View
214
Download
0
Category
Preview:
Citation preview
• Temperature Control UnitsWater & Oil30° - 500°F
• Portable ChillersAir & Water-Cooled20° - 70°F
• Central ChillersAir & Water-CooledPackages & Modules20° - 70°F
• Pump Tank StationsChilled or Tower Water200 - 3600 gallons
• Cooling Tower Cells45 - 540 tons
• Filters
• Heat Exchangers
WARRANTIES• Models with LE & HE
Control Instruments:2 Years : Entire machine.4 Years : AVTTM valve, controlinstrument and heater.
• Models with VE Control Instrument:2 Years : entire machine.4 Years : control instrument.
Nozzles, Barrels & Tools Heat Exchangers Troughs & Tanks Rolls Radiatorsand Air Coils
Jacketed Vesselsand Mixers
Lasers
Web: www.AdvantageEngineering.com
Phone: 317-887-0729
Molds & Dies
SENTRA® C SERIESWATER UNITS WITH SEAL-LESS
CENTRIFUGAL PUMP DESIGN
ImpellerSleeveBearing
SleeveBearing
SealedStator
SealedRotor
Cooling &lubricatingwater flow
path
MotorShaft
Volute From ProcessFlow
To ProcessFlow
Offered exclusively from Advantage, the C Series Sentratemperature control unit features a seal-less hermeticallysealed motor pump. The pump uses a small portion of thecirculated fluid to cool the motor and lubricate the motor’sdurable carbon graphite sleeve bearings. The rotor and statorare sealed in stainless steel enclosures for long life providingquiet and balanced operation. This design eliminates theneed for a pump seal used in traditional centrifugal pumps toisolate the circulated fluid from the motor.
No Pump Seals• No pump seal leaks• Never change a pump seal again
1.6 HP Centrifugal Pump• High flow rates• 10-60 GPM flow rates
10 to 16 KW Heaters• Low watt density immersion style
VE, LE or HE Control Instrument• Ultimate control flexibility
Hermetically Sealed Motor• Long service life• High temperature potting material• Liquid cooled• Liquid lubricated carbon graphite sleeve
bearings• Quiet operation• No fans • Vibration free
APPLICATIONS Sentra® Series temperature control units can be used on a variety of process applications that require 30°F to 250°F process water.
Cutaway of hermetically sealed motor pumpEnd view of hermetically sealed motor pump assembly
ADVANTAGE ENGINEERING, INC. 525 East Stop 18 Road Greenwood, IN 46142 phone: 317-887-0729 fax: 317-881-1277web site: www.AdvantageEngineering.com email: sales@AdvantageEngineering.com ©2009 ADVANTAGE ENGINEERING, INC. Form #ADV-660 1/09
SINCE PRODUCT INNOVATION AND IMPROVEMENT IS OUR CONSTANT GOAL, ALL FEATURES AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR LIABILITY.
ADVANTAGE PRODUCTS: TEMPERATURE CONTROLLERS • PORTABLE CHILLERS • CENTRAL CHILLERS • PUMP TANK STATIONS • TOWER SYSTEMS • FILTERS
Phone: 317-887-0729 Web: www.AdvantageEngineering.com
STANDARD FEATURES
CONTROL INSTRUMENTS
SPECIFICATIONS
PUMP CURVE
VISUAL COMPARISON Standard Pump vs. Seal-less Pump
Standard Sentra® pump withmechanical seal, seal flush
and bronze impeller.
Sentra® C seal-less pumpwith bronze impeller.
Model Designator for Sentra® C SeriesTemperature Control Units
S K - 1 0 6 0 - H E - C
Sentra® SeriesHeater KWNominal Flow
Rate GPM
Instrument• HE: HE Series• LE: LE Series• VE: VE Series
Pump• C : Heavy duty Hermetically Sealed Seal-less Motor Pump
A
B
C
D
E
F
G
H
I
J
K
L
M
A
B
C
D
E
F
G
H
I
J
K
M
A B C D A E
L
KW
HP
GPM
PSI
230 volt
460 volt
Height
Width
Depth
T/F3
S/D4
Shipping5
SK-
Heater1
Process Pump
Full Load Amperage
@3ø/60hz2
Dimensions (inches)
Connections (inches)
Weight (pounds)
1060
10
1.6
35
30
31.0
15.5
281/4
121/2
191/2
11/4
1/2
195
1660
16
1.6
35
30
45.5
23.0
281/4
121/2
191/2
11/4
1/2
195
Notes: 1. Derate heater output by 25% for 208/3/60 operation. 2. Consult factory for 50hz operations. 3. T - to process; F - from process. 4. S - water supply; D - drain. 5. Approximate unit shipping weight.
Control Instrument (not visible in photo)
Drain Connection
Cooling Valve (AVT valve shown in photo)
Pressure relief valve
Flow Meter (available on ‘HE’ Series models)
Hermetically sealed Pump Motor
Vented Stainless Steel Cabinet
Caster
Pressure Gauges
Heater
To Process Connection
From Process Connection
Water Supply Connection
A
B
C
Impeller
Mechanical Seal Components
Seal Flush
D
E
Standard Motor
Hermetically Sealed Motor
4
9
13
17
22
263035
39
4348
52
10 20 30 40 50 60 70 80 900
FLOW - GPM
SK PUMP ‘C’ PERFORMANCE
1.6 hp
PR
ES
SU
RE
- P
SI
‘HE’ Series ‘LE’ Series ‘VE’ Series
A fit for everyone’s unique needs... for every application. From basic temperature controland monitoring to advanced machine diagnostics and primary machine interface,Sentra® temperature control units include accurate and user-friendly control instruments.
Recommended