02 ADVC_206B_FV Protection Coordination and Timing

Embed Size (px)

Citation preview

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    1/39

    Protection Discrimination and Timing

    On the ADVC Controller

    With a flexVUE Operator Interface

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    2/39

    Schneider Electric 2 < AUTHOR >

    The purpose of this presentation is to show howprotection discrimination is achieved with the ADVCController.

    The following topics will be covered:

    Discrimination by time.

    Discrimination by current.

    Discrimination by time and current.

    Standard and non standard curves available on the ADVC.

    How protection curves can be modified to assist inachieving coordination and discrimination.

    Discrimination Overview

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    3/39

    Schneider Electric 3 < AUTHOR >

    Principle of Discrimination

    Correct discrimination ensuresthat the faulty part of a power

    system only is isolated as quicklyas possible, leaving all of thefault-free parts energised.

    Fault F1 may be detected by

    protection devices A, B, C and D.

    Time to Trip for D should beshorter than C which is shorterthan B etc.

    This ensures that only the circuitnecessary to clear the fault isdisconnected by either primary orback-up protection.

    A

    B

    C

    D

    F1

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    4/39

    Schneider Electric 4 < AUTHOR >

    Discrimination Interval

    The difference in operation time

    T between two successive

    protection devices is thediscrimination interval.

    It takes into account

    -Breaking timeTc

    of the

    downstream circuit breaker, which

    includes the breaker response time

    and the arcing time.

    -Time delay tolerances dT

    -Upstream protection unit overshoot

    time tr.

    -A safety margin m.

    T should therefore satisfy the

    relation:

    -T Tc + tr +2dT + m

    Example:

    -Tc = 50 ms

    -dT = 30 ms

    -Tr = 30 ms

    TB TA

    dTB dTATcB m trA

    30ms 30ms 30ms50ms 60ms

    Discrimination Interval T

    200 ms

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    5/39

    Schneider Electric 5 < AUTHOR >

    Time to Trip

    The time delay between Pickup

    and Trip is determined by the

    protection settings applied.

    The Time to Trip is dependant on

    whether the active trip is set to:

    -Definite Time

    -Instantaneous Only

    -Inverse Time

    Possible Active Trips

    -Trip 1

    -Trip 2

    -Trip 3

    -Trip4

    -Single Shot

    -Work Tag

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    6/39

    Schneider Electric 6 < AUTHOR >

    Trip Settings on the flexVUE Operator Interface

    PROTECTION MENU

    Protection Global

    Protection Trip Settings

    Protection Control

    Directional Elements

    ENGINEERING MENU

    Protection menu

    Configuration menu

    Power quality

    Telemetry menu

    Automation menu

    Measurements menu

    PROT TRIP SETTINGS

    Trip 1, 2, 3, 4

    (Reclose time, Protection &

    reset curve for P, E, SEF,

    NPS)

    Single Shot

    (SS reset time, Protection

    & reset curve for P, E, SEF,

    NPS)

    Work Tag

    (Protection & reset curve

    for P, E, SEF, NPS)

    Under Over Frequency

    (Under, Over, Normal

    Close, Low V inhibit,

    Bushing)

    Under Over Voltage

    (Under, Over, Config)

    Loss of Phase

    (On/Off/Alarm, Voltage,

    Timeout)

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    7/39Schneider Electric 7 < AUTHOR >

    Types of Discrimination

    Various means can be used by

    the ADVC controller to implement

    discrimination between devices.

    Time-based discrimination

    -Definite Time

    Current-based discrimination

    -Instantaneous Only

    Discrimination based on time and

    current-Inverse Curves

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    8/39Schneider Electric 8 < AUTHOR >

    Time-Based Discrimination

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    9/39Schneider Electric 9 < AUTHOR >

    Time-Based Discrimination

    Time-based discriminationconsists of assigning different

    time delays to the overcurrentprotection units distributedthrough the power system.

    The closer the relay is to thesource, the longer the time delay.

    Advantages:

    -Provides back-up

    -It is simple

    Drawbacks

    -The longest fault clearance timeoccurs for faults closest to thesource where the fault level ishighest.

    A

    B

    C

    D

    F1

    DT = 0.2s

    DT = 0.5s

    DT = 0.8s

    DT = 1.1s

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    10/39Schneider Electric 10 < AUTHOR >

    Trip 1 Phase Protection Definite Time

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    11/39

    Schneider Electric 11 < AUTHOR >

    1.0 s Definite Time Curve

    > 200A

    1.0s 4.00

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    12/39

    Schneider Electric 12 < AUTHOR >

    1.0 s Definite Time Curve with x4 Instantaneous

    >800A

    1.0s

    200-800A

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    13/39

    Schneider Electric 13 < AUTHOR >

    Current-Based Discrimination

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    14/39

    Schneider Electric 14 < AUTHOR >

    Current-Based Discrimination

    Current-based discrimination

    works on the principle that the

    further the fault is from the source,the lower the fault current will be.

    The threshold is set to a value

    lower than the minimum short-

    circuit current caused by a fault inthe protected section and higher

    than the maximum current caused

    by a fault in the next section.

    Each protection device should

    only pickup for faults located in

    the section of feeder immediately

    downstream.

    A

    B

    C

    D

    F1

    IsC=490A

    IsB=780A

    IsA=960A

    IscAmin = 1000A

    IscBmin = 800A

    IscCmin = 500A

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    15/39

    Schneider Electric 15 < AUTHOR >

    Current-Based Discrimination with Transformers

    For sections of lines separated by

    a transformer, it can be of benefit

    to use this system since it issimple, cost effective and fast

    (instantaneous).

    IsA < IscAmin

    IsA=960A

    F1

    IscAmin=1250A

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    16/39

    Schneider Electric 16 < AUTHOR >

    Current-Based Discrimination with Transformers

    Protection devices should be set

    such that:

    IscBmax < IsA < IscAmin

    Time delays TA and TB are

    independent and TA may be

    shorter than TB

    Drawbacks:

    -The upstream protection device (A)

    does not provide back-up for the

    downstream device.

    -In practice it is difficult to define the

    settings for two cascading

    protection devices and still ensure

    discrimination unless there are

    transformers between sections.

    IsB=600A

    IscBmax 760A

    F1

    IscAmin=1250A

    IsA=960A

    TA=0.6s

    TB=0.9s

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    17/39

    Schneider Electric 17 < AUTHOR >

    Current-Based Discrimination with Transformers

    IsB=600A

    IscBmax 760A

    F1

    IscBmax < IsA < IscAmin

    IscAmin=1250A

    IsA=960At

    I

    AB

    IsB IscB

    maxIsA IscA

    min

    TA

    TB

    TB=0.9s

    TA=0.6s

    To ensure discrimination:

    1.25 IscBmax < IsA < 0.8 IscAmin

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    18/39

    Schneider Electric 18 < AUTHOR >

    Trip 1 Phase Protection Instantaneous Only

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    19/39

    Schneider Electric 19 < AUTHOR >

    Instantaneous Only Curve

    0.3

    200A

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    20/39

    Schneider Electric 20 < AUTHOR >

    Instantaneous Only Curve with Minimum Time

    0.3

    > 200A

    0.30s

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    21/39

    Schneider Electric 21 < AUTHOR >

    Discrimination by Time and Current

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    22/39

    Schneider Electric 22 < AUTHOR >

    Discrimination by Time and Current

    A combination of both time andcurrent discrimination can be

    used to achieve totaldiscrimination with built-inredundancy or back-up.

    In the example below device Buses Definite Time and device Auses Definite Time with anInstantaneous multiplier.

    A

    B

    t

    I

    T

    B A

    A DT

    A Inst

    B DT

    IsB IsA IscB IinstA IscA

    Feeder 1

    Feeder 2

    A is thePrimary

    protection

    device for

    Feeder 1

    Back-up for

    feeder 2

    B is the

    Primary

    protection

    device for

    Feeder 2

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    23/39

    Schneider Electric 23 < AUTHOR >

    IDMT Inverse Time Curves

    With this characteristic, the time ofoperation is inversely proportional

    to the fault current level and theactual characteristic is a functionof both time and currentsettings.

    ADVC Inverse Curves

    -IEC255Standard Inverse

    Very Inverse

    Extremely Inverse

    -IEEE

    Standard Moderately Inverse

    Standard Very Inverse

    Standard Extremely Inverse

    -TCC

    42 Non-standard curves

    I

    t

    1 1

    0

    1

    0

    0

    1

    0

    0

    0

    0.01

    0.1

    1.0

    10.0

    IEC255 I C

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    24/39

    Schneider Electric 24 < AUTHOR >

    IEC255 Inverse Curves

    IEC60255 Standard Curves

    Standard Inverse Time

    Time to Trip = 0.14 / ( Im0.02 1)

    Very Inverse Time

    Time to Trip = 13.5 / ( Im 1)

    Extremely Inverse Time

    Time to Trip = 80.0 / (Im2 1)

    IEC255 Inverse Curves

    IEEE I C

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    25/39

    Schneider Electric 25 < AUTHOR >

    IEEE Inverse Curves

    IEEE Standard Inverse Curves

    Moderately Inverse Time

    Time to Trip = (0.0515( Im0.02

    1)) + 0.114

    Very Inverse TimeTime to Trip = (19.61 / (Im2 1))

    + 0.491

    Extremely Inverse Time

    Time to Trip = (28.2 / (Im2 1))

    + 0.1217

    IEEE Inverse Curves

    TCC N St d d I C

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    26/39

    Schneider Electric 26 < AUTHOR >

    TCC Non-Standard Inverse Curves

    The group of 42 TCC non-standard curves are generally

    plotted curves that do not complyto a formulae.

    -TCC136

    -TCC101

    -TCC131

    -TCC121

    -TCC161

    -TCC200

    Selection of TCC Inverse Curves

    S l ti I C

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    27/39

    Schneider Electric 27 < AUTHOR >

    Selecting an Inverse Curve

    IEC255 St d d I C

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    28/39

    Schneider Electric 28 < AUTHOR >

    IEC255 Standard Inverse Curve

    400A x2

    10.03s

    2000A x10

    2.97s

    2.00

    IEC255 St d d I C TM 2

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    29/39

    Schneider Electric 29 < AUTHOR >

    IEC255 Standard Inverse Curve TM x2

    2.00

    400A x2

    20.06s

    0.20

    2000A x10

    5.94s

    IEC255 St d d I C TM 0 2

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    30/39

    Schneider Electric 30 < AUTHOR >

    IEC255 Standard Inverse Curve TM x0.2

    2.00

    400A x2

    2.006s

    0.20

    2000A x10

    0.59s

    IEC255 St d d I C TM 0 2

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    31/39

    Schneider Electric 31 < AUTHOR >

    IEC255 Standard Inverse Curve TM x0.2

    2.00

    400A x2

    2.006s

    0.20

    2000A x10

    0.59s

    0.80

    IEC255 Standard Inverse Curve Min Time = 0 8s

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    32/39

    Schneider Electric 32 < AUTHOR >

    IEC255 Standard Inverse Curve Min Time = 0.8s

    2.00

    400A x2

    2.006s

    0.20

    2000A x10

    0.80s

    0.80

    0.20

    IEC255 Standard Inverse Curve Add Time = 0 2s

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    33/39

    Schneider Electric 33 < AUTHOR >

    IEC255 Standard Inverse Curve Add Time = 0.2s

    2.00

    400A x2

    2.206s

    0.20

    2000A x10

    0.80s

    0.80

    0.20

    IEC255 Standard Inverse Tripping Times

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    34/39

    Schneider Electric 34 < AUTHOR >

    IEC255 Standard Inverse Tripping Times

    BCDE

    40A

    IEC255SI

    200A

    IEC255SI

    A

    F1

    400A

    F2

    2500A

    Current Trip

    ACR Setting Multiple Time

    Fault F1 400A B X 10 2.97s

    E X 2 10.03s

    Fault F2 2000A E X 12.5 2.7s

    Effect of Applying Time Multiplier = 0 2

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    35/39

    Schneider Electric 35 < AUTHOR >

    Effect of Applying Time Multiplier = 0.2

    BCDE

    40A

    IEC255SI

    200A

    IEC255SI

    A

    F1

    400A

    F2

    2500A

    Current Trip Time

    ACR Setting Multiple Time Multiplier

    0.2

    Fault F1 400A B X 10 2.97s 0.594s

    E X 2 10.03s 2.006s

    Fault F2 2000A E X 12.5 2.7s 0.54s

    Effect of Applying Minimum Time = 2 0s

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    36/39

    Schneider Electric 36 < AUTHOR >

    Effect of Applying Minimum Time = 2.0s

    BCDE

    40A

    IEC255SI

    200A

    IEC255SI

    A

    F1

    400A

    F2

    2500A

    Current Trip Time Minimum

    ACR Setting Multiple Time Multiplier Time

    0.2 2.0s

    Fault F1 400A B X 10 2.97s 0.594s 2.0s

    E X 2 10.03s 2.006s 2.006s

    Fault F2 2000A E X 12.5 2.7s 0.54s 2.0s

    Effect of Applying Additional Time = 1 0s

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    37/39

    Schneider Electric 37 < AUTHOR >

    Effect of Applying Additional Time = 1.0s

    BCDE

    40A

    IEC255SI

    200A

    IEC255SI

    A

    F1

    400A

    F2

    2500A

    Current Trip Time Minimum Additional

    ACR Setting Multiple Time Multiplier Time Time

    0.2 2.0s 1.0s

    Fault F1 400A B X 10 2.97s 0.594s 2.0s 2.0s

    E X 2 10.03s 2.006s 2.006s 3.006s

    Fault F2 2000A E X 12.5 2.7s 0.54s 2.0s 2.0s

    Applying an Instantaneous Modifier

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    38/39

    Schneider Electric 38 < AUTHOR >

    Applying an Instantaneous Modifier

    BCDE

    40A

    IEC255SI

    200A

    IEC255SI

    A

    F2

    3000A

    Current

    ACR Setting

    Multiple

    Trip

    Time

    Instantaneous

    Multiplier

    Additional

    Time

    Minimum

    Time

    X 14 1.0s 2.0s

    Fault F2 3000A E X 15 2.52s

  • 7/28/2019 02 ADVC_206B_FV Protection Coordination and Timing

    39/39

    Protection Discrimination - Review

    The main objectives of Protection Coordination are:

    When a fault is detected, only the smallest part of the network necessary to

    isolate that fault should be disconnected.This means that for a given fault the primary protection device should operate

    in the shortest possible time to clear the fault.

    If the primary protection device fails to clear the fault in the expected time, aback-up device should clear the fault in a longer but still acceptable time.

    Three types of discrimination can be used by the ADVC controller:

    1. Discrimination by Time Definite time2. Discrimination by Current Instantaneous Only

    3. Discrimination by both Time and Current Inverse Curves

    Definite Time curves can be modified by:

    Instantaneous

    Instantaneous Only curves can be modified by:Minimum Time

    Inverse Curves can be modified by:

    Time Multiplier, Instantaneous, Additional Time and Minimum Time.