Type Y693 Gas Blanketing Regulator
IntroductionAn Accu-Pressure™ Gas Blanketing Regulator reduces a high pressure gas, such as nitrogen, to maintain a protective environment above any liquid stored in a vessel or tank when the liquid is being pumped out. Also when the vessel is suddenly cooled, causing vapors inside the vessel to contract, the regulator system replaces the volume of contracting vapors with a volume of blanketing gas to prevent the internal vessel pressure from decreasing. In both cases a slight positive vessel pressure prevents outside air, moisture and other contaminants from entering the vessel and the possible collapse of the vessel walls.
The Type Y693 (Figure 1) is a direct-operated regulator used for accurate pressure control on low pressure blanketing systems. Downstream pressure is sensed through an external control line in the lower casing of the regulator. The Type Y693 is available in NPS 1-1/2 and 2 / DN 40 and 50 body sizes.
Features• Ease of Inspection and Maintenance—The union
nut and/or hex head bolt connection between the body and actuator permits access to the disk and
orificebyonlyremovingthediaphragmcasingassembly without removing the body from the pipeline (see Figure 2).
• Accuracy of Control—Balanced trim and large diaphragm area reduces hysteresis to as little as +/- 0.50 in. w.c. / 1 mbar deviation from setpoint.
• Inlet Pressure Sensitivity—Less than 0.25 in. w.c. / 0.6 mbar setpoint shift over the entire inlet pressure range.
• Speed of Response—A change in vessel pressure registers directly under the diaphragm resulting in the fastest possible speed of response.
• Variety of Materials—Regulator body, trim and valve disk are available in various material combinationsforprocessfluidcompatibility.
• Outlet Pressure Stability—4 to 1 lever ratio reduces regulatorsensitivitytoinletpressurefluctuation.
• Tight Shutoff Capability—Aflat-faceddiskof Nitrile (NBR), Fluorocarbon (FKM) or Polytetrafluoroethylene(PTFE)providesexcellentshutoff capability.
Figure 1. Type Y693 Gas Blanketing Regulator
W6200
Bulletin 74.1:Y693
2
1.EndconnectionsforotherthanU.S.standardscanusuallybeprovided;consultyourlocalSalesoffice.2.Fabricatedbyusingslip-onflangesandsocketweldingnipplesintobody.3. The pressure/temperature limits in this Bulletin and any applicable standard limitation should not be exceeded.
SpecificationsThissectionliststhespecificationsfortheTypeY693gasblanketingregulators.Factoryspecificationarestampedon the nameplate fastened on the regulator at the factory.
Table 1. Outlet (Control) Pressure Ranges
OuTlET PRESSuRE RAnGES(1)COlORCOdE
COnTROl SPRInGWIRE dIAMETER
COnTROl SPRInG FREE lEnGTH PART
nuMBERIn. w.c. mbar In. mm In. mm
Light diaphragm plate
0.5 to 2.02 to 55 to 88 to 1818 to 32
1.2 to 5 5 to 12 12 to 20 20 to 45 45 to 80
BrownRed
BlackWhite StripeGreen
0.1090.1200.1300.1560.182
2.773.053.303.964.62
6.127.5317.887.507.25
155191200190184
1D8925270221D8926270221D8927270121D8932270321D893327032
Heavy diaphragm plate1 to 2 psig
1.5 to 3.3 psig2 to 5 psig
0.07 to 0.14 bar0.10 to 0.23 bar0.14 to 0.34 bar
BlueOrangeYellow
0.2250.2500.283
5.726.357.19
7.0936.916.50
176180165
1H9758270321H9759270321P615427142
Heavy diaphragm plate with brass closing cap and heavy duty spring adjustor
2 to 5.5 psig4 to 10 psig
0.14 to 0.38 bar0.28 to 0.69 bar
Green StripeRed
0.3630.406
9.2210.3
6.006.00
152152
0Y0664270221H8024000A2
1. Outlet pressure ranges are for installations with the spring barrel positioned in any direction. After installation always check/adjust the pressure setting.
Available ConfigurationsDirect-operated pressure reducing regulator with external registration requiring a downstream control line. Ten outlet pressure ranges from 0.5 in. w.c. to 10 psig / 1 mbar to 0.69 bar. Available in NPS 1-1/2 and 2 / DN 40 and 50 body sizes.
End Connections(1)
NPT(1) (standard)Flanged(2) (Optional)ENClassPN16,25and40RFFlanged(Optional)
Maximum Inlet Pressure(3)
150 psig / 10.3 bar
Maximum Outlet Pressure(3)
10 psig / 0.69 bar
Maximum Outlet Pressure (Casing)(3)
15 psig / 1.0 bar
Maximum Operating Outlet Pressure to Avoid Internal Part damage(3)
2 psig / 0.14 bar above outlet pressure setting
Outlet Pressure Ranges(3)
See Table 1
Construction MaterialsSee Table 2
Common Services and Materials CompatibilitySee Table 3
Material Temperature Capabilities(3)
nitrile (nBR):-20to180°F/-29to82°CFluorocarbon (FKM):40to300°F/4to149°CPTFE:0to300°F/-18to149°C
Orifice Diameter1/2 in. / 13 mm
Flow CapacitiesSee Table 6
Coefficients For Relief Valve SizingCg with fully open valve plug: 185C1: 33
Spring Case Connection3/4 NPT female connection
Approximate WeightsCast iron with Aluminum: 22 lbs / 10 kgWCC Steel or CF8M Stainless steel: 57 lbs / 26 kgWCC Steel with Aluminum: 35 lbs / 16 kg
Bulletin 74.1:Y693
3
Figure 2. Type Y693 Regulator Construction Features
AluMInuM lOWER CASInG VERSIOn
STEEl OR STAInlESS STEEl lOWER CASInG VERSIOn
W6240-1
VEnT
lOWERCASInG
ClOSInG CAP
AdjuSTInG SCREW
COnTROl SPRInG
SPRInG CASE
dIAPHRAGM
ORIFICE
SOFT dISK
W6239-1
VEnT
lOWERCASInG
ClOSInG CAP
AdjuSTInG SCREW
COnTROl SPRInG
SPRInG CASE
dIAPHRAGM
ORIFICE
SOFT dISK
Bulletin 74.1:Y693
4
Principle of OperationThe Type Y693 Gas Blanketing Regulator reduces a higher-pressure gas to maintain a positive low pressure of blanket gas over a stored liquid (see Figure 3). Also when the vessel (or tank) is suddenly cooled, causing vapors to contract, the regulator replaces the volume of contracting vapors with a volume of blanketing gas to prevent the internal vessel pressure from decreasing. In both cases, a positive vessel pressure prevents outside air from entering the vessel and reduces the possibility of atmospheric pressure collapsing the vessel.
Gas blanketing regulators respond to a slight decrease in internal vessel pressure (caused by pump out or atmospheric cooling) by throttling open to increase theflowrateofgasintothevessel.Whenthevessel’sliquid level has been lowered to the desired point and the vapor pressure reestablished, the regulator throttles closed.
When the liquid level drops and vessel pressure decreases below the setting of the control spring, the spring force on the diaphragm opens the disk assemblytosupplytherequiredflowofgastothevessel.Whenvesselpressurehasbeensatisfied,outlet pressure tends to increase slightly, acting on the diaphragm. When the outlet pressure exceeds the control spring setting, the diaphragm moves to close the disk assembly.
Sizing Blanketing SystemsWhen sizing a gas blanketing regulator system for a low-pressure application, you must consider the replacement of blanketing gas required for the liquid loss during pump out of the vessel plus the condensation/contraction of vessel vapors during atmospheric thermal cooling.
UsingtheestablishedproceduresfromAmericanPetroleum Institute Standard 2000 (API 2000), determinetheflowrateofblanketinggasrequired.
1. Determinethegasflowraterequiredtoreplacetheliquid being pumped out (see Table 4).
2. Determinethegasflowratedueto‘‘inbreathing’’caused by atmospheric thermal cooling (see Table 5).
3. Add the requirements of 1 and 2 and select regulator size, based on total capacity required from Table 6.
Figure 3. Typical Type Y693 Installation (Steel or Stainless steel lower casing version)
BlOCK VAlVE
BlOCK VAlVE
BlOCK VAlVE
VEnT VAlVE
VEnT VAlVE
VEnT VAlVE
TYPE Y693
COnTROl lInE
GAS BlAnKETInG PRESSuRE
VESSEl / TAnK
Sample sizing problem for blanketing applications:
VesselCapacity . . . . . . . . . . . 210,000 gal. / 795 000 L PumpIn/OutCapacity . . . . . . . . . 80 gal/min. / 303 L/m Inlet (header) Pressure . . . . . .40 psig / 2.8 bar Nitrogen Desired Blanket Setpoint. . . . . . . . 0.5 in. w.c. / 1 mbar
1. MultiplytheflowrateconversionfactorfromTable4bythepumpratetoobtaintheairflowrequiredtoreplace the volume of liquid pumped out.
8.021x80GPM=642SCFH
2. Determinetheairflowrequiredforthermalcoolingfrom Table 5.
210,000 gal. tank size requires 5000SCFH/134Nm3/h air
Totalrequiredflow:642+5000= 5642SCFH/151Nm3/h air
3. Convertairflowtonitrogenflowbymultiplyingtheairflowbythesquarerootof1dividedbythespecificgravityofnitrogen.
5642x1/1.97=5729SCFH/154Nm3/h nitrogen
A6342
Bulletin 74.1:Y693
5
Table 2. Type Y693 Regulator Construction Materials
PART nAMEMATERIAl
Aluminum lower Casing Version Steel or Stainless Steel lower Casing Version
Body Castiron WCBsteelorStainlesssteel
Body Gasket Composition Composition
UnionNut - - - - Steel or Stainless steel
Spring case Aluminum Aluminum,WCBsteelorStainlesssteel
Lower casing Aluminum WCBsteelorStainlesssteel
Orificeandbiasspring Stainless steel Stainless steel
Pusher post and stem Aluminum Stainless steel
Lever assembly Steel Stainless steel
Diaphragm Nitrile (NBR) or Fluorocarbon (FKM) Nitrile (NBR) or Fluorocarbon (FKM)
Controlspring,springseatandsplitring Plated steel Plated steel
Diaphragm plate Aluminum and Steel Aluminum and Steel
Disk and O-rings Nitrile (NBR) and Stainless steel, Fluorocarbon (FKM) andStainlesssteel,PTFEandStainlesssteel
Nitrile (NBR) and Stainless steel or Fluorocarbon (FKM) andStainlesssteelorPTFEandStainlesssteel
4. From Table 6, at 0.5 in. w.c. / 1 mbar set pressure and40psiginletpressure,aTypeY693willflow8880SCFH/238Nm3/hnitrogen.Thissatisfiesthe5729SCFH/154Nm3/h requirements.
Capacity InformationTable 6 gives typical nitrogen regulating capacities at selected inlet pressures and outlet pressure settings. Flows are in SCFH (60°F and 14.7 psia) of 0.97 specificgravitynitrogen.Forgasesofotherspecificgravities, multiply the given capacity of nitrogen by 0.985, and divide by the square root of the appropriate specificgravityofthegasrequired.Then,ifcapacityisdesiredinnormalcubicmetersperhoursat0°Cand1.01325 bar, multiplySCFHby 0.0268.
Todeterminewide-openflowcapacitiesforreliefsizing,usethefollowingformula:
Q =520GT
3417C1
PP1
CgP1SIN DEG
where,Cg = gassizingcoefficientfromSpecificationstableC1 =Cg/Cvor33fromtheSpecificationstableG = gasspecificgravity(air=1.0)
P1abs= inlet pressure, psia (add 14.7 psi to gauge inlet pressure to obtain absolute inlet pressure)
Q = flowrate,SCFHT = absolute temperature in °R of gas at inlet (°F + 460)
InstallationThe regulator may be installed in any position as longastheflowthroughthebodyisinthedirectionindicatedbytheflowarrowattachedtothebody.Installthe regulator as close as possible to the blanketed vessel using a straight run of pipe the same size or larger as the regulator body. Position the body and/or diaphragm spring case so it will not collect moisture or debris into the screened vent and also be self draining (as shown in Figure 3). If a block valve is required, installafullflowvalvebetweentheregulatorandtheblanketed vessel.
Attach a downstream pressure control line to the female connection in the lower spring case. The female pressure connection is a 1/2 NPT in the steel or Stainless steel lower spring case and a 3/4 NPT forthealuminumlowerspringcase.Connecttheother end of the control line to the vessel. To allow for self-drainage, install the control line at an angle so that any liquid material will drain away from the regulator. See Figure 4 for the location of the external control line connection.Externaldimensionsandconnectionsareshown in Figure 4.
Bulletin 74.1:Y693
6
Table 3. Materials Compatibility
CORROSIOn InFORMATIOn
FluidMaterial
FluidMaterial
Carbon Steel
Cast Iron
316 Stainless Steel
Carbon Steel
Cast Iron
316 Stainless Steel
Acetic Acid, Air FreeAcetic Acid VaporsAcetoneAcetyleneAlcohols
CCAAA
CCAAA
BAAAA
Hydrochloric Acid (Air Free)HydrogenHydrogen PeroxideHydrogenSulfide,LiquidMagnesium Hydroxide
CA
I.L.CA
CAACA
CAAAA
Aluminum SulfateAmmoniaAmmoniumChlorideAmmonium NitrateAmmonium Sulfate
CACAC
CACCC
AABAA
MethanolMethylEthylKetoneNatural GasNitric AcidPetroleumOils,Refined
AAACA
AAACA
AAABA
AmmoniumSulfiteBeerBenzene (Benzol)Benzoic AcidBoric Acid
CBACC
CBACC
AAAAA
Phosphoric Acid (Air Free)Phosphoric Acid VaporsPotassiumChloridePotassium HydroxidePropane
CCBBA
CCBBA
ABAAA
ButaneCalciumChloride(Alkaline)CarbonDioxide,DryCarbonDioxide,WetCarbonDisulfide
ABACA
ABACA
ABAAA
Silver NitrateSodium AcetateSodiumCarbonateSodiumChlorideSodiumChromate
CAACA
CAACA
AAABA
CarbonTetrachlorideCarbonicAcidChlorineGas,DryChlorineGas,WetChlorine,Liquid
BCACC
BCACC
BBBCC
Sodium HydroxideStearic AcidSulfurSulfur Dioxide, DrySulfur Trioxide, Dry
AAAAA
ACAAA
AAAAA
ChromicAcidCitricAcidCokeOvenGasCopperSulfateEther
CI.L.ACB
CCACB
BBABA
Sulfuric Acid (Aerated)Sulfuric Acid (Air Free)Sulfurous AcidTrichloroethyleneWater, Boiler Feed
CCCBB
CCCBC
CCBAA
EthylChlorideEthyleneEthyleneGlycolFormaldehydeFormic Acid
CAAB
I.L.
CAABC
AAAAB
Water, DistilledWater, SeaZincChlorideZinc Sulfate- - - -
ABCC
- - - -
ABCC
- - - -
ABCA
- - - -Freon, WetFreon, DryGasoline,RefinedGlucoseHydrochloric Acid (Aerated)
BBAAC
BBAAC
AAAAC
- - - -- - - -- - - -- - - -- - - -
- - - -- - - -- - - -- - - -- - - -
- - - -- - - -- - - -- - - -- - - -
- - - -- - - -- - - -- - - -- - - -
FluId InFORMATIOn
Fluid PTFE nitrile (nBR)
Fluorocarbon (FKM) Fluid PTFE nitrile
(nBR)Fluorocarbon
(FKM)
Acetic Acid (30%)AcetoneAlcohol,EthylAlcohol, MethylAmmonia, AnhydrousAmmonia, Gas (Hot)BenzeneBrine(CalciumChloride)Butadiene GasButane, GasButane, LiquidCarbonTetrachlorideChlorine,DryChlorine,WetCokeOvenGasEthylAcetateEthyleneGlycolFreon 11Freon 12
AAAAAAAAAAAAAAAAABB
BCAACCCACA+ACCCBCAAA
BCBCCCABBAAAAA
A+CA
A+B
Freon 22Freon 114GasolineHydrogen GasHydrogenSulfide(Dry)HydrogenSulfide(Wet)Jet Fuel (JP-4)Natural GasNatural Gas + H2S (Sour Gas)Nitric Acid (10%)Nitric Acid (50 to 100%)Nitrogen Oil (Fuel)PropaneSea WaterSulfur DioxideSulfuric Acid (to 50%)Sulfuric Acid (50 to 100%)Water (Ambient)Waterat200°F/93°C
ABAAAAAAAABAAAAAAAAA
CA
A+ACCA
A+BCCA
A+AACCCAB
CBAACCAACAAAAAAAAAAB
1. MarkownedbyInternationalNickelCo.2. MarkownedbySteliteDiv.,CabotCorp. A+ - Best possible selection. A - Recommended.
B - Minor to moderate effect. Proceed with caution.C-Unsatisfactory. I.L. - Information lacking.
Bulletin 74.1:Y693
7
Table 4. Flow Rate Conversion (Gas flow required to replace or displace Blanketing Gas with Pump-Out or Pump-In of Liquid)
MulTIPlY MAXIMuM PuMP RATE In: BY TO OBTAIn:
U.S.GPMU.S.GPH
Barrels/hourBarrels/day
8.0210.13375.615
0.2340
SCFHairrequiredSCFHairrequiredSCFHairrequiredSCFHairrequired
Table 5. Gas Flow Required for Thermal Heating (Outbreathing) or Cooling (Inbreathing) per API 2000 (Interpolate for Intermediate sizes)
VESSEl CAPACITY AIR FlOW RATE REQuIREdBarrels gal. SCFH nm3/h
6010050010002000
25004200
21,00042,00084,000
60100500
10002000
1.62.7
13.426.853.6
300040005000
10,00015,000
126,000168,000210,000420,000630,000
300040005000
10,00015,000
80.4107134268402
20,00025,00030,00035,00040,000
840,0001,050,0001,260,0001,470,0001,680,000
20,00024,00028,00031,00034,000
536643750831911
45,00050,00060,00070,00080,000
1,890,0002,100,0002,520,0002,940,0003,360,000
37,00040,00044,00048,00052,000
9921072117912861394
90,000100,000120,000140,000160,000
3,780,0004,200,0005,040,0005,880,0006,720,000
56,00060,00068,00075,00082,000
15011608182220102198
180,000 7,560,000 90,000 2412
Ordering InformationWhenordering,specify:
Application1. Type of gas being used for blanketing (nitrogen,
fuelgas,etc.);listanyfactorssuchasimpuritiesin the gas that may affect compatibility of the gas with the regulator trim parts.
2. Specificgravityofthegas
3. Temperature of the gas
4. Rangeofflowinginletpressurestoregulator
5. Regulator pressure setting
6. Flow rates a) Minimumcontrolledflow b) Normalflow c) Maximumflow
7. Line size and end connection size of adjacent piping
RegulatorRefertotheSpecificationstableonpage2.Carefullyreviewthedescriptionofeachspecificationandspecifythe desired selection wherever there is a choice to be made.AlwaysspecifythetypenumberasidentifiedintheAvailableConfigurationsspecification.
Bulletin 74.1:Y693
8
Table 6. Typical Type Y693 Blanketing Regulator Capacities in SCFH / Nm3/h of 0.97 Specific Gravity Nitrogen
-continued-
SPRInG RAnGE,PART nuMBER
And COlOR
COnTROl PRESSuRE SETTInG InlET PRESSuRE
CAPACITIES In SCFH / nm3/h OF 0.97 SPECIFIC GRAVITY nITROGEn FOR 1-1/2 And 2 In. / dn 40 And 50 BOdIES WITH
A 1/2 In. / 13 mm ORIFICEdeviation from Setpoint
±0.5 In. w.c. / ±1 mbar
-0.5 to 1 In. w.c. / -1 to 2 mbar
-0.5 to 2 In. w.c. / -1 to 5 mbar
In. w.c. mbar psig bar SCFH nm3/h SCFH nm3/h SCFH nm3/h
0.5 to 2 in. w.c. /1 to 5 mbar
1D892527022
Brown
0.5(1) 1(1)
251020406080100125150
0.140.340.691.42.84.15.56.98.6
10.3
7501570250050008800
12,1007100710071007100
20.142.167.0134236324190190190190
7501570250050008800
12,10015,40015,20014,20012,200
20.142.167.0134236324413407381327
7501570250050008800
12,10015,40018,60022,70026,700
20.142.167.0134236324413498608716
deviation from Setpoint±0.5 In. w.c. /
±1 mbar±1 In. w.c. /
±2 mbar-1 to 2 In. w.c. /
-2 to 5 mbarSCFH nm3/h SCFH nm3/h SCFH nm3/h
0.5 to 2 in. w.c. /1 to 5 mbar
1D892527022
Brown
1 2
251020406080100125150
0.140.340.691.42.84.15.56.98.6
10.3
7501570250050008800
12,1007100710071007100
20.142.167.0134236324190190190190
12702280340052008800
12,10015,40015,20014,20012,200
34.061.191.1139236324413407381327
12702280340052008800
12,10015,40018,60022,70026,700
34.061.191.1139236324413498608716
2 to 5 in. w.c. /5 to 12 mbar
1D892627022
Red
3 7
251020406080100125150
0.140.340.691.42.84.15.56.98.6
10.3
7501570250050008800
12,10011,20011,20011,20011,200
20.142.167.0134236324300300300300
12702280340052008800
12,10015,40014,20014,20014,200
34.061.191.1139236324413381381381
12702280340052008800
12,10015,40018,60022,70026,700
34.061.191.1139236324413498608716
5 to 8 in. w.c. /12 to 20 mbar1D892727012
Black
7 17
251020406080100125150
0.140.340.691.42.84.15.56.98.6
10.3
7101370211030505580
10,20014,20018,60011,20011,200
19.036.756.581.7150273381498300300
10702030313042608020
11,50015,40018,60022,70026,700
28.754.483.9114215308413498608716
10702030313042608020
11,50015,40018,60022,70026,700
28.754.483.9114215308413498608716
1. For set pressures less than 1 in. w.c. / 2 mbar use only Nitrile (NBR) elastomers.
Bulletin 74.1:Y693
9
Table 6. Typical Type Y693 Blanketing Regulator Capacities in SCFH / Nm3/h of 0.97 Specific Gravity Nitrogen (continued)
-continued-
SPRInG RAnGE,PART nuMBER
And COlOR
COnTROl PRESSuRE SETTInG InlET PRESSuRE
CAPACITIES In SCFH / nm3/h OF 0.97 SPECIFIC GRAVITY nITROGEn FOR 1-1/2 And 2 In. / dn 40 And 50 BOdIES WITH
A 1/2 In. / 13 mm ORIFICE
deviation from Setpoint
±1 In. w.c. / ±2 mbar
±2 In. w.c. / ±5 mbar
In. w.c. mbar psig bar SCFH nm3/h SCFH nm3/h
8 to 18 in. w.c. /20 to 45 mbar1D893227032
Gray
11 27
251020406080100125150
0.140.340.691.42.84.15.56.98.6
10.3
66012702130305071109540
13,20018,60022,70026,700
17.734.057.181.7191256354498608716
10201830284040607610
12,10015,40018,60022,70026,700
27.349.076.1109204324413498608716
deviation from Setpoint
±1 In. w.c. / ±2 mbar
±2 In. w.c. / ±5 mbar
SCFH nm3/h SCFH nm3/h
18 to 32 in. w.c. /45 to 80 mbar1D893327032
Dark green
20 50
251020406080100125150
0.140.340.691.42.84.15.56.98.6
10.3
590810
110015202740406066009140
22,70026,700
15.821.729.540.773.4109177245608716
7101420183030506090
10,20015,40018,60022,70026,700
19.038.149.081.7163273413498608716
deviation from Setpoint
±0.1 In. w.c. / ±0.007 mbar
±0.2 In. w.c. / ±0.014 mbar
SCFH nm3/h SCFH nm3/h
1 to 2 psig /69 to 138 mbar1H975827032
Dark blue
1 psig 69
251020406080100
0.140.340.691.42.84.15.56.9
250110017802640447065009140
10,400
6.7029.547.770.8120174245279
8601830294048708120
11,10015,40018,600
23.049.078.8131218297413498
deviation from Setpoint
±0.3 In. w.c. / ±0.021 mbar
±0.6 In. w.c. / ±0.041 mbar
SCFH nm3/h SCFH nm3/h
1.5 to 3.3 psig /103 to 228 mbar1H975827032
Orange
3 psig 0.21 bar
51020406080100
0.340.691.42.84.15.56.9
12202540386071009340
13,20015,800
32.768.1103190250354423
1730340052008880
12,10015,40018,600
46.491.1139238324413498
Bulletin 74.1:Y693
10
SPRInG RAnGE,PART nuMBER
And COlOR
COnTROl PRESSuRE SETTInG InlET PRESSuRE
CAPACITIES In SCFH / nm3/h OF 0.97 SPECIFIC GRAVITY nITROGEn FOR 1-1/2 And 2 In. / dn 40 And 50 BOdIES WITH
A 1/2 In. / 13 mm ORIFICE
deviation from Setpoint
±0.5 In. w.c. / ±1 mbar
±1 In. w.c. / ±2 mbar
psig bar psig bar SCFH nm3/h SCFH nm3/h
2 to 5 psig /138 mbar to 0.3 bar
1P615427142
Yellow
3 0.21
71020406080100
0.480.691.42.84.15.56.9
14002330406069009740
12,80015,200
37.562.4109185261343407
2200305052008880
12,10015,40018,600
59.081.7139238324413498
deviation from Setpoint
±0.6 In. w.c. / ±1 mbar
±1 In. w.c. / ±2 mbar
SCFH nm3/h SCFH nm3/h
2 to 5.5 psig /138 mbar to 0.4 bar
0Y066427022
Green Stripe
5 0.35
7 1020406080100
0.480.691.42.84.15.56.9
1200142024404260589075109140
32.238.165.4114158201245
16002230376062908730
11,40014,200
42.959.8101169234306381
deviation from Setpoint
±0.6 In. w.c. / ±1 mbar
±2 In. w.c. / ±5 mbar
SCFH nm3/h SCFH nm3/h
4 to 10 psig /276 mbar to 0.7 bar
1H8024000A2
Silver
10 0.69
1520 406080100
1.01.42.84.15.56.9
160020303650508065007920
42.954.497.8136174212
2600350066809300
11,90014,900
69.793.8179249319399
Table 6. Typical Type Y693 Blanketing Regulator Capacities in SCFH / Nm3/h of 0.97 Specific Gravity Nitrogen (continued)
Bulletin 74.1:Y693
11
In. /mm
14B0813-A
AluMInuM lOWER CASInG VERSIOn WITH A STEEl BOdY
14B0812-A
STEEl OR STAInlESS STEEl lOWER CASInG VERSIOn
3/4 nPTVEnTCOnnECTIOn
1/2 nPTdOWnSTREAMCOnTROlCOnnECTIOn
14.00 /356
11.88 /302
5.88 /149
2.94 /75
10.38 /264
17.44 /443
7.06 /1791-1/2 And 2 nPT
Figure 4. Type Y693 Dimensions
3/4 nPTVEnTCOnnECTIOn
3/4 nPTdOWnSTREAMCOnTROlCOnnECTIOn
12.25 / 311
6.12 /155
3.19 /81
2.19 /56
1-1/2 And 2 nPT
17.69 /449
14.00 /356
10.62 /270
Bulletin 74.1:Y693
©Emerson Process Management Regulator Technologies, Inc., 1994, 2014; All Rights Reserved
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC, a business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Process Management Regulator Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Process Management Regulator Technologies, Inc. product remains solely with the purchaser.
Industrial Regulators
Emerson Process Management Regulator Technologies, Inc.
USA - HeadquartersMcKinney, Texas 75070 USATel: +1 800 558 5853Outside U.S. +1 972 548 3574
Asia-PacificShanghai 201206, ChinaTel: +86 21 2892 9000
EuropeBologna 40013, ItalyTel: +39 051 419 0611
Middle East and AfricaDubai, United Arab EmiratesTel: +971 4811 8100
Natural Gas Technologies
Emerson Process ManagementRegulator Technologies, Inc.
USA - HeadquartersMcKinney, Texas 75070 USATel: +1 800 558 5853Outside U.S. +1 972 548 3574
Asia-PacificSingapore 128461, SingaporeTel: +65 6770 8337
EuropeBologna 40013, ItalyTel: +39 051 419 0611Chartres 28008, FranceTel: +33 2 37 33 47 00
Middle East and AfricaDubai, United Arab EmiratesTel: +971 4811 8100
TESCOM
Emerson Process ManagementTescom Corporation
USA - HeadquartersElk River, Minnesota 55330-2445, USATels: +1 763 241 3238 +1 800 447 1250
EuropeSelmsdorf 23923, GermanyTel: +49 38823 31 287
Asia-PacificShanghai 201206, ChinaTel: +86 21 2892 9499
For further information visit www.fisherregulators.com
Figure 4. Type Y693 Dimensions (continued)
B243814B0814-A
AluMInuM lOWER CASInG VERSIOn WITH A CAST IROn BOdY
1-1/2 And 2 nPT
3.19 /81
6.12 /155
12.25 /311
2.06 /52
10.62 /270
17.69 /449
3/4 nPTVEnTCOnnECTIOn
3/4 nPTdOWnSTREAMCOnTROlCOnnECTIOn
In. /mm
Recommended