7/27/2019 Apfc Analog Thesis
1/40
ABSTRACT
This project discusses the design, implementation and analysis of a single phase
(240V, 50Hz) capacitor bank controller unit. Power factor control using capacitor
banks reduces reactive power consumption which will lead to minimization of losses
and at the same time increases the electrical systems efficiency. Power saving issues
and reactive power management has brought to the creation of single phase capacitor
banks for domestic applications. The development of this project is to enhance and
upgrade the operation of single phase capacitor banks by developing a micro-
processor based control system. The control unit will be able to control capacitor
bank operating steps based on the varying load current. Current transformer is used to
measure the load current for sampling purposes. Fluorescent lamp will be use as
loads in this single phase capacitor bank developments. That fluorescent lamp shall
be divided into different load value to enable capacitor bank model is controlled
systematically.
1 | P a g e
7/27/2019 Apfc Analog Thesis
2/40
Unit -01
INTRODUCTION
&
PROBLEM IDENTIFICATION
2 | P a g e
7/27/2019 Apfc Analog Thesis
3/40
1.1 INTRODUCTION
Electrical energy efficiency is of prime importance to industrial and commercial
companies operating in today's competitive markets. Optimum use of plant and
equipment is one of the main concerns that industry tries to balance with energy
efficiency, for both economical and environmental reasons. As society becomes
increasingly conscious of its impact on the environment, reduced energy consumption
becomes more desirable, which, is an achievable goal for everyone. Through the use
of measures such as power factor control, electricity consumption is optimized, which
ultimately leads to reduced energy consumption and reduced CO2 greenhouse gas
emissions.
Within a cost conscious market, payback considerations are also important. This
report identifies the most appropriate application for power factor control based on
energy consumption, tariff metering, cost payback and emission reduction. Power
factor control is an appropriate means by which to improve the power quality of an
installation. Its application is dependent though on the size of the installation and the
extent that power factor control needs to be applied. The opportunity however exists
to make a significant environmental contribution whilst simultaneously providing
economic benefit.
3 | P a g e
7/27/2019 Apfc Analog Thesis
4/40
Currently, the effective of the capacitor bank as power factor control device was
produced a capacitor bank to domestic use. Also known as energy stability, it will
correct power factor base capacitor concept as compensator reactive current in the
single phase electric circuit. However, this device is less efficiency because the static
operation and did not control load change. The project titled Automatic Power
Factor Control was developed to enable operation single phase capacitor bank to
control follow load change. The operation of present single phase capacitor bank was
not able to operate base of current change according the increase or reduction load.
Because the present system could not detect load rating that changed, the operation
inefficient and power factor control not be optimum. This project is using fluorescent
magnetic ballast as the load.
1.2 Problem Identification
This project developed to improve the weakness of static capacitor bank. Static
capacitor bank is a traditional method was used to improve the power factor by using
capacitor banks. In the configuration of static capacitor bank, the value of capacitor
was fixed and cannot to control. The weakness of the static capacitor bank, which the
operations:
i. Capacitive compensation does not change according to increase or reduction in
loads.
ii. Could not detect load rating that change inefficiency
iii. Operation and power factor control not optimized.
4 | P a g e
7/27/2019 Apfc Analog Thesis
5/40
CUR RENT WAVEFOR MS WITH AND WITH OUT P FC:
Input Voltage
0
DC Bus Output Voltage
Without
PFC
0
Input Curren
5 | P a g e
With
PFC
7/27/2019 Apfc Analog Thesis
6/40
1.3 Target and Objectives of the Project
There are four objectives of this project, which is stated in the following
texts:
i. To learn the way of power factor control in power systems.
ii. To learn and identify methods to control capacitor banks.
iii. Identify one method of power factor control with the low cost and
practical.
iv. To provide an automatically controlled PFC unit that will bring the
power factor to as near to unity as practical (typically 0.9) and have
sufficient capacity for future PFC requirements or expansion.
7/27/2019 Apfc Analog Thesis
7/40
Unit-02
LITERATURE REVIEW
7/27/2019 Apfc Analog Thesis
8/40
POWER FACTOR:
Power factor is the ration between the KW and the KVA drawn by an
electrical load where the KW is the actual load power and the KVA is the
apparent load power. It is a measure of how effectively the current is being
converted into useful work output and more particularly is a good indicator
of the effect of the load current on the efficiency of the supply system.
APPARENT POWER REACTIVE POWER
ACTIVE POWER
Fig 2.1
All current will cause losses in the supply and distribution system. A load
with a power factor of 1.0 result in the most efficient loading of the supply
and a load with a power factor of 0.5 will result in much higher losses in the
supply system.
A poor power factor can be the result of either a significant phase difference
between the voltage and current at the load terminals, or it can be due to a
high harmonic content or distorted/discontinuous current waveform. Poor
7/27/2019 Apfc Analog Thesis
9/40
load current phase angle is generally the result of an inductive load such as
an induction motor, power transformer, lighting ballasts, welder or induction
furnace. A distorted current waveform can be the result of a rectifier,
variable speed drive, switched mode power supply, discharge lighting or
other electronic load.
A poor power factor due to an inductive load can be improved by the
addition of power factor correction, but, a poor power factor due to a
distorted current waveform requires a change in equipment design or
expensive harmonic filters to gain an appreciable improvement. Many
inverters are quoted as having a power factor of better than 0.95 when in
reality, the true power factor is between 0.5 and 0.75. The figure of 0.95 is
based on the Cosine of the angle between the voltage and current but does
not take into account that the current waveform is discontinuous and
therefore contributes to increased losses on the supply.
POWER FACTOR CORRECTION:
Capacitive Power Factor correction is applied to circuits which include
induction motors as a means of reducing the inductive component of the
current and thereby reduce the losses in the supply. There should be no
effect on the operation of the motor itself.
7/27/2019 Apfc Analog Thesis
10/40
An induction motor draws current from the supply that is made up of
resistive components and inductive components.
The resistive components are:
(i)Load current (ii) Loss current
The inductive components are:
(i)Leakage reactance (ii) Magnetizing current
Fig 2.2
The current due to the leakage reactance is dependent on the total current
drawn by the motor, but the magnetizing current is independent of the load
on the motor. The magnetizing current will typically be between20% and
60% of the rated full load current of the motor. The magnetizing current is
the current that establishes the flux in the iron and is very necessary if the
motor is going to operate. The magnetizing current
7/27/2019 Apfc Analog Thesis
11/40
does not actually contribute to the actual work output of the motor. It is the
catalyst that allows the motor to work properly. The magnetizing current and
the leakage reactance can be considered passenger components of current
that will not affect the power drawn by the motor, but will contribute to the
power dissipated in the supply and distribution system.
Taking an example, a motor with a current draw of 100 Amps and a power
factor of 0.75 the resistive component of the current is 75 Amps and this is
what the KWh meter measures. The higher current will result in an increase
in the distribution losses of (100 x 100) / (75 x 75) = 1.777 or a 78%
increase in the supply losses.
In the interest of reducing the losses in the distribution system, power factor
correction is added to neutralize a portion of the magnetizing current of the
motor. Typically, the corrected power factor will be 0.92 - 0.95 some power
retailers offer incentives for operating with a power factor of better than 0.9,
while others penalize consumers with a poor power factor. There are many
ways that this is metered, but the net result is that in order to reduce wasted
energy in the distribution system, the consumer will be encouraged to apply
power factor correction.
7/27/2019 Apfc Analog Thesis
12/40
Fig 2.3
Power factor correction is achieved by the addition of capacitors in parallel
with the connected motor circuits and can be applied at the starter, or applied
at the switchboard or distribution panel. The resulting capacitive current is
leading current and is used to cancel the lagging inductive current flowing
from the supply.
Capacitors connected at each starter and controlled by each starter are
known as "Static Power Factor Correction".
7/27/2019 Apfc Analog Thesis
13/40
STATIC CORRECTION:
As a large proportion of the inductive or lagging current on the supply is due
to the magnetizing current of induction motors, it is easy to correct each
individual motor by connecting the correction capacitors to the motor
starters. With static correction, it is important that the capacitive current is
less than the inductive magnetizing current of the induction motor. In many
installations employing static power factor correction, the correction
capacitors are connected directly in parallel with the motor windings. When
the motor is Off Line, the capacitors are also Off Line. When the motor is
connected to the supply, the capacitors are also connected providing
correction at all times that the motor is connected to the supply. This
removes the requirement for any expensive power factor monitoring and
control equipment. In this situation, the capacitors remain connected to the
motor terminals as the motor slows down. An induction motor, while
connected to the supply, is driven by a rotating magnetic field in the stator
which induces current into the rotor. When the motor is disconnected from
the supply, there is for a period of time, a magnetic field associated with the
rotor. As the motor decelerates, it generates voltage out its terminals at a
frequency which is related to its speed. The capacitors connected across the
motor terminals, form a resonant circuit with the motor inductance. If the
7/27/2019 Apfc Analog Thesis
14/40
motor is critically corrected, (corrected to a power factor of 1.0) the
inductive reactance equals the capacitive reactance at the line frequency and
therefore the resonant frequency is equal to the line frequency. If the motor
is over corrected, the resonant frequency will be below the line frequency. If
the frequency of the voltage generated by the decelerating motor passes
through the resonant frequency of the corrected motor, there will be high
currents and voltages around the motor/capacitor circuit. This can result in
severe damage to the capacitors and motor. It is imperative that motors are
never over corrected or critically corrected when static correction is
employed.
Static power factor correction should provide capacitive current equal to
80% of the magnetizing current, which is essentially the open shaft current
of the motor.
The magnetizing current for induction motors can vary considerably.
Typically, magnetizing currents for large two pole machines can be as low
as 20% of the rated current of the motor while smaller low speed motors can
have a magnetizing current as high as 60% of the rated full load current of
the motor. It is not practical to use a "Standard table" for the correction of
induction motors giving optimum correction on all motors. Tables result in
under correction on most motors but can result in over correction in some
cases. Where the open shaft current cannot be measured, and the
7/27/2019 Apfc Analog Thesis
15/40
magnetizing current is not quoted, an approximate level for the maximum
correction that can be applied can be calculated from the half load
characteristics of the motor.
Fig 2.4
It is dangerous to base correction on the full load characteristics of the motor
as in some cases, motors can exhibit a high leakage reactance and correction
to 0.95 at full load will result in over correction under no load, or
disconnected conditions.
Static correction is commonly applied by using one contactor to control both
the motor and the capacitors. It is better practice to use two contactors, one
7/27/2019 Apfc Analog Thesis
16/40
for the motor and one for the capacitors. Where one contactor is employed, it
should be up sized for the capacitive load. The use of a second contactor
eliminates the problems of resonance between the motor and the capacitors.
SUPPLY HARMONICS
Harmonics on the supply cause a higher current to flow in the capacitors.
This is because the impedance of the capacitors goes down as the frequency
goes up. This increase in current flow through the capacitor will result in
additional heating of the capacitor and reduce its life.
The harmonics are caused by many non-linear loads; the most common in
the industrial market today, are the variable speed controllers and switch
mode power supplies. Harmonic voltages can be reduced by the use of a
harmonic compensator, which is essentially a large inverter that cancels out
the harmonics. This is an expensive option. Passive harmonic filters
comprising resistors, inductors and capacitors can also be used to reduce
harmonic voltages. This is also an expensive exercise. In order to reduce the
damage caused to the capacitors by the harmonic currents, it is becoming
common today to install detuning reactors in series with the power factor
correction capacitors. These reactors are designed to make the correction
circuit inductive to the higher frequency harmonics. Typically, a reactor
7/27/2019 Apfc Analog Thesis
17/40
would be designed to create a resonant circuit with the capacitors above the
third harmonic, but sometimes it is below.
Adding the inductance in series with the capacitors will reduce their
effective capacitance at the supply frequency. Reducing the resonant or
tuned frequency will reduce the effective capacitance further. The object is
to make the circuit look as inductive as possible at the 5th harmonic and
higher, but as capacitive as possible at the fundamental frequency. Detuning
reactors will also reduce the chance of the tuned circuit formed by the
capacitors and the inductive supply being resonant on a supply harmonic
frequency, thereby reducing damage due to supply resonance amplifying
harmonic voltages caused by non-linear loads.
SUPPLY RESONANCE:
Capacitive Power factor correction connected to a supply causes resonance
between the supply and the capacitors. If the fault current of the supply is
very high, the effect of the resonance will be minimal, however in a rural
7/27/2019 Apfc Analog Thesis
18/40
installation where the supply is very inductive and can be high impedance,
the resonance can be very severe resulting in major damage to plant and
equipment.
To minimize supply resonance problems, there are a few steps that can be
taken, but they do need to be taken by all on the particular supply.
1) Minimize the amount of power factor correction, particularly when the
load is light. The power factor correction minimizes losses in the supply.
When the supply is lightly loaded, this is not such a problem.
2) Minimize switching transients. Eliminate open transition switching -
usually associated with generator plants and alternative supply switching,
and with some electromechanical starters such as the star/delta starter.
3) Switch capacitors on to the supply in lots of small steps rather than a few
large steps.
4) Switch capacitors on o the supply after the load has been applied and
switch off the supply before or with the load removal.
Harmonic Power Factor correction is not applied to circuits that draw either
discontinuous or distorted current waveforms.
Most electronic equipment includes a means of creating a DC supply. This
involves rectifying the AC voltage, causing harmonic currents. In some
cases, these harmonic currents are insignificant relative to the total load
current drawn, but in many installations, a large proportion of the current
7/27/2019 Apfc Analog Thesis
19/40
drawn is rich in harmonics. If the total harmonic current is large enough,
there will be a resultant distortion of the supply waveform which can
interfere with the correct operation of other equipment. The addition of
harmonic currents results in increased losses in the supply.
Power factor correction for distorted supplies cannot be achieved by the
addition of capacitors. The harmonics can be reduced by designing the
equipment using active rectifiers, by the addition of passive filters (LCR) or
by the addition of electronic power factor correction inverters which restore
the waveform back to its undistorted state. This is a specialist area requiring
either major design changes, or specialized equipment to be used.
7/27/2019 Apfc Analog Thesis
20/40
UNIT-3
WORKING METHODOLOGY
3.1 BLOCK DIAGRAM
7/27/2019 Apfc Analog Thesis
21/40
FIG 3.1
3.2 CIRCUIT DIAGRAM
7/27/2019 Apfc Analog Thesis
22/40
FIG 3.2
7/27/2019 Apfc Analog Thesis
23/40
3.3 COMPONENT DESCRIPTION
CURRENT TRANSFORMERS
Principle of operation of CT:
A current transformer is defined as as an instrument transformer
in which the secondary current is substantially proportional to the
primary current (under normal conditions of operation) and differs
in phase from it by an angle which is approximately zero for an
appropriate direction of the connections.
Current transformers are usually either measuring or
protective types.
7/27/2019 Apfc Analog Thesis
24/40
FIG 3.3
7/27/2019 Apfc Analog Thesis
25/40
Related Terms:
1) Rated primary current:
The value of primary current which appears in the designation of the
transformer and on which the performance of the current transformer
is based.
2) Rated secondary current:
The value of secondary current which appears in the designation of
the transformer and on which the performance of the current
transformer is based.
Typical values of secondary current are 1 A or 5 A. In the case of
transformer differential protection, secondary currents of 1/ root 3 A
and 5/ root 3 A are also specified.
3) Rated output:
The value of the apparent power (in volt-amperes at a specified power
(factor) which the current transformer is intended to supply to the
secondary circuit at the rated secondary current and with rated burden
connected to it.
7/27/2019 Apfc Analog Thesis
26/40
12-0-12 Transformer
Transformers are composed of a laminated iron core with one or more
windings of wire. They are called transformers because they transform
voltage and current from one level to another. An alternating current
flowing through one coil of wire, the primary, induces a voltage in one or
more other coils of wire, the secondary coils. It is the changing voltage
of AC current that induces voltage in the other coils through the changing
magnetic field. DC voltage such as from a battery or DC power supply
will not work in a transformer. Only AC makes a transformer work. The
magnetic field flows through the iron core. The faster the voltage
changes, the higher the frequency.
The lower the frequency, the more iron is required in the core for the
efficient transfer of power. In the USA, the line frequency is 60 Hertz
with a nominal voltage of 110 volts. Other countries use 50 Hertz, 220
volts. Transformers made for 50 Hertz must be a little heavier than ones
made for 60 Hertz because they must have more iron in the core. Line
voltage can vary a little and usually runs between 110 volts and 120 volts
or between 220 and 240 volts depending on country or power
connections. A house in the USA has 220 volts coming in but is split to
two legs of 110V by grounding the centre tap.
7/27/2019 Apfc Analog Thesis
27/40
The ratio of input voltage to output voltage is equal to the ratio of turns
of wire around the core on the input side to the output side. A coil of
wire on the input side is called the primary and on the output side is
called the secondary. There can be multiple primary and secondary coils.
The current ratio is opposite the voltage ratio. When the output voltage is
lower than the input voltage, the output current will be higher than the
input current. If there is 10 times the number of turns of wire on the
primary than the secondary and you put 120 volts on the primary, you
will get 12 volts out on the secondary. If you pull 2 amps out from the
secondary, you will only be using 0.2 amps or 200 milliamps going into
the primary.
Transformers can be built so they have the same number of windings on
primary and secondary or different numbers of windings on each. If they
are the same, the input and output voltage are the same and the
transformer is just used for isolation so there is no direct electrical
connection (they are only linked through the common magnetic field). If
there are more windings on the primary side than the secondary side, then
it is a step down transformer. If there are more windings on the primary
side, then it is a step up transformer.
A transformer can actually be used in reverse and will work fine. For
example, if you have a step up transformer built for transforming 120
7/27/2019 Apfc Analog Thesis
28/40
volts to 240 volts, you can also use it for a step down transformer by
putting 240 volts into the secondary side and you will get 120 volts on
the primary side. Effectively, the secondary becomes the primary and
vice versa.
Transformer Power Ratings
Voltage is measured in volts, current is measured in amps, and the unit of
measure for power is watts. Watts is equal to the volts times the amps.
There is a little loss of power in a transformer due to the combination of
resistance and reactance. Reactance is similar to resistance except it is the
resistance to an AC current or more technically, the resistance to change
in a change in current due to the change in the field created. This heat is
what limits the amount of current or power a transformer can handle. The
higher the current, the more heat is produced. When the wires get too
hot, the insulation breaks down and shorts with adjacent wires which
cause more heat which eventually melts wires and ruins the transformer.
A basic transformer has no additional components and so nothing to
protect it from overloading. If you were to connect the two output wires
directly together, that will constitute a short circuit and cause far too
much current to flow in both the primary and secondary and you will
burn out the transformer. In the same way, if you use the transformer to
power a hot wire foam cutter and you are using a wire with too little
7/27/2019 Apfc Analog Thesis
29/40
resistance for your foam cutter, you will burn out your transformer if you
don't have it protected by a proper value fuse or breaker. It has to be
made sure that the wire resistance, in other words, the gage or diameter,
and the length is correct to limit the amount of current to under the rating
of the transformer.
The higher the current, the larger the wires need to be that carry that
current. When the wires are larger, there is less resistance and so less
heat. The power that is changed to heat and lost can be calculated as
P=I2R. That means that if you double the current, the power lost to heat
increases by four times. If the transformer is a step down transformer,
then there will be more current on the output and so the wire in the
secondary windings will be heavier than the primary. The reverse is true
for a step up transformer.
A transformer may be rated in Amps, Volt-Amps (VA), or Watts (W).
For small transformers, VA and Watts is the same thing for all practical
purposes. In large industrial transformers, power factors get involved
and the two can be different. If the transformer is rated in amps, it
usually says X amps at X volts and is rated on the output or secondary
side. A 120V transformer with 24V out rated at 2 amps means that you
can only safely pull 2 amps from the secondary side. You can find the
7/27/2019 Apfc Analog Thesis
30/40
power rating of the transformer by multiplying the rated amps times the
output voltage so 2 X 24 = 48 watts.
If the transformer is rated in VA or watts, you can calculate the
maximum allowable output current by dividing the VA or watts by the
output voltage. So if the transformer is rated at 48 VA with 24 volts
output, the allowable output current is 48 / 24 = 2 amps.
Transformer Configurations
A 120 volt transformer with two wires in and two wires out is very
simple. You hook up the two wires on the primary side, the 120V side,
to a wall outlet and your output voltage is on the two wires coming from
the secondary side.
When a transformer is shown in an electronic circuit, it is shown as a
diagram like shown here. The parallel lines represent the laminated iron
core, the curved lines represent the primary and secondary windings, the
circles represent the terminations whether terminals or short wires.
Centre Tap
A common configuration is a centre tap or CT. The secondary side has
three wires out. The middle wire on the output side is attached to the
7/27/2019 Apfc Analog Thesis
31/40
secondary coil, usually at the middle. If the winding ratio is 5 to 1, then
with 120V input, you get 24 volts output on the two outside wires but if
you connect an outside wire and the centre wire, you get 12 volts because
you are using only half the secondary winding making the connection a
10 to 1 ratio. If the transformer is rated at 2 amps, you still can only use
2 amps output whether you use 12 volts or 24 volts. Often the centre tap
is grounded so you then have two 12 volt sources that can be used to
make + and - 12V DC after running through a converter (rectifier and
filter).
Power Supply Diagram
ELECTRO MAGNETIC RELAY:
7/27/2019 Apfc Analog Thesis
32/40
These are varying much reliable devices and widely used on field. The
operating frequency of these devices are minimum 10-20ms.That is 50Hz
100Hz.The relay which is used here can care 25mA currents continuously.
The electromagnetic relay operates on the principle magnetism. When the
base voltage appears at the relay driver section, the driver transistor will be
driver transistor will be
7/27/2019 Apfc Analog Thesis
33/40
driven into saturation and allow to flow current in the coil of the relay,
Which in turn create a magnetic field and the magnetic force produced
due to that will act against the spring tension and close the contact coil.
Whenever the base voltage is withdrawn the transistor goes to cutoff .So
no current flow in the coil of the relay. Hence the magnetic field
disappears so the contact point breaks automatically due to spring
tension. Those contact points are isolated from the low voltage supply, so
a high voltage switching is possible by the help of electromagnetic relays.
The electromagnetic relays normally having 2 contact points. Named as
normally closes (NC) , normally open (NO). Normally closed points will
so a short CKT path when the relay is off. Normally open points will so a
short CKT path when the relay is energized.
7/27/2019 Apfc Analog Thesis
34/40
2.5UF 400V 450VAC CBB60A CAPACITOR:
2.5UF 400V 450VAC CBB60A Motor Run Capacitors takes heavy-edge
metalized Al/Zn PP film or web-like fuse film as dielectric. Its
components are sealed with flame-retardant epoxy resin. It has cylindrical
outline with high reliability and stability.CBB60 capacitor has features of
small size, light weight, small tangent in waste angle, and good self-
concrescence. Applicable to start and operation with 50/60Hz. A. C
single motor, specially suit for micro pump, baric pump, micro motor and
so on.
7/27/2019 Apfc Analog Thesis
35/40
Transistor SL100:
SL100 is a general purpose, medium power NPN transistor. It is mostly
used as switch in common emitter configuration. The transistor terminals
require a fixed DC voltage to operate in the desired region of its
characteristic curves. This is known as the biasing. For switching
applications, SL100 is biased in such a way that it remains fully on if
there is a signal at its base. In the absence of base signal, it gets turned off
completely.
The emitter leg of SL100 is indicated by a protruding edge in the
transistor case. The base is nearest to the emitter while collector lies at
other extreme of the casing.
Rated Capacitance Motor Run Capacitor
Tolerance 2.5uF
Rated Voltage 5%
Brand 400/450VAC
Housing Material Cinco or Custom-made
Housing Shape Plastic
Terminal Round
Dielectric Material 2+2 6.35mmx0.8 pins
Operating Temperature Metallised Polypropylene Film
Frequency 25/70/21
explosion-proof Class 50/60Hz
P0
7/27/2019 Apfc Analog Thesis
36/40
7/27/2019 Apfc Analog Thesis
37/40
UNIT-4
CONCLUSION
&
RESULT
CONCLUSION:
It can be concluded that power factor correction techniques can be
applied to the industries, power systems and also households to make
them stable and due to that the system becomes stable and efficiency of
the system as well as the apparatus increases. The use of microcontroller
7/27/2019 Apfc Analog Thesis
38/40
reduces the costs. Due to use of microcontroller multiple parameters can
be controlled and the use of extra hard wares such as timer, RAM, ROM
and input output ports reduces. Care should be taken for overcorrection
otherwise the voltage and current becomes more due to which the power
system or machine becomes unstable and the life of capacitor banks
reduces.
ADVANTAGES OF IMPROVED POWER FACTOR:
Reactive power decreases
Avoid poor voltage regulation
Overloading is avoided
Copper loss decreases
Transmission loss decreases
Improved voltage control
Efficiency of supply system and apparatus increases
ADVERSE EFFECT OF OVER CORRECTION:
Power system becomes unstable
Resonant frequency is below the line frequency
Current and voltage increases
7/27/2019 Apfc Analog Thesis
39/40
REFERENCES:
P. N. Enjeti and R martinez, A high performance si ngle phase
rectifier with input power factor correction ,IEEE Trans. Power
Electron..vol.11,No.2,Mar.2003.pp 311-317
J.G. Cho,J.W. Won,H.S. Lee , Reduced conduction lo ss zero-
7/27/2019 Apfc Analog Thesis
40/40
voltage-transition power factor correction converter with low cost,IEEE
Trans.Industrial Electron..vol. 45,no 3,Jun. 2000,pp395-400
The 8051 Microcontroller and Embedded Systems by
Muhammad Ali Mazidi and Janice Gillispie Mazidi
8052 simulator for windows version 3.604
25Jun1999,sim8052@vaultbbs.com
www.fsinc.com
www.keil.com
Eleectric power industry reconstructing in India,Present scenario
and future prospects,S.N. Singh ,senior member,IEEE and S.C.
Srivastava,Senior Member,IEEE
Power factror correction, Reference design from Freescale