CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 2
Europe
General requirements
Requirements for non-hazardous apply
Electrical apparatus only to be used within
their electrical ratings for power
Hazardous areas divided in to Zones
Documentation
Area classification documents
Instructions for erection and connection
Documents for apparatus with special condit ions
marked with an X
Installation IEC 60079-14
7/27/2019 26 Juni Inspection and Maintenance Electrical
3/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 3
Europe
Installation IEC 60079-14
Assurance of Conformity of Apparatus
Certification
Selection of Apparatus
Specific information
Selection according to Zones
Selection according to Temperature Class
Selection according to Apparatus Class
External influences
7/27/2019 26 Juni Inspection and Maintenance Electrical
4/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 4
Europe
Check l ist - Apparatus
is appropriate to area classification
explosion group is correct
temperature class is correct
documentation is complete
no damage
no inadmissable modifications
bolts, cable entries etc. complete and tight
seals and gaskets satisfactoryelectrical connections are tight
lamp ratings, type and posit ion correct
flameparths within max. values and clean "d"
special conditions of use are complied with " i"
7/27/2019 26 Juni Inspection and Maintenance Electrical
5/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 5
Europe
Check l ist - Installation
Cable and wiring as selected
Cable and wiring earthed as required
Cable and wiring is not damaged
Cable entries correctly closed
Cable glands correct
No inadmissible bunching of cables
Fulfi lment of all special requirements
Proper function of all protective devicesInstallation corresponds to documentation
Potential equalization correct
Eletrostatic at safe level
Lightning protection according to the rules
Emergency switch-off according to the rules
Purg time is sufficient ("p")
7/27/2019 26 Juni Inspection and Maintenance Electrical
6/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 6
Europe
Check l ist - Installation
Electrical circui ts "e" and " i" separated
Ingress protection sufficient
Mechanical protection sufficient
Thermal protection suff icient
Chemical protection suff icient
7/27/2019 26 Juni Inspection and Maintenance Electrical
7/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 7
Europe
Inspection and MaintenanceIEC 60079-17
Maintenance to retain or restore to original spec. so to
perform its correct function
7/27/2019 26 Juni Inspection and Maintenance Electrical
8/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 8
Europe
Inspection -scrutiny with or without partial dismantling, and if necessary
measurement to reach a conclusion on the condition of the
apparatus
visual - inspection which identifies, without the use of
access equipment or tools, those defects, such as
missing bolts, which will be apparent to the eye close - aspects covered by a visual inspection and, in
addition, identif ies those defects, such as loose
bolts, which will be apparent only by the use of access
equipment, for example steps, (where necessary),
and tools
7/27/2019 26 Juni Inspection and Maintenance Electrical
9/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 9
Europe
Inspection
detailed - aspects covered by a visual inspection and,
in addition, identifies those defects, such as loose
terminations, which will only be apparent by opening
the enclosure, and/or using, where necessary, tools
and test equipment
init ial - inspection of all electrical apparatus, systems and
installations before they are brought into service
7/27/2019 26 Juni Inspection and Maintenance Electrical
10/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 10
Europe
Inspection
periodic - inspection of all electrical apparatus, systems
and installations carried out on routine basis
sample - inspection of a proport ion of the electrical
apparatus, systems and installations
continuous supervision - frequent attendance, inspection,service, care and maintenance of the electrical installation
by skilled personnel who have experience in the specif ic
installation and its environment in order to maintain the
explosion protection features of the installation in
satisfactory condition
7/27/2019 26 Juni Inspection and Maintenance Electrical
11/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 11
Europe
General requirements
documentation -
area classification
apparatus group and temperature class
technical information, spares lists, manufacturers
instructions etc. qualif ication of personnel -
experienced and trained personnel, with knowledge of types
of protection, installation practices, relevant rules and
regulations. With evidence of relevant experience and training
7/27/2019 26 Juni Inspection and Maintenance Electrical
12/21
7/27/2019 26 Juni Inspection and Maintenance Electrical
13/21
7/27/2019 26 Juni Inspection and Maintenance Electrical
14/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 14
Europe
Maintenance requirements
Remedial measures and alterations
maintain the integrity of the type of protection provided for
the apparatus; this may require consultation with the
manufacturer. Replacement parts shall be in accordance with
the safety documentation.
Alterations to apparatus shall not be carried out without
appropriate authorization where they adversely affect the
safety of the apparatus as stated in the safety documentation.
7/27/2019 26 Juni Inspection and Maintenance Electrical
15/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 15
Europe
Maintenance requirements
Maintenance of f lexible cables
Flexible cables, flexible conduits and their terminations are
particularly prone to damage. They shall be inspected at
regular intervals and shall be replaced if found to be
damaged or defective.
7/27/2019 26 Juni Inspection and Maintenance Electrical
16/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 16
Europe
Maintenance requirements
Withdrawal from service
If it is necessary, for maintenance purposes, to withdraw
apparatus, etc. from service, the exposed conductors shall be
a) correctly terminated in an appropriate enclosure, or
b) isolated from all sources of power supply and insulated, or
c) isolated from all sources of power supply and earthed.
If the apparatus is to be permanently withdrawn from service,
the associated wiring, which shall be isolated from all
sources of power supply, shall be removed, or, alternatively,correctly terminated in an appropriate enclosure.
7/27/2019 26 Juni Inspection and Maintenance Electrical
17/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 17
Europe
Maintenance requirements
Fastenings and tools
Where special bolts and other fastenings or special tools
are required, these items shall be available and shall be used.
Environmental conditions Electrical apparatus in a hazardous area can be adverselyaffected by the environmental conditions in which it is used.
Some of the key elements to consider are corrosion, ambient
temperature, ultraviolet radiation, ingress of water,
accumulation of dust or sand, mechanical effects and
chemical attack.
7/27/2019 26 Juni Inspection and Maintenance Electrical
18/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 18
Europe
7/27/2019 26 Juni Inspection and Maintenance Electrical
19/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 19
Europe
7/27/2019 26 Juni Inspection and Maintenance Electrical
20/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 20
Europe
7/27/2019 26 Juni Inspection and Maintenance Electrical
21/21
CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 21
Europe