23
V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 www.eaton.com 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2.3 Molded Case Circuit Breakers Series C 100% Rated Digitrip RMS 510 Circuit Breakers The NEC allows the breaker to be rated at 100% of its frame size in an assembly, provided that 90°C wire is applied at 75°C ampacity. Order as individual components: breaker frame (which includes trip unit) and rating plug. 100% Rated Digitrip RMS 510 Circuit Breakers Note 1 Includes B2016RDL rear connectors. Maximum Continuous Ampere Rating at 40°C Circuit Breaker Frame Only Digitrip Rating Plug Only L – Adjustable Long Delay Pickup (I r ) with Adjustable Long Delay Time S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I 2 t or Flat Response) I – Adjustable Instantaneous Pickup G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time Delay (I 2 t or Flat Response) Rated Current (I n ) Fixed Rating Plug LI LS LSI LIG LSG LSIG Catalog Number Catalog Number Three-Pole Standard Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac 1600 CRD316T51W CRD316T53W CRD316T52W CRD316T54W CRD316T55W CRD316T56W 800 RP6R16A080 1000 RP6R16A100 1200 RP6R16A120 1600 RP6R16A160 2000 1 CRD320T51W CRD320T53W CRD320T52W CRD320T54W CRD320T55W CRD320T56W 1000 RP6R20A100 1200 RP6R20A120 1600 RP6R20A160 2000 RP6R20A200 Three-Pole High Interrupting Capacity 600 Vac Rated 100 kAIC at 480 Vac 1600 CRDC316T53W CRDC316T52W CRDC316T54W CRDC316T55W CRDC316T56W 800 RP6R16A080 1000 RP6R16A100 1200 RP6R16A120 1600 RP6R16A160 2000 1 CRDC320T51W CRDC320T53W CRDC320T52W CRDC320T54W CRDC320T55W CRDC320T56W 1000 RP6R20A100 1200 RP6R20A120 1600 RP6R20A160 2000 RP6R20A200

2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

  • Upload
    others

  • View
    21

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 www.eaton.com

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2.3 Molded Case Circuit Breakers

Series C

100% Rated Digitrip RMS 510 Circuit BreakersThe NEC allows the breaker to be rated at 100% of its frame size in an assembly, provided that 90°C wire is applied at 75°C ampacity. Order as individual components: breaker frame (which includes trip unit) and rating plug.

100% Rated Digitrip RMS 510 Circuit Breakers

Note1 Includes B2016RDL rear connectors.

MaximumContinuousAmpereRatingat 40°C

Circuit Breaker Frame Only Digitrip Rating Plug OnlyL – Adjustable Long Delay Pickup (Ir) with Adjustable Long Delay TimeS – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response)I – Adjustable Instantaneous Pickup G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time Delay (I2t or Flat Response)

Rated Current (In)

Fixed Rating PlugLI LS LSI LIG LSG LSIG

Catalog Number Catalog Number

Three-Pole Standard Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac

1600 CRD316T51W CRD316T53W CRD316T52W CRD316T54W CRD316T55W CRD316T56W 800 RP6R16A080

1000 RP6R16A100

1200 RP6R16A120

1600 RP6R16A160

2000 1 CRD320T51W CRD320T53W CRD320T52W CRD320T54W CRD320T55W CRD320T56W 1000 RP6R20A100

1200 RP6R20A120

1600 RP6R20A160

2000 RP6R20A200

Three-Pole High Interrupting Capacity 600 Vac Rated 100 kAIC at 480 Vac

1600 — CRDC316T53W CRDC316T52W CRDC316T54W CRDC316T55W CRDC316T56W 800 RP6R16A080

1000 RP6R16A100

1200 RP6R16A120

1600 RP6R16A160

2000 1 CRDC320T51W CRDC320T53W CRDC320T52W CRDC320T54W CRDC320T55W CRDC320T56W 1000 RP6R20A100

1200 RP6R20A120

1600 RP6R20A160

2000 RP6R20A200

carment1
Typewritten Text
Cross Reference RA Part Number PN-222023
carment1
Red_Pointed_Right
carment1
Highlight
carment1
Red_Pointed_Up_Right
Page 2: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

V4-T2-250 Volume 4—Circuit Protection CA08100005E—August 2013 www.eaton.com

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2.3 Molded Case Circuit Breakers

Series C

Technical Data and Specifications

UL 489/CSA Interrupting Capacity Ratings 1

IEC 947-2 Interrupting Capacity Ratings 1

Notes1 Utilization Category A circuit breakers.2 100% rated breakers.

See Page V4-T2-251 for Trip Unit Specifications.

CircuitBreakerType

Numberof Poles

Interrupting Capacity (kA Symmetrical Amperes)Volts AC (50/60 Hz) 240 277 480 600

RD 3, 4 125 — 65 50

CRD 2 3 125 — 65 50

RDC 3, 4 200 — 100 65

CRDC 2 3 200 — 100 65

CircuitBreakerType

Numberof Poles

Interrupting Capacity (kA Symmetrical Amperes)Volts AC (50/60 Hz) 240 415 690

RD

Icu 3, 4 135 70 25

Ics 3, 4 100 50 13

RDC

Icu 3, 4 200 100 35

Ics 3, 4 100 50 18

carment1
Highlight
Page 3: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Volume 4—Circuit Protection CA08100005E—August 2013 www.eaton.com V4-T2-253

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2.3Molded Case Circuit Breakers

Series C

Dimensions and WeightsDimensions in Inches (mm)

RD Frame

RD-Frame, Three-Pole, 1600 and 2000 Amperes

Approximate Shipping Weight in Lbs (kg)

RD Frame

Note1 No four-pole for CRD and CRDC.

Numberof Poles Width Height Depth

3 15.50 (393.7) 16.00 (406.4) 9.75 (247.7)

4 20.00 (508.0) 16.00 (406.4) 9.75 (247.7)

PushToTrip

9.69

(246.1)

5.09

(129.4)

7.25

(184.2)

14.50

(368.3)

CL Breaker

HandleCL

11.13 (0.4) Dia.

(4 Holes) Use 4,

0.38 (Mil) Dia. Bolts

for Mounting Breaker

7.75

(196.9)

15.00

(381.0)

0.16

(4.0)

R Typ.

6.65

(166.7) 12.91

(327.8)

Front View

Side View15.50

(393.7)

9.00

(228.6)

16.00

(406.4)

Complete BreakerBreaker Type Three-Pole Four-Pole

1600 Amperes

RD, CRD 1, RDC, CRDC 1 102 (46.3) 135 (61.2)

2000 Amperes

RD, RDC 102 (46.3) 135 (61.2)

CRD, CRDC 130 (59.0) 175 (79.4)

2500 Amperes

RD, RDC 135 (61.2) 182 (82.6)

carment1
Highlight
Page 4: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Application Data29-167R

Page 1

Cutler-Hammer

Westinghouse &Cutler-Hammer ProductsFive Parkway CenterPittsburgh, Pennsylvania, U.S.A. 15220

Breaker Description Curve No. Page

Series C Types RD, CRD, RDC, CRDC Circuit Breakers Equipped WithDigitrip RMS 310 Trip Units

Typical Instantaneous Time-Phase Current Characteristic CurveBased on In ....................................................................................... SC-5629-93 2

Typical Long Delay/Short Delay Time-Phase CurrentCharacteristic Curve Based on In ................................................... SC-5630-93 3

Typical Ground Fault/Protection Time/Current CharacteristicCurve Based on In ............................................................................ SC-5631-93 4

Series C Types RD, CRD, RDC, CRDC Circuit Breakers Equipped WithDigitrip RMS 510/610/810 Trip Units

Typical Instantaneous Time-Phase Current Characteristic CurveBased on In ....................................................................................... SC-5626-93 5

Typical Long Delay/Short Delay Time-Phase CurrentCharacteristic Curve Based on Ir ␣ ................................................... SC-5627-93 6

Typical Ground Fault/Protection Time/Current CharacteristicCurve Based on In ............................................................................ SC-5628-93 7

Series C R-Frame Circuit Breakers Equipped With 1600/2000A Digitrip OPTIM Trip UnitsLong Delay I2t, Short Delay I2t ........................................................... SC-6336-96 9Long Delay I2t, Short Delay Flat ........................................................ SC-6337-96 10Long Delay I4t, Short Delay Flat ........................................................ SC-6338-96 11Instantaneous and Override, 1600 Amperes ................................... SC-6342-96 15Instantaneous and Override, 2000 Amperes ................................... SC-6343-96 16Ground Fault or Ground Fault Alarm Only, 1600 Amperes ........... SC-6345-96 18Ground Fault or Ground Fault Alarm Only, 2000 Amperes ........... SC-6346-96 19

Series C R-Frame Circuit Breakers Equipped With 2500A Digitrip OPTIM Trip UnitsLong Delay I2t, Short Delay I2t ........................................................... SC-6339-96 12Long Delay I2t, Short Delay Flat ........................................................ SC-6340-96 13Long Delay I4t, Short Delay Flat ........................................................ SC-6341-96 14Instantaneous and Override .............................................................. SC-6344-96 17Ground Fault or Ground Fault Alarm Only ...................................... SC-6347-96 20

DefinitionsIn is the maximum value of continuous current for which the trip unit can be set.In is the basis (or reference) for both the Instantaneous and the Ground protection currentsettings.The value of the rating plug is printed on the Rating Plug.

Ir is the basis for both the Long Delay and the Short Delay (if provided) protection currentsettings.The value of Ir is the Long Delay Current Setting x In.

Individual oversize copies of curves listed above printed on onion-skin paper are availablein limited quantity from:

Cutler-HammerWestinghouse &Cutler-Hammer ProductsFive Parkway CenterPittsburgh, PA 15220

When ordering onion-skin curves, use number at bottom of page where curve appears,i.e., SC-5629-93. Requests for full sets of curves will not be honored.

Time/Current Characteristic Curves forWestinghouse Series C® R-FrameCircuit Breakers

October 1997Mailed to: E/29-100A Westinghouse

Series C ®

Molded CaseCircuit BreakersR-Frame

Page 5: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Application Data29-167R

Page 2

AB DE-ION Circuit Breakers

October 1997

Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 310 Trip Units. Typical Instanta-neous Time-Phase Current Characteristic Curve Based on I

n

Curve No. SC-5629-93

6X

8X

4X

7X

2X

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard FixedRating Plug

Short DelayPick UpSettings(Tolerance ±10%)

5X

3X

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.5

.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

201054321.8.6

1.8.6CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.7 .9 6 7 8 9

20105432 6 7 8 9.7 .9

CURRENT IN AMPS

.02

.03

.04

.05Fixed InstantaneousOverride ➁

10,0

00

.1

.01

20,0

00

.001

SECO

NDS

30,0

00

40,0

00

50,0

00

100,

000

InterruptingRatingDeterminesEnd ofCurve ➂

NP6645C79H01

Short DelayPickup

In

In_Cat._Engaged

Remove

NP6635C68H07 Made in U.S.A.

Digitrip RMS 310

Cell No.

Digitrip RMS 310 Rating PlugFor Use in R Circuit Breaker Only

WestinghouseDigitalProtection

FrameRatingAmperes(Max.)

Available Rating PlugsAmpereRating (In)

Type Short DelayPickup RangeAmperes

CatalogNumber

(Icu)

500V

4265

380-415V

065100

IEC 947-2220-240V

125200

600V

5065

480V

065100

UL/CSA240V

125200

RD, CRDRDC, CRDC

Circuit Breaker Time/Current Curves (Phase Current) ➃

Series C® R-Frame Circuit BreakersEquipped With Type Digitrip RMS 310 Trip Units

Interrupting Ratings – 50/60 HzRMS Sym. Amperes (kA)

For 2500A styles, maximum short delay pickup setting = 6X.

For high fault current levels a fixed instantaneous override is provided at 17,500A(Tolerance ±15%).

The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

For ground fault time-current curves see SC-5631-93.

Not UL/CSA Listed.

Utilization Category AIcs = 0.25 IcuUimp = 8 kV

Typical Trip Unit Nameplate

For use with Trip Unit Catalog Numbers

2000A Max.RES2000LSRES2000LSGRES2000LS

2500A Max.RES2500LSRES2500LSGRES2500LS

16001400125012001000800800, 1000, 1200, 1600800, 1000, 1250, 1600

2000160014001250120010001000, 1200, 1600, 20001000, 1250, 1600, 2000

250020001600125012001200, 1600, 2000, 25001250, 1600, 2000, 2500

FixedFixedFixedFixedFixedFixedAdj.Adj.

FixedFixedFixedFixedFixedFixedAdj.Adj.

FixedFixedFixedFixedFixedAdj.Adj.

16RES16T16RES14T16RES125T➄16RES12T16RES10T16RES08TA16RES16T1A16RES16T2➄

20RES20T20RES16T20RES14T20RES125T➄20RES12T20RES10TA20RES20T1A20RES20T2➄

25RES25T25RES20T25RES16T25RES125T➄25RES12TA25RES25T1A25RES25T2➄

3200-128002800-112002500-100002400-96002000-80001600-64001600-128001600-12800

4000-160003200-128002800-112002500-100002400-96002000-80002000-160002000-16000

5000-150004000-120003200-96002500-75002400-720024000-150002500-15000

1600

2000

2500

BreakerType

1600A Max.RES1600LSRES1600LSGRES1600LS

NotesCurve accuracy applies from –20°C to +55°C ambient. For possible ampere derating forambient above 40°C, refer to Cutler-Hammer.

Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No.STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991.

Page 6: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Application Data29-167R

Page 3

AB DE-ION Circuit Breakers

October 1997

Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 310 Trip Units. Typical LongDelay/Short Delay Time-Phase Current Characteristic Curve Based on I

n

6X

8X

4X

3X

2X

Standard FixedRating Plug

200 ms

100 ms

I

300 ms

5X

FrameRatingAmperes(Max.)

Available Rating PlugsAmpereRating (In)

Type Short DelayPickup RangeAmperes

CatalogNumber

(Icu)

500V

4265

380-415V

065100

IEC 947-2220-240V

125200

600V

5065

480V

065100

UL/CSA240V

125200

Short DelayPickup

In

Short DelayTime

Sec

NP6645C79H02

In_Cat._Engaged

Remove

NP6635C68H07 Made in U.S.A.

Digitrip RMS 310

Cell No.

Digitrip RMS 310 Rating PlugFor Use in R Circuit Breaker Only

WestinghouseDigitalProtection

·

Circuit Breaker Time/Current Curves (Phase Current) ➃

Series C® R-Frame Circuit BreakersEquipped With Type Digitrip RMS 310 Trip Units

Interrupting Ratings – 50/60 HzRMS Sym. Amperes (kA)

Utilization Category AIcs = 0.25 IcuUimp = 8 kV

Typical Trip Unit Nameplate

For use with Trip Unit Catalog Numbers

2000A Max.RES2000LSIRES2000LSIGRES2000LSI

2500A Max.RES2500LSIRES2500LSIGRES2500LSI

16001400125012001000800800, 1000, 1200, 1600800, 1000, 1250, 1600

2000160014001250120010001000, 1200, 1600, 20001000, 1250, 1600, 2000

250020001600125012001200, 1600, 2000, 25001250, 1600, 2000, 2500

FixedFixedFixedFixedFixedFixedAdj.Adj.

FixedFixedFixedFixedFixedFixedAdj.Adj.

FixedFixedFixedFixedFixedAdj.Adj.

16RS16T16RS14T16RS125T➄16RS12T16RS10T16RS08TA16RS16T1A16RS16T2➄

20RS20T20RS16T20RS14T20RS125T➄20RS12T20RS10TA20RS20T1A20RS20T2➄

25RES25T25RES20T25RES16T25RES125T➄25RES12TA25RES25T1A25RES25T2➄

3200-128002800-112002500-100002400-96002000-80001600-64001600-128001600-12800

4000-160003200-128002800-112002500-100002400-96002000-80002000-160002000-16000

5000-150004000-120003200-96002500-75002400-720024000-150002500-15000

1600

2000

2500

BreakerType

1600A Max.RES1600LSIRES1600LSIGRES1600LSI

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.5

.5 201054321.8.6

1.8.6CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.7 .9 6 7 8 9

20105432 6 7 8 9

Short DelayPick UpSettings(Tolerance±10%)

Minimum TotalClearing Time

Maximum TotalClearing Time

.7 .9

.02

.03

.04

.05Fixed InstantaneousOverride ➁

InterruptingRatingDeterminesEnd ofCurve ➂

.1

.01

10,0

00

20,0

00

.001

SECO

NDS

CURRENT IN AMPS

30,0

00

40,0

00

50,0

00

100,

000

7X

200,

000

RD, CRDRDC, CRDC

For 2500A styles, maximum short delay pickup setting = 6X.For high fault current levels a fixed instantaneous override is provided at 17,500A(Tolerance ±15%).The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.For ground fault time-current curves see SC-5631-93.Not UL/CSA Listed.

➀➁

➃➄

NotesCurve accuracy applies from –20°C to +55°C ambient. For possible ampere derating forambient above 40°C, refer to Cutler-Hammer.

Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No.STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991.

Curve No. SC-5630-93

Page 7: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Application Data29-167R

Page 4

AB DE-ION Circuit Breakers

October 1997

Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 310 Trip Units. Typical GroundFault/Protection Time/Current Characteristic Curve Based on I

n

Curve No. SC-5631-93

1200

A.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR

1 MIN

UT

E2 H

OU

RS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 H

OU

R1

MIN

UT

E2

HO

UR

S

100

8060 907050 1000

800

600

900

700

500

400

300

200

4000

3000

2000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

600

A.

I

.15 SEC

Ground Fault PickupSettings(Tolerance ±10% Except,±20% on 200 A. Setting)

400

A.

200

A.

1000

A.

800

A.

.3 SEC

.5 SEC

NP6645C79H05

Short DelayPickup

In

In_Cat._Engaged

Remove

NP6635C68H07 Made in U.S.A.

Digitrip RMS 310

Cell No.

WestinghouseDigitalProtection

·

NP6645C79H06

In_Cat._Engaged

Remove

NP6635C68H07 Made in U.S.A.

Digitrip RMS 310

Cell No.

WestinghouseDigitalProtection

·

Gnd. FaultPickup

*

Gnd. FaultTime

Sec

Gnd.

Gnd. FaultPickup

*

Gnd. FaultTime

Sec

Gnd.

Short DelayPickup

In

Short DelayTime

Sec

*Gnd. Fault Pickup

A

BCDEFHK

200A

400A600A800A1000A1200A1200A1200A

SETTING CURRENT*Gnd. Fault Pickup

A

BCDEFHK

200A

400A600A800A1000A1200A1200A1200A

SETTING CURRENT

Digitrip RMS 310 Rating PlugFor Use in R Circuit Breaker Only

Digitrip RMS 310 Rating PlugFor Use in R Circuit Breaker Only

Circuit Breaker Time/Current Curves (Phase Current) ➀

Series C® R-Frame Circuit BreakersEquipped with Type Digitrip RMS 310 Trip Unitsfor Ground Fault Protection

For use with Trip Unit Catalog Numbers1600A Max.RES1600LSGRES1600LSIG

2000A Max.RES2000LSGRES2000LSIG

2500A Max.RES2500LSGRES2500LSIG

NotesCurve accuracy applies from –20°C to +55°C ambient.

Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2.For field testing using primary injection methods, follow NEMA publication AB-4-1991.

➀ For phase time-current curves see SC-5629-93 and SC-5630-93.

Page 8: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Application Data29-167R

Page 5

AB DE-ION Circuit Breakers

October 1997

Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 510/610/810 Trip Units. TypicalInstantaneous Time-Phase Current Characteristic Curve Based on I

n

2

10

M2

I M P O R T A N T

ApplicationDeterminesEnd of Curve

AvailableInstantaneousSettings2, 2.5, 3, 4, 5, 6, M1 or M2 x In

4

2.5

3 5

648

M1

3

9M2

7M1M2

3

1

Plug Rating (In) M1 M2

800-1600 A2000 A2500 A

8 x In8 x In7 x In

10 x In9 x In7 x In

Values for M1 and M2 as marked on Rating Plug

1

2

®

CURRENT IN MULTIPLES OF PLUG RATING In

TIM

E IN

SEC

ONDS

1000

500

300

200

100

TIME IN

SECONDS

.1.07.05 .7.5.4.3.2 1 75432 10 7050403020

.1.07.05 .7.5.4.3.2 1 75432 10 7050403020

400

900800700600

50

30

20

10

40

90807060

5

3

2

1

4

9876

.5

.3

.2

.1

.4

.9

.8

.7

.6

.05

.03

.02

.01

.04

.09

.08

.07

.06

1000

500

300

200

100

400

900800700600

50

30

20

10

40

90807060

5

3

2

1

4

9876

.5

.3

.2

.1

.4

.9

.8

.7

.6

.05

.03

.02

.01

.04

.09

.08

.07

.06

Series C R-Frame Circuit Breakers withDIGITRIP RMS 510/610/810 Trip UnitsTypical Instantaneous Time-Phase Current Characteristic Curve (I)

CURRENT IN MULTIPLES OF PLUG RATING In

TRIP UNITS ARE NOT AVAILABLE WITH ONLYINSTANTANEOUS PROTECTION. THIS CURVE MUST BEUSED in conjunction WITH Curve No. SC-5627-93 for LONGDELAY (and if applicable SHORT DELAY) PROTECTION toobtain the complete time-current characteristic.

Available Rating Plugs Marked 50/60 Hz

RatingAmperes(Max.)

PlugRating (In)Amperes

Frequency ➄Hz

CatalogNumber

1600 1600125012001000

800

50/605050/6050/6050/60

RP6R16A160RP6R16A125RP6R16A120RP6R16A100RP6R16A080

2000 20001600125012001000

50/6050/605050/6050/60

RP6R20A200RP6R20A160RP6R20A125RP6R20A120RP6R20A100

2500 250020001600

50/6050/6050/60

RP6R25A250RP6R25A200RP6R25A160

Interrupting Ratings @ 50/60 HzRMS Sym. Amperes (kA)

BreakerType

UL/CSA240V 480V 600V 220-240V 380-415V 500V

IEC 947-2 (Icu)

RD, CRDRDC, CRDC

125200

65100

5065

125200

65100

4265

Utilization Category AIcs = 0.5 IcuUimp = 8 kV

Notes

➀➁➂➃

➄➅➆➇

Tolerances➇

INST Range = 90% to 110% of setting

For 2000A Rating Plug.For 2500A Rating Plug.For 800-1600A Rating Plugs.The end of the curve is determined by the interrupting rating of the circuitbreaker. See above tabulation.The Rating Plug is for 50 and 60 Hz applications.Not UL/CSA listed.For Types RD and RDC only.Curves apply from –20°C to +55°C ambient. Temperatures above 95°Ccause automatic trip. For possible ampere derating for ambient above40°C, refer to Cutler-Hammer.

Curve No. SC-5626-93

Page 9: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Application Data29-167R

Page 6

AB DE-ION Circuit Breakers

October 1997

Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 510/610/810 Trip Units. TypicalLong Delay/Short Delay Time-Phase Current Characteristic Curve Based on I

r

Curve No. SC-5627-93

8

S2

AvailableLong DelayTimeSettingsShown@ 6 x Ir2, 4, 7, 10, 12,15, 20, 24

.1

SDM

2

AvailableLong Delay (Ir)Settings.5, .6, .7, .8, .85, .9, .95 or 1 x In = Ir

MinimumTotalClearingTime

MaximumTotalClearingTime

24

7

2

4

AvailableShort DelaySettings2, 2.5, 3, 4, 5, 6,S1(7) or S2(8) x Ir

.5 2

.4 2

2.2

.3 2

2

2.5

3 5

64

7S1

ApplicationDeterminesEnd of Curve

.3

1

TIM

E IN

SEC

ONDS

1000

500

300

200

100

TIME IN

SECONDS

400

900800700600

50

30

20

10

40

90807060

5

3

2

1

4

9876

.5

.3

.2

.1

.4

.9

.8

.7

.6

.05

.03

.02

.01

.04

.09

.08

.07

.06

1000

500

300

200

100

400

900800700600

50

30

20

10

40

90807060

5

3

2

1

4

9876

.5

.3

.2

.1

.4

.9

.8

.7

.6

.05

.03

.02

.01

.04

.09

.08

.07

.06

CURRENT IN MULTIPLES OF LONG DELAY SETTINGS Ir.1.07.05 .7.5.4.3.2 1 85432 10 3020

.1.07.05 .7.5.4.3.2 1 85432 10 403020

CURRENT IN MULTIPLES OF LONG DELAY SETTINGS IrCURRENT IN kA

Series C R-Frame Circuit Breakers withDIGITRIP RMS 510/610/810 Trip UnitsTypical Long Delay and Short DelayTime-Phase Current Characteristic Curve (LS)

6

6IMPORTANT

75432 10 20

.3

22.5 4

6

AvailableI2t ShapeShort Delay TimeSettingsIndicated by *

1

.5

.3

.2

.1

.4

.01705040302010

3.1

.4

.5

.2

Available FlatResponseShort DelayTime Settings.1, .2, .3, .4, or .5

FixedInstantaneousOverride

4

.1*

SDM

2

2.3*

.5* 2

®

Available Rating Plugs 50/60 Hz

RatingAmperes(Max.)

PlugRating (In)Amperes

Frequency ➄Hz

CatalogNumber

1600 1600125012001000

800

50/605050/6050/6050/60

RP6R16A160RP6R16A125RP6R16A120RP6R16A100RP6R16A080

2000 20001600125012001000

50/6050/605050/6050/60

RP6R20A200RP6R20A160RP6R20A125RP6R20A120RP6R20A100

2500 250020001600

50/6050/6050/60

RP6R25A250RP6R25A200RP6R25A160

Interrupting Ratings @ 50/60 HzRMS Sym. Amperes (kA)

BreakerType

UL/CSA240V 480V 600V 220-240V 380-415V 500V

IEC 947-2 (Icu)

RD, CRDRDC, CRDC

125200

65100

5065

125200

65100

4265

Utilization Category AIcs = 0.5 IcuUimp = 8 kV

Notes

➄➅➆➇

Tolerances➇

LDS Range = 150% to 130% of Setting.LDT Range = 67% to 100% of Setting, at 6 x Ir .SDS Range = 90% to 110% of Setting.

Long Time Memory function automatically shortens long time delay asoverload conditions recur.With zone interlocking on short delay utilized and no restraining signal, theminimum time band applies – regardless of setting.The end of the curve is determined by the interrupting rating of the circuitbreaker. See above tabulation.For high fault current levels a fixed instantaneous override is provided at17,500A (Tolerance ± 15%).The Rating Plug is for 50 and 60 Hz applications.Not UL/CSA listed.For Types RD and RDC only.Curves apply from –20°C to +55°C ambient. Temperatures above 95°C causeautomatic trip. For possible ampere derating for ambient above 40°C, referto Cutler-Hammer.

SDM

Page 10: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Application Data29-167R

Page 7

AB DE-ION Circuit Breakers

October 1997

Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 510/610/810 Trip Units. TypicalGround Fault/Protection Time/Current Characteristic Curve Based on I

n

A K

A

B

D

®

I2t Shape for GroundTime Delay Settings Indicated by *

AvailableGround FaultTime DelaySettingsFlat Response

.4

GDM

1

AvailableGround FaultSettings (Typical)for Exact Valuesand Tolerances ofLetter Codes,See Chart

.2 1

.1 1

.3 1

.5 1

.1* 1

.3* 1

.5* 1

GDM

AvailableGround FaultTime DelaySettingsI2t Response

CURRENT IN MULTIPLES OF PLUG RATING In

TIM

E IN

SEC

ONDS

1000

500

300

200

100

TIME IN

SECONDS

400

900800700600

50

30

20

10

40

90807060

5

3

2

1

4

9876

.5

.3

.2

.1

.4

.9

.8

.7

.6

.05

.03

.02

.01

.04

.09

.08

.07

.06

1000

500

300

200

100

400

900800700600

50

30

20

10

40

90807060

5

3

2

1

4

9876

.5

.3

.2

.1

.4

.9

.8

.7

.6

.05

.03

.02

.01

.04

.09

.08

.07

.06

CURRENT IN MULTIPLES OF PLUG RATING In.1.07.05 .7.5.4.3.2 1 75432 1 .7.5.4.3.2 1 75432 10

.1.07.05 .7.5.4.3.2 1 75432 1 .7.5.4.3.2 1 75432 10

Series C R-Frame Circuit Breakers withDIGITRIP RMS 510/610/810 Trip UnitsTypical Time-Ground Current Characteristic Curve (G)

800

1000

1200

1250

1600

2000

2500

200

250

300

312

400

500

625

Code A➄ B➄ C➄ D➄ E F H K

Ground Fault Settings (Amperes) ➁➂➃

I n plu

g ra

tings

ava

ilabl

e

Notes➀

➁➂➃

With zone interlocking on ground fault utilized and no restraining signal, the minimum timeband applies – regardless of setting.Except as noted tolerances on current levels are ± 10% of values shown in chart.The rating plug is for 50 Hz and 60 Hz, applications.All tabulated values are based on the use of a residual sensing scheme with the samerated current sensor in all phase and neutral conductors.For Testing Purposes Only: When using an external single phase current source to checklow level ground fault current settings, it is advisable to use the Auxiliary Power Module(APM). See TEST PROCEDURES in Instruction Leaflet.

240

300

360

375

480

600

750

280

350

420

438

560

700

875

320

400

480

500

640

800

1000

400

500

600

625

800

1000

1200

480

600

720

750

960

1200

1200

600

750

900

938

1200

1200

1200

800

1000

1200

1200

1200

1200

1200

GDM

Curve No. SC-5628-93

Page 11: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Application Data29-167R

Page 8

AB DE-ION Circuit Breakers

October 1997

Cutler-Hammer

Westinghouse &Cutler-Hammer ProductsFive Parkway CenterPittsburgh, Pennsylvania, U.S.A. 15220

Printed in U.S.A.

Page 12: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Application Data29-167R

Page 9

AB DE-ION Circuit Breakers

October 1997

Curve No. SC-6336-96

R-Frame Circuit Breakers Equipped with 1600/2000A Digitrip OPTIM Trip Units; Long Delay I2t, Short Delay I2t

.01 .01

10,000

5,000

3,000

2,000

1,000

500

300

200

100

50

30

20

10

5

3

2

1 11

.5 .5.5

.3 .3.3

.2 .2.2

.1 .1.1

.05 .05

.03 .03

.02 .02

1 M

INU

TE

1 H

OU

R2

HO

UR

ST

IME

INS

EC

ON

DS

TIM

EIN

SE

CO

ND

S

500

600

700

800

9002 3 20 304 5 6 7 40 50 60 70 80 90 100

100

300100.8

0.9 1

0.5

0.6

0.7 8 9

20 30 40 50 60 70 80 900.5

2 3 5 6 7 108 9

200

400

CURRENT IN MULTIPLES OF LONG DELAY SETTING I

CURRENT IN MULTIPLES OF LONG DELAY SETTING I

1000

2000

3000

4000

5000

6000

7000

8000

9000

10,0

00

0.8

0.7

0.6

0.9

1

Available Rating Plugs

Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

1600125012001000800

20001600125012001000

AmpereRating

(I )n

ORPL16A160ORPL16A125ORPL16A120ORPL16A100ORPL16A080

ORPL20A200ORPL20A160ORPL20A125ORPL20A120ORPL20A100

Rating PlugCatalogNumber

640 -1600500 -1250480 -1200400 -1000320 - 800

800 -2000640 -1600500 -1250480 -1200400 -1000

MaximumAmpereRating

1600

2000

Breaker

Type

RD, CRDRDC,CRDC

UL / CSA

Volts

kA

240

125200

480

65100

600

5065

IEC 947-2

Volts

RD,CRDRDC, CRDC

240 690

U = 8kV

415

kA

Rating

Utilization Category A

Short DelayPickup Range

1.5 to 8x IAmperes

r

Long DelayPickup Range

0.4 to 1 x IAmperes

n

960 - 12800750 - 10000720 - 9600600 - 8000480 - 6400

1200 - 16000960 - 12800750 - 10000720 - 9600600 - 8000

MinimumTotalClearingTime

MaximumTotalClearingTime

AvailableLong DelayTime SettingsShown @ 6 x Ir2-24 seconds +0 ⁄-30%in 0.1 secondincrements

AvailableShort DelayPickup Settings1.5 to 8 x Ir±5% in 0.1increments

Available I t SlopeShort Delay Time Settings0.1 to 0.5 seconds in0.01 second increments

2

Available Long DelayPickup Settings (I )r0.5 to 1 x I = In rin 0.01 increments

Notes1) For field testing primary injection methods, follow NEMA AB4-1991 publications.2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.3) There is a memory effect that can act to shorten the long delay. The memory effect

comes into play if a current above the long delay pickup value exists for a time and thenis cleared by the tripping of a downstream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time reduction is inverse to the amount of time that has elapsed since theprevious overload. Approximately five minutes is required between overloads tocompletely reset the memory.

4) The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), andSC-6347-96 (2500A)

6) This curve is shown as a multiple of the Long Delay Pickup Setting, (Iprogrammed in primary value amperes via a Breaker Interface Module, or OPTIMizer,or a Remote PC (IMPACC System).

7) The Long Delay Pickup Point (indicated by a flashing LED on the product) nominally occursat 116% of the I current, with a +/- 5% tolerance. The short delay settings have conventional100%, +/- 5% as the pickup points.

). This I setting isr r

r

I I

135200

100100

I I

70100

5050

I I

IMP

CU CS CU CS CU CS

2535

1318

8) For additional curve tolerances contact Cutler-Hammer.9) Total clearing times shown include the response times of the trip unit, the breaker opening, and the extinction of the arcing current.

Circuit Breaker Time/Current Curves (Phase Current)Series CT R - Frame Circuit BreakersEquipped With 1600/2000A Digitrip Optim Trip UnitsResponse: LONG DELAY I2t, SHORT DELAY I2t

ApplicationDeterminesEnd of Curve

.5

.3

.1

r

r

24

7

4

2

Page 13: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

October 1997

Application Data29-167RPage 10

AB DE-ION Circuit Breakers

Curve No. SC-6337-96

R-Frame Circuit Breakers Equipped with 1600/2000A Digitrip OPTIM Trip Units; Long Delay I2t, Short Delay Flat

.01 .01

10,000

5,000

3,000

2,000

1,000

500

300

200

100

50

30

20

10

5

3

2

1 11

.5 .5.5

.3 .3.3

.2 .2.2

.1 .1.1

.05 .05

.03 .03

.02 .02

1 M

INU

TE

1 H

OU

R2

HO

UR

ST

IME

INS

EC

ON

DS

TIM

EIN

SE

CO

ND

S

500

600

700

800

9002 3 20 304 5 6 7 40 50 60 70 80 90 100

100

300100.8

0.9 1

0.5

0.6

0.7 8 9

20 30 40 50 60 70 80 900.5

2 3 5 6 7 108 9

200

400

CURRENT IN MULTIPLES OF LONG DELAY SETTING I

CURRENT IN MULTIPLES OF LONG DELAY SETTING I

1000

2000

3000

4000

5000

6000

7000

8000

9000

10,0

00

0.8

0.7

0.6

0.9

1

Available Rating Plugs

1600125012001000800

20001600125012001000

AmpereRating

(I )n

ORPL16A160ORPL16A125ORPL16A120ORPL16A100ORPL16A080

ORPL20A200ORPL20A160ORPL20A125ORPL20A120ORPL20A100

Rating PlugCatalogNumber

640 -1600500 -1250480 -1200400 -1000320 - 800

800 -2000640 -1600500 -1250480 -1200400 -1000

MaximumAmpereRating

1600

2000

Short DelayPickup Range

1.5 to 8x IAmperes

r

960 - 12800750 - 10000720 - 9600600 - 8000480 - 6400

1200 - 16000960 - 12800750 - 10000720 - 9600600 - 8000

MinimumTotalClearingTime

MaximumTotalClearingTime

AvailableLong DelayTime SettingsShown @ 6 x Ir2-24 seconds +0 ⁄-30%in 0.1 secondincrements

AvailableLong Delay (I )rSettings0.5 to 1 x I = In rin 0.01 increments

AvailableShort DelayPickup Settings1.5 to 8 x Ir±5% in 0.1increments

Available FlatShort Delay Time Settings0.1 to 0.5 secondsin 0.01 second increments

Notes1) For field testing primary injection methods, follow NEMA AB4-1991 publications.2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.3) There is a memory effect that can act to shorten the long delay. The memory effect

comes into play if a current above the long delay pickup value exists for a time and thenis cleared by the tripping of a downstream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time reduction is inverse to the amount of time that has elapsed since theprevious overload. Approximately five minutes is required between overloads tocompletely reset the memory.

4) The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), andSC-6347-96 (2500A)

6) This curve is shown as a multiple of the Long Delay Pickup Setting, (Iprogrammed in primary value amperes via a Breaker Interface Module, or OPTIMizer,or a Remote PC (IMPACC System).

7) The Long Delay Pickup Point (indicated by a flashing LED on the product) nominally occursat 116% of the I current, with a +/- 5% tolerance. The short delay settings have conventional100%, +/- 5% as the pickup points.

). This I setting isr r

r

Long DelayPickup Range

0.4 to 1 x IAmperes

n

Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

Breaker

Type

RD, CRDRDC,CRDC

UL / CSA

Volts

kA

240

125200

480

65100

600

5065

IEC 947-2

Volts

RD,CRDRDC, CRDC

240 690

U = 8kVIMP

415

kA

Rating

Utilization Category A

ICU ICS

135200

100100

ICU ICS

70100

5050

ICU ICS

2535

1318

ApplicationDeterminesEnd of Curve

.1

.5

.3

8) For additional curve tolerances contact Cutler-Hammer.9) Total clearing times shown include the response times of the trip unit, the breaker opening, and the extinction of the arcing current.

Circuit Breaker Time/Current Curves (Phase Current)Series CT R - Frame Circuit BreakersEquipped With 1600/2000A Digitrip Optim Trip UnitsResponse: LONG DELAY I2t, SHORT DELAY FLAT

r

r

24

7

4

2

Page 14: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Application Data29-167R

Page 11

AB DE-ION Circuit Breakers

October 1997

Curve No. SC-6338-96

R-Frame Circuit Breakers Equipped with 1600/2000A Digitrip OPTIM Trip Units; Long Delay I4t, Short Delay Flat

.01 .01

10,000

5,000

3,000

2,000

1,000

500

300

200

100

50

30

20

10

5

3

2

1 11

.5 .5.5

.3 .3.3

.2 .2.2

.1 .1.1

.05 .05

.03 .03

.02 .02

1 M

INU

TE

1 H

OU

R2

HO

UR

ST

IME

INS

EC

ON

DS

TIM

EIN

SE

CO

ND

S

500

600

700

800

9002 3 20 304 5 6 7 40 50 60 70 80 90 100

100

300100.8

0.9 1

0.5

0.6

0.7 8 9

20 30 40 50 60 70 80 900.5

2 3 5 6 7 108 9

200

400

CURRENT IN MULTIPLES OF LONG DELAY SETTING I

CURRENT IN MULTIPLES OF LONG DELAY SETTING I

1000

2000

3000

4000

5000

6000

7000

8000

9000

10,0

00

0.8

0.7

0.6

0.9

1

Available Rating Plugs

1600125012001000800

20001600125012001000

AmpereRating

(I )n

ORPL16A160ORPL16A125ORPL16A120ORPL16A100ORPL16A080

ORPL20A200ORPL20A160ORPL20A125ORPL20A120ORPL20A100

Rating PlugCatalogNumber

640 -1600500 -1250480 -1200400 -1000320 - 800

800 -2000640 -1600500 -1250480 -1200400 -1000

MaximumAmpereRating

1600

2000

Short DelayPickup Range

1.5 to 8x IAmperes

r

960 - 12800750 - 10000720 - 9600600 - 8000480 - 6400

1200 - 16000960 - 12800750 - 10000720 - 9600600 - 8000

MinimumTotalClearingTime

MaximumTotalClearingTime

AvailableLong DelayTime SettingsShown @ 6 x Ir1-5 seconds +10 ⁄-40%in 0.1 secondincrements

AvailableShort DelayPickup Settings1.5 to 8 x Ir±5% in 0.1increments

Available FlatShort Delay Time Settings0.1 to 0.5 secondsin 0.01 second increments

Available Long DelayPickup Settings (I )r0.5 to 1 x I = In rin 0.01 increments

5

Notes1) For field testing primary injection methods, follow NEMA AB4-1991 publications.2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.3) There is a memory effect that can act to shorten the long delay. The memory effect

comes into play if a current above the long delay pickup value exists for a time and thenis cleared by the tripping of a downstream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time reduction is inverse to the amount of time that has elapsed since theprevious overload. Approximately five minutes is required between overloads tocompletely reset the memory.

4) The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), andSC-6347-96 (2500A)

6) This curve is shown as a multiple of the Long Delay Pickup Setting, (I-programmed in primary value amperes via a Breaker Interface Module, or OPTIMizer,or a Remote PC (IMPACC System).

7) The Long Delay Pickup Point (indicated by a flashing LED on the product) nominally occursat 116% of the I current, with a +/- 5% tolerance. The short delay settings have conventional100%, +/- 5% as the pickup points.

). This I setting isr r

r

Long DelayPickup Range

0.4 to 1 x IAmperes

n

Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

Breaker

Type

RD, CRDRDC,CRDC

UL / CSA

Volts

kA

240

125200

480

65100

600

5065

IEC 947-2

Volts

RD,CRDRDC, CRDC

240 690

U = 8kVIMP

415

kA

Rating

Utilization Category A

ICU ICS

135200

100100

ICU ICS

70100

5050

ICU ICS

2535

1318

8) For additional curve tolerances contact Cutler-Hammer.9) Total clearing times shown include the response times of the trip unit, the breaker opening, and the extinction of the arcing current.

ApplicationDeterminesEnd of Curve

5

1

.5

.1

Circuit Breaker Time/Current Curves (Phase Current)Series CT R - Frame Circuit BreakersEquipped With 1600/2000A Digitrip Optim Trip UnitsResponse: LONG DELAY I4t, SHORT DELAY FLAT

r

r

Page 15: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

October 1997

Application Data29-167RPage 12

AB DE-ION Circuit Breakers

Curve No. SC-6339-96

R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Long Delay I2t, Short Delay I2t

.01 .01

10,000

5,000

3,000

2,000

1,000

500

300

200

100

50

30

20

10

5

3

2

1 11

.5 .5.5

.3 .3.3

.2 .2.2

.1 .1.1

.05 .05

.03 .03

.02 .02

1 M

INU

TE

1 H

OU

R2

HO

UR

ST

IME

INS

EC

ON

DS

TIM

EIN

SE

CO

ND

S

500

600

700

800

9002 3 20 304 5 6 7 40 50 60 70 80 90 100

100

300100.8

0.9 1

0.5

0.6

0.7 8 9

20 30 40 50 60 70 80 900.5

2 3 5 6 7 108 9

200

400

CURRENT IN MULTIPLES OF LONG DELAY SETTING I

CURRENT IN MULTIPLES OF LONG DELAY SETTING I

1000

2000

3000

4000

5000

6000

7000

8000

9000

10,0

00

0.8

0.7

0.6

0.9

1

Available Rating Plugs

250020001600

AmpereRating

(I )n

ORPL25A250ORPL25A200ORPL25A160

Rating PlugCatalogNumber

1000 -2500800 -2000640 -1600

MaximumAmpereRating

2500

Short DelayPickup Range1.5 to 6.4 x I

Amperesr

1500 - 160001200 - 12800960 - 10240

MinimumTotalClearingTime

MaximumTotalClearingTime

AvailableLong DelayTime SettingsShown @ 6 x Ir2-24 seconds +0 ⁄-30%in 0.1 secondincrements

ApplicationDeterminesEnd of Curve

AvailableShort DelayPickup Settings1.5 to 6.4 x Ir±5% in 0.1increments

.5

.3

.1

Available I t SlopeShort Delay Time Settings0.1 to 0.5 seconds in0.01 second increments

2

Available Long DelayPickup Settings (I )r0.5 to 1 x I = In rin 0.01 increments

Notes1) For field testing primary injection methods, follow NEMA AB4-1991 publications.2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.3) There is a memory effect that can act to shorten the long delay. The memory effect

comes into play if a current above the long delay pickup value exists for a time and thenis cleared by the tripping of a downstream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time reduction is inverse to the amount of time that has elapsed since theprevious overload. Approximately five minutes is required between overloads tocompletely reset the memory.

4) The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), andSC-6347-96 (2500A)

6) This curve is shown as a multiple of the Long Delay Pick-up Setting, (I ). This I setting isprogrammed in primary value amperes via a Breaker Interface Module, or OPTIMizer,or a Remote PC (IMPACC System).

7) The Long Delay Pick-up Point (indicated by a flashing LED on the product) nominally occursat 116% of the I current, with a +/- 5% tolerance. The short delay settings have conventional100%, +/- 5% as the pickup points.

r r

r

Long DelayPickup Range

0.4 to 1 x IAmperes

n

Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

Breaker

Type

RDRDC

UL / CSA

Volts

kA

240

125200

480

65100

600

5065

IEC 947-2

Volts

RDRDC

240 690

U = 8kVIMP

415

kA

Rating

Utilization Category A

ICU ICS

135200

100100

ICU ICS

70100

5050

ICU ICS

2535

1318

8) For additional curve tolerances contact Cutler-Hammer.9) Total clearing times shown include the response times of the trip unit, the breaker opening, and the extinction of the arcing current.

Circuit Breaker Time/Current Curves (Phase Current)Series CT R - Frame Circuit BreakersEquipped With 2500A Digitrip Optim Trip UnitsResponse: LONG DELAY I2t, SHORT DELAY I2t

r

r

24

7

4

2

Page 16: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Application Data29-167R

Page 13

AB DE-ION Circuit Breakers

October 1997

Curve No. SC-6340-96

R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Long Delay I2t, Short Delay Flat

.01 .01

10,000

5,000

3,000

2,000

1,000

500

300

200

100

50

30

20

10

5

3

2

1 11

.5 .5.5

.3 .3.3

.2 .2.2

.1 .1.1

.05 .05

.03 .03

.02 .02

1 M

INU

TE

1 H

OU

R2

HO

UR

ST

IME

INS

EC

ON

DS

TIM

EIN

SE

CO

ND

S

500

600

700

800

9002 3 20 304 5 6 7 40 50 60 70 80 90 100

100

300100.8

0.9 1

0.5

0.6

0.7 8 9

20 30 40 50 60 70 80 900.5

2 3 5 6 7 108 9

200

400

CURRENT IN MULTIPLES OF LONG DELAY SETTING I

CURRENT IN MULTIPLES OF LONG DELAY SETTING I

1000

2000

3000

4000

5000

6000

7000

8000

9000

10,0

00

0.8

0.7

0.6

0.9

1

Available Rating Plugs

250020001600

ORPL25A250ORPL25A200ORPL25A160

1000 -2500800 -2000640 -1600

AmpereRating

(I )n

Rating PlugCatalogNumber

Short DelayPickup Range1.5 to 6.4 x I

Amperesr

MaximumAmpereRating

2500 1500 - 160001200 - 12800960 - 10240

MinimumTotalClearingTime

MaximumTotalClearingTime

ApplicationDeterminesEnd of Curve

.1

.5

.3

AvailableLong DelayTime SettingsShown @ 6 x Ir2-24 seconds +0 ⁄-30%in 0.1 secondincrements

Available FlatShort Delay Time Settings0.1 to 0.5 secondsin 0.01 second increments

AvailableShort DelayPickup Settings1.5 to 6.4 x Ir±5% in 0.1increments

Available Long DelayPickup Settings (I )r0.5 to 1 x I = In rin 0.01 increments

Notes1) For field testing primary injection methods, follow NEMA AB4-1991 publications.2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.3) There is a memory effect that can act to shorten the long delay. The memory effect

comes into play if a current above the long delay pickup value exists for a time and thenis cleared by the tripping of a downstream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time reduction is inverse to the amount of time that has elapsed since theprevious overload. Approximately five minutes is required between overloads tocompletely reset the memory.

4) The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), andSC-6347-96 (2500A)

6) This curve is shown as a multiple of the Long Delay Pick-up Setting, (I ). This I setting isprogrammed in primary value amperes via a Breaker Interface Module, or OPTIMizer,or a Remote PC (IMPACC System).

7) The Long Delay Pick-up Point (indicated by a flashing LED on the product) nominally occurs

8) For additional curve tolerances contact Cutler-Hammer.9) Total clearing times shown include the response times of the trip unit, the breaker opening, and the extinction of the arcing current.

at 116% of the I current, with a +/- 5% tolerance. The short delay settings have conventional100%, +/- 5% as the pickup points.

r r

r

Long DelayPickup Range

0.4 to 1 x IAmperes

n

Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

Breaker

Type

RDRDC

UL / CSA

Volts

kA

240

125200

480

65100

600

5065

IEC 947-2

Volts

RDRDC

240 690

U = 8kVIMP

415

kA

Rating

Utilization Category A

ICU ICS

135200

100100

ICU ICS

70100

5050

ICU ICS

2535

1318

Circuit Breaker Time/Current Curves (Phase Current)Series CT R - Frame Circuit BreakersEquipped With 2500A Digitrip Optim Trip UnitsResponse: LONG DELAY I2t, SHORT DELAY FLAT

r

r

24

7

4

2

Page 17: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

October 1997

Application Data29-167RPage 14

AB DE-ION Circuit Breakers

Curve No. SC-6341-96

R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Long Delay I4t, Short Delay Flat

.01 .01

10,000

5,000

3,000

2,000

1,000

500

300

200

100

50

30

20

10

5

3

2

1 11

.5 .5.5

.3 .3.3

.2 .2.2

.1 .1.1

.05 .05

.03 .03

.02 .02

1 M

INU

TE

1 H

OU

R2

HO

UR

ST

IME

INS

EC

ON

DS

TIM

EIN

SE

CO

ND

S

500

600

700

800

9002 3 20 304 5 6 7 40 50 60 70 80 90 100

100

300100.8

0.9 1

0.5

0.6

0.7 8 9

20 30 40 50 60 70 80 900.5

2 3 5 6 7 108 9

200

400

CURRENT IN MULTIPLES OF LONG DELAY SETTING I

CURRENT IN MULTIPLES OF LONG DELAY SETTING I

1000

2000

3000

4000

5000

6000

7000

8000

9000

10,0

00

0.8

0.7

0.6

0.9

1

Available Rating Plugs

250020001600

ORPL25A250ORPL25A200ORPL25A160

1000 -2500800 -2000640 -1600

AmpereRating

(I )n

Rating PlugCatalogNumber

Short DelayPickup Range1.5 to 6.4 x I

Amperesr

MaximumAmpereRating

2500 1500 - 160001200 - 12800960 - 10240

ApplicationDeterminesEnd of Curve

MinimumTotalClearingTime

MaximumTotalClearingTime

AvailableLong DelayTime SettingsShown @ 6 x Ir1-5 seconds +10 ⁄-40%in 0.1 secondincrements

Available FlatShort Delay Time Settings0.1 to 0.5 secondsin 0.01 second increments

AvailableShort DelayPickup Settings1.5 to 6.4 x Ir±5% in 0.1increments

Available Long DelayPickup Settings (I )r0.5 to 1 x I = In rin 0.01 increments

Notes1) For field testing primary injection methods, follow NEMA AB4-1991 publications.2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.3) There is a memory effect that can act to shorten the long delay. The memory effect

comes into play if a current above the long delay pickup value exists for a time and thenis cleared by the tripping of a downstream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time reduction is inverse to the amount of time that has elapsed since theprevious overload. Approximately five minutes is required between overloads tocompletely reset the memory.

4) The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), andSC-6347-96 (2500A)

6) This curve is shown as a multiple of the Long Delay Pick-up Setting, (I ). This I setting isprogrammed in primary value amperes via a Breaker Interface Module, or OPTIMizer,or a Remote PC (IMPACC System).

7) The Long Delay Pick-up Point (indicated by a flashing LED on the product) nominally occursat 116% of the I current, with a +/- 5% tolerance. The short delay settings have conventional100%, +/- 5% as the pickup points.

r r

r

Long DelayPickup Range

0.4 to 1 x IAmperes

n

Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

Breaker

Type

RDRDC

UL / CSA

Volts

kA

240

125200

480

65100

600

5065

IEC 947-2

Volts

RDRDC

240 690

U = 8kVIMP

415

kA

Rating

Utilization Category A

ICU ICS

135200

100100

ICU ICS

70100

5050

ICU ICS

2535

1318

.5

.1

8) For additional curve tolerances contact Cutler-Hammer.9) Total clearing times shown include the response times of the trip unit, the breaker opening, and the extinction of the arcing current.

Circuit Breaker Time/Current Curves (Phase Current)Series CT R - Frame Circuit BreakersEquipped With 2500A Digitrip Optim Trip UnitsResponse: LONG DELAY I4t, SHORT DELAY FLAT

r

r

Page 18: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Application Data29-167R

Page 15

AB DE-ION Circuit Breakers

October 1997

Curve No. SC-6342-96

R-Frame Circuit Breakers Equipped with 1600A Digitrip OPTIM Trip Units; Instantaneous and Override

.01

10,000

5,000

3,000

2,000

1,000

500

300

200

100

50

30

20

10

5

3

2

.5

.3

.2

.1

.05

.03

.02

1 M

INU

TE

1 H

OU

R2

HO

UR

ST

IME

INS

EC

ON

DS

1

100

20 30 40 50 60 70 80 902 3 4 5 6 7 108 91

2 3 20 304 5 6 7 40 50 60 70 80 90 100108 91

.01

.5

.3

.2

.1

.05

.03

.02

1

CURRENT IN MULTIPLES OF PLUG RATING I

CURRENT IN MULTIPLES OF PLUG RATING I AMPERES

2000

3000

30,0

00

4000

40,0

00

5000

50,0

00

6000

60,0

00

7000

70,0

00

8000

80,0

00

9000

10,0

00

20,0

00

1000

Available Rating Plugs

1600125012001000800

ORPL16A160ORPL16A125ORPL16A120ORPL16A100ORPL16A080

AmpereRating

(I )n

Rating PlugCatalogNumber

14875 -2012514875 -2012514875 -2012514875 -2012514875 -20125

OverrideAmperes

3200 -160002500 -125002400 -120002000 -100001600 - 8000

InstantaneousPickup Range2 to 10 x InAmperes

MaximumAmpereRating

1600

Available InstantaneousPickup Settings2 to 10 x In ± 10%In 0.1 Increments

Available Flat ResponseShort Delay Time Settings0.1 to 0.5 seconds in0.01 second increments

FixedInstantaneousOverride

Notes1) For field testing primary injection methods, follow NEMA AB4-1991 publications.2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.3) There is a memory effect that can act to shorten the long delay. The memory effect

comes into play if a current above the long delay pickup value exists for a time and thenis cleared by the tripping of a downstream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time reduction is inverse to the amount of time that has elapsed since theprevious overload. Approximately five minutes is required between overloads tocompletely reset the memory.

4) The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), andSC-6347-96 (2500A)

6) The instantaneous settings have conventional 100%, +/- 10% as the pickup points.

Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

Breaker

Type

RD, CRDRDC, CRDC

UL / CSA

Volts

kA

240

125200

480

65100

600

5065

IEC 947-2

Volts

RD, CRDRDC, CRDC

240 690

U = 8kVIMP

415

kA

Rating

Utilization Category A

ICU ICS

135200

100100

ICU ICS

70100

5050

ICU ICS

2535

1318

ApplicationDeterminesEnd of Curve

.3

.1

.5

7) For additional curve tolerances contact Cutler-Hammer.8) Total clearing times shown include the response times of the trip unit, the breaker opening, and the extinction of the arcing current.

Circuit Breaker Time/Current Curves (Phase Current)Series CT R - Frame Circuit BreakersEquipped With 1600A Digitrip Optim Trip UnitsResponse: INSTANTANEOUS AND OVERRIDE

n

n

102

Page 19: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

October 1997

Application Data29-167RPage 16

AB DE-ION Circuit Breakers

Curve No. SC-6343-96

R-Frame Circuit Breakers Equipped with 2000A Digitrip OPTIM Trip Units; Instantaneous and Override

.01

10,000

5,000

3,000

2,000

1,000

500

300

200

100

50

30

20

10

5

3

2

.5

.3

.2

.1

.05

.03

.02

1 M

INU

TE

1 H

OU

R2

HO

UR

ST

IME

INS

EC

ON

DS

1

100

20 30 40 50 60 70 80 902 3 4 5 6 7 108 91

2 3 20 304 5 6 7 40 50 60 70 80 90 100108 91

.01

.5

.3

.2

.1

.05

.03

.02

1

CURRENT IN MULTIPLES OF PLUG RATING I

CURRENT IN MULTIPLES OF PLUG RATING I AMPERES

2000

3000

30,0

00

4000

40,0

00

5000

50,0

00

6000

60,0

00

7000

70,0

00

8000

80,0

00

9000

10,0

00

20,0

00

1000

Available Rating Plugs

20001600125012001000

ORPL20A200ORPL20A160ORPL20A125ORPL20A120ORPL20A100

AmpereRating

(I )n

Rating PlugCatalogNumber

14875 -2012514875 -2012514875 -2012514875 -2012514875 -20125

OverrideAmperes

4000 -160003200 -128002500 -100002400 - 96002000 - 8000

InstantaneousPickup Range

2 to 8 x InAmperes

MaximumAmpereRating

2000

Available InstantaneousPickup Settings2 to 8 x In ± 10%In 0.1 Increments

Available Flat ResponseShort Delay Time Settings0.1 to 0.5 secondsin 0.01 second increments

FixedInstantaneousOverride

Notes1) For field testing primary injection methods, follow NEMA AB4-1991 publications.2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.3) There is a memory effect that can act to shorten the long delay. The memory effect

comes into play if a current above the long delay pickup value exists for a time and thenis cleared by the tripping of a downstream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time reduction is inverse to the amount of time that has elapsed since theprevious overload. Approximately five minutes is required between overloads tocompletely reset the memory.

4) The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), andSC-6347-96 (2500A)

6) The instantaneous settings have conventional 100%, +/- 10% as the pickup points.

Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

Breaker

Type

RD, CRDRDC, CRDC

UL / CSA

Volts

kA

240

125200

480

65100

600

5065

IEC 947-2

Volts

RD, CRDRDC, CRDC

240 690

U = 8kVIMP

415

kA

Rating

Utilization Category A

ICU ICS

135200

100100

ICU ICS

70100

5050

ICU ICS

2535

1318

ApplicationDeterminesEnd of Curve

.3

.1

.5

7) For additional curve tolerances contact Cutler-Hammer.8) Total clearing times shown include the response times of the trip unit, the breaker opening, and the extinction of the arcing current.

Circuit Breaker Time/Current Curves (Phase Current)Series CT R - Frame Circuit BreakersEquipped With 2000A Digitrip Optim Trip UnitsResponse: INSTANTANEOUS AND OVERRIDE

n

n

2 8

Page 20: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Application Data29-167R

Page 17

AB DE-ION Circuit Breakers

October 1997

R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Instantaneous and Override

Curve No. SC-6344-96

.01

10,000

5,000

3,000

2,000

1,000

500

300

200

100

50

30

20

10

5

3

2

.5

.3

.2

.1

.05

.03

.02

1 M

INU

TE

1 H

OU

R2

HO

UR

ST

IME

INS

EC

ON

DS

1

100

20 30 40 50 60 70 80 902 3 4 5 6 7 108 91

2 3 20 304 5 6 7 40 50 60 70 80 90 100108 91

.01

.5

.3

.2

.1

.05

.03

.02

1

CURRENT IN MULTIPLES OF PLUG RATING I

CURRENT IN MULTIPLES OF PLUG RATING I AMPERES

2000

3000

30,0

00

4000

40,0

00

5000

50,0

00

6000

60,0

00

7000

70,0

00

8000

80,0

00

9000

10,0

00

20,0

00

1000

Available Rating Plug

250020001600

ORPL25A250ORPL25A200ORPL25A160

AmpereRating

(I )n

Rating PlugCatalogNumber

14875 -2012514875 -2012514875 -20125

OverrideAmperes

5000 -160004000 -128003200 -10240

InstantaneousPickup Range2 to 6.4 x In

Amperes

MaximumAmpereRating

2500

6.4

Available InstantaneousPickup Settings2 to 6.4 x In ± 10%In 0.1 Increments

ApplicationDeterminesEnd of Curve

Available Flat ResponseShort Delay Time Settings0.1 to 0.5 secondsin 0.01 second increments

FixedInstantaneousOverride

Notes1) For field testing primary injection methods, follow NEMA AB4-1991 publications.2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.3) There is a memory effect that can act to shorten the long delay. The memory effect

comes into play if a current above the long delay pickup value exists for a time and thenis cleared by the tripping of a downstream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time reduction is inverse to the amount of time that has elapsed since theprevious overload. Approximately five minutes is required between overloads tocompletely reset the memory.

4) The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), andSC-6347-96 (2500A)

6) The instantaneous settings have conventional 100%, +/- 10% as the pickup points.7) For additional curve tolerances contact Cutler-Hammer.8) Total clearing times shown include the response times of the trip unit, the breaker opening, and the extinction of the arcing current.

Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

Breaker

Type

RDRDC

UL / CSA

Volts

kA

240

125200

480

65100

600

5065

IEC 947-2

Volts

RDRDC

240 690

U = 8kVIMP

415

kA

Rating

Utilization Category A

ICU ICS

135200

100100

ICU ICS

70100

5050

ICU ICS

2535

1318

.3

.1

.5

Circuit Breaker Time/Current Curves (Phase Current)Series CT R - Frame Circuit BreakersEquipped With 2500A Digitrip Optim Trip UnitsResponse: INSTANTANEOUS AND OVERRIDE

n

n

2

Page 21: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

October 1997

Application Data29-167RPage 18

AB DE-ION Circuit BreakersR-Frame Circuit Breakers Equipped with 1600A Digitrip OPTIM Trip Units; Ground Fault or Ground Fault Alarm Only

Curve No. SC-6345-96

.01

10,000

5,000

3,000

2,000

1,000

500

300

200

100

50

30

20

10

5

3

2

.5

.3

.2

.1

.05

.03

.02

1 M

INU

TE

1 H

OU

R2

HO

UR

ST

IME

INS

EC

ON

DS

1

CURRENT IN MULTIPLES OF RATING PLUG I

CURRENT IN MULTIPLES OF RATING PLUG I

.01

.5

.3

.2

.1

.05

.03

.02

1

.1.1

.2.2

.3.3

.4.4

.5.5

.6.6

.7.7

.8.8

.9.9

11

22

33

44

55

66

77

88

99

1010

.2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10

Available Rating Plugs

I t Slope forGround FaultTime Settings

2

Availaible I t ResponseGround Fault Time Settings0.1 to 0.5 secondsin 0.01 second increments

2

Available Ground FaultPickup Settings ±10%in 0.1 increments

Available Flat ResponseGround Fault Time Settings0.1 to 0.5 secondsin 0.01 second increments

Flat Shape forGround FaultTime Settings

.5

.3

.1

Notes1) For field testing primary injection methods, follow NEMA AB4-1991 publications.2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.3) There is a memory effect that can act to shorten the long delay. The memory effect

comes into play if a current above the long delay pickup value exists for a time and thenis cleared by the tripping of a downstream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time reduction is inverse to the amount of time that has elapsed since theprevious overload. Approximately five minutes is required between overloads tocompletely reset the memory.

4) The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

5) Ground fault level is electronically limited to a maximum of 1200 Amperes.6) For phase current curves, see SC-6336-96, SC-6337-96, SC-6338-96, SC-6339-96,

SC-6340-96, SC-6341-96, SC-6342-96, SC-6343-96, and SC-6344-96.7) The ground fault settings have conventional 100%, +/- 10% as the pickup points.8) For additional curve tolerances contact Cutler-Hammer.9) Total clearing times shown include the response times of the trip unit, the breaker opening, and the extinction of the arcing current.

1600125012001000800

ORPL16A160ORPL16A125ORPL16A120ORPL16A100ORPL16A080

AmpereRating

(I )n

Rating PlugCatalogNumber

400 -1200312.5 -1200300 -1200250 -1000200 - 800

Ground FaultPickup Range

Amperes

MaximumAmpereRating

1600

Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

Breaker

Type

RD, CRDRDC, CRDC

UL / CSA

Volts

kA

240

125200

480

65100

600

5065

IEC 947-2

Volts

RD, CRDRDC, CRDC

240 690

U = 8kVIMP

415

kA

Rating

Utilization Category A

ICU ICS

135200

100100

ICU ICS

70100

5050

ICU ICS

2535

1318

Circuit Breaker Time/Current Curves (Ground Current)Series CT R - Frame Circuit BreakersEquipped With 1600A Digitrip Optim Trip UnitsResponse: GROUND FAULT TRIP OR GROUND FAULT ALARM ONLY

n

n

1.0

.5

.5

.3

.1

.2

Page 22: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Application Data29-167R

Page 19

AB DE-ION Circuit Breakers

October 1997

Curve No. SC-6346-96

R-Frame Circuit Breakers Equipped with 2000A Digitrip OPTIM Trip Units; Ground Fault or Ground Fault Alarm Only

10,000

5,000

3,000

2,000

1,000

500

300

200

100

50

30

20

1 M

INU

TE

1 H

OU

R2 H

OU

RS

CURRENT IN MULTIPLES OF RATING PLUG I

CURRENT IN MULTIPLES OF RATING PLUG I

.1 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10

Available Rating Plugs

Notes1) For field testing primary injection methods, follow NEMA AB4-1991 publications.2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.3) There is a memory effect that can act to shorten the long delay. The memory effect

comes into play if a current above the long delay pickup value exists for a time and thenis cleared by the tripping of a downstream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time reduction is inverse to the amount of time that has elapsed since theprevious overload. Approximately five minutes is required between overloads tocompletely reset the memory.

4) The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

5) Ground fault level is electronically limited to a maximum of 1200 Amperes.6) For phase current curves, see SC-6336-96, SC-6337-96, SC-6338-96, SC-6339-96,

SC-6340-96, SC-6341-96, SC-6342-96, SC-6343-96, and SC-6344-96.7) The ground fault settings have conventional 100%, +/- 10% as the pickup points.8) For additional curve tolerances contact Cutler-Hammer.9) Total clearing times shown include the response times of the trip unit, the breaker opening, and the extinction of the arcing current.

20001600125012001000

ORPL20A200ORPL20A160ORPL20A125ORPL20A120ORPL20A100

AmpereRating

(I )n

Rating PlugCatalogNumber

500 -1200400 -1200312.5 -1200300 -1200250 -1000

Ground FaultPickup Range

Amperes

MaximumAmpereRating

2000

Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

Breaker

Type

RD, CRDRDC, CRDC

UL / CSA

Volts

kA

240

125200

480

65100

600

5065

IEC 947-2

Volts

RD, CRDRDC, CRDC

240 690

U = 8kVIMP

415

kA

Rating

Utilization Category A

ICU ICS

135200

100100

ICU ICS

70100

5050

ICU ICS

2535

1318

.01

10

5

3

2

.5

.3

.2

.1

.05

.03

.02

TIM

EIN

SE

CO

ND

S

1

.01

.5

.3

.2

.1

.05

.03

.02

1

.1 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10

I t Slope forGround FaultTime Settings

2

Availaible I t ResponseGround Fault Time Settings0.1 to 0.5 secondsin 0.01 second increments

2

Available Ground FaultPickup Settings ±10%in 0.1 increments

Available Flat ResponseGround Fault Time Settings0.1 to 0.5 secondsin 0.01 second increments

Flat Shape forGround FaultTime Settings

.5

.3

.1

Circuit Breaker Time/Current Curves (Ground Current)Series CT R - Frame Circuit BreakersEquipped With 2000A Digitrip Optim Trip UnitsResponse: GROUND FAULT TRIP OR GROUND FAULT ALARM ONLY

n

n

1.0

.5

.5

.3

.1

.2

Page 23: 2.3 Molded Case Circuit Breakers · 2019. 8. 15. · V4-T2-238 Volume 4—Circuit Protection CA08100005E—August 2013 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

October 1997

Application Data29-167RPage 20

AB DE-ION Circuit Breakers

Curve No. SC-6347-96

R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Ground Fault or Ground Fault Alarm Only

.01

10,000

5,000

3,000

2,000

1,000

500

300

200

100

50

30

20

10

5

3

2

.5

.3

.2

.1

.05

.03

.02

1 M

INU

TE

1 H

OU

R2 H

OU

RS

TIM

EIN

SE

CO

ND

S

1

CURRENT IN MULTIPLES OF RATING PLUG I

CURRENT IN MULTIPLES OF RATING PLUG I

.01

.5

.3

.2

.1

.05

.03

.02

1

.1.1

.2.2

.3.3

.4.4

.5.5

.6.6

.7.7

.8.8

.9.9

11

22

33

44

55

66

77

88

99

1010

.2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10

Available Rating Plugs

I t Slope forGround FaultTime Settings

2

Availaible I t ResponseGround Fault Time Settings0.1 to 0.5 secondsin 0.01 second increments

2

.5

.1

Available Flat ResponseGround Fault Time Settings0.1 to 0.5 secondsin 0.01 second increments

Flat Shape forGround FaultTime Settings

Notes1) For field testing primary injection methods, follow NEMA AB4-1991 publications.2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.3) There is a memory effect that can act to shorten the long delay. The memory effect

comes into play if a current above the long delay pickup value exists for a time and thenis cleared by the tripping of a downstream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time reduction is inverse to the amount of time that has elapsed since theprevious overload. Approximately five minutes is required between overloads tocompletely reset the memory.

4) The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

5) Ground fault level is electronically limited to a maximum of 1200 Amperes.6) For phase current curves, see SC-6336-96, SC-6337-96, SC-6338-96, SC-6339-96,

SC-6340-96, SC-6341-96, SC-6342-96, SC-6343-96, and SC-6344-96.7) The ground fault settings have conventional 100%, +/- 10% as the pickup points.8) For additional curve tolerances contact Cutler-Hammer.9) Total clearing times shown include the response times of the trip unit, the breaker opening, and the extinction of the arcing current.

250020001600

ORPL25A250ORPL25A200ORPL25A160

AmpereRating

(I )n

Rating PlugCatalogNumber

625 -1200500 -1200400 -1200

Ground FaultPickup Range

Amperes

MaximumAmpereRating

2500

Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

Breaker

Type

RDRDC

UL / CSA

Volts

kA

240

125200

480

65100

600

5065

IEC 947-2

Volts

RDRDC

240 690

U = 8kVIMP

415

kA

Rating

Utilization Category A

ICU ICS

135200

100100

ICU ICS

70100

5050

ICU ICS

2535

1318

Available Ground FaultPickup Settings ±10%in 0.01 increments

Circuit Breaker Time/Current Curves (Ground Current)Series CT R - Frame Circuit BreakersEquipped With 2500A Digitrip Optim Trip UnitsResponse: GROUND FAULT TRIP OR GROUND FAULT ALARM ONLY

.5

.1

n

n

1.0

.2