PV COMBI‐CON
Statcon’s PV COMBI‐CON series offers wide range ofString Monitoring Boxes suitable for different kind ofPV modules with DC bus voltages ranging from 400V
b b d
PV COMBI‐CON is available indifferent models to cater todifferent plant designs.
to 1000V DC. As many as 16 strings can be combinedin this with monitoring of all the relevant parameters.
Data such as string currents, bus voltage,temperature, SPD status, shunt trip etc is available in
Maintaining IP‐65 protectionthese boxes are designed forIndian environment conditionsoperating up to 50 degrees temp.
p , , pStandard RS485 over MODBUS protocol. Featuressuch as digital/ analog inputs, diode/ fuse protection,high voltage protection are all included.
PV COMBI CON is compatible with any standard
These String Monitoring boxescan be customized as per theuser requirements both in termsof mechanical layout and
PV COMBI‐CON is compatible with any standardpower supply that the user can provide for poweringup the control circuit. Surge protection is providedboth for strings and power supply. Suitable isolator/MCCB is provided at the output to isolate the string
electrical design.
box.
HIGHLIGHTS
• Design flexibility as per user requirements• Communication using Standard MODBUS RTU
HIGHLIGHTS
• Monitoring of bus voltage and individual string currents• Digital/ analog inputs for environmental sensors• Remote trip provision for output isolator• Both gland and MC4 options available.• Operation up to 50 degrees of temperature
IDENTIFICATION ACRONYM
STG 16 11 N 00
IDENTIFICATION ACRONYM
STG 16_ 11 N 00
STRING MONITOR
MAX. NO. OF Indicates the number of string inputsSTRING
FUSE IN INPUT 00 = No fuse in positive or negative 10 = Fuse in positive only 01 = Fuse in negative only 11 = Fuse in both positive and negative
DIODE D = with diodeN = without diode
ENCLOSURE MODEL TYPE
00 = Single box01 = Combined Boxes10 = Combined Boxes with PCB type fuse11 = Single Box with PCB type fuse
BLOCK DIAGRAM OF PV COMBI-CON (STG16_11N)
S1(+)
S2(+)
S16(+)
+DC BREAKER
SURGE VOLTAGE
CURRENT SENSE
S16(+)
S1(-)
VOLTAGE PROTECTION
INPU
T ST
RIN
G
CO
NN
ECTO
RS
PV FIELD
S2(-)
S16(-)
-
IRRADIANCEAMBIENT
TEMPERATURE
-485
CONTROL UNITEXTERNAL SERVICES
GND
+485
REFERENCE TEMPERATURE
WIND CONFIGURABLE DIGITAL INPUT
CONFIGURABLE ANALOG INPUT
A/D
CONFIGURABLE DIGITAL OUTPUT
PARAMETERS STG16_11N00 STG16_11N01 STG16_11N10Input SideDC Input String Voltage Range 450 -1000V 450 -1000V 450 -1000VAbsolute Max. DC Input String Voltage 1100V 1100V 1100VMax. Isc Current for Each Channel 16.0A 16.0A 16.0AMax. No. of Input Strings 16 16 16Current Accuracy ±2% Upper range value ±2% Upper range value ±2% Upper range valueR P t ti Y Y YReverse Protection Yes Yes YesOutput SideMax. Output Current 160A 160A 160AHigh Voltage Protection Yes Yes YesGround Cable Connection M25 ( up to 25mm2) M25 (up to 25mm2) M25 (up to 25mm2)Output DC Switch Rating 160A/ 1000V 160A/ 1000V 160A/ 1000VCommunicationUser Interface Via RS485 (MODBUS RTU Protocol) Via RS485 (MODBUS RTU Protocol) Via RS485 (MODBUS RTU Protocol)Control Supply (230V,50Hz ±15%AC or 110V ±10%DC) (230V,50Hz ±15%AC or 110V ±10%DC) (230V,50Hz ±15%AC or 110V ±10%DC)Configurable Input / Output ChannelsDigital Input Provided (5 Nos.) Provided (5 Nos.) Provided (5 Nos.)Analog Input Provided (3 Nos.) Provided (3 Nos.) Provided (3 Nos.)DigitalOuput Provided (2 Nos.) Provided (2 Nos.) Provided (2 Nos.)Data MonitoringData MonitoringBus Voltage Yes Yes YesString Current Yes Yes YesAmbient Temperature Yes Yes YesOver Voltage Status Yes Yes YesProvision for environmental sensors Yes Yes YesShunt Trip Status Yes(Optional) Yes(Optional) Yes(Optional)O ti C ditiOperating ConditionsAmbient Temperature Range (-10°C to 50°C) (-10°C to 50°C) (-10°C to 50°C)Relative Humidity 95% at 40°C 95% at 40°C 95% at 40°CMax. Operating Altitude without Derating 1000m 1000m 1000mEnvironmental Protection Rating IP65 IP65 IP65Enclosure Poly carbonate Poly carbonate Poly carbonateGeneral Arrangement Drawing Figure:1 Figure:2 Figure:3g g g g gSafetySafety Standard EN50102 EN50102 EN50102
Note:- Technical details are subject to change.
BLOCK DIAGRAM OF PV COMBI-CON (STG16_10N)
S1(+)
S2(+)
S16(+)
+DC BREAKER
SURGE VOLTAGE
CURRENT SENSE
S16(+)
S1(-)
VOLTAGE PROTECTION
INPU
T ST
RIN
G
CO
NN
ECTO
RS
PV FIELD
S2(-)
S16(-)
-
IRRADIANCEAMBIENT
TEMPERATURE
-485
CONTROL UNITEXTERNAL SERVICES
GND
+485
REFERENCE TEMPERATURE
WIND CONFIGURABLE DIGITAL INPUT
CONFIGURABLE ANALOG INPUT
A/D
CONFIGURABLE DIGITAL OUTPUT
PARAMETERS STG16_10N00 STG16_10N01 STG16_10N10Input SideDC Input String Voltage Range 450 -1000V 450 -1000V 450 -1000VAbsolute Max. DC Input String Voltage 1100V 1100V 1100VMax. Isc Current for Each Channel 16.0A 16.0A 16.0AMax. No. of Input Strings 16 16 16Current Accuracy ±2% Upper range value ±2% Upper range value ±2% Upper range valueR P t ti Y Y YReverse Protection Yes Yes YesOutput SideMax. Output Current 160A 160A 160AHigh Voltage Protection Yes Yes YesGround Cable Connection M25 ( up to 25mm2) M25 (up to 25mm2) M25 (up to 25mm2)Output DC Switch Rating 160A/ 1000V 160A/ 1000V 160A/ 1000VCommunicationUser Interface Via RS485 (MODBUS RTU Protocol) Via RS485 (MODBUS RTU Protocol) Via RS485 (MODBUS RTU Protocol)Control Supply (230V,50Hz ±15%AC or 110V ±10%DC) (230V,50Hz ±15%AC or 110V ±10%DC) (230V,50Hz ±15%AC or 110V ±10%DC)Configurable Input / Output ChannelsDigital Input Provided (5 Nos.) Provided (5 Nos.) Provided (5 Nos.)Analog Input Provided (3 Nos.) Provided (3 Nos.) Provided (3 Nos.)DigitalOuput Provided (2 Nos.) Provided (2 Nos.) Provided (2 Nos.)Data MonitoringData MonitoringBus Voltage Yes Yes YesString Current Yes Yes YesAmbient Temperature Yes Yes YesOver Voltage Status Yes Yes YesProvision for environmental sensors Yes Yes YesShunt Trip Status Yes(Optional) Yes(Optional) Yes(Optional)O ti C ditiOperating ConditionsAmbient Temperature Range (-10°C to 50°C) (-10°C to 50°C) (-10°C to 50°C)Relative Humidity 95% at 40°C 95% at 40°C 95% at 40°CMax. Operating Altitude without Derating 1000m 1000m 1000mEnvironmental Protection Rating IP65 IP65 IP65Enclosure Poly carbonate Poly carbonate Poly carbonateGeneral Arrangement Drawing Figure:4 Figure:5 Figure:6g g g g gSafetySafety Standard EN50102 EN50102 EN50102
Note:- Technical details are subject to change.
BLOCK DIAGRAM OF PV COMBI-CON (STG16_11D)
S1(+)
S2(+)
S16(+)
+DC BREAKER
SURGE VOLTAGE
CURRENT SENSE
S16(+)
S1(-)
VOLTAGE PROTECTION
INPU
T ST
RIN
G
CO
NN
ECTO
RS
PV FIELD
S2(-)
S16(-)
-
IRRADIANCEAMBIENT
TEMPERATURE
-485
CONTROL UNITEXTERNAL SERVICES
GND
+485
REFERENCE TEMPERATURE
WIND CONFIGURABLE DIGITAL INPUT
CONFIGURABLE ANALOG INPUT
A/D
CONFIGURABLE DIGITAL OUTPUT
PARAMETERS STG16_11DInput SideDC Input String Voltage Range 450 -1000VAbsolute Max. DC Input String Voltage 1100VMax. Isc Current for Each Channel 16.0AMax. No. of Input Strings 16Current Accuracy ±2% Upper range valueReverse Protection YesOutput SideMax. Output Current 160AHigh Voltage Protection YesGround Cable Connection M25 ( up to 25mm2)Output DC Switch Rating 160A/ 1000VCommunicationUser Interface Via RS485 (MODBUS RTU Protocol)Control Supply (230V,50Hz ±15%AC or 110V ±10%DC)Configurable Input / Output ChannelsDigital Input Provided (5 Nos.)Analog Input Provided (3 Nos.)DigitalOuput Provided (2 Nos.)D t M it iData MonitoringBus Voltage YesString Current YesAmbient Temperature YesOver Voltage Status YesProvision for environmental sensors YesShunt Trip Status Yes(Optional)Operating ConditionsAmbient Temperature Range (-10°C to 50°C)Relative Humidity 95% at 40°CMax. Operating Altitude without Derating 1000mEnvironmental Protection Rating IP65Enclosure Poly carbonateGeneral Arrangement Drawing Figure:7General Arrangement Drawing Figure:7SafetySafety Standard EN50102
Note:- Technical details are subject to change.
G.A. Drawing: STG16_11N00
Figure:1
Dimension: 640×440×179 (all in mm)Color : RAL 7035Weight : < 25kgProtection : IP65
G.A. Drawing: STG16_11N01
Figure:2Dimension: 1320×320×179 (all in mm)Color : RAL 7035Weight : < 25kgProtection : IP65
G.A. Drawing: STG16_11N10
Figure:3Dimension: 1320×320×179 (all in mm)Color : RAL 7035Weight : < 25kgProtection : IP65
G.A. Drawing: STG16_10N00
Dimension: 640×440×254 (all in mm)Color : RAL 7035
Figure:4
Color : RAL 7035Weight : < 25kgProtection : IP65
G.A. Drawing: STG16_10N01
Figure:5Dimension: 1200×320×179 (all in mm)Color : RAL 7035 light greyWeight : < 25kgProtection : IP65
G.A. Drawing: STG16_10N10
Figure:6
Dimension: 1320×320×179 (all in mm)Color : RAL 7035Weight : < 25kgProtection : IP65
G.A. Drawing: STG16_11D
Figure:7Dimension: 1600×440×179 (all in mm)Color : RAL 7035Weight : < 25kgProtection : IP65
For any technical issue concerning our products e-mail us.design@stat-con.com
For Sales & Marketing contact :For Sales & Marketing contact :
STATCON POWER CONTROLS LTD.A‐34, SECTOR‐59, NOIDA,G. B. NAGAR ‐ 201301 (U.P.)TELE: 0120‐4640200‐210 (11 LINES), FAX: 0120‐ 4640240Email to: info@stat‐con.com, projects@stat‐con.com
MANUFACTURING PLANT:Khasra No. 509, Vilage‐Chhijarsi Kulich Nagar, Pargana‐Dasna, Tehsil‐Dhaulana, Distt‐Panchsheel Nagar, (U.P.) INDIAPhone: 0122‐3058132‐140
KOLKATA BRANCH:1/1 NABA GAURANGA BASAK ROAD,KOLKATA ‐700080.BEHIND MRINALINI CINEMA HALL
CHENNAI BRANCH:
BEHIND MRINALINI CINEMA HALL.TEL: 9874817776 / 9874817760 / 9874817768Landline ‐ 033‐25601079
web site : www.stat-con.com
CHENNAI BRANCH:112 – Vasudevan Nagar,Jayabalam Street, Jafferkhanpet,Chennai – 600 083,Ph: 044‐43542116Mob. 09791034104