P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953EA
(B-F)/2
F/2
F/2
(B-F)/2
B
16'
8'
4'
I
KJ
F
2' (TYP.)
REAR EDGE OFFALSE CEILINGAND LUMBER PILE
(APPROX.)
ALUMINUM DUCT STACKS
WOOD STOPS
WET BULB TRAY (4' OFF FLOOR)
REAR DRY BULB SENSOR(4' OFF FLOOR)
FLOORDRAIN TROUGH(OPTIONAL)
INSULATED SERVICE DOOR
NOTE:CONTROL ROOM MAY NEEDTO BE BUILT LARGER IF ABOILER IS TO BE INSTALLED.A LARGER DOOR MAY ALSOBE REQUIRED.
VENT BOX
OPTIONAL VENT BOXLOCATION
NOTE:SPACE FANS EVENLYACROSS KILN CHAMBER
NOTE:WOOD STOPS IN FRONT OF DEHUMIDIFIERTO BE REMOVABLE TO ALLOW FORINSTALLATION OF DEHUMIDIFIER
CIRCULATING FANS
FRONT DRY BULB OVERHEAD(BRACKET BY NYLE)
FRONT EDGE OF FALSE CEILING AND LUMBER PILE
VENT BOX(IN WALL OVER DOOR)
OPTIONAL VENT BOXLOCATION
NOTE:CIRCULATING FANS ANDVENTS TO BE FIELD WIREDBY CUSTOMER
3/16" = 1' - 0"
KILN CHAMBER AND CONTROL ROOM PLAN VIEWA
ENTRY DOOR LOCATIONOPTIONS
A4
2'
NOTE:SEE SHEET 16 FOR CHAMBER SIZES
DEHUMIDIFIER
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
OPTIONAL STEAM/WATERSPRAY VALVE
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
3/16" = 1' - 0"
TYPICAL SECTION THROUGH KILN CHAMBER AND CONTROL ROOMA
2" BLUE STYROFOAMUNDER ONE LAYER OF 6 MIL
POLY VAPOR BARRIER
SEE NOTE 3 ON SHEET 15
SLOPE FLOOR 2" FROMFRONT TO DRAIN TROUGH
LUMBER PILE
WOOD STOPS ARE 4" PIPE OR EQUAL
DRAIN TROUGH4" DEEP x 8" WIDE
G
FRONTDRY BULB CIRCULATING FAN
12" PLYWOOD ALUMINUM
DUCT
HJ
DEHUMIDIFIER
INSULATE CONTROL ROOMIN ACCORDANCE W/ LOCALCONDITIONS
EAVE VENT
14" x 16" VENT BOXALLOW 141
2" WIDE x 16 12" HIGH R.O.
DEPTH OF FOOTINGS DETERMINEDBY LOCAL CODES OR FROST
CONDITIONS
RIDGE VENT
OPTIONAL SINGLE SLOPE ROOF
ALUMINUMROOFING OVER2x4 STRAPPING
NOTE:ROOF TRUSS DESIGN BY OTHERS
STEEL LINTEL BEAMSEE NOTE 1 ON SHEET 15
NOTE:INSULATE SPACEBEHIND LINTEL BEAMAND HEADER FRAMES
D
C
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
12" PLYWOOD
FALSE CEILING2x4
FIXED AIR DEFLECTOR TOEXTEND TO 6" BELOW TOP OF
LUMBER PILE. ( 12" PLYWOOD)
HINGED BAFFLE TO RESTAGAINST LUMBER PILE
OPTIONAL STEAM/WATERSPRAY VALVE
TREADED ROD TOSUPPORT FALSE CEILING
OPTIONALSTEAM COILSEE NOTE 11
ON SHEET 15
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
1/2" = 1' - 0"
ALTERNATE WALL/CONCRETE FLOOR DETAILA
3/4" = 1' - 0"
ALTERNATE 2x6 WALL SECTIONC
3/4" = 1' - 0"
ALTERNATE WALL/WOOD FLOOR DETAILB
R19 FIBERGLASS OR BLOWN MINERAL WOOL(NO CELLULOSE)
2x4 STUD WALLS
1" FOIL FACED POLYISOCYANURATE(SEE NOTE 6 ON SHEET 15)
12" CDX PLYWOOD OVER6 MIL POLY VAPOR BARRIER
12" PLYWOOD OR SIDING
(BE SURE OUTSIDE WALL ISWELL VENTILATED)
TREATED SILL
FLASHING
2" BLUE STYROFOAMOR FOIL FACED
POLY.AROUND PERIMETER 2" BLUE STYROFOAM
OR FOIL FACED POLY.6 MIL POLY BETWEEN
CONCRETE AND INSULATION
4" REINFORCED CONCRETE
R19 FIBERGLASSOR BLOWN MINERAL WOOL(NO CELLULOSE)
2x4 STUD WALLS
12" CDX PLYWOOD OVER6 MIL POLY VAPOR BARRIER
12" PLYWOOD OR SIDING
(BE SURE OUTSIDE WALL ISWELL VENTILATED)
TREATED SILL
FLASHING
FIBERGLASS OR STYROFOAMTO R30 MIN.
2x6 FLOOR STRINGERS
12" CDX PLYWOOD OVER 6 MILPOLY VAPOR BARRIER
2" BLUE STYROFOAM
2x8 HEADER
AIR SPACE TOWARDSOUTSIDE OF KILN
12" CDX PLYWOOD OR SIDING
(WELL VENTILATED)
2x6 WALL STUD
2" FOIL FACED POLY. OR 3" BLUE STYROFOAM
12" CDX OVER 6 MIL POLY V.B.
ALTERNATE SYSTEM:(2) 2" THK. LAYERS OF FOILFACED POLY.
SAME SYSTEM MAY BE USEDIN WALLS, ROOF, OR CEILING.
NOTE:ALTERNATIVE CONSTRUCTIONMETHODS MAY BE USED INWALLS AND CEILING.
1" FOIL FACED POLYISOCYANURATE(SEE NOTE 6 ON SHEET 15)
2" BLUE STYROFOAMOR FOIL FACED
POLY.AROUND PERIMETER
2" FOIL FACED POLYISOCYANURATE(SEE NOTE 6 ON SHEET 15)
*PREFERRED METHOD *
* NOTE: FOAM BOARD INSULATION CAN BE EITHER POLYISOCYANURATE OR EXTRUDED POLYSTYRENE (PREFERRED)
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
1/4" = 1' - 0"
SECTION THROUGH WIDTH OF KILNA
TYPICAL TRUSS OR RAFTER ROOF CONSTRUCTION
SEE NOTE 5 ON SHEET 15FOR FAN TRUSSCONSTRUCTION
VENT BOXSEE CHART 2 FOR R.O.(OPTIONAL LOCATION)
2 LAYERS OF 2"FOIL FACED INSULATION
(POLYISOCYANURATE)
AIR SPACE TOWARDSOUTSIDE OF KILN
12" CDX PLYWOODOR SIDING OVER
STRAPPING(WELL VENTILATED)
NOTE:WOOD STOPS IN FRONT OFDEHUMIDIFIER TO BE REMOVABLE TO ALLOW FORINSTALLATION OFDEHUMIDIFIER.
ALUMINUMDUCT
BY NYLE
DEHUMIDIFIER
SEE CHART ONPAGE 2 FORR.O. AT UNIT
WOOD STOPS (TYP.)4" STEEL PIPE OR EQUAL
12" CDX PLYWOODOVER 6 MIL POLY
TOP OF LUMBER PILE
INSULATED SERVICEDOOR
REAR DRYBLUB SENSOR
WET BULBTRAY &
SENSOR
CIRCULATING FANS (TYP.)SEE CHART 1 BELOW FOR R.O.
G
D
4'
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
2" BLUE STYROFOAMOR FOIL FACED POLY.
INSULATIONMODELL1200SL2500
QUANITY45
HP EA.23
UNIT DIM.30"36"
R.O. DIM.361
4" x 3614"
4214" x 421
4"
CHART 1: ROUGH OPENING FOR FANS
MODELL1200SL2500
UNIT DIM.14" W x 16" H
CHART 2: ROUGH OPENING FOR VENTS
20" W x 20" H
R.O. DIM.141
2" W x 1612" H
2012" W x 201
2" H
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
5/8" = 1' - 0"
TYPICAL FRONT WALL SECTIONA
SCREENED VENTING
TYPICAL 2x6CONSTRUCTION
2x4 STRAPPING
ALUMINUM ROOFING
PRE-ENGINEERED TRUSSESOR RAFTERS
FIXED AIR DEFLECTORSEE NOTE 4 ON SHEET 15 INSULATE CEILING WITH 2 LAYERS
OF FOIL FACED POLYISOCYANURATE.
FOR AN ALTERNATIVE, THE CEILINGMAY BE INSULATED WITH 1" FOIL FACEDAND 12" FIBERGLASS INSULATION.
12" PLYWOOD
2x4 OR 1x3 STRAPPING
AIR SPACE
ALUMINUM SIDING
ANCHOR BOLT4'-0" O.C.
PRESSURE TREATED SILLOVER STANDARD SILL SEAL
NOTE:USE ONLY STAINLESS STEEL OR ALUMINUMFASTENERS WHERE SUBJECT TO KILN CONDITIONS
6" 2500# TEST CONCRETEW/ 6x6x6 WIRE REINFORCEMENT(DO NOT USE QUICK SET CONC.)
2" BLUE STYROFOAM
NOTE:DEPTH OF FOOTINGSDETERMINED BY LOCALCODES AND FROST CONDITIONS
2"6"
6"
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
1" = 1' - 0"
FRAMING AT VENT BOXA
NOTE:FRAMING SHOWN IS FOR WALL OVER DOORWITH CLEARANCE THROUGH FIXED DEFLECTOR .THE VENT BOX ROUGH OPENING WILL BE THESAME FOR THE REAR VENT.
ROOF FRAMING
VENT BOX
LINTEL BEAM(SIZED BY OTHERS)
R.O.
R.O.
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
NOTE: SEE CHART 2 ON SHEET 3 FOR VENT ROUGH OPENING
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
2" = 1' - 0"
GASKET AT DOOR JAMBB
2" = 1' - 0"
MATING FLANGE DET.A
L2" x 2" x 18" ALUM. ANGLE
PERIMETER GASKET
OTHER DOOR
34" TEK SCREW
NOTE:CENTER GASKET MAY BE INSTALLEDEITHER INSIDE OR OUTSIDE
PERIMETER DOOR GASKET
34" TEK SCREW L2" x 1" x 18" ALUM. ANGLE
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
3" = 1' - 0"
DETAIL FOR HINGE PINSB
6" = 1' - 0"
TYP. HINGE PLATE DETAILA
3" = 1' - 0"
HINGE ASSEMBLYC
4"
GRIND FLUSH
1" SCH. 40 PIPE
14"
SLIDE 34" PIPE IN TO
1" SCH. 40 PIPE ON BOTTOMSECTION OF HINGE
& WELD AT END
34" SCH. 40 PIPE
414"41
4"
114"
114"
114"
114"
9"612"
114"
14" ALUM. PL.
1" SCH. 40 PIPE
114"
Ø 38"
TOP SECTIONMOUNTED TO
DOOR
BOTTOM SECTIONATTACHED TO
BUILDING
114"
114"
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
4" = 1' - 0"
TURN BUCKLE ANCHORSA
L2x2x14" WELEDED
TO DOOR
L2x2x14" WELEDEDTO DOOR
FEED CABLE THROUGH ANGLE BRACKETAND PLACE 2 STAINLESS STEEL
CABLE CLAMPS TO SECURE END
316" OR 1
4" STAINLESS STEEL CABLE(USE STAINLESS STEEL TURNBUCKLES,CLAMPS, AND THIMBLES TO SECURE)
KILN DOOR(BOTTOM CORNER)
KILN DOOR(TOP CORNER)
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
3/4" = 1' - 0"
SLIDING BARREL LATCHESA
1" SCH. 40 PIPE SLEEVEIN CONCRETE FOR DOOR
PIN
DOOR PIN ASSEMBLY
TRUCK LATCH ASSEMBLY
DOOR LATCH
NOTE:TRUCK LATCH, DOOR LATCH, AND DOORPIN ASSEMBLIES MAY BE PURCHASEDFROM NYLE.
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
3/4" = 1' - 0"
KILN DOOR & HEADERA
L12"x12" ANGLE,
34" TEK SCREW, &FOLDED RUBBERBOTTOM DOOR GASKET1"
6 MIL VAPOR BARRIER
12" PLYWOOD
L2"x1"x18" ANGLE,
34" TEK SCREW, &PERIMETER GASKET
LINTEL BEAM TO BESIZED BY OTHERS
6 MIL VAPOR BARRIER12" PLYWOOD
2 LAYERS OF 2" FOIL FACED INSULATION
12" PLYWOOD
C
D
KILN FLOOR
NOTE:DOOR GASKET KITS AREAVAILABLE FROM NYLE.
INSTALL ANGLES AND GASKETSSO THE GASKET WILL BE SLIGHTLYCOMPRESSED.
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
1/2" = 1' - 0"
DOOR FRAMINGA
E/2 - 1"10" 1'-4" 2' 2' 2' 2' 2' 9"
C - 1 1/2"
1'-3"
9"
C/2 - 28 3/4"
9"
C/2 - 28 3/4"
9"
1'-3"
STAINLESS STEELTURN BUCKLE ONINSIDE OF DOOR
2x6 TYP.
2 LAYERS OF 2" FOIL FACEDPOLYISOCYANURATE
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
1/4" = 1' - 0"
FRONT WALL FRAMINGA
RAFTERS OR TRUSSES
LINTEL BEAM
NOTE:GASKET AND GASKET HARDWARE AREAVAILABLE FROM NYLE AT EXTRA COST.
DOOR HARDWARE AND FRAMING KITS AREALSO AVAILABLE FROM NYLE. CONTACTNYLE FOR MORE INFORMATION.
C
D
E
2x6 STUDS 2'-0" O.C.
2x6
2x6
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
1/4" = 1' - 0"
FRONT ELEVATIONA
ALUMINUM ROOF
ALUMINUMSIDING
DOORLATCHES
DOORPINS
TURNBUCKLE TURNBUCKLE
TOP OF LUMBER PILE
DOORHINGE
4'
1'-8"
C/2 - 1'-8"
C/2 - 1'-8"
1'-8"
C
DOOROPENING
A11
B7
C8
E/2 - 1" E/2 - 1"
G
TOP OFCONCRETE PAD
VENT
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
GENERAL NOTES
1. STEEL LINTELA steel lintel to support the weight of the roof should besized by a local engineer. If no additional kilns are planned,trusses can run parallel to front of building thus eliminatingthe need for heavy-duty lintel beam.
2. DEHUMIDIFIER PADPad for dehumidifier should be even with top offoundation and control room floor. Dehumidifier shouldbe min. 8" above kiln floor to facilitate trapping theunit drain.
3. DRAIN TROUGH TRAPProvide a trap at one end of drain trough to preventair from entering the kiln from the drain.
4. FIXED AIR DEFLECTORSFixed air deflectors are used to enhance air flow. Ifmore than one kiln is being built, vents will need to beplaced in front and back wall of each kiln. Allow 8"-10"at both sides of vent opening when constructingdeflectors to facilitate vent installation.
5. FAN TRUSSConstruct fan truss with 2X4 framing and cover one orboth sides of truss with 1
4" or greater plywood. Seerough opening chart for fan rough openings. Spread fansevenly across the width of kiln.
6. Polyisocyanurate insulation board (Celotex, Thermax, R-Factor,or Tuff-R) is strongly recommended for interior insulationsheathing, 1" is shown but thicker is preferred especially if usingfiberglass or blown mineral wool insulation. (When spraying,spray 2 layers at a 2.2 lb/cu. ft density. No interior plywood orvapor barrier is necessary if insulation is sprayed on.)
7. DO NOT USE CELLULOSE OR EXPANDED POLYSTYRENE (WHITESTYROFOAM) INSULATION IN THE DRYING KILN.
8. INSTALL EXHAUST VENTS AT CONVENIENT ELEVATION TOALLOW FOR MANUAL ADJUSTMENT.
9. POWERED VENT SYSTEM AVAILABLE, CONTACT NYLE.
10. FALSE CEILING SYSTEMThe false ceiling is used to enhance proper air flow through thelumber pile. It should be of sufficient strength to permitmaintenance of fans. Treaded rod may be used to suspend thekiln ceiling.Nyle offers an all aluminum false ceiling system that consists ofaluminum panels extending the width of the kiln chamber andreaching to the front and back of the lumber pile. The falseceiling would be supplied with a system of ropes and pulleys topermit the panels to be raised and lowered. Contact Nyle fordetails.
11. HEATSteam heat consists of a steam coil duct mounted with 1"supply and 3
4" drain outlet. A boiler will be required. All pipingfrom the coil to the boiler is to be supplied by the customer.Electric heat consists of duct mounted heavy-duty electricelement completely pre-wired. Electric heat is standard, steamor hot water is an extra cost option.
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
P.O. Box 1107 Bangor, Maine 04402Tel: 1-207-989-4335 Fax: 207-989-1101 Email: [email protected]
1-800-777-6953
KILN CHAMBER SIZE CHART1
DRAWINGS ARE SUGGESTIONS ONLY. VERIFY DESIGN AND ENGINEERINGLOCALLY. NYLE PROVIDES THESE DRAWINGS AT NO CHARGE AND TAKES NORESPONSIBILITY FOR THEIR USE.
13000
BF OFLUMBER
NET LENGTH(ft.)
STICKERSIZE (ft.)
PKGS.DEEP
# OF 4"BOLSTERS
# OFLAYERS A B C D E F G
BUILDING DIMENSIONS (OPEN SPACE INSIDE) (ft.)
18 4 4 4 53 21 24 11 14 19 16 1025 4 3 2 59 28 20 11.5 14 26 12 10
4 3 3 78 28 15 17 133 65 13 15 11
4 3 74 14 17 13
15000
4 4 88 17 19 154 4 103 19 22 18
UNITH I J
UNIT DIMENSIONS (in.)
L1200S 54 64 66K
39
BUILDING WIDTHBUILDING DEPTHDOOR HEIGHTEAVE HEIGHTDOOR WIDTHLUMBER DEPTHLUMBER HEIGHTUNIT HEIGHTUNIT WIDTHUNIT DEPTHDISTANCE UNIT EXTENDS INTO CHAMBER
A -B -C -D -E -F -G -H -I -J -K -ROUGH OPENING FOR UNIT
SHALL HAVE A 1" CLEARANCEAROUND UNIT.
2000022000250003000035000
2525252525
44
4
44
28282828
2024242424
2626
262626
1216161616
10000 18 4 3 3 54 22 24 11 15 19 12 10