12
General Application [email protected] Differential Pressure Control Valves

Differential Pressure Control Valves

Embed Size (px)

Citation preview

General Application

[email protected]

Differential Pressure Control

Valves

KNOWLEDGE ● QUALITY ● INNOVATION ● MANUFACTURING EXCELLENCE ● CUSTOMER FOCUS www.frese.eu 2

Types of Differential Pressure Control Valve

Pilot Operated DPCV Direct Acting DPCV

KNOWLEDGE ● QUALITY ● INNOVATION ● MANUFACTURING EXCELLENCE ● CUSTOMER FOCUS www.frese.eu 3

Typical Direct Acting Differential Pressure Control Valve

Flanged Angle Pattern Threaded Oblique Pattern

1) Adjustment Nut

2) Spring Cover

3) Test Plugs

4) Housing

5) Piston

6) Capillary Tube Connection

7) Adjustment Spring

KNOWLEDGE ● QUALITY ● INNOVATION ● MANUFACTURING EXCELLENCE ● CUSTOMER FOCUS www.frese.eu 4

DPCV Pressure Diagram 4

KNOWLEDGE ● QUALITY ● INNOVATION ● MANUFACTURING EXCELLENCE ● CUSTOMER FOCUS www.frese.eu 5

DPCV Application Static Balancing Solution

KNOWLEDGE ● QUALITY ● INNOVATION ● MANUFACTURING EXCELLENCE ● CUSTOMER FOCUS www.frese.eu 6

DPCV Application Dynamic Balancing Solution

KNOWLEDGE ● QUALITY ● INNOVATION ● MANUFACTURING EXCELLENCE ● CUSTOMER FOCUS www.frese.eu 7

DPCV Typical Partner Valve Arrangements

Double Regulating Valve

(FODRV) Flow Limiting Valve (CFR)

KNOWLEDGE ● QUALITY ● INNOVATION ● MANUFACTURING EXCELLENCE ● CUSTOMER FOCUS www.frese.eu 8

DPCV Commissioning

12

kPa

14

kPa

KNOWLEDGE ● QUALITY ● INNOVATION ● MANUFACTURING EXCELLENCE ● CUSTOMER FOCUS www.frese.eu 9

DPCV P-Band

12

kPa

14

kPa

11 kPa

0.014 l/s 0.111 l/s 0.167 l/s

3 k

Pa

P-

Ba

nd

KNOWLEDGE ● QUALITY ● INNOVATION ● MANUFACTURING EXCELLENCE ● CUSTOMER FOCUS www.frese.eu 10

DPCV Hysteresis

0

10

20

30

40

50

60

70

80

90

100

0 100 200 300 400 500 600 700

Pressure [kPa]

Flow [lph]

KNOWLEDGE ● QUALITY ● INNOVATION ● MANUFACTURING EXCELLENCE ● CUSTOMER FOCUS www.frese.eu 11

DPCV Pump Sizing Calculation

Pump pressure (ΔPP) = Differential pressure in system (ΔPS) + Pressure loss across

valve (ΔPV )

• Desired differential pressure in system = 30 kPa

• Desired flow in system = 10 m3/h

• Selected DPCV Kvs = 29 m3/h (DN50)

→ Required pump pressure (ΔPP) = 30 + ((10/29)2 * 100) = 30 kPa + 11.9 kPa = 41.9 kPa

General Application

[email protected]

Differential Pressure Control

Valves