The materials included in this compilation are for the use of Dwyer Instruments, Inc. potential customers and current employees as a resource only. They may not be reproduced, published, or transmitted electronically for commercial purposes. Furthermore, the Company's name, likeness, product names, and logos, included within these compilations may not be used without specific, written prior permission from Dwyer Instruments, Inc. ©Copyright 2011 Dwyer Instruments, Inc.
Citation preview
Series GSTA
Carbon Monoxide /
Nitrogen Dioxide
Transmitter
The materials included in this compilation are for the use of Dwyer Instruments, Inc. potential customers and current employees as a resource only. They may not be reproduced, published, or transmitted electronically for commercial purposes. Furthermore, the Company’s name, likeness, product names, and logos, included
within these compilations may not be used without specific, written prior permission from Dwyer Instruments, Inc. ©Copyright 2011 Dwyer Instruments, Inc
Key Specifications
Surface Mount Configuration
Range 0 to 200 PPM / 500 PPM CO (Field Selectable) and 0 to 10 PPM NO2
Accuracy: 2% F.S. for CO; 3% F.S. for NO2 at Time of Calibration
Universal Output: Field Selectable 0 to 5 VDC / 0 to 10 VDC / 4 to 20 mA
Dip Switch Selection for Inverted Outputs and Zero Suppression
Key Specifications
Sensor Type: Industrial Grade
Electrochemical Sensor
Sensor Life 3 to 5 Years with Recommended
Calibration Check Every 6 Months
Field Replaceable
Remote LCD Display
Useful for Calibration
Sensor Technology
Gas Enters Sensor Through Capillary and Passes Through
Filter
Gas Goes Through Electrochemical Reaction Upon Contact
with Electrode (i.e. CO + H2O => CO2 + 2H+ + 2e-)
CO2 Released Diffuses into the Air, Hydrogen Ions Migrate
to the Electrolyte, and the Electrons Generate the Charge
on the Working Electrode
Sensor Technology
Secondary Oxidation Reaction Occurs (i.e. O2 + 4H+ + 4e-
=> 2H2O) at the Counter Electrode
Thus, Water Used to Create Electrons At One Electrode
and Electrons Used to Recreate Water At Other Electrode
When Two Electrodes are Connected, Small Current is
Generated Proportional To The Gas Concentration
Third Electrode Used is a Electrical Reference and is
located in the Electrolyte
Features and Benefits
Industrial Grade Electrochemical Sensor
Longer Sensor Life Leads to Less Frequent
Sensor Replacements
Higher Accuracy at Lower Concentrations
Allow Sensors to Require less Frequent
Calibrations
Field Replaceable Sensors
Transmitters Are Replaced Less Frequently
Features &
Benefits Remote LCD Display
Building Occupants Do Not See Readings
That They Do Not Understand
Lowers Transmitter Cost To Customer By
Having One Display for Multiple
Transmitters
Allows Customer To Know When Sensor
Reaches End of Life By Displaying “Bad
Sen”
Features and Benefits
Dip Switch Selectable Range
Reduces Inventory By Only Needing One
Model for 0 to 200 PPM or 0 to 500 PPM CO
Universal Outputs
Reduces Inventory by Only Needing One
Model for 0 to 5 VDC, 0 to 10 VDC, 4 to 20
mA
Works With Majority of Building
Management Controllers
Features and Benefits
Removable Terminal Blocks
Reduces Installation Time and Cost
Multiple Knockouts on Housing
Reduces Installation Cost By Allowing
Installer to Run Wire or Conduit to Nearest
Side of Housing
GSTA Future Product
Additions GSTB Communicating Transmitter with
BACNet and Modbus
GSTC Master Controller
Accepts Multiple GSTB inputs
Audible and Visual Alarms
Two Relay Outputs
Communications
Data Logging Capability
GSTA Applications
Underground Parking Garages
Monitor the Exhaust Gases From Automobiles
Signal To Building Management System to Operate Exhaust Fans and High Gas Level Warning Alarms
465 to 700 Square Meter Coverage Area
GSTA Applications
Loading Docks
Monitor the Gas Levels from Fork Lifts and
Trucks
GSTA Applications
Automobile Service
Bays or New Car
Dealerships
Monitor the Carbon
Monoxide from
Automobile Exhaust
Signal To Building
Management System
to Operate Exhaust
Fans and High Gas
Level Warning
Alarms
GSTA Applications
Boiler or Mechanical
Rooms
Monitor the
Combustion Gases
from Gas Fired
Boilers