Upload
theiva
View
232
Download
7
Tags:
Embed Size (px)
Citation preview
Slide 1
Session1-2
Power System Protection-Overview
N. Theivarajan . Head, Power Plant Control Division .Reactor Design GroupIGCAR.
This Material Is Adopted From Many Sources For MAPS/NPCIL Course In March 2015
Typical Power Plant SLD For Coordination Study
Major Power System Objects of Protection
TransformersMotorsGeneratorsSwitchgear Cable Systems/FeedersTransmission Lines/Associated Systems Power Electronic Converters/Inverters Power System Components Capabilities.Broad Performance CapabilitiesVoltage: Rated , Power Fre., Switching, Impulse Withstand
Current:Rated, Short time, Short Circuit withstand,Negative Phase sequence,
Power: Real, Reactive, Apparent
Thermal Capabilities:
Speed : Over speed, Critical Speed,..
Some of The Major Issues With Power System Components InsulationDesign defects or errorsImproper manufacturingImproper installationAging insulationContaminationElectricalLightning surgesSwitching surgesDynamic overvoltagesThermalCoolant failureOvercurrentOvervoltageAmbient temperatureMechanicalOvercurrent forcesEarthquakeForeign object impactSnow or iceDeviation on Performance Characteristics /Capabilities due to:
Three-phase fault (a-b-c, a-b-c-g)Phase-to-phase fault (a-b, b-c, c-a)Two-phase-to-ground fault (a-b-g, b-c-g, c-a-g)Phase-to-ground fault (a-g, b-g, c-g)
Voltage Surges
Exceeding Thermal Limits
GENERAL PROTECTION PERSPECTIVES
PROTECTION DEVICES &CHARACTERISTICES Input Parameters Available For Protection Devices.
CurrentVoltageFrequencyPressureTemperatureFlowVibration
Type of Protection Devices :
Thermal Electromechanical Static Microprocessor/Numerical Performance CharacteristicsOver current- Phase or GroundDirectional Over current Inverse time/Definite time / IDMT Under voltageOvervoltage
Differential- Low , High Impedance, REF, Current Distance- Many Characteristics Phase comparisonDirectional comparison
MCB and MCCBs With Built in Protection FunctionThermal-magnetic MCCB operating characteristic
Typical electronic low-voltage circuit breaker trip characteristic
Magnetic-trip MCCB operating characteristic
HRC Fuses
Thermal Over Load Relays
Protective Relays
Over current Relays
Directional Over current Relays
Earth Fault Relay Connection
Power Relays
Differential Relays
High Impedance Differential Protection
This type of protection is normally used for protection of motors, generators, bus bars as well as for restricted earth fault protection of transformers.
This type of protection is used to protect an area with the same voltage level.Percentage Biased Differential Protection For Transformers
The term percentage differential stems from the fact that the operating threshold increases with the through current.
Simple comparison of the currents in each upstream phase with the currents in the same downstream phases is not suitable fortransformer differential protection.
The upstream and downstream currents of a power transformer do not have the same amplitude or the same phase angle,
When the transformer is energized, its magnetizing current is only seen upstream.
Low Impedance Differential Protection.
This protection is used for bus bar differential protection. It is very costly and space-consuming, as it requires a large number of modules and matching CTs which need one ormore cubicles according to switchboard size
In the case of a double bus bar switchboard, the protection must be continually informed on the position of the transfer switches in order to direct the currents of each feeder and incomer to the relay associated with monitoring of the bus bar on which this feeder or incomer is connected.
The CTs associated with this sophisticated protection may have different ratios. Their secondaries are also defined as class X in most cases. However, as saturation can be tolerated , knee point voltage requirements are less severe than for high impedance differential protection.
Pilot protection schemes -Three categories.
Directional comparison scheme
Distance or Directional relays determine whether each terminal sees the fault as forward or reverse.
By exchanging this information, the fault can be classified as either internal or external to the protected line segment.
Phase comparison- Current only Pilot protection.
Phase comparison protection systems compare the phase angles of currents entering at one terminal of the line and the currents leaving at the other terminal of the line.
If the fault is external, the currents entering and exiting the line should be in phase with each other. Current differential schemes
Send information about the magnitude and angle of the currents entering and exiting the line.
This type of pilot protection requires higher bandwidth tele protection channels, and it is becoming more common with the availability of fiber-optic networks.