Upload
nguyenhanh
View
216
Download
1
Embed Size (px)
Citation preview
Long-Term Verification Test of a 275 kV-3 kA REBCO HTS Model Cable
Shinichi Mukoyama, Masashi Yagi, Takaharu Mitsuhashi, Jin Liu(Furukawa Electric)
Takeshi Ohkuma, Osamu Maruyama (ISTEC-SRL)Naoki Hayakawa (Nagoya Univ.)
Xudong Wang, Atsushi Ishiyama (Waseda Univ.)Naoyuki Amemiya (Kyoto Univ.)
Takayo Hasegawa (Showa Cable Systems)Takashi Saitoh (Fujikura)
This work was supported by the NEDO in M-PACC project.
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
2
Cur
rent
[kA
]
Voltage [kV]
0
5
2.5
0 300100 200
*Albany (NY) 330m, Bi-Y
Super-ACE500m, BiFurukawa
*LIPA(NY)600m, Bi-Y
*HYDRA (NY) 300m,Y(AMSC)
*Soul500m,Y(AMSC)
KERI,LS‐cable100m,Y
*New Orleans 1760m,Y(AMSC)
*Columbus200m,Bi
M-PACC,Y30m
Furukawa
M-PACC,Y15m
500MVA 1000MVA 1500MVA250MVA
*Amsterdam6km,Y
Y:YBCOBi:BSCCO*:in grid
Barcelona30m,Bi
30m, Y
*Bi実証200~m
*CEPRI, Beijing1000m,Y
20kV-2kAMoscow, 200m,Bi
HTS Cable projects in the world
Longest
Highest
We can be available for any HTS cables with high current, high voltage, and DC.All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
3
Merits of 275 kV HTS cable
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
・The capacity of the 275 kV HTS cable having 1.5 GW corresponds to a typical overhead transmission line.・The total loss of the 275 kV HTS cable becomes one-fifth of that of the XLPE / OF cable.
XLPE cable 3cct HTS cable
Rating voltage
275kV 275kV
Rating capacity
1,500MVA 1,500MVA
(3 circuit = 9 cables)
(1 circuit = 3 cables)
Current 1.05kA×3 3.15kA
Transmission loss
284 kW/km 59 kW/km
Outer diameter
155mm×9 150mm×3
Overhead line
HTS Cable
XLPE/OFCable
~1/5~1/5
Compact Compact
Tunnel constructionInstallationCooling systemCableManufacturing costHTS wires
0
10
20
30
40
50
現用ケーブルConventional cable
超電導ケーブルSuperconducting cable
Cabl
e c
onst
ruction c
ost
[×
0.1
B\/km
-cct]
土木費布設費冷却システムケーブル費
ケーブル製作費超電導線
53%低減Decrease of 53%
Conventional cable Superconducting cable
4
Development of 275 kV-3 kA HTS cable
Hastelloy ~100m
Gd2Zr2O7(~1.0m)
CeO2 (~1.0m)
YBCO (~1.5m)Ag (~30m)
Cu (~25m)
structure of coated conductor (FJK)
InsulationHTS Shield
HTS conductor
Ic: 300 A/cm at 77 KWire made by Fujikura/Showa and SRL
(1) Low Loss:-AC loss and dielectric loss<0.8 W/m at 3 kArms and 275 kV
(2) Design of Electrical insulation:cable, termination and joint
(PD free at AC 310 kV, no BD at impulse 1155 kV)*[PD: Partial Discharge, BD: Breakdown]
(3) Endurance of over-current:63.0 kArms for 0.6 s;
(4) Compact:<150 mm (outer diameter)
Technical Targets:
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
5
2008~2010: Fundamental technology and system design・AC loss reduction・Over-current test・Design of electrical insulation・Design of the cable system
2011: Fabrication and Evaluation of Test Cable・Fabrication・Evaluation (Ic, Withstand voltage test ,
over-current characteristics)
2012: Demonstration system・275kV-3kA Cable fabrication ・Transportation (Japan→Shenyang, China)・Installation (System construction)・Verification test (Ic, AC current test, Withstand voltage test ,
AC loss and dielectric loss, Long-term verification test)
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
Development contents
6
AC loss measurement
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2011
-5
0
5
10
15
20
25
30
-4 -3 -2 -1 0 1 2 3 4Crit
ical
cur
rent
den
sity
(109 A
/m2 )
Lateral positon (mm)
Trapezoidwith 0.8 mm-shoulder
4
6
10-11
2
4
6
10-10
2
4
6
10-9
2
Nor
mal
ized
AC
loss
[J/m
/cyc
le/A
2 ]
1.00.80.60.40.2It(peak current) / Ic
HTS conductor at 2011 Ic=9020 A at 73.7 K Ic=8150 A at 74.4 K Ic=6270 A at 77.3 K Calculation
0.124 W/m at 3 kA
HTS conductor at 2010 Ic=9200 A at 68.7 K Ic=8550 A at 70.0 K Ic=6700 A at 72.5 K Ic=4700 A at 77.3 K Calculation
0.235 W/m at 3 kA
BSuperconductor
Substrate
The calculation: taking Jc distribution into account
AC loss of the designed conductor was low, 0.124 W/m at 3kA.
AC loss is reduced by using 3 mmW tape to suppress the perpendicularity field on the tape.Cutting method of tape has been improved to prevent damege of cutting part.
Investigation of insulation material(275kV HTS cable)
30282624222018
PD inception stress [kVrms/mm]
Cum
ulat
ive
prob
abili
ty [
%]
99.999990705030
1053
10.50.3
0.1
1 mmt model cable No.2 &No.3 10 mmt model cable
70
60
50
40
30
Brea
kdow
n st
ress
[kV/
mm
]
10-3
10-2
10-1
100
101
102
103
time [hour]
n=50
PPLP-C (0.3 MPa(abs))
65hで破壊102hで破壊せず
70
60
50
40
30
Brea
kdow
n st
ress
[kV/
mm
]
10-3
10-2
10-1
100
101
102
103
time [hour]
n=50
n=49
PPLP-A (0.59 MPa(abs.))
PPLP-A (0.3 MPa(abs.)) PPLP-C (0.3 MPa(abs.))
AC B.D stress Imp. B.D stress
PDIEV-t
To reduce dielectric loss, pp laminated paper with a higher pp ratio of 60% was used.
7All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2011
8
Design of 275 kV-3 kA HTS cable
8
Structure Specification Diameter mm
Former Hollow stranded copper35.4
HTS conductor 2-layer YBCO
Insulation PP laminated paper81.0
HTS Shield 1-layer YBCO
Cu Protective Copper tape88.0
Protection Insulation paper
Cryostat pipe SUS and PVC sheath 150
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
PE shieth O.D. 150mm
HTS conducting layer
HTS Shield layer
PP laminated papert
Cu protection layer
Cryostat pipe
Cu stranded former
9
HTS core of 50 m
HTS Shield
HTS conductor
Insulation
Cu hollow former
PE φ150mm
Vacuuminsulation
30 m for demonstration
HTS core with cryostat pipe
sample tests,Ic, over-current,withstand voltage tests.
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
In VISCAS
275kV-3kA Cable fabrication
10
Testing condition
Test Shipping testSample cable of 5 m
Long term verification test30 m cable
Referenced standard
1 Partial discharge test 310 kV-10min 310 kV-10min
2 Critical currentmeasurement
DC DC
3 Load-cycle(Long-term verification test)
200 kV-1 month3 kA ON/OFFMore than 20 cylcles
JEC-3408
4 Critical currentDielectric loss
DC
5 Impulse voltage ± 1155 kV-3shots After long term test±1155 kV-3shots
JEC-3408
6 Partial discharge test 310 kV-10min 310 kV-10min
7 Voltage test 320 kV(2U0) 15min 320 kV(2U0) 15min IEC62067
6 Voltage test 400 kV(2.5U0)30min
400 kV(2.5U0) 30min IEC62067
・Test conditions were decided as a shipping test and a long term verification test, referring to the conventional cable standards of IEC and JEC.
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
11
Long-term Characteristics (V-t)
V-t of PDIE and breakdown at 0.3 MPa(abs.)
Life time constant of PDIE was 80. There was no degradation after the V-t of PDIE.Life time constant of B.D. was 50. There was degradation after the V-t of B.D.
Evaluation of the Long-term characteristics (V-t) of model cables with insulation thicknesses of 1 mm
11
60
50
40
30
20
AC V
olta
ge [k
V/m
m]
10-3
10-2
10-1
100
101
102
103
time [hour]
V-t of PDIE, n=80
V-t of AC breakdown stress, n=50
0.3 MPa(abs)
760h
42.3 kV/mm65 h
ntypeAC days
daysyearsUV1
0 )30
36530(
Long-term verification test
275 kV
Voltage 160 kV 200kV
term 30 years 30 days
n (life time constant) =50U0=160 kV
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
12
(Voltage tap distance: 1.5 m)
Ic=6440 A (@1µm/cm)
Current [A]
Gen
erat
ed V
olta
ge [m
V]
Ic was obtained as 6440A at 77.3 K,almost agreed the sum of all the used YBCO tapes
Over-current test:At 63.0 kArms for 0.6 s, which was the worst situation in 275 kV systems
No Ic degradation after 63.0kArms for 0.6sec
Ic:
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
Sample tests (1) Ic, Over-current test
TransformerTransformer
Short HTS cable with a joint part
13
5
4
3
2
1
0
Sin
gals
of C
D-5
[V]
Time [10 ms/div]
-40
-20
0
20
40
Applied V
oltage [kV] sinals of CD-5
Voltage [kV]
Detection of the PD inception stress
13
Model cable Voltage test AC Voltage test 400kV 30min
Imp Voltage test 1155 kV
PD test 310 kV (no P.D.)
The sample was PD free at AC 310 kV for 10 minutes and withstood at AC 400 kV in LN2 under atmospheric pressure.
Sample tests (2) voltage withstand tests
LN2/ PP laminated paper
Sample cable
Cryostat for voltage tests
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
14
Visual confirmationAcceleration
TerminalCable joint HTS Cable
After Vs. Before Comparison result:There was no troubleduring the transportation.
Chiba,Yokohama
China
JapanShenyang
Dalian
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
Joint construction and Transportation
15
System construction (1)
Transformer
Testing sites
Terminal
XLPE cables for current carrying
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
16
Monitoring
Cooling system
安全弁
安全弁
安全弁安全弁
安全弁
LN2 circulating in the closed loop,No cooler.
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
System construction (2)
17
Joint
Cold Evaporator
Cooling system house
Transformer
Cooling system
monitoring
PD test monitor
Voltage controller
Current controller
Control room
Terminal
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
Finished in October 2012
System construction (3)
18
System construction
Joint
30 m HTS Cable
AC Transformer
Cooling system house
Joint & Termination
19
Conductor layer: 6800 A
Shield layer: 7000 A
Ic: 77.3K
All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
-4000
-2000
0
2000
4000
Cur
rent
[A]
50x10-3403020100
Time [s]
Conductor Current Shield Current
AC current test: 3 kArms
The rate of shield current to conductor current is about 75%, which is due to 13 m long of the normal conduction part in the shield circuit according to the results of numerical calculation. The inductance of normal conductor is dominant. The shield rate of only HTS cable is 98.6%
Withstand voltage test :
No PD(partial discharge ) at AC 310 kV for 10 minutes
Before long-term test
Results of Verification test (1)
20All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
Long-term test(11/18~12/20)
Operation Temperature
72 K
Cooling capacity
>3 kW
Voltage 200 kVCurrent 3 kACycle >20 (8h ON, 16h OFF)Term 1 month
Successfully conducted200 kV- 1 month:Determined by assuming insulation degradation in 30 years
Voltage Current
Results of Verification test (2)
21All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
After long-term test
Suggesting the superior reliability of this HTS cable system even for 30 years.
PD test:
No-PD was observed at AC 310 kV for 10 minutes
Ic: No degradation
AC loss: 0.19 W/m
Dielectric loss: 0.44 W/m at the operating voltage of 160 kV, which is almost 25% lower than the designed value of 0.60 W/m
(measured by the calorimetric method)
Results of Verification test (3)
2222All Rights Reserved, Copyright© FURUKAWA ELECTRIC CO., LTD. 2013
Summary
275kV-3kA HTS cable was designed and fabricated:・HTS Cable outer diameter 150 mm・Ic 6440 A at 77.3 K of the conduction layers of 1.5 m long part・PD-free at 310 kV and No BD at 400 kV in LN2 under atmospheric pressure・No Ic degradation after the over-current of 63.0 kArms for 0.6 s
Construction of demonstration system was completed:・Included the 30 m long HTS cable, two terminals, a cable joint and a cooling
system
Verification test :・Ic of HTS conductor and HTS shield were 6800 A and 7000 A, respectively・Long-term verification test was successfully conducted ・No-PD and No-Ic degradation after the long-term verification test
These results show a success in the development of 275kV-3kA HTS cable with the world's highest voltage and largest capacity