Upload
nikola-andjelic
View
41
Download
1
Embed Size (px)
DESCRIPTION
mhgcfjfchgcghx
Citation preview
Electrical Power and Energy Systems 32 (2010) 849–856
Contents lists available at ScienceDirect
Electrical Power and Energy Systems
journal homepage: www.elsevier .com/locate / i jepes
Optimal sizing and placement of distributed generation in a network system
Sudipta Ghosh *, S.P. Ghoshal, Saradindu GhoshDepartment of Electrical Engineering, National Institute of Technology, Durgapur 713209, India
a r t i c l e i n f o
Article history:Received 28 March 2009Received in revised form 22 December 2009Accepted 28 January 2010
Keywords:Distributed generation (DG)Newton Raphson (N-R)Objective function (OF)Weighting factor
0142-0615/$ - see front matter � 2010 Elsevier Ltd. Adoi:10.1016/j.ijepes.2010.01.029
* Corresponding author. Tel.: +91 98321 54472.E-mail address: [email protected] (S. Ghosh).
a b s t r a c t
With ever-increasing demand of electricity consumption and increasing open access particularly inrestructured environment, transmission line congestion is quite frequent. For maximum benefit and mit-igation of congestion, proper sizing and position of distributed generators are ardently necessary. Thispaper presents a simple method for optimal sizing and optimal placement of generators. A simple con-ventional iterative search technique along with Newton Raphson method of load flow study is imple-mented on modified IEEE 6 bus, IEEE 14 bus and IEEE 30 bus systems. The objective is to lower downboth cost and loss very effectively. The paper also focuses on optimization of weighting factor, which bal-ances the cost and the loss factors and helps to build up desired objectives with maximum potentialbenefit.
� 2010 Elsevier Ltd. All rights reserved.
1. Introduction
Electric utilities are now seeking upcoming new technologies toprovide acceptable power quality and higher reliability to theircustomers in restructured environment. Non-conventional genera-tion is growing more rapidly around the world, for its low size, lowcost and less environmental impact with high potentiality [1–3].Investments in distributed generation (DG) enhance environmen-tal benefits particularly in combined heat and power applications.
A multitude event, such as, system efficiency, environmentalbenefits and transmission congestion management have createda new arena in electric power system. The key element of thisnew arena is to operate several DG units near load centers insteadof expanding central generation station. DG may come from a vari-ety of sources and technologies. DGs from renewable sources, likewind, solar and biomass are often called as ‘Green energy’. In addi-tion to this, DG includes micro-turbines, gas turbines, diesel en-gines, fuel cells, stirling engines and internal combustionreciprocating engines [4–6]. Now-a-days, wind energy has becomethe most competitive among all the renewable energy availablewith us [7]. DG refers to small sources ranging between 1 kWand 50 MW electrical power generations, which are normallyplaced close to consumption centers. So, DG means a generationunit, which is connected to the distribution network rather thanthe high voltage transmission network.
DG renders a group of advantages, such as, economical, environ-mental and technical. The economical advantages are reduction oftransmission and distribution cost, electricity price and saving of
ll rights reserved.
fuel. Environmental advantages entail reductions of sound pollu-tion and emission of green house gases. Technical advantages cov-er wide varieties of benefit, like, line loss reduction, peak shaving,increased system voltage profile and hence increased power qual-ity and relieved transmission and distribution congestion as wellas grid reinforcement. It can also provide the stand-alone remoteapplications with the required power. So, optimal placement ofDGs and optimal sizing attract active research interests. Severalresearchers have worked in this area [8–14]. DGs are placed atoptimal locations to reduce only losses [8]. Some researchers pre-sented some power flow algorithms to find the optimal size of DGat each load bus [9,10]. Wang and Nehrir have shown analyticalapproaches for optimal placement of DG in terms of loss [11]. Chir-adeja has quantified the benefit of reduced line loss in radial distri-bution feeder with concentrated load [12]. Further, manyresearchers have used evolutionary computational methods forfinding the optimal DG placement [15–20]. Mithulananthan hasused GA for placement of DG to reduce the losses [16]. Celli andGhiani have used a multiobjective evolutionary algorithm for thesizing and placement of DG [19]. Nara et.al., have used Tabu searchalgorithm to find optimal placement of distributed generator [20].
This paper presents a simple search approach determining foroptimal size and optimal placement of DG using N-R method ofload flow study. Both optimal DG size and optimal bus locationare determined to obtain the best objective. The multiobjectiveoptimization covers optimization of both cost and loss simulta-neously. The cost coefficients of DG are taken from Ref. [21]. TheIEEE 6 bus and IEEE 30 bus data are obtained from Refs. [9] and[22] respectively. Ref. [23] is used to obtain IEEE 14 bus systemdata. Further, using DGs at various buses the systems are modifiedand employed for load flow study.
850 S. Ghosh et al. / Electrical Power and Energy Systems 32 (2010) 849–856
2. Methodology
As mentioned, this paper focuses on a simple conventional N-Rmethod to solve a system of non-linear algebraic equation of theform f (x) = 0. Here, N-R method is applied to solve power flowequation in polar form. Bus data have been changed to incorporatethe effect of DG. When the DG is connected to a bus, correspondingbus is assumed to be a P � V bus. Further, it is assumed that thereactive power of DG is 20% of the active power generated. N-Rmethod is available in standard books [23,24].
2.1. Injected power
The complex injected power at bus ‘i’ is given as:
S�i ¼ V�iXn
k¼1
YikVk ð1Þ
0 100 200 300 400 50
100
200
300
400
500
600
700
Weigh
O F
Increasing
Fig. 1. Variation of OF with weig
0 100 200 300 400 50
2000
4000
6000
8000
10000
12000
14000
Weigh
O F
Increasing
Fig. 2. Variation of OF with weig
The unknown variables updated after mth iteration are givenas:
Ddðmþ1Þi ¼ DdðmÞi þ Ddi ð2Þ
jVijðmþ1Þ ¼ jVijðmÞ þ DjVij ð3Þ
2.2. Line power flow
Power flow from ith bus to jth bus through the line connectedbetween these buses is given by
Sij ¼ ViI�ij ¼ Vi
Vi � Vj
Zijþ ViYij0
� ��ð4Þ
00 600 700 800 900 1000ting factor
DG size
hting factor for IEEE 6 bus.
00 600 700 800 900 1000ting factor
DG size
hting factor for IEEE 14 bus .
S. Ghosh et al. / Electrical Power and Energy Systems 32 (2010) 849–856 851
Similarly, the power flow from the jth bus to ith bus is givenas:
Sji ¼ VjI�ji ¼ Vj
Vj � Vi
Zjiþ VjYji0
� ��ð5Þ
2.3. Line losses
The total line losses for all the buses connected to the system isthe sum total of all power flows given by:
Pi ¼Xbus no:
i¼1
Xbus no:
j¼1
ðSij þ SjiÞ
¼Xbus no:
i¼1
Xbus no:
j¼1
fðPij þ jQ ijÞ þ ðPji þ jQjiÞg ð6Þ
0 100 200 300 400 50
2000
4000
6000
8000
10000
12000
14000
16000
18000
Weig
O F
Increasi
Fig. 3. Variation of OF with weig
2 3100
200
300
400
500
600
700
800
Bus
O F
Incresing DG
Fig. 4. Variation of OF with variation of position of DG
2.4. Objective function (OF)
The main objective of the power flow solution has been directedtowards optimization of OF governed by the relation:
OF ¼ CðPDGÞ þW � E ð7Þ
where, C (PDG) = total cost of DG as a function of DG rating, PDG,W = weighting factor, E = total active loss and C (PDG) = aDG + bDG
PDG + cDG (PDG)2 respectively, aDG, bDG and cDG are the quadratic costcoefficient of specified DG.
3. Results and discussion
3.1. Calculation of OF
Eqs. (1)–(6) are solved to obtain total line losses of a system andthus total active and reactive power loss may be obtained sepa-
00 600 700 800 900 1000
hting factor
ng DG size
hting factor for IEEE 30 bus.
4 5 66number
size
s having different ratings for IEEE 6 bus system.
852 S. Ghosh et al. / Electrical Power and Energy Systems 32 (2010) 849–856
rately. In this work, only the active power loss component is con-sidered. Fig. 1 shows the variation of OF as a function of weightingfactor for different ratings of DG in the range of 1–20 MW for mod-ified IEEE 6 bus system. It may be seen from the figure that theoptimum value of weighting factor is close to 500 for any rangeof DG. Similarly, the weighting factor is 150 for both modified IEEE14 bus and IEEE 30 bus systems, as depicted in Figs. 2 and 3 respec-tively. Thus, weighting factor values of 500 and 150 are consideredfor optimization search in modified IEEE 6 bus, 14 bus and 30 busrespectively. In the whole work, bus 1 is considered as a slack bus.
3.2. Optimum location of DG
Fig. 4 indicates the variation of OF as a function of bus place-ment of DG for modified IEEE 6 bus system. It is seen that a mini-mum value of OF is obtained when DG (irrespective of its rating) isplaced at bus no. 3. It is clear from the figure that the magnitude of
2 3 4 5 6 71900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
Bus
O F
Fig. 5. Variation of OF with variation of position of DG
0 1 2 3 4 5 6 7 8 9 10 11 12 13 142400
2600
2800
3000
3200
3400
3600
Bus
O F
Fig. 6. Variation of OF with variation of position of DG
OF increases with the increase of DG rating with DG placed at high-er bus number. Similarly, optimum location of DG is obtained forIEEE 14 bus and 30 bus systems from Figs. 5 and 6 respectively.It may be seen that the OFs are minimum when the DG is placedat bus numbers 8 and 11 (which are low voltage buses) for IEEE14 bus and IEEE 30 bus systems respectively. Although it is appar-ent from Fig. 5 that placement of DG at bus number 3 gives lowervalue of OF than that at bus no 8, but bus number 3 is not consid-ered since it is a high voltage bus. Similarly, for IEEE 30 bus systemthe lower values of OF appears with bus numbers 5, 7 and 8, butthose buses are again high voltage buses. Therefore, bus number11, which is a low voltage bus, is taken into consideration.
3.3. Optimum DG rating
Fig. 7 represents variation of objective function with the size ofDG. A 6 MW DG seems to be the optimum size for IEEE 6 bus sys-
8 9 10 11 12 13 1414 number
increasing DGsize
s having different ratings for IEEE 14 bus system.
15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 3030number
Increasing DG size
s having different ratings for IEEE 30 bus system.
S. Ghosh et al. / Electrical Power and Energy Systems 32 (2010) 849–856 853
tem. Similarly, from Figs. 8 and 9 and 16 MW and 35 MW respec-tively are the optimum DG sizes for IEEE 14 bus and IEEE 30 bussystems respectively.
3.4. Comparison of the results of the proposed method with those ofPower World Simulator software
The comparison of the results obtained by the proposed methodand those obtained by the Power World Simulator software (Sim-ulator 11.0 Glover Sarma Education Edition) is presented in Table1. The results of the proposed method seem to be better than thoseof the Power World Simulator. The last column of Table 1 indicatesthe superiority of the proposed method in percentage, as given by:
P1 � P2
P1� 100%
0 2 4 6170
180
190
200
210
220
230
240
250
DG size
O F
Fig. 7. Variation of OF as a function o
0 4 8 12 161995
2000
2005
2010
2015
2020
2025
2030
DG siz
O F
Fig. 8. Variation of OF as a function o
where P1 = value of OF using Power World Simulator, P2 = value ofOF using proposed method.
3.5. Variation of bus voltage with DG size
Fig. 10 shows the effect of change in DG size at bus number 3 onthe voltage magnitudes of other buses in IEEE 6 bus system. Here,effects on bus numbers 2, 4 and 6 are taken into considerationsince they are essentially load buses. As may be seen from the fig-ure, the bus voltages are increasing with increase in DG size for busnumbers 2 and 4 and reach to the highest values, corresponding toDG size 11 MW and 14 MW respectively. The bus voltages fallafterwards with increasing DG size. In bus number 6 of coursethe bus voltages are increasing continuously, throughout the con-sidered range of DG. As stated in Section 3.3, the optimized size of
8 10 12 14
(MW)
f DG size for IEEE 6 bus system.
20 24 28 32 36 4040
e (MW)
f DG size for IEEE 14 bus system.
15 20 25 30 35 40 45 50502565
2570
2575
2580
2585
2590
DG size (MW)
O F
Fig. 9. Variation of OF as a function of DG size for IEEE 30 bus system.
Table 1Comparison results of proposed method with Power World Simulator.
IEEE modifiedsystems
Placement of DG(bus no.)
Size(MW)
Active loss (MW) OF
Power WorldSimulator
Proposedmethod
Power WorldSimulator (P1)
Proposedmethod (P2)
% Superiority of the proposedmethod
6 Bus 3 6 0.17 0.17 175.00 175.00 014 Bus 8 16 11.72 11.70 1998.00 1995.00 0.1530 Bus 11 35 13.76 13.61 2589.00 2566.50 0.87
0 2 4 6 8 10 12 14 16 18 200.9905
0.991
0.9915
0.992
0.9925
0.993
0.9935
0.994
DG size (MW)
Vol
tage
(p.
u)
bus no 2
bus no 4
bus no 6
Fig. 10. Voltage profile of IEEE 6 bus system.
854 S. Ghosh et al. / Electrical Power and Energy Systems 32 (2010) 849–856
DG is 6 MW as far as OF (i.e. both cost and loss) is considered. Thevariation of voltages from maximum voltage level for DG size be-yond 6 MW is very small of the order of 0.00015 and 0.0002 p.u.respectively, for bus number 2 and 4. Therefore, optimum DG sizemay be chosen as 6 MW. The bus voltages of these representativebuses have increased after the optimal placement of the optimalDG.
Similar conclusions may be drawn from Figs. 11 and 12 with re-spect to IEEE 14 bus and 30 bus systems respectively. In these twosystems the voltages of few representative load buses, where bus
voltages are low have increased after the optimal placement ofthe optimal DG.
4. Conclusions
From the above studies on modified IEEE 6, 14 and 30 bus sys-tems, the major contribution in the present work are:
(1) The optimized value of weighting factor is computed.
0 20 40 60 80 100 120 140 160 180 2000.975
0.98
0.985
0.99
0.995
1
1.005
1.01
1.015
DG size (MW)
Vol
tage
(p.
u)
busno 7busno 26busno 29busno 30
Fig. 12. Voltage profile of IEEE 30 bus system.
0 20 40 60 80 100 120 140 160 180 200
1.02
1.025
1.03
1.035
1.04
1.045
1.05
DG size (MW)
Vol
tage
(p.
u)
bus no 4bus no 5bus no 14
Fig. 11. Voltage profile of IEEE 14 bus system.
S. Ghosh et al. / Electrical Power and Energy Systems 32 (2010) 849–856 855
(2) The optimum locations and optimal sizes of DG are obtained.The optimum DG location obtained by the proposed methodvalidates the results of observation of Wang C. and NehrirM.H. [11] for IEEE 6 bus system.
(3) Due to the placement of optimal DG size at its optimumlocation it is observed that the voltages of load buses areimproved and the losses are reduced substantially.
(4) The OF values (that is, combination of cost and line losses)computed with the proposed method proved to be betterthan the simulation results obtained with Power World Sim-ulator software.
References
[1] Puttgen HB, Macgregor PR, Lambert FC. Distributed generation: semantic hypeor the dawn of a new era? IEEE Power Energy Mag 2003(January/February):22–9.
[2] Martin G. Renewable energy gets the green light in Chicago. IEEE Power EnergyMag 2003;22(November/December):34–9.
[3] Sonderegger RC, Henderson D, Bubb S, Steury J. Distributed asset insight. IEEEPower Energy Mag 2004(May/June):32–9.
[4] Rahman S. Green power: what is it and where can we find it? IEEE PowerEnergy Mag 2003(January/February):30–7.
[5] Kishinevsky Y, Zelingher S. Coming clean with fuel cells. IEEE Power EnergyMag 2003(November/December):20–5.
[6] Andrews CJ, Weiner SA. Visions of a hydrogen future. IEEE Power Energy Mag2004(March/April):26–34.
[7] Slootweg JG, Kling WL. Is the answer blowing in the wind? IEEE Power EnergyMag 2003(November/December):26–33.
[8] Griffin T, Tomsovic K, Secrest D, Law A. Placement of dispersed generationsystems for reduced losses. In: Proceedings 33rd annual Hawaii internationalconference system sciences, Maui, HI; 2000. p. 1446–54.
[9] Rau NS, Wan YH. Optimum location of resources in distributed planning. IEEETrans Power Syst 1994;9:2014–20.
[10] Kim JO, Nam SW, Park SK, Singh C. Dispersed generation planning usingimproved Hereford ranch algorithm. Electr Power Syst Res 1998;47(11).
[11] Wang C, Nehrir M Hashem. Analytical approaches for optimal placement ofdistributed generation sources in power systems. IEEE Trans Power Syst2004;19(4):2068–76.
[12] Chiradeja P. Benefit of distributed generation: a line loss reduction analysis.IEEE/PES transmission and distribution conference & exhibition: Asia andPacific, China Dalian; 2005. p. 1–5.
856 S. Ghosh et al. / Electrical Power and Energy Systems 32 (2010) 849–856
[13] Singh RK, Goswami SK. Optimum allocation of distributed generations basedon nodal pricing for profit, loss reduction, and voltage improvement includingvoltage rise issue. Int J Electr Power Energy Syst 2010;32(6):637–44.
[14] Frías P, Gómez T, Cossent R, Rivier J. Improvements in current Europeannetwork regulation to facilitate the integration of distributed generation. Int JElectr Power Energy Syst 2009;31(9):445–51.
[15] Niknam T, Ranjbar AM, Sirani AR, Mozafari B, Ostadi A. Optimal operation ofdistribution system with regard to distributed generation: a comparison ofevolutionary methods. IEEE Conf IAS 2005;22:2690–6.
[16] Mithulananthan N, Oo Than, Phu Le Van. Distributed generator placement inpower distribution system using genetic algorithm to reduce losses.Thammasat Int J Sci Technol 2004;9(3):55–62.
[17] Keane A, O’Malley M. Optimal allocation of embedded generation ondistribution networks. IEEE Trans Power Syst 2005;20(3):1640–6.
[18] Kim Kyu-Ho, Lee Yu-Jeong, Rhee Sang-Bong, Lee Sang-Kuen, You Seok-Ku.Dispersed generator placement using fuzzy-GA in distribution system. IEEEPower Eng Soc Summer Meet 2002:1148–53.
[19] Celli G, Ghiani E, Mocci S, Pilo F. A multiobjective evolutionary algorithm forthe sizing and siting of distributed generation. IEEE Trans Power Syst2005;20(2):750–7.
[20] Nara K, Hayashi Y, Ikeda K, Ashizawa T. Application of tabu search to optimalplacement of distributed generators. IEEE PES Winter Meet 2001:918–23.
[21] Gautam Durga, Mithlananthan Nadarajah. Optimal DG placement inderegulated electricity market. Electric Power Syst Res 2007;77:1627–36.
[22] Yokoyama R, Bae SH, Morita T, Sasaki H. Multiobjective optimal generationdispatch based on probability security criteria. IEEE Trans Power Syst1988;3:317–24.
[23] Pai MA. Computer techniques in power system analysis. New Delhi: TataMcGraw-Hill Publishing Company Limited; 2006.
[24] Saadat Hadi. Power system analysis. New Delhi: Tata McGraw-Hill PublishingCompany Limited; 2006.