    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 2

    Europe

    General requirements

    Requirements for non-hazardous apply

    Electrical apparatus only to be used within

    their electrical ratings for power

    Hazardous areas divided in to Zones

    Documentation

    Area classification documents

    Instructions for erection and connection

    Documents for apparatus with special condit ions

    marked with an X

    Installation IEC 60079-14

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    3/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 3

    Europe

    Installation IEC 60079-14

    Assurance of Conformity of Apparatus

    Certification

    Selection of Apparatus

    Specific information

    Selection according to Zones

    Selection according to Temperature Class

    Selection according to Apparatus Class

    External influences

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    4/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 4

    Europe

    Check l ist - Apparatus

    is appropriate to area classification

    explosion group is correct

    temperature class is correct

    documentation is complete

    no damage

    no inadmissable modifications

    bolts, cable entries etc. complete and tight

    seals and gaskets satisfactoryelectrical connections are tight

    lamp ratings, type and posit ion correct

    flameparths within max. values and clean "d"

    special conditions of use are complied with " i"

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    5/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 5

    Europe

    Check l ist - Installation

    Cable and wiring as selected

    Cable and wiring earthed as required

    Cable and wiring is not damaged

    Cable entries correctly closed

    Cable glands correct

    No inadmissible bunching of cables

    Fulfi lment of all special requirements

    Proper function of all protective devicesInstallation corresponds to documentation

    Potential equalization correct

    Eletrostatic at safe level

    Lightning protection according to the rules

    Emergency switch-off according to the rules

    Purg time is sufficient ("p")

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    6/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 6

    Europe

    Check l ist - Installation

    Electrical circui ts "e" and " i" separated

    Ingress protection sufficient

    Mechanical protection sufficient

    Thermal protection suff icient

    Chemical protection suff icient

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    7/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 7

    Europe

    Inspection and MaintenanceIEC 60079-17

    Maintenance to retain or restore to original spec. so to

    perform its correct function

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    8/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 8

    Europe

    Inspection -scrutiny with or without partial dismantling, and if necessary

    measurement to reach a conclusion on the condition of the

    apparatus

    visual - inspection which identifies, without the use of

    access equipment or tools, those defects, such as

    missing bolts, which will be apparent to the eye close - aspects covered by a visual inspection and, in

    addition, identif ies those defects, such as loose

    bolts, which will be apparent only by the use of access

    equipment, for example steps, (where necessary),

    and tools

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    9/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 9

    Europe

    Inspection

    detailed - aspects covered by a visual inspection and,

    in addition, identifies those defects, such as loose

    terminations, which will only be apparent by opening

    the enclosure, and/or using, where necessary, tools

    and test equipment

    init ial - inspection of all electrical apparatus, systems and

    installations before they are brought into service

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    10/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 10

    Europe

    Inspection

    periodic - inspection of all electrical apparatus, systems

    and installations carried out on routine basis

    sample - inspection of a proport ion of the electrical

    apparatus, systems and installations

    continuous supervision - frequent attendance, inspection,service, care and maintenance of the electrical installation

    by skilled personnel who have experience in the specif ic

    installation and its environment in order to maintain the

    explosion protection features of the installation in

    satisfactory condition

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    11/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 11

    Europe

    General requirements

    documentation -

    area classification

    apparatus group and temperature class

    technical information, spares lists, manufacturers

    instructions etc. qualif ication of personnel -

    experienced and trained personnel, with knowledge of types

    of protection, installation practices, relevant rules and

    regulations. With evidence of relevant experience and training

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    12/21

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    13/21

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    14/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 14

    Europe

    Maintenance requirements

    Remedial measures and alterations

    maintain the integrity of the type of protection provided for

    the apparatus; this may require consultation with the

    manufacturer. Replacement parts shall be in accordance with

    the safety documentation.

    Alterations to apparatus shall not be carried out without

    appropriate authorization where they adversely affect the

    safety of the apparatus as stated in the safety documentation.

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    15/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 15

    Europe

    Maintenance requirements

    Maintenance of f lexible cables

    Flexible cables, flexible conduits and their terminations are

    particularly prone to damage. They shall be inspected at

    regular intervals and shall be replaced if found to be

    damaged or defective.

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    16/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 16

    Europe

    Maintenance requirements

    Withdrawal from service

    If it is necessary, for maintenance purposes, to withdraw

    apparatus, etc. from service, the exposed conductors shall be

    a) correctly terminated in an appropriate enclosure, or

    b) isolated from all sources of power supply and insulated, or

    c) isolated from all sources of power supply and earthed.

    If the apparatus is to be permanently withdrawn from service,

    the associated wiring, which shall be isolated from all

    sources of power supply, shall be removed, or, alternatively,correctly terminated in an appropriate enclosure.

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    17/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 17

    Europe

    Maintenance requirements

    Fastenings and tools

    Where special bolts and other fastenings or special tools

    are required, these items shall be available and shall be used.

    Environmental conditions Electrical apparatus in a hazardous area can be adverselyaffected by the environmental conditions in which it is used.

    Some of the key elements to consider are corrosion, ambient

    temperature, ultraviolet radiation, ingress of water,

    accumulation of dust or sand, mechanical effects and

    chemical attack.

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    18/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 18

    Europe

  • 7/27/2019 26 Juni Inspection and Maintenance Electrical

    19/21

    CEAG Sicherheitstechnik GmbHInst & Maint 250804.ppt/01.08.2002/Eg/ Page 19

    Europe