2-9_Heinonen

Embed Size (px)

Citation preview

  • 8/3/2019 2-9_Heinonen

    1/25

    MAINTENANCE AND LIFE TIME EXTENSION OF

    POWER TRANSFORMERS

    Kari Heinonen

    Infratek Finland Oy

    2010 EuroDoble Colloquium

    18-20 October 2010

    Birmingham, United Kingdom

  • 8/3/2019 2-9_Heinonen

    2/25

    10.9.2010 K Heinonen, Infratek Finland Oy 2

    ABSTRACT Visual inspections

    Oil testing

    Oil filtering

    Bushings

    OLTC

    Transformer refurbishment

    Copper corrosion

    Failure investigation

  • 8/3/2019 2-9_Heinonen

    3/25

    10.9.2010 K Heinonen, Infratek Finland Oy 3

    Fig. 1. Finnish 110 kV 400 kV transformer population.

    /2/.

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    1956

    1957

    1958

    1959

    1960

    1961

    1962

    1963

    1964

    1965

    1966

    1967

    1968

    1969

    1970

    1971

    1972

    1973

    1974

    1975

    1976

    1977

    1978

    1979

    1980

    1981

    1982

    1983

    1984

    1985

    1986

    1987

    1988

    1989

    1990

    1991

    1992

    1993

    1994

    1995

    1996

    1997

    1998

    1999

    2000

    2001

    2002

    2003

    Vuosimalli

    k

    pl

    Perushuolletut Huoltamattomat

  • 8/3/2019 2-9_Heinonen

    4/25

    10.9.2010 K Heinonen, Infratek Finland Oy 4

    1 Visual inspections

    1 to 6 monthsinterval

    Bushings:Oil level, Leakages

    etc.

    Corrective actionsimmediately withdangerous findings

  • 8/3/2019 2-9_Heinonen

    5/25

    10.9.2010 K Heinonen, Infratek Finland Oy 5

    2 Oil analysis

    There are not any

    excuses why not to applyfrequent oil analysing.

    DGA and break

    down voltage test:2 years period

    Otheranalysis:

    10 year period

    Warranty period: morefrequent monitoring

  • 8/3/2019 2-9_Heinonen

    6/25

    10.9.2010 K Heinonen, Infratek Finland Oy 6

    2 Oil analysis continues

    Bushings with oil-

    paper insulation: DGA10 years interval, OR

    Power Factor

    measurement, 10

    years interval

  • 8/3/2019 2-9_Heinonen

    7/25

    10.9.2010 K Heinonen, Infratek Finland Oy 7

    2 Oil analysis continues

    FIELD TESTING RESULTS, Bushing

    ASEA GOB 650, 123 kV, 800 A

    Ser. Numb. PF1 PF2 C1 C2

    104807 0,14 % 80,5 % 180 pF 190 pF

    IEC -60137 < 0,7 %

    DGA results ppm (KELMAN Transport X)

    H2 CO2 CO C2H4 C2H6 CH4 C2H2 TCG

    27 3819 964 4 9 18

  • 8/3/2019 2-9_Heinonen

    8/25

    10.9.2010 K Heinonen, Infratek Finland Oy 8

    2 Oil analysis continues

    BUSHINGS 110 kV DGA results ppm (KELMAN Transport X and Lab.analysis)

    Serial

    TYPE Numb H2 CO2 CO C2H4 C2H6 CH4 C2H2 TCG

    GOB 650 104807 27 3819 964 4 9 18

  • 8/3/2019 2-9_Heinonen

    9/25

    10.9.2010 K Heinonen, Infratek Finland Oy 9

    3 On-site and on-line gas analysis

    280 MVA,

    400/15 kV

    On-line gas

    monitoring

  • 8/3/2019 2-9_Heinonen

    10/25

    10.9.2010 K Heinonen, Infratek Finland Oy 10

    4 Oil filtering, degassing and regeneration

    On-site oil filtering: Start ofrepair activities needs to bedelayed

    Not any corrective action

    Low break down voltage:Filtering and oil degassing

    Continuous degassing

    Oil regeneration: Aged oil asgood as new oil.

  • 8/3/2019 2-9_Heinonen

    11/25

    10.9.2010 K Heinonen, Infratek Finland Oy 11

    5 Monitoring of transformer bushings

    Oil sampling or powerfactor measurement 10year period

    When refurbishingTrafo:Lab. Testing: voltage test,tan delta, partial

    discharges, capacitance.

    2,0 % of all 110 kVbushings tested had minorfailures and 2,5 % ofbushings had to bescrapped immediately

  • 8/3/2019 2-9_Heinonen

    12/25

    10.9.2010 K Heinonen, Infratek Finland Oy 12

    5 Monitoring of transformer bushings continue

    LAB. TESTING RESULTS

    ASEA GOB 550, 123 kV, 800 A

    PD PD

    Ser. Numb. Tan d 0,61 x Un 1,0 x Un.

    141399 0,45 % < 3 pC < 3 pC141341 0,46 % < 3 pC < 3 pC

    141334 0,45 % < 3 pC < 3 pC

    141335 0,50 % < 3 pC < 3 pC

    IEC -60137 < 0,7 % < 5 pC < 10 pC

    Voltage test 0,75 x 230 kV, 50 Hz, 1 min

  • 8/3/2019 2-9_Heinonen

    13/25

    10.9.2010 K Heinonen, Infratek Finland Oy 13

    6 On-load tap-changer service

    Five to six years

    period

    Oil sampling, visual

    inspections, relaytesting, bushing and

    transformer power

    factor testing etc.during the same

    outage.

  • 8/3/2019 2-9_Heinonen

    14/25

    10.9.2010 K Heinonen, Infratek Finland Oy 14

    7 Transformer refurbishment

    Refurbishment: Lifting of active part

    (core and windings; untanking)

    On-site, power plant, repair shop,

    at the manufacturer

    Finland ca. 30 % of all 110 kV

    400 kV transformers(ca. 2000 pcs.) revised

    WHY: Better reliability,

    Longer lifetime, Environment

    Cost 1520 % of new price.

  • 8/3/2019 2-9_Heinonen

    15/25

    10.9.2010 K Heinonen, Infratek Finland Oy 15

    7 Transformer refurbishment continues

    110 kV transformers:

    Trailertransportationto workshop

    4 to 6 weeks including

    transportations

    On-site refurbishment:

    * 110 kV, 100 MVA +

    * (220 kV transformers)

    * 400 kV transformers

  • 8/3/2019 2-9_Heinonen

    16/25

    10.9.2010 K Heinonen, Infratek Finland Oy 16

    7 Transformer refurbishment continues

    Tightening of windings

    Drying of paper insulation

    Revision and modifications oftap-changerincludingselector

    Oil degassing and filtering

    High-voltage testing ofbushings Replacement of gaskets

    Replacement of protection relays and devices

    Addition of a separate expansion vessel for on-load

    tap-changer etc. Painting

    Documentation

  • 8/3/2019 2-9_Heinonen

    17/25

    10.9.2010 K Heinonen, Infratek Finland Oy 17

    .

    7 Transformer refurbishment continues

    Findings 1 / 120 kV, 63 MVA, 1974

  • 8/3/2019 2-9_Heinonen

    18/25

    10.9.2010 K Heinonen, Infratek Finland Oy 18

    .

    7 Transformer refurbishment continues

    Findings 2 / 121 kV, 50 MVA, 1969

  • 8/3/2019 2-9_Heinonen

    19/25

    10.9.2010 K Heinonen, Infratek Finland Oy 19

    8 Refurbishment of distribution andspecial transformers

    50 kVA 1000 kVA: Whenmoving the transformer

    Electric filter rectifiertransformers: Oil samplingwith five years interval andrevision by lifting the active

    part with ten years interval.

  • 8/3/2019 2-9_Heinonen

    20/25

    10.9.2010 K Heinonen, Infratek Finland Oy 20

    9 Other maintenance methods

    Thermocamera:

    Local surface hot-spots, loose contacts

    Low voltagetransformer busbars:plastic coatingagainst animals

    Replacement of oldtype surge arresters

  • 8/3/2019 2-9_Heinonen

    21/25

    10.9.2010 K Heinonen, Infratek Finland Oy 21

    10 Copper corrosion

    Some oils are

    more risky thanthe others.

    Identify risky trafos

    Start actions toreduce the risk

    (lower temperature,passivator addition).

  • 8/3/2019 2-9_Heinonen

    22/25

    10.9.2010 K Heinonen, Infratek Finland Oy 22

    11 Failure investigations

    Data: protectionrelays, fault recorders,visual and audible

    observations etc..

    Electricalmeasurements andoil testing

    False alarm?

    Can we repair it on-site?

    Active part lifting isneeded?

    Transport is needed?

  • 8/3/2019 2-9_Heinonen

    23/25

    10.9.2010 K Heinonen, Infratek Finland Oy 23

    11 Failure investigations continuesFAILURE STUDY CHECK LIST

    Date and time of failure (hour, minutes and seconds, if also seconds are available))

    Which protection relays / which functions have activated and how (alarm or/and tripping; gas relaytripping before alarm etc.)?

    Take the oil sample for laboratory analysis (bottom valve) immediately after the failure and about 24hours after the failure. For 220 and 400 kV transformers also top valve sampling immediately after the

    failure. Is there gas in gas relay, how much, what color, is it air or flammable gas? Take gas sample also for

    laboratory analysis.

    What indications do fault recorders have related to tripping (also nearby substations)?

    Transformer load when tripping and mean load 1 hour and 24 hour prior tripping?

    On-load tap-changer (OLTC) position when tripping?

    Has OLTC operated during tripping and to which direction?

    OLTC counter reading and operations from previous OLTC-revision?

    Temperature indicators (oil, winding) indication: indication when tripping and max. pointer indications? All abnormal findings according to visual inspection (tank or/and radiator deformations etc.)?

    Marks of arching: Bushings, transformer cover, cables etc.?

    Cleanness of porcelain insulators?

    Dead animals and otherdebris on transformer cover?

    Abnormal sounds from transformer before failure?

    Has there been breaker or disconnector operations near the transformer before tripping (same or

    nearby substations)? Have there been transmission or distribution network disturbances or over voltages just before orduring tripping?

    Weatherconditions during and before tripping?

    Is there some abnormal according to visual inspection with surge arresters, protection capacitors,disconnectors, circuit breakers and other equipment near the transformer?

  • 8/3/2019 2-9_Heinonen

    24/25

    10.9.2010 K Heinonen, Infratek Finland Oy 24

    12 Conclusions

    Utilize the existing transformer capacity as long time as

    possible

    There are not any excuses why not to apply frequent oil

    analysing

    Bushings shall be oil sampled or power factor

    measured every 10th year

    Transformerrefurbishment / untanking Once during

    lifetime

  • 8/3/2019 2-9_Heinonen

    25/25

    10.9.2010 K Heinonen, Infratek Finland Oy 25

    Thank you foryour attention