2
LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707 www.lvscontrols.com Project: Model No.: Comments: APPLICATION FEATURES MOUNTING In the past, emergency lights were kept on 24 hours a day to meet life safety codes. Now, you can use a UL 924 listed Emergency Power Control, Model LUT-ALCR, to convert normal light fixtures into approved emergency lights. The LUT-ALCR saves energy and money while ensuring compliance with both life safety and energy codes. During normal operation, the same room switch, occupancy sensor, relay panel, or lighting control switches normal and emergency fixtures on and off simultaneously. During a utility power interruption, the LUT-ALCR automatically bypasses the normal lighting controls, turning the emergency lights ON, regardless of switch position. The LUT-ALCR is ceiling or wall mounted in a junc- tion box with a double gang plaster ring and is usually located in the area where the emergency fixtures are installed. Unique, Patented Automatic Diagnostic Fire Alarm, Remote Test & 0-10V Dimming Option When the room switch is turned off, the LUT-ALCR will run a 2.5 self-test routine, verifying that the emergency power source was available and that the LUT-ALCR, ballast, and lamp(s) are all functioning correctly. This feature eliminates the need for time-consuming and costly manual monthly testing and is approved for this purpose. This also allows the unit to be installed in remote or inaccessible locations, because the unit does not rely on access to its manual test switch. LED COMPATIBILE Utility & Emergency Power Indicator LED’s Slim, aractive flush mount profile allows easy access to manual test switch and LED’s. U L ® UL924 LISTED C US 5 YEAR WARRANTY LUT-ALCR UL924 Emergency Power Control Switched Loads up to 20A

201700816 LUT ALCR Template - Lutron Electronics · specifications single line drawing wiring diagram ordering information additional resources lvs, inc. 2555 nicholson street, san

  • Upload
    hatuong

  • View
    318

  • Download
    2

Embed Size (px)

Citation preview

LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707

www.lvscontrols.com

Project:

Model No.:

Comments:

APPLICATION

FEATURESMOUNTING

In the past, emergency lights were kept on 24 hours a day to meet life safety codes. Now, you can use a UL 924 listed Emergency Power Control, Model LUT-ALCR, to convert normal light fixtures into approved emergency lights. The LUT-ALCR saves energy and money while ensuring compliance with both life safety and energy codes.

During normal operation, the same room switch, occupancy sensor, relay panel, or lighting control switches normal and emergency fixtures on and off simultaneously.

During a utility power interruption, the LUT-ALCR automatically bypasses the normal lighting controls, turning the emergency lights ON, regardless of switch position.

The LUT-ALCR is ceiling or wall mounted in a junc-tion box with a double gang plaster ring and is usually located in the area where the emergency fixtures are installed.

Unique, Patented Automatic Diagnostic

Fire Alarm, Remote Test & 0-10V Dimming Option

When the room switch is turned off, the LUT-ALCR will run a 2.5 self-test routine, verifying that the emergency power source was available and that the LUT-ALCR, ballast, and lamp(s) are all functioning correctly. This feature eliminates the need for time-consuming and costly manual monthly testing and is approved for this purpose. This also allows the unit to be installed in remote or inaccessible locations, because the unit does not rely on access to its manual test switch.

LED COMPATIBILE

Utility & Emergency Power Indicator LED’s

Slim, attractive flush mount profile allows easy access to manual test switch and LED’s.

UL®UL924 LISTEDC US

5YEAR

WARRANTY

LUT-ALCRUL924 Emergency Power Control Switched Loads up to 20A

SPECIFICATIONS

SINGLE LINE DRAWING

WIRING DIAGRAM

ORDERING INFORMATION ADDITIONAL RESOURCES

LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707

www.lvscontrols.com20170816_LUT001_Spec

LUT-ALCRFor 0-10V dimming, see LUT-ALCR-D

Installation InstructionsTheory of Operation & FAQAlternative Wiring Diagrams

Terms & Conditions/Warranty Information

DESIGNATEDEMERGENCY

LIGHTS

NORMALROOM LIGHTS

LUT-ALCRUL 1008

Transfer SwitchOr Equivalent

NormalUtility Power

Emergency Power Source

(Neutral Not Shown)

LUT-ALCR

NORMALPANEL

NormalUtility Power

EMERGENCYPANEL OR INVERTER

$

LUT-ALCR

EMERGENCY HOT

#3 WHITE

NORMAL PANEL

EMPOWER

TEST

UTILITYPOWER

20A

#2 RED

#1 BLACK

*

Relay Panel, Power Pack, Sensor, or other (optional)*

Normal Light (optional)

EMERGENCY PANEL OR INVERTER

20ANORMAL HOT

NORMAL NEUTRALEMERGENCY NEUTRAL

#4 WHITE/BLUE

#5 YELLOW

#6 BLUE

Emergency Light

Note: Emergency Light is also called N/E Light or Normal/Emergency

Light by many specifiers

MODEL NO.

SENSING INPUT

LOAD RATING

BALLAST LOAD RATING

INCANDESCENT LOAD

WARRANTY

LUT-ALCR

120V - 277V

120V - 277V (20A)

20A (120-277V)

1200W (120V) / 1500W (277V)

5 Year Replacement Warranty

ELECTRICAL

MOUNTING

RATING

SHIPPING WEIGHT / COLOR

TEMPERATURE

FLUSH MOUNTED SIZE

BODY SIZE

4-11/16” Junction Box w/ double gang ring

UL94V-0

32ºF - 140ºF (0ºC - 60ºC)

MECHANICAL

12 oz. / White

5” x 5” x 0.2” (W X L X D)

3.5” x 2.75” x 1.5” (W X L X D)

Fire Alarm Tie-In/Override www.lvscontrols.com/assets/UL924FAI.pdf

Fire Alarm Jumper(see additional

resources)