Upload
independent
View
0
Download
0
Embed Size (px)
Citation preview
SHEAR FAILURE IN PLAIN CONCRETE AS
APPLIED TO CONCRETE PAVEMENT OVERLAYS
Yi Xu1 and John N Karadelis
2
1, 2
Department of Civil Engineering, Architecture and Building, Coventry
University, CV1 5FB, UK
Abstract. This study applied the modified Iosipescu loading configuration on
beams and direct shear loads on cylinders to investigate the concrete behaviour
under minimal flexural and prominent shear stress conditions, particularly in plain
concrete tests. It aims to make a contribution in understanding the behaviour of a
concrete pavement under shear loading and failure and ultimately design an
adequate overlay system. A finite element model corresponding to the modified
Iosipescu beam test was set up to assist with the recognition and study of the
complex stress patterns developing at high stress concentration regions and the
evaluation of principal stresses. Both, normal and high strength concrete were
used, to imitate the performance of the existing (old) pavement and the prospect
overlay under shear. On the basis of the laboratory results and the preliminary
finite element analysis, it was found that all specimens failed abruptly without
warning in a typical brittle-material / shear-failure manner. Considerably higher
shear strengths were achieved compared to those specified in the standards.
Unexpectedly, the high strength concrete developed slightly lower shear strength
than the normal concrete. This is probably attributed to insufficient compaction
and relatively less effective aggregate interlock in high shear regions. The research
is in progress.
Introduction and Literature Survey
Shear failure at cracks/joints is a major cause of degradation of concrete
pavements. It leads to serviceability problems and introduces reflective cracks and
becomes an issue of structural integrity, durability, riding quality and safety of the
deteriorated pavement.
To address the problem, a Rapid Pavement Repair and Strengthening Management
System (RPRSMS) is under development at the Department of Civil Engineering,
Yi Xu and John N Karadelis
2
Coventry University. It aims to bring to light the structural and functional
deficiencies and extend the life of the pavement and at the same time introduce
substantial benefits, such as saving construction materials, time and labour costs,
by bonding a layer of special-quality concrete on top of the existing damaged
pavement. Therefore, all the aforementioned contribute to a more sustainable
pavement repair system.
In this study, the modified Iosipescu loading configuration [1] was adopted for
testing the beams. Direct shear loads were applied on cylindrical specimens to
investigate the concrete behaviour under high shear and low moment conditions.
Cylinder torsion tests were carried out to assist with the investigation of the
concrete shear performance. A finite element model simulated the behaviour of the
specimens and assisted with the recognition and study of the loading configuration
that otherwise would not be easily identifiable (complex stress patterns developing
at high stress concentration regions, evaluation of stresses and stress intensity
factors). Both, normal and high strength concrete were used, to imitate the
performance of the existing/old pavement and the prospect overlay under shear.
Glass fibre was added to the high strength concrete mix in an effort to enhance its
shear resistance further. The influence of coarse aggregate, mixing procedure,
compaction and curing method on the shear resistance was also assessed
experimentally. Emphasis was given to the experience built up so far, so essential
for outlining future similar type of work.
Shear Problems in Pavement Overlays
Three possible main failure modes were identified:
Flexure failure: The crack propagates upwards into the new overlay due to
exceeding its flexural strength.
Shear failure: The crack propagates upwards into the new overlay mainly due
to insufficient shear resistance.
Delamination: The crack develops along the interface.
In a real pavement scenario, failure takes place under the combined effects of
bending moment, shear force and possible involvement of axial force due to
boundary conditions. This article isolates and focuses on the problem of shear
failure. Parallel studies on flexural and delamination problems are currently under
scrutiny by other members of our research group at Coventry University. The
findings will be combined to formulate optimum design guidelines for a “Green”
concrete overlay.
When the load is located either side of an existing, old crack, high shear stress
becomes dominant and a relative vertical displacement is expected at crack edges,
which may lead to reflective cracking into the overlay under repetitive traffic
loads, as shown in Figure 1.
Shear Failure in Plain Concrete as Applied to Concrete Pavement Overlays
3
Figure 1. Reflective shear cracking under repetitive traffic loading (Left)
Figure 2. Correlation of ACI 318-02 with experimental data [2] (Right)
Depending on the nature of crack edge movement, it can be categorized into mode
I openning, mode II shearing/sliding and mode III tearing. Mode II corresponds to
the shearing problem but it usually coexists with mode I. The Paris’ law [3], as
shown below is usually deployed to describe the crack propagation under repetitive
loading.
(1)
where, Keq = equivalent stress intensity factor; A, n= fracture mechanics factors; c=
crack length; N = number of loading cycles; dc/dN = increase of crack length per
load cycle.
A fracture mechanics approach may be needed to highlight the crack initiation and
propagation process. The stress intensity factor, K, due to bending and shear is one
of the fundamental input parameters. Therefore, it was investigated in the
following experimental study, assisted by numerical modelling.
Design Codes and Standards on Shear
A selection of design codes and published formulae from previous researchers are
summarized in Table I. The following assumptions are made to derive
representative shear strengths using each code: A relatively high compressive
strength of fc’=fck=50MPa is assumed. The shear span-to-depth ratio
is employed based on the geometry of the single notch shear beam test as shown in
Figure 3. Since the steel ratio, ρ, is deemed necessary in some of the codes, to
execute the calculation and return a non-zero result, a minimal value of
is assumed. It is understood that errors may be introduced by the latter
and some empirical formulae may become invalid in the case of plain concrete.
Yi Xu and John N Karadelis
4
Design
Codes and
Published
Formulae
Shear Strength
(MPa)
Shear
strength
(MPa)
Comments
Eurocode 2
[4]
0.48
0.72 If the safety factor
is omitted.
ACI 318-02
[5]
1.13 for
, i.e. relatively
large shear span-to-depth
ratio
17 ≤ 0.29√
2.05 for
i.e. relatively
small shear span-to-depth
ratio
. 1.17 General
≤ √ 5.87 Deep beams ( ≤ )
A23.3-94 [6] . 1.414 No consideration for a/d
Zsutty
Eqn [7, 8]
1.057 a/d > 2.5 or a/d < 2.5 under
indirect load, as provided
by side flanges
3.204 1.5 < a/d < 2.5 with direct
loading (top load & bottom
supports), lower bound
strength predictor
Table I. Summary of Design Codes and Published Shear Design Formulae [4-8] 1) Not all standards/codes take a/d into account, commonly acknowledged as one of
the most influential parameters in evaluation of the shear strength. 2) steel ratio, , not
applicable in plain concrete. 3) Generally, ≤ 68.9 MPa in ACI 318-02 [5]. 4) A
wide scatter was presented in the correlation of ACI 318-02 with experimental data, as
shown in Figure 2.
Experimental, Pilot Study
Materials
Stage I. Three concrete mixes were tested in the preliminary experimental work.
They were Ordinary Portland Cement Concrete (OPC1) as control specimens, plain
Polymer Modified Cement Concrete (PMC1) and Polymer Modified Cement
Concrete with 4kg/m3 glass fibre (PMC2). Following previous studies [9, 10], the
Shear Failure in Plain Concrete as Applied to Concrete Pavement Overlays
5
PMC mix developed is of relatively high strength and high modulus of rapture and
suitable for roller compaction. A specially modified Kango hummer was used to
consolidate the specimens. 10mm granite was employed for coarse aggregate.
Stage II. In addition to the mixes in stage I, three more concrete mixes were
produced and tested in cylinder direct shear mode. All six mixes are summarized in
Table II. Gritstone replaced granite in OPC2, PMC3 and PMC4 as its aggregate
crushing value (ACV), tested according to BS 812-110:1990 [11], indicated that
the former has a higher resistance to crashing than the latter (11.40% and 19.98%).
Also, PMC4 was cast following a new mixing and curing method in accordance
with ASTM 1439 [12] (4-day moist curing at 23±2oC and relative humidity of
approx. 95%, followed by 24-days air curing at room temperature environment). A
new compaction device simulated the hammering and vibrating actions.
Coarse
Aggregate
Fibre
Used
Mixing
Method
Curing
Method
Compaction
Equipment
OPC1 Granite N/A Traditional Traditional Kango
OPC2 Gritstone N/A Traditional Traditional Kango
PMC1 Granite N/A Traditional Traditional Kango
PMC2 Granite Glass Traditional Traditional Kango
PMC3 Gritstone N/A Traditional Traditional Kango
PMC4 Gritstone N/A New New Vib. Comp/tor
Table II Summary of Concrete Mixes
Single Notch Shear Beam Test (SNSBT)
Figure 3. Specimen Geometry and Loading and Crack Trajectory
This paper adopts the concept of single edge notched beams employed by
Iosipescu [1] and Arrea and Ingraffea [13]. This single notch short beam shear test
created a concentrated shear zone in the (near) absence of bending moments at the
notch and evaluated the shear strength level of OPC1, PMC1 and PMC2. Twelve
Yi Xu and John N Karadelis
6
beams were tested comprising four beams per mix. The geometry and loading
arrangements are shown in Figure 3. All the beams failed abruptly with the crack
propagating from the tip of the notch in an inclined 45o direction, reaching the
surface of the specimen to the opposite side of the applied force P (Figure 3). The
results were summarized in Table III. Despite the high compressive strengths of
PMC, the latter failed earlier under shear than ordinary concrete. This is in
harmony with existing literature [14-16].
Figure 4 shows the variation of shear stress versus shear strain for a magnitude of
shear stress up to 2.5MPa, before failure occurs. Four beams were tested for each
mix. A wide range of scatter points (hatched areas) was present in the results. The
same scatter was reported in Figure 2. Both PMC1 and PMC2 mixes show steeper
slopes, i.e. higher shear modulus than the OPC1. Comparing plain PMC1 with
glass-fibre reinforced PMC2 it is observed that the shear stress develops faster in
PMC2. This indicates that the introduction of glass fibre did enhance the shear
resistance of PMC but not the ductility.
Overall, PMC has high compressive strength but lower shear strength, possibly due
to insufficient compaction. The addition of glass fibre enhanced the shear
properties of the PMC. A good consistency exists between the average saturated
densities and the shear strengths. In descending order, both rank as: OPC1 > PMC2
> PMC1, as listed in Table III. As compaction during PMC casting is critical,
insufficient compaction may induce voids (low density). When subject to shear,
these voids become weak points and eventually lead to failure at a “lower-than-
expected” load. However, in compression, the microstructures developed by
superior ingredients still allow for good performance.
Figure 4. Shear Stress/ Strain at the Initial Stage
For a single edge crack subject to in-plane shear, a relationship has been developed
by Tada [17] for KII, the stress intensity factor, as shown below.
Shear Failure in Plain Concrete as Applied to Concrete Pavement Overlays
7
(2)
Where: Q = applied shear at the notch at the onset of slow crack growth; a = crack
depth, 27mm in the testing geometry; b = height of the beam, 100mm; B = width
of the beam, 100mm.
Substituting the above values into Eqn. (2), the latter is reduced to:
in (3)
All beams failed abruptly. Owing to the rapid crack development, the load at the
onset of slow crack growth was not detected. If the failure loads were to be used in
the assessment, the average KII for OPC1, PMC1 and PMC2 would be 2435, 2136
and 2390 respectively. As failure occurs at a higher load than that
needed for initial crack growth, the actual K-values are likely to be smaller than
those calculated. Although the definitive estimates of KII are not available at the
current stage, the PMC returned with smaller toughness than the OPC. Further
investigation into the aggregate interlock and friction is underway. Additional tests
conducted to increase confidence are cylinder torsion tests and direct shear tests as
explained in the following paragraphs.
Cylinder Torsion Test
A total of eight concrete cylinders, four OPC1 and four plain PMC1 with 100mm
diameter and 200mm length were cast. Table III provides all necessary properties
and results. Studying failed specimens of OPC and PMC showed that the fractured
plane in PMC was smoother than that of OPC. Hence, the aggregate failed to
demonstrate good interlocking abilities.
Cylinder Direct Shear Test
The Iowa Testing Method 406-C [18] on four 150mm diameter by 300mm long
OPC1 cylinders and four PMC2 (glass fibre) cylinders was adopted. To enhance
the shear strength performance of PMC, the coarse aggregate as well as the mixing,
compacting and curing methods were revised in stage II. Gritstone replaced granite
in OPC2, PMC3 and PMC4. The new mixing, compaction and curing methods
were deployed for PMC4, as described earlier. The test arrangement is pictured in
Figure 5. All cylinders were sheared off in a vertical plane, as shown in Figure 6.
PMC2 (with glass fibre) delivered higher shear strength than plain PMC1, similar
to OPC1. The results were summarized in Figure 7. Unexpectedly, they failed to
demonstrate a clear enhancement in shear strength, beside the use of gritstone. It is
likely that the water absorption value for gritstone was used in the granite mix
(PMC1), by mistake. As the water absorption of granite is higher than that of
gritstone, the w/c ratio of PMC1 was found to be 0.33, while all other PMC mixes
Yi Xu and John N Karadelis
8
revealed 0.37. Had the correct value been used, PMC1 should have a lower shear
strength than the current value, or even lower than that of PMC3 and PMC4. An
investigation is currently under way. Nevertheless, the new mixing /compaction
/curing methods did exhibit a great improvement to the strength and density,
proving that effective compaction is essential in strength enhancement. This good
practice shall be continued in the next phase of experiments.
Summary
The results in all three tests are summarized in the same Table III. Results
involving gritstone and the new mixing/compaction/curing methods have been
discussed in the previous chapter and therefore are not repeated herein.
Figure 5. Cylinder Dir Shear Test Figure 6. Failed Section (PMC2)
It is noted that the tests carried out have excellent consistency on the evaluation of
shear performance. Despite high compressive strength, plain PMC failed to
provide an equivalent shear resistance as the OPC. This is attributed to the high
strength hydrated cement paste (HCP) in PMC and the relatively weak coarse
aggregate, which led to less efficient interlock at the failure planes. The OPC
failure face exposes a great amount of aggregates and most of the failure takes
place at the HCP-aggregate interface. In contrast, the PMC shows a much
smoother face through crushed aggregates. Hence, the replacement of granite with
gritstone.
Figure 7. Summary of Results
5.26 5.55 4.59 5.28 4.26 4.53
38
64 62 54.5
67 74.5
0
10
20
30
40
50
60
70
80
0
1
2
3
4
5
6
OPC1 OPC2 PMC1 PMC2 PMC3 PMC4
Co
mp
ress
ive
Str
ength
(MP
a)
Shea
r S
tren
gth
(M
Pa)
Concrete Mixes Shear Strength (Mpa) Compressive Strength (Mpa)
Shear Failure in Plain Concrete as Applied to Concrete Pavement Overlays
9
Compaction was also blamed for the “lower than expected” shear resistance of
PMC. Different from high/normal-workability concrete, potent compaction in
PMC is essential to attain the desired strength. After examining the cube densities,
it was deduced that there were voids in the mix due to insufficient compaction.
Hence, the investment in the new vibrating-compactor.
Mat.
Prop.
Compr.
Stren. (MPa)
Density
(kg/m3)
Mean Shear Strength (MPa)
Estimated Mean
Shear Modulus
G (GPa)
Tests
Cube Compre.
Test SNSBT Torsion
Direct
Shear SNSBT
Tors
ion
OPC1 38.0 2361.1 3.59 3.59 5.26 15.5 15.9
PMC1 60.5 2298.7 2.90 2.79 - 24.7 17.2
PMC2 54.5 2323.6 3.52 - 5.28 26.2 -
Table III. Summary of Test Results
PMC2 with a glass fibre input did improve the shear properties of plain PMC to a
similar level of OPC, but failed to provide the required ductility. Hence, glass
fibres were replaced with steel fibres and later with synthetic fibres. A “cock-tail”
of reinforcement has been introduced in the mix to enhance the shear performance
and to provide the required resistance to reflective cracking. This is currently under
investigation.
A quick comparison of Table III with Table I reveals that all experimentally
obtained shear strengths are much higher than most of the values obtained by the
codes. The following reasoning is stated:
All tests had very small shear span-to-depth (a/d) ratio. The a/d ratio was
0.067 and 0.46 respectively in cylinder direct shear test and SNSBT. It is
generally agreed that the influence of a/d is not insignificant [5]. A low a/d
implies small bending moment, in which case, most of the cross section is
available to resist shear. Hence, a high shear property is expected. Also, a low
a/d ratio corresponds to a strong “strut” (arch) action. Hence, the high shear
resistance could be attributed to the high compressive strength in concrete.
It is noted that in some of the formulae in the codes, the shear strength, , is
derived from . The correlation between
and is summarized from
diagonal – tension failure, a form of indirect shear failure, whereas the tests
conducted were direct shear. Additionally, even in the case of diagonal
tension, a wide scatter is usually present in experimental investigations as
shown in Figure 2. Therefore, in this case, the real concrete shear capacity is
under-estimated by the empirical formulae.
Yi Xu and John N Karadelis
10
Finite Element (FE) Analysis
A 2D FE-model corresponding to the single notch shear beam test was setup using
ANSYS software [19] to study the stress distribution and the associated
parameters. The material properties obtained in the experiment (Table III) were
used in the model. The 6-node triangular PLANE183 element, with two degrees of
freedom (DOF) per node, supporting plasticity, large deflection and strain
behaviour was used. This is defined by a quadratic shape function, considered to be
well suited to model irregular meshes occurring at crack regions. All usual output
is supported by the analysis, plus the displacement extrapolation method in
calculating stress intensity factors. A “singularity” point was created at the crack
tip with skewed nodes at quarter positions. The failure loads from the experimental
tests were introduced. A non-linear, large displacement analysis was performed,
converging after a few iterations. It is stressed here that this is a preliminary model
designed to help with experimentation rather than the other way round.
Figure 8 portrays the high stress concentration at the crack tip. The maximum
shear strengths and the mode II stress intensity factor derived at the crack tip are
listed in Table IV with the corresponding experimental results for comparison. It
was found that shear stress at the crack tip is nearly twice the average shear
strength of the reduced cross section above the crack in OPC1 (6.63 corresponding
to 3.59). The predicted KII results are lower than the measured values calculated
using Tada’s formula [17] in OPC1 (1216 compared to 2435). Swartz conducted a
similar single notch shear test configuration both experimentally and numerically
on concrete beams [20], noticing a similar discrepancy between KII values. This
leads to suggestions that Tada’s formula may need modification to reflect the real
geometry and loading conditions. Note that to calculate K using FEM, the crack
width has to be zero. However, a 2mm width crack was created in the test beams.
This should be allowed for. A 3D model is currently under development.
Predicted
Shear Stress
at Crack Tip
(MPa)
Measured
Average Shear
Strength
(MPa)
Predicted
KII
@ Crack Tip
(
Measured
KII
@ Crack Tip
( OPC1 6.63 3.59 1216 2435
PMC1 5.82 2.90 1047 2136
PMC2 6.51 3.52 1172 2390
Table IV. Numerical Modelling Results
Figure 8. SNSBT Model Shear Stress, Sxy - Plot
Shear Failure in Plain Concrete as Applied to Concrete Pavement Overlays
11
Conclusions
All specimens failed abruptly in a typical shear failure and brittle material manner.
The introduction of glass fibre did not provide acceptable results. Other forms of
reinforcement are currently under scrutiny. Steel fibres seemed to be a successful
alternative to conventional shear reinforcement.
On the basis of the laboratory results, it was found that considerably higher shear
strengths were achieved than those specified in the standards. This is attributed to
the nature of the tests with relatively low a/d ratio. For reasons explained earlier, it
is considered inappropriate to apply the indirect and empirical shear design
procedure on direct shear tests involving minimal bending, especially in the case of
plain concrete.
The high strength concrete developed slightly lower shear strength than the normal
concrete and this is attributed to the relatively less effective aggregate interlock in
high shear regions and possibly insufficient compaction. A replacement coarse
aggregate was introduced contributing to the shear capacity but requires further
confirmation. The new mixing, compaction and curing method was also tested and
proved to be effective in increasing the shear strength. This successful practice
shall be continued and developed further to achieve better results. This is an on-
going research programme funded by an EPSRC grant. The final results should be
published next year.
Acknowledgements
The financial support of the Engineering and Physical Science Research Council
(EPSRC), UK and Aggregate Industries (AI) is gratefully acknowledged. The
authors would like to express their gratitude to Dr. Salah Zoorob and all the
colleagues and technical staff at Coventry University for their valuable suggestions
and comments. Special mention should also be made to Tarmac, Everbuild
Products, AGS Mineraux and Power Minerals for providing the research materials.
References
[1] Iosipescu, N. (1967), J. Mater., vol.2, n. 3, p. 537-566.
[2] Leet, K. M. and Bernal, D. (1997), Reinforced Concrete Design: Conforms to
1995 ACI Codes, McGraw-Hill, New York.
[3] Paris, P. C. and Erdogan, F. A. (1963), J. Basic Eng., vol. 85, n. 4, p. 528-534.
Yi Xu and John N Karadelis
12
[4] Beeby, A. W. and Narayanan, R. S. (1995), Designers' Handbook to
Eurocode 2 Part 1.1, Design of Concrete Structures, Telford, London.
[5] ACI Committee 318. (2002), Building Code Requirements for Structural
Concrete (ACI 318-02) and Commentary (ACI 318R-02). American Concrete
Institute, USA.
[6] CSA Technical Committee on Reinforced Concrete Design. (1994), Design
of Concrete Structures A23.3-94, Canadian Standards Association, Canada.
[7] Zsutty, T. C. (1968), ACI Struct. J., vol. 65, n. 11, p. 943-951.
[8] Zsutty, T. C. (1971), ACI J. Proceedings, vol. 68, n. 2, p.138-143.
[9] Karadelis, J. N. and Koutselas, K. (2003), In: Proceeding of 10th
International Conference, Structural Faults and Repair., Engineering Technical
Press, Edinburgh.
[10] Koutselas, K. (2010), Sustainable 'Green' Overlays for Strengthening and
Rehabilitation of Concrete Pavements, PhD Thesis, Coventry University, Coventry,
(unpublished).
[11] British Standard. (1990), BS 812-110:1990 Testing Aggregates - Part 110:
Methods for Determination of Aggregate Crushing Value (ACV), BSI, UK.
[12] ASTM. (1999), ASTM Designation: C1439-99 Standard Test Methods for
Polymer-Modified Mortar and Concrete, ASTM International, West
Conshohocken.
[13] Arrea, M. and Ingraffea, A. R. (1982), Mixed-mode Crack Propagation in
Mortar and Concrete, Cornel University, New York.
[14] Song, J., Kang, W., Kim, K. S. and Jung, S. (2010), Struct. Eng. Mech., vol.
34, n. 1, p. 15-38.
[15] Taylor, H. P. J. (1974), ACI J., vol. SP42, p. 43-78.
[16] Walraven, J. C. (1981), J. Struct. Division, vol. 107, p. 2245-2270.
[17] Tada, H., Paris, P. C. and Irwin, G. R. (2000), The Stress Analysis of Cracks
Handbook. The American Society of Mechanical Engineers, New York.
[18] Iowa Department of Transportation. (2000), Method of Test for Determining
the Shearing Strength of Bonded Concrete, Iowa Department of Transportation,
Iowa.
[19] ANSYS. (2009), ANSYS 12, SAS IP, Inc, Canonsburg, PA, USA
[20] Swartz, S. E., Lu, L. W., Tang, L. D. and Refai, T. M. E. (1988), Exp. Mech.,
vol. 28, n. 2, p. 146-153.