+)
RS
485
EH2C
EH1C
CO
(+)(-)RC
RS4
85Ex
pFa
ctor
y
Com1
Com2
Config
G
G
G
YR
SW1 Test
FP1 – 15oF/30oF
JW2 - Alarm
P11
P5
P2 P1
P8
P7
P9
P6
P3
SW2
P13P4 FP2 – 15oF/30oF
RV – B/O
ACC – Dip 1
ACC – Dip 2
CC – Dual/SingleL – Pulse/Continuous
Reheat/Normal
Fact
ory
Use
Field ConnectionsField Connections
C
LP
FP1
F
CC
G
Y1
1
2
3
4
5
6
7
8
Off On
N/A
RS4
85 N
ET
EH1LED 1
LED 3
LED 2
LED 5
LED 4
SCT
SUC
PHW HW
MOTO
R
RS48
5
P7
ZONE
P9
ABC
STEP
PER
ANA
SPR
DHDI
V
NO
CO
M
K6
NO
CO
M
K5
C R L1 L1 L2 L2P1
2P1
0P5
P11
CR(-)(+) CR(-)(+) CR(-)(+)
P4P2
K1K2
K3
HA2
HA1
SGI
LOOP
PWM
VSSL
OSL
IP3
V+CRTXRX +5
P14
LLT
P1LA
TFL
OWLW
TEW
T
CT2
43
CT2
43
CT1
21
CT1
21
StatusG
DISC
HP1
6
P17
P18
P15
(Aurora Expansion Board)AXB™
See Figure 1 for DHW wiring.
SW1
Modbus Add. IDFuture Use
12345
ONOFF
Future UseAcc 2 – Dip 4Acc 2 – Dip 5
P8 P6
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 30
Versatec Variable Speed Series3-6 Tons 60Hz
Engineering Guide Specifi cationsGeneralFurnish and install WaterFurnace Water Source Heat Pumps
as indicated on the plans. Equipment shall be completely
assembled, piped and internally wired. Capacities
and characteristics as listed in the schedule and the
specifi cations that follow. The reverse cycle heating/cooling
units shall be either suspended type with horizontal air inlet
and discharge or fl oor mounted type with horizontal air
inlet and vertical upfl ow air discharge. Units shall be AHRI/
ISO 13256-1 certifi ed and listed by a nationally recognized
safety-testing laboratory or agency, such as ETL Testing
Laboratory. Each unit shall be computer run-tested at the
factory with conditioned water and operation verifi ed to
catalog data. Each unit shall be mounted on a pallet and
shipped in a corrugated box or stretch-wrapped. The
units shall be designed to operate with entering liquid
temperature between 20°F and 120°F [-6.7°C and 48.9°C].
Casing and CabinetThe cabinet shall be fabricated from heavy-gauge galvanized
steel and fi nished with optional corrosion-resistant powder
coating. This corrosion protection system shall meet the
stringent 1000 hour salt spray test per ASTM B117. The
interior shall be insulated with 1/2 in. thick, multi-density,
cleanable aluminum foil coated glass fi ber with edges sealed
or tucked under fl anges to prevent the introduction of glass
fi bers into the discharge air. Standard cabinet panel insulation
must meet NFPA 90A requirements, air erosion and mold
growth limits of UL-181, stringent fungal resistance test per
ASTM-C1071 and ASTM G21, and shall meet zero level bacteria
growth per ASTM G22. Unit insulation must meet these
stringent requirements or unit(s) will not be accepted.
One (horizontal) to two (vertical) blower and two
compressor compartment access panels shall be ‘lift-out’
removable with supply and return ductwork in place.
A duct collar shall be provided on the supply air opening.
Standard size 1 in. [2.54 cm] MERV 4 fi lters shall be provided
with each unit. Units shall have a return air fi lter rack that
is fi eld convertible from 1 in. [2.54 cm] to 2 in. [5.1 cm]. The
upfl ow vertical units shall have a removable insulated divider
panel between the air handling section and the compressor
section to minimize the transmission of compressor noise
and to permit operational service testing without air bypass.
Vertical units shall be supplied with left or right horizontal air
inlet and top vertical air discharge. Horizontal units shall be
supplied with left or right air inlet and side or end air discharge.
The compressor shall be double isolation mounted using
selected durometer grommets to provide vibration free
compressor mounting. The compressor mounting bracket
shall be acoustically deadened galvanized steel to prevent
vibration transmission to the cabinet.
Option: AlpinePure MERV 13 Filter - A 2 in. thick [51 mm]
MERV 13 fi lter can help fulfi ll a credit under the LEED Rating
System. Its low initial resistance promotes low energy
consumption (0.21 in. w.g. @ 300 fpm) and provides nearly
twice the life of a standard fi lter (300 fpm vs. standard 500
fpm application).
Option: A Super Quiet Sound package shall include multi-
density full coverage compressor blanket.
Option: An internally mounted low pressure drop (high Cv) water solenoid valve shall be factory installed for use in
variable speed pumping applications.
Option: An internally mounted automatic fl ow regulator shall be set to 3 gpm/ton to deliver optimal fl ow to the unit.
Refrigerant CircuitAll units shall utilize the non-ozone depleting and low global
warming potential refrigerant R-410A. All units shall contain
a sealed refrigerant circuit including a hermetic motor-
compressor, bidirectional thermostatic expansion valve,
fi nned tube air-to-refrigerant heat exchanger, reversing
valve, coaxial tube water-to-refrigerant heat exchanger,
optional hot water generator coil, and service ports.
Compressors shall be high-effi ciency single speed rotary or
scroll type designed for heat pump duty and mounted on
vibration isolators. The compressor shall be double isolation
mounted using selected durometer grommets to provide
vibration free compressor mounting. Compressor motors
shall be single-phase PSC with overload protection.
Option: AlumiSeal electro-coated air coil.
The coaxial water-to-refrigerant heat exchanger shall be
designed for low water pressure drop and constructed of
a convoluted copper (cupronickel option) inner tube and
a steel outer tube. Refrigerant to air heat exchangers shall
utilize enhanced corrugated lanced aluminum fi ns and
rifl ed aluminum tube construction rated to withstand 600
psig (4135 kPa) refrigerant working pressure. Refrigerant
to water heat exchangers shall be of copper inner water
tube and steel refrigerant outer tube design, rated to
withstand 600 psig (4135 kPa) working refrigerant
pressure and 450 psig (3101 kPa) working water pressure.
The thermostatic expansion valve shall provide proper
superheat over the entire liquid temperature range with
minimal “hunting.” The valve shall operate bidirectionally
without the use of check valves.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 31
Versatec Variable Speed Series3-6 Tons 60Hz
Engineering Guide Specifi cations cont.Option: Cupronickel refrigerant to water heat exchanger shall be of copper-nickel inner water tube and steel
refrigerant outer tube design, rated to withstand 600 psig
(4135 kPa) working refrigerant pressure and 450 psig (3101
kPa) working water pressure. Water lines shall also be of
cupronickel construction.
Option: Hot water generator - Internal double wall
vented hot water generator coil refrigerant to water heat
exchangers shall be of copper inner water tube and steel
refrigerant outer tube design, rated to withstand 600 psig
(4135 kPa) working refrigerant pressure and 450 psig (3101
kPa) working water pressure.
Option: ThermaShield coated water-to-refrigerant heat exchanger, water lines and refrigerant suction lines
shall be insulated to prevent condensation at low liquid
temperatures below 50°F.
Option: AlpinePure hot gas bypass
Blower Motor and AssemblyThe blower shall be a direct drive centrifugal type with a
dynamically balanced wheel. The housing and wheel shall
be designed for quiet low outlet velocity operation. The
blower housing shall be removable from the unit without
disconnecting the supply air ductwork for servicing of the
blower motor. The blower motor shall be isolated from the
housing by rubber grommets. The motor shall be permanently
lubricated and have thermostatic overload protection.
Variable speed ECM blower motor shall be a variable speed
ECM type. The variable speed ECM blower motor shall be
soft starting, shall maintain constant cfm over its operating
static range, and shall provide 12 cfm settings. Variable
speed ECM motors shall be long-life ball bearing type.
ElectricalA control box shall be located within the unit compressor
compartment and shall contain a 50VA or 75VA transformer,
24 volt activated, 2 pole compressor contactor, terminal
block for thermostat wiring and solid-state controller for
complete unit operation. Electromechanical operation WILL
NOT be accepted. Units shall be name-plated for use with
time delay fuses or HACR circuit breakers. Unit controls shall
be 24 volt and provide heating or cooling as required by the
remote thermostat/sensor.
An Aurora microprocessor-based controller that interfaces
with a multi-stage electronic thermostat to monitor and
control unit operation shall be provided. The control shall
provide operational sequencing, blower speed control,
high and low pressure switch monitoring, freeze detection,
condensate overfl ow sensing, lockout mode control, LED
status and fault indicators, fault memory, fi eld selectable
options and accessory output. The control shall provide fault
retry three times before locking out to limit nuisance trips.
A detachable terminal block with screw terminals will
be provided for fi eld control wiring. All units shall have
knockouts for entrance of low and line voltage wiring. The
blower motor and control box shall be harness plug wired
for easy removal.
Option: An Aurora Unitary Protocol Converter (UPC) shall be included that communicates directly with the Aurora
Heat Pump Controls and allows access/control of a variety
of internal Aurora heat pump operations such as sensors,
relay operation, faults and other information. In turn, the
UPC shall convert the internal Aurora Modbus protocol to
BACnet MS/TP, or N2 protocols for communication over a
BAS system. Additional individual unit confi guration items
such as ECM fan speeds or freeze protection settings shall
be directly available over the BAS without the need for
access to the actual heat pump.
Option: Aurora UPC DDC communication protocols: LonWorks
PipingSupply and return water connections shall be FPT copper
fi ttings fi xed to the corner post, which eliminate the need
for backup pipe wrenches.
With vertical units, the condensate connection shall be a 3/4
in. [19.1 mm] PVC socket with internally-trapped hose that
can be routed to front or side corner post locations.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 32
Versatec Variable Speed Series3-6 Tons 60Hz
Engineering Guide Specifi cations cont.
Hanger Kit(included with horizontal units only - fi eld installed) The hanger kit shall consist of galvanized steel brackets,
bolts, lock washers, and isolators and shall be designed to
fasten to the unit bottom panel for suspension from 3/8 in.
threaded rods. Brackets shall not inhibit fi lter removal in any
way.
AccessoriesThermostat (field-installed)
A communicating auto-changeover electronic digital
thermostat shall be provided. The thermostat shall offer
variable speed heating and cooling staging with precise
temperature control. An OFF-HEAT-AUTO-COOL-EMERG
system switch, OFF-AUTO-INTERMITTENT blower switch,
and indicating display shall be provided. The thermostat
shall display in °F or °C. The thermostat shall provide real
time energy consumption data of the unit.
Color Touchscreen Thermostat (field-installed)
A color touchscreen communicating auto-changeover
electronic digital thermostat shall be provided. The
thermostat shall offer variable speed heating and cooling
staging with precise temperature control. An OFF-
HEAT-AUTO-COOL-EMERG system switch, OFF-AUTO-
INTERMITTENT blower switch, and indicating display shall
be provided. The thermostat shall display in °F or °C. The
thermostat shall provide real time and historical energy
consumption data of the unit.
Hose Kits – Ball Valves (field-installed)
A fl exible steel braid hose featuring Kevlar® reinforced
EPDM core with ANSI 302/304 stainless steel outer braid
and fi re rated materials per ASTM E 84-00 (NFPA 255,
ANSI/UL 723 & UBC 8-1). Ball valve at one end; swivel
connector with adapter at the other end (swivel to adapter
connection via fi ber or EPDM gasket). Swivel connection
provides union between heat pump and piping system. The
hoses feature brass fi ttings, stainless steel ferrules. A full
port ball valve shall be provided with integral P/T (pressure/
temperature) port on supply hose.
Specifi cations:
• Temperature range of 35°F [2°C] to 180°F [82°C].
• Max. working pressure of 400 psi [2757 kPa] for 1/2 in.
and 3/4 in. hose kits; max. working pressure of 350 psi
[kPa] for 1 in. and 1-1/4 in. hose kits.
Hose Kits – Automatic Balancing and Ball Valves(field-installed)A flexible steel braid hose featuring Kevlar® reinforced EPDM
core with ANSI 302/304 stainless steel outer braid and fire
rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL
723 & UBC 8-1). Ball valve at one end; swivel connector with
adapter at the other end (swivel to adapter connection via
fiber or EPDM gasket). Swivel connection provides union
between heat pump and piping system. The hoses feature
brass fittings, stainless steel ferrules. A full port ball valve
shall be provided with integral P/T (pressure/temperature)
port on supply hose and automatic balancing valve with
integral P/T ports and full port ball valve on return hose.
Specifi cations:
• Temperature range of 35°F [2°C] to 180°F [82°C]
• Max. working pressure of 400 psi [2757 kPa] for 1/2 in.
and 3/4 in. hose kits; max. working pressure of 350 psi
[2413 kPa] for 1 in. and 1-1/4 in. hose kits
• Minimum burst pressure of four times working pressure
Hose Kits – Automatic Balancing and Ball Valves with ‘Y’ strainer (field-installed)A fl exible steel braid hose featuring Kevlar® reinforced
EPDM core with ANSI 302/304 stainless steel outer braid
and fi re rated materials per ASTM E 84-00 (NFPA 255,
ANSI/UL 723 & UBC 8-1). Ball valve at one end; swivel
connector with adapter at the other end (swivel to adapter
connection via fi ber or EPDM gasket). Swivel connection
provides union between heat pump and piping system.
The hoses feature brass fi ttings, stainless steel ferrules. A
“y” strainer is provided on one end for fl uid straining and
integral “blowdown” valve. A full port ball valve shall be
provided with integral P/T (pressure/temperature) port on
supply hose and automatic balancing valve with integral P/T
ports and full port ball valve on return hose.
Specifi cations:
• Temperature range of 35°F [2°C] to 180°F [82°C]
• Max. working pressure of 400 psi [2756 kPa] for 1/2 in.
and 3/4 in. hose kits; max. working pressure of 350 psi
[2413 kPa] for 1 in. and 1-1/4 in. hose kits
• Minimum burst pressure of four times working pressure
Hot Water Pump KitAn accessory pump kit is available for hot water generation
option. This kit includes hot water pump, fi ttings, and water
heater kit necessary for potable water application.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2750AU 09/18 33
Versatec Variable Speed Series3-6 Tons 60Hz
Revision Guide
Pages: Description: Date: By:
10 Made Correction to Blower Performance Data Notes 13 Sept 2018 MA
Misc. Removed Waterside Economizer Option, Hot Gas Reheat/Bypass Option 11 July 2017 MA
All Document Creation 20 Dec., 2016 JM