5- UNITS MANUF: GALAXY MODEL#: GXH-105 EDPT MEA: 130-04-E CAPACITY: 2 1 2 G.P.M. INPUT: 105,000 BTU OUTPUT: 86,000 BTU/HR ENERGY EFFICIENT FACTOR MIN. 81% 34" x 24" FA WIRE MESH. NEW STEEL DOOR 1 1/2 FPSC FRESH AIR WINDOW CALCULATION REQ'D. 1 sq. in. per 1000 BTU Total: 5 Units = : (5x105,000) Total: 525,000 BTU REQ'D. = MIN. 525 sq. inch. PROV'D. = 34" x 24" = 816 sq. inch. O.K. AREA OF WORK AS SHOWN IN DETAIL NEW. MECH. RM. 25'-8 1/4" 7'-4" EXISTING METAL CHIMNEY 63'-7 1 2 " EXISTING 34"X 24" FA WINDOW OPENING 18'-6 1/8" 63'-10 1 2 " 22'-1" EXISTING & PROPOSE CELLAR PLAN SCALE: 1/4"-1'-0" 3'X6'8" ZONING: R4 MAP #: 18c BLOCK #: 11945 LOT #: 43 AREA OF WORK 34" x 24" FA WIRE MESH. NEW STEEL DOOR 1 1/2 FPSC NEW. MECH. RM. EXISTING METAL CHIMNEY 34" X 24" EXISTING WINDOW OPENING PARTIAL CELLAR PLAN SCALE: 1/2"-1'-0" ELECTRICAL NOTES: MECHANICAL & PLUMBING NOTES: 1. MECHANICAL AND PLUMBING WORK SHALL BE FILED AS REQUIRED WITH THE APPROPRIATE CITY AGENCIES, UPON COMPLETION WORK, CONTRACTOR SHALL ARRANGED FOR AND OBTAIN RELEVANT SIGN-OFF. 2. ALL MECHANICAL AND PLUMBING WORK SHALL CONFORM TO THE NYC CODE AND ALL LOCAL LAWS. 1. THE ELECTRIC INSTALLATION AND REPAIRS SHALL BE IN STRICT ACCORDANCE WITH THE NEW YORK CITY CODE AND OTHER CODES OR AGENCIES HAVING JURISDICTION. 2. CONTRACTOR SHALL PROCURE REQUIRED PERMITS FOR HIS WORK. 3. EACH DWELLING UNIT SHALL BE PROVIDED WITH A SEPARATE METER. 4. ALL EXPOSED WIRING, UNLESS OTHERWISE NOTED SHALL BE INSTALLED IN EMT CONDUIT. ALL CONCEALED WIRING MAY BE FLEXIBLE METALLIC CONDUIT. 5. SMOKE DETECTORS SHALL BE INSTALLED IN WIRING BEFORE ELECTRICAL SWITCHES ARE WIRED INTO LINE. CODE PRESCRIPTIVE VALUE PROPOSED DESIGN VALUE ITEM DESCRIPTION BOILER REPLACEMENT ENERGY ANALYSIS FOR ALTERATION - CLIMATE ZONE 4 81% EFFICIENCY AFUE ECCCNYC, SECTION 403.7 AND TABLE 403.7 NYS ENERGY COMPLIANCE EXISTING 2 AND HALF STORY BRICK 5-FAMILY HOUSE. PROPOSED: 1. INSTALL FIVE NEW UNITS IN NEW MECH. ROOM IN CELLAR. 2. INSTALLATION OF DOOR. ALL WORK IN EXISTING CELLAR. SCOPE OF WORK SPECIAL INSPECTION CODE / SECTION MECHANICAL SYSTEMS BC 1704.15 HEATING SYSTEM BC 1704.23 7. GAS PIPING TO COMPLY WITH RS-16 SEC. D 115 8. FIXED VENT FOR BOILER COMBUSTION AIR TO BE PROVIDED AT A RATE OF 1 SIN PER 1,000 BTU OF BOILER INPUT. BOILER NOTES: 1. PROVIDE A MIN. OF 18" CLEARANCE AROUND EACH BOILER. 2. NO GAS OR ELECTRIC METER IN BOILER ROOM. 3. BOILER TO BE ON CONCRETE BLOCK BASE. 4. CEILING OVER BOILER ROOM TO BE MIN. ONE(1) HR. FIRE RATED. 5. BOILER ROOM DOOR TO BE 1 1/2 FPSC. 6. NO STORAGE IN BOILER ROOM. BOILER ROOM NOTES 1. PIPE SIZING SHALL COMPLY WITH SECTION FGC 402. 2. PIPING MATERIALS SHALL COMPLY WITH SECTION FGC 403. 3. PIPING SYSTEM INSTALLATION SHALL COMPLY WITH SECTION FGC 404 4. RESERVED SHALL COMPLY WITH SECTION FGC 405. 5. INSPECTION, TESTING AND PURGING SHALL COMPLY WITH SECTION FGC 406. 6. PIPING SUPPORT SHALL COMPLY WITH SECTION FGC 407. 7. DRIPS AND SLOPED PIPING SHALL COMPLY WITH SECTION FGC 408. 8. SHUTOFF VALVES SHALL COMPLY WITH SECTION FGC 409. 9. FLOW CONTROLS SHALL COMPLY WITH SECTION FGC 410. 10.APPLIANCE CONNECTIONS SHALL COMPLY WITH SECTION FGC 411. GAS PIPING INSTALLATION NOTES: FROM 2008 NYC FUEL GAS CODE SCALE 1/8"=1'0" SITE PLAN 108th AVENUE 40.00' 160.00' 123.36' 123.19' 28.78' 12.29' LAKEWOOD AVE. CELLAR ENTRANCE C H A I N L I N K F E N C E A S P H A L T P A V E D D R I V E W A Y EXISTING TWO AND HALF STORY BRICK DWELLING HOUSE # 146 -42 2 STORY BRICK WALL E/S 3'-11"E WALL S/S 0'-0 1 2 " N 90° C O N C R E T E W A L L 90° WALL S/S 0'-4" N 0'-2 1 2 "W CONCRETE PAVED DRIVEWAY BRICK WALL WITH IRON FENCE ON TOP 21'-9 1 2 " T W O S T O R Y F R A M E 22'-1" 63'-10 1 2 " 63'-7 1 2 " PRESENT STREET LINE FINAL MAP LINE CITY OF NEW YORK 15' -1 1 2 " 14'-4 1 2 " 99°45' 00" 21°8' 41.9" 4'-6"S STEPS 0'-7 1 2 " E SPA PLACE 2'-11 1 2 " 3'-10 1 2 " 1 STORY FRAME STEPS 90° SEE UNIT NOTES ON THIS SHEET 3'X6'8" 1 12'-0" 6'-5" NEW EXIST. OPEN CELLAR LEGEND EXISTING WALLS & PARTITIONS DENOTES APPROVED TYPE SMOKE DETECTOR & CARBON MONOXIDE C.M.&S.D. DEMOLITION WALLS DENOTES FLOOR DRAIN FIRST FL GAS RISER DIAGRAM N.T.S. CELLAR 1" 1" 1" UNIT UNIT UNIT DENOTES 2 HR RATED PARTITION CONSTRUCTED OF 3 5 8 " METAL STUDS @ 16" O.C. WITH 2 LAYERS 5/8" TYPE 'x' G.W.B EACH SIDE-TWO HR. RATED (GA FILE NO. WP 4135 & B.S.A. No. 171-52-SM). U-1 NEW NEW NEW 1 REMARKS DOOR SCHEDULE SYMBOL STYLE SIZE FRAME/ THK. RATING TYPE 3' X 6'8' 1 3/4" METAL MECH. ROOM SGL HINGED STANDARD HARDWARE 1 1/2 FPSC DOOR MAT. 2HR. F RATED INTERIOR PARTITION NEW U-2 NEW U-3 NEW U-4 NEW U-5 NEW U-1 NEW U-2 NEW U-3 NEW U-4 NEW U-5 EXIST. STORAGE AREA 6'-5" 13'-10" UP UP EXIST. GM EXIST. 3)EXISTING GAS METERS EXIST. GM EXIST. GM EXIST. EXIST. EXIST. 1" 1" UNIT UNIT NEW NEW EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. LANDING CO DRAIN RISER DIAGRAM 4" 4" S FIRST FL 6" SANITARY MIN. SLOPE: 1/8"/FT C.M.&S.D. C.M.&S.D. N.T.S. N.T.S. EXISTING WALL TO BE REMOVED EXISTING WALL TO BE REMOVED NEW WALL 2 HR. F. RATED 1 REMOTE CONTROL FOR BURNER SHUT-OFF SWITCHES (5) 15'-6" 6'-9" 12'-8" THE ARCHITECT SHALL NOT HAVE CONTROL OR CHARGE OF AND SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, DEVIATIONS, TECHNIQUES, SEQUENCES, OR PROCEDURES, OR FOR SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK, FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR, SUBCONTRACTORS OR ANY OTHER PERSONS PERFORMING ANY OF THE WORK, OR FOR THE FAILURE OF ANY OF THEM TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. ALWAYS USE DIMENSIONS AS SHOWN. DRAWINGS ARE NOT TO BE SCALED. PROJECT SEAL & SIGNATURE DATE: PROJECT No: DRAWING BY: CHK BY: T. AJAYI B. AWOSIKA DWG No: CADO FILE No: A R C H I T E C T S C O N S U L T AN T S P L A N N E R S BANJI AWOSIKA ARCHITECT P.C. 140-23 Queens Blvd. Jamaica, NY 11435 Tel. 1(718) 657 5004 Fax. 1(718) 657 2447 B OF 1 No. REVISION DATE D.O.B. No: 11/13/2014 146-42 LAKEWOOD AVE. J: LAKEWOOD AVE 146-42 Lakewood Avenue Queens, New York A-001.00 CELLAR PLAN, NOTES, RISER DIAGRAMS, DOOR SCHEDULE.

146-42 LAKEWOOD AVENUE QUEENS-DWG 1

Embed Size (px)

Citation preview

Page 1: 146-42 LAKEWOOD AVENUE QUEENS-DWG 1

5- UNITS

MANUF: GALAXY

MODEL#: GXH-105 EDPT

MEA: 130-04-E

CAPACITY: 2

1

2

G.P.M.

INPUT: 105,000 BTU

OUTPUT: 86,000 BTU/HR

ENERGY EFFICIENT

FACTOR MIN. 81%

34" x 24" FA WIRE MESH.

NEW STEEL

DOOR 1 1/2 FPSC

FRESH AIR WINDOW CALCULATION

REQ'D. 1 sq. in. per 1000 BTU

Total: 5 Units =

: (5x105,000)

Total: 525,000 BTU

REQ'D. = MIN. 525 sq. inch.

PROV'D. = 34" x 24" = 816 sq. inch. O.K.

AREA OF WORKAS SHOWN INDETAIL

NEW. MECH. RM.

25'-8 1/4"

7'-4"

EXISTING METAL

CHIMNEY

63'-7

1 2

"

EXISTING 34"X 24"

FA WINDOW OPENING

18'-6 1/8"

63'-10

1 2

"

22'-1"

EXISTING & PROPOSE CELLAR PLANSCALE: 1/4"-1'-0"

3

'

X

6

'

8

"

ZONING: R4MAP #: 18cBLOCK #: 11945LOT #: 43

AREA

OF WORK

34" x 24" FA WIRE MESH.

NEW STEEL

DOOR 1 1/2 FPSC

NEW. MECH. RM.

EXISTING

METAL CHIMNEY

34" X 24" EXISTING

WINDOW OPENING

PARTIAL CELLAR PLANSCALE: 1/2"-1'-0"

ELECTRICAL NOTES:

MECHANICAL & PLUMBING NOTES:1. MECHANICAL AND PLUMBING WORK SHALL BE FILED AS REQUIRED WITH THE

APPROPRIATE CITY AGENCIES, UPON COMPLETION WORK, CONTRACTOR

SHALL ARRANGED FOR AND OBTAIN RELEVANT SIGN-OFF.

2. ALL MECHANICAL AND PLUMBING WORK SHALL CONFORM TO THE NYC CODE

AND ALL LOCAL LAWS.

1. THE ELECTRIC INSTALLATION AND REPAIRS SHALL BE IN STRICT

ACCORDANCE WITH THE NEW YORK CITY CODE AND OTHER CODES OR

AGENCIES HAVING JURISDICTION.

2. CONTRACTOR SHALL PROCURE REQUIRED PERMITS FOR HIS WORK.

3. EACH DWELLING UNIT SHALL BE PROVIDED WITH A SEPARATE METER.

4. ALL EXPOSED WIRING, UNLESS OTHERWISE NOTED SHALL BE INSTALLED IN

EMT CONDUIT. ALL CONCEALED WIRING MAY BE FLEXIBLE METALLIC CONDUIT.

5. SMOKE DETECTORS SHALL BE INSTALLED IN WIRING BEFORE ELECTRICAL

SWITCHES ARE WIRED INTO LINE.

CODE PRESCRIPTIVE VALUEPROPOSED DESIGN VALUEITEM DESCRIPTION

BOILER REPLACEMENT

ENERGY ANALYSIS FOR ALTERATION - CLIMATE ZONE 4

81% EFFICIENCY AFUE ECCCNYC, SECTION 403.7 AND TABLE 403.7

NYS ENERGY COMPLIANCE

EXISTING 2 AND HALF STORY BRICK 5-FAMILY HOUSE.

PROPOSED:

1. INSTALL FIVE NEW UNITS

IN NEW MECH. ROOM IN CELLAR.

2. INSTALLATION OF DOOR.

ALL WORK IN EXISTING CELLAR.

SCOPE OF WORK

SPECIAL INSPECTION CODE / SECTION

MECHANICAL SYSTEMSBC 1704.15

HEATING SYSTEM

BC 1704.23

7. GAS PIPING TO COMPLY WITH RS-16 SEC. D 115

8. FIXED VENT FOR BOILER COMBUSTION AIR TO BE

PROVIDED AT A RATE OF 1 SIN PER 1,000 BTU

OF BOILER INPUT.

BOILER NOTES:

1. PROVIDE A MIN. OF 18" CLEARANCE AROUND EACH BOILER.

2. NO GAS OR ELECTRIC METER IN BOILER ROOM.

3. BOILER TO BE ON CONCRETE BLOCK BASE.

4. CEILING OVER BOILER ROOM TO BE MIN. ONE(1) HR. FIRE RATED.

5. BOILER ROOM DOOR TO BE 1 1/2 FPSC.

6. NO STORAGE IN BOILER ROOM.

BOILER ROOM NOTES

1. PIPE SIZING SHALL COMPLY WITH SECTION FGC 402.

2. PIPING MATERIALS SHALL COMPLY WITH SECTION FGC 403.

3. PIPING SYSTEM INSTALLATION SHALL COMPLY WITH SECTION FGC 404

4. RESERVED SHALL COMPLY WITH SECTION FGC 405.

5. INSPECTION, TESTING AND PURGING SHALL COMPLY WITH SECTION FGC 406.

6. PIPING SUPPORT SHALL COMPLY WITH SECTION FGC 407.

7. DRIPS AND SLOPED PIPING SHALL COMPLY WITH SECTION FGC 408.

8. SHUTOFF VALVES SHALL COMPLY WITH SECTION FGC 409.

9. FLOW CONTROLS SHALL COMPLY WITH SECTION FGC 410.

10.APPLIANCE CONNECTIONS SHALL COMPLY WITH SECTION FGC 411.

GAS PIPING INSTALLATION NOTES:FROM 2008 NYC FUEL GAS CODE

SCALE 1/8"=1'0"

SITE PLAN

108th AVENUE

40.00'

160.00'

123.3

6'

123.1

9'

28.78'

12.29'L

A

K

E

W

O

O

D

A

V

E

.

CELLAR ENTRANCE

C H

A I

N L

I N K

F

E N

C E

A S

P H

A L

T P

A V

E D

D

R I

V E

W A

Y

EXISTING

TWO AND HALF

STORY BRICK DWELLING

HOUSE # 146 -42

2 STORY BRICK

WALLE/S 3'-11"E

WALL

S/S

0'-0

1 2 "

N

90°

C O N C R E T E W A L L

90°WALL

S/S

0'-4

" N

0'-2 12"W

CO

NCRET

E P

AVED

D

RIV

EWAY

BRICK WALL WITH IRON

FENCE ON TOP

21'-9 12 "

T W

O S T

O R

Y F

R A

M E

22'-1"

63'-1

0 1 2

"

63'-7

1 2 "

PRESENT STREET LINE

FINAL MAP LINE CITY OF

NEW YORK

15' -1 12 "

14'-4 12 "

99°45' 00"

21°8

' 41.

9"

4'-6

"S

STE

PS

0'-7 12 " E

SP

A P

LA

CE

2'-1

1 1 2"

3'-10 12 "

1 S

TO

RY

F

RA

ME

STE

PS

90°

SEE UNIT NOTES

ON THIS SHEET

3

'

X

6

'

8

"

1

12'-0"

6'-5"

NEW

EXIST. OPEN CELLAR

LEGEND

EXISTING WALLS & PARTITIONS

DENOTES APPROVED TYPE SMOKE DETECTOR & CARBON MONOXIDE

C.M.&S.D.

DEMOLITION WALLS

DENOTES FLOOR DRAIN

FIRST FL

GAS RISER DIAGRAM

N.T.S.

CELLAR

1"

1"

1"

UNIT

UNIT

UNIT

DENOTES 2 HR RATED PARTITION CONSTRUCTED OF 3

5

8

" METAL STUDS @ 16" O.C.

WITH 2 LAYERS 5/8" TYPE 'x' G.W.B EACH SIDE-TWO HR. RATED (GA FILE NO. WP 4135 &

B.S.A. No. 171-52-SM).

U-1

NEW

NEW

NEW

1

REMARKS

DOOR SCHEDULE

SYMBOL STYLESIZE FRAME/THK. RATING TYPE

3' X 6'8'1 3/4"

METALMECH. ROOM

SGL HINGEDSTANDARD HARDWARE1 1/2 FPSC

DOOR MAT.

2HR. F RATED INTERIOR PARTITION

NEW

U-2

NEW

U-3

NEW

U-4

NEW

U-5

NEW

U-1

NEW

U-2

NEW

U-3

NEW

U-4

NEW

U-5

EXIST. STORAGE AREA

6'-5"

13'-10"

UP

UP

EXIST. GM

EXIST.

3)E

XIS

TIN

G

GA

S M

ET

ER

S

EXIST. GM

EXIST. GM

EXIST.

EXIST.

EXIST.

1"

1"UNIT

UNIT

NEW

NEW

EXIST.

EXIST.

EX

IS

T.

EX

IS

T.

EXIST.

EX

IS

T.

EX

IS

T. LA

ND

IN

G

CO

DRAIN RISER DIAGRAM

4"

4" S

FIRST FL

6" SANITARY

MIN. SLOPE: 1/8"/FT

C.M.&S.D.

C.M.&S.D.

N.T.S. N.T.S.

EXISTING WALL

TO BE REMOVED

EXISTING WALL

TO BE REMOVED

NEW WALL

2 HR. F. RATED

1

REMOTE CONTROL FOR

BURNER SHUT-OFF

SWITCHES (5)

15'-6"

6'-9"

12'-8"

THE ARCHITECT SHALL NOT HAVE CONTROL OR CHARGE OF AND

SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS,

DEVIATIONS, TECHNIQUES, SEQUENCES, OR PROCEDURES, OR FOR

SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE

WORK, FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR,

SUBCONTRACTORS OR ANY OTHER PERSONS PERFORMING ANY OF THE

WORK, OR FOR THE FAILURE OF ANY OF THEM TO CARRY OUT THE

WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. ALWAYS USE

DIMENSIONS AS SHOWN. DRAWINGS ARE NOT TO BE SCALED.

PROJECT

SEAL & SIGNATURE DATE:

PROJECT No:

DRAWING BY:

CHK BY:

T. AJAYI

B. AWOSIKA

DWG No:

CADO FILE No:

A R C H I T E C T S

C O N S U L T AN T SP L A N N E R S

BANJI AWOSIKA ARCHITECT P.C.

140-23 Queens Blvd.Jamaica, NY 11435Tel. 1(718) 657 5004Fax. 1(718) 657 2447

B

OF 1

No.

REVISION DATE

SHORING AREA & EXCAVATION DETAIL 03.22.101

D.O.B. No:

11/13/2014

146-42 LAKEWOOD AVE.

J: LAKEWOOD AVE

146-42 Lakewood Avenue Queens, New York

A-001.00

CELLAR PLAN, NOTES, RISER DIAGRAMS, DOOR

SCHEDULE.

AutoCAD SHX Text
UP 7 RISERS
AutoCAD SHX Text
UP 9 RISERS EXIST.
AutoCAD SHX Text
F.D.
AutoCAD SHX Text
1
AutoCAD SHX Text
(Catherine Pl.)
AutoCAD SHX Text
(Lincoln Ave.)
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
(Kouwenhoven Pl.)
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
F.D.
AutoCAD SHX Text
3 1/2" SOUND ATTENUATION BLANKETS TO UNDERSIDE OF SLAB PROVIDE 2-20 GAUGE STUDS AT DOOR JAMBS BOTTOM TRACK ACOUSTICAL SEALANT (TYP)
AutoCAD SHX Text
STRUCTURE ABOVE TOP TRACK ANCHORED TO STRUCTURE ABOVE ACOUSTICAL SEALANT (TYP) SUSPENDED CEILING IF OCCURS SEE RCP 2-LAYERS OF 5/8" FIRE RATED GWB EACH SIDE EXTEND TO UNDERSIDE OF SLAB ABOVE 3 5/8" MTL STUDS @ 16" O.C.
AutoCAD SHX Text
F.D.
AutoCAD SHX Text
4"FD
AutoCAD SHX Text
F.D.
AutoCAD SHX Text
1