Upload
shashank11
View
212
Download
0
Embed Size (px)
Citation preview
8/3/2019 2-9_Heinonen
1/25
MAINTENANCE AND LIFE TIME EXTENSION OF
POWER TRANSFORMERS
Kari Heinonen
Infratek Finland Oy
2010 EuroDoble Colloquium
18-20 October 2010
Birmingham, United Kingdom
8/3/2019 2-9_Heinonen
2/25
10.9.2010 K Heinonen, Infratek Finland Oy 2
ABSTRACT Visual inspections
Oil testing
Oil filtering
Bushings
OLTC
Transformer refurbishment
Copper corrosion
Failure investigation
8/3/2019 2-9_Heinonen
3/25
10.9.2010 K Heinonen, Infratek Finland Oy 3
Fig. 1. Finnish 110 kV 400 kV transformer population.
/2/.
0
10
20
30
40
50
60
70
80
90
100
1956
1957
1958
1959
1960
1961
1962
1963
1964
1965
1966
1967
1968
1969
1970
1971
1972
1973
1974
1975
1976
1977
1978
1979
1980
1981
1982
1983
1984
1985
1986
1987
1988
1989
1990
1991
1992
1993
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
Vuosimalli
k
pl
Perushuolletut Huoltamattomat
8/3/2019 2-9_Heinonen
4/25
10.9.2010 K Heinonen, Infratek Finland Oy 4
1 Visual inspections
1 to 6 monthsinterval
Bushings:Oil level, Leakages
etc.
Corrective actionsimmediately withdangerous findings
8/3/2019 2-9_Heinonen
5/25
10.9.2010 K Heinonen, Infratek Finland Oy 5
2 Oil analysis
There are not any
excuses why not to applyfrequent oil analysing.
DGA and break
down voltage test:2 years period
Otheranalysis:
10 year period
Warranty period: morefrequent monitoring
8/3/2019 2-9_Heinonen
6/25
10.9.2010 K Heinonen, Infratek Finland Oy 6
2 Oil analysis continues
Bushings with oil-
paper insulation: DGA10 years interval, OR
Power Factor
measurement, 10
years interval
8/3/2019 2-9_Heinonen
7/25
10.9.2010 K Heinonen, Infratek Finland Oy 7
2 Oil analysis continues
FIELD TESTING RESULTS, Bushing
ASEA GOB 650, 123 kV, 800 A
Ser. Numb. PF1 PF2 C1 C2
104807 0,14 % 80,5 % 180 pF 190 pF
IEC -60137 < 0,7 %
DGA results ppm (KELMAN Transport X)
H2 CO2 CO C2H4 C2H6 CH4 C2H2 TCG
27 3819 964 4 9 18
8/3/2019 2-9_Heinonen
8/25
10.9.2010 K Heinonen, Infratek Finland Oy 8
2 Oil analysis continues
BUSHINGS 110 kV DGA results ppm (KELMAN Transport X and Lab.analysis)
Serial
TYPE Numb H2 CO2 CO C2H4 C2H6 CH4 C2H2 TCG
GOB 650 104807 27 3819 964 4 9 18
8/3/2019 2-9_Heinonen
9/25
10.9.2010 K Heinonen, Infratek Finland Oy 9
3 On-site and on-line gas analysis
280 MVA,
400/15 kV
On-line gas
monitoring
8/3/2019 2-9_Heinonen
10/25
10.9.2010 K Heinonen, Infratek Finland Oy 10
4 Oil filtering, degassing and regeneration
On-site oil filtering: Start ofrepair activities needs to bedelayed
Not any corrective action
Low break down voltage:Filtering and oil degassing
Continuous degassing
Oil regeneration: Aged oil asgood as new oil.
8/3/2019 2-9_Heinonen
11/25
10.9.2010 K Heinonen, Infratek Finland Oy 11
5 Monitoring of transformer bushings
Oil sampling or powerfactor measurement 10year period
When refurbishingTrafo:Lab. Testing: voltage test,tan delta, partial
discharges, capacitance.
2,0 % of all 110 kVbushings tested had minorfailures and 2,5 % ofbushings had to bescrapped immediately
8/3/2019 2-9_Heinonen
12/25
10.9.2010 K Heinonen, Infratek Finland Oy 12
5 Monitoring of transformer bushings continue
LAB. TESTING RESULTS
ASEA GOB 550, 123 kV, 800 A
PD PD
Ser. Numb. Tan d 0,61 x Un 1,0 x Un.
141399 0,45 % < 3 pC < 3 pC141341 0,46 % < 3 pC < 3 pC
141334 0,45 % < 3 pC < 3 pC
141335 0,50 % < 3 pC < 3 pC
IEC -60137 < 0,7 % < 5 pC < 10 pC
Voltage test 0,75 x 230 kV, 50 Hz, 1 min
8/3/2019 2-9_Heinonen
13/25
10.9.2010 K Heinonen, Infratek Finland Oy 13
6 On-load tap-changer service
Five to six years
period
Oil sampling, visual
inspections, relaytesting, bushing and
transformer power
factor testing etc.during the same
outage.
8/3/2019 2-9_Heinonen
14/25
10.9.2010 K Heinonen, Infratek Finland Oy 14
7 Transformer refurbishment
Refurbishment: Lifting of active part
(core and windings; untanking)
On-site, power plant, repair shop,
at the manufacturer
Finland ca. 30 % of all 110 kV
400 kV transformers(ca. 2000 pcs.) revised
WHY: Better reliability,
Longer lifetime, Environment
Cost 1520 % of new price.
8/3/2019 2-9_Heinonen
15/25
10.9.2010 K Heinonen, Infratek Finland Oy 15
7 Transformer refurbishment continues
110 kV transformers:
Trailertransportationto workshop
4 to 6 weeks including
transportations
On-site refurbishment:
* 110 kV, 100 MVA +
* (220 kV transformers)
* 400 kV transformers
8/3/2019 2-9_Heinonen
16/25
10.9.2010 K Heinonen, Infratek Finland Oy 16
7 Transformer refurbishment continues
Tightening of windings
Drying of paper insulation
Revision and modifications oftap-changerincludingselector
Oil degassing and filtering
High-voltage testing ofbushings Replacement of gaskets
Replacement of protection relays and devices
Addition of a separate expansion vessel for on-load
tap-changer etc. Painting
Documentation
8/3/2019 2-9_Heinonen
17/25
10.9.2010 K Heinonen, Infratek Finland Oy 17
.
7 Transformer refurbishment continues
Findings 1 / 120 kV, 63 MVA, 1974
8/3/2019 2-9_Heinonen
18/25
10.9.2010 K Heinonen, Infratek Finland Oy 18
.
7 Transformer refurbishment continues
Findings 2 / 121 kV, 50 MVA, 1969
8/3/2019 2-9_Heinonen
19/25
10.9.2010 K Heinonen, Infratek Finland Oy 19
8 Refurbishment of distribution andspecial transformers
50 kVA 1000 kVA: Whenmoving the transformer
Electric filter rectifiertransformers: Oil samplingwith five years interval andrevision by lifting the active
part with ten years interval.
8/3/2019 2-9_Heinonen
20/25
10.9.2010 K Heinonen, Infratek Finland Oy 20
9 Other maintenance methods
Thermocamera:
Local surface hot-spots, loose contacts
Low voltagetransformer busbars:plastic coatingagainst animals
Replacement of oldtype surge arresters
8/3/2019 2-9_Heinonen
21/25
10.9.2010 K Heinonen, Infratek Finland Oy 21
10 Copper corrosion
Some oils are
more risky thanthe others.
Identify risky trafos
Start actions toreduce the risk
(lower temperature,passivator addition).
8/3/2019 2-9_Heinonen
22/25
10.9.2010 K Heinonen, Infratek Finland Oy 22
11 Failure investigations
Data: protectionrelays, fault recorders,visual and audible
observations etc..
Electricalmeasurements andoil testing
False alarm?
Can we repair it on-site?
Active part lifting isneeded?
Transport is needed?
8/3/2019 2-9_Heinonen
23/25
10.9.2010 K Heinonen, Infratek Finland Oy 23
11 Failure investigations continuesFAILURE STUDY CHECK LIST
Date and time of failure (hour, minutes and seconds, if also seconds are available))
Which protection relays / which functions have activated and how (alarm or/and tripping; gas relaytripping before alarm etc.)?
Take the oil sample for laboratory analysis (bottom valve) immediately after the failure and about 24hours after the failure. For 220 and 400 kV transformers also top valve sampling immediately after the
failure. Is there gas in gas relay, how much, what color, is it air or flammable gas? Take gas sample also for
laboratory analysis.
What indications do fault recorders have related to tripping (also nearby substations)?
Transformer load when tripping and mean load 1 hour and 24 hour prior tripping?
On-load tap-changer (OLTC) position when tripping?
Has OLTC operated during tripping and to which direction?
OLTC counter reading and operations from previous OLTC-revision?
Temperature indicators (oil, winding) indication: indication when tripping and max. pointer indications? All abnormal findings according to visual inspection (tank or/and radiator deformations etc.)?
Marks of arching: Bushings, transformer cover, cables etc.?
Cleanness of porcelain insulators?
Dead animals and otherdebris on transformer cover?
Abnormal sounds from transformer before failure?
Has there been breaker or disconnector operations near the transformer before tripping (same or
nearby substations)? Have there been transmission or distribution network disturbances or over voltages just before orduring tripping?
Weatherconditions during and before tripping?
Is there some abnormal according to visual inspection with surge arresters, protection capacitors,disconnectors, circuit breakers and other equipment near the transformer?
8/3/2019 2-9_Heinonen
24/25
10.9.2010 K Heinonen, Infratek Finland Oy 24
12 Conclusions
Utilize the existing transformer capacity as long time as
possible
There are not any excuses why not to apply frequent oil
analysing
Bushings shall be oil sampled or power factor
measured every 10th year
Transformerrefurbishment / untanking Once during
lifetime
8/3/2019 2-9_Heinonen
25/25
10.9.2010 K Heinonen, Infratek Finland Oy 25
Thank you foryour attention