  • 7/27/2019 28pg Technical Info

    1/26

    180 2010 Lttlfu POWR-GARD Product Catalogwww.lttlfu.co

    Section OverviewThis Technical Application Guide or Fuseology section provides the

    inormation needed to select the correct types o Litteluse POWR-GARD

    uses or most applications. I there are any questions or i additional

    data is needed or a specic use, call the Litteluse Technical Supportand Engineering Service Group at 1-800-TEC-FUSE (1-800-832-3873)

    or visit us online at www.litteluse.com.

    Fuseology Fundamentals.................................................... 181-182

    Selection Considerations .................................................... 182-186

    Time-current Curves and Peak Let-through Charts ............. 187-189

    Selective Coordination ........................................................ 189-191

    UL/CSA Fuse Classes and Applications .............................. 192-193

    Electrical Saety Guide ........................................................ 194-195

    Terms and Defnitions ......................................................... 196-202

    Motor Protection Tables ..................................................... 203-205

    Alphanumeric Index o Catalog Numbers ........................... 206-207

    Condensed Fuse Cross Reerence ............................................ 208

    TECHNICAL APPLICATION GUIDE

    Table o Contents

    Additional Technical Information

    An expanded Technical

    Application Guide andFuseology section,

    white papers, and

    a library o technical

    inormation is

    available online at

    www.litteluse.com/technicalcenter.

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    2/26

    181 www.lttlfu.co 2010 Lttlfu POWR-GARD Product Catalog

    FUsEOLOGy FUNDAmENTALs

    I. OVERCURRENT PROTECTION

    FUNDAMENTALS(FUSES AND HOW THEY WORK)

    IntroductionAn important part o developing quality overcurrent protection

    is an understanding o system needs and overcurrent

    protective device undamentals. This section discusses these

    topics with special attention to the application o uses. I

    you have additional questions, call our Technical Support and

    Engineering Services Group at 1-800-TEC-FUSE (1-800-832-

    3873). Denitions o terms used in this section are located

    towards the end o this Technical Application Guide.

    Why Overcurrent Protection?All electrical systems eventually experience overcurrents.

    Unless removed in time, even moderate overcurrents

    quickly overheat system components, damaging insulation,

    conductors, and equipment. Large overcurrents may melt

    conductors and vaporize insulation. Very high currents

    produce magnetic orces that bend and twist bus bars.

    These high currents can pull cables rom their terminals and

    crack insulators and spacers.

    Too requently, res, explosions, poisonous umes and

    panic accompany uncontrolled overcurrents. This not only

    damages electrical systems and equipment, but may cause

    injury or death to personnel nearby.

    To reduce these hazards, the National Electrical Code(NEC), OSHA regulations, and other applicable design and

    installation standards require overcurrent protection that will

    disconnect overloaded or aulted equipment.

    Industry and governmental organizations have developed

    perormance standards or overcurrent devices and testing

    procedures that show compliance with the standards and

    with the NEC. These organizations include: the American

    National Standards Institute (ANSI), National Electrical

    Manuacturers Association (NEMA), and the National

    Fire Protection Association (NFPA), all o which work in

    conjunction with Nationally Recognized Testing Laboratories

    (NRTL) such as Underwriters Laboratories (UL).

    Electrical systems must meet applicable code requirements

    including those or overcurrent protection beore electric

    utilities are allowed to provide electric power to a acility.

    What is Quality Overcurrent Protection?A system with quality overcurrent protection has the

    ollowing characteristics:

    Meets all legal requirements, such as NEC, OSHA, local1.

    codes, etc.

    Provides maximum saety or personnel, exceeding2.

    minimum code requirements as necessary.

    Minimizes overcurrent damage to property, equipment,3.

    and electrical systems.Provides coordinated protection. Only the protective4.

    device immediately on the line side o an overcurrent

    opens to protect the system and minimize unnecessary

    downtime.

    Is cost eective while providing reserve interrupting5.

    capacity or uture growth.

    Consists o equipment and components not subject to6.

    obsolescence and requiring only minimum maintenance

    that can be perormed by regular maintenance personnel

    using readily available tools and equipment.

    Overcurrent Types and Eects

    An overcurrent is any current that exceeds the ampere rating oconductors, equipment, or devices under conditions o use. The

    term overcurrent includes both overloads and short-circuits.

    OverloadsAn overload is an overcurrent conned to normal current

    paths in which there is no insulation breakdown.

    Sustained overloads are commonly caused by installing

    excessive equipment such as additional lighting xtures

    or too many motors. Sustained overloads are also caused

    by overloading mechanical equipment and by equipment

    breakdown such as ailed bearings. I not disconnected

    within established time limits, sustained overloads

    eventually overheat circuit components causing thermaldamage to insulation and other system components.

    Overcurrent protective devices must disconnect circuits and

    equipment experiencing continuous or sustained overloads

    beore overheating occurs. Even moderate insulation

    overheating can seriously reduce the lie o the components

    and/or equipment involved. For example, motors overloaded

    by just 15% may experience less than 50% o normal

    insulation lie.

    Temporary overloads occur requently. Common causes

    include temporary equipment overloads such as a machine

    tool taking too deep o a cut, or simply the starting o an

    inductive load such as a motor. Since temporary overloads

    are by denition harmless, overcurrent protective devices

    should not open or clear the circuit.

    It is important to realize that uses selected must have

    sucient time-delay to allow motors to start and temporary

    overloads to subside. However, should the overcurrent

    continue, uses must then open beore system components

    are damaged. Litteluse POWR-PRO and POWR-GARD

    time-delay uses are designed to meet these types o

    protective needs. In general, time-delay uses hold 500% o

    the rated current or a minimum o ten seconds, yet will still

    open quickly on higher values o current.

    Technical Application Guide

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    3/26

    182

    Technical Application Guide

    2010 Lttlfu POWR-GARD Product Catalogwww.lttlfu.co

    Even though government-mandated high-eciency motors

    and NEMA Design E motors have much higher locked rotorcurrents, POWR-PRO time-delay uses such as the FLSR_

    ID, LLSRK_ID, or IDSR series have sucient time-delay to

    permit motors to start when the uses are properly selected

    in accordance with the NEC.

    Short-CircuitsA short-circuit is an overcurrent fowing outside o its normal

    path. Types o short-circuits are generally divided into

    three categories: bolted aults, arcing aults, and ground

    aults. Each type o short-circuit is dened in the Terms and

    Denitions section.

    A short-circuit is caused by an insulation breakdown or

    aulty connection. During a circuits normal operation, theconnected load determines current. When a short-circuit

    occurs, the current bypasses the normal load and takes a

    shorter path, hence the term short-circuit. Since there is

    no load impedance, the only actor limiting current fow is

    the total distribution systems impedance rom the utilitys

    generators to the point o ault.

    A typical electrical system might have a normal load impedance

    o 10 ohms. But in a single-phase situation, the same system

    might have a load impedance o 0.005 ohms or less. In order

    to compare the two scenarios, it is best to apply Ohms Law (I

    = E/R or AC systems). A 480 volt single-phase circuit with the

    10 ohm load impedance would draw 48 amperes (480/10 = 48).

    I the same circuit has a 0.005 ohm system impedance when

    the load is shorted, the available ault current would increase

    signicantly to 96,000 amperes (480/0.005 = 96,000).

    As stated, short-circuits are currents that fow outside

    o their normal path. Regardless o the magnitude o

    overcurrent, the excessive current must be removed quickly.

    I not removed promptly, the large currents associated

    with short-circuits may have three proound eects on an

    electrical system: heating, magnetic stress, and arcing.

    Heatingoccurs in every part o an electrical system when

    current passes through the system. When overcurrents

    are large enough, heating is practically instantaneous. The

    energy in such overcurrents is measured in ampere-squared

    seconds (I2

    t). An overcurrent o 10,000 amperes that lasts or0.01 seconds has an I2t o 1,000,000 A2s. I the current could

    be reduced rom 10,000 amperes to 1,000 amperes or the

    same period o time, the corresponding I2t would be reduced

    to 10,000 A2s, or just one percent o the original value.

    I the current in a conductor increases 10 times, the I2t

    increases 100 times. A current o only 7,500 amperes

    can melt a #8 AWG copper wire in 0.1 second. Within

    eight milliseconds (0.008 seconds or one-hal cycle), a

    current o 6,500 amperes can raise the temperature o #12

    AWG THHN thermoplastic insulated copper wire rom its

    operating temperature o 75C to its maximum short-circuit

    temperature o 150C. Any currents larger than this may

    immediately vaporize organic insulations. Arcs at the pointo ault or rom mechanical switching such as automatic

    transer switches or circuit breakers may ignite the vapors

    causing violent explosions and electrical fash.

    Magnetic stress(or orce) is a unction o the peak current

    squared. Fault currents o 100,000 amperes can exert orces

    o more than 7,000 lb. per oot o bus bar. Stresses o this

    magnitude may damage insulation, pull conductors rom

    terminals, and stress equipment terminals suciently such

    that signicant damage occurs.

    Arcingat the point o ault melts and vaporizes all o the

    conductors and components involved in the ault. The arcs

    oten burn through raceways and equipment enclosures,

    showering the area with molten metal that quickly starts resand/or injures any personnel in the area. Additional short-circuits

    are oten created when vaporized material is deposited on

    insulators and other suraces. Sustained arcing-aults vaporize

    organic insulation, and the vapors may explode or burn.

    Whether the eects are heating, magnetic stress, and/or

    arcing, the potential damage to electrical systems can be

    signicant as a result o short-circuits occurring.

    II. SELECTION CONSIDERATIONSSelection Considerations or Fuses (600 volts and below)

    Since overcurrent protection is crucial to reliable electricalsystem operation and saety, overcurrent device selection

    and application should be careully considered. When

    selecting uses, the ollowing parameters or considerations

    need to be evaluated:

    Current Rating

    Voltage Rating

    Interrupting Rating

    Type o Protection and Fuse Characteristics

    Current Limitation

    Physical Size

    Indication

    Current RatingThe current rating o a use is the AC or DC current,

    expressed in amperes, which the use is capable o carrying

    continuously under specied conditions. Fuses selected

    or a circuit must have ampere ratings that meet NEC

    requirements, namely those ound in NEC Articles 240 and

    430. These NEC requirements establish maximum ratings

    and in some cases, minimum ratings. When selecting a

    use, it is generally recommended to select a current rating

    as close as possible to the systems normal running current.

    FUsEOLOGy FUNDAmENTALs

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    4/26

    183

    Technical Application Guide

    www.lttlfu.co 2010 Lttlfu POWR-GARD Product Catalog

    Voltage Rating

    The voltage rating o a use is the maximum AC or DCvoltage at which the use is designed to operate. Fuse

    voltage ratings must equal or exceed the circuit voltage

    where the uses will be installed, and uses used in DC

    circuits must be specically rated or DC applications. In

    terms o voltage, uses may be rated or AC only, DC only, or

    both AC and DC. However, exceeding the voltage ratings or

    using an AC only use in a DC circuit could result in violent

    destruction o the use.

    The standard 600 volt rated uses discussed in this section

    may be applied at any voltage less than or equal to their

    rating. For example, a 600 volt use may be used in a 277

    volt or even a 32 volt system, but not any system exceeding

    600 volts.

    NOTE: This does not apply to semiconductor fuses and medium

    voltage fuses. See the semiconductor and medium voltage

    fuse application information on www.littelfuse.com for voltage

    limitations of these fuses.

    Interrupting RatingThe interrupting rating o a use is the highest available

    symmetrical rms alternating current that the use is required

    to saely interrupt at its rated voltage under standardized test

    conditions. A use must interrupt all overcurrents up to its

    interrupting rating without experiencing damage. Standard

    UL uses are available with interrupting ratings o 10,000 A,

    50,000 A, 100,000 A, 200,000 A, and 300,000 A.

    NEC Article 110.9 requires that all equipment intended

    to break current at ault levels have an interrupting rating

    sucient or the system voltage and current available at

    the equipments line terminals. Reer to Figure 1. It is vitally

    important to select uses with interrupting ratings which

    equal or exceed the available ault current.

    The recommendation to standardize on uses with at least

    a 200,000 ampere interrupting rating (AIR) ensures that alluses have an adequate interrupting rating while providing

    reserve interrupting capacity or uture increases in available

    ault current.

    300,000 AIR Fuses

    Litteluse POWR-PRO use series have a Litteluse Sel-

    Certied interrupting rating o 300,000 amperes rms

    symmetrical. The 300,000 ampere testing was perormed

    in a Nationally Recognized Testing Laboratory, and the tests

    were UL witnessed. UL has ruled that uses with a UL

    interrupting rating greater than 200,000 amperes must be

    marked as Special Purpose Fuses and may not be labeled

    as UL Listed Class RK5, RK1, L, etc.

    Type o Protection and Fuse CharacteristicsTime current characteristics determine how ast a use

    responds to overcurrents. All uses have inverse time

    characteristics; that is, the use opening time decreases as

    the magnitude o overcurrent increases. When properly rated

    in accordance with NEC requirements, uses provide both

    overload and short-circuit protection to system conductors

    and components. However, in some instances such as when

    uses are used to backup circuit breakers or to provide motor

    branch circuit short-circuit and ground ault protection, uses

    provide only short-circuit protection. A uses response to

    overcurrents is divided into short-circuits and overloads.

    Short-CircuitsA uses short-circuit response is its opening time on higher-

    value currents. For power uses, higher-value currents are

    generally over 500-600% o the uses current rating. As

    stated earlier, all uses have inverse time characteristics: the

    higher the current, the aster the opening time. Since short-

    circuits should be removed quickly, inverse time is especially

    important or short-circuit protection.

    Overloads

    While uses must disconnect overloaded conductors and

    equipment beore the conductors and components are

    seriously overheated, they should not disconnect harmless

    temporary overloads. To provide sucient overloadprotection or system conductors, UL has established

    maximum use opening times at 135% and 200% o a

    uses current rating. All UL Listed uses or application in

    accordance with the National Electrical Code must meet

    these limits whether they are ast-acting or time-delay uses.

    As just stated, a use is designed to respond to two types

    o overcurrents short circuits and overloads. As a result,

    selecting the proper use or a given application usually

    involves deciding whether to use a time-delay use or a

    ast-acting use. A more in-depth review o both possible

    scenarios is important at this time.

    sELECTION CONsIDErATIONs

    Main Switchboard

    Available Fault

    Current = 125,000A

    Available Fault

    Current = 85,000AAll fuses in main switchboard

    must have an A.I.R. of at least

    125,000A. Next higher standard

    rating is 200,000A.

    Fuses in panel must have at

    least an 85,000 A.I.C. Next higher

    standard rating is 100,000A., but

    best choice is time-delay fuses

    with 200,000 A.I.R.

    Figure 1 Interrupting Rating Requirements per NEC

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    5/26

    184

    Technical Application Guide

    2010 Lttlfu POWR-GARD Product Catalogwww.lttlfu.co

    Fast-Acting (Normal-Opening) Fuses

    Fast-acting uses (sometimes called Normal-openinguses) have no intentional time-delay. Typical opening

    times at 500% o the use ampere rating range rom 0.05

    second to approximately 2 seconds. Fast-Acting uses

    are suitable or non-inductive loads such as incandescent

    lighting and general-purpose eeders, or branch circuits

    with little or no motor load. When protecting motors and

    other inductive loads, ast-acting uses must be rated at

    200-300% o load currents to prevent nuisance opening on

    in-rush currents. Fuses with such increased ratings no longer

    urnish adequate protection rom overloads and only provide

    short-circuit protection. Overload relays or other overload

    protection devices must be provided to properly protect

    conductors and equipment rom overload conditions.

    All ast-acting uses provide ast short-circuit response

    within their interrupting rating. Some are considered current-

    limiting, such as UL Class T and Class J. Others are non-

    current-limiting, such as UL Class H.

    Time-Delay (SLO-BLO) Fuses

    Most UL Class CC, CD, G, J, L, RK5 and RK1 uses, plus

    some o the UL Listed Miscellaneous uses are considered

    time-delay. I so, they are identied as such on the use

    label with the words Time-Delay, T-D, D, or some

    other suitable marking. Minimum time-delay varies with

    the use class, and to some degree with the use ampere

    rating. UL standards or POWR-GARD use series FLNR,

    FLNR_ID, FLSR, FLSR_ID, IDSR (UL Class RK5), LLNRK,LLSRK, LLSRK_ID (UL Class RK1), and JTD, JTD_ID (UL

    Class J) require these uses to carry 500% rated current or a

    minimum o 10 seconds. Standards or CCMR and KLDR (UL

    Class CC and CD) and SLC (UL Class G) uses require them

    to carry 200% rated current or a minimum o 12 seconds.

    Although there is no UL Classication or time-delay Class

    L uses, it is still permissible or them to be marked Time-

    Delay. The amount o time-delay is determined by the

    manuacturer. Litteluse KLPC series and KLLU series uses

    will hold 500% current or 10 seconds or more.

    In addition to providing time-delay or surges and short time

    overloads, time-delay uses meet all UL requirements or

    sustained overload protection. On higher values o current,

    time-delay uses are current-limiting; meaning they remove

    large overcurrents in less than one-hal cycle (0.00833

    seconds). Time-delay uses provide the best overall protection

    or both motor and general purpose circuits, and eliminate

    nuisance use opening and most situations o downtime.

    Compared to ast-acting uses, time-delay uses can be

    selected with ratings much closer to a circuits operating

    current. For example, on most motor circuits Class RK5 and

    RK1 uses can be rated at 125-150% o a motors ull load

    current (FLA). This provides superior overload and short-

    circuit protection, and oten permits the use o smaller,

    less expensive disconnect switches. Time-delay useshave gradually replaced most one-time (UL Class K5) and

    renewable (UL Class H) uses. Today, more than 50% o all

    uses sold by electrical distributors are time-delay uses.

    Dual Element Fuses

    Litteluse time-delay FLNR, FLNR_ID, FLSR, FLSR_ID, IDSR

    (UL Class RK5), and LLNRK, LLSRK, LLSRK_ID (UL Class RK1),

    and some JTD, JTD_ID (UL Class J) series uses have true

    dual-element construction meaning the use has an internal

    construction consisting o separate short-circuit and overload

    sections or elements. Time-delay elements are used or

    overload protection, and separate ast acting use elements or

    links are used to provide current-limiting short-circuit protection.

    Very Fast-Acting Fuses

    This category o uses exists or limited applications. The

    principle use o very ast acting uses is to protect solid-

    state electronic components, such as semiconductors. Fuse

    series designated as Semiconductor Fuses have special

    characteristics including quick overload response, very

    low I2t and Ipeak currents, and peak transient voltages, that

    provide protection or components that cannot withstand

    line surges, low value overloads, or short-circuit currents.

    Very ast-acting uses are designed or very ast response to

    overloads and short-circuits, and are very current-limiting.

    Effect of Ambient Temperature on Fuses

    The current carrying capacity o uses is 110% o the use

    rating when installed in a standard UL test circuit and tested

    in open air at 25C ambient. This allows or derating to 100%

    o rating in an enclosure at 40C ambient. At higher ambient

    temperatures, the continuous current carrying capacity will

    be decreased as shown in Figure 2. This closely ollows

    the derating tables or all electrical equipment and can help

    reduce equipment burnout due to high ambient conditions.

    sELECTION CONsIDErATIONs

    A

    A

    B

    B

    0 0

    20

    40

    60

    20

    40

    60

    AMBIENT TEMPERATURE

    PERCENT

    OFUPRATING

    PERCENTOFDOWNRATING

    KEY TO CHART:

    Curve A - Slo-Blo Fuse

    Curve B - Medium and Fast-Acting Fuses

    -60C

    -76F

    -40C

    -40F

    -20C

    -4F

    0C

    32F

    20C

    68F

    40C

    104F

    60C

    140F

    80C

    176F

    100C

    212F

    120C

    248F

    140C

    264F

    Figure 2 Fuse Rerating Curve

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    6/26

    185

    Technical Application Guide

    www.lttlfu.co 2010 Lttlfu POWR-GARD Product Catalog

    Litteluse time-delay (SLO-BLO) uses derate quicker in

    higher ambient conditions, thus acting as sel-protectingdevices that maintain their integrity until ater opening.

    Current LimitationA current-limiting use is one that opens and clears a ault

    in less than 180 electrical degrees, or in other words, within

    the rst hal electrical cycle (0.00833 seconds). See the

    denition o Current-limiting Fuse and Figure 13in the Terms

    and Denitions section.

    NEC Article 240.2 states that a current-limiting overcurrent

    protective device must reduce the peak let-through current to a

    value substantially less than the potential peak current that would

    have occurred i the use were not used in the circuit or were

    replaced with solid conductors o the same impedance. The totaldestructive heat energy (I2t) to the circuit and its components is

    greatly minimized as a result o using current-limiting uses.

    It is important to note that UL Class H Renewable uses

    designed decades ago are considered non-current limiting. Other

    than Midget uses, almost all other use types used in todays

    electrical systems and applications are considered current-

    limiting per the above parameters. This selection consideration

    now involves determining the degree or level o current

    limitation required to properly protect a given device or system.

    It is also important to point out that matching useholders

    and/or useblocks must reject non-current-limiting uses and

    accept only current-limiting uses o the stated UL Class.

    Physical SizeWhile oten overlooked, the physical size or overall

    dimensions o the use to be used in a given application is

    another important selection consideration to evaluate. There

    is a trend toward reduction o size in almost everything, and

    electrical equipment is no exception. Fuse size is actually

    determined by the size and dimensions o the useblock or

    disconnect switch in which it is installed.

    While saving space may be an important actor when

    selecting the proper uses, other considerations should not

    be overlooked. Some o these include:

    Does the smallest use have the most desirablecharacteristics or the application?

    Does the equipment in which the use will be installed

    provide adequate space or maintenance?

    Do smaller uses coordinate well with the systems other

    overcurrent protection?

    I looking at just physical dimensions, a 600 volt, 60 ampere,

    200,000 AIR, time-delay, dual-element UL Class CD use is smaller

    than a similarly rated UL Class J use, which is in turn, considerably

    smaller than a similarly rated UL Class RK1 or Class RK5 use.

    However, smaller-sized uses can sometimes have less time-delay

    or more nuisance openings than their larger counterparts, so it is

    always important to consider all actors involved.

    IndicationThe newest consideration or selecting the best use or a

    given application is indication. Many o the more commonly

    used UL use classes are now available in both indicating

    and non-indicating versions. Built-in, blown-use indication

    that quickly identies which use or uses within an electrical

    panel or system have blown can be ound on the Litteluse

    POWR-PRO LLSRK_ID Class RK1, FLNR_ID, FLSR_ID and

    IDSR Class RK5, and JTD_ID Class J use series.

    The indicating eature on these uses provides reduced

    downtime, increased saety, and reduced housekeeping or

    troubleshooting headaches and delays. Litteluse Indicator

    uses will help lower the costs associated with downtime,

    provide longer use lie by minimizing nuisance openings,

    increase system perormance by minimizing equipment

    damage, and improve saety by minimizing accidents.

    III. GENERAL FUSING RECOMMENDATIONSBased on the above selection considerations, the ollowing

    is recommended:

    Fuses with ampere ratings rom 1/10 through 600 amperes

    When available ault currents are less than 100,000

    amperes and when equipment does not require the morecurrent-limiting characteristics o UL Class RK1 uses,

    FLNR and FLSR_ID Series Class RK5 current-limiting uses

    provide superior time-delay and cycling characteristics

    at a lower cost than RK1 uses. I available ault currents

    exceed 100,000 amperes, equipment may need the

    additional current-limitation capabilities o the LLNRK,

    LLSRK and LLSRK_ID series Class RK1 uses.

    Fast-acting JLLN and JLLS series Class T uses possess

    space-saving eatures that make them especially suitable

    or protection o molded case circuit breakers, meter

    banks, and similar limited-space applications.

    Time-delay JTD_ID and JTD series Class J uses are used

    in OEM motor control center applications as well as otherMRO motor and transormer applications requiring space-

    saving IEC Type 2 protection.

    Class CC and Class CD series uses are used in control

    circuits and control panels where space is at a premium.

    The Litteluse POWR-PRO CCMR series uses are best

    used or protection o small motors, while the Litteluse

    KLDR series uses provide optimal protection or control

    power transormers and similar devices.

    For questions about product applications, call our Technical

    Support Group at 800-TEC-FUSE.

    sELECTION CONsIDErATIONs

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    7/26

    186

    Technical Application Guide

    2010 Lttlfu POWR-GARD Product Catalogwww.lttlfu.co

    Fuses with ampere ratings rom 601 through 6,000 amperes

    For superior protection o most general-purpose and motor

    circuits, it is recommended to use the POWR-PRO KLPC

    series Class L uses. The Class L uses are the only time-

    delay use series available in these higher ampere ratings.

    Inormation on all the Litteluse use series reerenced above

    can be ound on the UL/CSA Fuse Classes and Applications

    Charts ound later in this Technical Application Guide.

    IV. SELECTION CONSIDERATIONS FORFUSEHOLDERSEqually important to the selection o the proper use is the

    correct selection o the proper useholder or use block ora given application. Fuseholders are available using most o

    the same Selection Considerations outlined above or UL

    use classes. Considerations or useholders include:

    Current Rating

    Voltage Rating

    Interrupting Rating

    Physical Size

    Indication

    Additional selection considerations or useholders and

    useblocks include:

    Number o poles

    Mounting conguration

    Connector type

    Number o PolesThe number o poles or each set o uses is determined by

    the characteristics o the circuit. Most use block series are

    available in 1, 2, or 3 pole congurations, although some are

    also available with our or more poles. The option to gang

    individual useblocks into longer strips will be determined by

    the available space and type o wire being used.

    Mounting Confguration

    Depending on the use block design, another selectionconsideration to evaluate is how the useblock is mounted

    or inserted into the panel. Historically, useblocks simply

    screwed into the back o the panel, but many newer designs

    have now added (or replaced the screw-in design with) a DIN

    rail mounting capability. The DIN rail mounting eature allows

    the blocks to be quickly installed and removed rom the rails.

    Connector TypeFor Litteluse useblocks, a choice o three connector types

    or wire terminations is available:

    Screw or use with spade lugs or ring terminals.

    Screw with Pressure Plate or use with solid orstranded wire without terminal and recommended or

    applications where vibration will be a actor.

    Box Lug the most durable o the three options and

    used with all types o solid wire and Class B and Class C

    stranded wire.

    There are a ew additional aspects to keep in mind when

    selecting the useholder or useblock needed or a given

    application. UL Class H blocks accept Class H, Class K5, and

    Class R uses. Similarly, Midget-style useblocks accept both

    Midget and UL Class CC uses.

    Both UL Class R and Class CC useholders contain a

    rejection eature which prevents the insertion o a dierentClass or type o use. The physical size and dimensions o

    UL Class J and Class T uses accomplish the same thing in

    preventing the insertion o a dierent Class o use as well.

    V. CIRCUIT PROTECTION CHECKLISTTo select the proper overcurrent protective device or an

    electrical system, circuit and system designers should ask

    themselves the ollowing questions beore a system is

    designed:

    What is the normal or average current expected?

    What is the maximum continuous (three hours or more)

    current expected?What inrush or temporary surge currents can be

    expected?

    Are the overcurrent protective devices able to distinguish

    between expected inrush and surge currents, and open

    under sustained overloads and ault conditions?

    What kind o environmental extremes are possible? Dust,

    humidity, temperature extremes and other actors need

    to be considered.

    What is the maximum available ault current the

    protective device may have to interrupt?

    Is the overcurrent protective device rated or the system

    voltage?

    Will the overcurrent protective device provide the saest

    and most reliable protection or the specic equipment?

    Under short-circuit conditions, will the overcurrent

    protective device minimize the possibility o a re or

    explosion?

    Does the overcurrent protective device meet all the

    applicable saety standards and installation requirements?

    Answers to these questions and other criteria will help to

    determine the type overcurrent protection device to use or

    optimum saety, reliability and perormance.

    sELECTION CONsIDErATIONs

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    8/26

    187

    Technical Application Guide

    www.lttlfu.co 2010 Lttlfu POWR-GARD Product Catalog

    The perormance capabilities o various uses are graphically

    represented by two dierent types o use characteristiccurves: time-current curves and peak let-through charts.

    These curves and charts dene the operating characteristics

    o a given use, and assist system designers and engineers

    in selecting the proper use to protect equipment and

    electrical systems.

    Understanding Time-current CurvesTime-current curves provide a graphical representation

    or plot o a uses average melting (opening) time at any

    current. Time-current curves or Litteluse POWR-GARD

    uses can be ound online at

    www.litteluse.com/technicalcenter .

    In order to make the curves more readable, the perormanceinormation is presented on log-log paper. The overcurrent

    values appear across the bottom and increase in magnitude

    rom let to right. Average melting times appear on the

    let-hand side o the curve and increase in magnitude rom

    bottom to top. The ampere ratings o the individual uses

    or a given series are listed at the top and increase in rating

    rom let to right. Figure 4shows the average melting time

    curves or a typical time-delay use series.

    As discussed earlier in the Fuseology Fundamentals

    section, time-delay, ast-acting, and very ast-acting uses

    all respond dierently based on the overcurrents occurring

    in the systems each is protecting. To illustrate the basic

    dierences between each type o use, Figure 5compares

    the average melting times or 100 and 600 amp ratings

    o three use types: Litteluse dual-element, time-delay

    LLSRK series RK1 uses; Litteluse normal opening NLS

    series uses; and Litteluse very ast acting L60S series

    semiconductor uses.

    To better illustrate this point, Table 3also compares the

    opening times or each o these uses.

    Peak Let-through ChartsPeak let-through charts illustrate the maximum instantaneous

    current through the use during the total clearing time. Thisrepresents the current limiting ability o a use.

    Fuses that are current-limiting open severe short-circuits

    within the rst hal-cycle (180 electrical degrees or 0.00833

    seconds) ater the ault occurs. Current-limiting uses also

    reduce the peak current o the available ault current to a

    value less than would occur without the use. This reduction

    is shown in Figure 6.

    A uses current-limiting eects are shown graphically on

    Peak Let-through charts such as the one shown in Figure 7.

    The values across the charts bottom represent the available

    FUsE CHArACTErIsTIC CUrvEs AND CHArTs

    1000800

    600

    400

    300

    200

    10080

    60

    40

    30

    20

    108

    6

    4

    3

    2

    1.8

    .6

    .4

    .3

    .2

    .1.08

    .06

    .04

    .03

    .02

    .01

    200

    300

    400

    600

    800

    1000

    2000

    3000

    4000

    6000

    8000

    10000

    20000

    30000

    40000

    60000

    80000

    100000

    10

    20

    30

    40

    60

    80

    100

    15A

    30A

    60A

    100A

    200A

    400A

    600A

    TIME

    INSECONDS

    CURRENT IN AMPERES

    1000800600

    400

    300

    200

    1008060

    40

    30

    20

    108

    6

    4

    3

    2

    1.8

    .6

    .4

    .3

    .2

    .1.08

    .06

    .04

    .03

    .02

    .01

    200

    300

    400

    600

    800

    1000

    2000

    3000

    4000

    6000

    8000

    10000

    20000

    30000

    40000

    60000

    80000

    100000

    10

    20

    30

    40

    60

    80

    100

    100 AMP

    600 AMP

    GREEN = TIME DELAY FUSE

    RED = NORMAL OPENING FUSEBLUE = VERY FAST ACTING FUSE

    TIMEINSECONDS

    CURRENT IN AMPERES

    AmPErErATING

    FUsE TyPEOPENING TImE IN sECONDs

    500% rATING 800% rATING 1200% rATING

    100

    Time-DeLAy 12 c. 0.9 c. 0.14 c.

    NORmAL OPeNiNG 2 c. 0.7 c. 0.3 c.

    VeRy FAsT-ACTiNG 1.3 c. 0.02 c. >0.01 c.

    600

    Time-DeLAy 14 c. 0 .7 c. 0 .045 c.

    NORmAL OPeNiNG 10 c. 3 c. 1.1 c.

    VeRy FAsT-ACTiNG 2 c. 0 .05 c. >0.01 c.

    Figure 4 Average Melting Time Curves for Typical Time-Delay

    Fuse Series

    Figure 5 Comparison of Average Melting Times for Three Fuse

    Types

    Table 3 Comparative Opening Times for Time-Delay, Fast-

    Acting, and Very Fast-Acting Fuses

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    9/26

    188

    Technical Application Guide

    2010 Lttlfu POWR-GARD Product Catalogwww.lttlfu.co

    (also reerred to as potential or prospective) rms symmetrical

    ault current. The values on the charts let side represent

    the instantaneous available peak current and the peak let-

    through current or various use ratings.

    To better explain the unction o these charts, lets run

    through an example. Start by entering the chart on the

    bottom at 100,000 rms symmetrical amperes and read

    upwards to the A-B line. From this point, read horizontally

    to the let and read the instantaneous peak let-thru current

    o 230,000 amperes. In a circuit with a typical 15% short-

    circuit power actor, the instantaneous peak o the available

    current is approximately 2.3 times the rms symmetrical

    value. This occurs since the A-B line on the chart has a2.3:1 slope.

    The diagonal curves that branch o the A-B line illustrate the

    current-limiting eects o dierent use ampere ratings ora given use series. To continue the example rom above,

    enter the chart in Figure 7on the bottom at 100,000 rms

    symmetrical amperes and read upwards to the intersection

    o the 200 ampere use curve. Now read rom this point

    horizontally to the let and read a peak let-through current o

    approximately 20,000 amperes.

    What this tells us is that the 200 ampere use has reduced

    the peak current during the ault rom 230,000 amperes to

    20,000 amperes. In other words, this is the current-limiting

    eect o the 200 ampere use. 20,000 amperes is less than

    one-tenth o the available current. This is important because

    the magnetic orce created by current fow is a unction o

    the peak current squared. I the peak let-through current oa current-limiting use is one-tenth o the available peak, the

    magnetic orce is reduced to less than 1/100 o what would

    occur without the use.

    Using the Peak Let-through Charts

    (Up-Over-and-Down)Peak Let-through Charts or Litteluse POWR-GARD uses

    can be ound online at www.litteluse.com/technicalcenter.

    These charts are useul in determining whether a given use

    can properly protect a specic piece o equipment.

    For example, given an available ault-current o 100,000

    rms symmetrical amperes, determine whether 600 amp

    250 volt time-delay Class RK1 uses can suciently protectequipment that has a 22,000 amp short-circuit rating. Reer

    to Figure 8.

    Start by locating the 100,000 A available ault-current on the

    bottom o the chart (Point A) and ollow this value upwards

    to the intersection with the 600 amp use curve (Point B).

    Next, ollow this point horizontally to the let to intersect

    with the A-B line (Point C). Finally, read down to the bottom

    o the chart (Point D) to read a value o approximately

    18,000 amps.

    Can the use selected properly protect the equipment or

    this application? Yes, the POWR-PRO LLNRK 600 ampere

    RK1 current-limiting uses have reduced the 100,000amperes available current to an apparent or equivalent

    18,000 amps. When protected by 600 amp LLNRK RK1

    uses, equipment with short-circuit ratings o 22,000 amps

    may be saely connected to a system having 100,000

    available rms symmetrical amperes.

    This method, sometimes reerred to as the Up-Over-and-

    Down method, may be used to:

    Provide back-up short-circuit protection to large air1.

    power circuit breakers.

    Enable non-interrupting equipment such as bus duct to be2.

    FUsE CHArACTErIsTIC CUrvEs AND CHArTs

    Peak Let-through Current

    Peak Current which would occur

    without current limitationCurrent

    Time

    100

    1000000

    200000

    300000

    400000

    600000

    800000

    100000

    20000

    30000

    40000

    60000

    80000

    10000

    2000

    30004000

    6000

    8000

    1000

    200

    300

    400

    600

    800

    100

    200

    300

    400

    600

    800

    1000

    2000

    3000

    4000

    6000

    8000

    10000

    20000

    30000

    40000

    60000

    80000

    100000

    200000

    FUSE

    AMPERE

    RATING

    600

    400

    200

    10060

    30

    A

    B

    AVAILABLE FAULT CURRENT

    SYMMETRICAL R.M.S. AMPERES

    PEAKLET-THRUINAMPERES

    Figure 7 Peak Let-through Charts

    Figure 6 Current limiting effect of fuses

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    10/26

    189

    Technical Application Guide

    www.lttlfu.co 2010 Lttlfu POWR-GARD Product Catalog

    installed in systems with available short-circuit currents

    greater than their short circuit (withstand) ratings.

    However, this method may not be used to select uses or

    backup protection o molded case or intermediate ramecircuit breakers. National Electrical Code (NEC) Article

    240.86 requires Series Ratings. Reer to the NEC or more

    inormation.

    UL Listed use-to-circuit breaker series ratings are now

    available rom most national load center and panelboard

    manuacturers. Listings are shown in their product digests,

    catalogs, and online. Many local builders have also obtained

    use-to-circuit breaker series ratings. For additional

    inormation contact the Litteluse Technical Support Group at

    1-800-TEC-FUSE (1-800-832-3873).

    Short-Circuit Current Rating (SCCR)Since 2005, the NEC has required Industrial Control Panels

    to be labeled with their SCCR. These labels allow users and

    inspectors to compare the SCCR o the equipment to the

    available ault current in order to avoid potential hazards in

    acilities. For additional inormation, the latest specic NEC

    requirements, and solutions on how to increase the SCCR

    or a panel, visit www.litteluse.com/SCCR.

    Selective CoordinationA coordinated or selective system is a system whose

    overcurrent protective devices have been careully chosen and

    their time-current characteristics coordinated.

    Only the overcurrent device immediately on the line side o an

    overcurrent will open or any overload or short-circuit condition.

    To urther clariy, reer to the Terms and Denitions section

    or the denition o Selective Coordination and Figure 15or a

    graphical example.

    Since the advent o electrical and electronic equipment,

    businesses have become entirely dependent on the

    continuous availability o electric energy. Loss o power

    halts all production and order processing, yet expenses

    continue to increase. Even many UPS systems become

    unintentionally non-selective causing power loss to

    computers and other critical equipment. Non-selectivity may

    deeat otherwise well-engineered UPS systems.

    In a selective system, none o this occurs. Overloads andaults are disconnected by the overcurrent protective device

    immediately on the line side o the problem. The amount o

    equipment removed rom service is minimized, the aulted

    or overloaded circuit is easier to locate, and a minimum

    amount o time is required to restore ull service.

    For these and many other reasons, selectivity is the

    standard by which many systems are judged and designed.

    Fuse SelectivityTo get a better sense o how to ensure that uses are

    selectively coordinated within an electrical system, reer

    to Figure 4shown earlier in this Technical Application

    Guide. This gure shows typical average melting time-current curves or one class o uses. Note that the curves

    are roughly parallel to each other and that or a given

    overcurrent, the smaller use ratings respond quicker than

    the larger ratings. The heat energy required to open a use

    is separated into melting I2t and arcing I2t (see denition o

    Ampere-Squared-Seconds). The sum o these is the total

    clearing I2t.

    For a system to be considered coordinated, the smaller

    use total clearing I2t must be less than the larger use

    melting I2t. In other words, i the downstream (branch)

    use opens the circuit beore the overcurrent aects

    the upstream (eeder) use element, the system will be

    considered selective. This can be determined by analyzing

    curves displaying melting and total clearing I2t, or rom

    minimum melting and maximum clearing time-current

    curves.

    But the simplest method o coordinating low voltage power

    uses is by using a Fuse Coordination Table such as the

    one shown in Table 4. This table is only applicable or the

    Litteluse POWR-PRO and POWR-GARD use series listed.

    Tables such as this greatly reduce design time. For example,

    the coordination table shows that POWR-PRO KLPC Class

    L uses coordinate at a two-to-one ratio with other Class L

    uses, with POWR-PRO LLNRK / LLSRK / LLSRK_ID series

    FUsE CHArACTErIsTICs CUrvEs AND CHArTs

    100

    1000000

    200000

    300000

    400000

    600000

    800000

    100000

    20000

    30000

    40000

    60000

    80000

    10000

    2000

    3000

    4000

    6000

    8000

    1000

    200

    300

    400

    600

    800

    100

    200

    300

    400

    600

    800

    1000

    2000

    3000

    4000

    6000

    8000

    10000

    20000

    30000

    40000

    60000

    80000

    100000

    200000

    FUSE

    AMPERE

    RATING

    600

    400

    200

    100

    60

    30

    A

    B

    D A

    BC

    AVAILABLE FAULT CURRENT

    SYMMETRICAL R.M.S. AMPERES

    PEAKLET-THRUINAMPERES

    Figure 8 Peak Let-through Chart for POWR-PRO LLNRK Class

    RK1 Dual-Element Fuses Using the Up-Over-and-Down Method

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    11/26

    190

    Technical Application Guide

    2010 Lttlfu POWR-GARD Product Catalogwww.lttlfu.co

    Class RK1 uses, and POWR-PRO JTD / JTD_ID series Class

    J uses.

    In the system shown in Figure 9, the 3000 amp Class L

    main uses are at least twice the ratings o the 1500, 1200,

    and 1000 amp Class L eeder uses. Using the 2:1 ratio

    just reerenced above, it is determined that these uses

    will coordinate. The Coordination Table also shows that the

    LLSRK_ID series time-delay RK1 eeder and branch circuit

    uses coordinate at a two-to-one ratio with the Class L

    eeder uses, so the entire system in Figure 9would be

    considered 100% coordinated.

    Circuit Breaker CoordinationAs a result o the numerous types o circuit breakers

    and circuit breaker trip units available in todays market,developing a coordinated circuit breaker system or

    coordinating circuit breakers with uses is beyond the scope

    o this Technical Application Guide. For urther questions,

    contact the Litteluse Technical Support Group.

    NEC Requirements or SelectiveCoordination

    Component Short-Circuit Protecting Ability

    As shown in Figure 10, the NEC requires equipment

    protection to be coordinated with overcurrent protective

    devices and the available ault current in order to prevent

    extensive damage to the equipment. Essentially, this

    means that electrical equipment must be capable owithstanding heavy overcurrents without damage or be

    properly protected by overcurrent protective devices that

    will limit damage.

    When a severe ault occurs in an unprotected circuit, current

    immediately increases to a very high value. This is the

    available or prospective ault current. Some uses respond

    so quickly to the increasing current that they interrupt

    current within the rst hal-cycle - or beore the current even

    reaches its rst peak. This is illustrated in Figure 6ound

    earlier in the Technical Application Guide. Such uses are

    termed current-limiting uses.

    Current-limiting uses stop damaging current aster than

    any other protective device, and greatly reduce or totally

    prevent component damage rom high ault currents. This

    perormance capability helps users meet the NEC Article

    110.10 requirements listed in Figure 10.

    Pre-Engineered SolutionsApplicable code requirements also continue to expand with

    each new edition o the National Electrical Code. As o the

    2008 edition o the NEC, the ollowing requirements need to

    be met and can be, utilizing Litteluse POWR-GARD Pre-

    Engineered Solutions:

    NEC 517.26 Healthcare Essential Electrical Systems

    NEC 620.62 Elevators

    NEC 700.27 Emergency Systems

    NEC 701.18 Legally Required Standby Systems

    NEC 708.54 Critical Operations Power Systems

    sELECTIvE COOrDINATION

    LINE-sIDE FUsEs LOAD-sIDE FUsEs

    AmPErE

    rANGEUL CLAss

    LITTELFUsE

    CATALOG NO.

    TImE-DELAy FUsEs

    AmPErE rANGE, UL CLAss AND CATALOG NO.

    FAsT-ACTING FUsEs

    AmPErE rANGE, UL CLAss AND CATALOG NO.

    601-6000 601-4000 30-600 30-600 30-600 30-600 30-1200 30-600 1-60

    L L RK1 J RK5 RK1 T J G

    KLPC

    LDCKLLU

    LLNRK

    LLsRK_iD

    JTD_iD

    JTD

    FLNR_iD

    FLsR_iD

    iDsR

    KLNR

    KLsR

    JLLN

    JLLsJLs sLC

    601-6000 L KLPC 2:1 2:1 2:1 2:1 4:1 2:1 2:1 2:1 N/A

    601-4000 L KLLU 2:1 2:1 2:1 2:1 4:1 2:1 2:1 2:1 N/A

    601-2000 L LDC 2:1 2:1 2:1 2:1 4:1 2:1 2:1 2:1 N/A

    30-600 RK1 LLNRK N/A N/A 2:1 2:1 8:1 3:1 3:1 3:1 4:130-600 RK1 LLsRK_iD N/A N/A 2:1 2:1 8:1 3:1 3:1 3:1 4:1

    30-600 J JTD_iD N/A N/A 2:1 2:1 8:1 3:1 3:1 3:1 4:1

    30-600 RK5 iDsR N/A N/A 1.5:1 1.5:1 2:1 1.5:1 1.5:1 1.5:1 1.5:1

    30-600 RK5 FLNR_iD N/A N/A 1.5:1 1.5:1 2:1 1.5:1 1.5:1 1.5:1 1.5:1

    30-600 RK5 FLsR_iD N/A N/A 1.5:1 1.5:1 2:1 1.5:1 1.5:1 1.5:1 1.5:1

    30-600 RK1 KLNR N/A N/A 3:1 3:1 8:1 3:1 3:1 3:1 4:1

    30-600 RK1 KLsR N/A N/A 3:1 3:1 8:1 3:1 3:1 3:1 4:1

    30-1200 T JLLN N/A N/A 3:1 3:1 8:1 3:1 3:1 3:1 4:1

    30-1200 T JLLs N/A N/A 3:1 3:1 8:1 3:1 3:1 3:1 4:1

    30-600 J JLs N/A N/A 3:1 3:1 8:1 3:1 3:1 3:1 4:1

    1-60 G sLC N/A N/A 3:1 3:1 4:1 2:1 2:1 2:1 2:1

    Table 4 Fuse Coordination Table. Selecting the Correct Fuse Ampere Ratio to Maintain Selectively Coordinated Systems. (Ratios are

    expressed as Line-Side Fuse to Load-Side Fuse.)

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    12/26

    191

    Technical Application Guide

    www.lttlfu.co 2010 Lttlfu POWR-GARD Product Catalog

    The Litteluse product line o Pre-Engineered Solutions

    includes:

    LPS Series POWR-Switch (single elevator shunt-trip

    disconnect switch)

    LPMP Series POWR-Switch Panel (multiple elevator

    shunt-trip disconnect switches)

    LCP Selective Coordination Panel

    These products continue to gain in popularity because they

    meet NEC requirements and oer simple, economical

    solutions or a variety o applications.

    Visit www.litteluse.com/lcp or more inormation

    on Litteluse Pre-Engineered Solution products and

    corresponding selective coordination requirements.

    sELECTIvE COOrDINATION

    KLPC

    3000

    KLPC

    1500

    KLPC

    1200

    KLPC

    1000

    LLSRK

    200

    LLSRK

    200

    LLSRK

    400

    LLSRK

    400

    Figure 9 Example of Selectively Coordinated Fused System

    NATIONAL ELECTRICAL CODE

    ARTICLE 110 Requirements or Electrical Installations

    I. General

    110.3. Examination, Identiication, Installation, and Use o Equipment.

    (A)Examination. In judging equipment, considerations such as the ollowing shall be evaluated:

    (5) Heating eects under normal conditions o use and also under abnormal conditions likely to arise in service.

    (6) Arcing eects.

    (B)Installation and Use. Listed or labeled equipment shall be used or installed in accordance with any instructions included in the listing

    or labeling.

    110.9 Interrupting Rating. Equipment intended to interrupt current at ault levels shall have an interrupting rating not less than the

    nominal circuit voltage and the current that is available at the line terminals o the equipment.

    Equipment intended to interrupt current at other than ault levels shall have an interrupting rating at nominal circuit voltage not less than

    the current that must be interrupted.

    110.10 Circuit Impedance, Short-Circuit Ratings, and Other Characteristics. The overcurrent protective devices, the total

    impedance, the equipment short-circuit current ratings, and other characteristics o the circuit to be protected shall be selected and

    coordinated to permit the circuit protective devices used to clear a ault to do so without extensive damage to the electrical equipment o

    the circuit. This ault shall be assumed to be either between two or more o the circuit conductors or between any circuit conductor and

    the equipment grounding conductor(s) permitted in 250.118. Listed equipment applied in accordance with their listing shall be considered

    to meet the requirements o this section.

    ARTICLE 240 Overcurrent Protection

    240.1 Scope. Parts I through VII o this article provide the general requirements or overcurrent protection and overcurrent protective

    devices not more than 600 volts, nominal. Part VIII covers overcurrent protection or those portions o supervised industrial installations

    operating at voltages o not more than 600 volts, nominal. Part IX covers overcurrent protection over 600 volts, nominal.

    (FPN): Overcurrent protection or conductors and equipment is provided to open the circuit i the current reaches a value that

    will cause an excessive or dangerous temperature in conductors or conductor insulation. See also Articles 110.9 or requirements or

    interrupting ratings and 110.10 or requirements or protection against ault currents.

    (Reproduced by permission o NFPA)

    Figure 10 National Electrical Code Requires Effective Overcurrent Protection

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    13/26

    192

    Technical Application Guide

    2010 Lttlfu POWR-GARD Product Catalogwww.lttlfu.co

    UL/CsA FUsE CLAssEs AND APPLICATIONs

    CLASS LSTANDARDS: UL Standard 248-14,

    CSA Standard C22.2, No. 106, classied as HRCI-L

    VOLTAGE RATING: 600 volts, AC and/or DC

    CURRENT RATINGS: 601-6000 amps

    KLPC also available 200-600A; LDC also available 150-600A

    INTERRUPTING RATING: AC: 200,000 amps rms symmetrical

    DC: 50,000, 100,000, or 200,000 amps

    Not interchangeable with any other UL use class.

    Time delay: Class L uses may be marked Time-Delay although UL does not

    investigate time-delay characteristics o Class L uses.

    KLPC & KLLU: 10 seconds at 500% current rating

    LDC: 4 seconds at 500% current rating

    LF SERIES: KLPC, KLLU, LDC

    PAGES: 11-13

    CLASS RSTANDARDS: UL Standard 248-12,

    CSA Standard C22.2, No. 106, classied as HRCI-R

    VOLTAGE RATINGS: 250 and 600 volts, AC; 125 and 300 volts DC

    CURRENT RATINGS: 0-600 amps

    INTERRUPTING RATING: 200,000 amps rms symmetrical

    TWO CLASSES: RK1 and RK5

    Time delay is optional or Class R uses.

    Time Delay uses are required to hold 500% current rating or a minimum o ten seconds.

    Same dimensions as UL Class H uses, terminals modied to provide rejection eature.

    Fits UL Class R useholders which reject non Class R uses.

    Physically interchangeable with UL Class H, NEMA Class H, and UL Classes K1 &

    K5 when equipment has Class H useholders.

    CLASS KSTANDARDS: UL Standard 248-9; No CSA Standard

    VOLTAGE RATINGS: 250 and 600 volts, AC

    CURRENT RATING: 0-600 amps

    INTERRUPTING RATINGS: Three permitted: 50,000, 100,000, and 200,000 amps

    rms symmetrical

    Time delay is optional or Class K uses.

    Time Delay uses are required to hold 500% current rating or a minimum o ten seconds.

    Same Dimensions and Physically interchangeable with UL Class H useholders.Class K uses are not permitted to be labeled Current Limiting because there is no rejec-

    tion eature as required by NEC Article 240-60(B).

    CLASS JSTANDARDS: UL Standard 248-8,

    CSA Standard C22.2, No. 106, classied as HRCI-JVOLTAGE RATING: 600 volts, AC

    CURRENT RATINGS: 0-600 amps

    INTERRUPTING RATING: 200,000 amps rms symmetrical

    Not interchangeable with any other UL use class.

    Time delay optional: Minimum o 10 seconds at 500% current rating.

    LF SERIES: Time Delay: JTD_ID, JTD

    Fast Acting: JLS

    PAGES: 27-29

    CLASS G

    STANDARDS: UL Standard 248-5CSA Standard C22.2, No. 106, classied as HRCI Misc.

    VOLTAGE RATING: 480 volts, AC

    CURRENT RATINGS: 0-60 amps

    INTERRUPTING RATING: 100,000 amps rms symmetrical

    Not interchangeable with any other UL use class.

    Time delay optional: Minimum o 12 seconds at 200% current rating.

    LF SERIES: SLC

    PAGE: 32

    CLASS RK1High degree o current limitation.

    Provides IEC Type 2 (no damage)

    protection or motor starters and

    control components. Time Delay

    optional, LLSRK_ID Series provides

    visual indication o blown use.

    LF SERIES: Time Delay: LLNRK,

    LLSRK, LLSRK_ID

    Fast Acting: KLNR, KLSR

    PAGES: 16-18

    CLASS RK5Moderate degree o current limita-

    tion, adequate or most applica-

    tions. Time delay optional.

    FLNR_ID, FLSR_ID and IDSR series

    provides visual indication o blown

    use.

    LF SERIES: FLNR, FLNR_ID,

    FLSR, FLSR_ID, and IDSR

    PAGES: 19-22

    CLASS K5Same prescribed degree o current

    limitation as RK5 uses when

    tested at 50,000 or 100,000 amps

    rms symmetrical.

    LF SERIES: NLN, NLS

    PAGE: 24

    CLASS TSTANDARDS: UL Standard 248-15

    CSA Standard C22.2, No. 106, classied as HRCI-T

    VOLTAGE RATINGS: 300 and 600 volts AC, 125 and 300 volts DC

    CURRENT RATINGS: 0-1200 amps

    900 to 1200 amps UL Recognized or 600V version

    INTERRUPTING RATING: 200,000 amps rms symmetrical

    Fast-Acting uses. High degree o current limitation.

    Very small uses; space-saving and non-interchangeable with any other UL use class.

    LF SERIES: JLLN, JLLS

    PAGES: 30-31

    CLASS CC/CDSTANDARDS: UL Standard 248-4,

    CSA Standard C22.2, No. 106, classied as HRCI Misc.

    VOLTAGE RATING: 600 volts, AC

    CURRENT RATINGS: UL Class CC: 0-30 amps

    UL Class CD: 35-60 amps

    INTERRUPTING RATINGS: 200,000 amps rms symmetrical

    Time delay optional: Minimum o 12 seconds at 200% current rating.

    LF SERIES: Time Delay: CCMR (motors), KLDR (transormers)

    Fast Acting: KLKR

    PAGES: 33-35

    CLASS K1Same prescribed degree o current

    limitation as RK1 uses when

    tested at 50,000 or 100,000 amps

    rms symmetrical.

    LF SERIES: Time Delay: LLNRK,

    LLSRK

    Fast Acting: KLNR,

    KLSR

    PAGE: 16

    Overcurrent and short-circuit protection o power and lighting eeders and branch circuits

    Current Limiting

    Fuses which meet the requirements or current limiting uses are required to be labeled Current Limiting. Fuse labels must

    include: UL/CSA use class, manuacturers name or trademark, current rating, AC and/or DC voltage rating, and AC and/or DC

    interrupting rating. Time Delay, D, TD or equivalent may also be included on the label when the use complies with the

    time delay requirements o its class.

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    14/26

    193

    Technical Application Guide

    www.lttlfu.co 2010 Lttlfu POWR-GARD Product Catalog

    UL/CsA FUsE CLAssEs AND APPLICATIONs

    FUSES FOR SUPPLEMENTARY OVERCURRENT PROTECTIONSTANDARDS: UL Standard 248-14; CSA Standard C22.2,

    No. 59-1. Three Classications covered:

    NOTE: Fuses may be rated or AC and/or DC when suitable or

    such use.

    (1) MICRO FUSES

    Voltage ratings: UL, 125 volts; CSA, 0-250 volts

    Current ratings: UL, 0-10 amps; CSA, 0-60 amps

    Interrupting rating: 50 amps rms symmetrical

    (2) MINIATURE FUSES (CSA classies these as Supplemental Fuses)

    Voltage ratings: UL, 125 or 250 volts; CSA, 0-600 volts

    Current ratings: UL, 0-30 amps; CSA, 0-60 amps

    Interrupt ing rating: 10,000 amps rms symmetrical

    (3) MISCELLANEOUS CARTRIDGE FUSES (CSA classies these as

    Supplemental Fuses)

    Voltage ratings: UL, 125 to 600 volts; CSA, 0-600 volts

    Current ratings: UL, 0-30 amps; CSA 0-60 amps

    Interrupting ratings: 10,000, 50,000, or 100,000 amps rms symmetrical

    Time delay (Optional); Minimum delay at 200% use rating:5 seconds or uses rated 3 amps or less

    12 seconds or uses rated more than 3 amps

    LF SERIES: BLF, BLN, BLS, FLA, FLM, FLQ, FLU, KLK, KLKD (600 Volts DC), SPF

    NOTE: Litteluse electronic uses are also covered by these standards; see

    electronic section o this catalog, or request Electronic Designers Guide (Publication

    No. EC101) or complete listing.

    PAGES: 37-39

    SPECIAL PURPOSE FUSESThere are no UL Standards covering this category o uses. These uses have

    special characteristics designed to protect special types o electrical or electronic

    equipment such as diodes, SCR, transistors, thyristors, capacitors, integrally used

    circuit breakers, parallel cable runs, etc.

    Fuses may be UL Recognized or use as a component in UL Listed equipment.

    UL Recognized uses are tested or characteristics such as published interrupting

    capacity. They are also covered by UL re-examination service.

    Non-renewable

    VOLTAGE RATINGS: up to 1000 volts AC and/or DC

    AMPERE RATINGS: up to 6000 amperes

    INTERRUPTING RATINGS: up to 200,000 amperes

    Many o these uses are extremely current limiting. When considering application o

    these uses, or i you have special requirements, contact Litteluse Technical Support

    Group or assistance.

    LF SERIES: KLC, LA15QS, LA30QS, LA50QS, LA60QS, LA60X, LA70QS, LA100P,

    LA120X, LA070URD, LA130URD, L15S, L25S, L50S, L60S, L70S, JLLS 900 amp

    through 1200 amp

    PAGES: 62-81

    CLASS HSTANDARDS: UL Standard 248-6

    CSA Standard C22.2, No. 59.1

    Also known as NEMA Class H, and sometimes reerred to as NEC or Code

    uses

    VOLTAGE RATINGS: 250 and 600 volts, AC

    AMPERE RATINGS: 0-600 amps

    INTERRUPTING RATINGS: 10,000 amps rms symmetrical

    Two types: one-time and renewable

    Physically interchangeable with UL Classes K1 & K5;

    Fits UL Class H useholders which will also accept K1, K5, RK5, and RK1 uses.

    Manuacturers are upgrading Class H One-time uses to Class K5 per UL Standard

    248-9D, See Class K uses.

    ONE-TIME FUSES

    (NON-RENEWABLE)Time delay: Optional

    Time-delay uses must hold 500%

    current rating or a minimum o ten

    seconds.

    LF SERIES: NLKP

    PAGES: 25-26

    RENEWABLE FUSESOnly Class H uses may be renew-

    able. While time delay is optional,

    no renewable uses meet require-

    ments or time delay.

    Some renewable uses have a mod-

    erate amount o time delay, reerredto as time lag to dierentiate

    rom true time delay.

    LF SERIES: RLN, RLS

    REPLACEABLE LINKS SERIES:

    LKN, LKS

    PAGES: 25-26

    PLUG FUSESSTANDARDS: UL Standard 248-11,

    CSA Standard C22.2, No. 59.1

    VOLTAGE RATINGS: 125 volts AC only

    AMPERE RATINGS: 0-30 amps

    INTERRUPTING RATINGS: 10,000 amps rms symmetrical. Interrupting rating

    need not be marked on use.

    Two types: Edison-base and Type S

    EDISON-BASE: Base is same as standard light bulb. All amp ratings interchange

    able. NEC permits Edison-base plug uses to be used only as replacements or

    existing uses, and only when there is no evidence o tampering or overusing.

    TYPE S: Not interchangeable with Edison-base uses unless non-removable Type

    S use adapter is installed in Edison-base use socket. To prevent overusing,

    adapters have three ampere ratings: 10-15, 16-20, and 21-30 amps.

    Time delay: Fuses may be time delay, i so, they are required to hold 200% o rating

    or 12 seconds minimum.

    NOTE: Plug uses may be used where there is not more than 125 volts between

    conductors or more than 150 volts rom any conductor to ground. This permits their

    use in 120/240 volts grounded, single-phase circuits.

    LF SERIES: Edison-base: TOO, TLO

    Type S: SOO, SLO

    Type S Adapters: SAO

    PAGE: 63

    Non-Current Limiting

    Overcurrent and short-circuit protection o power and lighting eeders and branch circuits

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    15/26

    194

    Technical Application Guide

    2010 Lttlfu POWR-GARD Product Catalogwww.lttlfu.co

    ELECTrICAL sAFETy GUIDE

    Introduction

    Electrical saety is an important issue or employers andemployees alike. Unortunately, thousands o electrical

    accidents continue to occur each year resulting in permanent

    disabilities to personnel and excessive medical and

    equipment replacement costs.

    OSHA requirements are oten the motivating actor

    increasing electrical saety in the workplace. OSHA

    continues to increase enorcement activities and is seeking

    to increase penalties or violations.

    Typical OSHA violations related to electrical saety include

    improper Lockout/Tagout, aulty electrical wiring, ailure to

    ollow electrical sae work practices, ailure to assess and

    identiy hazards, ailure to train employees and ailure to

    provide PPE (personal protective equipment) to workers.

    Industry consensus standards such as NFPA 70E, Standard

    or Electrical Saety in the Workplace, has been created

    at the request o OSHA to dene and quantiy electrical

    hazards including Shock, Arc-Flash and Arc-Blast.

    Steps to Electrical Saety Compliance

    Dene the project scope and identiy any current saetyprogram gaps

    Collect data and document your electrical system

    Evaluate your electrical system through engineering

    analysis

    Identiy hazards and re-engineer to reduce hazards

    Label equipment to communicate hazards

    Update or develop an Electrical Saety Program

    Obtain Personnel Protective Equipment (PPE) and

    insulated tools

    Train Personnel

    Maintain and Audit One-Line Drawings and Electrical

    Saety Programs

    OSHA Standard 29 Part 1910 Subpart S (electrical)

    generally addresses electrical saety standards, work

    practices, and maintenance requirements.

    NFPA 70E Standard for Electrical Safety in the Workplace

    is an industry consensus standard that ocuses on saety

    requirements to protect employees. OSHA commonly is

    reerred to as the What or Shall and NFPA 70E as the

    How with regards to electrical saety compliance.

    You MUST assess and identiy all hazards above 50 volts NFPA 70E explains how to perorm a Shock & Arc-Flash Hazard

    Assessment down to 50 volts using tables and calculations

    You MUST put saeguards in place or hazards above 50 volts

    NFPA 70E establishes Hazard Risk Categories, ProtectionBoundaries, LO/TO, PPE requirements and the use o Energized

    Work Permits

    You MUST train employees on sae work practices NFPA 70E denes Qualied and Unqualied workers along with

    training requirements

    WHAT: OSHA REQUIRES YOU...

    TO COMPLY WITH 1910 SUBPART S

    HOW: NFPA 70E MUST BE FOLLOWED...

    TO COMPLY WITH 1910 SUBPART S

    Tabl 5 - Coparon of OsHA and NFPA 70e

    OSHA and NFPA 70E reinorce the need or Electrical

    Hazard Analysis. Electrical Hazard Analysis should address

    all potential hazards including Shock, Arc-Flash, Arc-Blast

    and burns. OSHAs general duty clause requires a workplace

    ree rom hazards and OSHA 1910.132(d) requires employersto identiy hazards and protect workers. NFPA 70E Article

    110.8(B)(1) specically requires Electrical Hazard Analysis

    within all areas o the electrical system that operate at 50

    volts or greater.

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    16/26

    195

    Technical Application Guide

    www.lttlfu.co 2010 Lttlfu POWR-GARD Product Catalog

    ELECTrICAL sAFETy GUIDE

    Sources o Electrical Hazards and Faults

    Exposed energized parts

    Equipment atigue or ailure

    Accidental contact with energized parts

    Worn or broken insulation

    Loose connections

    Improperly maintained equipment or circuit breakers

    Water or liquid near electrical equipment

    Obstructions near or on equipment

    Improper grounding

    Types o Electrical Faults

    It is well documented and estimated that 95% o electricalaults start as ground aults. The remaining 5% are either

    phase-to-phase or three-phase aults. So in essence, i we

    are able to eliminate phase-to-ground aults, or 95% o all

    aults, we have essentially reduced the potential or 95%

    o the Arc-Flash Hazard, making the electrical system much

    saer.

    Reducing Electrical Hazards

    There are many methods and practices or reducing Arc-Flash and other electrical hazards while conorming to

    OSHA, NEC, and NFPA 70E regulations and guidelines.

    Circuit designers and electrical engineers should careully

    consider the ollowing recommendations:

    Design the hazard out o the system through engineering

    design and component selection

    Identiy and assess electrical hazards

    Use and upgrade to current-limiting overcurrent

    protective devices

    Implement an Electrical Saety Program

    Observe sae work practices

    Use properly selected Personal Protective Equipment

    (PPE) including insulated tools

    Use Warning Labels to identiy and communicate

    electrical hazards

    Enorce Lockout/Tagout procedures and use Energized

    Electrical Work Permits

    Increase system protection by achieving Selective

    Coordination and using Ground Fault Protection devices.LEADING INITIATOrs OF FAULTs % OF ALL FAULTs

    Exposure to moisture 22.5%

    Shortening by tools, rodents, etc. 18.0%

    Exposure to dust 14.5%

    Other mechanical damage 12.1%Exposure to chemicals 9.0%

    Normal deterioration from age 7.0%

    Tabl 6 - Ladng ntator of lctrcal fault

    exapl of warnng labl

    WARNINGArc-Flash and Shock Hazard

    Appropriate PPE Required

    Warning: Changes in equipment settings or systemconfiguration will invalidate the calculated values andPPE requirements

    Equipment: TX-38 Pri

    Protection: NE-38

    9 inches Flash Hazard Boundary0.35 cal/cm2 Flash Hazard at 18 inches

    Untreated Cotton LS Shirt/ Pants,Category 0 Safety Glasses, Ear Plugs, V-Rated Tools/

    Gloves (AN), Leather Gloves (AN)

    480 VAC Shock Hazardwhen cover is removed00 Glove Class42 inches Limited Approach12 inches Restricted Approach1 inch Prohibited Approach

    Prepared on: 7/26/10 By:

    For more inormation on Electrical Saety, visit

    www.litteluse.com/services

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    17/26

    196

    Technical Application Guide

    2010 Lttlfu POWR-GARD Product Catalogwww.lttlfu.co

    Adjustable Alarm Level A setting on a protection relay at

    which an LED or an output contact operates to activate a visualor audible alarm.

    Adjustable Time Delay A setting on a protection relay that

    determines the time between the ault detection and relay

    operation.

    AIC or A.I.C. See Interrupting Capacity.

    AIR or A.I.R. See Interrupting Rating.

    Alarm Relay Contact The output o the relay that acts as a

    switch and is connected to a visual or audible alarm.

    Ambient Temperature The air temperature surrounding a

    device. For uses or circuit breakers in an enclosure, the air

    temperature within the enclosure.

    Ampacity The current in amperes that a conductor can carry

    continuously under the conditions o use without exceeding

    its temperature rating. It is sometimes inormally applied to

    switches or other devices which are more properly reerred to

    by their ampere rating.

    Ampere Rating The current rating, in amperes, that is

    marked on uses, circuit breakers, or other equipment.

    Ampere-Squared-Seconds (I2t) A means o describing the

    thermal energy generated by current fow. When a use is

    interrupting a current within its current-limiting range, the term

    is usually expressed as melting, arcing, or total clearing I2t.

    Melting I 2t is the heat energy passed by a use ater anovercurrent occurs and until the use link melts. It equals

    the rms current squared multiplied by the melting time in

    seconds. For times less than 0.004 seconds, melting I2t

    approaches a constant value or a given use.

    Arcing I 2t is the heat energy passed by a use during its

    arcing time. It is equal to the rms arcing current squared (see

    denition below), multiplied by arcing time.

    Clearing I 2t (also Total Clearing I2t) is the ampere-squared

    seconds (I2t) through an overcurrent device rom the

    inception o the overcurrent until the current is completely

    interrupted. Clearing I2t is the sum o the Melting I2t plus the

    Arcing I2t.

    Analog Output A 01 mA, 420 mA or 05 Vdc signal rom

    a protection relay used to pass inormation to a device or

    controller.

    Arc-Blast A pressure wave created by the heating, melting,

    vaporization, and expansion o conducting material and

    surrounding gases or air.

    Arc-Flash The sudden release o heat energy and intense

    light at the point o an arc. Can be considered a short-circuit

    through the air, usually created by accidental contact between

    live conductors.

    Arc Gap The distance between energized conductors or

    between energized conductors and ground. Shorter arc gapsresult in less energy being expended in the arc, while longer

    gaps reduce arc current. For 600 volts and below, arc gaps o

    1.25 inches (32 mm) typically produce the maximum incident

    energy.

    Arc Rating A rating assigned to material(s) that relates to the

    maximum incident energy the material can resist beore break

    open o the material or onset o a second-degree burn. The arc

    rating is typically shown in cal/cm.

    Arcing Current (See Figure 11) The current that fows

    through the use ater the use link has melted and until the

    circuit is interrupted.

    Figure 11 Arcing and melting currents plus arcing, melting and

    clearing times

    Arcing I2t See Ampere-Squared-Seconds (I2t).

    Arcing Fault A short-circuit that arcs at the point o ault. The

    arc impedance (resistance) tends to reduce the short-circuit

    current. Arcing aults may turn into bolted aults by welding o

    the aulted components. Arcing aults may be phase-to-phase

    or phase-to-ground.

    Arcing Time (See Figure 11) The time between the melting

    o a use link or parting o circuit breaker contacts, until the

    overcurrent is interrupted.

    Arc Voltage (See Figure 12) Arc voltage is a transient voltage

    that occurs across an overcurrent protection device during

    the arcing time. It is usually expressed as peak instantaneous

    voltage (Vpeak or Epeak), or on rare occasion as rms voltage.

    Asymmetrical Current See Symmetrical Current.

    Available Short-Circuit Current (also Available or

    Prospective Fault Current) The maximum rms Symmetrical

    Current that would fow at a given point in a system under

    bolted-ault conditions. Short-circuit current is maximum during

    the rst hal-cycle ater the ault occurs. See denitions o

    Bolted Fault and Symmetrical Current.

    TErms AND DEFINITIONs

    Peak Let-through Current

    Peak Current which would occur

    without current limitationCurrent

    Time

    MeltingTime

    ArcingCurrent

    ArcingTime

    MeltingCurrent

    Arcing Energy (l2t)

    Melting Energy (l2t)

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    18/26

    197

    Technical Application Guide

    www.lttlfu.co 2010 Lttlfu POWR-GARD Product Catalog

    Blade Fuse See Knie Blade Fuse.

    Body The part o a use enclosing the use elements and

    supporting the contacts. Body is also reerred to as cartridge,

    tube, or case.

    Bolted Fault A short-circuit that has no electrical resistanceat the point o the ault. It results rom a rm mechanical

    connection between two conductors, or a conductor and

    ground. Bolted aults are characterized by a lack o arcing.

    Examples o bolted aults are a heavy wrench lying across two

    bare bus bars, or a crossed-phase condition due to incorrect

    wiring

    Boundaries o Approach Protection boundaries established

    to protect personnel rom shock and Arc-Flash hazards.

    Calorie The amount o heat needed to raise the temperature

    o one gram o water by one degree Celsius.1 cal/cm is

    equivalent to the exposure on the tip o a nger by a cigarette

    lighter or one second.

    Cartridge Fuse A use that contains a current-responsive

    element inside a tubular use body with cylindrical errules (end

    caps).

    Case Size (also Cartridge Size) The maximum allowable

    ampere rating o a cartridge use having dened dimensions

    and shape. For example, case sizes or UL Listed Class H, K, J,

    RK1, and RK5 are 30, 60, 100, 200, 400, and 600 amperes. The

    physical dimensions vary with use class, voltage, and ampere

    rating. UL Standards establish the dimensions or each UL

    Fuse Class. This catalogs product section contains case size

    dimensions or all Litteluse POWR-GARD uses.

    Clearing I2t See Ampere-Square-Seconds (I2t).

    Clearing Time (see Figure 11) The time between the

    initiation o an overcurrent condition to the point at which the

    overcurrent is interrupted. Clearing Time is the sum o Melting

    Time and Arcing Time.

    Conormal Coating Coating used to protect circuit boards

    rom pollutants, corrosion, and mildew.

    Contacts (Fuse) The external metal parts o the use used to

    complete the circuit. These consist o errules, caps, blades or

    terminals, as shown in this catalog.

    Coordination or Coordinated System See Selective

    Coordination.Continuous Load An electrical load where the maximum

    current is expected to continue or three hours or more.

    CT Loop The electrical circuit between a current transormer

    and a protection relay or monitoring device.

    Current-Based Protection Protection parameters (trip-levels/

    data collection etc.) derived rom current levels in a circuit.

    Current-limiting Fuse (See Figure 13) A use which, when

    interrupting currents within its current-limiting range, reduces

    the current in the aulted circuit to a magnitude substantially

    less than that obtainable in the same circuit i the device was

    replaced with a solid conductor having comparable impedance.

    To be labeled current limiting, a use must mate with auseblock or useholder that has either a rejection eature or

    dimensions that will reject non-current-limiting uses.

    Figure 13 Current-limiting Fuse

    Current-limiting Range - For an individual overcurrent

    protective device, the current-limiting range begins at the

    lowest value o rms symmetrical current at which the device

    becomes current-limiting (the threshold current) and extends

    to the maximum interrupting capacity o the device. See

    denitions o Threshold Current and Interrupting Capacity.

    Current Rating See Ampere Rating.

    Current Transormer (CT) A transormer that produces a

    current in its secondary circuit in a known proportion to current

    in its primary circuit.

    Data Logging Collecting and storing inormation in a

    ormat that can be reviewed or trending, troubleshooting and

    reporting.

    DFT (Discrete Fourier Transorm) Harmonic Filter An

    algorithm used to measure the undamental component o

    current and voltage and reject harmonics. This allows lower trip

    settings and eliminates nuisance trips due to harmonics.

    TErms AND DEFINITIONs

    INSTANTANEOUS ARC VOLTAGE

    183% OF CYCLEPEAK

    RESTORED VOLTAGE

    PEAK

    Current

    TimeFault occurs

    Arc is extinguished

    Current which

    would flow if

    not interrupted

    Current before fault

    Fuse opens andclears short circuit

    in less than cycle

    Figure 12 Transient overvoltage during arcing time

    ourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineeri

  • 7/27/2019 28pg Technical Info

    19/26

    198

    Technical Application Guide

    2010 Lttlfu POWR-GARD Product Catalogwww.lttlfu.co

    Distance to Arc Reers to the distance rom the receiving

    surace to the arc center. The value used or most calculationsis typically 18 inches.

    Dual-Element Fuse A use with internal construction

    consisting o a separate time-delay overload element(s) that

    interrupts overcurrents up to approximately 500%-600% o its

    nominal rating, plus separate use links that quickly open higher

    value currents. All dual-element uses have time delay, but,

    since there are other methods o achieving time delay, not all

    time-delay uses have dual-element construction. See Time-

    Delay Fuse.

    EFCT (Earth Fault Current Transormer) A current

    transormer engineered to accurately detect low level ground-

    ault current.

    Electrical Hazard Analysis A study perormed to identiy the

    potential electrical hazards to which personnel may be exposed.

    The analysis should address both shock and Arc-Flash hazards.

    Electrically Sae Work Condition Condition where the

    equipment and or circuit components have been disconnected

    rom electrical energy sources, locked/tagged out, and tested to

    veriy all sources o power are removed.

    Element A uses internal current-carrying components that

    melt and interrupt the current when subjected to an overcurrent

    o suc