2 Earthing System - Maintenance

Embed Size (px)

Citation preview

  • 8/10/2019 2 Earthing System - Maintenance

    1/53

    s.ganesh babu. 1

    Earthing System -

    Maintenance

    S.Ganesh Babu

  • 8/10/2019 2 Earthing System - Maintenance

    2/53

    The primary objectives of a grounding system

    are to:

    s.ganesh babu. 2

    Protects personnel and sensitive equipment.

    Dissipateslightningstrikes.

    Discharges short circuit currents.

    Prevents damage from power and switching

    surges.

    Provides stable reference.

    Safety to human life, appliances, machines,

    equipments etc.)

    http://en.wikipedia.org/wiki/Surge_protectionhttp://en.wikipedia.org/wiki/Surge_protectionhttp://en.wikipedia.org/wiki/Surge_protection
  • 8/10/2019 2 Earthing System - Maintenance

    3/53

    The primary objectives of a grounding system are to:

    s.ganesh babu. 3

    Control Radio Frequency (RF) Emissions& Electromagnetic Interferences.

    Provide a stable reference potential for

    instrument accuracy.

    Provide a discharge path for short circuits

    and lightning strikes (fault current /surge

    protection

    http://en.wikipedia.org/wiki/Radio_Frequencyhttp://en.wikipedia.org/wiki/Emissionshttp://en.wikipedia.org/wiki/Electromagnetic_interferencehttp://en.wikipedia.org/wiki/Surge_protectionhttp://en.wikipedia.org/wiki/Surge_protectionhttp://en.wikipedia.org/wiki/Surge_protectionhttp://en.wikipedia.org/wiki/Surge_protectionhttp://en.wikipedia.org/wiki/Electromagnetic_interferencehttp://en.wikipedia.org/wiki/Emissionshttp://en.wikipedia.org/wiki/Radio_Frequency
  • 8/10/2019 2 Earthing System - Maintenance

    4/53

    What are the risks?

    s.ganesh babu. 4

    20+ fires a day are caused by faulty electricalinstallations

    Fires are 12 times more likely to be caused by

    faulty electrics than, say, by gas

    2000+ people are injured through electrocution

    every year

    As per National Crime Records Bureau (NCRB)of India, around 15 people die every day due to electrical

    accidents, which account for nearly 3% of total

    accidental deaths.

  • 8/10/2019 2 Earthing System - Maintenance

    5/53

    What are the risks?

    s.ganesh babu. 5

    The majority of deaths, injuries and damage

    would have been prevented by an installation

    inspection.

    Older properties (10+ years old) are mostat risk.

    The danger is increased, as it is usually

    out-of-sight, under floorboards, behindwalls.

    The function of the earthing system is two-

    fold.

  • 8/10/2019 2 Earthing System - Maintenance

    6/53

    s.ganesh babu. 6

    Purpose of protective earthing

    To ensure the safety of the people and

    property within the zone served by it.

    It requires a high current capacity path withrelatively low impedence at the fundamental

    frequency.

    To ensure that the voltages developed under

    high fault conditions are not hazardous.

  • 8/10/2019 2 Earthing System - Maintenance

    7/53

    s.ganesh babu. 7

    Effectively earthed system is one in

    which:

    --The ratio of zero sequence reactance

    to that of positive sequence reactanceis less than 3.

    -- The ratio of the zero sequence

    resistance to that of positive

    sequence resistance is less than 1.

  • 8/10/2019 2 Earthing System - Maintenance

    8/53

    s.ganesh babu. 8

    NEED FOR A RELIABLE LOW IMPEDENCE

    CONNECTION.

    A GOOD LOW IMPEDENCE CONNECTION

    TO GROUND CONSISTS OF:

    A high conductivity.

    Corrosion resistant conductor (copper is a good

    choice).

    To be buried at a depth in the earth that it will not

    freeze nor dry out.

    Large enough to contact a suitably a large volume of

    earth covering a large area.

    Located in such a position that it is not influenced by

    other earthing system.

  • 8/10/2019 2 Earthing System - Maintenance

    9/53

    s.ganesh babu. 9

    Effect of large earth volume and area.

    A large volume of earth reduces the current density in

    the soil and so the resistance to the earth.

    A large area connection allows the shaping of the

    electric field to be accomplished, reducing the touch and

    step voltage.

    It is hence, called a clean earth, atleast as clean as it gets.

    The traditional thought of providing a low impedence

    path to earth is now dispensed with.

    Modern practice requires shaping of the field in the

    ground to control voltage gradients around the eartrh

    electrode.

  • 8/10/2019 2 Earthing System - Maintenance

    10/53

    s.ganesh babu. 10

    EARTH AS A SPHERE WITH DIFFERENT

    LAYERS OF EARTH RESISTIVITY

    CORE

  • 8/10/2019 2 Earthing System - Maintenance

    11/53

    s.ganesh babu. 11

    VARIATION OF SOIL RESISTIVITY WITH

    TEMPERATURE.

    TEMPERATURE

    DEG.C

    Clay mixed with sand, 15% moisture.

    Resistivity in ohm-meter

    20 72

    10 99

    0 (water) 138.

    0 (ice) 300minus 5 790

    minus 15 3,300

  • 8/10/2019 2 Earthing System - Maintenance

    12/53

    s.ganesh babu. 12

    VARIATION OF SOIL RESISTIVITY WITH

    MOISTURE CONTENT.

    MOISTURE

    CONTENT

    %AGE BY WEIGHT.

    RESISTIVITY OF

    CLAY WITH

    SAND.

    RESISTIVITY OF SAND

    0 10 TO POWER 7 -

    2.5 1500 3x 10 to power 6

    5 430 50,000

    10 185 2100

    15 105 650

    20 63 270

    30 42 -

  • 8/10/2019 2 Earthing System - Maintenance

    13/53

    s.ganesh babu. 13

    REDUCTION OF EARTH RESISTIVITY:

    METHODS.

    Chemicals traditionally used for changingresistivity are:

    -- sodium chloride, NaCl (salt)

    -- magnesium sulphate MgSo4,-- Copper Sulphate CuSo4,

    -- Sodium Carbonate,NaCo3, (Washing Soda),

    -- Calcium Chloride, CaCl. Earth resistivity can be reduced to:

    -- 0.2 ohm meter using NaCo3,or

    -- 0.1 ohm meter using salt.

  • 8/10/2019 2 Earthing System - Maintenance

    14/53

    s.ganesh babu. 14

    1.2 grams per liter of salt in dissolved water has aresistivity of 5.0 ohm meter, while 6 grams per

    liter of salt in dissolved water has a resistivity of10 ohm meter.

    GYPSUM:

    has water retention property.

    Low solubility.

    Resistivity of 510 ohm meter.

    Neither acidic nor alkaline with Ph value between 6.2 to6.9.

    BLAST FURNACE SLAG: Use of blast furnace slag on the granulated form is on an

    experimental stage.

  • 8/10/2019 2 Earthing System - Maintenance

    15/53

    s.ganesh babu. 15

    BENTONITE:

    -- Mixed in the ratio of 1 : 6 with blackcotton soil.

    -- Is a volcanic product.

    -- Is acidic by nature, with Ph value of 10.5.-- Absorbs 5 times of water.

    -- Swells upto 13 times its dry volume.

    -- Non corrosive.-- resistivity is 5.0 ohm meter.

  • 8/10/2019 2 Earthing System - Maintenance

    16/53

    s.ganesh babu. 16

    MARCONITE:

    -- Developed by Marconi communications Ltd in 1962.

    -- Contains crystalline form of carbon with low sulphurand Chloride content.

    -- Used in a concrete form with carbonceous aggregaatereplacing HBG metal.

    -- Resistivity of 2.0 ohm meter reduces to 0.1 ohm meterwhen mixed with concrete.

    -- Retains moisture even in dry / hot climates.

    -- Used for anti static flooring and electro magnetticscreening.

    -- In slurry state, causes corrosion on metals.-- Alumunium, tin coated, or galvanised steel not to be

    used in marconite.

    -- Used in Rocky locations.

  • 8/10/2019 2 Earthing System - Maintenance

    17/53

    s.ganesh babu. 17

    The three demands of an Earth system

    LIGHTNING AND SHORT CIRCUIT:

    The earthing system should protect:

    -- occupants.

    -- damages such as fire, explosions, and flash over due to

    lightning.-- over heating due to short circuit.

    SAFETY:

    -- must conduct lightning and short circuit currentswithout introducing intolerable step and touchpotentials.

  • 8/10/2019 2 Earthing System - Maintenance

    18/53

    s.ganesh babu. 18

    EQUIPMENT PROTECTION AND

    FUNCTIONALITY:

    by providing a low impedance path to the

    unbalanced and neutral currents that are generated in

    an electrical network.

    Should provide proper protective coverage to all the

    connected equipments and cables, through

    protectinve sheilding and zoning to lightning system.

  • 8/10/2019 2 Earthing System - Maintenance

    19/53

    s.ganesh babu. 19

    Electrical earthing is designed primarily to render

    electrical installation safe. The purpose of earthing

    are :

    1. Protection to the plant

    2. Protection to the personnel and

    3. Improvement in service reliability

    Non- current carrying parts with conducting surface

    such as tanks of Power Transformers, and frame

    work of circuits breakers, structural steel work in

    switch yard instrument transformer cases, lightningarresters and armored cables armoring should be

    effectively grounded for protection of equipments and

    operating personnel. Earth connections of all

    equipments should be made in duplicate.

  • 8/10/2019 2 Earthing System - Maintenance

    20/53

    s.ganesh babu. 20

    Connecting lead should have sufficient currentcarrying capacity.

    L A s should have independent earth electrodewhich should be inter connected to the stationgrounding system.

    All paints, enamel, seals should be removedfrom the point off contact of metal surfaces

    before earth connections are made. The resistances of earth system should not

    exceed 2 ohms for 33/11 KV Sub Stations.

    But in the sub stations of Distribution

    companies Earth resistance Maximum of 1 Ohmis maintained.

    Suitable grounding mat should be provided inthe sub station yard.

  • 8/10/2019 2 Earthing System - Maintenance

    21/53

    s.ganesh babu. 21

    I n a Sub Station the following shall be earthed.

    The neutral point of the systems of different voltageswhich have to be earthed.

    Apparatus, frame work and other non-current carryingmetal work associated with each system, for exampletransformer tanks, switch gear frame work etc.,

    Extraneous metal frame work not associated with thepower systems, for example, boundary, fence, steelstructures etc.,

    The earthing Means connecting of Electricalequipment, machinery or an electrical system with thegeneral mass of earth is termed as earthing orgrounding

  • 8/10/2019 2 Earthing System - Maintenance

    22/53

    s.ganesh babu. 22

    The earthing system must provide an environmentwhich is free from the possibility of fatal electricshock.

    The earthing system must provide a lowimpedance path for fault and earth leakage currentsto pass to earth.

    The earthing conductors must possess sufficientthermal capacity to pass the highest fault current

    for the required time The earthing conductors must have sufficient

    mechanical strength and corrosion resistance.

    A Sub Station earthing system has to satisfy four

    requirements:

  • 8/10/2019 2 Earthing System - Maintenance

    23/53

    s.ganesh babu. 23

    Earthing can be broadly divided as :

    System Grounding ( System

    Earthing)

    Equipment Grounding (Safety

    Grounding).

    Discharge grounding.

  • 8/10/2019 2 Earthing System - Maintenance

    24/53

    s.ganesh babu. 24

    System Grounding:

    It is a connection to the ground of a part of the plant formingpart of the operating circuits for example the star point of thetransformer or the neutral conductor. The grounding of thelighting, arrestors also comes under the head of systemgrounding. The provision of system ground reduces to

    considerable extent the magnitude of the transient overvoltages and there by increases the life of electrical equipment

    besides minimizing the services interruptions.

    Thus the fundamental purpose of system ground is the

    protection of installation and improvement in quality ofservice. The system ground also will ensure the safety of the

    personnel to some extent, as it helps to clear the fault speedily.

  • 8/10/2019 2 Earthing System - Maintenance

    25/53

    s.ganesh babu. 25

    Safety Grounds (Equipment Grounding)

    It is a connection to the ground of non-current carrying parts of the equipments like

    Motors, Transformer Tanks, Switchgearenclosures, Metallic enclosures of allelectrically operated equipments and also theinstallations used to carry/ Support electrical

    equipments.

    By connecting the frames to a low resistanceground system, a sufficiently high currentwill flow into the ground when accidentallythe live parts of the equipment / Machinerytouch the frames, and consequently saves theoperating personnel from fatal accidents.

  • 8/10/2019 2 Earthing System - Maintenance

    26/53

    Safety Grounds (Equipment Grounding)

    Thus the equipment grounding isbasically intended to safeguard to a

    great extent from the hazards of touch

    voltages. The safety ground is so

    designed that the potential differenceappearing between the frames and the

    neighboring ground is kept within safe

    limits.

    s.ganesh babu. 26

  • 8/10/2019 2 Earthing System - Maintenance

    27/53

    s.ganesh babu. 27

    Separation of system and safety grounds:

    During ground fault conditions, the fault currentflows via the system ground. When the system andsafety grounds are inter connected, the fault currentflowing (via) the system ground rises the potential ofthe safety ground. Also the flow of current to safety

    ground results in hazardous potential gradient in andaround sub station. In view of the above it is sometimes suggested that separate system and safetygrounds will avoid the danger arising due to potentialgradients. The idea is that by connecting the systemground to a separate earthing system situated in anaccessible spot, the ground fault current does not flowthrough the safety ground.

  • 8/10/2019 2 Earthing System - Maintenance

    28/53

    s.ganesh babu. 28

    However, this separate system of grounds

    has many disadvantages and can be more

    hazardous as mentioned below With separate grounds we can avoid

    danger due to potentials only for faults

    outside the stations. Short circuit currents will be more if the

    fault occurs in the sub stations.

    The resistance may be more and in somecases sufficient currents may not flow to

    operate the relays.

  • 8/10/2019 2 Earthing System - Maintenance

    29/53

    s.ganesh babu. 29

    For effective separation of the earthing systems, thesystem ground shall be installed at a distance of at

    least twice the diagonal length of the sub stationwhich is covered by safety grounding. The neutral ofthe transformer has to be connected to this remoteearthing by means of insulated leads. Even with this

    arrangement one cannot always be sure about thecomplete isolation of the two systems and there isalways a chance of inadequate electrical connectionthrough buried neutral pipes etc., Hence, this is

    impracticable, complicated and costly. It is thereforea common practice to install a common groundingsystem and design the same for effective earthing andsafer potential gradients.

  • 8/10/2019 2 Earthing System - Maintenance

    30/53

    s.ganesh babu. 30

    System Earthing

    System earthing is governed by provisions of Rule -Of I.E Rules, 1956. Unearthed systems have beentried and due to the phenomenon of Arcing Groundsassociated with them, theses have been abandoned,excepting in a few cases of power station auxiliaries

    supply systems where other arrangements are madefor indicating earth faults. In an ungrounded systemthe insulation of all the equipments, lines etc, willhave to be much higher values as compared to those

    of equipments and lines of a grounded system. Thisaspect greatly reduces the costs and ensures moresafety.

  • 8/10/2019 2 Earthing System - Maintenance

    31/53

    s.ganesh babu. 31

    Types of System Earthing:

    Earthing through a resistance.

    Earthing through a reactance.

    Earthing through a Peterson coil

    Earthing directly or solidearthing.

  • 8/10/2019 2 Earthing System - Maintenance

    32/53

    s.ganesh babu. 32

    Sub Station EarthingBecause of the difficulties and disadvantages involved inmarinating the system grounding and safety grounding

    separately it is the common practice now to have a combinedgrounding system at the sub stations. The impedance toground should be as low as possible. The impedance of theearth system shall not exceed the following limits in the substations

    Power Stations 0.5 OhmsMajor Sub stations above 110 KV 1.0 Ohms

    Minor Sub Stations below 110

    KV

    2.0 Ohms

    Distribution Transformer Station 5.0 Ohms

    Transmission line supports 10.0 Ohms

  • 8/10/2019 2 Earthing System - Maintenance

    33/53

    s.ganesh babu. 33

    Touch Potential

    Touch potential is the potential differencebetween the ground surface potential wherea person is standing and the potential of hisoutstretched hand (s) which are in contactwith an earthed structure. It is normallyassumed that a personsmaximum reach is

    1.0 meter.

  • 8/10/2019 2 Earthing System - Maintenance

    34/53

    Step Potential

    s.ganesh babu. 34

    Step Potential is the potential

    difference between outstretchedfeet, at a spacing of 1.0 meterwithout the person touching anyearthed structure

  • 8/10/2019 2 Earthing System - Maintenance

    35/53

    Mesh Potential

    s.ganesh babu. 35

    The maximum potential differencebetween the centre of a mesh in an

    earth grid, and an earthed structureconnected to the buried gridconductors. It is worst casescenario of a touch potential.

  • 8/10/2019 2 Earthing System - Maintenance

    36/53

    s.ganesh babu. 36

    Transferred potential

    The transferred potential is a touch potential

    which is transferred some distance by an earth

    referenced metallic conductor. For example,

    consider a screened cable connecting two sub

    stations which are some distance apart. If aperson disconnects the earthed termination at

    one end of a screened cable he may be subjected

    to the full ground potential rise occurring due toan earth fault. This can be a very high touch

    potential.

  • 8/10/2019 2 Earthing System - Maintenance

    37/53

    s.ganesh babu. 37

    Earthing in a sub station must conform

    to the requirements of the Indian

    Electricity Rules and follow the

    directives laid down in section I and III

    of IS : 3043-1966. the earthing systemhas to be designed to have a low overall

    impedance, and a current carrying

    capacity consistent with fault current.

  • 8/10/2019 2 Earthing System - Maintenance

    38/53

    s.ganesh babu. 38

    The factors which influence the design

    are:

    Duration of fault.

    Magnitude of the fault current.

    Resistivity of the underlying strata.

    Resistivity of the surface material

    Material of the earth electrode.

    Material of earthing mat conductor.

    Shock duration.

    Earth mat geometry.

  • 8/10/2019 2 Earthing System - Maintenance

    39/53

    s.ganesh babu. 39

    Steps to be taken for design purpose:

    Finalize lay out plan of the substation.

    This gives the area to be covered by the earth mat.

    Obtain the earth resistivity of the location where

    substation is to be located. Determine the fault current likely to develop at the SS

    through system studies. A correction factor of 1.2 to1.5 may be used for the determined value.

    Assumption of duration of fault is taken as 1.0 sec For calculating safe step and mesh potentials, a

    duration of 0.5 sec may be assumed.

  • 8/10/2019 2 Earthing System - Maintenance

    40/53

    s.ganesh babu. 40

    A uniform corrosion allowance of 0.12 mm per year

    is considered for steel as ground conductor.

    Life of a substation is taken as 40 years. Steel corrodes 6 times faster than copper.

    The electrodes spacing shall not be greater than twice

    that of the length of the electrode. The spacing of the mesh earth conductors shall be

    between 3 to 5 meters.

    Various specifications such as the area of the earth

    mat, Number of electrodes, size of the earthconductors shall calculated based on the

    mathematical formulae and conductor constants.

    Th b f l d i i b h f ll i h b

  • 8/10/2019 2 Earthing System - Maintenance

    41/53

    s.ganesh babu. 41

    The number of electrodes is given by the following thumbrule:

    N = I (fault) / 250,

    for a earth resistivity of 500 ohm meters.N = I (fault) / 500,

    for a earth resistivity of 5000 ohm meter.

    The current density of the unbalanced current in a normalsystem shall not exceed 40A / Mtr.sq.

    Short time over load under fault condition is given by

    I = (7.57 *10cube) / root of rho * t, where t is theduration of fault in secs.

    Safe step potential : (116 + 0.7 rho) / root t

    Safe touch potential : ( 116 + 0.17 rho ) / root t.

    where rho refers to surface earth resistivity and t , theduration of fault current in secs.

  • 8/10/2019 2 Earthing System - Maintenance

    42/53

    s.ganesh babu. 42

    The size of the earth bus and earth conductor

    are given by

    A = 0.0054 I x root t,

    for sweated and rivetted joints.(250deg)

    A = 0.0044 I x root t,for brazed joints.(450 deg.)

    These values are applicable for copper only

    and higher values are to be taken for steel.

  • 8/10/2019 2 Earthing System - Maintenance

    43/53

    s.ganesh babu. 43

    100 X 16 mm and 75 X 8mm size MS steel flats arebeing ordered for forming the earthing system for

    EHT Sub station and 33/11 KV Sub Stationsrespectively

    Earth mat shall be formed with the steel flats buriedin the ground at a depth of 500mm.

    The earth mat shall extend over the entire switchgearyard and beyond the security fencing of structuralyard by at least one meter.

    The outer most peripheral earthing conductorsurrounding the earth mat shall be of 100 x 16 mmsize MS flat.

  • 8/10/2019 2 Earthing System - Maintenance

    44/53

    s.ganesh babu. 44

    The intermediate earthing conductors forming theearth mat shall be of 75 x 8 mm size flat.

    All the risers used for connecting the equipment

    steel structures etc., to earth mat shall be of 50 x6mm size excepting for earthing of L A s andtransformer neutrals for which 100 x 16 mm or 75x 8 mm size shall be used.

    All Junctions (crossing of the steel flats while

    forming the earth mat and taking risers from theearthmat for giving earth connections toequipments, steel structural conducts, cableshearths shall be propersly welded.

    Proper earthing lugs shall be used for connectingthe earth terminals of equipments to the earthingsteel flat.

  • 8/10/2019 2 Earthing System - Maintenance

    45/53

    s.ganesh babu. 45

    Provisions shall be made for thermal expansion of thesteel flats by giving suitable bends.

    The earth mat shall be formed by placing 75 x8mm MSflat at a distance 5 meters along the length & breadth ofthe sub station duly welding at crossing.

    All the equipments, steel structural, conduits, cablesheaths shall be solidly grounded by connecting to theearthing mat at least two places for each.

    The ground mat of the switchyard shall be properlyconnected to the earth mat of the control house at leastat two points.

    welding is done shall be given a coat of blackasphalitic varnish and then covered with hessain tape toavoid rusting.

  • 8/10/2019 2 Earthing System - Maintenance

    46/53

    s.ganesh babu. 46

    All paints, enamel and scale shall be removed frompoint of contact in metal surfaces before applyingground connections.

    The risers taken along the main switchyard structuresand equipment structures up to their top) shall beclamped to the structure at an interval of not more thanone meter with ground connectors.

    75 X 8 mm ground conductor shall run in cable trenchesand shall be connected to the ground amt at an intervalof 5 meters.

    Grounding electrodes 2.75 Mtrs length 100 mm dia 9mm thickness CI Pipes shall be provided at all their

    peripheral corners of the earthiong mat and also atDistance of 10 Mtrs along length & width of switchgearand in the entire switch yard.

  • 8/10/2019 2 Earthing System - Maintenance

    47/53

    s.ganesh babu. 47

    The grounding electrodes shall be drived into the

    ground and their tops shall be welded to a clamp and

    the clamp together with the grounding shall be

    welded to the ground conductor.

    The switchyard surface area shall be covered by a

    layer of crushed rock of size 25 x 40 mm to a depth

    of 100mm

    Transformers and L A s and single phase potential

    transformer shall be provided with earth pits near

    them for earthing and these earth pits in turn shall be

    connected to the earth mat.

  • 8/10/2019 2 Earthing System - Maintenance

    48/53

    s.ganesh babu. 48

    Power Transformers neutral shall be providedwith double earthing. Neutral earthing and

    body earthing of power transformers shall be

    connected to separate earth electrode.

    the entire earthing system shall be laid withconstructional conveniences in the filed,keeping in view the above points.

    The joints and tap-offs where welding is done

    shall be given a coat of black asphaliticvarnish and then covered with hessain tape toavoid rusting.

  • 8/10/2019 2 Earthing System - Maintenance

    49/53

    s.ganesh babu. 49

    THE PERMISSIBLE LIMITS OF STEP POTENTIAL AND TOUCH

    POTENTIAL SHALL BE

    Maximum Acceptable step Voltage

    Fault clearance times

    Fault clearance times 0.2 Seconds 0.35 Seconds 0.7 Seconds

    On soil 1050 V 600 V 195 V

    On chippings 150mm) 1400 V 800 V 250 V

    Maximum Acceptable Touch Voltage

    Fault clearance times

    Fault clearance times 0.2 Seconds 0.35 Seconds 0.7 Seconds

    On soil 3200 V 1800 V 535 V

    On chippings 150mm) 4600 V 2600 V 815 V

  • 8/10/2019 2 Earthing System - Maintenance

    50/53

    s.ganesh babu. 50

    EARTH GRID- MATERIALThe following are the minimum sizes of materials to used.

    S.

    No

    Item Material to be used

    1 Grounding Electrodes CI pipe 100 mm (inner dia)

    Meters long with a flange at

    the top2 Earth mat 75 X 8mm MS Flat

    3 Connection to between

    electrodes and earthmat

    75 X 8mm MS Flat

    4 Connection to betweenearth mat and equipment

    (Top Connections)

    50 x 6mm MS Flat

  • 8/10/2019 2 Earthing System - Maintenance

    51/53

    s.ganesh babu. 51

    The size of trench for burying earth mat shall be 300mm X500mm. The earth mat shall be buried in the ground at a depthof 500mm. The earth mat shall extend over the entire switch

    yard. All junctions and risers in the earth flat shall be properly

    welded by providing additional flat pieces for contact betweentwo flats

    Provision shall be made for thermal expansion of steel flats by

    giving smooth circular bends Bending shall not cause anyfatigue in the material.

    After welding, the joints and tap offs shall be given two coatsof Bitumen paint

    Back filling of earth mat trench to be done with good earth,

    free of stones and other harmful mixtures. Back fill shall beplaced in layer of 150mm, uniformly spread along the ditch,and tampered by approved means

    EARTH ELECTRODES

  • 8/10/2019 2 Earthing System - Maintenance

    52/53

    s.ganesh babu. 52

    EARTH ELECTRODES

    Earth electrodes shall be of CI pipe 100mm (inner dia) 2.75 meterslong with a flange at the top and earth flat already indicated andshall be connected to earth grid in the Sub Station. All earth pitsare to excavated and the preferred backfill is a mixture of coke andsalt in alternate layers. A suitable size cement collar may be

    provided to each earth electrode. All bolted earth mat connectionsand strip connections to plant and equipment panel will be subject

    to strict scrutiny. Transformer Neutrals shall be connected directlyto the earth electrode by two independent MS strips of 75 X 8mm.The transformer body earthing shall be done with 75 X 8mm flat.The independent connections of MS strips with earth mat shall begiven on either side of the Transformer. All contact surface must

    be filled or ground flat ensures good electrical connection, and thecontact surface shall be protected with a contact lubricant.Following this all connections shall be painted with heavy coats of

    bituminous black paint so as to exclude moisture.

    EARTH GRID WORK DETAILS

  • 8/10/2019 2 Earthing System - Maintenance

    53/53

    s ganesh babu 53

    EARTH GRIDWORK DETAILS

    Neutral connection earth pipe shall never be used for theequipment earthing.

    A separate earth electrode shall be provided adjacent to thestructures supporting Lightning Arrestors. Earth connectionshall be as short and as straight as practicable. For arrestorsmounted near for protecting transformers earth conductors

    shall be connected directly to the tank.

    An Earthing pad shall be provided under each operatinghandle of the isolator and operating mechanism of the circuit

    breakers. Operating handle of the isolator and supporting

    structures shall be bonded together by a flexible connectionand connected to the earthing grid.

    All equipment and switchgear etc., erected shall be earthedas per I.E Rules 1956.